pcvme0614 (vrv iii-s 50hz)_tcm185-140379
TRANSCRIPT
All rights reservedPrinted in Japan 08/06/003 Y.Kc
DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
Cautions on product corrosion
Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
Printed on 100% recycled paper with soy ink.Specifications, designs and other content appearing in this brochure are current as of August 2006 but subject to change without notice.
ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the
About ISO 14001
ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at
About ISO9001
JMI-0107 JQA-1452 EC99J2044 JQA-E-90108
HE AT P UM P
A s p e c i a l a i r c o n d i t i o n i n g s y s te m d e s i g n e df o r s m a l l o f f i c e s a n d s h o p s
Heat P ump Type 50 Hz
PCVME0614
For high outdoor temperature use
HE AT P UM PHeat P ump Type 50 Hz
PCVME0614
A s p e c i a l a i r c o n d i t i o n i n g s y s te m d e s i g n e df o r s m a l l o f f i c e s a n d s h o p s
For high outdoor temperature use
SSThe 5S +2E c onc epts of
E xtending the c ore “ 5S ” c onc ept—S pac e s aving, S uffic ient c apac ity, S lim des ign,
S ound- reduc ed operation and S ingle phas e power s upply—Daikin’ s VR V III- S
offers added value with the “ 2E ” c onc ept—E as y ins tallation and E as y
maintenanc e. With all thes e features and more, we proudly pres ent the ideal air
c onditioning s ys tem des igned for s mall- s ized buildings .
The ideal air conditioning system for
small offices and shops
S pac e s aving
S uffic ient c apac ity
S lim des ign
S ound-reduc ed operation
S ingle phas e power s upply
E as y ins tallation
E as y maintenanc e E2Econcept
5Sconcept
21
The VRV III-S is highly space saving, featuring slim and compact outdoor units. It is suitable for small offices and shops with the capacity of 6 HP.
Slim, compact and sufficient capacity
The compact, trunk-shaped outdoor unit can easily be installed on a balcony, realizing complete system installation within each floor. This enables more useful utilization of the space on the building rooftop.
Outdoor unit can be installed on a balcony
ContentContent
Introduction..............page 1
Main features...........page 3
Control systems.....page 9
Indoor units line up.....page 15
Specifications.................page 27
Indoor units . . . . . . . . . . . .page 27
Outdoor units . . . . . . . .page 34
Option list..........................page 35
Indoor units . . . . . . . . . . . . . .page 35
Outdoor units . . . . . . . . . . .page 37
C ontrol s ys tems . . . . . .page 37
A slim outdoor unit and a wide range of indoor unitsTo s uit the variety of rooms found in s mall
offic es and s hops , the VR V III- S s ys tem offers a
s lim outdoor unit and a wide range of indoor
units .
VR V III- S indoor and outdoor units are almos t
as eas y to ins tall as res idential air c onditioning
s ys tems , making them ideal for s mall offic es
MAIN FEATURERS
The trunk-shaped outdoor unit can be neatly installed outside the office.
A wide range of indoor units includes 82 models in 15 types. The indoor units can be selected to match every room and preference.
15 types 82 models
6 HP (15.5 kW)
Indoor units
Outdoor unit
RXYMQ6PV4A
43
Conversion rates
Btu/h = kW x 3412RT = kW x 0.284
Indoor unit lineup
Ceiling mounted cassette(Double flow)
Type Capacity
IndexHP
20 40 62.5 80 100 1255031.25250.8 HP 1.6 HP 2.5 HP 3.2 HP 4 HP 5 HP2 HP1.25 HP1 HP
Btu 7500 15400 24200 30700 38200 4780019100123009600
Ceiling mountedcassette (Multi flow)super cassette
FXCQ-M
FXFQ-M
Slim ceilingmounted duct
Ceiling mountedduct
Ceiling suspended
Wall mounted
Floor standing
Concealedfloor standing
Ceiling mountedcassette corner
FXDQ-NAVE(with drain-up pump)
FXDQ-NVET(without drain-up pump)
FXMQ-MA
FXHQ-MA
FXAQ-MA
FXLQ-MA
FXNQ-MA
FXKQ-MA
Ceiling mountedbuilt-in FXSQ-M
FXDQ-PVET(without drain-up pump)
FXDQ-PVE(with drain-up pump)
(700 mm width type)
(900/1,100 mm width type)
• R410A VRV system indoor units are not compatible with the R22 VRV system.Notes:
New
New
New
New
New
New
NewCeiling suspendedcassette
Type
—
1.6 HP0.8 HP 1.25 HP1 HP
— — — —
HP
Connection Unit20 4031.2525
BEVQ125MAVE
5 HP
BEVQ100MAVEBEVQ71MAVE
2 HP 4 HP3 HP
— FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1
50 12510071Index
1.3 ton0.6 ton 1.0 ton0.8 tonRTCapacity7500 15400123009600
4.0 ton1.6 ton 3.2 ton2.3 ton19100 478003820027300Btu
• Indoor units in the 63 class are not available for the above model.• BEV units are necessary for Connection unit series indoor units. Refer to the Connection unit series catalog for details.
Notes:
600X600 multi flow ceiling mounted cassette
FXZQ-M
RT 0.6 ton 1.3 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton1.6 ton1.0 ton0.8 ton
New
New
Energy efficiency and quiet operationOutdoor units have been newly des igned us ing the new c ompres s or
to realize energy s aving performanc e and quiet operation.
MAIN FEATURERS
Higher COP during both coolingand heating operations
Quiet operation provides luxurious comfortQuietness is yet another important feature of Daikin’s VRV III-S system. To reduce noise and realize comfortable operation, latest technologies and features are applied to the outdoor units.
One of the top features of the VRV III-S is its energy efficiency. It achieves high COP during cooling and heating operations by employing the new compressor.
These two new features work to significantly reduce noise. Guides are added to the bell mouth intake to reduce turbulence in the airflow generated by fan suction. The new Aero Spiral Fan features fan blades with the bent blade edges, further reducing turbulence.
Smooth Air Inlet Bell Mouth and Aero Spiral Fan
A larger sub-cooled area reduces refrigerant flow sound by making it easer to form a liquid seal in front of the electrical valve.
SC heat exchanger
Super Aero Grille Refined ventilation mechanism enables further reduction in required fan power.
Escaping eddies are sucked in by the bent blade edges, reducing overall turbulence.
Conventional Newly developed
A collection of cutting-edge technologies realizes efficient and quiet operation.
Improving the high efficiency compressor to achieve a higher COP
2
5
1
Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory.
Above values are based on the following nominal conditions:Note: • 2 build-in units are connected (4 HP: FXFQ50M x 2; 5 HP:
FXFQ63M x 2; and 6 HP: FXFQ63M + FXFQ80M.)• Indoor temp. of 27°C DB/19°C WB, and outdoor temp. of 35°C DB.
DC fan motorEfficiency improved in all areas compared to conventional AC motors, especially at low speeds.
4
Sine wave DC inverter >> Smooth sine wave DC inverter Use of an optimized sine wave smoothes motor rotation, further improving operating efficiency.
Use of neodymium magnets in the motor enables efficient generation of high torque, reducing the size of the compressor.
>> Powerful magnets
Changes to the shape of the spiral and volume ratio result in optimal refrigerant layout.
>> Optimal refrigerant configurationThe strength of the casing has been increased by boosting the internal dome pressure.
>> Stronger materials
Overheating losses are reduced by pressurizing the area around the motor, boosting energy saving performance in conjunction with other features.
Reluctance DC Scroll Compressor
Neodymium magnets are much more powerful than the commonly used ferrite magnets.Ferrite magnet
Neodymium magnet
3DC motor efficiency
(comparison with a conventional AC motor)
200 300 400 500 600 700 800 900 10000
20
40
80
60
100
Effic
ienc
y (%
)
Motor speed (rpm)
AC motorAC motorAC motorApprox.40%
increase
Approx.20%
increase
DC motorDC motorDC motorDC fan motor structure
Neo aero spiral fan blade tips
Lower operation sound is achieved!
RXYMQ6PV4A
ReluctanceDC motorBy introducing high pressure oil, the
reactive force from the fixed scroll is added to the internal force, thereby reducing thrust losses. This results in improved efficiency and suppressed sound levels.
High thrust mechanism
3
4 1
5
2
Cooling
Heating
Heating
Cooling 5 3
5 5
3 . 0 3
3 . 6 2
6 HP
6 HP
6 HP
6 HP
65
Nighttime quiet operation function
Set on the outdoor PCB. Time of maximum temperature is memorized. The low operating mode will become active 8 hours*2 after the peak temperature in the daytime, and operation will return to normal 10 hours*3 after that. The operation sound level for the night mode can be selected from 47 dB (Step 1), 44 dB (Step 2) and 41 dB (Step 3).
Automatic modeMode 1.
Automatic modeMode 1.
Starting time and ending time can be input. (External control adaptor for outdoor unit, DTA104A61 or DTA104A62, and a subsequently obtained timer are necessary.)
Manual modeMode 2.
Combination of mode 1 and 2 can be used depending on your needs.
Combined modeMode 3.
*1. Determine which mode to select depending on the climatic characteristics of each country.
*2. Initial setting. Can be selected from 6, 8 and 10 hours.*3. Initial setting. Can be selected from 8, 9 and 10 hours.
Note: • This function is available in setting at site.• The relationship of outdoor temperature (load) and time shown in the graph is just an example.
Peak in the outdoor temperature
Cap
acity
%
8 hrs 10 hrs
Ope
ratio
n so
und
dB
47
8:00 12:00 16:00 20:00 0:00 4:00 8:00
50
100
500
Load
%
Night mode endsNight mode starts Night mode endsNight mode starts
Night Mode
44
41
(Initial setting)(Initial setting)
Step 1 max. - 3dB( 4 HP/11.2 kW)
Step 2 max. - 6dB( 4 HP/11.2 kW)
Step 3 max. - 9dB( 4 HP/11.2 kW)
Step 1: 47 dB
Step 2: 44 dB
Step 3: 41 dB
Operation sound level selectablefrom 3 steps for the night mode
The capacity reduction rate differs depending on the operation sound level step selected.
Design flexibility Easy installationVR V III- S s ys tems offer broad des ign flexibility with long refrigerant piping
lengths and multiple indoor unit c ombinations , whic h provides generous freedom
for offic e and s hop des ign both ins ide and out.
A variety of func tions are provided that make ins tallation eas ier, s uc h as
s imple wiring and piping and automatic tes t operation.
Easy maintenanceVR V III-S features a self-diagnosis function for outdoor units that can determine the
status of each component. Also, a new memory function helps to identify the problem if
MAIN FEATURERS
Unique piping and wiring systems make it possible to install a VRV III-S system quickly and easily. Simple wiring and piping connection
A new type of printed circuit board has been adopted that is easy to see and wire during installation.
Easy wiring
Simply press the test operation button and the unit performs an automatic system check, including wiring, shutoff valves, sensors, and refrigerant volume. The results are returned automatically after the check finishes.
Automatic test operation
Operating data for the preceding 3 minutes is automatically stored in memory. Should a malfunction occur, this speeds up the process of identifying and fixing the cause of the problem.
Memory function for operation data
Daikin’s advanced REFNET piping system makes installation easy. Only two main refrigerant lines are required in any one system. REFNET greatly reduces the imbalances in refrigerant flow between units, while using small-diameter piping.
>> REFNET piping system A super wiring system is used to enable shared use of the wiring between indoor and outdoor units and the central control wiring, with a relatively simple wiring operation. The DIII-NET communication system is employed to enable the use of advanced control system.
>> Super wiring system
For a 6 HP installation
Multiple indoor unit combinations are possible*. As many as 9 indoor units can be connected to single outdoor unit, making the VRV III-S a remarkably versatile system.* Indoor units can be connected up to 130% of the capacity of the outdoor unit.
As many as 9 indoor units can be connected to single outdoor unit
The VRV III-S provides the long piping length possibility of 150 m, with a total piping length of 300 m. If the outdoor unit is installed above indoor units the height difference can be up to a maximum of 50 m. These generous allowances facilitate an extensive variety of system designs.
Long piping design possible
Actual piping length
150 mTotal piping length
300 m
1 2 3 4
5 6 7 8
units9
50 m*1
*2 15 m
Height difference
Level differencebetween indoorunits.
*1. 40 m when the outdoor unit is installed below indoor units.*2. Maximum piping length between the indoor unit and the first branch is 40 m.
Note:
The versatile operating range of the VRV III-S system works to reduce limitations on installation locations. The operating temperature range for heating goes all the way down to -20°C, while cooling can be performed with outdoor temperatures as high as 50°C. Both these achievements are due to the employment of a high-pressure dome-type compressor.
-20
-10
0
10
20
30
40
50
15.5°C WBHeating
50°C DBCooling
-5°C DB
–20°C WB
Outdoor temperature operating rangeWide operating temperature range
Outdoor unitCentralremote
controllerIndoor unit
87
New
New
New
* Refer to the Engineering Data for cooling/heating capacities.* Please contact your distributor to confirm cooling/heating capacities when outdoor
temperatures are 46°C or higher.
Control systemsThe VR V III- S s ys tem us es the s ame DIII- NE T c ommunic ation s ys tem
as the VR V, enabling the us e of advanc ed c ontrol s ys tems .
CONTROL SYSTEMS
Wired remote controller (Optional)
The same operation modes and settings as with wired remote controllers are possible.
Signal receiver unit(Separate type)
Wireless remote controller
The concealed-type remote controller smartly fits into a night table or console panel in a hotel room.
Wireless remote controller (Optional)
Simple remote controller (Optional)
Wide variation of remote controllers for indoor units
Individual control systems
* Refer to the page 35 for the model names.
• A light receiving unit for a ceiling-mounted cassette (double-flow, multi-flow) type, ceiling-suspended type and wall-mounted type is mounted into the indoor unit.
Signal receiver unit(Installed type)
Signal receiving unit can be installed on the panel ex. Ceiling mounted cassette (multi-flow) type
Wired remote controller with weekly schedule timer (Optional)
BRC1D61
24-hour clock function (1-hour backup for power failures)
Includes ventilation mode and airflow rate switching, the main functions of HRV series.
Programming function for each day of week.
Scheduling possible of start/stop and temperature limit (5 settings/day)
Programming can be enabled or disabled.
Copy function for programmed schedules.
Adds new, advanced functions to those of the above wired remote controller.
Notes: 1. Standard remote controllers (BRC1C62) not required. 2. If the BRC1D61 is connected to the centralized remote controller, the schedule function is not available.
Easier to read because LCD screen is larger.Digital display lets you set temperature in 1°C units.Lets you individually program by timer the respective times for operation start and stop within a maximum of 72 hours.Equipped with a thermostat sensor in the remote controller that makes possible more comfortable room temperature control.Enables you to select cool/heat/fan operation mode with the indoor remote controller of your choice without using the cool/heat selector.
Constantly monitors malfunctions in the system for 80 items, and is equipped with a "self-diagnosis function" that lets you know by message immediately when a malfunction occurs.Lets you carry out various field settings by remote controller.Enables you to select the ventilation mode and the volume of the HRV.The rubber switch and the oil-resisting resin casing have been adopted for durability.
* When the auto-swing function is not available, the message, THIS FUNCTION IS NOT AVAILABLE is displayed when the wind direction adjustment button is pressed.BRC1C62
The remote controller has centralized its frequently used operation selectors and switches (on/off, operation mode, temperature setting and airflow volume), making itself suitable for use in hotel rooms or conference rooms.The exposed type remote controller is fitted with a thermostat sensor.
Concealed type(For hotel use)
(BRC3A61)
Exposed type(BRC2C51)
Outdoor unit
Indoor unit
Forced OFF input
Remote controllerRemote controller
Remote controllerRemote controller
Remote controllerRemote controller
Remote controller
Remote controller
HRV
The indoor unit can be connected by the two remote controller, for example one in the room and the other one in the control room, which can control the operation of indoor unit freely.(The last command has a priority.) Of course, the group control by two remote controller is also possible.
Control by two remote controller
The system can be expanded to add several controllers, such as BMS, Forced OFF input and etc.
Expansion of system control
In all the series of VRV, Cool/Heat changeover in the same refrigerant circuit can be changed by the remote controller of the indoor unit.
Control of Cool/Heat changeover
One remote controller can control the operation of max.16 indoor units at the same time.
Group controlEquipment related to the central control
1 2 3
The wiring of remote controller can be extended to max.500m and it is possible to install the remote controllers for the different indoor units in one place.
Remote control
The operation of HRV can be controlled by the remote controller of the indoor unit. Of course, the remote controller can display the time to clean the filter.
Control for the combined operation
4
4
3
2
1
Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.
The wired remote controller supports a wide range of control functions
109
Wired remote controller
Wired remote controller with weekly schedule timer
Wireless remote controller(Installed signal receiver unit)
Wireless remote controller(Separate type signal receiver unit)
Simple remote controller(Exposed type)
Simple remote controller(Concealed type: for Hotel use)
FXCQ FXZQ FXKQ FXSQ FXMQ FXHQ FXAQ FXL(N)Q FXUQFXDQFXFQ
CONTROL SYSTEMS
Up to 64 groups of indoor units (128 units) can be centrally controlled.
Optional controllers for centralized control can be combined freely, and system can be designed in accordance with building scale and purpose.
System integration with various air-conditioning peripheral equipment such as HRV (Heat Reclaim Ventilation) is easy.
Wiring can be run up to a total length of 2 km, and adapts easily to large-scale system expansion.
Centralized control systems
Central remote controllerDCS302CA61
Unified ON/OFF controllerDCS301BA61
Schedule timerDST301BA61
Central remote controller (Optional)
Unified ON/OFF controller (Optional)
Schedule timer (Optional)
16 groups of indoor units can be operated simultaneously/individually.
Max. 128 indoor units can be operated as programmed schedule.
• Max. 64 groups (128 indoor units controllable)• Max. 128 groups (128 indoor units) are controllable by using 2 central remote controllers,
which can control from 2 different places.• Zone control• Malfunction code display• Max. wiring length 1,000 m (Total: 2,000 m)• Combination with Unified ON/OFF controller, schedule timer and BMS system• Airflow volume and direction can be controlled individually for indoor units in each group
operation.• Ventilation volume and mode can be controlled for Heat Reclaim Ventilation (HRV).• Up to 4 Operation/Stop pairs can be set per day by connecting a schedule timer.
• Max. 16 groups (128 indoor units) controllable• 2 remote controllers can be used to control from 2 different places.• Operating status indication (Normal operation, Alarm)• Centralized control indication• Max. wiring length 1,000 m (Total: 2,000 m)• Compact size casing (Thickness: 16 mm)• Combination with Central Remote controller, Schedule timer and BMS system
• Max. 128 indoor units controllable• When used in combination with a central remote controller, a maximum of 8 weekly schedule
patterns can be set, while the central controller can be used to select desired zones. Up to 2 Operation/Stop pairs can be set per day.
• Max. 48 hours back up power supply• Max. wiring length 1,000 m (Total: 2,000 m)• Compact size casing (Thickness: 16 mm)• Combination with Central Remote controller, Unified ON/OFF controller and BMS system
64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.
For more details, please refer to the Engineering Data.
1. Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.• Certain indoor units limit the functions of some control systems.
Central control adaptor kit (DTA107A55).
Wiring adaptorfor other air-conditioners (DTA103A51)
Central remote controller(DCS302CA61)
Up to 2 units connectable
Unified on/off controller(DCS301BA61)
Connection of up to 8 unitspossible
Schedule timer (DST301BA61)1 unit connection possible ; 8 weekly schedule control patterns possible
Forced shut-down input
Independent and centralized control of HRV is possible.
Unification adaptor for computerized control * (DCS302A52)
Interlink Building Management System (host computer monitor panel) also possible
6 cores 7 cores max.
Address setting of central control can be performed from the remote controller.
Group control of up to 16 units is possible (group control via automatic address setting)
System without remote control is also available.
Interface adaptor for SkyAir series (built-in indoor unit) (DTA102A52)
Connectable number of centralized control equipment
Central remotecontoroller 2 units
Unified on /offcontoroller 8 units
Schedule timer 1 unit
Outdoor-air processing unit can be connected.
1
1211
CONTROL SYSTEMS
1413
Color LCD touch panel icon displaySmall manageable size Simplified engineeringMulti language (English, French, Italian, German, Spanish and Chinese)Yearly scheduleP.P.D. (Power Proportinal Distribution function) (Optional)Auto heat/cool change-overTemperature limitationHistory of 500 actionsAir Conditioning Network Service System (Optional Maintenance Service)Simple Interlock Function
New communication functions in the user-friendly icon-based multilingual controller simplify centralized control of the VRV system.
ACC center• Air Conditioning Network Service System
Forced OFF from the fire alarm
Pi Port
• Connection to power consumption meter when using power proportional distribution function. (Optional)
DIII-NETPlus Adapter(option)(DCS601A52)
Number of indoor unit expanded from 64 to 128.
Indoor Unit
RS-232C
Control pump, lighting
Monitoring of roomenter/exit sign
Simple Interlock Function
Public phone line
Air Conditioning Network Service System modem for connections
• CSV output of power proportional distribution results (Optional)
PCMCIAFlash
Memory
Mobile PhoneTrouble reports
Forced OFF contact input
HRV
Dio Unit (DEC102A51)
Di Unit (DEC101A51)
D -NET
SpecialFunction 6
SpecialFunction 1
Remote monitoring and control
SpecialFunction 5
SpecialFunction 3
SpecialFunction 2
SpecialFunction 4
SpecialFunction 6
SpecialFunction 1
SpecialFunction 3
SpecialFunction 5
SpecialFunction 3
SpecialFunction 2
SpecialFunction 4
SpecialFunction 6
SpecialFunction 7
SpecialFunction 7
SpecialFunction 1
SpecialFunction 3
SpecialFunction 5
SpecialFunction 3
SpecialFunction 2
SpecialFunction 4
Doubling of number of control points by adding a D -NET Plus Adapter (Optional)SpecialFunction 1
SpecialFunction 1
Support for centralized control from elsewhere using a PC with a Web browser (Optional)SpecialFunction 2
SpecialFunction 2
Sending of e-mail alerts to a specified address when malfunctions occur (Optional)SpecialFunction 3
SpecialFunction 3
Built-in modem for connecting to Airnet Service System (Optional)SpecialFunction 4
SpecialFunction 4
Built-in Ethernet port for connecting to the Internet or an intranetSpecialFunction 5
SpecialFunction 5
Management of facilities / equipment other than A/C units(Compatible with Dio unit and Di unit)Special
Function 6Special
Function 6
SpecialFunction 7
SpecialFunction 7 Simple Interlock Function
S pe c ia l F u n c t io n s
Trouble reports
Unification adaptorfor computerized control
[DCS302A52]
Unified ON/OFF andstatus monitoring from the central monitoring panel
DCS601C51
Advanced control systems
INDOOR UNITS LINE UP
1615
600 mm
Class 20
32/27
25/32
34/28
63
37/32
40/50
34/29
80
39/34
125
44/38
34/29 36/30 39/3437/32 41/36 46/40
(dB(A))
350mm
The thin unit (only 350 mm high) can be installed in a ceiling space as narrow as 355 mm. All models feature a compact design with a depth of only 600 mm.
(When a high-efficiency filter is attached, the unit's height is 400mm.)
Low operating sound
Designed with higher air flow suitable for high ceiling application up to 3 meter.
Providing 2 different settings of standard and ceiling soiling prevention, the auto swing mechanism ensures even distribution of airflow and room temperature.
Two types of optional high-efficiency filter are available (65% and 95% NBS).
A long-life filter (maintenance free up to one year) is equipped as standard accessory.
Drain-up pump is equipped as standard accessory with 600 mm lift. Major maintenance work can be performed by
removing the panel. A flat-type suction grille and a detachable blade make cleaning easy.
220V
240VOperating
Sound (H/L)
Ceiling mounted cassette(double-flow) type
FXCQ20M/FXCQ25M/FXCQ32MFXCQ40M/FXCQ50M/FXCQ63MFXCQ80M/FXCQ125M
Thin, lightweight, and easy to install in narrow ceiling space
Ceiling MountedCassette(Double-flow)
Type
Ceiling MountedCassette(Multi-flow)Super Cassette
Ceiling MountedCassette Corner
Wall Mounted
Floor Standing
Concealed FloorStanding
FXCQ-MVE
FXFQ-MVE
FXHQ-MAVE
HPIndex
FXKQ-MAVE
FXLQ-MAVE
FXNQ-MAVE
FXMQ-MAVE
Model name
20 25 31.25 40 50 62.5 80 100 1250.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP
RT
Capacity Btu 7500 9600 12300 15400 19100 24200 30700 38200 478000.6 ton 0.8 ton 1.0 ton 1.3 ton 1.6 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton
FXDQ-NAVE(900/1,100 mm
width type)
FXDQ-NVET(900/1,100 mm
width type)
with drain-up pump
without drain-up pump
FXSQ-MVECeiling MountedBuilt-in
Ceiling Suspended
Ceiling Mounted Duct
FXAQ-MAVE
Ceiling SuspendedCassette
Type
—
FXUQ-MAV1
Model name20 4031.2525
BEVQ125MAVEBEVQ100MAVEBEVQ71MAVE50 12510071
• Indoor units in the 63 class are not available for the above models.• BEV units are necessary for Connection unit series indoor units. Refer to the Connection unit series catalog for details.
Notes:
• R410A VRV system indoor units are not compatible with the R22 VRV system.Note:
Connection unit series indoor units
154007500 123009600 4780019100 3820027300Btu
Connection UnitIndex
1.3 ton0.6 ton 1.0 ton0.8 ton
0.8 HP 1.6 HP1.25 HP1 HP
4.0 ton1.6 ton 3.2 ton2.3 ton
2 HP 5 HP4 HP3 HP
RT
Capacity HP
Slim Ceiling Mounted Duct
FXDQ-PVE(700 mm
width type)
FXDQ-PVET(700 mm
width type)
with drain-up pump
without drain-up pump
New
600X600multi flow ceiling mounted cassette
FXZQ-M7V1B
New
New
New
New
New
New
New
Conversion rates
Btu/h = kW x 3412RT = kW x 0.284
INDOOR UNITS LINE UP
1817
Ceiling mounted cassette(multi-flow) type
Compact, quiet and easy-to-install Super Cassette type
Regardless of their difference in capacity, all indoor units feature the same panel size and design, in consideration of harmonized interior decor.
The FXFQ25M-80M are thin models (246mm) which can be installed in narrow false ceilings of at least 265mm depth.
(220V-240V)(dB(A))
Single branch– 8 patterns
2 branches–2 patterns
Number of discharge outlets usedFXFQ25M-80M FXFQ100M-125M
4-way air discharge
3-way air discharge
2-way air discharge
4-way air discharge
3-way air discharge
2-way air discharge
Ceilingheight
Standard 2.7m3.0m3.5m
3.0m3.3m3.5m
3.5m3.8m
–
3.2m3.6m4.2m
3.6m4.0m4.2m
4.2m4.2m
–High ceilingHigh ceiling
Note: Set standard 4-way discharge when shipped.High ceiling types and will be set for remote control operation1 2
12
40˚40˚10˚ 10˚
Pattern
2 Draft Prevention setting
Pattern
1 Standard setting
7 discharge patterns in 2 to 4 directions can be selected to suit the requirements of installation site or the shape of the room.The number of installation method using ducts has increased as shown below.
Pipinglocation
Has been set to standard setting at time of shipment. This can be changed using the remote control
Closed
Branched
Pipinglocation
ClosedBranched
25˚ 25˚
60˚ 60˚35˚35˚
65˚ 65˚
Pattern
3 Setting to prevent soiling of ceiling
750mm
Because of the light weight, suspension is easy.Low operating sound
Installing the fresh air intake is easy using the optional kit which requires no special chambers.A long-life filter (maintenance free up to two years) is equipped as a standard accessory.
Provided with high lift drain water lift-up mechanism. (Increased lift of drain pipe up to 750 mm from the ceiling.)
Note: Operating sound may increase more than that when using with 3-way discharge or 2-way discharge, or when using together with a optional kit. : The values of Hi mode Sound level represent those during cooling operation. Those during heating operation are shown in brackets for two models only.
42(43) /36
125
39/33
100
36/31
80
33(34) /28
63
32/27
50
31/27
40
30/27
32
30/27
25Operating
sound (H/L)
Class
FXFQ25M/FXFQ32M/FXFQ40MFXFQ50M/FXFQ63M/FXFQ80MFXFQ100M/FXFQ125M
Can also be installed in high ceilings.
There are 3 patterns in auto swing operation
Quiet, stylish unitwith a horizontal blow capability
Exactly matches the European style architectural module (600 mm x 600 mm).
Switch box is inside the unit, which makes maintainance and installation easy.
Less draft than FXFQ cassette discharge angle: 25° to 60° 0° to 60°
Low operating sound(240V)(dB(A))
600 x 600 multi flow ceiling mountedcassette type
FXZQ20M/FXZQ25M/FXZQ32MFXZQ40M/FXZQ50M
New model
0°
60°
0°
60°
Auto swing
Settable to 5 different levels between 0° and 60°
Angles can be set on site to prevent drafts (0°-35°) or soiling of the ceiling (25°-60°)
32/26OperatingSound (H/L)
20 25 32 40 50
32/26 34/28 37/29 42/35
Class
INDOOR UNITS LINE UP
2019
Slim ceiling mountedduct type
Slim design, quietness and static pressure switching
FXDQ20N(A)/FXDQ25N(A)/FXDQ32N(A)FXDQ40N(A)/FXDQ50N(A)/FXDQ63N(A)FXDQ20P/FXDQ25P/FXDQ32P
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.10 Pa-30 Pa/factory set: 10 Pa for FXDQ-P models.15 Pa-44 Pa/factory set: 15 Pa for FXDQ-N(A) models.
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
Low operating sound
36/32
63
35/31
50
34/30
40
33/29
32
33/29
25
33/29
20Operating
sound (H/L)
Class(dB(A))
The values of operation sound level represent those for rear-suction operation.Sound level values for bottom-suction operation can be obtained by adding 5 dB. Values are based on the following conditions:FXDQ-P: external static pressure of 10 Pa; FXDQ-N(A): external static pressure of 15 Pa.
1,100 mm in width for the FXDQ63N(A) model.
200mm900 mm
Suction grille*AIR
AIR
Discharge grille*
Air filterSuspension bolt*
240 mm
*: To be obtained locally
750mm
Ceiling
FXDQ-P and FXDQ-N(A) models are available in two types to suit different installation conditionsFXDQ-PVE, FXDQ-NAVE: with a drain-up pump (750 mm lift) as a standard accessoryFXDQ-P(N)VET: without a drain-up pump
Only 700 mm200 mm
Great for hotel use!
Compliant with the RoHS Directive ** For FXDQ-PVE and FXDQ-NAVE models only.
Suited to use in drop-ceilings!
Ceiling mounted cassettecorner type
Slim design for flexible installation
3
32˚C 30˚C28˚C 26˚C 24˚C
22˚C
20˚C
2
1
0 1 2 3 4 5 6 (m)
(m)
Panel spac er
20 mm
Min.195 mm
Main body
Air disc harge grille (option)
Set for front discharge using a suspended ceiling.
Downward discharge is shut off and air is blown straight out (front discharge).
Compliant with the RoHS Directive*
Single-flow type allows effective air discharge from corner or from drop-ceiling.
Front discharge is possible with a air discharge unit (optional), which allows the installation in the drop-ceiling or sagging wall.
Slim body needs only 220 mm space above the ceiling. If you use panel spacer (optional), the unit can be installed in the min. space of 195 mm.
A long-life filter (maintenance free up to one year) is equipped as standard accessory.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism ensures even distribution of airflow and room temperature.
500 mm
Drain-up pump is equipped as standard accessory with 500 mm lift.
Main body
Downward disc harge
Air disc harge grille (option)
FXKQ25MA/FXKQ32MAFXKQ40MA/FXKQ63MANew
NE W
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
NE W
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
INDOOR UNITS LINE UP
2221
Ceiling mountedduct type
High static pressure allows flexible duct design
More than 150 Pa of external static pressure
Compliant with the RoHS Directive*
High external static pressure allows extensive duct work for flexible applications.
Optional accessories include a drain-up kit, high-efficiency filters (65% and 95% NBS) and a long-life filter (maintenance free up to 1 year).
Full line-up of 8 models from 40 to 250 type.
Indoor unit
Min450mm390mm
Without drain Drain-up pump is equipped as optional ac c essory with 750 mm
750mm
120mm
FXMQ40MA/FXMQ50MAFXMQ63MA/FXMQ80MAFXMQ100MA/FXMQ125MA
New
NE W
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
Ceiling mountedbuilt-in type
Highly flexible for various application
FXSQ20M/FXSQ25M/FXSQ32MFXSQ40M/FXSQ50M/FXSQ63MFXSQ80M/FXSQ100M/FXSQ125M
250 mm
Min.350 mm
Highly flexible installation is possible with a complete line-up of optional kits to satisfy the various needs, such as the design concept, interior decoration and so on.
The unit can be installed, if there is a space of 350 mm above ceiling. (when suction panel is used.)
Drain-up pump is equipped as standard accessory with 250 mm lift.
High external static pressure allows to use even flexible ducts of various length.
Low operating sound
Two types of optional high-efficiency filter are available (65% and 95% NBS).
A long-life filter (maintenance free up to one year) is equipped as standard accessory.
37/32
39/34Operating
Sound (H/L)
20 25
37/32
32
38/32
40
38/32
50
41/36
63
42/35
80
43/37
100
43/37
125
46/41
39/34 40/34 40/34 43/38 44/37 45/39 45/39 48/43
(dB(A))
Class
Standard
With duct (case 1)
With duct (case 2)
Cassette style (standard filter)
Cassette style (high efficiency filter)
Long-life filter
Long-life filter
Air suc tion c anvas bellows
Air suc tion panel
Air suc tion panel
Ac c ess panel Ac c ess panel
Ac c ess panel Air suc tion c anvas bellows
Ceiling returnLong-life filter
Long-life filter
S c reening door
S c reening door
High effic ienc yfilter
220V
240V
Installation examples ( Optional parts)
INDOOR UNITS LINE UP
2423
Wall mounted type
Sophisticated design and compact casing harmonized with your interior décor
Drain pan and air filter can be kept clean by mildew-proof polystyrene.
Compact and stylish design that does not detract from the décor of the room.
Drain-up kit
1,000mm
Height of drain-up
Indoor unit
Drain-pump kit is available as optional accessory, which lifts the drain 1,000 mm from the bottom of the unit.
Auto-swing ensures efficiency of air distribution. The louver closes automatically when the unit stops.
5 steps of discharge angle can be set by remote controller.
Washable grille, the front grille can be easily removed for washing.
Discharge angle is automatically set at the same angle as the previous operation when restarts. (Initial setting; 10˚ for cooling and 70˚ for heating)
1,050 mm
For 50, 63 Class–70 mm
–200 mm
290
mm
More compact than compared with previous model. (50, 63 class)
Drastic 10 kg weight reduc tion from 24 kg to 14 kg.Volume reduc ed by 22%. S pac e savings of up to 47%.
Flexible installation.Drain pipe c an be fitted to from either left or right s ides .
Low operating sound
46/39
63
42/36
50
39/34
40
37/29
32
36/29
25
35/29
20Operating
sound (H/L)
Class(220V-240V)(dB(A))
FXAQ20MA/FXAQ25MAFXAQ32MA/FXAQ40MAFXAQ50MA/FXAQ63MA
Compliant with the RoHS Directive*
New
NE W
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
Ceiling suspended type
Slim body with quiet and wide air flow
Compliant with the RoHS Directive*
Adoption of newly designed QUIET STREAM FAN
Drain-up kit (optional) c an be eas ily inc orporated.
E asy-to-c lean flat des ign
Maintenanc e is eas ier bec ause everything c an be performed from below the unit.
Non-dew Flap with no implanted bris tles
Class
Operating sound (H/L)
32
36/31
63
39/34
100
45/37
(220V-240V)(dB(A))Low operating sound
Uses the quiet s tream fan and many more advanc ed tec hnologies .
S ound absor ption member
Turbulent flow is produc ed
S traightening vane
Quiet s tream fan
Installation is easy
Maintenance is easy
Drain-up kit(built ins ide main unit)
600mm
B ristle-free Flap minimizes c ontamination and makes c leaning s impler.
Non-dew Flap
100°New model
Wide air discharge openings produce a spreading 100° air flow.
A long-life filter (maintenanc e free up to one year) is equipped as s tandard
FXHQ32MA/FXHQ63MAFXHQ100MA
New
NE W
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
INDOOR UNITS LINE UP
2625
Ceiling suspendedcassette type
This ultra-thin indoor unit achieves optimumair distribution, and can be installedwithout the need for ceiling cavity
FXUQ71MAV1FXUQ100MAV1FXUQ125MAV1
Connection unitNew
New
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
Connection unit is the device for connecting above indoor units to VRV III-S.
Depending on installation site requirements or room conditions, 2-way, 3-way and 4-way discharge patterns are available.
Compliant with the RoHS Directive*NE W
Compliant with the RoHS Directive*NE W
4-way air flowfrom the center of the store.
The 3-way air flow can distributecomfortable air throughout the room.
Only one unit is needed to distribute comfortable airthroughout an L-shaped store.
BEVQ-MAVE
Connection unit for indoor unit
Indoor unitPiping length*1
Indoor unit
R emote c ontroller
S uper wiring ( DIII-NE T )
S ingle-phase 220-240 Vpower supply
VR V -S series outdoor unit
Refrigerant piping layout External wiring layout
Notes:G as pipeLiquid
pipe
ModelMaximum piping lengthbetween the BEV unitand the indoor units.
FXUQ-MAV1 5 m
*1
• When connecting centralized-control device, it is necessary to install an interface adaptor for an indoor unit (DTA102A52).
• Connection unit BEVQ-MA is necessary for each indoor unit.
• The refrigerant piping height difference between the indoor units and the BEV unit must be within 4 m.
• The BEV unit must be installed within a maximum height difference between indoor units of 15 m.
• Branching of the refrigerant piping is not possible downstream of the BEV unit.
Floor standing type
A great unit for perimeter zone air conditioning
Wall hanging Floor installation
Floor standing types can be hung on the wall for easier cleaning. Since running the piping from the back allows the unit to be hung on walls. Cleaning under the unit, where dust tends to accumulate, is considerably easier.
A long-life filter (maintenance free up to one year) is equipped as standard accessory.
Compliant with the RoHS Directive*
The adoption of a fiber-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier.
Concealed floorstanding type
A great unit to be concealed in the skirting-wall of perimeter
C onnec ting port
R efrigerant piping
Applies also to floor standing type (FXNQ-MA).
The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design.
Compliant with the RoHS Directive*
The connecting port faces downward, greatly facilitating on-site piping work.
A long-life filter (maintenance free up to one year) is equipped as standard accessory.
FXNQ20MA/FXNQ25MAFXNQ32MA/FXNQ40MAFXNQ50MA/FXNQ63MA
New
New
FXLQ20MA/FXLQ25MAFXLQ32MA/FXLQ40MAFXLQ50MA/FXLQ63MA
NE W
NE W
New
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
SPECIFICATIONS
INDOOR UNIT SINDOOR UNITS
2827
FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE
Galvanized steel plate
7/5
247/17732/27
305X775X600
26.0
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
BYBC32G-W1
White (10Y9/0.5)
53X1,030X680
8.0
9/6.5
318/23034/28
305X775X600
26.0
6.4
12.7
53X1,030X680
8.0
9/6.5
318/23034/28
305X775X600
26.0
6.4
12.7
53X1,030X680
8.0
12/9
424/31834/29
305X990X600
31.0
6.4
12.7
BYBC50G-W1
53X1,245X680
8.5
12/9
424/31834/29
305X990X600
32.0
6.4
12.7
53X1,245X680
8.5
16.5/13
582/45937/32
305X1,175X600
35.0
9.5
15.9
BYBC63G-W1
53X1,430X680
9.5
26/21
918/74139/34
305X1,665X600
47.0
9.5
15.9
BYBC125G-W1
53X1,920X680
12.0
33/25
1,165/88344/38
34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40305X1,665X600
48.0
9.5
15.9
53X1,920X680
12.0
C e ilin g M o u n t e d C a s s e t t e <D o u b le f lo w > T y p e
MODEL FXFQ25MVE
Galvanized steel plate
246X840X840
24.0
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
BYCP125D-W1
White (10Y9/0.5)
45X950X950
5.5
45X950X950
5.5
45X950X950
5.5
45X950X950
5.5
45X950X950
5.5
45X950X950
5.5
45X950X950
5.5
45X950X950
5.5
246X840X840
24.0
6.4
12.7
FXFQ32MVE
15/1113/10 13/10
30/27 30/27
530/388
31/27
246X840X840
24.0
6.4
12.7
FXFQ40MVE
16/11
565/388459/353 459/353
32/27
246X840X840
24.0
6.4
12.7
FXFQ50MVE
18.5/14
653/494
33(34) /28
246X840X840
25.0
9.5
15.9
FXFQ63MVE
20/15
706/530
36/31
246X840X840
25.0
9.5
15.9
FXFQ80MVE FXFQ100MVE FXFQ125MVE
26/21
918/741
39/33
288X840X840
29.0
9.5
15.9
30/24
1,059/847
42(43) /36
288X840X840
29.0
9.5
15.9
Casing
1 phase, 220-240 V, 50 HzPower supply
Air flow rate (Hi/Lo) m3/min
cfm
Dimensions (HXWXD) mm
Machine weight kg
Piping connections Liquid(Flare)mm
Gas(Flare)mm
Drain piping
Panel(Option) Model
Colour
mm
C e ilin g M o u n t e d C a s s e t t e <M u lt i- f lo w > T y p e
MODEL
Casing
1 phase, 220-240 V, 50 HzPower supply
Air flow rate (Hi/Lo) m3/min
cfm
Dimensions (HXWXD) mm
Machine weight kg
Piping connections Liquid(Flare)mm
Gas(Flare)mm
Drain piping
Panel(Option) Model
Colour
mm
Sound level (Hi/Lo)
Dimensions(HXWXD)
Dimensions(HXWXD)
weight kg
weight kg
dB (A)
50 Hz/60 Hz 220V50 Hz 240V
dB(A)Sound level (Hi/Lo)
Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.)•Sound level : Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
: The values of Hi mode Sound level represent those during cooling operation.Those during heating operation are shown in brackets for two models only.
7,800/7,500
2,000/1,900
2.5
8,500
2,200
9,900/9,600
2,500/2,400
3.2
10,900
2,800
12,600/12,300
3,200/3,100
4.0
13,600
3,400
16,000/15,400
4,000/3,900
5.0
17,100
4,300
19,800/19,100
5,000/4,800
6.3
21,500
5,400
24,900/24,200
6,300/6,100
8.0
27,300
6,900
31,700/30,700
8,000/7,700
10.0
34,100
8,600
2.3/2.2 2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 14.5/14.0
49,500/47,800
12,500/12,000
16.0
54,600
13,800
Cooling capacity (*1)/(*2)
kW
Btu/h
0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 4.1/4.0RT
kcal/h
Heating capacity (*3)
kW
Btu/h
0.7 0.9 1.1 1.4 1.8 2.3 2.8 4.5RT
kcal/h
Cooling capacity(*1)/(*2)
kW
9,900/9,600
2,500/2,400
3.2
10,900
2,800
12,600/12,300
3,200/3,100
4.0
13,600
3,400
16,000/15,400
4,000/3,900
5.0
17,100
4,300
19,800/19,100
5,000/4,800
6.3
21,500
5,400
24,900/24,200
6,300/6,100
8.0
27,300
6,900
2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0
31,700/30,700
8,000/7,700
10.0
34,100
8,600
39,600/38,200
10,000/9,600
12.5
42,700
10,800
11.6/11.2 14.5/14.0
49,500/47,800
12,500/12,000
16.0
54,600
13,800
Btu/h
0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 3.3/3.2 4.1/4.0RT
kcal/h
Heating capacity(*3)
kW
Btu/h
kcal/h
0.9 1.1 1.4 1.8 2.3 2.8 3.6 4.5RT
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
C e ilin g M o u n t e d C a s s e t t e C o r n e r T y p e
Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m •Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level (FXZQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center.
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
FXKQ25MAVE
Galvanized steel plate11/9
FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
11/9 13/10 18/15388/318 388/318 459/353 635/530
215X1,110X71031.0 6.4
12.7VP25 (External Dia, 32/Internal Dia, 25)
BYK45FJW1White (10Y9/0.5)
70X1,240X8008.5
215X1,110X71031.0 6.4
12.7
70X1,240X8008.5
215X1,110X71031.0 6.4
12.7
70X1,240X8008.5
215X1,310X71034.0 9.5
15.9
BYK71FJW1
70X1,440X8009.5
Dimensions (HXWXD) mmMachine weight kgPiping connections Liquid(Flare)mm
Gas(Flare)mmDrain piping
Panel (Option) ModelColour
mmweight kg
Dimensions(HXWXD)
38/33 38/33 40/34 42/3740/35 40/35 42/36 44/39
Casing
1 phase, 220-240 V, 50 HzPower supply
Air flow rate (Hi/Lo)
MODEL
m3/mincfm
50 Hz50 Hz
Sound level (Hi/Lo) dB (A)
50 Hz/60 Hz 220V50 Hz 240V
MODEL
50Hz
kcal/h 2,000/1,900
9/7
Btu/hRT
Heating capacity (*3)
RTBtu/h
318/247
FXZQ25M7V1B
2,500/2,4009,900/9,600
0.8/0.8
0.910,900
9/7318/247
FXZQ32M7V1B
3,200/3,10012,600/12,300
1.1/1.0
1.113,600
9.5/7.5335/265
FXZQ40M7V1B
4,000/3,900kW 2.9/2.8 3.7/3.6 4.7/4.5
16,000/15,4001.3/1.3
1.417,100
11/8388/282
600X600 Multi Flow Ceiling Mounted Cassette Type
260X575X57518
6.4 12.7
VP20 (External Dia, 26/Internal Dia, 20)BYFQ60B7W1
White (6.5Y9.5/0.5)55X700X700
2.7
6.4 12.7
55X700X7002.7
6.4 12.7
55X700X7002.7
6.4 12.7
55X700X7002.7
Dimensions (HXWXD) mmMachine weight kgPiping connections Liquid(Flare)mm
Gas(Flare)mmDrain piping
Panel (Option) ModelColour
mmweight kg
Dimensions(HXWXD)
Casing
Power supply
50HzAir flow rate (Hi/Lo)
Cooling capacity (*1)/(*2)
FXZQ50M7V1B
5,000/4,8005.8/5.6
19,800/19,1001.6/1.6
1.821,500
14/10494/353
6.4 12.7
55X700X7002.7
cfmm3/min
8,5002,800 3,400 4,300kcal/h 5,4002,200
Galvanized steel plate
0.7
kW 3.2 4.0 5.0 6.32.5
7,800/7,5000.7/0.6
1 phase, 220-240 V, 50 Hz
FXZQ20M7V1B
2.3/2.2
Sound level (Hi/Lo) dB(A) 240V 32/26 32/26 34/28 37/29 42/35
kW
9,900/9,6002,500/2,400
3.2
10,9002,800
Btu/hkcal/h
Heating capacity(*3)
kW
Btu/h
12,600/12,3003,200/3,100
4.0
13,6003,400
16,000/15,4004,000/3,900
5.0
17,1004,300
2.9/2.8 3.7/3.6 4.7/4.5 7.3/7.1
24,900/24,2000.8/0.8RT 1.1/1.0 1.3/1.3 2.1/2.0
6,300/6,100
8.0
27,3000.9RT 1.1 1.4 2.3
6,900kcal/h
Cooling capacity(*1)/(*2)
INDOOR UNIT SINDOOR UNITS
SPECIFICATIONS
3029
S lim C e ilin g M o u n t e d D u c t T y p e
Galvanized steel plate
8.0/6.4
282/226
8.0/6.4
282/226
8.0/6.4
282/226
33/29 33/29 33/29
Air flow rate (Hi/Lo) m3/min
cfm
dB(A)
Casing
1 phase, 220-240 V, 50 HzPower supply
200X700X620
23.0
6.4
12.7
200X700X620
23.0
6.4
12.7
200X700X620
23.0
6.4
12.7
Dimensions(HXWXD)
Sound level (Hi/Lo)
PaExternal static pressure
mm
Machine weight kg
Piping connections Liquid(Flare)mm
Gas(Flare)mm
Drain piping VP20 (External Dia, 26/Internal Dia, 20)
30-10 1
32
S lim C e ilin g M o u n t e d D u c t T y p e
Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.
1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting is 10 Pa for FXDQ-P models and 15 Pa for FXDQ-N(A) models.)
2 : The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB. 3 : Values are based on the following conditions: FXDQ-P: external static pressure of 10 Pa; FXDQ-N(A): external static pressure of 15 Pa.•Equivalent piping length : 7.5m •Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level (FXDQ-P, FXDQ-N(A)) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Galvanized steel plate
9.5/7.5
335/265
9.5/7.5
335/265
10.5/8.5
371/300
10.5/8.5
371/300
12.5/10.0
441/353
16.5/13.0
583/459
33/29 33/29 33/29 34/30 35/31 36/32
Air flow rate (Hi/Lo) m3/min
cfm
dB(A)
Casing
1 phase, 220-240 V, 50 HzPower supply
200X900X620
26.0
6.4
12.7
200X900X620
26.0
6.4
12.7
200X900X620
26.0
6.4
12.7
200X900X620
27.0
6.4
12.7
200X900X620
28.0
6.4
12.7
200X1,100X620
31.0
9.5
15.9
Dimensions(HXWXD)
PaExternal static pressure
mm
Machine weight kg
Piping connections Liquid(Flare)mm
Gas(Flare)mm
Drain piping VP20 (External Dia, 26/Internal Dia, 20)
44-15 1
Sound level (Hi/Lo) 32
Cooling capacity(*1)/(*2)
kW
7,800/7,500
2,000/1,900
9,900/9,600
2,500/2,400
12,600/12,300
3,200/3,100
RT 0.7/0.6
Btu/h
kcal/h
8,500
2,200
10,900
2,800
13,600
3,400
Btu/h
0.7 0.9 1.1RT
2.5 3.2 4.0kW
kcal/h
Heating capacity(*3)
0.8/0.8 1.1/1.0
2.3/2.2 2.9/2.8 3.7/3.6
Cooling capacity(*1)/(*2)
kW
7,800/7,500
2,000/1,900
9,900/9,600
2,500/2,400
12,600/12,300
3,200/3,100
16,000/15,400
4,000/3,900
19,800/19,100
5,000/4,800
24,900/24,200
6,300/6,100
2.3/2.2
Btu/h
0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0RT
kcal/h
8,500
2,200
10,900
2,800
13,600
3,400
17,100
4,300
21,500
5,400
27,300
6,900
Btu/h
0.7 0.9 1.1 1.4 1.8 2.3RT
2.5 3.2 4.0 5.0 6.3 8.0kW
kcal/h
Heating capacity(*3)
2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
C e ilin g M o u n t e d B u ilt - in T y p e
Galvanized steel plate
FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE
9/6.5 9/6.5 9.5/7 11.5/9 15/11 21/15.5 27/21.5 28/22 38/28318/230 318/230 335/247 406/318 530/388 741/547 953/759 988/777 1,341/988
Casing
1 phase, 220-240 V, 50 HzPower supply
300X550X80030.0 6.4
12.7VP25 (External Dia, 32/Internal Dia, 25)
300X550X80030.0 6.4
12.7
38/32
300X550X80030.0 6.4
12.7
38/32
300X700X80030.0 6.4
12.7
300X700X80031.0 6.4
12.7
300X1,000X80041.0 9.5
15.9
43/37
300X1,400X80051.0 9.5
15.9
43/37
300X1,400X80051.0 9.5
15.9
46/41
300X1,400X80052.0 9.5
15.9
Dimensions(HXWXD) mm
External static pressure Pa
Machine weight kgPiping connections Liquid(Flare)mm
Gas(Flare)mm
White (10Y9/0.5)55X650X500
3.0
55X650X5003.0
55X650X5003.0
55X800X5003.5
55X800X5003.5
55X1,100X5004.5
55X1,500X5006.5
55X1,500X5006.5
55X1,500X5006.5
Panel(Option)Colour
mm
BYBS32DJW1 BYBS32DJW1 BYBS32DJW1 BYBS45DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1
41/36 42/3537/32 37/3240/34 40/34 45/39 45/39 48/4343/38 44/3739/34 39/34
Sound level (Hi/Lo)
Model
Dimensions(HXWXD)
Drain piping
weight kg
MODEL
Air flow rate (Hi/Lo)
220V240V
50 Hz
88-39-20 88-39-20 64-39-15 88-49-20 88-59-29 88-49-20 113-82 107-75 78-391 1 1 1 1 1 2 22
m3/mincfm
50 Hz50 Hz50 Hz
dB (A)
Cooling capacity(*1)/(*2) 7,800/7,500
2,000/1,900
2.5
8,5002,200
9,900/9,6002,500/2,400
3.2
10,9002,800
12,600/12,3003,200/3,100
4.0
13,6003,400
16,000/15,4004,000/3,900
5.0
17,1004,300
19,800/19,1005,000/4,800
6.3
21,5005,400
24,900/24,2006,300/6,100
8.0
27,3006,900
31,700/30,7008,000/7,700
10.0
34,1008,600
39,600/38,20010,000/9,600
12.5
42,70010,800
2.3/2.2
49,500/47,80012,500/12,000
16.0
54,60013,800
Btu/h0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 3.3/3.2 4.1/4.0RT
kcal/h
kW
Btu/hkcal/h
0.7 0.9 1.1 1.4 1.8 2.3 2.8 3.6 4.5RT2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 11.6/11.2 14.5/14.0
Heating capacity(*3)
kW
MODEL FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MAVE FXMQ100MAVE FXMQ125MAVE
Galvanized steel plate
14/11.5
494/406
39/35
390X720X690
44.0
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
14/11.5
494/406
39/35
390X720X690
44.0
6.4
12.7
14/11.5
494/406
39/35
390X720X690
44.0
9.5
15.9
19.5/16
688/565
42/38
390X720X690
45.0
9.5
15.9
29/23
1,024/812
43/39
390X1,110X690
63.0
9.5
15.9
36/29
1,271/1,024
45/42
390X1,110X690
65.0
9.5
15.9
41/37 41/37 41/37 44/40 45/41 47/44
m3/min
cfm
Dimensions (HXWXD) mm
Machine weight kg
Piping connections Liquid(Flare)mm
Gas(Flare)mm
Drain piping
C e ilin g M o u n t e d D u c t T y p e
Casing
1 phase, 220-240 V, 50 HzPower supply
Air flow rate (Hi/Lo)
Sound level (Hi/Lo)Pa (50Hz) 157-118 157-118 157-118 157-108 157-98 191-152 External static pressure 2 2 2 2 2 2
dB (A)
50 Hz/60 Hz 220V
50 Hz 240V
Cooling capacity(*1)/(*2)
kW
16,000/15,400
4,000/3,900
5.0
17,100
4,300
19,800/19,100
5,000/4,800
6.3
21,500
5,400
24,900/24,200
6,300/6,100
8.0
27,300
6,900
31,700/30,700
8,000/7,700
10.0
34,100
8,600
49,500/47,800
12,500/12,000
16.0
54,600
13,800
4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 14.5/14.0
Btu/h
1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 4.1/4.0RT
kcal/h
Heating capacity(*3)
kW
Btu/h
1.4 1.8 2.3 2.8 4.5
39,600/38,200
110,000/9,600
12.5
42,700
10,800
11.6/11.2
3.3/3.2
3.6RT
kcal/h
Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB. 1 : External static pressure is changeable to change over the connectors inside electrical box, this pressure means "High static pressure-Standard-Low static pressure". 2 : External static pressure is changeable to change over the connectors inside electrical box, this pressure means "High static pressure-Standard".•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.)•Sound level : (FXSQ-M, FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
without drain-up pump
with drain-up pump
FXDQ20NVET FXDQ25NVET FXDQ32NVET FXDQ40NVET FXDQ50NVET FXDQ63NVETMODEL
FXDQ20NAVE FXDQ25NAVE FXDQ32NAVE FXDQ40NAVE FXDQ50NAVE FXDQ63NAVE
FXDQ20PVET FXDQ25PVET FXDQ32PVETMODEL without
drain-up pump
FXDQ20PVE FXDQ25PVE FXDQ32PVEwith drain-up pump
INDOOR UNITS INDOOR UNIT S
SPECIFICATIONS
3231
MODEL FXHQ32MAVE
White (10Y9/0.5)
FXHQ63MAVE FXHQ100MAVE
C e ilin g S u s p e n d e d T y p e
cfm
12/10 17.5/14 25/19.5
Dimensions(HXWXD) mm
Machine weight kg
Piping connections Liquid(Flare)mmGas(Flare)mm
Drain piping
36/31 39/34 45/37
195X960X680
24.0
6.4 12.7
VP20 (External Dia, 26/Internal Dia, 20)
195X1,160X680
28.0
9.5 15.9
195X1,400X680
33.0
9.5 15.9
Casing
1 phase, 220-240 V, 50 HzPower supply
m3/minAir flow rate (Hi/Lo)
424/353 883/688618/494
dB(A)Sound level (Hi/Lo)
Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level : (FXHQ-MA, FXAQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
W a ll M o u n t e d T y p e
MODEL FXAQ25MAVE
White (3.0Y8.5/0.5)
36/29
290X795X230
11.0
Casing
1 phase, 220-240 V, 50 HzPower supply
37/29
290X795X230
11.0
FXAQ40MAVE
39/34
290X1,050X230
14.0
282/177 318/194 424/318
Dimensions (HXWXD) mm
Machine weight kg
Piping connections Liquid(Flare)mm
Gas(Flare)mm
Drain piping
m3/minAir flow rate (Hi/Lo)
cfm
8/5 9/5.5
FXAQ32MAVEFXAQ20MAVE
35/29
290X795X230
11.0
265/159
7.5/4.5 12/9
VP13 (External Dia, 18/Internal Dia, 13)
6.4 6.4 6.4 6.4
12.7 12.7 12.7 12.7
42/36
290X1,050X230
14.0
FXAQ63MAVE
15/12 19/14
530/424
46/39
290X1,050X230
14.0
671/494
FXAQ50MAVE
6.4 9.5
12.7 15.9
dB(A)Sound level (Hi/Lo)
Cooling capacity(*1)/(*2)
kW
12,600/12,300
3,200/3,100
4.0
13,600
3,400
24,900/24,200
6,300/6,100
8.0
27,300
6,900
3.7/3.6 7.3/7.1 11.6/11.2
39,600/38,200
10,000/9,600
12.5
42,700
10,800
Btu/h
1.1/1.0 2.1/2.0 3.3/3.2RT
kcal/h
Heating capacity(*3)
kW
Btu/h
1.1 2.3 3.6RT
kcal/h
Cooling capacity(*1)/(*2)
3.2
Btu/h
kcal/h
Heating capacity(*3)
kW
Btu/h
kcal/h
5.0
9,900/9,600 16,000/15,400
2,500/2,400 4,000/3,900
10,900 17,100
2,800 4,300
13,600
3,400
12,600/12,300
3,200/3,100
4.0
2.9/2.8
2.5
7,800/7,500
2,000/1,900
8,500
2,200
2.3/2.2 4.7/4.53.7/3.6kW
24,900/24,200
6,300/6,100
27,300
6,900
8.0
21,500
RT 0.9 1.41.10.7 2.31.8
5,400
6.3
5,000/4,800
19,800/19,100
RT 0.8/0.8 1.3/1.31.1/1.00.7/0.6 2.1/2.01.6/1.6
7.3/7.15.8/5.6
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
Note : Specifications are based on the following conditions ;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level : (FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
F lo o r S t a n d in g T y p e / C o n c e a le d F lo o r S t a n d in g T y p e
MODELFXLQ20MAVE
FXLQ:Ivory white (5Y7.5/1) / FXNQ:Galvanized steel plateCasing
Power supply
Air flow rate (Hi/Lo) m3/min
cfm
7/6
247/212
600X1,000X222
25.0
6.4
12.7
21O.D.
Dimensions (HXWXD)
Machine weight
Piping connections Liquid(Flare)mm
Gas(Flare)mm
Drain piping
FXLQ25MAVE
7/6
247/212
600X1,000X222
25.0
6.4
12.7
282/212 388/300 494/388 565/424
FXLQ32MAVE
8/6
600X1,140X222
30.0
6.4
12.7
FXLQ40MAVE
11/8.5
600X1,140X222
30.0
6.4
12.7
FXLQ50MAVE
14/11
600X1,420X222
36.0
6.4
12.7
FXLQ63MAVE
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
16/12
600X1,420X222
610X930X220 610X930X220 610X1,070X220 610X1,070X220 610X1,350X220 610X1,350X220
36.0
19.0 19.0 23.0 23.0 27.0 27.0
9.5
15.9
mmFXLQ
FXNQ
kgFXLQ
FXNQ
35/32 35/32 35/32 38/33 39/34 40/35
37/34 37/34 37/34 40/35 41/36 42/37
FXLQ
FXNQ
1 phase, 220-240 V, 50 Hz
Sound level (Hi/Lo) dB (A)
50 Hz/60 Hz 220V
50 Hz 240V
Cooling capacity(*1)/(*2) 7,800/7,500
2,000/1,900
8,500
2,200
Btu/h
kcal/h
Heating capacity(*3)
kW
Btu/h
kcal/h
2.3/2.2
9,900/9,600
2,500/2,400
10,900
2,800
2.9/2.8
12,600/12,300
3,200/3,100
13,600
3,400
3.7/3.6
16,000/15,400
4,000/3,900
17,100
4,300
4.7/4.5
19,800/19,100
5,000/4,800
6.3
21,500
5,400
5.8/5.6
24,900/24,200
0.7/0.6RT 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0
6,300/6,100
8.0
27,300
0.7RT 0.9 1.1 1.4 1.8 2.3
6,900
7.3/7.1kW
2.5 3.2 4.0 5.0
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
INDOOR UNITS OUT DOOR UNIT S
SPECIFICATIONS
3433
C e ilin g s u s p e n d e d c a s s e t t e t y p e
Power supply 1 phase, 220-240 V, 50 Hz
Indoorunit m3/minAir flow rate (H/L)
Sound level (230 V)
Casing
dBAmmDimensions (HXWXD)kgMachine weight
40/35
Piping connectionsLiquidGas
Drain piping VP 20 (External Dia. 26/Internal Dia. 20)
25
White(10Y9/0.5)19/14
671/494cfm
165X895X895
9.5 (Flare)15.9 (Flare)
43/38
31
29/211,024/741
230X895X89544/39
31
32/231,130/812
230X895X895
mm
ModelIndoor unit
Connection unit BEVQ71MAVEFXUQ71MAV1
BEVQ100MAVEFXUQ100MAV1
BEVQ125MAVEFXUQ125MAV1
Note : Specifications are based on the following conditions ;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.)•Sound level : (FXUQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m below the unit center. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Connection unit series indoor units* A type of BEV unit is necessary for each Connection unit series indoor unit. Refer to the Engineering Data for details.* If indoor units from the Connection unit series are connected within a single refrigerant system to indoor units from any other series,
cooling/heating switchover will not be possible using the remote controller of the Connection unit series indoor units. However, if the remote controller of an indoor unit from the other series is set as a master remote controller, cooling/heating switchover will be possible.
* If all indoor units are from the Connection unit series, an outdoor unit Cool/Heat selector will be needed to enable cooling/heating switchover. * Group control between Connection Unit series equipment within one system is possible. However, group control with the other VRV II indoor
units is not possible.
Heat Pump TypeModel
Power supply
Heating capacity (*5)
Capacity control %
Motor output kWm3/min
Casing colorCompressor
Air flow ratemmDimensions (H x W x D)
1 phase, 230/240 V, 50 Hz
24 to 100
Hermetically sealed scroll type
1,345 x 900 x 320kgMachine weight 125
Liquid pipe mmPiping connections ø9.5 (Flare)Gas pipe mm ø19.1 (Brazing)
dB (A)Sound level (C/H) (*6)
kgRefrigerant chargeRefrigerant oil
53/55Refrigerant R410A
61,400
RXYMQ6PV4A
15,500
kW
18.0
Cooling capacity (*1)/(*2)
Cooling (*1)/(*2)Cooling (*3)/(*4)Heating (*5)Cooling (*1)/(*2)Cooling (*3)/(*4)Heating (*5)
Kcal / h
RT
Cooling capacity (*3)/(*4)
54,100/40,0004.5/3.3
4.4/3.3
5.1
4.67/4.384.59
3.29/2.673.32/2.62
3.92
4.82/4.39
52,900/39,100
Btu / h13,600/10,100
13,300/9,850
kW
Kcal / h
RTBtu / h
kW
Kcal / h
RTBtu / h
kW
15.8/11.7
15.5/11.5
4.0
1063.5
Ivory white (5Y7.5/1)
Refer to the name plate of the compressor.
Power consumption
COP
Note : 1. Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 46°CDB. (*3) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35°CDB. (*4) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 46°CDB.•Heating : (*5) Indoor temp. of 20°CDB, and outdoor temp. 7°CDB/6°CWB.•Sound level : (*6) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.• Refrigerant charge is required. (Chargeless piping length 0 m) Apply C1220T-1/2H for over ø19.1. Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
Conversion rates
kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3
kWKcal/h 7,100/6,900Btu/h 28,300/27,300
kWKcal/h
Heating capacity (Max.)(*3)
9.07,700
Btu/h 30,700
10,000/9,60039,600/38,200
12.510,80042,700
8.3/8.0 11.6/11.2 14.5/14.012,500/12,00049,500/47,800
RT 2.4/2.3 3.3/3.2 4.1/4.0
14.012,00047,800
RT 2.6 3.6 4.0
Cooling capacity(*1)/(*2)
OPTION LIST
INDOOR UNIT SINDOOR UNITS
3635
FXFQ25M FXFQ32M FXFQ40M FXFQ50M FXFQ63M FXFQ80M FXFQ100M FXFQ125M1
4
BYCP125D-W1
KAFP556D80 KAFP556D160KAFP557D80 KAFP557D160KAFP552H80 KAFP552H160KAFP553H80 KAFP553H160
KDT-55D160
KDP55D160
Filter related
5 Fresh air intake kit
Decoration Panel2 KDBH55D160WSealing Member of air discharge outlet3 KDBP55H160WAPanel spacer
High efficiency filter unit 65%High efficiency filter unit 90%Replacement high efficiency filter 65%Replacement high efficiency filter 90%Filter chamberLong life replacement filter Non-woven type
Chamber type Without T shape and fanWith T shape without fan
KDDFP55D160
Ultra long-life filterReplacement ultra long-life filter
Direct installation type
KAFJ551C160KAFP55D160KAFJ55K160HKDDP55D160
KDDP55D160KKDDJ55X160
No.
C e ilin g m o u n t e d s u p e r c a s s e t t e t y p e ( M u lt i f lo w t y p e )Type
Item
6 KDP55D80Branch duct chamber7 KKSJ55K160Chamber connection kit8 KDT-55D80Insulation kit for high humidity
C e ilin g m o u n t e d c a s s e t t e t y p e ( D o u b le f lo w t y p e )
No.
1
2
Decoration PanelHigh efficiency filter 65% 1 High efficiency filter 90% 1
Long life replacement filter
Filter related bottom suction
FXCQ20MFXCQ25MFXCQ32M
FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M
KAFJ532G36 KAFJ532G56 KAFJ532G160KAFJ532G80KAFJ533G36 KAFJ533G56 KAFJ533G160KAFJ533G80KDDFJ53G36Filter chamber KDDFJ53G56 KDDFJ53G160KDDFJ53G80KAFJ531G36 KAFJ531G56 KAFJ531G160KAFJ531G80
TypeItem
BYBC32G-W1 BYBC50G-W1 BYBC125G-W1BYBC63G-W1
Note: 1 Filter chamber is required if installing high efficiency filter.
C e ilin g m o u n t e d c a s s e t t e c o r n e r t y p eNo. Type
Item FXKQ25MA,FXKQ32MA,FXKQ40MA FXKQ63MA
1
2
BYK45FJW1 BYK71FJW1KPBJ52F56W KPBJ52F80WKAFJ521F56 KAFJ521F80
K-HV7AW K-HV9AWKDBJ52F56W KDBJ52F80WKFDJ52FA56 KFDJ52FA80
Panel related
Air inlet and air discharge outlet related
Decoration PanelPanel SpacerLong life replacement filterAir discharge grilleAir discharge blind panelFlexible duct (with shutter)
Note: 1 For without drain-up pump type only.
Note: 1 For without drain-up pump type only.
No. FXDQ20N, FXDQ25N, FXDQ32N, FXDQ40N, FXDQ50N FXDQ63N
1 KDT25N50 KDT25N63Insulation kit for high humidity
S lim c e ilin g m o u n t e d d u c t t y p e ( 9 0 0 / 1, 10 0 m m w id t h t y p e 1)Type
Item
No. FXDQ20P,FXDQ25P,FXDQ32P
1 KDT25N32Insulation kit for high humidity
S lim c e ilin g m o u n t e d d u c t t y p e ( 7 0 0 m m w id t h t y p e 1)Type
Item
No.
C e ilin g m o u n t e d d u c t t y p eFXMQ40MA FXMQ50MA FXMQ63MA FXMQ80MA FXMQ100MA FXMQ125MA
1 Drain pump kit
3 Filter chamber
KDU-30L125VE
2 High efficiency filterKAFP372A8065%
90%KAFP372A160
KAFP373A80 KAFP373A160KDDFP37A80 KDDFP37A160
4 Long life replacement filter KAFP371A80 KAFP371A160
TypeItem
C e ilin g s u s p e n d e d t y p eFXHQ32MA
1 Drain pump kit2 Replacement long-life filter (Resin net)
KDU50M60VEKAFJ501D56
3 L-type piping kit (for upward direction) KHFP5M35
FXHQ63MAKDU50M125VE
KAFJ501D80KHFP5M63
FXHQ100MA
KAFJ501D112
No. TypeItem
W a ll m o u n t e d t y p eFXAQ25MAFXAQ20MA
1 Drain pump kit K-KDU572CVE
FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MANo. TypeItem
F lo o r s t a n d in g t y p eFXLQ20MA
1 Long life replacement filter
FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MAKAFJ361K28 KAFJ361K45 KAFJ361K71
No. TypeItem
C o n c e a le d f lo o r s t a n d in g t y p eFXNQ20MA
1 Long life replacement filter
FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MAKAFJ361K28 KAFJ361K45 KAFJ361K71
No. TypeItem
C e ilin g s u s p e n d e d c a s s e t t e t y p eNo.
Replacement long-life filter12345
Sealing member of air discharge outlet (*1)
Decoration panel for air dischargeVertical flap kitL-shape piping kit
FXUQ71MAV1
KDBHJ49F80KDBTJ49F80KDGJ49F80
KHFP49M140
KDBHJ49F140KDBTJ49F140KDGJ49F140
FXUQ100MAV1 FXUQ125MAV1KAFJ495F140
(*1): This option is necessary for setting up 2-way (opposing directional) air flow when the air conditioner is installed.Note:
TypeItem
C e ilin g m o u n t e d b u ilt - in t y p eFXSQ20MFXSQ25MFXSQ32M
1 BYBS32DJW1KTBJ25K36W
FXSQ40MFXSQ50M
BYBS45DJW1KTBJ25K56W
FXSQ63M
BYBS71DJW1KTBJ25K80W
FXSQ80MFXSQ100M
BYBS125DJW1KTBJ25K160W
FXSQ125M
Panel related Decoration PanelAccess panel
3
KAFJ252L36KAFJ253L36
KAFJ252L56KAFJ253L56
KAFJ252L80KAFJ253L80
KAFJ252L160KAFJ253L160
Filter related
2 High efficiency filter 65% 2 High efficiency filter 90%
KAFJ251K36 KAFJ251K56 KAFJ251K80 KAFJ251K160KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160DKAJ25L36B KAJ25L56B KAJ25L80B KAJ25L160B
Long life replacement filter
KSA-25K36KBBJ25K36
KSA-25K56KBBJ25K56
KSA-25K80KBBJ25K80
KSA-25K160KBBJ25K160
Air suction canvasScreening door
KDJ2507K36 KDJ2507K56 KDJ2507K80 KDJ2507K160Air suction flangeKDAJ25K36 KDAJ25K56 KDAJ25K71 KDAJ25K140Air discharge adaptor
KNM25K32V1 KNM25K50V1 KNM25K63V1 KNM25K125V1
2 KEA25K32VE0.75
KEA25K50VE1.2
KEA25K63VE1.4
KEA25K100VE2.1
KEA25K125VE2.8
1 Auxiliary electric heater
4Air inlet and air discharge outlet related
5 Natural evaporating pan type humidifier 1 3
ModelCapacity
240V/220VkW
Filter chamber
For bottom suctionFor rear suction
No.Type
Item
Note: 1 One adaptor for wiring (KRP1B61) per indoor unit is required if installing an electric heater or a natural evaporating pan type humidifier. An electric heater cannot be used for VRV system cooling only.
2 If installing a high filter in the ceiling mounted built-in type, an assembly chamber for either bottom or rear suction is required. 3 For 50 Hz models only. A special order is required for 60 Hz models.
6 0 0 x 6 0 0 m u lt i f lo w c e ilin g m o u n t e d c a s s e t t e t y p eNo. FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M
1 Decoration panel2 Sealing member of air discharge outlet3 Panel spacer4 Replacement long-life filter
BYFQ60B7W1KDBHQ44B60KDBQ44B60KAFQ441B60
5 Fresh air intake kit Direct installation type KDDQ44X60
TypeItem
C ONT R OL S Y S T E MS
C ONTR OL S Y S TE MS
OUTDOOR UNITS
OPTION LIST
3837
O p e r a t io n c o n t r o l s y s t e m o p t io n a l a c c e s s o r ie s
Note: 1. Installation box is necessary for each adaptor marked .2. Up to 2 adaptors can be fixed for each installation box.3. Only one installation box can be installed for each indoor unit.
No.
34
FXCQ-M FXFQ-M FXKQ-MA FXSQ-MFXDQ-PFXDQ-N(A) FXAQ-MA FXLQ-MA
FXNQ-MA
Remote controllerWireless H/PWired
Simplified remote controller (Exposed type)
5 Adaptor for wiring6-1 Wiring adaptor for electrical appendices (1)6-2 Wiring adaptor for electrical appendices (2)
Remote controller for hotel use (Concealed type)
7 Remote sensor
9 External control adaptor for outdoor unit (Must be installed on indoor units)
TypeItem
BRC7C62 BRC7E61W BRC4C61 BRC4C62 BRC7E618
KRP1B59
DTA104A62
—Wired remote controller with weekly schedule timer
—
— KRCS01-1
KRP1B61 KRP2A62 KRP2A61 KRP4A53 KRP4A51
——
BRC4C62BRC4C62
KRP2A61KRP1B61BRC3A61BRC2C51
FXMQ-MA
BRC4C62
DTA104A61
8 Installation box for adaptor PCB Note 2,3KRP1D98 —Note 3
KRP1C93Note 2,3KRP4A93
Note 2,3KRP1B96
BRC2C51BRC3A61
KRP1B61KRP2A61KRP4A51
KRP2A62 KRP2A61 KRP4A52 KRP4A51 KRP4A51
—— Note 4,6KRP1B101
DTA104A61
FXUQ-MA
BRC7C528W
KRP2A62———
KRP1B97
KRP4A53
—DTA104A53DTA104A61 DTA104A61 DTA104A62DTA104A61
BRC1D61
FXZQ-M
BRC7E61W
KRP1B57
Note 4,6KRP1B101
FXHQ-MA
BRC7E63W
—KRP1B3KRP1B56KRP2A53KRP4A54
KRP1B61KRP2A61KRP4A51
2
1
KRCS01-1Note 5KRP4A91
4. Up to 2 installation boxes can be installed for each indoor unit.5. Installation box is necessary for second adaptor.6. Installation box is necessary for each adaptor.
BRC1C62
Wire fixture for preventing overturning
H e a t p u m p t y p eNo.
1 Cool/Heat Selector1-1 Fixing Box
2 REFNET Header
3 REFNET Joint
KJB111AKHRP26M22H (Max. 4 branch)KHRP26M33H (Max. 8 branch)
KHRP26M22T
KRC19-26A
RXYMQ6PV4A
5 Fixture for preventing overturning KPT-60B1606 K-KYZP15C
4 KKPJ5F180Central drain plug
S y s t e m c o n f ig u r a t io n
•Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one system.
Note 2,DCS302CA61Central remote controller1
•Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units (128 units). Can turn units ON/OFF twice per day.
Note 2DST301BA61Schedule timer3
•Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
Note 2DCS301BA61Unified ON/OFF controller2
KJB212AElectrical box with earth terminal (2 blocks)2-1
KEK26-1Noise filter (for electromagnetic interface use only)2-1
KJB311AElectrical box with earth terminal (3 blocks)1-1
DTA102A52Interface adaptor for SkyAir-series4
DTA107A555
DTA103A51Wiring adaptor for other air-conditioner6
No. Part name Model No. Function
•Up to 1024 units can be centrally controlled in 64 different groups.•Wiring restrictions (max. lengh : 1,000m, total wiring lengh : 2,000m, max. number of branches : 16) apply to each adaptor.
DTA109A51D -NETExpander Adaptor
7
•Fixing plate for DTA109A51KRP4A92Mounting plate7-1
•Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System.
* To use any of the above optional c ontrollers , an appropriate adaptor must be installed on the produc t unit to be c ontrolled.
For UAT(Y)-K(A),FD-K
For SkyAir, FD(Y)M-FA, FDY-KAFDYB-KA, FDY-KA, FVY(P)J-A
Central control adaptor kit
B u ild in g m a n a g e m e n t s y s t e m
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through LONWORKS® communication.DMS504B514
3
•Expansion kit, installed on DMS502A51, to provide 3 more DIII-NET communication ports. Not usable independently.DAM411A13-1
•Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to 4 units.DPF201A515
•Enables temperature measurement output for 4 groups; 0-5VDC.DPF201A526
•Enables temperature setting input for 16 groups; 0-5VDC.DPF201A537
No. Part name Model No. Function
*2 Interface for use in LONWORKS®
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through BACnet® communication.DMS502A51*1 Interface for use in BACnet®
Optional DIII board
Cont
act/a
nalog
signa
l
Parallel interfaceBasic unitTemperaturemeasurement unitsTemperaturesetting units
•Air conditioner management system that can be controlled by personal computers.DAM602B51
KJB411ADAM602B52
256 unitsDAM602B51x2512 unitsDAM602B51x3768 unitsDAM602B51x41024 unitsintelligent Manager III
128 units
2Number of units to be connected
HardwareBasic
•Expansion kit, installed on DMS502A51, to provide 16 more wattmeter pulse input points. Not usable independently.
•External temperature sensor for intelligent Manager.
DAM412A1
DAM101A51
Optional Di board
Optional DIII Ai unit2-4
•8 pairs based on a pair of On/Off input and abnormality input.DEC101A51Di unit2-5
3-2
1-11-4
1
Electrical box with earth terminal (4 blocks)
DCS601A521-1 •Additional 64 groups (10 outdoor units) is possible.
DCS004A511-3 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.•Wall embedded switch box.
DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.
Com
mun
icat
ion
line
Note : *1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS® is a registered trade mark of Echelon Corporation. *3. Installation box for adaptor must be procured on site.
DCS002C511-2intelligent Touch Controller
DIII-NET plus adaptor
Web
intelligent Touch Controller
P. P. D.HardwareHardware
Software
Basic
Option •P. P. D.: Power Proportional Distribution function
•4 pairs based on a pair of On/Off input and abnormality input.DEC102A51Dio unit2-6
2-1
2-2
2-3
•Power Proportional Distribution functionDAM002A51
Option Software
2-1
•Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.DAM004A512-2
•ECO (Energy saving functions.)DAM003A51
P.P.D.
Web
Eco2-3
•Interface between the central monitoring board and central control units.DCS302A528 Unification adaptor forcomputerized control
Notes: 1. Installation box for adaptor must be procured on site. 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary.