pdc chapter 8

Upload: satya-sagar

Post on 09-Jan-2016

223 views

Category:

Documents


0 download

DESCRIPTION

FEED BACK CONTROLERS

TRANSCRIPT

  • Chapter 8Feedback Controllers

  • Chapter 8

  • Error Signal

  • Proportional Control

  • Chapter 8

  • Reverse or Direct Acting ControllerDirect-Acting (Kc < 0): output increases as input increases"Reverse-Acting (Kc > 0): output increases as input decreases"

  • Chapter 8

  • Proportional Band (PB)PB is the error (% of the range of controlled variable) required to move the output from its lowest to its highest value.

  • Example 2: Flow Control LoopAssume FT is direct-acting.

    1.) Air-to-open (fail close) valve ==> ?2.) Air-to-close (fail open) valve ==> ?

    Consequences of wrong controller action??Chapter 8

  • Chapter 9

  • Example 3: Liquid Level Control Control valves are air-to-open Level transmitters are direct actingChapter 8Question: Type of controller action?

  • Chapter 8INTEGRAL CONTROL ACTION

  • Proportional-Integral (PI) Controller

  • Reset TimeReset time is the time that the integral mode repeats the action of proportional mode.

  • Example: Heat Exchanger Control Loop

  • Reset Windup

  • Reset Windup

  • Anticipatory or Derivative Control Action

  • Proportional-Integral-Derivative (PID) Control

    Now we consider the combination of the proportional, integral, and derivative control modes as a PID controller.Many variations of PID control are used in practice (see Table 8.1, page 194)Next, we consider the three most common forms.

  • Parallel Form of PID Control

  • Effects of Anticipatory (Derivative) Control Action

  • Drawbacks of Anticipatory (Derivative) Control Action

  • Chapter 8

    _973067743.doc

  • Parallel-Form PID Controller with Derivative Filter

  • Derivative and Proportional KicksOne disadvantage of the previous PID controllers is that a sudden change in set point (and hence the error, e) will cause the derivative term momentarily to become very large and thus provide a derivative kick to the final control element.

  • Elimination of Derivative and Proportional Kicks in Parallel-Form Controllers

  • Series Form of PID Control

  • Elimination of Derivative Kick in Series-Form Controllers

  • Expanded (Non-interacting) Form of PID Control

  • Chapter 8

  • Typical Response of Feedback Control SystemsConsider response of a controlled system after a sustained disturbance occurs (e.g., step change in disturbance variable)Chapter 8

  • Chapter 8

  • Chapter 8

  • Automatic and Manual Control Modes Automatic Mode Controller output, p(t), depends on e(t), controller constants, and type of controller used. ( PI vs. PID etc.) Manual Mode Controller output, p(t), is adjusted manually. Manual Mode is very useful when unusual conditions exist:plant start-upplant shut-downemergencies Percentage of controllers "on manual ?? (30% in 2001, Honeywell survey)Chapter 8

  • Digital PID Controller

    where,

    = the sampling period (the time between successive samples of the controlled variable)= controller output at the nth sampling instant, n=1,2,= error at the nth sampling unit

    velocity form - see Equation (8-19)(pd)- incremental changeChapter 8

  • PID-Most complicated to tune (Kc, I, D) .-Better performance than PI-No offset-Derivative action may be affected by noisePI-More complicated to tune (Kc, I) .-Better performance than P-No offset-Most popular FB controllerP-Simplest controller to tune (Kc).-Offset with sustained disturbance or set point change.Controller ComparisonChapter 8

  • Summary of the Characteristics of the Most Commonly Used Controller Modes1. Two Position:Inexpensive.Extremely simple.2. Proportional:Simple.Inherently stable when properly tuned.Easy to tune.Experiences offset at steady state.3. Proportional plus integral:No offset.Better dynamic response than reset alone.Possibilities exist for instability due to lag introduced.Chapter 8

  • 4. Proportional plus derivative:Stable.Less offset than proportional alone (use of higher gain possible).Reduces lags, i.e., more rapid response.5. Proportional plus reset plus rate:Most complexRapid responseNo offset.Difficult to tune.Best control if properly tuned.Chapter 8

  • On-off Controllers Simple Cheap Used In residential heating and domestic refrigerators Limited use in process control due to continuous cycling of controlled variable excessive wear on control valve.

    Example 1: Temperature control of jacketed vessel.

    Chapter 8

  • On-Off ControllersSynonyms:two-position or bang-bang controllers.Controller output has two possible values.Chapter 8

  • Practical case (dead band)Chapter 8