pe7214/pe7216/pe7324/pe7328 · 4 description: 100-240v 16a 0u 14-outlet pdu function: 14-outlet...

17
As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7214 / PE7216 / PE7324 /PE7328 eco PDUs are intelligent PDUs that contain 14, 16, 24, or 28 AC outlets and are available in various IEC socket configurations. NRGence eco PDUs provide secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center's health environment via sensors. NRGence eco PDUs offer remote power control combined with real-time power measurement – allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device, bank, or outlet level, depending on the model, from practically any location via a TCP/IP connection. NRGence eco PDU supports any 3rd party V3 SNMP Manager Software and NRGence eco Sensors (eco PDU Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it. With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible. 1 ECO PDU PE7214/PE7216/PE7324/PE7328

Upload: others

Post on 04-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco

PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7214 / PE7216 / PE7324

/PE7328 eco PDUs are intelligent PDUs that contain 14, 16, 24, or 28 AC outlets and are available in various IEC

socket configurations.

NRGence eco PDUs provide secure, centralized, intelligent, power management (power on, off, cycle) of data

center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well

as the ability to monitor the center's health environment via sensors.

NRGence eco PDUs offer remote power control combined with real-time power measurement – allowing you to

control and monitor the power status of devices attached to the PDUs, either at the PDU device, bank, or outlet

level, depending on the model, from practically any location via a TCP/IP connection.

NRGence eco PDU supports any 3rd party V3 SNMP Manager Software and NRGence eco Sensors (eco PDU

Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an

intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power

status of the equipment connected to it.

With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable,

and most cost effective way to remotely manage power access for multiple computer installations and allocate

power resources in the most efficient way possible.

1

ECO PDUPE7214/PE7216/PE7324/PE7328

Page 2: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

2

Connections•Support10/100MbitEthernetInterface

•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity,IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring

•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensors forracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

Description: 100-240V20A0U14-OutletPDUFunction: 14-OutletMetering,

0-OutletSwitchingControl&1-BankMetering

InputPowerPlug: NEMA6-20P

PowerCapacity: 4.2kW

SocketConfiguration:

IEC60320C19(2)

IEC60320C13(12)

Features

ECO PDUPE7214B

Page 3: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

3

Optional AccessoriesEnvironment Sensors

PartNo. Sensor

EA1140 Temperature

EA1240 Temperature/Humidity

EA1340 DifferentialPressure/Temperature

Cable Holders

PartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door Sensors

PartNo. Sensor

EA1440 PhotoDoorSensor

EA1441 InductiveProximityDoorSensor

EA1442 ReedDoorSensor

• Lok-U-PlugInstallation

Model PE7214BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 20AMax;16A(ULde-rated)InputFrequency 50-60HzInputConnection 1xNEMA6-20PInputPower 4160VA(Max)3328VA(ULde-rated)

OutletTypeTotal:12xIEC320C13+2xIEC320C19Bank1:Outlet1–14;12xC13+2xC19

NominalOutputVoltage 100–240VAC

MaximumOutputCurrent(Outlet)

C13:15A(Max)12A(ULde-rated)C19:20A(Max)16A(ULde-rated)

MaximumOutputCurrent(Bank) 20A(Max)16A(ULde-rated)

MaximumOutputCurrent(Total) 20A(Max)16A(ULde-rated)

Breakers 1x20ANon-Fusebreaker

Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort 4

MeteringAccuracy

VoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%

MechanicalDimension(HxWxD) 91x6.6x4.4cmShippingDimensions(HxWxD)

100x19x17cm

Weight/ShippingWeight 2.7/3.8kg

PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C

Humidity(Operating&Storage)

0–80%RH,Non-Condensing

ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification ByRequest

PackageContents1. PE7214B2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord

Specifications

RackMountKit

2X-018G

SidePanelMountKit(2X-018G)

Mounting Kit

Page 4: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

4

Description: 100-240V16A0U14-OutletPDUFunction: 14-OutletMetering,

0-OutletSwitchingControl&1-BankMetering

InputPowerPlug: IEC60320C20

PowerCapacity: 3.7kW

SocketConfiguration:

IEC60320C19(2)

IEC60320C13(12)

FeaturesConnections•Support10/100MbitEthernetInterface

•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity,IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring

•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensors forracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

ECO PDUPE7214G

Page 5: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

5

Optional AccessoriesEnvironment Sensors

PartNo. Sensor

EA1140 Temperature

EA1240 Temperature/Humidity

EA1340 DifferentialPressure/Temperature

Cable Holders

PartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door Sensors

PartNo. Sensor

EA1440 PhotoDoorSensor

EA1441 InductiveProximityDoorSensor

EA1442 ReedDoorSensor

• Lok-U-PlugInstallation

Model PE7214GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 16AMaxInputFrequency 50-60HzInputConnection 1xIEC60320C20InputPower 3680VA(Max)

OutletTypeTotal:12xIEC320C13+2xIEC320C19Bank1:Outlet1–14;12xC13+2xC19

NominalOutputVoltage 100–240VAC

MaximumOutputCurrent(Outlet)

C13:10A(Max)C19:16A(Max)

MaximumOutputCurrent(Bank) 16A(Max)

MaximumOutputCurrent(Total) 16A(Max)

Breakers 1x16ANon-Fusebreaker

Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort 4

MeteringAccuracy

VoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%

MechanicalDimension(HxWxD) 91x6.6x4.4cmShippingDimensions(HxWxD)

100x19x17cm

Weight/ShippingWeight 2.7/3.8kg

PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to40˚C/-20to60˚C

Humidity(Operating&Storage)

0–80%RH,Non-Condensing

ComplianceEMCVerification CE,OthersbyRequestSafetyVerification CE-LVD,OthersbyRequest

PackageContents1. PE7214G2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord

Specifications

RackMountKit

2X-018G

SidePanelMountKit(2X-018G)

Mounting Kit

Page 6: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

Connections•Support10/100MbitEthernetInterface

•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring

•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

Description: 100-240V20A0U16-OutletPDUFunction: 16-OutletMetering,

0-OutletSwitchingControl&1-BankMetering

InputPowerPlug: NEMA6-20P

PowerCapacity: 4.2kW

SocketConfiguration:

IEC60320C19(2)

IEC60320C13(14)

Features

6

ECO PDUPE7216B

Page 7: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

• Lok-U-PlugInstallation

Model PE7216BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 20AMax;16A(ULde-rated)InputFrequency 50-60HzInputConnection 1xNEMA6-20PInputPower 4160VA(Max)3328VA(ULde-rated)

OutletTypeTotal:14xIEC320C13+2xIEC320C19Ban1-1:Outlet1–8;7xC13+1xC19Bank1-2:Outlet9–16;7xC13+1xC19

NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)

C13:15A(Max)12A(ULde-rated)C19:20A(Max)16A(ULde-rated)

MaximumOutputCurrent(Bank) 20A(Max)16A(ULde-rated)

MaximumOutputCurrent(Total) 20A(Max)16A(ULde-rated)

Breakers 1x20ANon-Fusebreaker

Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort 4

MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%

MechanicalDimension(HxWxD) 132.5x6.6x4.4cmShippingDimensions(HxWxD)

142x16x17cm

Weight/ShippingWeight 3.7/7.7kg

PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C

Humidity(Operating&Storage)

0–80%RH,Non-Condensing

ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification TUV-CB,OthersbyRequest

PackageContents1. PE7216B2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord

7

Optional AccessoriesSpecifications

Environment Sensors

PartNo. Sensor

EA1140 Temperature

EA1240 Temperature/Humidity

EA1340 DifferentialPressure/Temperature

Cable Holders

PartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door Sensors

PartNo. Sensor

EA1440 PhotoDoorSensor

EA1441 InductiveProximityDoorSensor

EA1442 ReedDoorSensor

RackMountKit

2X-018G

SidePanelMountKit(2X-018G)

Mounting Kit

Page 8: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

Connections•Support10/100MbitEthernetInterface

•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring

•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

Description: 100-240V16A0U16-OutletPDUFunction: 16-OutletMetering,

0-Outlet Switching Control &1-BankMetering

InputPowerPlug: IEC60320C20

PowerCapacity: 3.7kW

SocketConfiguration:

IEC60320C19(2)

IEC60320C13(14)

Features

8

ECO PDUPE7216G

Page 9: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

• Lok-U-PlugInstallation

Model PE7216GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 16AMaxInputFrequency 50-60HzInputConnection 1xIEC60320C20InputPower 3680VA(Max)

OutletTypeTotal:14xIEC320C13+2xIEC320C19Bank1-1:Outlet1–8;7xC13+1xC19Bank1-2:Outlet9–16;7xC13+1xC19

NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)

C13:10A(Max)C19:16A(Max),TUVDe-rated15A(Max)

MaximumOutputCurrent(Bank) 16A(Max),TUVDe-rated15A(Max)

MaximumOutputCurrent(Total) 16A(Max).TUVDe-rated15A(Max)

Breakers 1x16ANon-Fusebreaker

Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort 4

MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%

MechanicalDimension(HxWxD) 132.5x6.6x4.4cmShippingDimensions(HxWxD)

142x16x17cm

Weight/ShippingWeight 3.7/7.7kg

PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to40˚C/-20to60˚C

Humidity(Operating&Storage)

0–80%RH,Non-Condensing

ComplianceEMCVerification CE,OthersbyRequestSafetyVerification TUV-CB,CE-LVD,OthersbyRequest

PackageContents1. PE7216G2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord

9

Optional AccessoriesSpecificationsEnvironment Sensors

PartNo. Sensor

EA1140 Temperature

EA1240 Temperature/Humidity

EA1340 DifferentialPressure/Temperature

Cable Holders

PartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door Sensors

PartNo. Sensor

EA1440 PhotoDoorSensor

EA1441 InductiveProximityDoorSensor

EA1442 ReedDoorSensor

RackMountKit

2X-018G

SidePanelMountKit(2X-018G)

Mounting Kit

Page 10: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

Connections•Support10/100MbitEthernetInterface

•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring

•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

Description: 100-240V30A0U24-OutletPDUFunction: 24-OutletMetering,

0-Outlet Switching Control &2-BankMetering

InputPowerPlug: NEMAL6-30P

PowerCapacity: 6.2kW

SocketConfiguration:

IEC60320C19(3)

IEC60320C13(21)

Features

10

ECO PDUPE7324B

Page 11: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

Model PE7324BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 30AMax;24A(ULde-rated)InputFrequency 50-60HzInputConnection NEMAL6-30PInputPower 6240VA(Max)4992VA(ULde-rated)

OutletType

Total:21xIEC320C13+3xIEC320C19Bank1-1:Outlet1–8;7xC13+1xC19Bank1-2:Outlet9–16;7xC13+1xC19Bank2:Outlet17–24;7xC13+1xC19

NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)

C13:15A(Max)12A(ULde-rated)C19:15A(Max)12A(ULde-rated)

MaximumOutputCurrent(Bank) 15A(Max)12A(ULde-rated)

MaximumOutputCurrent(Total) 30A(Max)24A(ULde-rated)

Breakers 2x16AUL489Breaker

Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort 4

MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%

MechanicalDimension(HxWxD) 177.5x6.6x4.4cmShippingDimensions(HxWxD)

189x21x17cm

Weight/ShippingWeight 6.5/10.5kg

PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C

Humidity(Operating&Storage)

0–80%RH,Non-Condensing

ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification TUV-CB,OthersbyRequest

PackageContents1. PE7324B2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)

11

Optional AccessoriesSpecificationsEnvironment Sensors

PartNo. SensorEA1140 TemperatureEA1240 Temperature/HumidityEA1340 DifferentialPressure/Temperature

Cable HoldersPartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door SensorsPartNo. Sensor

EA1440 PhotoDoorSensorEA1441 InductiveProximityDoorSensorEA1442 ReedDoorSensor

• Lok-U-PlugInstallation

• Side Mount Installation

• Side Panel Double Mount Installation

• Button Mount Installation

SlideRailKit(2X-016G)

SidePanelDoubleMountKit(2X-019G)

ButtonMountKit(2X-017G)

SidePanelMountKit(2X-018G)

Mounting Kit

2X-018G

RackMountKit

Page 12: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

Connections•Support10/100MbitEthernetInterface

•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring

•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

Description: 100-240V32A0U24-OutletPDUFunction: 24-OutletMetering,

0-OutletSwitchControl&2-BankMetering

InputPowerPlug: IEC6030932A

PowerCapacity: 7.4kW

SocketConfiguration:

IEC60320C19(3)

IEC60320C13(21)

Features

12

ECO PDUPE7324G

Page 13: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

• Lok-U-PlugInstallation

Model PE7324GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent

32AMax

InputFrequency 50-60HzInputConnection IEC6030932AInputPower 7360VA(Max)

OutletType

Total:21xIEC320C13+3xIEC320C19

Bank1-1:Outlet1–8;7xC13+1xC19

Bank1-2:Outlet9–16;7xC13+1xC19

Bank2:Outlet17–24;7xC13+1xC19NominalOutputVoltage

100–240VAC

MaximumOutputCurrent(Outlet)

C13:10A(Max)

C19:16A(Max),TUVDe-rated15A(Max)MaximumOutputCurrent(Bank)

16A(Max),TUVDe-rated15A(Max)

MaximumOutputCurrent(Total)

32A(Max),TUVDe-rated30A(Max)

Breakers 2x16AUL489Breaker

MeteringPerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort

4

MeteringAccuracy

VoltageRange:100VAC~250VAC+/-1%

PowerRange:100W~5000W+/-2%

CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%MechanicalDimension(HxWxD) 177.5x6.6x4.4cmShippingDimensions

(HxWxD)189x21x17cm

Weight/ShippingWeight

6.2/10.2kg

PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage)

0to40˚C/-20to60˚C

Humidity

(Operating&Storage)0–80%RH,Non-Condensing

ComplianceEMCVerification CE,OthersbyRequestSafetyVerification TUV-CB,CE-LVD,OthersbyRequest

PackageContents1. PE7324G2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)

13

Optional AccessoriesSpecifications

Environment SensorsPartNo. Sensor

EA1140 TemperatureEA1240 Temperature/HumidityEA1340 DifferentialPressure/Temperature

Cable HoldersPartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door SensorsPartNo. Sensor

EA1440 PhotoDoorSensorEA1441 InductiveProximityDoorSensorEA1442 ReedDoorSensor

• Side Mount Installation

• Side Panel Double Mount Installation

• Button Mount Installation

SlideRailKit(2X-016G)

SidePanelDoubleMountKit(2X-019G)

ButtonMountKit(2X-017G)

SidePanelMountKit(2X-018G)

Mounting Kit

2X-018G

RackMountKit

Page 14: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

Connections•Support10/100MbitEthernetInterface•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

Description: 100-240V30A0U28-OutletPDUFunction: 28-OutletMetering,

0-Outlet Switching Control &2-BankMetering

InputPowerPlug: NEMAL6-30P

PowerCapacity: 6.2kW

SocketConfiguration:

IEC60320C19(4)

IEC60320C13(24)

Features

14

ECO PDUPE7328B

Page 15: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

• Lok-U-PlugInstallation

Optional Accessories

Model PE7328BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 30AMax;24A(ULde-rated)InputFrequency 50-60HzInputConnection NEMAL6-30PInputPower 6240VA(Max)4992VA(ULde-rated)

OutletTypeTotal:24xIEC320C13+4xIEC320C19Bank1:Outlet1–14;12xC13+2xC19Bank2:Outlet15–28;12xC13+2xC19

NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)

C13:15A(Max)12A(ULde-rated)C19:15A(Max)12A(ULde-rated)

MaximumOutputCurrent(Bank) 15A(Max)12A(ULde-rated)

MaximumOutputCurrent(Total) 30A(Max)24A(ULde-rated)

Breakers 2x16AUL489Breaker

Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort 4

MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%

MechanicalDimension(HxWxD) 135.9x6.6x4.4cmShippingDimensions(HxWxD)

142x16x17cm

Weight/ShippingWeight 4.1/7.9kg

PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C

Humidity(Operating&Storage) 0–80%RH,Non-Condensing

ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification TUV-CB,OthersbyRequest

PackageContents1. PE7328BPDU2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)

Specifications

15

Environment Sensors

PartNo. Sensor

EA1140 Temperature

EA1240 Temperature/Humidity

EA1340 DifferentialPressure/Temperature

Cable Holders

PartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door Sensors

PartNo. Sensor

EA1440 PhotoDoorSensor

EA1441 InductiveProximityDoorSensor

EA1442 ReedDoorSensor

SidePanelDoubleMountKit(2X-019G)

SidePanelMountKit(2X-018G)

• Side Mount Installation

2X-018G

Mounting Kit

RackMountKit

• Side Panel Double Mount Installation

Page 16: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

Connections•Support10/100MbitEthernetInterface

•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet

•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS

•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)

Metering•PDUandoutletlevelpowermeteringandmonitoring

•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring

•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting

•Supportdoorsensor

OutletSwitchControl•AlwaysOn

Description: 100-240V32A0U28-OutletPDUFunction: 28-OutletMetering,

0-OutletSwitchControl&2-BankMetering

InputPowerPlug: IEC6030932A

PowerCapacity: 7.4kW

SocketConfiguration:

IEC60320C19(4)

IEC60320C13(24)

Features

16

ECO PDUPE7328G

Page 17: PE7214/PE7216/PE7324/PE7328 · 4 Description: 100-240V 16A 0U 14-Outlet PDU Function: 14-Outlet Metering, 0-Outlet Switching Control & 1-Bank Metering Input Power Plug: IEC 60320

• Lok-U-PlugInstallation

Optional Accessories

Model PE7328GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 32AMaxInputFrequency 50-60HzInputConnection IEC6030932AInputPower 7360VA(Max)

OutletTypeTotal:24xIEC320C13+4xIEC320C19Bank1:Outlet1–14;12xC13+2xC19Bank2:Outlet15–28;12xC13+2xC19

NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)

C13:10A(Max)C19:16A(Max),TUVDe-rated15A(Max)

MaximumOutputCurrent(Bank) 16A(Max)

MaximumOutputCurrent(Total) 32A(Max)

Breakers 2x16AUL489Breaker

Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring

OutletSwitch NoneEnvironmentSensorPort 4

MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%

MechanicalDimension(HxWxD) 135.9x6.6x4.4cmShippingDimensions(HxWxD)

142x16x17cm

Weight/ShippingWeight 4.1/7.9kg

PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage) 0to40˚C/-20to60˚C

Humidity(Operating&Storage)

0–80%RH,Non-Condensing

ComplianceEMCVerification CE,OthersbyRequestSafetyVerification TUV-CB,CE-LVD,OthersbyRequest

PackageContents1. PE7328GPDU2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)

Specifications

ATEN International Co., Ltd. 3F., No.125, Sec. 2, Datong Rd., Sijhih District., New Taipei City 221, TaiwanPhone: 886-2-8692-6789 Fax: 886-2-8692-6767 www.aten.com E-mail: [email protected]

© Copyright 2017 ATEN® International Co., Ltd.ATEN and the ATEN logo are trademarks of ATEN International Co., Ltd. All rights reserved. All other trademarks are the property of their respective owners.

17

Environment SensorsPartNo. Sensor

EA1140 TemperatureEA1240 Temperature/Humidity

EA1340 DifferentialPressure/Temperature

Cable HoldersPartNo. Description

2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!

2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)

Door SensorsPartNo. Sensor

EA1440 PhotoDoorSensor

EA1441 InductiveProximityDoorSensor

EA1442 ReedDoorSensor

SidePanelDoubleMountKit(2X-019G)

SidePanelMountKit(2X-018G)

• Side Mount Installation

2X-018G

Mounting Kit

RackMountKit

• Side Panel Double Mount Installation

Publish Date: 04/2017 V4.0