peer 2 peer presentation (sep 2001)
TRANSCRIPT
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
1/31
Vega
Peer to Peer Networking
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
2/31
Vega -
Peer to Peer Networking
Applications
High rise buildings
Multi-building complex
Multi-loop applications
Conventional system upgrade to analogue
addressable.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
3/31
Vega -
Peer to Peer Networking
Benefits
Reduced installation costs
Distributed intelligence
Remote indication & control
Distributed risk complete with autonomous
operation.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
4/31
Vega -
Peer to Peer Networking
48
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
5/31
Vega -
Peer to Peer Networking
Shared zone/plant principle - Zone/plant to group
programming across network
System configuration from 2 to 48 panels
Support for Vega options: repeaters & motherboards
Up to 2km between nodes.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
6/31
Vega -
Peer to Peer Networking
Zone to group programming across the network
Latching & non-latching alarms
512 event log entries local & network
Zone isolations across network.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
7/31
Vega -
Peer to Peer Networking
Network information:
RS 422 communications
Twin twisted pair cable
Up to 2km between nodes
Reliable & proven communications.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
8/31
Vega -
Peer to Peer Networking
System configuration via Viper or via the Membrane
Selectable options for unique configurations per system
Selectable options for priority level transmit & receive.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
9/31
Vega -
Peer to Peer Networking
Configuration options:
Number Attached Panels
Selectable in Viper, each panel must be programmed
with the correct number of network panels
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
10/31
Vega -
Peer to Peer Networking
Configuration options:
Display & Broadcast Alarms
If set to No, the panel will inhibit the transmission &
receipt of all network alarms.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
11/31
Vega - Peer to Peer Networking
Configuration options:
Global Evacuate
If set to Yes, the panel will transmit locally generated
evacuate signals & receive evacuate signals from the
network.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
12/31
Vega - Peer to Peer Networking
Configuration options:
Act on T1 / T2
If set to Yes, the panel will shall respond to any network
timer acknowledge signals.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
13/31
Vega -
Peer to Peer Networking
Configuration options:
Global Silence / Reset
If set to Yes, the panel will transmit & receive all silence
& reset commands.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
14/31
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
15/31
Vega -
Peer to Peer Networking
Configuration Options:
Panel of origin S/R override
Selection of this option allows a network panel to silence
and reset the panel of origin.
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
16/31
Vega -
Peer to Peer Networking
Priority Text Tx Rx
0 Evac Y Y
1 Fire Y Y
2 Alert N N
3 Pre-alarm N N4 Fault N N
Transmit / Receive Options
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
17/31
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
18/31
Vega -
Peer to Peer Networking
Connection DetailsPanel 01 Panel 02 Panel 02 Panel 03
Talk out (+) (+) Listen in Listen out (+) (+) Listen in
Talk out (-) (-) Listen in Listen out (-) (-) Listen in
Listen in (+) (+) Talk out Talk in (+) (+) Talk out
Listen in (-) (-) Talk out Talk in (-) (-) Talk out
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
19/31
Vega Peer to Peer
Panel of Origin
FIRE
Total 01
Access Level 1
1st Z001 Ground Floor East Wing
Operate to list devices
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
20/31
Vega Peer to Peer
Network Panel
FIRE
Total 01
Access Level 1
1st Z001 Ground Floor East Wing
Operate to list devices
NetworkEvent
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
21/31
Vega Peer to Peer
Network Panel
FIRE
Total 01
1st Z001 Ground Floor East Wing
Dev 01:001.1 Outside room 101
Panel 01 Accommodation on block #1
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
22/31
Vega Peer to Peer
Panel of Origin
FIRE
Total 01
1st Z001 Ground Floor East Wing
Break glass outside room 101
Loop 01 Dev 001.1 Zone 001 tot 001/001
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
23/31
Vega Peer to Peer
Panel of Origin
EVACUATE Access level 3
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
24/31
Vega Peer to Peer
Network Panel
REMOTE EVACUATE Access level 1
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
25/31
Vega Peer to Peer
Panel of Origin
FAULT
Total 01
Zone Z001 Ground Floor East Wing
Optical Room G121 Switch room 02
Loop 01 Dev 008.1 Zone 001 tot 001/001
Access level 1
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
26/31
Vega Peer to Peer
Network Panel
FAULT
Total 01
Zone Z001 Ground Floor East Wing
Device 01:998.1 Room G121 Switch room 02
Panel 01 Accommodation block #1
Access level 1
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
27/31
Vega Peer to Peer
Event Log - Network Event
Access level 3 List event log
Event 007 Network event
Fire Priority 1
Panel 01 Accommodation block #1
Zone 001 Ground floor east wing
Device 01:001.1 Room G121 Switch room
11:38am Monday 14 Aug 2000
to scroll, + to quit
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
28/31
Vega Peer to Peer
Event Log - Local Event
Access level 3 List event log
Event 003 Network event
Fire Priority 1
Zone 003 Second floor east wing
D001.1 Loop 01
Break glass Central staircase
11:39am Monday 14 Aug 2000
to scroll, + to quit
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
29/31
Vega Peer to Peer - Example #1
SPECIFICATION
1. Panel 3 manual evacuate sounders constant, panels 2 & 4 sounders pulsed
panels 1 & 5 silent
2. Silence alarms & reset from panel 4
3. Fault on panel 5 signalled locally & to panel 1 only
4. Pre-alarm on panel 4 signalled locally & to panel 1 only
5. Pre-alarm on panel 3 signalled locally & to panel 1 only.
1 2 3 4 5
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
30/31
Vega Peer to Peer - Example #2
SPECIFICATION
1. Panel of origin sounders constant network panels pulsed with 2 min
timer to evacuate
2. Output to operate in each panel to shutdown the air conditioning
3. Network panels to have ability to silence own sounders only.
1 2 3
-
8/12/2019 Peer 2 Peer Presentation (Sep 2001)
31/31
Vega Peer to Peer - Example #3
SPECIFICATION
1. Alarm On Panel 3 T1, 60s T2 180s, after ex area of T2 panel 3 sounders evacuate
panels 2 & 4 sounders pulse for 180s & panels 1 & 5 silent
2. After 180s panels 2 & 4 evacuate & panels 1 & 5 pulse for 180s
then evacuate.
1 2 3 4 5