AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Models PEFY-P20VMA(L)-E, PEFY-P25VMA(L)-E, PEFY-P32VMA(L)-E, PEFY-P40VMA(L)-E, PEFY-P50VMA(L)-E, PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E PEFY-P80VMA(L)-E PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E 2012

Upload: others

Post on 05-Feb-2021

7 views

Category:

Documents


0 download

TRANSCRIPT

  • AIR CONDITIONERS

    TECHNICAL & SERVICE MANUALModels PEFY-P20VMA(L)-E,

    PEFY-P25VMA(L)-E,PEFY-P32VMA(L)-E,PEFY-P40VMA(L)-E,PEFY-P50VMA(L)-E,PEFY-P63VMA(L)-E

    PEFY-P71VMA(L)-EPEFY-P80VMA(L)-EPEFY-P100VMA(L)-EPEFY-P125VMA(L)-EPEFY-P140VMA(L)-E

    2012

    http://planetaklimata.com.ua/http://planetaklimata.com.ua/

  • ii

    HWE0812B GB

    Safety PrecautionsRead before installation and performing electrical work

    Symbol explanations

    Thoroughly read the following safety precautions prior to installation.Observe these safety precautions for your safety.This equipment may have adverse effects on the equipment on the same power supply system.Contact the local power authority before connecting to the system.

    WARNINGThis symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.

    CAUTIONThis symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-age to the unit.

    Indicates an action that must be avoided.

    Indicates important instructions.

    Indicates a parts that requires grounding.

    Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.)

    Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main unit label.)

    WARNINGCarefully read the labels affixed to the main unit.

    WARNING

    Ask your dealer or a qualified technician to install the unit.

    Improper installation by the user may result in water leak-age, electric shock, or fire.

    Properly install the unit on a surface that can withstand its weight.

    Unit installed on an unstable surface may fall and cause in-jury.

    Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the cable.

    Improperly connected cables may produce heat and start a fire.

    Take appropriate safety measures against wind gusts and earthquakes to prevent the unit from toppling over.

    Improper installation may cause the unit to topple over and cause injury or damage to the unit.

    Only use accessories (i.e., air cleaners, humidifiers, electric heaters) recommended by Mitsubishi Electric.

    Do not make any modifications or alterations to the unit. Consult your dealer for repair.

    Improper repair may result in water leakage, electric shock, or fire.

    Do not touch the heat exchanger fins with bare hands.

    The fins are sharp and pose a risk of cuts.

    In the event of a refrigerant leak, thoroughly ventilate the room.

    If gaseous refrigerant leaks out and comes in contact with an open flame, toxic gases will be generated.

    Properly install the unit according to the instructions in the Installation Manual.

    Improper installation may result in water leakage, electric shock, or fire.

    Have all electrical work performed by an authorized electri-cian according to the local regulations and the instructions in this manual. Use a dedicated circuit.

    Insufficient power supply capacity or improper installation of the unit may result in malfunctions of the unit, electric shock, or fire.

    0000001526.book i ページ 2012年9月13日 木曜日 午後7時14分

    http://planetaklimata.com.ua/katalog-proizvoditeli/Mitsubishi-Electric/

  • iiHWE0812B GB

    Precautions for handling units for use with R410A

    WARNING

    Keep electrical parts away from water.

    Wet electrical parts pose a risk of electric shock, smoke, or fire.

    Securely attach the control box cover.

    If the cover is not installed properly, dust or water may infil-trate and pose a risk of electric shock, smoke, or fire.

    Only use the type of refrigerant that is indicated on the unit when installing or relocating the unit.

    Infiltration of any other types of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.

    When installing the unit in a small space, take appropriate precautions to prevent leaked refrigerant from reaching the limiting concentration.

    Leaked refrigerant gas will displace oxygen and may cause oxygen starvation. Consult your dealer before installing the unit.

    Consult your dealer or a qualified technician when moving or reinstalling the unit.

    Improper installation may result in water leakage, electric shock, or fire.

    After completing the service work, check for a refrigerant leak.

    If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, toxic gases will be gener-ated.

    Do not try to defeat the safety features of the unit.

    Forced operation of the pressure switch or the temperature switch by defeating the safety features for these devices, or the use of accessories other than the ones that are recom-mended by Mitsubishi Electric may result in smoke, fire, or explosion.

    Consult your dealer for proper disposal method.

    Do not use a leak detection additive.

    CAUTION

    Do not use the existing refrigerant piping.

    A large amount of chlorine that may be contained in the re-sidual refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate.

    Use refrigerant piping materials made of phosphorus deox-idized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and moisture.

    Contaminants in the refrigerant piping may cause the refrig-erator oil to deteriorate.

    Store the piping materials indoors, and keep both ends of the pipes sealed until immediately before brazing. (Keep el-bows and other joints wrapped in plastic.)

    Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate or cause the compressor to malfunction.

    Use a small amount of ester oil, ether oil, or alkyl benzene to coat flares and flanges.

    Infiltration of a large amount of mineral oil may cause the re-frigerator oil to deteriorate.

    Charge the system with refrigerant in the liquid phase.

    If gaseous refrigerant is drawn out of the cylinder first, the composition of the remaining refrigerant in the cylinder will change and become unsuitable for use.

    Only use R410A.

    The use of other types of refrigerant that contain chloride may cause the refrigerator oil to deteriorate.

    Use a vacuum pump with a check valve.

    If a vacuum pump that is not equipped with a check valve is used, the vacuum pump oil may flow into the refrigerant cy-cle and cause the refrigerator oil to deteriorate.

    Prepare tools for exclusive use with R 410A. Do not use the following tools if they have been used with the conventional refrigerant: gauge manifold, charging hose, gas leak detec-tor, check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.

    If the refrigerant or the refrigerator oil that may be left on these tools are mixed in with R410A, it may cause the refrigerator oil in the new system to deteriorate. Infiltration of water may cause the refrigerator oil to deteriorate.Leak detectors for conventional refrigerants will not detect an R410A leak because R410A is free of chlorine.

    Do not use a charging cylinder.

    If a charging cylinder is used, the composition of the refrigerant in the cylinder will change and become unsuitable for use.

    Exercise special care when handling tools for use with R410A.

    Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate.

    0000001526.book ii ページ 2012年9月13日 木曜日 午後7時14分

    http://planetaklimata.com.ua/proizvoditeli/kondicionery-mitsubishi-electric/

  • CONTENTS

    HWE0812B GB

    I Features[1] Features.................................................................................................................................... 1

    II Components and Functions[1] Components and Functions...................................................................................................... 2

    III Specfications[1] Specifications............................................................................................................................ 4

    1.Specfications .......................................................................................................................... 42.Electrical component specifications........................................................................................ 7

    IV Outlines and Dimensions[1] Outlines and Dimensions.......................................................................................................... 8[2] Service Space......................................................................................................................... 10

    V Wiring Diagram[1] Wiring Diagram ....................................................................................................................... 11

    VI Refrigerant System Diagram[1] Refrigerant system diagram.................................................................................................... 13

    VII Troubleshooting[1] Troubleshooting ...................................................................................................................... 14

    1.Check methods..................................................................................................................... 142.DC fan motor (fan motor/indoor control board)..................................................................... 183.Address switch setting .......................................................................................................... 194.Voltage test points on the control board ............................................................................... 205.Dipswitch setting (Factory setting)........................................................................................ 21

    VIII Disassembly Procedure[1] Disassembly Procedure.......................................................................................................... 24

    1.Control box ........................................................................................................................... 242.Thermistor (Intake air) .......................................................................................................... 253.Drainpan ............................................................................................................................... 264.Thermistor (Gas pipe) (Liquid pipe) ...................................................................................... 275.Fan and fan motor ................................................................................................................ 286.Heat exchanger .................................................................................................................... 29

    0000001526.book 1 ページ 2012年9月13日 木曜日 午後7時14分

  • HWE0812B GB

    0000001526.book 2 ページ 2012年9月13日 木曜日 午後7時14分

  • [ I Features ]

    - 1 -HWE0812B GB

    I Features

    [1] Features

    Model Cooling capacity/Heating capacity

    kW

    PEFY-P20VMA(L)-E 2.2/2.5

    PEFY-P25VMA(L)-E 2.8/3.2

    PEFY-P32VMA(L)-E 3.6/4.0

    PEFY-P40VMA(L)-E 4.5/5.0

    PEFY-P50VMA(L)-E 5.6/6.3

    PEFY-P63VMA(L)-E 7.1/8.0

    PEFY-P71VMA(L)-E 8.0/9.0

    PEFY-P80VMA(L)-E 9.0/10.0

    PEFY-P100VMA(L)-E 11.2/12.5

    PEFY-P125VMA(L)-E 14.0/16.0

    PEFY-P140VMA(L)-E 16.0/18.0

    0000001526.book 1 ページ 2012年9月13日 木曜日 午後7時14分

  • [ II Components and Functions ]

    - 2 -HWE0812B GB

    II Components and Functions

    [1] Components and Functions1. Indoor (Main) Unit

    2. Remote Controller[PAR-21MAA]Once the operation mode is selected, the unit will remain in the selected mode until changed.

    (1) Remote Controller Buttons

    Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-surement of room temperature.

    (1) In case of rear inlet (2) In case of bottom inlet

    1 [Set Temperature] Button 7 [Vane Control] Button2 [Timer Menu] Button 8 [Ventilation] Button

    [Monitor/Set] Button [Operation] Button3 [Mode] Button 9 [Check/Clear] Button

    [Back] Button 10 [Test Run] Button4 [Timer On/Off] Button 11 [Filter] Button

    [Set Day] Button [ ] Button5 [Louver] Button 12 [ON/OFF] Button

    [Operation] Button 13 Position of built-in room thermistor6 [Fan Speed] Button 14 [Set Time] Button

    Air inlet

    Air outlet Air outlet

    Air inlet

    0000001526.book 2 ページ 2012年9月13日 木曜日 午後7時14分

  • [ II Components and Functions ]

    - 3 -HWE0812B GB

    (2) Remote Controller Display

    A Current time/Timer time I Louver swing

    B Centralized control indicator J Ventilation

    C Timer OFF indicator K Filter sign

    D Timer mode indicator L Sensor position

    E Operation mode display: COOL, DRY, AUTO, FAN, HEAT

    M Room temperature

    F Function mode indicator N Vane setting

    G Preset temperature O Fan speed

    H Power indicator P Operation lamp

    0000001526.book 3 ページ 2012年9月13日 木曜日 午後7時14分

  • [ III Specfications ]

    - 4 -HWE0812B GB

    III Specfications

    [1] Specifications

    1. Specfications

    *1 Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).

    Model PEFY-P20VMA(L)-E

    PEFY-P25VMA(L)-E

    PEFY-P32VMA(L)-E

    PEFY-P40VMA(L)-E

    Power supply Voltage V 1-phase 220-230-240

    Frequency Hz 50/60

    Cooling capacity *1 kW 2.2 2.8 3.6 4.5

    Heating capacity *1 kW 2.5 3.2 4.0 5.0

    Power consumption *2 Cooling kW 0.06(0.04) 0.07(0.05) 0.09(0.07)

    Heating kW 0.04(0.04) 0.05(0.05) 0.07(0.07)

    Current consumption *2 Cooling A 0.53(0.42) 0.55(0.44) 0.64(0.53)

    Heating A 0.42(0.42) 0.44(0.44) 0.53(0.53)

    External finish Galvanized

    Dimensions Height mm 250

    Width mm 700 900

    Depth mm 732

    Net weight *2 kg 23(22) 26(25)

    Heat exchanger Cross fin(Aluminium fin and copper tube)

    Fan Type Sirocco fan x 1

    Airflow rate (Low-Mid-High)

    m3/min 6.0-7.5-8.5 7.5-9.0-10.5 10.0-12.0-14.0

    External static pressure

    Pa 35/50/70/100/150

    Motor Output kW 0.085

    Air filter PP Honeycomb fabric (washable)

    Refrigerant pipe dimensions

    Gas (Brazed connection)

    mm[in.] ø12.7[ø1/2]

    Liquid (Brazed connection)

    mm[in.] ø6.35[ø1/4]

    Drain pipe dimensions mm[in.] O.D. 32[1-1/4]

    Operating noise(Low-Mid-High) 35Pa dB (A) 23-24-25 23-25-28 23-26-29

    50Pa 23-25-26 23-26-29 23-27-30

    70Pa 23-26-28 24-27-30 24-28-31

    100Pa 24-27-30 25-28-32 26-29-33

    150Pa 25-30-34 28-32-36 29-33-37

    35Pa 26-27-28 28-30-34

    50Pa 26-28-29 28-30-34

    70Pa 26-29-31 29-32-36

    100Pa 27-30-33 29-33-37

    150Pa 28-33-37 31-35-40 32-36-40

    Measurement location 1

    Aux. duct

    * Measured in anechoic room.

    2m 2m

    1.5m

    * Measured in anechoic room.

    2m 1m

    Aux. duct

    1.5m

    Measurement location 2

    0000001526.book 4 ページ 2012年9月13日 木曜日 午後7時14分

  • [ III Specfications ]

    - 5 -HWE0812B GB

    *1 Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).

    Model PEFY-P50VMA(L)-E

    PEFY-P63VMA(L)-E

    PEFY-P71VMA(L)-E

    PEFY-P80VMA(L)-E

    Power supply Voltage V 1-phase 220-230-240

    Frequency Hz 50/60

    Cooling capacity *1 kW 5.6 7.1 8.0 9.0

    Heating capacity *1 kW 6.3 8.0 9.0 10.0

    Power consumption *2 Cooling kW 0.11(0.09) 0.12(0.10) 0.14(0.12)

    Heating kW 0.09(0.09) 0.10(0.10) 0.12(0.12)

    Current consumption *2 Cooling A 0.74(0.63) 1.01(0.90) 1.15(1.04)

    Heating A 0.63(0.63) 0.90(0.90) 1.04(1.04)

    External finish Galvanized

    Dimensions Height mm 250

    Width mm 900 1100

    Depth mm 732

    Net weight *2 kg 26(25) 32(31)

    Heat exchanger Cross fin(Aluminium fin and copper tube)

    Fan Type Sirocco fan x 1

    Sirocco fan x 2

    Airflow rate (Low-Mid-High)

    m3/min 12.0-14.5-17.0

    13.5-16.0-19.0

    14.5-18.0-21.0

    External static pressure

    Pa 35/50/70/100/150

    Motor Output kW 0.085 0.121

    Air filter PP Honeycomb fabric (washable)

    Refrigerant pipe dimensions

    Gas (Brazed con-nection)

    mm[in.] ø12.7[ø1/2] ø15.88[ø5/8]

    Liquid (Brazed connection)

    mm[in.] ø6.35[ø1/4] ø9.52[ø3/8]

    Drain pipe dimensions mm[in.] O.D. 32[1-1/4]

    Operating noise(Low-Mid-High) 35Pa dB (A) 24-28-31 25-28-32 26-29-33

    50Pa 25-29-32 25-29-33 26-29-34

    70Pa 26-30-33 26-30-34 26-30-35

    100Pa 27-31-34 27-31-35 29-33-37

    150Pa 29-34-38 32-37-41

    35Pa 28-31-35 29-32-35 30-33-37

    50Pa 28-32-35 29-32-36 30-34-38

    70Pa 29-33-37 30-33-38 31-36-39

    100Pa 30-34-38 31-35-39 33-37-41

    150Pa 32-37-41 33-38-41 36-41-44

    Measurement location 1

    Aux. duct

    * Measured in anechoic room.

    2m 2m

    1.5m

    * Measured in anechoic room.

    2m 1m

    Aux. duct

    1.5m

    Measurement location 2

    0000001526.book 5 ページ 2012年9月13日 木曜日 午後7時14分

  • [ III Specfications ]

    - 6 -HWE0812B GB

    *1 Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).

    Model PEFY-P100VMA(L)-E

    PEFY-P125VMA(L)-E

    PEFY-P140VMA(L)-E

    Power supply Voltage V 1-phase 220-230-240

    Frequency Hz 50/60

    Cooling capacity *1 kW 11.2 14.0 16.0

    Heating capacity *1 kW 12.5 16.0 18.0

    Power consumption *2 Cooling kW 0.24(0.22) 0.34(0.32) 0.36(0.34)

    Heating kW 0.22(0.22) 0.32(0.32) 0.34(0.34)

    Current consumption *2 Cooling A 1.47(1.36) 2.05(1.94) 2.21(2.10)

    Heating A 1.36(1.36) 1.94(1.94) 2.10(2.10)

    External finish Galvanized

    Dimensions Height mm 250

    Width mm 1400 1600

    Depth mm 732

    Net weight *2 kg 42(41) 46(45)

    Heat exchanger Cross fin(Aluminium fin and copper tube)

    Fan Type Sirocco fan x 2

    Airflow rate (Low-Mid-High)

    m3/min 23.0-28.0-33.0 28.0-34.0-40.0 29.5-35.5-42.0

    External static pressure

    Pa 35/50/70/100/150

    Motor Output kW 0.244

    Air filter PP Honeycomb fabric (washable)

    Refrigerant pipe dimensions

    Gas (Brazed con-nection)

    mm[in.] ø15.88[ø5/8]

    Liquid (Brazed connection)

    mm[in.] ø9.52[ø3/8]

    Drain pipe dimensions mm[in.] O.D. 32[1-1/4]

    Operating noise(Low-Mid-High) 35Pa dB (A) 28-32-36 31-35-39 31-35-40

    50Pa 28-33-37 32-36-40 33-37-42

    70Pa 30-35-39 32-37-41 34-38-43

    100Pa 31-36-40 33-39-42 35-39-44

    150Pa 33-38-43 37-40-44 37-41-45

    35Pa 31-36-40 35-40-44 36-41-45

    50Pa 32-37-41 35-40-44 36-41-45

    70Pa 33-38-42 37-41-45 38-42-46

    100Pa 35-39-43 38-42-46 39-43-47

    150Pa 37-42-45 39-44-47 40-45-48

    Measurement location 1

    Aux. duct

    * Measured in anechoic room.

    2m 2m

    1.5m

    * Measured in anechoic room.

    2m 1m

    Aux. duct

    1.5m

    Measurement location 2

    0000001526.book 6 ページ 2012年9月13日 木曜日 午後7時14分

  • [ III Specfications ]

    - 7 -HWE0812B GB

    2. Electrical component specifications

    Component Sym-bol

    PEFY-P20VMA(L)-E

    PEFY-P25VMA(L)-E

    PEFY-P32VMA(L)-E

    Room temperature thermistor

    TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Fuse FUSE 250V 6.3A

    Fan motor 8-pole, Output 85W SIC-70CW-D885-1

    Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)

    Power supply terminal block

    TB2 (L, N, ) 250V 20A

    Transmission terminal block

    TB5TB15 (1, 2) 250V 15A, (M1, M2, S) 250V 20A

    Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less

    Component Sym-bol

    PEFY-P40VMA(L)-E

    PEFY-P50VMA(L)-E

    PEFY-P63VMA(L)-E

    PEFY-P71VMA(L)-E

    PEFY-P80VMA(L)-E

    Room temperature thermistor

    TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Fuse FUSE 250V 6.3A

    Fan motor 8-pole, Output 85W SIC-70CW-D885-2

    8-pole, Output 121W SIC-70CW-D8121-1

    Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)

    Power supply terminal block

    TB2 (L, N, ) 250V 20A

    Transmission terminal block

    TB5TB15

    (1, 2) 250V 15A, (M1, M2, S) 250V 20A

    Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less

    Component Sym-bol

    PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E

    Room temperature thermistor

    TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

    Fuse FUSE 250V 6.3A

    Fan motor 8-pole, Output 244W SIC-101CW-D8244-1

    Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)

    Power supply terminal block

    TB2 (L, N, ) 250V 20A

    Transmission terminal block

    TB5TB15 (1, 2) 250V 15A, (M1, M2, S) 250V 20A

    Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less

    0000001526.book 7 ページ 2012年9月13日 木曜日 午後7時14分

  • [ IV Outlines and Dimensions ]

    - 8 -HWE0812B GB

    IV Outlines and Dimensions

    [1] Outlines and Dimensions1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA-E

    Note 1 Use M10 suspension bolts. (not supplied)2 Provide an access door for maintenance at the bottom.3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMA-E models, which have 2

    fans. The PEFY-P20~50VMA-E model have 1 fans.

    4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake duct on the intake side.

    1558

    1358

    1500

    1300

    7Mo

    del

    A66

    080

    0

    1200

    700

    754

    900

    954

    860

    9E 11

    D 1060

    C

    1100

    B 1154

    PEFY

    -P14

    0VMA

    -EPE

    FY-P

    100,1

    25VM

    A-E

    PEFY

    -P63

    ,71,80

    VMA-

    EPE

    FY-P

    40, 5

    0VMA

    -EPE

    FY-P

    20,25

    ,32VM

    A-E

    1400

    1600

    1454

    1654

    1500

    1700

    1360

    1560

    14 16

    1000

    1000F

    858

    800

    G 658

    1058

    600

    1480

    1280

    55

    300

    150

    44 49

    800

    1000

    260

    LK 33

    0

    JH 1200

    1500

    1700

    54 5432

    037

    0

    544M

    780

    4

    N 990

    121210P 10 10ø1

    5.88

    ø9.52

    ø12.7

    ø6.35

    Gas p

    ipe1

    Liquid

    pipe

    2

    650 -10

    (Actua

    l leng

    th)

    Less

    than

    300m

    m

    Less than 700mm

    Drain

    hose

    (I.D.ø

    32)

    Air F

    ilter

    G 21

    A

    B (Suspension bolt pitch)

    C

    23

    Air

    inlet

    L6J

    KK x (M - 1) = N

    P - ø2.9

    40

    D (Duct) 20 100

    57

    73

    10

    643

    (Sus

    pens

    ion bo

    lt pitc

    h)

    10030100 x (E - 1) = F

    5815

    Susp

    ensio

    n bolt

    hole

    4 - 1

    4 x 30

    Slot

    2 x E

    - ø2

    .9 Air outle

    t

    250

    40

    33122

    178(Duct)23

    1023

    832

    700732

    136

    67 356

    100

    41217

    2 1

    Contr

    ol bo

    xRe

    friger

    ant p

    iping

    Braz

    ing co

    nnec

    tion (

    liquid

    )

    Refrig

    eran

    t pipi

    ngBr

    azing

    conn

    ectio

    n (ga

    s)

    Drain

    pump

    Term

    inal b

    lock (

    Powe

    r sou

    rce)

    Term

    inal b

    lock (

    Tran

    smiss

    ion)

    Drain

    pipe

    (O.D

    .ø32

    )(S

    ponta

    neou

    s dra

    ining

    )

    Drain

    pipe

    (O.D

    . ø32

    )

    2 x 2

    - ø2.9

    210

    18

    112

    1111

    2

    KJ

    112

    P - ø

    2.9

    11 112

    JK

    L6

    JK

    K x (

    M - 1

    ) = N

    0000001526.book 8 ページ 2012年9月13日 木曜日 午後7時14分

  • [ IV Outlines and Dimensions ]

    - 9 -HWE0812B GB

    2. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMAL-E

    Note 1 Use M10 suspension bolts. (not supplied)2 Provide an access door for maintenance at the bottom.3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMAL-E models, which have

    2 fans. The PEFY-P20~50VMAL-E model have 1 fans.

    4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake duct on the intake side.

    1558

    1358

    1500

    1300

    7M

    odel

    A66

    080

    0

    1200

    700

    754

    900

    954

    860

    9E 11

    D 1060

    C

    1100

    B 1154

    PEFY

    -P14

    0VM

    AL-E

    PEFY

    -P10

    0,12

    5VM

    AL-E

    PEFY

    -P63

    ,71,

    80VM

    AL-E

    PEFY

    -P40

    , 50V

    MAL

    -EPE

    FY-P

    20,2

    5,32

    VMAL

    -E

    1400

    1600

    1454

    1654

    1500

    1700

    1360

    1560

    14 16

    1000

    1000F

    858

    800

    G 658

    1058

    600

    1480

    1280

    55

    300

    150

    44 49

    800

    1000

    260

    LK 33

    0

    JH 1200

    1500

    1700

    54 5432

    037

    0

    544M

    780

    4

    N 990

    121210P 10 10ø1

    5.88

    ø9.5

    2

    ø12.

    7ø6

    .35

    Gas p

    ipe1

    Liquid

    pipe

    2

    250

    40

    33122

    21

    23

    178(Duct)23

    10

    3270

    0732

    136

    67 356

    100

    217

    643

    (Sus

    pens

    ion bo

    lt pitc

    h) A

    ir Fi

    lter

    Cont

    rol b

    oxRe

    frige

    rant

    pipi

    ngBr

    azing

    conn

    ectio

    n (liq

    uid)

    Refri

    gera

    nt p

    iping

    Braz

    ing co

    nnec

    tion

    (gas

    )Te

    rmina

    l bloc

    k (Po

    wer s

    ourc

    e)

    Term

    inal b

    lock (

    Tran

    smiss

    ion)

    Drain

    pipe

    (O.D

    .ø32

    )2

    x 2 -

    ø2.9

    2 1

    (Actu

    al len

    gth)

    320 -10

    J 6P - ø2.9

    D (Duct)

    210

    18

    G

    A

    B (Suspension bolt pitch)

    C

    100 x (E - 1) = F

    Air

    outle

    tAi

    rinl

    et

    Susp

    ensio

    n bo

    lt hole

    4 -

    14 x

    30 S

    lot2

    x E -

    ø2.9

    Drain

    hose

    (I.D.

    ø32)

    K x (M - 1) = NKLK

    112

    1111

    2

    24

    20 100

    57

    7310

    10030

    15

    J

    K x (

    M - 1

    ) = N

    KJ

    6L

    KJ

    11211

    P - ø

    2.9

    112

    0000001526.book 9 ページ 2012年9月13日 木曜日 午後7時14分

  • [ IV Outlines and Dimensions ]

    - 10 -HWE0812B GB

    [2] Service Space1.PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E

    Secure enough access space to allow for the maintenance, inspection, and replacement of the motor, fan, drain pump, heat exchanger, and electric box in one of the following ways.Select an installation site for the indoor unit so that its maintenance access space will not be obstructed by beams or other objects.(1) When a space of 300 mm or more is available below the unit between the unit and the ceiling (Fig. 1)• Create access door 1 and 2 (450 × 450 mm each) as shown in Fig. 2.(Access door 2 is not required if enough space is available below the unit for a maintenance worker to work in.)

    (2) When a space of less than 300 mm is available below the unit between the unit and the ceiling (At least 20 mm of space should be left below the unit as shown in Fig. 3.)• Create access door 1 diagonally below the electric box and access door 3 below the unit as shown in Fig. 4.or• Create access door 4 below the electric box and the unit as shown in Fig. 5.

    Elec

    tric b

    ox

    Ceiling

    Min. 300 mm

    Min. 10 mm

    View

    ed fr

    om

    the

    direc

    tion

    of th

    e ar

    row

    A

    Acce

    ss do

    or 2 (

    450 ×

    450)

    Ceilin

    g beam

    Intak

    e air

    Supp

    ly air

    Elec

    tric b

    ox

    Ceilin

    g

    Min. 20 mm

    Min.10 mm

    View

    ed fr

    om

    the

    direc

    tion

    of th

    e ar

    row

    B

    Ceilin

    g beam

    Acce

    ss do

    or 3

    Intak

    e air

    Supp

    ly air

    700

    450

    475

    450

    R 50~1

    5045

    0

    450

    100~

    200

    Botto

    m o

    f indo

    or u

    nit

    Maint

    enan

    ce ac

    cess

    spac

    e

    Min. 3

    00 m

    m

    (View

    ed fr

    om

    the

    direc

    tion

    of

    the

    arro

    w A)

    Acce

    ss do

    or 2

    (450

    × 45

    0)

    Acce

    ss do

    or 1

    (450

    × 45

    0)

    Q

    Elec

    tric b

    ox

    Acce

    ss do

    or 3

    Q 50

    S

    777

    450 100

    ~200

    Maint

    enan

    ce ac

    cess

    spac

    e

    Botto

    m of

    indoo

    r unit

    Elec

    tric b

    ox

    (View

    ed fr

    om th

    e dir

    ectio

    n of

    th

    e ar

    row

    B)

    Acce

    ss do

    or 1

    (450

    × 45

    0)

    450

    4757

    0050

    Min. 3

    00 m

    m

    777

    T

    50

    50Q

    700

    Maint

    enan

    ce ac

    cess

    spac

    e

    Botto

    m of

    indoo

    r unit

    Electri

    c box

    Min. 3

    00 m

    m

    (View

    ed fr

    om th

    e dir

    ectio

    n of

    th

    e ar

    row

    B)

    Acce

    ss do

    or 4

    Fig.

    1

    Fig.

    3

    Fig.

    2

    Fig.

    4Fi

    g. 5

    PE

    FY-P

    20,2

    5,32

    VM

    A(L

    )-E

    PE

    FY-P

    40,5

    0VM

    A(L

    )-E

    PE

    FY-P

    63,7

    1,80

    VM

    A(L

    )-E

    PE

    FY-P

    100,

    125V

    MA

    (L)-

    EP

    EFY

    -P14

    0VM

    A(L

    )-E

    Q 700

    900

    1100

    1400

    1600

    S 800

    1000

    1200

    1500

    1700

    T 1300

    1500

    1700

    2000

    2200

    R50

    ~150

    150~

    250

    250~

    350

    400~

    500

    500~

    600

    (mm

    )M

    odel

    Uni

    t: m

    m

    0000001526.book 10 ページ 2012年9月13日 木曜日 午後7時14分

  • [ V Wiring Diagram ]

    - 11 -HWE0812B GB

    V Wiring Diagram

    [1] Wiring Diagram1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E

    2 1

    INSI

    DE S

    ECTI

    ON

    OF

    CONT

    ROL

    BOX

    FUSE

    (16A

    )

    BREA

    KER

    (16A

    )

    PULL

    BOX

    TO N

    EXT I

    NDOO

    R UN

    IT

    TO M

    A RE

    MOTE

    CO

    NTRO

    LLER

    TO O

    UTDO

    OR U

    NIT

    BC C

    ONTR

    OLLE

    RRE

    MOTE

    CON

    TROL

    LER

    P.B.

    21

    TB15

    2 1

    TB2

    NL

    S (S

    HIEL

    D)

    M2 M1

    TB5

    ACL

    21

    1 3

    35

    1

    X10

    U

    DC2

    80-3

    40V

    Rect

    ifier c

    ircui

    t

    U

    (Red

    )

    X01

    CNP

    F01

    DSA

    ZNR0

    2

    CND

    ZNR0

    1

    (Blue

    )

    Drain

    pump

    Fan m

    otor

    53

    21

    44

    45

    67

    12

    11

    23

    (Blue

    )CN

    XB1

    CNMF

    CNXA

    1CN

    XC1

    ONLY

    FOR

    PEF

    Y-P·

    VMA-

    E

    MS 3~

    M 1~

    I.B.

    1

    431 2

    21542 3

    CN4F

    (Blue

    )CN

    XA2

    CN52

    CN20

    CN41

    CN51

    CNXB

    2

    CNXC

    2(R

    ed)

    CN44

    (Gre

    en)

    1 2 4321 3 4

    1 2

    13

    (Blac

    k)

    (Red

    )

    CN3A

    (Blue

    )

    (Red

    )

    CN2A

    LED1

    LED2

    CN27

    SWE

    CN90

    CN10

    5

    CN2M

    (Blue

    )ONOF

    FSW

    3

    SW2

    SW1

    1 2 43

    CN4F

    TH21

    A

    FSTH

    23TH

    22t°

    FOR

    PEFY

    -P·V

    MA-E

    REFE

    R TO

    "A" F

    OR P

    EFY-

    P·VM

    AL-E

    21 653 4

    CN60

    CN32

    SWA

    SW4

    SW11

    SW12

    SW14

    SWC

    SW5

    POW

    ER S

    UPPL

    YAC

    220-

    240V

    50

    ,60Hz

    M LEV

    0000001526.book 11 ページ 2012年9月13日 木曜日 午後7時14分

  • [ V Wiring Diagram ]

    - 12 -HWE0812B GB

    Table.1 SYMBOL EXPLANATION

    SYM-BOL

    NAME SYM-BOL

    NAME SYM-BOL

    NAME

    I.B. Indoor controller board CN32 Connector (Remote switch) SW2 (I.B.)

    Switch (for capacity code)

    P.B. Power supply board CN41 Connector (HA terminal-A) SW3 (I.B.)

    Switch (for mode selection)

    TB2 Power source terminal block CN51 Connector (Centrally control) SW4(I.B.)

    Switch (for model selection)

    TB5 Transmission terminal block CN52 Connector (Remote indica-tion)

    SW5(I.B.)

    Switch (for mode selection)

    TB15 Transmission terminal block CN90 Connector (Wireless) SWE(I.B.)

    Connector (emergency opera-tion)

    F01 Fuse AC 250V 6.3A CN105 Connector (IT terminal) SW11(I.B.)

    Switch (1s digit address set)

    ZNR01,02

    Varistor CN2A Connector (0-10V Analog in-put)

    SW12(I.B.)

    Switch (10ths digit address set)

    DSA Arrester FS Float switch SW14(I.B.)

    Switch (BRANCH No.)

    X01 Aux. relay TH21 Thermistor (inlet air temp.de-tection)

    SWA(I.B.)

    Switch (for static pressure se-lection)

    X10 Aux. relay TH22 Thermistor (piping temp.de-tection / liguid)

    SWC(I.B.)

    Switch (for static pressure se-lection)

    ACL AC reactor (Power factor im-provement)

    TH23 Thermistor (piping temp. de-tection / gas)

    CN27 Connector (Damper) SW1(I.B.)

    Switch (for mode selection)

    Note 1 Wiring to TB2, TB5, and TB15 indicated by the double-dashed lines is on-site work.2 terminal block, connector.

    0000001526.book 12 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VI Refrigerant System Diagram ]

    - 13 -HWE0812B GB

    VI Refrigerant System Diagram

    [1] Refrigerant system diagram

    (A) Gas pipe thermistor TH23

    (B) Gas pipe

    (C) Liquid pipe

    (D) Brazed connections

    (E) Strainer (#100 mesh)

    (F) Linear expansion valve

    (G) Liquid pipe thermistor TH22

    (H) Heat exchanger

    (I) Room temperature thermistor TH21

    Capacity PEFY-P20, 25, 32, 40, 50VMA(L)-E

    PEFY-P63, 71, 80, 100, 125, 140VMA(L)-E

    Gas pipe ø12.7 [1/2] ø15.88 [5/8]

    Liquid pipe ø6.35 [1/4] ø9.52 [3/8]

    (H)

    (I)

    (F)

    (E)(E)

    (C)

    (G)

    (A)

    (D)

    (B)

    0000001526.book 13 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 14 -HWE0812B GB

    VII Troubleshooting

    [1] Troubleshooting

    1. Check methods1. Component and check points(1) Thermistor

    Room temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)Disconnect the connector and measure the resistance between terminals with a tester.(Ambient temperature 10°C - 30°C)

    1) Thermistor characteristic graph

    (2) Fan motor (CNMF)Refer to the page on "DC fan motor (fan motor/indoor control board)."

    (3) Linear expansion valveDisconnect the connector, and measure the resistance between terminals with a tester.Refer to the next page for details.

    Normal Abnormal

    4.3kΩ - 9.6kΩ Open or short

    (Refer to the thermistor characteristic graph below.)

    Low-temperature thermistorRoom temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)Drain sensor (DS)

    Thermistor R0 = 15 kΩ 3%Multiplier of B = 3480 kΩ 2%

    0°C 15kΩ10°C 9.6kΩ20°C 6.3kΩ25°C 5.2kΩ30°C 4.3kΩ40°C 3.0kΩ

    (A) Temperature (°C)

    (B) Resistance (kΩ)

    Normal Abnormal

    1-5 2-6 3-5 4-6 Open or shortWhite-Red Yellow-Brown Orange-Red Blue-Brown

    200 kΩ 10%

    (A) Brown (D) Orange

    (B) Red (E) Yellow

    (C) Blue (F) White

    Rt = 15 exp { 3480( ) }1273+t

    1273

    0

    10

    20

    30

    40

    50

    -20 -10 0 10 20 30 40 50

    (A)

    (B)

    1 2 3 4 5 6

    LEV

    M

    (A)

    (B)

    (C)

    (D)

    (E)

    (F) CN60

    0000001526.book 14 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 15 -HWE0812B GB

    1) Summary of linear expansion valve (LEV) operationThe LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board.The LEV position changes in response to the pulse signal.

    Indoor control board and LEV connection

    Pulse signal output and valve operation

    The output pulse changes in the following order:When the valve closes 1 -> 2 -> 3 -> 4 -> 1When the valve opens 4 -> 3 -> 2 -> 1 -> 4When the valve position remains the same, all output signals will be OFF.If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.

    (A) Brown (F) White

    (B) Red (G) Control board

    (C) Blue (H) Connection (CN60)

    (D) Orange (I) Drive circuit

    (E) Yellow (J) Linear expansion valve

    Phase number

    Output pulse1 2 3 4

    ø1 ON OFF OFF ONø2 ON ON OFF OFFø3 OFF ON ON OFFø4 OFF OFF ON ON

    4

    3

    6

    5

    2

    1

    (G)

    (H)

    (I)

    (J) (A)

    (A)

    (B)

    (B)

    (C)

    (C)

    (D)

    (D) (E)

    (E)

    (F) (F)

    12VDC

    M

    4

    6

    2 3

    5 1

    0000001526.book 15 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 16 -HWE0812B GB

    2) LEV operation

    When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A.When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the figure, it makes louder noise than would be heard when there is an open phase. Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against your ear.

    3) Troubleshooting

    (a) Close

    (b) Open

    (c) Fully open valve (2000 pulses)

    (d) No. of pulses

    (e) Extra tightning (80 - 100 pulse)

    (f) Valve opening degree(f)

    (a)

    (b)

    (e)

    (d)

    (c)

    Symptom Checking Criteria Remedy

    Circuit failure on the microcomputer

    Disconnect the connectors on the control board, and connect LEDs to test the cir-cuit as shown below.

    Pulse signals are output for 10 seconds when the main power is turned on. If there are LEDs that do not light up at all or remain lit after the pulses are turned off, there is a problem with the driving circuit.

    Replace the in-door control board if driving circuit failure is detected.

    Locked LEV The motor will idle and make small clicking noise if it is run while the LEV is locked. If this clicking noise is heard both when the valve is fully closed and while it is being opened, it indicates a problem.

    Replace the LEV.

    Disconnected or shorted LEV motor coils

    easure the resistance between the coils with a tester (red-white, red-orange, brown-yellow, brown-blue). The normal range of resistance is 150 Ω 10%

    Replace the LEV.

    654321

    1 k LED

    0000001526.book 16 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 17 -HWE0812B GB

    (4) Drain-up mechanismMeasure the resistance between the terminals with a tester. (coil temperature 20°C)

    (5) Drain float switch (CN4F)Disconnect the connector, and measure the resistance between terminals with a tester.

    Valve closure fail-ure (leaky valve)

    To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature that appears on the operation monitor on the outdoor unit's multi control board while operating the indoor unit in question in the FAN mode and the other indoor units in the cooling mode.

    Replace the LEV if the amount of leakage is great.

    (A) Termistor (TH21)

    Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly lower than the inlet temperature on the remote controller, valve closure failure is suspected. If the amount of leakage is insignificant, replacement of LEV is unnec-essary unless it is causing a problem.

    Misconnections of connectors or con-tact failure

    Perform a visual check for disconnected connectors.Perform a visual check of lead wire color.

    Disconnect the connectors on the control board and perform a continuity test.

    Symptom Checking Criteria Remedy

    (A)

    LEV

    Normal Abnormal

    340 Ω Open or short

    (A) Moving part

    (B) Switch

    (C) Magnet

    Position of the moving part Normal Abnormal

    Up Short (any position but short)

    Down Open (any position but open)

    13

    1234

    (A)

    (A)

    (B)(C)

    0000001526.book 17 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 18 -HWE0812B GB

    2. DC fan motor (fan motor/indoor control board)1. CAUTION

    A high voltage is applied to the connector for connection to the fan motor (CNMF). Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor.

    2. TroubleshootingSymptom: Indoor unit fan does not run.

    Check fan motor connector contact (CNMF).

    Replace the indoor control board.

    Replace the indoor control board.

    Fix the connection.

    Yes

    No

    Yes

    No

    Yes

    No

    Check the fan motor position thermistor signal.Get the motor to make a full rotation or more, and measure the voltage at the test point VFG.(same with the voltage between fan connector 7 (+) and 4(-))

    Is the fan motor connector (CNMF) fully inserted?

    Is the voltage within the normal range?

    Replace the motor.Are 0VDC and 15VDC displayed alternately?

    Check the power supply.Measure the voltage at the indoor control board.

    310 - 340VDC (same with the voltage between fan connector 1 (+) and 4(-))

    15VDC (same with the voltage between fan connector 5 (+) and 4(-)) 1 - 6.5VDC (same with the voltage between fan connector 6 (+) and 4(-))

    [Values for Vsp are the values that are measured with the fan motor in operation. Vsp is 0V when the fan motor is stopped.]

    VDCPower supply voltage

    0000001526.book 18 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 19 -HWE0812B GB

    3. Address switch settingMake sure that power to the unit is turned off.

    1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12).Address setting is not required when the unit remote controller is used.On-site address setting is required for the indoor units to run.

    2. Address settings vary in different systems.Refer to the section on address setting in the outdoor unit installation manual.

    3. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit).To set the address to "3," set SW12 to "0" and SW11 to "3."To set the address to "25," set SW 12 to "2" and SW 11 to "5."

    (A) Indoor unit control board

    (B) Factory setting

    ONOFF

    SW4

    (A)

    (B)Please see the WIRING LABEL on the control box.

    body7.fm 19 ページ 2012年9月19日 水曜日 午前11時56分

  • [ VII Troubleshooting ]

    - 20 -HWE0812B GB

    4. Voltage test points on the control board1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E

    F01 Fuse(AC 250V 6.3A)

    CND Power supply voltage (220 - 240VAC)

    CN2M For M-NET transmission cable connection (24 - 30VDC)

    SWE Emergency operation

    SW2 Capacity setting

    SW4 Function setting

    SW3 Function setting

    CN32 Remote start/stop adapter

    CN3A For MA remote controller cable connection (10 - 13 VDC (Between 1 and 3.))

    CN52 Remote display

    CN51 Centralized control

    CN41 JAMA standard HA terminal A

    CN44 Thermistor (liquid/gas tempera-ture)

    CN4F Float thermistor

    CN20 Thermistor (Inlet temperature)

    CNMF Fan motor output1 - 4: 310 - 340 VDC5 - 4: 15 VDC6 - 4: 0 - 6.5 VDC7 - 4: Stop 0 or 15 VDC

    Run 7.5 VDC(0 - 15 pulse)

    CNP Drain-up mechanism output (200VAC)

    (*1)

    VFG Voltage on the (-) side of PC51 and C25(Same with the voltage between 7 (+) and 4 (-) of CNMF)

    VCC Voltage between the C25 pins 15 VDC(Same with the voltage between 5 (+) and 4 (-) of CNMF)

    Vsp Voltage between the C53 pins0VDC (with the fan stopped)1 - 6.5VDC (with the fan in opera-tion)(Same with the voltage between 6 (+) and 4 (-) of CNMF)

    CN3A

    CN2M

    SW4

    CND

    F01

    CN32Indoor controller board

    Power supply board

    SW3

    PC51(*1)

    CN41CN51CN52

    CN20

    CN4FCN44

    C25(*1)

    C53(*1)

    CNMF

    SWESW2

    CNP

    0000001526.book 20 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 21 -HWE0812B GB

    5. Dipswitch setting (Factory setting)1. Function setting(1) SW1

    1) Adress board

    (2) SW3

    1) Indoor control boardDipswitch settings must be made while the unit is stopped.

    Switch position Function Switch setting

    ON OFF

    1 Active Thermistor (Intake air thermistor)

    Built-in thermistor on the remote controller

    Indoor unit

    2 Filter clogging detection Available Unavailable

    3 Filter life 2500 hr 100 hr

    4 Outdoor air intake Enabled Disabled

    5 Remote display Thermo-ON signal Fan output

    6 Humidifier operation During heating mode During heating operation

    7 Fan speed Low Very low

    8 Fan speed at heating Thermo-OFF Preset fan speed Follows the setting of SW1-7

    9 Auto restart after power failure Enabled Disabled

    10 Power start/stop Enabled Disabled

    Factory setting

    Switch position Function Switch setting

    ON OFF

    1 Unit type Cooling only Heat pump

    2 - - -

    3 - - -

    4 - - -

    5 - - -

    6 - - -

    7 - - -

    8 Heating 4-deg up Disabled Enabled

    9 - - -

    10 - - -

    Factory setting

    PEFY-P25, 40, 63, 71, 80, 100, 125, 140VMA(L)-EPEFY-P20VMA(L)-E PEFY-P32, 50VMA(L)-E

    0000001526.book 21 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VII Troubleshooting ]

    - 22 -HWE0812B GB

    2. Capacity code setting(1) SW21) Indoor control board

    Dipswitch settings must be made while the unit is stopped.Factory settingThe switches are set to correspond to the unit capacity.

    3. Model setting(1) SW41) Indoor control board

    Dipswitch settings must be made while the unit is stopped.

    Note: Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller off). There is no need to power cycle the unit.

    4. Power voltage setting(1) SW51) Indoor control board

    Dipswitch settings must be operated with the main power turned OFF.

    Factory settingPlease see the WIRING LABEL on the control box.

    Factory settingPlease see the WIRING LABEL on the control box.

    Set SW5 to 240V side when the power supply is 240 volts.When the power supply is 220 and 230 volts, set SW5 to 220V side.

    PEFY-P25VMA(L)-EPEFY-P20VMA(L)-E PEFY-P32VMA(L)-E PEFY-P40VMA(L)-E

    PEFY-P50VMA(L)-E PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E PEFY-P80VMA(L)-E

    PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E

    body7.fm 22 ページ 2012年9月19日 水曜日 午前11時53分

  • [ VII Troubleshooting ]

    - 23 -HWE0812B GB

    5. External static pressure(1) SWA, SWC1) Indoor control board

    Note: Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation status (RUN/STOP) or the remote controller status (ON/OFF).

    6. 1s and 10ths digits(1) SW11, SW12 (Rotary switch)

    The use of a network remote controller (PAR-F27MEA) requires address setting. 1) Indoor control board

    Address settings must be made while the unit is stopped.

    7. Connection No. setting(1) SW14 (Rotary switch)

    This switch is used when the unit connected to an R2 series of outdoor unit. 1) Indoor control board

    Note: Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller is OFF.

    All models Factory setting

    Factory setting

    Factory setting

    35Pa

    1 2 3

    SWA SWC

    50Pa

    1 2 3

    SWA SWC

    70Pa

    1 2 3

    SWA SWC

    100Pa

    1 2 3

    SWA SWC

    150Pa

    123

    SWA SWC1

    2

    1

    2

    1

    2

    1

    2

    1

    2

    1 2 3

    SWA SWC

    1

    2

    0000001526.book 23 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VIII Disassembly Procedure ]

    - 24 -HWE0812B GB

    VIII Disassembly Procedure

    [1] Disassembly Procedure

    1. Control boxExercise caution when removing heavy parts.

    1. Removing the control box cover(1) Remove the three fixing screws on the cover (A) to re-

    move it.

    Fig.1

    Fig.2

    (A)

    0000001526.book 24 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VIII Disassembly Procedure ]

    - 25 -HWE0812B GB

    2. Thermistor (Intake air)Exercise caution when removing heavy parts.

    1. Remove the control box cover according to the procedure in section [1].

    2. Remove the thermistor.(1) Pull out the thermistor holder (B) and thermistor (C) on

    the control box.

    Fig.3

    (B), (C)

    0000001526.book 25 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VIII Disassembly Procedure ]

    - 26 -HWE0812B GB

    3. DrainpanExercise caution when removing heavy parts.

    1. Removing the filter and the bottom plate(1) Push down the tab on the filter, and pull out the filter in

    the direction of the arrow 1.(2) Remove the fixing screws on the bottom plate (D), (E) to

    remove it.

    Fig.4

    2. Removing the drainpan(1) Pull out the drain pan in the direction of the arrow 2.

    Fig.5

    NoteDrain the water out of the drain pan before removing it.

    (D) (E)

    0000001526.book 26 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VIII Disassembly Procedure ]

    - 27 -HWE0812B GB

    4. Thermistor (Gas pipe) (Liquid pipe)Exercise caution when removing heavy parts.

    1. Remove the drain pan according to the procedure in sec-tion [1].

    2. Removing the Heat exchanger cover(1) Remove the four fixing screws on the heat exchanger cov-

    er (F) to remove it.

    Fig.6

    3. Removing the thermistor(1) Remove the thermistor (G) from the thermistor holder (H)

    on the copper tube.

    Thermistor sizeLiquid pipe: ø8mmGas pipe: ø6mm

    Fig.7

    (F)

    HEX

    (G), (H)

    0000001526.book 27 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VIII Disassembly Procedure ]

    - 28 -HWE0812B GB

    5. Fan and fan motorExercise caution when removing heavy parts.

    1. Removing the filter and the bottom plate(1) Push down the tab on the filter, and pull out the filter in the

    direction of the arrow 1.(2) Remove the fixing screws on the bottom plate (J) to re-

    move it.

    Fig.8

    (a) Tab

    2. Removing the fan casing (bottom half)(1) Squeeze the tabs on the fan casing to remove it in the di-

    rection of arrow 2.

    Fig.9

    3. Removing the motor cable(1) Remove the motor cable threw the rubber bush.4. Removing the fan motor and the Sirocco fan(1) Remove the two motor fixing screws to remove the motor

    and the Sirocco fan in the direction of arrow 3.

    Fig.10

    (2) Remove the four fan case fixing screws to take the top half of the fan casing off.

    Fig.11

    (J)

    (a)

    0000001526.book 28 ページ 2012年9月13日 木曜日 午後7時14分

  • [ VIII Disassembly Procedure ]

    - 29 -HWE0812B GB

    6. Heat exchangerExercise caution when removing heavy parts.

    1. Remove the drain pan according to the procedure in section [1].

    2. Remove the heat exchanger cover according to the proce-dure in section [4] 2.

    3. Removing the cover(1) Remove the five fixing screws on the cover (K) to remove it.

    Fig.12

    (K) Pipe support plate

    4. Removing the Heat exchanger(1) Remove the fixing screws on the heat exchanger (M) to re-

    move it.

    Fig.13

    (K)

    (M)

    0000001526.book 29 ページ 2012年9月13日 木曜日 午後7時14分

  • KB79U866H02_GB.fm Page 18 Monday, April 25, 2011 3:16 PM

  • HWE0812B

    New publication effective Sep. 2012Specifications subject to change without notice