peme… · abbreviations: lps: low pressure switch hps: high pressure switch pt: pressure...

155
[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012 Project: Doc: Version: Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page: Control System Operations Manual AGE Page 1 of 155 Pemex 1000m3 Atlantic Sea Control System Operations Manual PLC Firmware Version: 6.10 HMI Firmware Version: 6.10

Upload: others

Post on 16-Oct-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 1 of 155

Pemex 1000m3 Atlantic Sea Control System

Operations Manual

PLC Firmware Version: 6.10 HMI Firmware Version: 6.10

Page 2: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 2 of 155

Document Revision:

Version Author Date Effected Pages Description 01a AGE 10-11-2012 All Initial Draft

Abbreviations:

LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers (1.0 E-03

Modbus: A high-level protocol for industrial networks developed in 1979 by Modicon (now Schneider Automation Inc.). Providing services at layer 7 of the OSI model, it defines a request/response message structure for a client/server environment. Modbus runs over various data links including its own Modbus+ token passing network and serial links such as RS-232 and RS-485. It is widely used with TCP/IP over Ethernet. Individual device networks connected to Modbus+ or serial links hook into Ethernet via gateways for transport over an IP network or the

) DSRC: Danfoss Sea Recovery Corporation FWF: Fresh Water Flush Modbus: High level communications protocol for industrial networks Definitions:

Internet. Modbus is governed by the Modbus-IDA Organization, a merger of the Modbus Organization and IDA Group in 2003. For more information, visit www.modbus.org.

Page 3: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 3 of 155

1. The Control Panel…….….………..………………………………………………………………..…… 7

Table of Contents:

2. Initial System Checks/Commissioning …………………………………………………......... 10

2.1 Entering Commissioning Mode …………………………………………….. 10 2.2 Motor and Pump rotation Checks…………………………………………. 16 2.3 Valve Operation Checks…………………………………………..……………. 18

3. Editing System Set-points (Normal User)…..……………………………………..………….. 26 3.1 Entering Set-point Editing Mode As Normal User..………………… 26 3.2 Booster Pump Minimum Inlet Pressure ………………………………… 28 3.3 Booster Pump Maximum Inlet Pressure ……………………………….. 28 3.4 Booster Pump MinimumOutlet Pressure …………………………….. 29 3.5 Booster Pump MaximumOutlet Pressure …………………………….. 29 3.6 Booster Pump Output Error Maximum Operation Time ……….. 29 3.7 ISave Pump Output Error Maximum Operation Time ……………. 30 3.8 Maximum 20u Filter Differential Pressure …………………………….. 30 3.9 Maximum 5u Filter Differential Pressure ……………………..……….. 30 3.10 Minimum Feed System Flow Rate ………………………………….……… 31 3.11 Maximum Feed System Flow Rate …………………………………………. 31 3.12 Minimum ISave System Flow Rate ………………………………………… 31 3.13 Maximum ISave System Flow Rate ………………………………………… 32 3.14 Minimum High Pressure Pump Inlet Pressure ………………………… 32 3.15 Maximum High Pressure Pump Inlet Pressure …………….…………. 32 3.16 Minimum High Pressure Pump Outlet Pressure …………………….. 32 3.17 Maximum High Pressure Pump Outlet Pressure …………………….. 33 3.18 Maximum High Pressure Pump Running Hours ……………….….…. 34 3.19 Maximum ISave Pump Running Hours ……………………………….….. 34 3.20 Maximum Booster Pump Running Hours ….……………………….….. 35 3.21 Maximum Individual Membrane Element Differential ………...… 35 3.22 Maximum Expected Clean Membrane Element Differential ...… 35 3.23 Maximum Permeate Line Pressure …………………………………..……. 35 3.24 Acceptable Maximum Salinity Level …………………………………..….. 36 3.25 Acceptable Minimum Salinity Level ……………………………………… 36 3.26 Fresh Water Flush Time ……………………………………………………….. 36 3.27 Minimum Allowable Fresh Water FlushPressure ..……………….. 37 3.28 Low Pressure Valve Actuation Time ……………………………………… 37 3.29 ISave By-Pass Valve Actuation Time ……………………………….…….. 37 3.30 High Pressure Valve Actuation Time ………………………………….…… 38

Page 4: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 4 of 155

3.31 Product Diversion Valve Actuation Time ………………………….…… 38 3.32 PPM Conversion Factor ………………………………………………………… 38 3.33 Saving System Set-point Data Changes As Normal User ……….. 39

4. Editing System Set-points (Master User)…..……………………………………..………….. 39

4.1 Entering Set-point Editing Mode As Master User..……….………… 39 4.2 Booster Pump Minimum Inlet Pressure ………………………………… 43 4.3 Booster Pump Maximum Inlet Pressure ……………………………….. 44 4.4 Booster Pump Minimum Outlet Pressure …………………………….. 44 4.5 Booster Pump Maximum Outlet Pressure …………………………….. 44 4.6 Booster Pump Output Error Maximum Operation Time ……….. 45 4.7 ISave Pump Output Error Maximum Operation Time ……………. 45 4.8 Maximum 20u Filter Differential Pressure …………………………….. 45 4.9 Maximum 5u Filter Differential Pressure ……………………..……….. 46 4.10 Minimum Feed System Flow Rate ………………………………….……… 46 4.11 Maximum Feed System Flow Rate …………………………………………. 46 4.12 Minimum ISave System Flow Rate ………………………………………… 47 4.13 Maximum ISave System Flow Rate ………………………………………… 47 4.14 Minimum High Pressure Pump Inlet Pressure ………………………… 47 4.15 Maximum High Pressure Pump Inlet Pressure ………………….……. 48 4.16 Minimum High Pressure Pump Outlet Pressure …………………….. 48 4.17 Maximum High Pressure Pump Outlet Pressure …………………….. 48 4.18 Maximum High Pressure Pump Running Hours ……………….….…. 50 4.19 Maximum ISave Pump Running Hours ……………………………….….. 50 4.20 Maximum Booster Pump Running Hours ….……………………….….. 50 4.21 Maximum Individual Membrane Element Differential ………...… 50 4.22 Maximum Expected Clean Membrane Element Differential ...… 51 4.23 Maximum Permeate Line Pressure …………………………………..……. 51 4.24 Acceptable Maximum Salinity Level …………………………………..….. 51 4.25 Acceptable Minimum Salinity Level ……………………………………..… 52 4.26 Fresh Water Flush Time ……………………………………………………..….. 52 4.27 Minimum Allowable Fresh Water Flush Pressure ..……………..….. 52 4.28 Low Pressure Valve Actuation Time …………………………………..…… 53 4.29 ISave By-Pass Valve Actuation Time ……………………………….….….. 53 4.30 High Pressure Valve Actuation Time ………………………………….…… 53 4.31 Product Diversion Valve Actuation Time ………………………………… 54 4.32 ISave Pump Minimum Discharge Pressure ……………………………… 54 4.33 ISave Pump Maximum Discharge Pressure ……………………………… 54

Page 5: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 5 of 155

4.34 Valve BF-1004 Left Closed Pressure Detection Limit ……………….. 56 4.35 Valve BF-1000 Left Closed Pressure Detection Limit ……………….. 56 4.36 Maximum Allowable System Brine Pressure ………………………….. 56 4.37 System Size Selector ……………………………………………………..……….. 57 4.38 PPM Conversion Factor ………………………………………………………….. 57 4.39 System Time and Date …………………………………………………………... 57 4.40 System Automatic Pressure Control Dead Band Size …………….… 57 4.41 Minimum Allowable Permeate Production Flow Rate …………….. 58 4.42 Maximum Allowable Permeate Production Flow Rate ……………. 58 4.43 Maximum Total Membrane Rack Allowable Differential ………… 59 4.44 High Pressure Pump Minimum Allowable Speed ……………………. 60 4.45 Control Off Period For Auto Pressure Decrease ………………………. 60 4.46 Auto Pressure System Processing Delay Time …………………………. 61 4.47 Control Off Period For Auto Pressure Increase ………………………. 61 4.48 Booster Pump Initial Requested PID Output Pressure ……………. 61 4.49 ISave Pump Stage 1 Requested Rotation Speed …………………….. 61 4.50 ISave Device Speed Triggering Close Of Air Bleed Valve ……….… 62 4.51 ISave Pump Stage 2 Requested Rotation Speed …………………….. 62 4.52 Membrane Air Bleed Purge Time Stage 1 ………………………………. 62 4.53 Membrane Air Bleed Purge Time Stage 2 ………………………………. 62 4.54 High Pressure Pump Requested Rotation Speed ……………………. 63 4.55 Booster Pump Final Requested PID Output Pressure ……………… 63 4.56 ISave Minimum Pressure Before Power Off ……..……………………. 63 4.57 Saving System Set-point Data Changes As Master User ……….... 65

5. Start-Up Operations ……………………………………………………………………………………. 67

5.1 Overview ……………………………………………………………………………… 67 5.2 Automatic Start-up Operation ………..……………………………………. 68

6. Automatic Shutdown Operation …………………………………………………………………. 75

7. Emergency ShutdownOperation ..………………………………………………………………. 76

8. System Critical Error Messages …………………………………………………………………….. 77 8.1 System Fault Codes and Possible Causes ……………………………….. 78

9. System Performance Messages …………………………………………………………………….. 100

9.1 System Performance Notification and Possible Causes ………….. 101

10. System Status Messages ……………………………………………………………………………….. 105

Page 6: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 6 of 155

11. VFD System Status Messages ………………………………………………………………………… 106

12. Menu Navigation …………………………………………………………………………………………… 107 12.1 Accessing The System Operation Screen ………………………….…….. 107 12.2 Accessing VFD System Health Monitors ……………..…………………… 108 12.3 Accessing Feed Water System Health Monitors ………………………. 110 12.4 Accessing High Pressure System Health Monitors …………………… 112 12.5 Accessing Permeate Water System Health Monitors ………………. 114 12.6 Accessing System Logs and Trending ………………………………………. 117 12.7 Accessing TheSystem Pump Hour Meter ………………………………… 118 12.8 Accessing System Message Centers ………………………………………… 120 12.9 Accessing Pressure Sensor Zero Point Calibration Screens ..…… 123 12.10 Accessing Flow Sensor Zero Point Calibration Screens ..……….… 125 12.11 Accessing Salinity Sensor Calibration Screens ………………………… 127 12.12 Accessing The System Information Screen ……………………………… 129

13. System Maintenance …………………………………………………………………………………….. 130 13.1 Performing Pressure Sensor Zero-point Calibrations …...………… 130 13.1 Performing Flow Sensor Zero-point Calibrations …..........………… 133 13.3 Performing Salinity Sensor Calibrations …………………………………. 136

14. Manual Actuation of System Valves ………...…………………………………………………… 139

14.1 Actuating the Membrane Pressure Relief Valve ……………………… 139 14.2 Actuating the Product Diversion Valve …………………………….…….. 141 14.3 Actuating Media Filter Control & Feed Water Valves …………….. 142

15. Fresh Water Flushing ……………………………………………………………………………………. 143 16. Activating Accessories ……………………………………………………………………………………. 145

17. Automatic Multi-Media Filter Functions ....…………………………………………………… 148

17.1 Accessing Multi-Media Filter Options….…….…………………………… 148 17.2 Auto MMF Sequence Delay Time (Minutes) ………..………….…….. 150 17.3 Auto MMF Backwashing Time (Minutes) ……………………………….. 150 17.4 Auto MMF Rinsing Time (Minutes) …………………………………………. 150 17.5 Auto MMF Differential Pressure (PSI) …………………………………….. 151 17.6 Saving Multi-Media filter Option Settings………………………………. 151 17.7 Activating the backwash manually while operating in auto ….. 153 17.8 Automatic activation of the backwash cycle ………………………….. 154 17.9 Activating the backwash manually while in standby ……………… 155

Page 7: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 7 of 155

1.

The Control Panel

6 10 9

8

7

1

2

3

4

5

17

12

14

15

13

11

16

Page 8: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 8 of 155

Item Number Item Description

-------------------------------------------------------------------- 1 Touch Screen Interface 2 Emergency Stop Button 3 System Auto-Start Button 4 Booster Pump Control Operator 5 System Main Power Indicator 6 System Auto-Stop Button 7 High Pressure Pump Status Indicator 8 System Fault Indicator 9 Fresh Water Flush Indicator 10 ISave Pump Status Indicator 11 Media Filter Auto Backwash Button/Indicator 12 Media Filter Auto Rinse Indicator 13 Product Pump Control Operator 14 Chemical Pre-Treatment Control Operator 15 Chemical Post-Treatment control Operator 16 Clean In Place Mode Control Operator 17 Panel Power Disconnect

Page 9: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 9 of 155

The new Atlantic Sea control system incorporates the very latest in powerful control system technology as well as highly intelligent programming. At the core of the control system is the all new 32 bit Programmable Logic Controller (PLC); this device provides constant supervision of your water maker. Should any problem arise during operation this intelligent hardware will first analyze if this fault could possibly damage the water maker, if so it classifies this error as ‘critical’ and performs a rapid shutdown of the unit to prevent damage, rapid shutdowns usually require 10 seconds to complete. However, if the controller deems the current problem as ‘non critical’ the water maker is allowed to continue operating; meanwhile the control system will alert operators that service is required by beeping and displaying a warning notification on the system touch screen; the controller will continue to monitor the situation closely and if the current problem should become ‘critical’ the control system will take action to prevent damage and rapidly shut the water maker down. The reason for the shutdown will be displayed on the system touch screen. This manual has been written to help walk you through the various features offered by the installed control system. During fault situations your water maker control system produces messages to help point you to the root cause of the problem; contained within this manual is a list of trouble shooting tips based on these messages; each tip will detail the likely possibilities which resulted in the call for the associated fault message. The new Atlantic Sea control system also comes with an available Modbus interface. This Modbus interface can be used to create an open communications interface between locally hosted control systems and the Atlantic Sea water maker. Via the Modbus interface it is possible to monitor all control system inputs and outputs; it is also possible to monitor data normally displayed on the control system touch screen including alarm information, performance information, system pressure information and salinity information. For further information on the Modbus interface, please refer to the Atlantic Sea Modbus Specification documentation. The new Atlantic Sea control system also comes with an available Ethernet internet interface. This interface can be used to remotely monitor and control the Atlantic Sea water maker for any computer with browser software within the locally hosted IP network. The system can also be modified to accept remote connections from outside the locally hosted network via use of static IP addressing. When used the internet interface performs as a direct simulation of the system HMI interface, and no special programming is required to facilitate its use. For further information on the internet interface, please refer to the Atlantic Sea Internet Interface Specification documentation.

Page 10: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 10 of 155

2. Initial System Checks/Commissioning.

The new Atlantic Sea control system comes loaded with a special utility tool designed to aid in the initial system checks and commissioning of the system. This utility can be accessed in the following manner.

Please note it is not possible to enter commissioning mode while the water maker is operating. Trying to enter commissioning mode while the unit is running will simply not be permitted, and the commissioning screens shown in this section will fail to appear as stated in this document.

Stop system operation before attempting to enter commissioning mode (including any FWF Activity).

2.1 Entering Commissioning Mode

From the Main Splash screen press the arrow in the lower right corner.

This will take you to the main menu screen. Once here press the arrow next to the ‘System Information’ text, as shown on the next page.

Press Here

Page 11: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 11 of 155

This will take you to the ‘system information‘screen which details various pieces of machine information. Press on the shown area to access the hidden commissioning mode screens.

If the unit was not running and not fresh water flushing, pressing the illustrated area will switch the controller into commissioning mode. This is confirmed by the system information screen being replaced with the first of manydiagnostic screens. This first screen as shown on the next page,details analog inputs currently being received by the controller. This screen can be used to check for proper external sensor functionality. A red indicator as detailed on the example signifies that either the analog channel is disabled or enabled and the input is not present or at fault, if a field instrument is connected to this channel but this indicator remains red, this implies there is a problem with the connected instrument or

Press Here

Press Here

Page 12: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 12 of 155

system wiring, when the indicator is green this implies the channel is enabled and the input is present and as expected (healthy).

Press on the ‘More’ button at the top right corner of the screen to move to the next screen. This will take you to the second commissioning screen. This second screen as shown below,details digitalinputs currently being received by the controller. This screen can be used to check for proper external sensor functionality. A red indicator as detailed on the example signifies that the input is not present; when the indicator is green this implies the input is present. This screen can be used to verify external equipment wiring to devices such as valves and pressure limit switches, it should be noted that pressure limit switches always show as present when within safe operating conditions.

Press Here

Press Here

Page 13: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 13 of 155

Press on the ‘More’ button at the top right corner of the screen to move to the next screen.

This will take you to the third commissioning screen.This third screen as shown below, details control fuse status and control panel door indicator status, this screen can be used to check for control fuse failure and for proper external door lamp functionality. A red indicator as detailed on the example signifies that either the input or output is not present; when the indicator is green this implies the input or output is present or active.

Press on the ‘More’ button at the top right corner of the screen to move to the next screen.

This will take you to the fourth commissioning screen.This fourth screen as shown below, details digital outputs currently being powered (driven) by the controller, this screen can be used to check for proper external equipment functionality. A red indicator as detailed on the example signifies that the output or is not currently active (Off); when the indicator is green this implies the output is currently active (On) and the external device connected should be functioning.

Press Here

Page 14: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 14 of 155

Press on the ‘More’ button at the top right corner of the screen to move to the next screen.

This screen can be used to jog all connected pumps. Each time the jog button is pressed, the pump is remotely commanded to jog for a few seconds, this jog consists of a very slow acceleration and immediate stop. Typically a maximum of 3 full motor rotations will be permitted during each jog request. For a pump to jog successfully, the pump must be enabled, and the pump operator (if applicable) must be in the ‘Off’ position (Center). This screen can also be used to send configuration data to the connected system VFD’s

Details on performing motor rotation checks can be found in section 3.2

Press Here Press Here Press Here Press Here

Press Here Press Here To Exit

Press Here

VFD Setup commands

Page 15: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 15 of 155

If you do not wish to carry out motor rotation checks at this time, press on the ‘More’ button located in the top right hand corner of the screen to move to the ‘System Valve Checks’ screen. Information on valve checks can be found in section 3.3.

Page 16: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 16 of 155

2.2 Motor and Pump Rotation Checks

Step 1.

Once at the motor jog screen press the booster pump button to jog the Booster Pump. Once pressed a command will be sent to the drive system which slowly accelerates the pump motor for a few seconds and then stops it, therefore it is best to carry out this procedure with two people, one who can activate the jog command and one who can watch the pump motor rotation direction. If the Booster Pump motor spins in the direction indicated on the pump motor coupler then proceed to step 2; if the Booster Pump motor does not spin in the correct direction refer to the ‘VFD Controls and Setup’ section of this manual for further instructions on how to change the motor rotation direction. Once you have completed the steps required to change motor rotation direction detailed in the ‘VFD Controls and Setup’ section confirm motor direction is correct by returning to this commissioning screen and running the jog procedure one more time before proceeding any further.

Step 2.

Once correct Booster Pump rotation has been confirmed press the High Pressure Pump button to jog the High Pressure Pumps. Once pressed a command will be sent to the drive systems which slowly accelerate the pump motors for a few seconds and then stops them, therefore it is best to carry out this procedure with two people, one who can activate the jog command and one who can watch the pumps motor rotation direction. If the High Pressure Pump motors spin in the direction indicated on the pump motor casings then proceed to step 3; if the High Pressure Pump motors do not spin in the correct direction refer to the ‘VFD Controls and Setup’ section of this manual for further instructions on how to change the motor rotation direction. Once you have completed the steps required to change motor rotation direction detailed in the ‘VFD Controls and Setup’ section confirm motor direction is correct by returning to this commissioning screen and running the jog procedure one more time before proceeding any further.

Step 3.

Once correct High Pressure Pump rotation has been confirmed press the ISave Pump button to jog the ISave Pump(s). Once pressed a command will be sent to the drive system which slowly accelerates the pump motor for a few seconds and then stops it, therefore it is best to carry out this procedure with two people, one who can activate the jog command and one who can watch the pump motor rotation direction. If the ISave Pump motor spin in the direction indicated on the ISave Pressure Exchanger casings then proceed to step 3; if the ISave Pump motor do not spin in the correct direction refer to the

Page 17: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 17 of 155

‘VFD Controls and Setup’ section of this manual for further instructions on how to change the motor rotation direction. Once you have completed the steps required to change motor rotation direction detailed in the ‘VFD Controls and Setup’ section confirm motor direction is correct by returning to this commissioning screen and running the jog procedure one more time before proceeding any further.

Step 4.

Once correct ISave Pump rotation has been confirmed press the Product Pump button to jog the Product Pump. Once pressed a command will be sent to the contactor which rapidly accelerates the pump motor for a ¼ of a second and then stops it, therefore it is best to carry out this procedure with two people, one who can activate the jog command and one who can watch the pump motor rotation direction. If the Product Pump motor spins in the direction indicated on the pump motor casing then proceed to step 3; if the Product Pump motor does not spin in the correct direction refer to the ‘VFD Controls and Setup’ section of this manual for further instructions on how to change the motor rotation direction. Once you have completed the steps required to change motor rotation direction detailed in the ‘VFD Controls and Setup’ section confirm motor direction is correct by returning to this commissioning screen and running the jog procedure one more time before proceeding any further.

Once these tests have been completed and correct rotation of all connected pumps has been confirmed you may exit commissioning mode by pressing the arrow in the top left corner five times. This will return you to the main operations menu.

Page 18: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 18 of 155

2.3 Valve Operation Checks While viewing the ‘Motor Rotation Checks’ Screen press on the ‘More’ button located in the top right corner of the screen. This will take you to the sixth commissioning screen. This screen can be used to manually drive all of the automatic valves currently connected to the control system. To activate a valve simply press on the action you require. If the tested valve indicates a fault condition, the ‘Fault Log’ button will appear which will allow you to view what fault has been detected.

If the tested valve indicates a fault condition, the ‘Fault Log’ button will appear which will allow you to view what fault has been detected, as shown below.

Press Here

Press Here Press Here Press Here Press Here Press Here

Press Here

Press Here

Page 19: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 19 of 155

Press the ‘Fault Log’ button to be taken to the fault message center screen

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept& Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept& Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

Page 20: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 20 of 155

Once you have successfully tested and confirmed the operation of the valves detailed on the sixth commissioning screen press the ‘More’ button in the top right hand corner of the display to move on to the next screen of valve position check utilities. The seventh commissioning screen titled ‘Media System Checks’ operates in a much similar manner to the last screen, this screen can be used to test the functionality of your automatic media filter valves, as shown below:

Again additional screens are available for testing all elements of the automatic multi-media filter system, press on the arrow in the upper right hand corner of the ‘Media System Checks’ Screen to access these additional valve testing utilityscreens, as shown below:

Again additional screens are available for testing all elements of the automatic multi-media filter system, press on the arrow in the upper right hand corner of the ‘Media System Checks’ Screen to access these additional valve testing utility screens, as shown on the next page:

Press Here

Press Here

Press Here

Press Here

Page 21: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 21 of 155

Again additional screens are available for testing all elements of the automatic multi-media filter system, press on the arrow in the upper right hand corner of the ‘Media System Checks’ Screen to access these additional valve testing utility screens, as shown below:

Again additional screens are available for testing all elements of the automatic multi-media filter system, press on the arrow in the upper right hand corner of the ‘Media System Checks’ Screen to access these additional valve testing utility screens, as shown on the next page:

Press Here

Press Here

Press Here

Press Here

Page 22: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 22 of 155

Once again if the tested valve indicates a fault condition, the ‘Fault Log’ button will appear which will allow you to view what fault has been detected, as shown below:

Press the ‘Fault Log’ button to be taken to the fault message center screen

Press Here

Press Here

Press Here

Page 23: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 23 of 155

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

Once you have successfully tested and confirmed the operation of the multi-media system valves detailed on the seventh thru eleventh commissioning screens press the ‘More’ button in the top right hand corner of the eleventh screen to move on to the next screen of valve position check utilities. The twelfth commissioning screen operates in a much similar manner to the last screen, this screen can be used to test the functionality of your High Pressure Isave Isolation System valve, as shown on the next page:

Page 24: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 24 of 155

If the tested valve indicates a fault condition, the ‘Fault Log’ button will appear which will allow you to view what fault has been detected, as shown below.

Press the ‘Fault Log’ button to be taken to the fault message center screen

Press Here

Press Here

Page 25: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 25 of 155

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

Page 26: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 26 of 155

3. Editing System Set-points (Normal User). The new Atlantic Sea control system comes pre-loaded with typical alarm level set points, system shutdown values, etc. However, these set-points can be accessed and changed should the need arise. It should be noted that changing these configurations is not recommended. Hence access to the system set-point editing mode has been restricted with a password. To gain access to these features, please contact Danfoss Sea Recovery to obtain the required password. 3.1 Entering Set-point Editing ModeAs Normal User

From the Main Splash screen press the arrow in the lower right corner.

This will take you to the main menu screen. Press on the shown area to access the hidden system set-point editing mode screens.

Press Here

Press Here

Page 27: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 27 of 155

Once this area has been pressed the password entry dialogue box will appear. Enter the password given to you by Danfoss Sea Recovery, and press the ‘ENT’ key. To cancel this operation press the ‘CAN’ key as shown below:

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Entering the correct password will bring you to the following screen.

From this screen it is possible to change the following system set-points:

Enter Password and press here

To cancel press here

Press on value to change

Press Here For Next Page

Page 28: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 28 of 155

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated below:

If you enter a value that is not valid for that particular entry field the numerical entry pad will not accept your entry and will instead display a “??”, in order for you to proceed you must enter a value that is within allowable tolerances for that entry field, or press ‘CAN’ to abort set-point entry and return to the old value, allowable tolerances for a particular entry field are listed in the fields description.

3.2 Booster Pump Minimum Inlet Pressure (Absolute) [Range = > 10]

This value determines the alarm level associated with the booster pump inlet pressure. During normal operation the booster pump will pull a small vacuum at its inlet, an excessive vacuum can indicate a feed water problem, when an excessive vacuum is detected the system will not shut down the water maker but it will indicate the problem by flashing the booster pump inlet pressure bar on the feed system monitors page.

Typical values entered here are 10 PSI [ABSOLUTE]

3.3 Booster Pump Maximum Inlet Pressure (Absolute) [Range = <30]

This value determines the alarm level associated with the booster pump inlet pressure. The water maker can function with either just a flooded line or a small amount of positive pressure feeding the booster pump. Too much positive pressure however will result in over pressurization of system components once the system activates the booster pump, hence the amount of positive pressure being feed into the booster pump must be within specifications. If this inlet pressure is above specifications the system will not shutdown the water maker but it will indicate the problem by flashing the booster pump inlet pressure bar on the feed system monitors page.

Typical values entered here are 25 PSI [ABSOLUTE]

Enter desired set-point value here

Enter Value and press here

To cancel press here

Page 29: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 29 of 155

3.4 Booster Pump Minimum Outlet Pressure [Range = > 20 &< 45]

This value determines the alarm and shutdown level associated with the performance output of the booster pump. During normal operation the booster pump output should be in the range of 60 to 80 PSI, when the booster pump output falls below the value set here it is usually because of either mechanical failure within the booster pump, booster pump motor overload trips, or the booster pump has lost prime and is now running dry. Once the system detects the output pressure of the pump has dropped below the value specified here, it will generate an alarm that results in complete shutdown of the water maker.

Typical values entered here are 20 PSI

3.5 Booster Pump Maximum Outlet Pressure [Range = > 60 &< 100]

This value determines the alarm level associated with the performance output of the booster pump. During normal operation the booster pump output should be in the range of 60 to 80 PSI, when the booster pump output rises above the value set here it is usually because of either flow from the pump has been restricted, or inlet pressure into the water maker is above specifications. Once the system detects the output pressure of the pump has exceeded the value specified here, it will not shutdown the water maker generate an alarm that results in complete shutdown of the water maker but it will indicate the problem by flashing the Media Filter Inlet pressure bar on the feed system monitors page.

Typical values entered here are 85 PSI

3.6 Booster Pump Output Error Maximum Operation Time [Range = > 30&<150]

This value determines how many seconds the control system will wait before acknowledging a booster pump output error fault, for example when a value of ‘10’ is entered, the system will not trigger a shutdown unless the output of the booster pump has been detected as below the value set in 4.4 consistently for 10 seconds. This entry field helps eliminate system shutdowns due to momentary fluctuations in booster pump outlet pressure

Typical values entered here are 45 SECONDS

Page 30: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 30 of 155

3.7 ISave Pump Output Error Maximum Operation Time [Range = > 10 &< 30]

This value determines how many seconds the control system will wait before acknowledging an ISave pump output error fault, for example when a value of ‘10’ is entered, the system will not trigger a shutdown unless the output of the ISave pump has been detected as below the pre-set value consistently for 10 seconds. This entry field helps eliminate system shutdowns due to momentary fluctuations in ISave pump outlet pressure

Typical values entered here are 10 SECONDS

3.8 Maximum 20u Filter Differential Pressure [Range = > 10 &< 35]

This value determines at what differential pressure the control system will alert you that the 20u cartridge filter requires replacement, as the cartridge filter begins to fill with dirt, its differential pressure will increase, if a filter is allowed to run with too high a differential pressure bypass can occur, this is potentially dangerous to the health of the water maker therefore it is advised to select a value based on the filter manufactures recommendations. The value also drives the interactive graphic shown on the P&ID and ‘Feed System Monitors’ page, as the filter becomes more and more clogged this graphic will change to give you a visual indication of the current dirt level.

Typical values entered here are 25 PSI

3.9 Maximum 5u Filter Differential Pressure [Range = > 10 &< 35]

This value determines at what differential pressure the control system will alert you that the 5u cartridge filter requires replacement, as the cartridge filter begins to fill with dirt, its differential pressure will increase, if a filter is allowed to run with too high a differential pressure bypass can occur, this is potentially dangerous to the health of the water maker therefore it is advised to select a value based on the filter manufactures recommendations. The value also drives the interactive graphic shown on the P&ID and ‘Feed System Monitors’ page, as the filter becomes more and more clogged this graphic will change to give you a visual indication of the current dirt level.

Typical values entered here are 25 PSI

Page 31: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 31 of 155

3.10 Minimum Feed system Flow Rate [Range = > 300 &< 350]

This value determines at what feed flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 310 GPM. If the control system sees flow drop below the value stated here it will not shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a ‘System Performance Monitor’ alarm indicating the detected problem. If system flow drops below the value specified here it could indicate a high pressure pump or ISave pump failure is imminent.

3.11 Maximum Feed system Flow Rate [Range = > 350 &<400]

This value determines at what feed flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 310 GPM. If the control system sees flow rise above the value stated here it will not immediately shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a performance warning (See Performance Warning Messages) indicating the detected problem. If system flow continues to exceed the value specified here for 2 minutes the control system will shut-down the water maker. High flow rates can be an indication of a breached line/significant leak, therefore after 2 minutes action is taken to protect the integrity of the location in which the water maker is housed.

3.12 Minimum ISave System Flow Rate [Range = < 100]

This value determines at what ISave flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 175 GPM. If the control system sees flow drop below the value stated here it will not shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a ‘System Performance Monitor’ alarm indicating the detected problem. If system flow drops below the value specified here it could indicate that the ISave back pressure regulator is not set correctly and mixing could occur resulting in lowered system production output.

Page 32: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 32 of 155

3.13 Maximum ISave system Flow Rate [Range = < 220]

This value determines at what feed flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 175 GPM. If the control system sees flow rise above the value stated here it will not immediately shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a performance warning (See Performance Warning Messages) indicating the detected problem. If system flow exceeds the value specified here it could indicate that the ISave back pressure regulator is not set correctly and over-flushing could occur resulting in shortened pre-filter system life.

3.14 Minimum High PressurePump Inlet Pressure[Range = > 20 &< 70]

This value determines what the minimum operating inlet pressure of the high pressure pump is. If the unit is in operation but fails to reach or exceed the pressure set-point established here the control system will perform a rapid shutdown of the water maker system to protect system components from damage and will alert the user of this error by raising a System Critical Fault Message (See System Critical Fault Messages)

Typical values entered here are 29 PSI in all pump applications

3.15 Maximum High PressurePump Inlet Pressure[Range = > 45 &< 80]

This value determines what the maximum operating inlet pressure of the high pressure pump is. If the unit is in operation but exceeds the pressure set-point established here the control system will perform a rapid shutdown of the water maker system to protect system components from damage and will alert the user of this error by raising a System Critical Fault Message (See System Critical Fault Messages)

Typical values entered here are 75 PSI in all pump applications

3.16 Minimum High PressurePump OutletPressure[Range = > 300 &< 350]

This value determines what the minimum operating pressure of the high pressure pump system is. If the unit is in operation but fails to reach or exceed the pressure set-point established here the control system will initially alert the user of this error by raising a performance warning (See Performance Warning Messages), if after a predetermined time the operator has failed to rectify the situation the control system will perform an automatic rapid shutdown of the water maker to protect system components from damage.

Typical values entered here are 350 PSI in all pump applications

Page 33: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 33 of 155

3.17 Maximum High Pressure Pump Outlet Pressure[Range = > 500&< 1050]

This value determines what the maximum operating pressure of the high pressure pump system. If the unit is in operation and begins to approach the pressure set-point established here the control system will attempt to prevent the breach of this pressure threshold by accelerating and decelerating system pumps in an attempt to lower recovery rates, if this solution does not aid the over pressure situation the control system will perform an automatic rapid shutdown of the water maker to protect system components from damage.

Typical values entered here are 975 PSI in all pump applications

Press the arrow in the upper right hand corner of the screen to move into the next menu

Pressing the arrow in the top right hand corner of the screen will bring you to the following screen:

Again from this screen it is possible to change the following system set-points:

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated on the next page:

Press on value to change

System Lifetime Operation Timer (Not affected by client hour meter resets)

Press Here To Save Your Settings and Exit These Screens

Page 34: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 34 of 155

If you enter a value that is not valid for that particular entry field the numerical entry pad will not accept your entry and will instead display a “??”, in order for you to proceed you must enter a value that is within allowable tolerances for that entry field, or press ‘CAN’ to abort set-point entry and return to the old value, allowable tolerances for a particular entry field are listed in the fields description.

3.18 Maximum High Pressure Pump Running Hours [Range = > 1950 &< 8050]

The value here determines at what number of operational hours the water maker will call for high pressure pump servicing. Once the entered number of hours is exceeded the system will raise a performance warning (See Performance Warning Messages), stating the high pressure pump is due for servicing. Operation over these hours is allowed, but is not recommended.

Typical values entered here are 8000 Hrs in Danfoss pump applications

3.19 Maximum ISave Pump Running Hours [Range = > 6000 &< 8050]

The value here determines at what number of operational hours the water maker will call for ISave pump servicing. Once the entered number of hours is exceeded the system will raise a performance warning (See Performance Warning Messages), stating the Isave pump is due for servicing. Operation over these hours is allowed, but is not recommended.

Typical values entered here are 8000 Hrs in Danfoss ISave applications

Enter desired set-point value here

Enter Value and press here

To cancel press here

Page 35: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 35 of 155

3.20 Maximum Booster Pump Running Hours [Range = > 1500 &< 3000]

The value here determines at what number of operational hours the water maker will call for booster pump servicing. Once the entered number of hours is exceeded the system will raise a performance warning (See Performance Warning Messages), stating the booster pump is due for servicing. Operation over these hours is allowed, but is not recommended.

Typical values entered here are 2000 Hrs in all applications

3.21 Maximum Individual Membrane Element Differential Pressure [Range = >5 &<20]

This value determines how the controller re-acts to membrane differential pressures. As a membrane becomes fouled the differential pressure across the membrane inlet and outlet ports increases, the control system can be used to monitor the current fouling status of the membranes but this feature is only provided as a visual aid to the operator.

Typical values entered here are 12 PSI in all membrane applications

3.22 Maximum Expected Clean Membrane Element Differential Pressure [Range = >1&<5]

This value determines how the controller re-acts to membrane differential pressures. New from the manufacturer a membrane generates a differential pressure across the membrane inlet and outlet ports. It is important that this initial value be established and correctly set within the control system to allow for correct membrane fouling information.

Typical values entered here are 3 PSI in all Dow &Toray membrane applications

3.23 Maximum Permeate Line Pressure [Range = > 45]

This value determines the alarm level at which the control system will begin notifying you of permeate line back pressure problems, during normal operation the permeate line should never see in excess of 50 PSI of back pressure, excessive back pressure can cause cracking of the carbon filter housings which can lead to leaks and loss of production

Typical values entered here are 45 PSI

Page 36: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 36 of 155

3.24 Acceptable Maximum Salinity Level [Range = > 500 &< 1800]

This value stated in uS/cm determines at what product water conductivity level the system will activate the diversion valve and UV sterilizer (if fitted). It should be noted that during normal operation activation of the diversion valve will only take place once the system has completed start up, and system pressure has been raised above minimum. Once all of these conditions are met, the water maker will begin a 2 minute delay, this delay is provided to allow the product water salinity to drop down to levels that can be accurately monitored, after this delay has expired the control system will begin actively monitoring the product water salinity. Once the product water measured conductivity drops below the number inputted here, the water maker deems the water as acceptable.

Typical values entered here are 1200 uS/cm in all applications

3.25 Acceptable Minimum Salinity Level [Range = > 50 &< 150]

This setting allows you to determine what minimum salinity level from the salinity probe will be accepted. Domestic systems cannot produce product water with salinity lower than the value entered here, therefore any readings below this value causes the water maker control system to reject the salinity probe input under the suspicion that the salinity probe has been removed from the system pipe work and is currently sitting in air. It should be noted that the system has to be fully operation and the salinity reading must be consistently below the value set here for 30 seconds before the system will re-act. Once it has been determined that the salinity probe has been removed from the system pipe work the control system will drop into ‘Manual Salinity Control Operation’ (See Section 6.8)

Typical values entered here are 100 in domestic water applications

3.26 Fresh Water Flush Time [Range = > 300 &< 900]

The value entered here (in seconds) determines how long the fresh water system will operate for once active pumps have been stopped by pressing the ‘Auto-Stop’ button. It should be noted that Fresh Water Flush mode can only be activated when shutting the system down using the “Auto-Stop’ button, any other method of shutdown excluding automatic backwashes will de-activate the Fresh Water Flushing Mode for that occurrence. Once the allotted time has expired the fresh water flush system will enter a dormant mode for 7 days before repeating the flushing cycle. The dormant cycle of 7 days is not alterable by the system user.

Typical values entered here are 600 Seconds in all applications

Page 37: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 37 of 155

3.27 Minimum Allowable Fresh Water Flush Pressure [Range = > 15 &< 60]

This value determines the alarm level associated with Fresh Water Flushing faults. In order for the fresh water flush system to operate correctly there must be sufficient pressure in the system to ensure the high pressure pump bypass check valve opens. If there is not sufficient pressure to allow this, the control system will raise an alarm to notify the operator that Fresh Water Flushing is not taking place as designed. It should be noted that during a Fresh Water Flushing Cycle the incoming fresh water pressure must be below the value entered here consistently for 60 seconds before the control system will re-act to it.

Typical values entered here are 30 PSI in all applications

3.28 Low Pressure Valve Actuation Time [Range = > 10 &< 25]

The value entered here (in seconds) determines how long the control system will wait for movement of an automated low pressure valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 15 Seconds in all applications

3.29 ISave By-pass Valve Actuation Time [Range = > 5 &< 35]

The value entered here (in seconds) determines how long the control system will wait for movement of an automated ISave By-pass valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 8 Seconds in all applications

Page 38: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 38 of 155

3.30 High Pressure Valve Actuation Time [Range = > 2 &< 15]

The value entered here (in seconds) determines how long the control system will wait for movement of an automated high pressure valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 4 Seconds in all applications

3.31 Product Diversion Valve Actuation Time [Range = > 10 &< 45]

The value entered here (in seconds) determines how long the control system will wait for movement of a the product diversion valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 35 Seconds in all applications

3.32 PPM Conversion Factor

Europe and the US use different scaling factors when converting uS/cm in to PPM. Within the US a scaling factor of approximately 0.5 is used, within Europe a factor of 0.67 is used. Press on the conversion factor you desire, once set the selected conversion factor button will remain depressed. Changing this scaling factor results in a different bar and numbering system on the product water salinity monitoring page when ‘PPM’ is selected as the preferred viewing unit.

Page 39: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 39 of 155

3.33 Saving System Set-point Data ChangesAs Normal User

Once you have completed your system changes you must save your data before being allowed to exit the system set-point editing screens. To save your changes navigate to the final set-point editing screen and press the ‘Save Settings To EEPROM’ button as shown below:

If you do not save your settings by pressing the button as shown, the system will automatically save your settings if it monitors that you have not touched the touch screen for 60 seconds, in either case when system settings are being saved the following screen will be shown briefly. Once the saving procedure has been completed, the controller will return to the main splash screen as illustrated below:

Press Here

Page 40: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 40 of 155

4. Editing System Set-points (Master User). The new Atlantic Sea control system comes pre-loaded with typical alarm level set points, system shutdown values, etc. However, these set-points can be accessed and changed should the need arise. It should be noted that changing these configurations is not recommended. Hence access to the system set-point editing mode has been restricted with a password. To gain access to these features, please contact Danfoss Sea Recovery to obtain the required password. 4.1 Entering Set-point Editing ModeAs Master User

From the Main Splash screen press the arrow in the lower right corner.

This will take you to the main menu screen. Press on the shown area to access the hidden system set-point editing mode screens.

Press Here

Press Here

Page 41: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 41 of 155

Once this area has been pressed the password entry dialogue box will appear. Enter the password given to you by Danfoss Sea Recovery, and press the ‘ENT’ key. To cancel this operation press the ‘CAN’ key as shown below.

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Entering the correct password will bring you to the following screen.

Enter Password and press here

To cancel press here

Press Here To Enter Master User Settings

Page 42: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 42 of 155

Once this area has been pressed the password entry dialogue box will appear. Enter the password given to you by Danfoss Sea Recovery, and press the ‘ENT’ key. To cancel this operation press the ‘CAN’ key as shown on the next page.

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Entering the correct password will bring you to the following screen.

From this screen it is possible to change the following system set-points:

Enter Password and press here

To cancel press here

Please Note: ‘Master User Button’ No Longer Available

Press Here For Next Page

Page 43: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 43 of 155

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated below:

As a master user there are no limitations on values that you can enter in a specific field. As a master user it should be noted that you can alter set-point data outside of that originally established at DSRC factory, entry of data in this mode should only be attempted by a skilled representative of DSRC or by an operator under the direct guidance of DSRC technical staff. Entry of data in this mode that is not sanctioned by DSRC will result in all warranties of the equipment being voided.

4.2 Booster Pump Minimum Inlet Pressure (Absolute) [Range = No Limit]

This value determines the alarm level associated with the booster pump inlet pressure. During normal operation the booster pump will pull a small vacuum at its inlet, an excessive vacuum can indicate a feed water problem, when an excessive vacuum is detected the system will not shut down the water maker but it will indicate the problem by flashing the booster pump inlet pressure bar on the feed system monitors page.

Typical values entered here are 10 PSI [ABSOLUTE]

Enter desired set-point value here

Enter Value and press here

To cancel press here

Page 44: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 44 of 155

4.3 Booster Pump Maximum Inlet Pressure (Absolute) [Range = No Limit]

This value determines the alarm level associated with the booster pump inlet pressure. The water maker can function with either just a flooded line or a small amount of positive pressure feeding the booster pump. Too much positive pressure however will result in over pressurization of system components once the system activates the booster pump, hence the amount of positive pressure being feed into the booster pump must be within specifications. If this inlet pressure is above specifications the system will not shutdown the water maker but it will indicate the problem by flashing the booster pump inlet pressure bar on the feed system monitors page.

Typical values entered here are 25 PSI [ABSOLUTE]

4.4 Booster Pump Minimum Outlet Pressure [Range = No Limit]

This value determines the alarm and shutdown level associated with the performance output of the booster pump. During normal operation the booster pump output should be in the range of 60 to 80 PSI, when the booster pump output falls below the value set here it is usually because of either mechanical failure within the booster pump, booster pump motor overload trips, or the booster pump has lost prime and is now running dry. Once the system detects the output pressure of the pump has dropped below the value specified here, it will generate an alarm that results in complete shutdown of the water maker.

Typical values entered here are 20 PSI

4.5 Booster Pump Maximum Outlet Pressure [Range = No Limit]

This value determines the alarm level associated with the performance output of the booster pump. During normal operation the booster pump output should be in the range of 60 to 80 PSI, when the booster pump output rises above the value set here it is usually because of either flow from the pump has been restricted, or inlet pressure into the water maker is above specifications. Once the system detects the output pressure of the pump has exceeded the value specified here, it will not shutdown the water maker generate an alarm that results in complete shutdown of the water maker but it will indicate the problem by flashing the Media Filter Inlet pressure bar on the feed system monitors page.

Typical values entered here are 85 PSI

Page 45: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 45 of 155

4.6 Booster Pump Output Error Maximum Operation Time [Range = No Limit]

This value determines how many seconds the control system will wait before acknowledging a booster pump output error fault, for example when a value of ‘10’ is entered, the system will not trigger a shutdown unless the output of the booster pump has been detected as below the value set in 4.4 consistently for 10 seconds. This entry field helps eliminate system shutdowns due to momentary fluctuations in booster pump outlet pressure

Typical values entered here are 45 SECONDS

4.7 ISave Pump Output Error Maximum Operation Time [Range = No Limit]

This value determines how many seconds the control system will wait before acknowledging an ISave pump output error fault, for example when a value of ‘10’ is entered, the system will not trigger a shutdown unless the output of the ISave pump has been detected as below the pre-set value consistently for 10 seconds. This entry field helps eliminate system shutdowns due to momentary fluctuations in ISave pump outlet pressure

Typical values entered here are 10 SECONDS

4.8 Maximum 20u Filter Differential Pressure [Range = No Limit]

This value determines at what differential pressure the control system will alert you that the 20u cartridge filter requires replacement, as the cartridge filter begins to fill with dirt, its differential pressure will increase, if a filter is allowed to run with too high a differential pressure bypass can occur, this is potentially dangerous to the health of the water maker therefore it is advised to select a value based on the filter manufactures recommendations. The value also drives the interactive graphic shown on the P&ID and ‘Feed System Monitors’ page, as the filter becomes more and more clogged this graphic will change to give you a visual indication of the current dirt level.

Typical values entered here are 25 PSI

Page 46: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 46 of 155

4.9 Maximum 5u Filter Differential Pressure [Range = No Limit]

This value determines at what differential pressure the control system will alert you that the 5u cartridge filter requires replacement, as the cartridge filter begins to fill with dirt, its differential pressure will increase, if a filter is allowed to run with too high a differential pressure bypass can occur, this is potentially dangerous to the health of the water maker therefore it is advised to select a value based on the filter manufactures recommendations. The value also drives the interactive graphic shown on the P&ID and ‘Feed System Monitors’ page, as the filter becomes more and more clogged this graphic will change to give you a visual indication of the current dirt level.

Typical values entered here are 25 PSI

4.10 Minimum Feed system Flow Rate [Range = No Limit]

This value determines at what feed flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 310 GPM. If the control system sees flow drop below the value stated here it will not shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a ‘System Performance Monitor’ alarm indicating the detected problem. If system flow drops below the value specified here it could indicate a high pressure pump or ISave pump failure is imminent.

4.11 Maximum Feed system Flow Rate [Range = No Limit]

This value determines at what feed flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 310 GPM. If the control system sees flow rise above the value stated here it will not immediately shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a performance warning (See Performance Warning Messages) indicating the detected problem. If system flow continues to exceed the value specified here for 2 minutes the control system will shutdown the water maker. High flow rates can be an indication of a breached line/significant leak, therefore after 2 minutes action is taken to protect the integrity of the location in which the water maker is housed.

Page 47: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 47 of 155

4.12 Minimum ISave system Flow Rate [Range = No Limit]

This value determines at what ISave flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 175 GPM. If the control system sees flow drop below the value stated here it will not shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a ‘System Performance Monitor’ alarm indicating the detected problem. If system flow drops below the value specified here it could indicate that the ISave back pressure regulator is not set correctly and mixing could occur resulting in lowered system production output.

4.13 Maximum ISave system Flow Rate [Range = No Limit]

This value determines at what feed flow rate the control system will alert you that the system is experiencing difficulty. During normal operation the control system would expect to see approximately 175 GPM. If the control system sees flow rise above the value stated here it will not immediately shutdown the water maker but it will indicate the problem by flashing the feed system flow rate bar on the feed system monitors page, it will also raise a performance warning (See Performance Warning Messages) indicating the detected problem. If system flow exceeds the value specified here it could indicate that the ISave back pressure regulator is not set correctly and over-flushing could occur resulting in shortened pre-filter system life.

4.14 Minimum High PressureInlet Pressure[Range = No Limit]

This value determines what the minimum operating inlet pressure of the high pressure pump is. If the unit is in operation but fails to reach or exceed the pressure set-point established here the control system will perform a rapid shutdown of the water maker system to protect system components from damage and will alert the user of this error by raising a System Critical Fault Message (See System Critical Fault Messages)

Typical values entered here are 29 PSI in all pump applications

Page 48: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 48 of 155

4.15 Maximum High PressureInlet Pressure[Range = No Limit]

This value determines what the maximum operating inlet pressure of the high pressure pump is. If the unit is in operation but exceeds the pressure set-point established here the control system will perform a rapid shutdown of the water maker system to protect system components from damage and will alert the user of this error by raising a System Critical Fault Message (See System Critical Fault Messages)

Typical values entered here are 75 PSI in all pump applications

4.16 Minimum High PressurePump Outlet Pressure[Range = No Limit]

This value determines what the minimum operating pressure of the high pressure pump system is. If the unit is in operation but fails to reach or exceed the pressure set-point established here the control system will initially alert the user of this error by raising a performance warning (See Performance Warning Messages), if after a predetermined time the operator has failed to rectify the situation the control system will perform an automatic rapid shutdown of the water maker to protect system components from damage.

Typical values entered here are 350 PSI in all pump applications

4.12 Maximum High Pressure Pump Outlet Pressure[Range = No Limit]

This value determines what the maximum operating pressure of the high pressure pump system. If the unit is in operation and begins to approach the pressure set-point established here the control system will attempt to prevent the breach of this pressure threshold by accelerating and decelerating system pumps in an attempt to lower recovery rates, if this solution does not aid the over pressure situation the control system will perform an automatic rapid shutdown of the water maker to protect system components from damage.

Typical values entered here are 975 PSI in all pump applications

Press the arrow in the upper right hand corner of the screen to move into the next menu

Page 49: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 49 of 155

Pressing the arrow in the top right hand corner of the screen will bring you to the following screen:

Again from this screen it is possible to change the following system set-points:

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated below:

As a master user there are no limitations on values that you can enter in a specific field. As a master user it should be noted that you can alter set-point data outside of that originally established at DSRC factory, entry of data in this mode should only be attempted by a skilled representative of DSRC or by an operator under the direct guidance of DSRC technical staff. Entry of data in this mode that is not sanctioned by DSRC will result in all warranties of the equipment being voided.

Press on value to change

Press Here For Next Page

Enter desired set-point value here

Enter Value and press here

To cancel press here

Page 50: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 50 of 155

4.18 Maximum High Pressure Pump Running Hours [Range = No Limit]

The value here determines at what number of operational hours the water maker will call for high pressure pump servicing. Once the entered number of hours is exceeded the system will raise a performance warning (See Performance Warning Messages), stating the high pressure pump is due for servicing. Operation over these hours is allowed, but is not recommended.

Typical values entered here are 8000 Hrs in Danfoss pump applications

4.19 Maximum ISave Pump Running Hours [Range = No Limit]

The value here determines at what number of operational hours the water maker will call for ISave pump servicing. Once the entered number of hours is exceeded the system will raise a performance warning (See Performance Warning Messages), stating the Isave pump is due for servicing. Operation over these hours is allowed, but is not recommended.

Typical values entered here are 8000 Hrs in Danfoss ISave applications

4.20 Maximum Booster Pump Running Hours [Range = No Limit]

The value here determines at what number of operational hours the water maker will call for booster pump servicing. Once the entered number of hours is exceeded the system will raise a performance warning (See Performance Warning Messages), stating the booster pump is due for servicing. Operation over these hours is allowed, but is not recommended.

Typical values entered here are 2000 Hrs in all applications

4.21 Maximum Individual Membrane Element Differential Pressure [Range = No Limit]

This value determines how the controller re-acts to membrane differential pressures. As a membrane becomes fouled the differential pressure across the membrane inlet and outlet ports increases, the control system can be used to monitor the current fouling status of the membranes but this feature is only provided as a visual aid to the operator.

Typical values entered here are 12 PSI in all membrane applications

Page 51: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 51 of 155

4.22 Maximum Expected Clean Membrane Element Differential Pressure [Range = No Limit]

This value determines how the controller re-acts to membrane differential pressures. New from the manufacturer a membrane generates a differential pressure across the membrane inlet and outlet ports. It is important that this initial value be established and correctly set within the control system to allow for correct membrane fouling information.

Typical values entered here are 3 PSI in all Dow &Toray membrane applications

4.23 Maximum Permeate Line Pressure [Range = No Limit]

This value determines the alarm level at which the control system will begin notifying you of permeate line back pressure problems, during normal operation the permeate line should never see in excess of 50 PSI of back pressure, excessive back pressure can cause cracking of the carbon filter housings which can lead to leaks and loss of production

Typical values entered here are 45 PSI in all applications

4.24 Acceptable Maximum Salinity Level [Range = No Limit]

This value stated in uS/cm determines at what product water conductivity level the system will activate the diversion valve and UV sterilizer (if fitted). It should be noted that during normal operation activation of the diversion valve will only take place once the system has completed start up, and system pressure has been raised above minimum. Once all of these conditions are met, the water maker will begin a 2 minute delay, this delay is provided to allow the product water salinity to drop down to levels that can be accurately monitored, after this delay has expired the control system will begin actively monitoring the product water salinity. Once the product water measured conductivity drops below the number inputted here, the water maker deems the water as acceptable.

Typical values entered here are 1200 uS/cm in all applications

Page 52: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 52 of 155

4.25 Acceptable Minimum Salinity Level [Range = No Limit]

This setting allows you to determine what minimum salinity level from the salinity probe will be accepted. Domestic systems cannot produce product water with salinity lower than the value entered here, therefore any readings below this value causes the water maker control system to reject the salinity probe input under the suspicion that the salinity probe has been removed from the system pipe work and is currently sitting in air. It should be noted that the system has to be fully operation and the salinity reading must be consistently below the value set here for 30 seconds before the system will re-act. Once it has been determined that the salinity probe has been removed from the system pipe work the control system will fault and rapidly shutdown

Typical values entered here are 100 in domestic water applications

4.26 Fresh Water Flush Time [Range = No Limit]

The value entered here (in seconds) determines how long the fresh water system will operate for once active pumps have been stopped by pressing the ‘Auto-Stop’ button. It should be noted that Fresh Water Flush mode can only be activated when shutting the system down using the “Auto-Stop’ button, any other method of shutdown excluding automatic backwashes will de-activate the Fresh Water Flushing Mode for that occurrence. Once the allotted time has expired the fresh water flush system will enter a dormant mode for 7 days before repeating the flushing cycle. The dormant cycle of 7 days is not alterable by the system user.

Typical values entered here are 600 Seconds in all applications

4.27 Minimum Allowable Fresh Water Flush Pressure [Range = No Limit]

This value determines the alarm level associated with Fresh Water Flushing faults. In order for the fresh water flush system to operate correctly there must be sufficient pressure in the system to ensure the high pressure pump bypass check valve opens. If there is not sufficient pressure to allow this, the control system will raise an alarm to notify the operator that Fresh Water Flushing is not taking place as designed. It should be noted that during a Fresh Water Flushing Cycle the incoming fresh water pressure must be below the value entered here consistently for 60 seconds before the control system will re-act to it.

Typical values entered here are 30 PSI in all applications

Page 53: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 53 of 155

4.28 Low Pressure Valve Actuation Time [Range = No Limit]

The value entered here (in seconds) determines how long the control system will wait for movement of an automated low pressure valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 15 Seconds in all applications

4.29 ISave By-pass Valve Actuation Time [Range = No Limit]

The value entered here (in seconds) determines how long the control system will wait for movement of an automated ISave By-pass valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 8 Seconds in all applications

4.30 High Pressure Valve Actuation Time [Range = No Limit]

The value entered here (in seconds) determines how long the control system will wait for movement of an automated high pressure valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 4 Seconds in all applications

Page 54: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 54 of 155

4.31 Product Diversion Valve Actuation Time [Range = No Limit]

The value entered here (in seconds) determines how long the control system will wait for movement of a the product diversion valve to complete. If the correct feedback from the valve has not been received before this time expires, the system will either generate a performance warning, or shutdown the unit and generate a fault warning, the action taken depends on what operational state the water maker was in at the time of failure. It should be noted that entering a value that is less than the stated actuator actuation time will result in constant errors from the control system. This value is pre-set at DSRC and should not be changed unless you are instructed to do so by a member of DSRC technical support staff.

Typical values entered here are 35 Seconds in all applications

4.32 ISave Pump Minimum Discharge Pressure [Range = No Limit]

The value entered here (in PSI) determines the minimum allowable ISave discharge pressure. If discharge pressures fall below this set-point the control system will initiate a rapid shutdown of the system and alert the user by presenting a system Critical Error Fault Message (Please see System Critical Fault Messages)

Typical values entered here are 14 PSI in all applications

4.33 ISave Pump Maximum Discharge Pressure [Range = No Limit]

The value entered here (in PSI) determines the maximum allowable ISave discharge pressure. If discharge pressures rise above this set-point the control system will initiate a rapid shutdown of the system and alert the user by presenting a system Critical Error Fault Message (Please see System Critical Fault Messages)

Typical values entered here are 20 PSI in all applications

Press the arrow in the upper right hand corner of the screen to move into the next menu

Page 55: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 55 of 155

Pressing the arrow in the top right hand corner of the screen will bring you to the following screen:

Again from this screen it is possible to change the following system set-points:

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated below:

As a master user there are no limitations on values that you can enter in a specific field. As a master user it should be noted that you can alter set-point data outside of that originally established at DSRC factory, entry of data in this mode should only be attempted by a skilled representative of DSRC or by an operator under the direct guidance of DSRC technical staff. Entry of data in this mode that is not sanctioned by DSRC will result in all warranties of the equipment being voided.

Press on value to change

Enter desired set-point value here

Enter Value and press here

To cancel press here

System Size Notification Window

System Size Selection Button

Manual System Size Program Button

System Lifetime Operation Timer (Not affected by client hour meter resets)

Press Here For Next Page

Page 56: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 56 of 155

4.34 Valve BF-1004 Left Closed Pressure Detection Limit [Range = No Limit]

During normal operation the control system measures differential pressures across various sections of system pipework, this is done to determine if manual valves located within this pipework section that provide no position feedback to the control have been positioned correctly. If differential pressures across these sections of pipe work exceed the values set here (in PSI) the control system can safely establish that the system pipe work manual valves are not positioned correctly and can shut the system down safely thus preventing any damage

Typical values entered here are 50 PSI on all systems

4.35 Valve BF-1000 Left Closed Pressure Detection Limit [Range = No Limit]

During normal operation the control system measures differential pressures across various sections of system pipework, this is done to determine if manual valves located within this pipework section that provide no position feedback to the control have been positioned correctly. If differential pressures across these sections of pipe work exceed the values set here (in PSI) the control system can safely establish that the system pipe work manual valves are not positioned correctly and can shut the system down safely thus preventing any damage

Typical values entered here are 50 PSI on all systems

4.36 Maximum Allowable System Brine Pressure (PSI) [Range = No Limit]

This value (in PSI) determines at what detected pressure the emergency brine monitoring system will trigger an emergency brine isolation protocol event. This value should NOT be altered unless specifically told to do so by a Danfoss Sea Recovery Engineer. Altering this value could cause significant damage to the system in an emergency brine blockage event.

Typical values entered here are 75 PSI on all systems

Page 57: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 57 of 155

4.37 System Size Selector

Pressing this button causes the control system scroll through the available system recovery sizes within Atlantic Sea product line, each time the button is pressed the system will increment to the next available size as listed here: 250, 350, 500, 720 & 1000. Once the maximum system size has been reached pressing the system size selection button again will cause the system to return the beginning of the list.

4.38 PPM Conversion Factor

Europe and the US use different scaling factors when converting uS/cm in to PPM. Within the US a scaling factor of approximately 0.5 is used, within Europe a factor of 0.67 is used. Press on the conversion factor you desire, once set the selected conversion factor button will remain depressed. Changing this scaling factor results in a different bar and numbering system on the product water salinity monitoring page when ‘PPM’ is selected as the preferred viewing unit.

4.39 System Time and Date

This will allow you to change the time and date stored within the touch screen. To access this high level editing screen an additional password is required. Contact Danfoss Sea Recovery for further details.

4.40 System Automatic Pressure Control Dead Band Size (PSI)

During automatic system pressure control operation the control system is constantly trying to keep system pressure at the desired set-point, to prevent the system from continuously hunting back and forth around the desired pressure set-point the control algorithm has a dead band setting. This setting allows the control system to pause automatic pressure control providing the system operation pressure is within +/- the value established here. For example if 30 PSI is set, the control system will attempt to reduce system operational pressures to the desired set-point (i.e. 975 PSI). Providing the operational system pressure is within +/- 15 PSI of the desired set-point the auto pressure control algorithm with pause to prevent hunting, meaning system pressures will range between 960 to 990 PSI before any further automatic pressure control action is taken.

Typical values entered here are 20 PSI on all systems

Page 58: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 58 of 155

4.41 Minimum Allowable Permeate Production Flow Rate [Range = No Limit]

* Please note: *

Entering data into this field is only permitted if the user has selected ‘Manual System Production Variable Settings’, confirmation that this mode is enabled is given by the ‘System Size Notification Window’. Once manual settings are enabled the text within the window will change from a standard system production size to ‘MANUAL MODE’. To enter manual mode, press the ‘Manual System Production Variable Settings’ button.

This value determines what minimum permeate flow rates the controller should expect to see during normal operation, if the controller sees permeate flow rates drop below this level consistently for 60 seconds it will alert you by raising a performance warning (See Performance Warning Messages) indicating the detected problem, the water maker will not shut down and will continue to function at these lower permeate flow rates. However attempts should be made to discover why permeate flow rates have fallen.

Normal values are automatically entered here as system sizes are adjusted using the ‘System Size Selector’ button. However in manual mode any value can be entered here.

4.42 Maximum Allowable Permeate Production Flow Rate [Range = No Limit]

* Please note: *

Entering data into this field is only permitted if the user has selected ‘Manual System Production Variable Settings’, confirmation that this mode is enabled is given by the ‘System Size Notification Window’. Once manual settings are enabled the text within the window will change from a standard system production size to ‘MANUAL MODE’. To enter manual mode, press the ‘Manual System Production Variable Settings’ button.

This value determines what maximum permeate flow rates the controller should expect to see during normal operation, if the controller sees permeate flow rates rise above this level consistently for 60 seconds it will alert you by raising a performance warning (See Performance Warning Messages) indicating the detected problem, the water maker will not shut down and will continue to function at these higher permeate flow rates. However attempts should be made to discover why permeate flow rates have risen, and corrections performed to bring them back to within normal levels before membrane damage occurs.

Normal values are automatically entered here as system sizes are adjusted using the ‘System Size Selector’ button. However in manual mode any value can be entered here

Page 59: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 59 of 155

4.43 Maximum Total Membrane Rack Allowable Pressure Differential [Range = No Limit]

This value determines the calculated pressure differential allowable for the connected/configured membrane rack. This number should not be tampered with unless absolutely required. This number is only valid once the system commissioning engineer has successfully set up the ‘Maximum Individual Membrane Element Differential Pressure’ (5.16) entry field. This number is used by the system to calculate the current membrane fouling state and drive the indication graphic in the ‘Monitors’ section

Press the arrow in the upper right hand corner of the screen to move into the next menu

Pressing the arrow in the top right hand corner of the screen will bring you to the following screen:

Again from this screen it is possible to change the following system set-points:

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated on the next page:

Press on value to change

Press Here For Next Page

Page 60: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 60 of 155

As a master user there are no limitations on values that you can enter in a specific field. As a master user it should be noted that you can alter set-point data outside of that originally established at DSRC factory, entry of data in this mode should only be attempted by a skilled representative of DSRC or by an operator under the direct guidance of DSRC technical staff. Entry of data in this mode that is not sanctioned by DSRC will result in all warranties of the equipment being voided.

4.44 High Pressure Pump Minimum Allowable Speed [Range = No Limit]

This value (in RPM) determines at which operation point the control system will stop automatic pressure control and rapidly shutdown the water maker. This setting comes into effect when automatic pressure control is reducing the RPM of the high pressure pumps in an attempt to keep system pressure below the threshold set-point. If the high pressure pumps are requested to slow down to this minimum allowable speed this indicates something has gone seriously wrong with the high pressure system and represents the possibility of high mixing within the ISave device. At this point the system must be shutdown to avoid any damage

Typical Values set here are 600 RPM in all applications

4.45 Control Off Period For Auto Pressure Decrease [Range = No Limit]

This value (in Seconds) determines the sample and processing rate of the automatic pressure control algorithm, the algorithm samples system data and acts upon this data after this control period has expired, this control period is only used when the algorithm is assessing the system pressure and detects that a reduction in pressure is required.

Typical values entered here are 5 seconds in all applications

Enter desired set-point value here

Enter Value and press here

To cancel press here

Page 61: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 61 of 155

4.46 Auto Pressure System Processing Delay Time [Range = No Limit]

This value (in Seconds) determines the processing delay time required by the automatic pressure control algorithm, the algorithm samples system data and acts upon this data after this control period has expired, this control period is always used and system pressure increase or decrease requests must be present for this period of time before the control algorithm will act to correct them.

Typical values entered here are 10 seconds in all applications

4.47 ControlOff Period For Auto Pressure Increase [Range = No Limit]

This value (in Seconds) determines the sample and processing rate of the automatic pressure control algorithm, the algorithm samples system data and acts upon this data after this control period has expired, this control period is only used when the algorithm is assessing the system pressure and detects that an increase in pressure is required.

Typical values entered here are 60 seconds in all applications

4.48 Booster Pump Initial Requested PID Output Pressure [Range = No Limit]

This value (in PSI) determines the target output pressure of the system booster pump during the first stage of automatic system start up. Once activated the control system will steadily accelerate the booster pump until this requested pressure is achieved at the input of the High Pressure pumps

Typical values entered here are 40 PSI in all applications

4.49 ISave Pump Stage 1 Requested Rotation Speed [Range = No Limit]

This value (in RPM) determines the target output speed of the ISave energy recovery device during the first stage of automatic system start up. Once required the control system will steadily accelerate the ISave device up to this requested speed where is will hold this speed until requested to enter stage 2 of the start-up process.

Typical values entered here are 750 RPM in all applications

Page 62: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 62 of 155

4.50 ISave Device Speed Triggering Close Of Air Bleed Valve [Range = No Limit]

This value (in RPM) determines which target output speed of the ISave device will trigger the closing of the system membrane air bleed valve. During automatic start up this valve is always open. However as the ISave device begins to accelerate this valve must be closed to prevent cavitation of the ISave pressure exchanger.

Typical values entered here are 300 RPM in all applications

4.51 ISave Pump Stage 2 Requested Rotation Speed [Range = No Limit]

This value (in RPM) determines the target output speed of the ISave energy recovery device during the second stage of automatic system start up. Once required the control system will steadily accelerate the ISave device up to this requested speed which completes the start-up process for the ISave device

Typical values entered here are 1160 RPM in all applications

4.52 Membrane Air Bleed Purge Time Stage 1 [Range = No Limit]

This value (in Seconds) determines how long the control system will suspend automatic start-up of the system to allow air within the high pressure system to be purged. This delay time is used only in stage 1 of system start up and delays the initial activation of the ISave device until air has been purged.

Typical values entered here are 300 Seconds in all applications

4.53 Membrane Air Bleed Purge Time Stage 2 [Range = No Limit]

This value (in Seconds) determines how long the control system will suspend automatic start-up of the system to allow air within the high pressure system to be purged. This delay time is used only in stage 2 of system start up and delays the acceleration of the ISave device up to stage 2 speeds until remaining air has been purged from the system using the over flush technique.

Typical values entered here are 60 Seconds in all applications

Page 63: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 63 of 155

4.54 High Pressure Pump Requested Rotation Speed [Range = No Limit]

This value (in RPM) determines the target output speed of the High Pressure pumps. Once required the control system will steadily accelerate the High Pressure Pumps up to this requested speed which completes the start-up process for the High Pressure Pumping System

Typical values entered here are 1160 RPM in all applications

4.55 Booster Pump Final Requested PID Output Pressure [Range = No Limit]

This value (in PSI) determines the target output pressure of the system booster pump during the final stage of automatic system start up. Once activated the control system will steadily decelerate the booster pump until this requested pressure is achieved at the input of the High Pressure pumps

Typical values entered here are 34 PSI in all applications

4.56 ISave Minimum Pressure Before Power Off [Range = No Limit]

This value (in PSI) determines the maximum target pressure of the membrane system allowable before system shutdown can complete. During automatic shutdown the control system initially stops the high pressure pump, and then decelerates the ISave device back down to speeds set in stage 1 of the ISave start-up (4.49). Once this target RPM has been reached the control system delays further shutdown of the unit until system membrane pressures have dropped to below the value set here. Once this target pressure has been released the control system will initiate a full shutdown of the ISave device along with requesting the membrane air bleed valve to open to release any remaining pressure held in the membrane system.

Typical values entered here are 300 PSI in all applications

Press the arrow in the upper right hand corner of the screen to move into the next menu

Page 64: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 64 of 155

Pressing the arrow in the top right hand corner of the screen will bring you to the following screen:

From this screen it is possible to change system PID control set-points:

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated on the next page:

As a master user there are no limitations on values that you can enter in a specific field. As a master user it should be noted that you can alter set-point data outside of that originally established at DSRC factory, entry of data in this mode should only be attempted by a skilled representative of DSRC or by an operator under the direct guidance of DSRC technical staff. Entry of data in this mode that is not sanctioned by DSRC will result in all warranties of the equipment being voided.

Press on value to change

Enter desired set-point value here

Enter Value and press here

To cancel press here

Press Here To Save Your Settings and Exit These Screens

Page 65: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 65 of 155

Many system PID set-points can be altered from this screen, however it is not encouraged. These system set-points should only be changed under direct instruction from a DSRC representative hence no descriptions of these setting as provided in this manual. Altering these set-points without expert knowledge of system software design can result in server instability. Please contact DSRC personnel before attempting to make changes to settings located here. Any attempt to alter these settings creates a change log which can be accessed by DSRC personnel. Any authorized changes can result in DSRC voiding system warranties

4.57 Saving System Set-point Data ChangesAs Master User

Once you have completed your system changes you must save your data before being allowed to exit the system set-point editing screens. To save your changes navigate to the final set-point editing screen and press the ‘Save Settings To EEPROM’ button as shown below:

Next Page

Page 66: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 66 of 155

If you do not save your settings by pressing the button as shown, the system will automatically save your settings if it monitors that you have not touched the touch screen for 60 seconds, in either case when system settings are being saved the following screen will be shown briefly. Once the saving procedure has been completed, the controller will return to the main splash screen as illustrated on the next page:

Once the system has returned to the main splash screen, set-point data saving is complete and ‘Master User’ Editing mode is canceled. To enter set-point data as a master user entry into the master set-point editing mode must be carried out once again as detailed in section 5.1.

Prev. Page

Press Here

Page 67: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 67 of 155

5. Start-Up Operations

5.1 Overview

The new Atlantic Sea control system has an extremely complicated and comprehensive automatic start up control program designed to start up and monitor all aspects of the water maker system to ensure correct operation. Effective energy recovery requires this automatic start-up control program and as such there are no ways to start the system manually. The controller requires that all of the systems connected devices, equipment and sensory instruments are 100% functional. If any of these previously mentioned components are not 100% functional automatic start-up will not be permitted and attempts to run the system will result in failure. The cause of the failure will be reported to the user via the user display. Repeated attempts to run the water maker system while faults of this nature are being reported are not recommended.

The automatic start-up program ensures maximum energy recovery and enables complete hands free operation of the water maker unit, the operator simply requests a start up from the water maker and stands by as the water maker takes care of all of the required steps needed to place the water production facility into full operation whilst maximizing energy recovery. If any problems arise during the start-up, the control system will take any actions needed to safely shut-down the system and prevent any damage, it will then alert the operator as to what the difficulty was.

Page 68: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 68 of 155

5.2 Automatic Start up Operation

Automatic start-up operation is an integrated feature of to the Atlantic Sea Series of products. It allows for virtually hands free start-up of the system and all associated equipment. This automatic start-up operation can also be carried out remotely via the Modbus communications link (if installed) or via the internet interface.

Ensure that the main circuit breaker located in the top right corner of the control panel is in the ‘ON’ position and that the ‘Power On’ Indicator on the front of the control panel is illuminated.

Ensure that the main circuit breaker located in the top right corner of the power distribution panel is in the ‘ON’ position and that the ‘Power On’ Indicator on the front of the power distribution panel is illuminated.

Ensure that the E-Stop button is not pressed in on either panel. If the E-stop button is illuminated, the button is pressed in, release it by turning the mushroom in a clockwise direction.

Ensure no alarms or faults are currently being indicated. If the alarm light is illuminated or flashing an alarm or performance warning is present, accept or clear these alarms before attempting to proceed.

If the control panel has just been powered up, please wait for the ‘System Auto-Stop’ light to illuminate before attempting to automatically start-up the system. Requests to start-up before this light is illuminated will simply be ignored.

To initiate an automatic start-up of the system simply press the ‘Auto-Start’ button on the control panel door or navigate to the ‘System Operation’ screen (See Menu Navigation). Once the screen has been accessed, press the ‘Start System’ button.

Page 69: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 69 of 155

Immediately after the ‘Auto-Start’ button is pressed, the green indicator light embedded in the button will begin to flash rapidly, at this moment the system is performing system pre-checks, if a problem is detected the system will abort the automatic start-up routine and display a system fault notification screen detailing the problem (See System Critical Error Messages), as shown below:

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

The operator must correct the detected problem before re-attempting automatic operation.

If no pre-check errors are detected the control system will begin a 10 second count-down. During the count-down the system will beep intermittently and display a warning screen as shown on the next page, if the user wishes to abort the start-up they may do so by either pressing the ‘Auto-Stop’ button, Emergency Stop’ button or by pressing the abort start-up button displayed on the system start-up countdown timer screen as illustrated on the next page:

Page 70: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 70 of 155

Once the 10 second count-down has been completed the control system will begin placing system automated valves into the required position for system start up. This process can take up to 2 minutes and during this time there will be no pump activity. This is normal, it may also be possible to hear some slight hissing sounds and sounds associated with the movement of water and air in water, this is also normal, once correct valve positions have been confirmed the control system will begin to ramp up booster pump speed to achieve the desired high pressure pump inlet pressures, during this ramping procedurethe booster pump operator light will illuminate indicating that the booster pump is running, it may also be possible to hear a slight oscillation of pump speed as the system PID control begins to compensate for system process delays.

The control system constantly performs system checks while ramping the booster pump, target pressures within the system pipe work are expected, if system pressures fail to reach expected levels the system will abort the automatic operation routine the booster pump will be decelerated back to a stopped condition and the controller will display a system fault notification screen detailing the problem (See System Critical Error Messages), as shown on the next page:

Page 71: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 71 of 155

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

The operator must correct the detected problem before re-attempting automatic operation.

Once correct booster pump output pressures have been achieved the control system will enter into a paused state while waiting for any air trapped within the system pipe work to be vented via the air bleed valve, during the paused state the control system will also assess the condition of the system pre-filtration stage. If any system pre-filtration stage is found to be 50% dirty or higher the control system will issue a warning, this warning simply states that the water maker is being started with dirty filters and as a result will require a maintenance visit sooner than normal, this warning screen gives you the option of aborting the automatic start-up operation so filters can be changed or backwashed; if the operator chooses to ignore this message the control system will assume normal start-up operation is desired and will continue with the start-up process after the air purging delay. An example of the dirty filter warning screen can be seen on the next page:

Page 72: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 72 of 155

The operator can choose to view this screen during the pre-programmed delay or he can simply press on the button labeled ‘IGNORE’ to return to the previously viewed screen, if the operator does choose to stop the system at this point to clean or backwash filters as recommended the system can be stopped by either pressing the ‘Auto-Stop’ button on the control panel front door or by pressing on the button labeled ‘STOP SYSTEM’ on the warning screen shown above. If the media filter system is the cause of this warning screen the operator can choose to backwash the filter directly from this screen by pressing the backwash button.

If pre-filtration stage checks return normal results this warning screen is not displayedand after the pre-set air purging time has expired the control system will continue with the next stage of the system start up.

During the next phase of the start-up sequence the control system will begin spinning up the ISave device, this spin up procedure is done in several steps, during the entire spin up procedure system process pipe work pressure and flows are closely monitored, if any process variable strays beyond design limits the system will abort the automatic operation routine and as quickly as possible return the water maker back to a fully stopped state; once this rapid shutdown has been completed the controller will display a system fault notification screen detailing the problem (See System Critical Error Messages), as shown on the next page:

Page 73: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 73 of 155

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

The operator must correct the detected problem before re-attempting automatic operation.

The ISave device will begin the spin up procedure by gradually accelerating up to a pre-set speed. During this acceleration the membrane air bleed valve will remain open; however once the ISave device has accelerated past a pre-set speed this valve will be closed. Upon receiving confirmation that the air vent valve has fully closed the ISave will continue to accelerate up to the requested speed as configured in the stage 1 start-up program setting area. Once this speed has been achieved the control system will begin a period of over flushing and air bleeding, this stage lasts for approximately 1 minute. During this time the ISave runs whilst being flooded by feed water from the booster pump, this over flushing purges residual air from the high pressure piping system. Once this over flushing period has ended the ISave device is accelerated up to the normal operating speed as defined in the stage 2 start-up program setting area, once this speed is reached the control system begins monitoring the ISave flow rates.

Now that the ISave device has been fully started the control system can begin the next stage of the automatic start-up procedure, during this phase the High Pressure pump system is slowly accelerated up

Page 74: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 74 of 155

to operational speed, as the high pressure pump accelerates the system membrane pressure will begin to rise until production of permeate water begins, during this process the automatic pressure control system within the controller is activated. Once the High Pressure pump has reached full operation speed the control system enters the final state of automatic start-up.

During the final stage of automatic start-up the control system begins to decelerate the booster pump until over flushing is reduced to approximately 10%, If at any time during the automatic start-up procedure a significant problem is detected the control system will begin a rapid automatic shutdown of the unit, once the shutdown has been completedthe controller will display a system fault notification screen detailing the problem (See System Critical Error Messages), as shown below:

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

The operator must correct the detected problem before re-attempting automatic operation.

Page 75: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 75 of 155

6. Automatic Shutdown Operation

At any time in the automatic start up process the system can be shut down by pressing the ‘Auto-Stop’ button, pressing this button results in a controlled shutdown of the system. This controlled shut down can take up to 15 minutes to complete depending on where the system was in its automatic start up routine at the time the ‘Auto-Stop’ button was pressed.

Once pressed the ‘Auto-Stop’ button will begin to flash. This response is to inform you a system shutdown is now in progress. Once the system shut down is completed the ‘System Auto Stop’ light will remain steadily illuminated.

If a system fault is detected during shutdown the controller will display a system fault notification screen detailing the problem (See System Critical Error Messages), as shown below:

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

The operator must correct the detected problem before re-attempting automatic operation.

Page 76: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 76 of 155

7. Emergency Shutdown Operation:

To shut down the system in an emergency press the E-Stop button, pressing this button cause all rotating equipment to cease immediately.Once the E-Stop is released the system will move any activated valves to their home position (if applicable), the ‘Auto-Stop’ button will remain steadily illuminated once this action is completed.

The controller will also display a system fault notification screen detailing that the E-Stop button was activated during operation (See System Critical Error Messages), as shown below:

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

The operator must release the E-Stop button and accept this warning before re-attempting automatic operation.

Page 77: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 77 of 155

8. System Critical Error Messages

The AtlanticSea control system contains four message centers, all of which are intended to provide as much information to the operator as possible. The main of the four message centers is the critical error message center.

During operation if a system failure occurs which could result in the unsafe operation of the water maker, the fault is deemed as a ‘Critical Error’. These types or faults cause an immediate shutdown of the water maker and all associated equipment. The critical error message center is the information window used by the operator to examine system faults of this nature. Typically when these faults occur they are preceded by a ‘System Warning’ screen as shown below:

Pressing ‘Highlight Alarm Message’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept & Clear Alarm Message’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept & Clear Alarm Message’ to exit this screen. Pressing ‘Help Me With This Fault’ will call up the on-line interactive help files associated with this fault condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

When a system fault is detected the system fault light remains steadily illuminated, andthe general alarm contact also changes state until the fault is cleared by the operator,this can be done by pressing the ‘Accept & Clear Alarm Message’button on the touch screen or by pressing and holding the ‘Auto-Stop’ button for 2 seconds.

Page 78: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 78 of 155

8.1 System fault codes and possible causes

Number Fault Displayed Possible Causes

1 F:001 VFD-100 Communications Failure

Modbus Communications with the indicated VFD have failed to return the correct checksum 6 times within the past 60 seconds. The system no longer has open communications with this VFD and as a result a rapid shutdown followed by a VFD power cycle has taken place. Check power to the drive is stable, and check all communication cables to the drive are intact and not damaged. If this does not rectify the problem contact Danfoss Sea Recovery Technical Services for further assistance.

2 F:002 VFD-101 Communications Failure

Modbus Communications with the indicated VFD have failed to return the correct checksum 6 times within the past 60 seconds. The system no longer has open communications with this VFD and as a result a rapid shutdown followed by a VFD power cycle has taken place. Check power to the drive is stable, and check all communication cables to the drive are intact and not damaged. If this does not rectify the problem contact Danfoss Sea Recovery Technical Services for further assistance.

3 F:003 VFD-102 Communications Failure

Modbus Communications with the indicated VFD have failed to return the correct checksum 6 times within the past 60 seconds. The system no longer has open communications with this VFD and as a result a rapid shutdown followed by a VFD power cycle has taken place. Check power to the drive is stable, and check all communication cables to the drive are intact and not damaged. If this does not rectify the problem contact Danfoss Sea Recovery Technical Services for further assistance.

4 F:004 VFD-103 Communications Failure

Modbus Communications with the indicated VFD have failed to return the correct checksum 6 times within the past 60 seconds. The system no longer has open communications with this VFD and as a result a rapid shutdown followed by a VFD power cycle has taken place. Check power to the drive is stable, and check all communication cables to the drive are intact and not damaged. If this does not rectify the problem contact Danfoss Sea Recovery Technical Services for further assistance.

Page 79: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 79 of 155

5 F:005 Total Communications Failure With System VFD's Check 480vAC Source

The control system has detected a complete loss of communications with all VFD's connected to the unit; usually this type of failure is attributed to a total power failure of the 480vAC power source. Check power systems and communications cables, if this does not fix the failure, re-boot the water maker.

6

F:006 Fault - Alarm Condition Present VFD-100. Please Check Drive Message Log For Further Info

A dangerous alarm condition was detected in VFD-100, to prevent damage the system was shutdown, the nature of this alarm may be logged in the VFD reporting monitor, check the monitor for further information

7 F:007 Fault - Current Limit Has Been Exceeded VFD-100

VFD-100 has reported the load connected has reached the maximum available current limits of the VFD device, as a protective measure the VFD is now winding back power to aid cooling. This reduction of output power can result in system process instabilities, as a result a rapid shutdown was initiated.

8 F:008 Fault - Thermal Limited Have Been Exceeded VFD-100

VFD-100 has reported that the heatsink within the unit is approaching maximum temperature, if maximum temperature is exceeded the drive will automatically shutdown to prevent damage.

9

F:009 Fault - Alarm Condition Present VFD-101. Please Check Drive Message Log For Further Info

A dangerous alarm condition was detected in VFD-101, to prevent damage the system was shutdown, the nature of this alarm may be logged in the VFD reporting monitor, check the monitor for further information

10 F:010 Fault - Current Limit Has Been Exceeded VFD-101

VFD-101 has reported the load connected has reached the maximum available current limits of the VFD device, as a protective measure the VFD is now winding back power to aid cooling. This reduction of output power can result in system process instabilities, as a result a rapid shutdown was initiated.

11 F:011 Fault - Thermal Limited Have Been Exceeded VFD-101

VFD-101 has reported that the heatsink within the unit is approaching maximum temperature, if maximum temperature is exceeded the drive will automatically shutdown to prevent damage.

Page 80: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 80 of 155

12

F:012 Fault - Alarm Condition Present VFD-102. Please Check Drive Message Log For Further Info

A dangerous alarm condition was detected in VFD-102, to prevent damage the system was shutdown, the nature of this alarm may be logged in the VFD reporting monitor, check the monitor for further information

13 F:013 Fault - Current Limit Has Been Exceeded VFD-102

VFD-102 has reported the load connected has reached the maximum available current limits of the VFD device, as a protective measure the VFD is now winding back power to aid cooling. This reduction of output power can result in system process instabilities, as a result a rapid shutdown was initiated.

14 F:014 Fault - Thermal Limited Have Been Exceeded VFD-102

VFD-102 has reported that the heatsink within the unit is approaching maximum temperature, if maximum temperature is exceeded the drive will automatically shutdown to prevent damage.

15

F:015 Fault - Alarm Condition Present VFD-103. Please Check Drive Message Log For Further Info

A dangerous alarm condition was detected in VFD-103, to prevent damage the system was shutdown, the nature of this alarm may be logged in the VFD reporting monitor, check the monitor for further information

16 F:016 Fault - Current Limit Has Been Exceeded VFD-103

VFD-103 has reported the load connected has reached the maximum available current limits of the VFD device, as a protective measure the VFD is now winding back power to aid cooling. This reduction of output power can result in system process instabilities, as a result a rapid shutdown was initiated.

17 F:017 Fault - Thermal Limited Have Been Exceeded VFD-103

VFD-103 has reported that the heatsink within the unit is approaching maximum temperature, if maximum temperature is exceeded the drive will automatically shutdown to prevent damage.

18

F:018 A Critical Class Fault Has Occurred With Fault VFD-100. Power Cycle The Drive To Reset

VFD-100 detected a critical fault and performed and emergency shutdown to prevent equipment damage, this type of emergency shutdown is only triggered when a none 'self-clearing' fault is detected. The drive was power cycled to clear this error, but the connected motors must be checked completely before the unit is operated.

19

F:019 A Critical Class Fault Has Occurred With Fault VFD-101. Power Cycle The Drive To Reset

VFD-101 detected a critical fault and performed and emergency shutdown to prevent equipment damage, this type of emergency shutdown is only triggered when a none 'self-clearing' fault is detected. The drive was power cycled to clear this error, but the connected motors must be checked completely before the unit is operated.

Page 81: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 81 of 155

20 F:020 A Critical Class Fault Has Occurred With Fault VFD-102. Power Cycle The Drive To Reset

VFD-102 detected a critical fault and performed and emergency shutdown to prevent equipment damage, this type of emergency shutdown is only triggered when a none 'self-clearing' fault is detected. The drive was power cycled to clear this error, but the connected motors must be checked completely before the unit is operated.

21 F:021 A Critical Class Fault Has Occurred With Fault VFD-103. Power Cycle The Drive To Reset

VFD-103 detected a critical fault and performed and emergency shutdown to prevent equipment damage, this type of emergency shutdown is only triggered when a none 'self-clearing' fault is detected. The drive was power cycled to clear this error, but the connected motors must be checked completely before the unit is operated.

22

F:022 Booster Pump Output Failed To Reach Target

The system attempted to start-up automatically but the booster pump was unable to reach the desired target output pressure within the allowed time. This could be due to severely blocked pre-filtration or some other type of pressure loss either within the system or within the booster pump itself. If no pressure losses can be found it is recommended to disassemble the booster pump stacks to see if damage has occurred.

23 F:023 ISave Brine Pressure Is Below Minimum Range

The system was running or starting up when the ISave brine line pressure dropped below minimum specifications. This can be caused by a defective booster pump, severely blocked pre-filtration, or by the ISave back pressure regulator being set incorrectly. If the ISave BPR has not been adjusted begin checking for sources of booster pump pressure loss

24 F:024 ISave Brine Pressure Is Above Maximum Range

The system was running or starting up when the ISave brine line pressure exceeded maximum specifications. This can be caused by the ISave back pressure regulator being set incorrectly. If the ISave BPR has not been adjusted begin checking for blockages in the ISave brine line

25 F:025 HP Pump Inlet Pressure Is Below Minimum Range

The system was running or starting up when the HP Pump inlet pressure dropped below minimum specifications. This can be caused by a defective booster pump, severely blocked pre-filtration.

26 F:026 HP Pump Inlet Pressure Is Above Maximum Range

The system was running or starting up when the HP Pump inlet pressure exceeded maximum specifications. This can be caused by a rapid increase in system inlet pressure. Check system inlet pressures and any associated regulating equipment

Page 82: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 82 of 155

27

F:027 System Membrane Pressure High Despite Automatic Production Control

The system was running or starting up when membrane pressures exceeded maximum. The control system then activated the automatic pressure control program to correct this issue, but after reducing HP Pump speeds to minimum the system membrane pressure still exceeded maximum and could not be rectified. As a result a rapid shutdown was initiated.

28

F:028 CH4-CH1 Differential Sum Above Maximum Set Value (BF-1004 Is Closed)

The system was running or starting up when the differential pressure across a section of system pipework exceeded the detection threshold. This indicates to the controller that a manual valve in this section of pipework has been closed. The suspected valve is listing in the fault message. Ensure the valve is fully open before attempting to run the system again

29

F:029 CH1-CH13 Differential Sum Above Maximum Set Value (BF-1002 Is Closed)

The system was running or starting up when the differential pressure across a section of system pipework exceeded the detection threshold. This indicates to the controller that a manual valve in this section of pipework has been closed. The suspected valve is listing in the fault message. Ensure the valve is fully open before attempting to run the system again

30

F:030 HP Pump Low Pressure Switch Detected HP Pump Inlet Pressure Loss

Inlet pressure to the High Pressure pump dropped to extremely low levels before transducers were able to detect. This initiated a rapid shutdown of the unit but possible cavitation of the HP Pumps may off occurred. It is advised to find the loss of booster pressure (check water source) before re-starting the system. If re-starting can take place the pump should be checked for higher operating temperatures. The pump swash face should never exceed the temperature of the system water feed.

31

F:031 HP Pump High Pressure Switch Detected HP Pump Outlet Pressure High

The system High Pressure pump outlet pressure exceeded the maximum allowable for system containment before the automatic pressure reduction program could rectify the problem. Such a rapid increase in system pressure is unusual. Any cause for this increase in pressure should be fully investigated before re-attempting auto-start operations.

32

F:032 Membrane High Pressure Switch Detected HP Pump Outlet Pressure High

The system membrane outlet pressure exceeded the maximum allowable for system containment before the automatic pressure reduction program could rectify the problem. Such a rapid increase in system pressure is unusual. Any cause for this increase in pressure should be fully investigated before re-attempting auto-start operations.

Page 83: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 83 of 155

33 F:033 System Cannot Start When Power Panel Disconnect Is Off

The operator is attempting to auto-start the system with the power disconnect to the high power 480vAC control panel switch to the off position. The system cannot activate pumps in this condition. Please turn on the high power panel before re-attempting auto-start operations

34 F:034 PT-1004 Faulted. System Auto-Start Not Available

Pressure transducer PT-1004 is reporting a fault. Check the system messaging area for help diagnosing the type of failure detected, and rectify before continuing

35 F:035 PT-1005 Faulted. System Auto-Start Not Available

Pressure transducer PT-1005 is reporting a fault. Check the system messaging area for help diagnosing the type of failure detected, and rectify before continuing

36 F:036 TDS-1001 Faulted. System Auto-Start Not Available

Salinity transducer TDS-1001 is reporting a fault. Check the system messaging area for help diagnosing the type of failure detected, and rectify before continuing

37 F:037 PT-1008 Faulted. System Auto-Start Not Available

Pressure transducer PT-1008 is reporting a fault. Check the system messaging area for help diagnosing the type of failure detected, and rectify before continuing

38 F:038 Reserved Reserved

39 F:039 PT-1009 Faulted. System Auto-Start Not Available

Pressure transducer PT-1009 is reporting a fault. Check the system messaging area for help diagnosing the type of failure detected, and rectify before continuing

40 F:040 PT-1000 Faulted. System Auto-Start Not Available

Pressure transducer PT-1000 is reporting a fault. Check the system messaging area for help diagnosing the type of failure detected, and rectify before continuing

41 F:041 PT-1001 Faulted. System Auto-Start Not Available

Pressure transducer PT-1001 is reporting a fault. Check the system messaging area for help diagnosing the type of failure detected, and rectify before continuing

42

F:042 Pump Operators Not In Correct Position For Auto-Start to Continue

The operator is attempting to activate the auto-start feature with the booster pump switch located in either the ‘manual’ or ‘off’ position. Please rotate the switch to the ‘auto’ position before re-attempting auto-start operations

43 F:043 E-Stop Condition Present When Auto-Start Requested

Please check system E-Stop push buttons and rotate any de-pressed buttons in a clockwise direction to release them.

44 F:044 E-Stop Condition Present After Auto-matic Run Started

The system was running or starting up when a user pressed the E-Stop button. The water maker was immediately stopped. When ready, release the de-pressed E-Stop button by rotating it in a clockwise direction. Allow 2 minutes for the control panel to re-set before re-attempting auto-start operations.

Page 84: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 84 of 155

45 F:045 MF1-IVA Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF1-IVA (Media Filter 1 Inlet Valve A) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

46 F:046 MF1-OVA Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF1-OVA (Media Filter 1 Outlet Valve A) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

47 F:047 MF1-IVB Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF1-IVB (Media Filter 1 Inlet Valve B) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

48 F:048 MF1-OVB Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF1-OVB (Media Filter 1 Outlet Valve B) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

49 F:049 MF1-RV Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF1-RV (Media Filter 1 Rinse Valve) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

50 F:050 MF2-IVA Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF2-IVA (Media Filter 2 Inlet Valve A) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

51 F:051 MF2-OVA Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF2-OVA (Media Filter 2 Outlet Valve A) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

Page 85: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 85 of 155

52 F:052 MF2-IVB Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF2-IVB (Media Filter 2 Inlet Valve B) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

53 F:053 MF2-OVB Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF2-OVB (Media Filter 2 Outlet Valve B) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

54 F:054 MF2-RV Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MF2-RV (Media Filter 2 Rinse Valve) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

55 F:055 PDV Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve PDV (Product Diversion Valve) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

56 F:056 MABV Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MABV (Membrane Air Bleed Valve) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

57 F:057 IS IV Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve IS IV (ISave Isolation Valve) changed without any commands from the control system. The reason for this could be the valve has been placed in manual mode and moved by an operator. This situation cannot occur during automatic operation

58

F:058 MANUAL CIP Valve Position Error. Auto-Start Cannot Continue

The system was running or starting up when the position of valve MANUAL CIP (Manual Clean In Place Valve). The reason for this could be the valve has been moved by an operator. This situation cannot occur during automatic operation

Page 86: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 86 of 155

59

F:059 Backwashing Fault. Media Filter 1 Inlet Valve A Position Incorrect

The control system is attempting to automatically backwash the media filter system but the valve detailed is in the incorrect position for this program sequence. The valve may be placed in manual, check to ensure it is switched to the auto position and if required re-boot the water maker.

60

F:060 Backwashing Fault. Media Filter 1 Outlet Valve A Position Incorrect

The control system is attempting to automatically backwash the media filter system but the valve detailed is in the incorrect position for this program sequence. The valve may be placed in manual, check to ensure it is switched to the auto position and if required re-boot the water maker.

61

F:061 Backwashing Fault. Media Filter 1 Inlet Valve B Position Incorrect

The control system is attempting to automatically backwash the media filter system but the valve detailed is in the incorrect position for this program sequence. The valve may be placed in manual, check to ensure it is switched to the auto position and if required re-boot the water maker.

62

F:062Backwashing Fault. Media Filter 1 Outlet Valve B Position Incorrect

The control system is attempting to automatically backwash the media filter system but the valve detailed is in the incorrect position for this program sequence. The valve may be placed in manual, check to ensure it is switched to the auto position and if required re-boot the water maker.

63

F:063 Backwashing Fault. Media Filter 1 Rinse Valve Position Incorrect

The control system is attempting to automatically backwash the media filter system but the valve detailed is in the incorrect position for this program sequence. The valve may be placed in manual, check to ensure it is switched to the auto position and if required re-boot the water maker.

64

F:064 Backwashing Fault. Media Filter 2 Inlet Valve A Position Incorrect

The control system is attempting to automatically backwash the media filter system but the valve detailed is in the incorrect position for this program sequence. The valve may be placed in manual, check to ensure it is switched to the auto position and if required re-boot the water maker.

65

F:065 Backwashing Fault. Media Filter 2 Outlet Valve A Position Incorrect

The control system is attempting to automatically backwash the media filter system but the valve detailed is in the incorrect position for this program sequence. The valve may be placed in manual, check to ensure it is switched to the auto position and if required re-boot the water maker.

Page 87: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 87 of 155

66 Valve MF1-IVA Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 1 Inlet 'A' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

67 REM-Valve MF1-IVA Did Not Respond To Open Command

The control system commanded the media filter 1 inlet valve 'A' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

68 REM-Valve MF1-IVA Did Not Complete Entire Open Movement

The control system commanded the media filter 1 inlet valve 'A' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

69 Valve MF1-IVA Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

70 Valve MF1-IVA Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

71 REM-Valve MF1-IVA Did Not Respond To Close Command

The control system commanded the media filter 1 inlet valve 'A' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

72 REM-Valve MF1-IVA Did Not Complete Entire Close Movement

The control system commanded the media filter 1 inlet valve 'A' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 88: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 88 of 155

73 Valve MF1-OVA Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 1 outlet 'A' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

74 REM-Valve MF1-OVA Did Not Respond To Open Command

The control system commanded the media filter 1 outlet valve 'A' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

75 REM-Valve MF1-OVA Did Not Complete Entire Open Movement

The control system commanded the media filter 1 outlet valve 'A' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

76 Valve MF1-OVA Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

77 Valve MF1-OVA Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

78 REM-Valve MF1-OVA Did Not Respond To Close Command

The control system commanded the media filter 1 outlet valve 'A' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

79 REM-Valve MF1-OVA Did Not Complete Entire Close Movement

The control system commanded the media filter 1 outlet valve 'A' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 89: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 89 of 155

80 Valve MF1-IVB Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 1 Inlet 'B' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

81 REM-Valve MF1-IVB Did Not Respond To Open Command

The control system commanded the media filter 1 inlet valve 'B' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

82 REM-Valve MF1-IVB Did Not Complete Entire Open Movement

The control system commanded the media filter 1 inlet valve 'B' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

83 Valve MF1-IVB Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

84 Valve MF1-IVB Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

85 REM-Valve MF1-IVB Did Not Respond To Close Command

The control system commanded the media filter 1 inlet valve 'B' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

86 REM-Valve MF1-IVB Did Not Complete Entire Close Movement

The control system commanded the media filter 1 inlet valve 'B' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 90: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 90 of 155

87 Valve MF1-OVB Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 1 outlet 'B' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

88 REM-Valve MF1-OVB Did Not Respond To Open Command

The control system commanded the media filter 1 outlet valve 'B' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

89 REM-Valve MF1-OVB Did Not Complete Entire Open Movement

The control system commanded the media filter 1 outlet valve 'B' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

90 Valve MF1-OVB Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

91 Valve MF1-OVB Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

92 REM-Valve MF1-OVB Did Not Respond To Close Command

The control system commanded the media filter 1 outlet valve 'B' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

93 REM-Valve MF1-OVB Did Not Complete Entire Close Movement

The control system commanded the media filter 1 outlet valve 'B' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 91: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 91 of 155

94 Valve MF1 RV Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 1 rinse valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

95 Valve MF1 RV Did Not Respond To Open Command

The control system commanded the media filter 1 rinse valve to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

96 Valve MF1 RV Did Not Complete Entire Open Movement

The control system commanded the media filter 1 rinse valve to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

97 Valve MF1 RV Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

98 Valve MF1 RV Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

99 Valve MF1 RV Did Not Respond To Close Command

The control system commanded the media filter 1 rinse valve to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

100 Valve MF1 RV Did Not Complete Entire Close Movement

The control system commanded the media filter 1 rinse valve to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 92: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 92 of 155

101 Valve MF2-IVA Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 2 Inlet 'A' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

102 REM-Valve MF2-IVA Did Not Respond To Open Command

The control system commanded the media filter 2 inlet valve 'A' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

103 REM-Valve MF2-IVA Did Not Complete Entire Open Movement

The control system commanded the media filter 2 inlet valve 'A' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

104 Valve MF2-IVA Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

105 Valve MF2-IVA Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

106 REM-Valve MF2-IVA Did Not Respond To Close Command

The control system commanded the media filter 2 inlet valve 'A' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

107 REM-Valve MF2-IVA Did Not Complete Entire Close Movement

The control system commanded the media filter 2 inlet valve 'A' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 93: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 93 of 155

108 Valve MF2-OVA Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 2outlet 'A' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

109 REM-Valve MF2-OVA Did Not Respond To Open Command

The control system commanded the media filter 2 outlet valve 'A' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

110 REM-Valve MF2-OVA Did Not Complete Entire Open Movement

The control system commanded the media filter 2 outlet valve 'A' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

111 Valve MF2-OVA Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

112 Valve MF2-OVA Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

113 REM-Valve MF2-OVA Did Not Respond To Close Command

The control system commanded the media filter 2 outlet valve 'A' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

114 REM-Valve MF2-OVA Did Not Complete Entire Close Movement

The control system commanded the media filter 2 outlet valve 'A' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 94: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 94 of 155

115 Valve MF2-IVB Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 2 Inlet 'B' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

116 REM-Valve MF2-IVB Did Not Respond To Open Command

The control system commanded the media filter 2 inlet valve 'B' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

117 REM-Valve MF2-IVB Did Not Complete Entire Open Movement

The control system commanded the media filter 2 inlet valve 'B' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

118 Valve MF2-IVB Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

119 Valve MF2-IVB Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

120 REM-Valve MF2-IVB Did Not Respond To Close Command

The control system commanded the media filter 2 inlet valve 'B' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

121 REM-Valve MF2-IVB Did Not Complete Entire Close Movement

The control system commanded the media filter 2 inlet valve 'B' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 95: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 95 of 155

122 Valve MF2-OVB Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 2 outlet 'B' valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

123 REM-Valve MF2-OVB Did Not Respond To Open Command

The control system commanded the media filter 2 outlet valve 'B' to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

124 REM-Valve MF2-OVB Did Not Complete Entire Open Movement

The control system commanded the media filter 2 outlet valve 'B' to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

125 Valve MF2-OVB Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

126 Valve MF2-OVB Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

127 REM-Valve MF2-OVB Did Not Respond To Close Command

The control system commanded the media filter 2 outlet valve 'B' to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

128 REM-Valve MF2-OVB Did Not Complete Entire Close Movement

The control system commanded the media filter 2 outlet valve 'B' to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 96: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 96 of 155

129 Valve MF2 RV Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 2 rinse valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

130 Valve MF2 RV Did Not Respond To Open Command

The control system commanded the media filter 2 rinse valve to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

131 Valve MF2 RV Did Not Complete Entire Open Movement

The control system commanded the media filter 2 rinse valve to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

132 Valve MF2 RV Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

133 Valve MF2 RV Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

134 Valve MF2 RV Did Not Respond To Close Command

The control system commanded the media filter 2 rinse valve to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

135 Valve MF1 RV Did Not Complete Entire Close Movement

The control system commanded the media filter 2 rinse valve to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 97: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 97 of 155

136 Valve PDV Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the product diversion valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

137 Valve PDV Did Not Respond To Open Command

The control system commanded the product diversion valve to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

138 Valve PDV Did Not Complete Entire Open Movement

The control system commanded the product diversion valve to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

139 Valve PDV Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

140 Valve PDV Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

141 Valve PDV Did Not Respond To Close Command

The control system commanded the product diversion valve to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

142 Valve PDV Did Not Complete Entire Close Movement

The control system commanded the product diversion valve to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 98: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 98 of 155

143 Valve MA BV Was Fully Open, Then Position FeedBack Was Lost

The control system has lost all position feedback from the media filter 2 rinse valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

144 Valve MA BV Did Not Respond To Open Command

The control system commanded the membrane air bleed valve to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

145 Valve MA BV Did Not Complete Entire Open Movement

The control system commanded the membrane air bleed valve to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

146 Valve MA BV Opening Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

147 Valve MA BV Closing Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

148 Valve MA BV Did Not Respond To Close Command

The control system commanded the membrane air bleed valve to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

149 Valve MA BV Did Not Complete Entire Close Movement

The control system commanded the membrane air bleed valve to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 99: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 99 of 155

150 Valve IS IV Was Fully Closed, Then Position FeedBack Was Lost

The control system has lost all position feedback from the ISave Isolation valve. Check valve wiring for breaks or snags, also check that frame inter-connection points have not pulled apart.

151 Valve IS IV Did Not Respond To Close Command

The control system commanded the ISave Isolation valve to open but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

152 Valve IS IV Did Not Complete Entire Close Movement

The control system commanded the ISave Isolation valve to open. The valve responded to the command but failed to open fully in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

153 Valve IS IV Closing Fault This fault indicator is usually raised along with either a failure to respond to open command fault, or an open command motion failed to complete.

154 Valve IS IV Opening Fault This fault indicator is usually raised along with either a failure to respond to close command fault, or a close command motion failed to complete.

155 Valve IS IV Did Not Respond To Open Command

The control system commanded the ISave Isolation valve to close but the valve did not respond to the command at all. Check that the valve is switched to 'Auto' and that all power wiring is free from breaks or snags. Check 5 x 20mm fuses within the control panel for failures (indicated by red light)

156 Valve IS IV Did Not Complete Entire Open Movement

The control system commanded the ISave Isolation valve to close. The valve responded to the command but failed to close completely in the time allowed. Probable cause of failure is either power loss to the valve, or a worn and failing actuator. Check 5 x 20 mm fuses within control panel for failures (indicated by red light); Switch to commissioning mode and manually test valve to check actuator performance.

Page 100: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 100 of 155

9. System Performance Messages

The Atlantic Sea control system contains four message centers, all of which are intended to provide as much information to the operator as possible. The most commonly displayed of the four message centers is the performance message center.

During operation, if a system fault which results in the water maker not operating at peak efficiency is detected, the fault is deemed as a ‘Non Critical Error’. These types of faults do not require an immediate shutdown of the water maker. While safe to do so the water maker will continue to run and prompt the operator that attention is required by logging the fault in the performance message center. The performance message center is the information window used by the operator to examine system faults of this nature. Typically when these faults occur they are preceded by a ‘Performance Warning’ screen as shown below:

Pressing ‘Highlight AlertMessage’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept This Notification’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept’ to exit this screen. Pressing ‘More Information On This Notice’will call up the on-line interactive help files associated with this alarm condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

Page 101: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 101 of 155

When a system performance fault is detected the system fault indicator will blink at 0.5 second intervals, the general alarm contact will not change state in these situations. The system fault indicator will continue to blink until the fault is accepted by the operator; this can be done by pressing the ‘Accept This Notification’button in the performance message center. Once a fault has been accepted the system fault indicator will stop blinking, but a log of the fault is kept within the performance message center. This list of potential problems can be viewed at any time by manually navigating back to the performance message center (See Menu Navigation)

9.1 System performance notifications and possible causes

Number Message Displayed Possible Causes

1 P:001 Automatic Media Filter Function Has Been Disabled

The system has detected a problem with sensors required for the operation of the automatic multimedia function, therefore until these sensors have been repaired, this function has been disabled

2

P:002 MultiMedia Filter Differential Pressure Exceeds Specified Maximum

The system has detected the differential pressure across the media filter has exceeded specified set-points; the filter should be backwashed soon.

3 P:003 PT-1006 Pressure Transducer Faulty. Please Replace

The system is currently in operation but has detected a non-critical sensor failure. Operation can still continue however some automatic functions may not be available. This defective sensor should be replaced as soon as possible. Power to the control panel should always be removed before attempting replacement

4 P:004 PT-1002 Pressure Transducer Faulty. Please Replace

The system is currently in operation but has detected a non-critical sensor failure. Operation can still continue however some automatic functions may not be available. This defective sensor should be replaced as soon as possible. Power to the control panel should always be removed before attempting replacement

5 P:005 PT-1003 Pressure Transducer Faulty. Please Replace

The system is currently in operation but has detected a non-critical sensor failure. Operation can still continue however some automatic functions may not be available. This defective sensor should be replaced as soon as possible. Power to the control panel should always be removed before attempting replacement

6 P:006 PT-1007 Pressure Transducer Faulty. Please Replace

The system is currently in operation but has detected a non-critical sensor failure. Operation can still continue however some automatic functions may not be available. This defective sensor should be replaced as soon as possible. Power to the control panel should always be removed before attempting replacement

Page 102: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 102 of 155

7 P:007 FT-1001 Pressure Transducer Faulty. Please Replace

The system is currently in operation but has detected a non-critical sensor failure. Operation can still continue however some automatic functions may not be available. This defective sensor should be replaced as soon as possible. Power to the control panel should always be removed before attempting replacement

8 P:008 FT-1003 Pressure Transducer Faulty. Please Replace

The system is currently in operation but has detected a non-critical sensor failure. Operation can still continue however some automatic functions may not be available. This defective sensor should be replaced as soon as possible. Power to the control panel should always be removed before attempting replacement

9 P:009 FT-1002 Pressure Transducer Faulty. Please Replace

The system is currently in operation but has detected a non-critical sensor failure. Operation can still continue however some automatic functions may not be available. This defective sensor should be replaced as soon as possible. Power to the control panel should always be removed before attempting replacement

10

P:010 Extended Delay In Producing Potable Water. Check System Settings

The system is running in automatic mode, but has not been able to product potable water within the normal time frames. Check system pressure settings

11 P:011 Potable Water Quality Dropped Below Specifications. Please Check Settings

The system is running in automatic mode and was producing potable water, but for some unknown reason the water quality of the product water deteriorated and is no longer acceptable. Check system pressure settings

12 P:012 Diversion Valve Has Cycled 6 Times In the Past 60 Minutes. Check Settings

The system is running in automatic mode and was producing potable water, but for some unknown reason the water quality of the product water fluctuated between potable and non-potable 6 times within the last 60 minutes. Check system pressure settings

13 P:013 Insufficient Fresh Water Flush Inlet Pressure

Fresh water flush mode is currently active but insufficient pressure is detected at the fresh water flush inlet.

14 P:014 Product Pump Will Not Operate Until Diversion Valve Has Cycled

The operator has moved the product pump operator switch into the manual position. The control system is notifying the operator that even in manual control mode the control system will not activate the pump until the product diversion valve has cycled as until this point the feed line to the pump will be dry.

Page 103: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 103 of 155

15 P:015 System Pre-Treatment Chemical Tank Is Low, Pump De-activated. Please Fill Tank

The control system has detected that the pre-treatment chemical tank is low on chemical and has de-activated the pump to protect it from damage. The tank must be filled and the control switch for the pump must be turned ‘off’ and back to ‘on’ to re-activate the systempump

16 P:016 System Post-Treatment Chemical Tank Is Low, Pump De-activated. Please Fill Tank

The control system has detected that the post-treatment chemical tank is low on chemical and has de-activated the pump to protect it from damage. The tank must be filled and the control switch for the pump must be turned ‘off’ and back to ‘on’ to re-activate the systempump

17

P:017 System Membrane Differential Pressure Exceeded. CIP Advised

The differential pressure across the membrane chain has exceeded specifications. Chemical cleaning is required to remove scaling. If this does not solve the problem, membrane replacement may be required.

18

P:018 System Media Filter Is 75% Fouled. A Cleaning Will Take Place Shortly

The media filter array is becoming blocked; soon it will cause the control system to shut-down and backwash the filter system

20 P:019 System 20u Filter Bank Is 75% Fouled. A Change Out may be Required Soon

The 20u cartridge filter is becoming blocked; soon it will cause the control system to shutdown to protect components from filter bypass. Maintenance crews should be alerted that a filter change out will soon be required

21 P:020 System 5u Filter Bank Is 75% Fouled. A Change Out may be Required Soon

The 5u cartridge filter is becoming blocked; soon it will cause the control system to shutdown to protect components from filter bypass. Maintenance crews should be alerted that a filter change out will soon be required

22 P:021 System Membranes Are 75% Fouled. A Cleaning In Place Is Recommended

The membrane array is becoming blocked; soon it will cause problems with the energy recovery features of the unit. Maintenance crews should be alerted that a filter change out will soon be required

23 P:022 System Production Rates Are Lower Than Expected, Possible Membrane Fouling Issue

The control system has detected that system permeate flow rates are low, measure production water flow rates using and external device to confirm readings, if readings are confirmed contact DSRC for assistance. If readings are not confirmed, check flow transducer for calibration errors.

Page 104: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 104 of 155

24

P:023 System Production Rates Are Higher Than Expected, Possible Membrane Damage Or Over Pressure

The control system has detected that system permeate flow rates are high, measure production water flow rates using and external device to confirm readings, if readings are confirmed contact DSRC for assistance. If readings are not confirmed, check flow transducer for calibration errors.

25

P:024 ISave Flow Rates Are Lower Than Expected. Possible Mixing Issue

The control system has detected that system ISave flow rates are low, measure water flow rates using and external device to confirm readings, if readings are confirmed contact DSRC for assistance. If readings are not confirmed, check flow transducer for calibration errors.

26

P:025 ISave Flow Rates Are Higher Than Expected. Loss Of Booster Pump Performance Will Result

The control system has detected that system ISave flow rates are high, measure water flow rates using and external device to confirm readings, if readings are confirmed contact DSRC for assistance. If readings are not confirmed, check flow transducer for calibration errors.

** = Indicates optional components

Page 105: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 105 of 155

10. SystemStatus Messages

The Atlantic Sea control system contains four message centers, all of which are intended to provide as much information to the operator as possible. The most commonly used of the four message centers is usually the system status message center.

During operation, anytime the water maker senses a change in external input, or if the water maker makes a decision to operate any part of the water maker a message detailing what is currently happening will be displayed in the system status message center. The system status message center is the information window used by the operator to examine any internal messages generated by the water maker.

To access this messaging screen navigate to the system message selection menu (See Menu Navigation) and press the arrow alongside the ‘System Status Messages’ text. Doing so will present you with the following screen:

Pressing ‘HighlightMessage’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Back’ will exit the message list. Pressing ‘Help Me With This Message’will call up the on-line interactive help files associated with this message condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

When a system status message is displayed, the system fault indicator will not illuminate and the general alarm contact will not change state.

Page 106: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 106 of 155

11. VFD System Status Messages

The Atlantic Sea control system contains four message centers, all of which are intended to provide as much information to the operator as possible. The fourth message center contains data reported by the system VFD’s.

During operation, anytime the water maker detects a new message within a connected VFD buffer, the control system transfers this message over to the control system HMI for display to the user in a central location. This information will remain present after a system run, until the next auto-start event is requested.

To access this messaging screen navigate to the system message selection menu (See Menu Navigation) and press the arrow alongside the ‘VFDSystem Information’ text. Doing so will present you with the following screen:

Pressing ‘HighlightMessage’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Back’ will exit the message list. Pressing ‘Help Me With This Message’will call up the on-line interactive help files associated with this message condition, these on-line help files will assist you in diagnosing and solving the problem (if installed)

When a VFD system status message is displayed, the system fault indicator will not illuminate unless the event has triggered an automatic rapid shutdown of the unit, in this case the general alarm contact will also change state.

Page 107: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 107 of 155

12. Menu Navigation

The Atlantic Sea control system has many user interface menus and screens, all of which are designed to present as much information to the operator as possible. Navigating these screens is quite simple and begins when moving from the home screen by pressing the arrow in the lower right corner of the screen. Once you press this arrow the screen will change to the main operation menu as shown below:

12.1 Accessing the ‘System Operation’ Screen:

From the System Main Menu screen, system functions and secondary menu systems can be accessed. To enter the system operation screen press on the arrow next to the text ‘System Operation’ as shown below:

Pressing the arrow in the top left hand corner of the system operation screen will return you to the Main Menu Screen, as shown on the next page:

Page 108: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 108 of 155

12.2 Accessing VFD System Health Monitors:

To view all information relating to the water makers VFD system health, access the ‘Motor VFD System Monitoring’ screen. This is done in the following manner; from the System Main Menu Screen press on the arrow next to the text ‘System Monitors’ as shown below:

This will display the ‘System Monitor Selection’ Screen, from this screen you can access various machine monitors including the motor VFD system health monitor. Accessing the motor VFD system health monitor requires one further step. Press on the large colored button surrounding the text ‘Motor VFD System’ as detailed on the next page:

Page 109: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 109 of 155

Pressing the ‘Motor VFD System’ monitor button will bring you to the screen shown above, from this screen select the VFD system you wish to monitor by pressing on the colored button surrounding the text relative to your choice, in the following example VFD-100 is selected as shown below:

To return to the main menu simply press the back button in the upper left corner of the display three times as illustrated on the next page:

Page 110: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 110 of 155

12.3 Accessing Feed Water System Health Monitors:

To view all information relating to the water makers feed water system health, access the ‘Feed Water System Monitoring’ screen. This is done in the following manner; from the System Main Menu Screen press on the arrow next to the text ‘System Monitors’ as shown below:

This will display the ‘System Monitor Selection’ Screen, from this screen you can access various machine monitors including the feed water system health monitor. Accessing the feed water system health

Page 111: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 111 of 155

monitor requires one further step. Press on the large colored button surrounding the text ‘Feed Water System’ as detailed below:

By default the system will display system pressures in PSI and system flow rates in GPM. This can be changed to Bar and M3Hr respectively if the user prefers this measuring system. To change from Imperial to Metric display press the ‘Metric’ button in the upper right section of the monitoring screen. As you press the ‘Metric’ button it will change to ‘Imperial’, to return to Imperial display press the ‘Imperial’ button and vice versa as shown below. Please note when switching between Imperial and Metric units the system will remember the last chosen unit of display and will automatically select it next time you access any system monitor:

Readings displayed in PSI & GPM Readings displayed in Bar and M3Hr

Imperial or Metric

Press Here

Page 112: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 112 of 155

Pressing the arrow next to the text ‘Back’ will return you to the ‘System Monitors Selector’ screen, pressing it again will return you to the System Main Menu Screen, as shown below:

12.4 Accessing High Pressure System Health Monitors:

To view all information relating to the water makers high pressure system health, access the ‘High Pressure System Monitoring’ screen. This is done in the following manner; from the System Main Menu Screen press on the arrow next to the text ‘System Monitors’ as shown below:

This will display the ‘System Monitor Selection’ Screen, from this screen you can access various machine monitors including the high pressure system health monitor. Accessing the high pressure system health monitor requires one further step. Press on the large colored button surrounding the text ‘High Pressure System’ as detailed on the next page:

Page 113: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 113 of 155

By default the system will display system pressures in PSI and system flow rates in GPM. This can be changed to Bar and M3Hr respectively if the user prefers this measuring system. To change from Imperial to Metric display press the ‘Metric’ button in the upper left section of the monitoring screen. As you press the ‘Metric’ button it will change to ‘Imperial’, to return to Imperial display press the ‘Imperial’ button and vice versa as detailed below. Please note when switching between Imperial and Metric units the system will remember the last chosen unit of display and will automatically select it next time you access any system monitor:

Readings displayed in PSI & GPM Readings displayed in Bar and M3Hr Pressing the arrow next to the text ‘Back’ will return you to the ‘System Monitors Selector’ screen, pressing it again will return you to the System Main Menu Screen as detailed on the next page:

Imperial or Metric

Press Here

Page 114: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 114 of 155

12.5 Accessing Permeate Water System Health Monitors:

To view all information relating to the water makers permeate water system health, access the ‘Permeate Water System Monitoring’ screen. This is done in the following manner; from the System Main Menu Screen press on the arrow next to the text ‘System Monitors’ as shown below:

This will display the ‘System Monitor Selection’ Screen, from this screen you can access various machine monitors including the permeate water system health monitor. Accessing the permeate water system health monitor requires one further step. Press on the large colored button surrounding the text ‘Permeate Water System’ as detailed on the next page:

Page 115: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 115 of 155

By default the system will display system pressures in PSI, system flow rates in GPM and permeate water salinity in PPM. Pressure and flow readings can be changed to Bar and M3Hr respectively, while permeate water salinity can be changed to uS/CM if the user prefers these measuring systems. To change pressure and flow readings from Imperial to Metric display press the ‘Metric’ button in the upper left section of the monitoring screen. As you press the ‘Metric’ button it will change to ‘Imperial’, to return to Imperial display press the ‘Imperial’ button and vice versa as shown below. Please note when switching between Imperial and Metric units the system will remember the last chosen unit of display and will automatically select it next time you access any system monitor:

Readings displayed in PSI & GPM Readings displayed in Bar and M3Hr

Imperial or Metric

Page 116: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 116 of 155

To change system permeate readings from Imperial to Metric display press the ‘uS/CM’ button in the upper left section of the monitoring screen. As you press the ‘uS/CM’ button it will change to ‘PPM’, to return to PPM display press the ‘PPM’ button and vice versa as shown below:

Readings displayed in PPM Readings displayed in uS/CM As you press the ‘PPM’ button the type of display you see will differ depending on what the regional settings are within the water maker (US/EU) When switching between uS/cm and PPM the system will remember the last chosen unit of display and will automatically return to it when you next access the permeate system monitoring feature.

Pressing the arrow next to the text ‘Back’ will return you to the ‘System Monitors Selector’ screen, pressing it again will return you to the System Main Menu Screen as shown below:

PPM or uS/CM

Press Here

Page 117: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 117 of 155

12.6 Accessing System Logs and Trending

The Atlantic Sea Digital Control system comes loaded with several newreal time element monitors. These monitors’ trend and log data in a plot recorder style whenever the system is in operation. To view these real time monitors access the ‘System Logs and Charts’ screen. This is done in the following manner; from the System Main Menu Screen press on the arrow next to the text ‘System Logs and Charts’ as shown below:

From this screen it is possible to access the several system logs and trending screens. In the following example the VFD system speed logs will be accessed, the following procedure can be used to access any of the system log screen available on the shown menu screen. Press the arrow next to the text “VFD-101-103 Speed Trending Information Recorders, as shown below:

Page 118: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 118 of 155

Pressing the arrow next to the text ‘Back’ will return you to the ‘System Logs and Charts Menu’ screen, pressing it again will return you to the System Main Menu Screen as shown below:

12.7 Accessing TheSystem Pump Hour Meters

The water maker control system is equipped with essential pump hour meters. At all times when any essential pump is in operation the corresponding hour meter is activated. This allows the system operator to see how much usage all relative system pumps have endured since there last re-build by a simple press of a button. Viewing these hour meters is done in the following manner; from the System Main Menu Screen press on the arrow next to the text ‘Essential Pump Hour Meters’ as shown below:

Press here to reset

Press here to go back

Page 119: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 119 of 155

From this ‘System Maintenance Information’ screen it is possible to view the total amount of running hours endured by any essential pump. It is also possible to reset this number after servicing has been completed to prevent continuous system performance warning messages from being called during operation. Resetting of this accumulated hour meter can only be done once the counter has reached or exceeded the relative operation hours maintenance period, until this time, the ‘Reset’ button is not active.

Pressing the arrow in the top left hand corner of the System Maintenance Information screen once will return you to the Main Menu screen.

Page 120: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 120 of 155

12.8 Accessing System Message Centers

To view system message centers, press on the arrow next to the text ‘System Message Centers’ as shown below:

Pressing this button will lead you to the ‘System Message Centers Menu’ Screen, from here you can access all three of the control system message centers.

To access the ‘System Critical Fault’ message center, press on the arrow next to the text ‘System Critical Fault Messages’, doing so will open the requested message center as shown below:

To return back to the menu screen press the back button

Press here to go back

Press here to go back

Page 121: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 121 of 155

To access the ‘System Performance’ message center, press on the arrow next to the text ‘System Performance Messages’, doing so will open the requested message center as shown below:

To return back to the menu screen press the back button

To access the ‘System Status’ message center, press on the arrow next to the text ‘System Status Messages’, doing so will open the requested message center as shown below:

To return back to the menu screen press the back button

Press here to go back

Press here to go back

Page 122: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 122 of 155

To access the ‘VFD System Information’ message center, press on the arrow next to the text ‘VFD System Information, doing so will open the requested message center as shown below:

To return back to the menu screen press the back button

To return to the main menu screen press the arrow in the top left corner of the screen, pressing this button will return you to the main menu screen as shown below:

Press here

Press here to go back

Page 123: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 123 of 155

12.9 Accessing Pressure Sensor Zero Point Calibration Screens

To access the pressuresensor zero point calibration screen, press on the arrownext to the text ‘System Sensor Calibration’, doing this will bring you to the ‘System Sensor Calibration Menu’ screen as shown below:

From this screen you can access the pressuresensor zero point calibration screen by pressing on the arrow next to the text ‘Pressure Sensor Zero-Point Calibration’, doing this will bring you to the ‘Password Required’ screen as shown below:

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Press here to go back

Enter Password and press here

To cancel press here

Page 124: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 124 of 155

Entering the correct password will bring you to the following screen.

From this screen you can perform a zero-point calibration of all connected pressuresensors simultaneously. Please see the ‘System Maintenance’ section for further details.

Pressing the arrow in the top left had corner of the ‘Pressure Sensor Zero Point Calibration’ screen will return you to the ‘System Sensor Calibration Menu’ screen, pressing the arrow in the top left hand corner of the ‘System sensor Calibration Menu’ screen will return you to the System Main Menu, as shown below:

Page 125: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 125 of 155

12.10 Accessing Flow Sensor Zero Point Calibration Screens

To access the flow sensor zero point calibration screen, press on the arrownext to the text ‘System Sensor Calibration’, doing this will bring you to the ‘System Sensor Calibration Menu’ screen as shown below:

From this screen you can access the flow sensor zero point calibration screen by pressing on the arrow next to the text ‘Flow Sensor Zero-Point Calibration’, doing this will bring you to the ‘Password Required’ screen as shown below:

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Press here to go back

Enter Password and press here

To cancel press here

Page 126: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 126 of 155

Entering the correct password will bring you to the following screen.

From this screen you can perform a zero-point calibration of all connected flow sensors simultaneously. Please see the ‘System Maintenance’ section for further details.

Pressing the arrow in the top left had corner of the ‘Flow Sensor Zero Point Calibration’ screen will return you to the ‘System Sensor Calibration Menu’ screen, pressing the arrow in the top left hand corner of the ‘System sensor Calibration Menu’ screen will return you to the System Main Menu, as shown below:

Page 127: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 127 of 155

12.11 Accessing Salinity Sensor Calibration

To access the salinity sensor calibration screen, press on the arrownext to the text ‘System Sensor Calibration’, doing this will bring you to the ‘System Sensor Calibration Menu’ screen as shown below:

From this screen you can access the salinity sensor calibration screen by pressing on the arrow next to the text ‘Salinity Sensor Calibration’, doing this will bring you to the ‘Password Required’ screen as shown below:

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Press here to go back

Enter Password and press here

To cancel press here

Page 128: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 128 of 155

Entering the correct password will bring you to the following screen.

From this screen you can perform a calibration of the salinity sensor system. Please see the ‘System Maintenance’ section for further details.

Pressing the arrow in the top left had corner of the ‘Salinity Sensor Calibration’ screen will return you to the ‘System Sensor Calibration Menu’ screen, pressing the arrow in the top left hand corner of the ‘System sensor Calibration Menu’ screen will return you to the System Main Menu, as shown below:

Page 129: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 129 of 155

12.12 Accessing The System Information Screen

To access the system information screen, press on the arrownext to the text ‘System Information’, doing this will bring you to the ‘System Information’ screen as shown below:

From the screen you can view important information such as software versions and system installed features. Accessing this screen may be required when talking with DSRC technical personnel.

Pressing the arrow in the top left had corner of the ‘System Information’ screen will return you to the ‘System Main Menu’ screen, as shown below:

Page 130: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 130 of 155

13. System Maintenance

13.1 Performing Pressure Sensor Zero-Point Calibrations

To access the pressure sensor zero point calibration screen, press on the arrownext to the text ‘System Sensor Calibration’, doing this will bring you to the ‘System Sensor Calibration Menu’ screen as shown below:

From this screen you can access the pressure sensor zero point calibration screen by pressing on the arrow next to the text ‘Pressure Sensor Zero-Point Calibration’, doing this will bring you to the ‘Password Required’ screen as shown below:

Press here to go back

Enter Password and press here

To cancel press here

Page 131: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 131 of 155

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Entering the correct password will bring you to the following screen.

From this screen you can perform a zero-point calibration of all connected pressure sensors simultaneously, with the exception of sensor PT-1000 as this sensor is an absolute sensor, and therefore cannot be zeroed which is why it is not present on the display.

Before performing zero point calibrations it is extremely important that the following steps are performed, failure to do so may result in the control system reporting ‘consistent calibration errors’ while these types of errors will not prevent the system from running, they will affect the accuracy of the affected field sensors measurement, which could in turn affect the water makers performance.

1. Shut the system down 2. Isolate the incoming water supply 3. Isolate the brine water line 4. Isolate the product water line 5. Perform a complete system drain

Once you have completed all of these steps press the ‘Perform Pressure Sensor Zero Point Calibration’ button on the display, once pressed the control system will perform all required calculations to zero out any static readings.

Page 132: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 132 of 155

If there is a problem detected with a pressure sensing instrument the control system will alert you by displaying a ‘PT-10xx Fault!!’, where ‘xx’ denotes the sensor number. In these situations the zero point calibration features will be disabled. Indication of this status is given to the user as shown below:

In these situations the affected field sensor must be repaired or replaced before zero-point calibration can continue.

Once you have completed your zero point calibrations pressing the arrow in the top left had corner of the ‘Pressure Sensor Zero Point Calibration’ screen will return you to the ‘System Sensor Calibration Menu’ screen, pressing the arrow in the top left hand corner of the ‘System sensor Calibration Menu’ screen will return you to the System Main Menu, as shown below:

Notification of defective sensor channels

Notification that calibration function not available

Page 133: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 133 of 155

13.2 Performing Flow Sensor Zero-Point Calibrations

To access the flow sensor zero point calibration screen, press on the arrownext to the text ‘System Sensor Calibration’, doing this will bring you to the ‘System Sensor Calibration Menu’ screen as shown below:

From this screen you can access the flow sensor zero point calibration screen by pressing on the arrow next to the text ‘Flow Sensor Zero-Point Calibration’, doing this will bring you to the ‘Password Required’ screen as shown below:

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Press here to go back

Enter Password and press here

To cancel press here

Page 134: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 134 of 155

Entering the correct password will bring you to the following screen.

From this screen you can perform a zero-point calibration of all connected flow sensors simultaneously.

Before performing zero point calibrations it is extremely important that the following steps are performed, failure to do so may result in the control system reporting ‘consistent calibration errors’ while these types of errors will not prevent the system from running, they will affect the accuracy of the affected field sensors measurement, which could in turn affect the water makers performance.

1. Shut the system down 2. Isolate the incoming water supply 3. Isolate the brine water line 4. Isolate the product water line 5. Perform a complete system drain

Once you have completed all of these steps press the ‘Perform Flow Sensor Zero Point Calibration’ button on the display, once pressed the control system will perform all required calculations to zero out any static readings.

Page 135: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 135 of 155

If there is a problem detected with a pressure sensing instrument the control system will alert you by displaying a ‘FT-100x Fault!!’, where ‘x’ denotes the sensor number. In these situations the zero point calibration features will be disabled. Indication of this status is given to the user as shown below:

In these situations the affected field sensor must be repaired or replaced before zero-point calibration can continue.

Once you have completed your zero point calibrations pressing the arrow in the top left had corner of the ‘Flow Sensor Zero Point Calibration’ screen will return you to the ‘System Sensor Calibration Menu’ screen, pressing the arrow in the top left hand corner of the ‘System sensor Calibration Menu’ screen will return you to the System Main Menu, as shown below:

Notification of defective sensor channels

Notification that calibration function not available

Page 136: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 136 of 155

13.3 Performing Salinity Sensor Calibrations

To access the salinity sensor calibration screen, press on the arrownext to the text ‘System Sensor Calibration’, doing this will bring you to the ‘System Sensor Calibration Menu’ screen as shown below:

From this screen you can access the salinity sensor calibration screen by pressing on the arrow next to the text ‘Salinity Sensor Calibration’, doing this will bring you to the ‘Password Required’ screen as shown below:

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Press here to go back

Enter Password and press here

To cancel press here

Page 137: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 137 of 155

Entering the correct password will bring you to the following screen.

From this screen you can perform a calibration of the salinity sensor system.

Before performing a calibration please perform the requested actions listed on the screen, these requests have been expanded here for further clarification.

1. Shut the system down 2. Isolate the clients permeate line pipe work (if applicable) and drain the product water line

within the water maker frame. 3. Remove the salinity sensor from the water maker. 4. Place the salinity sensor probe into a bag of uS/cm testing solution.

If required change the value of the testing solution within the controller calibration software by pressing on the value currently entered, a number entry pop up screen will be displayed. Enter the newly required calibration solution value and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated below:

Enter desired set-point value here

Enter Value and press here

To cancel press here

Page 138: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 138 of 155

5. Once the new value has been entered or if this step is not required, simply press the ‘Calibrate Salinity Probe’ button, the moment this button is pressed the displayed salinity reading will be automatically adjusted to reflect the same value as the testing solution.

6. Remove the salinity sensor from the bag of testing solution and re fit it into the water maker. 7. Open all product water valves on the clients pipe work (if required)

Salinity sensor calibration is now complete.

If there is a problem detected with the salinity probe the control system will alert you by displaying a ‘Salinity Sensor Fault Detected’ message. In these situations the salinity sensor calibration feature will be disabled. Indication of this status is given to the user as shown below:

In these situations the salinity sensor fault must be located and be repaired or the sensor replaced before calibration can continue.

Once you have completed your salinity sensor calibrations, pressing the arrow in the top left had corner of the screen twice will return you to the System Main Menu, as shown below:

Notification of defective salinity sensor

Notification that calibration function not available

Page 139: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 139 of 155

14. Manual Actuation of System Valves.

Manual actuation of system valves maybe required in emergency situations. Actuating these valves can be carried out in the following manner:

14.1 Actuating the Membrane Pressure Relief Motorized Valve

To manually actuate this valve the operator must first remove power from the valve actuator motor. This is done by locating the red wire within the controller cabinet. This wire will be found in the following location: Locate TB4 in the lower middle section of the controller enclosure (See figure 1.1)

Figure 1.1

Once TB4 is located, identify terminal number 7, this terminal will have a red wire connected to it, using a small flat bladed screw driver (maximum width 3mm) open the spring clamp terminal by pushing the flat bladed screw driver fully into the terminal release terminal and remove the red wire (See figure 1.2)

Figure 1.2

Page 140: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 140 of 155

Cover the bare conductor of the red wire with electrical insulation tape. You can now close the controller door and power up the system, and when requested to do so you can manually actuate the high pressure by-pass valve by moving the yellow handle into the position required (See figure 1.3)

Figure 1.3

Page 141: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 141 of 155

14.2 Actuating Product Water Diversion Motorized Valves

To manually actuate this valve the operator must first select manual mode on the value actuator body. This can be done by locating the small switch located beneath the valve actuator power and feedback plugs. Once this switch is located, switch it to the ‘Manual’ position. (See figure 2.1)

Figure 2.1

Once the switch has been set to the ‘Manual’ Position the valve can be actuated by turning the handle on top of the valve to the position required (See figure 2.2)

Figure 2.2

Page 142: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 142 of 155

14.3 Actuating Media Filter Control & Feed Water Valves

To manually actuate these valves the operator must first select manual mode on the value actuator body. This can be done by locating the small switch located beneath the valve actuator power and feedback plugs. Once this switch is located, switch it to the ‘Manual’ position. (See figure 3.1)

Figure 3.1

Once the switch has been set to the ‘Manual’ Position the valve can be actuated by turning the handle on top of the valve to the position required (See figure 3.2)

Figure 3.2

Page 143: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 143 of 155

15. Fresh Water Flushing

Each time a running pump is stopped using the ‘Auto-Stop’ button the fresh water flush system will automatically be activated. Once all running pumps have been stopped the fresh water flush valve will open allowing fresh water into the system. The valve will remain open for 10 minutes to allow fresh water to completely fill the water maker pipe work and membrane vessels, during this time the fresh water flush indicator on the control panel door will remain steadily illuminated.

After the 10 minute fresh water flush cycle has ended, the valve will close and the fresh water flush indicator light on the panel door will extinguish. The control system will now enter ‘Sleep Mode’, while in this state the fresh water flush indicator light will illuminate for 1 second each hour. This brief flashing is indicating that the fresh water flush mode is still active but currently waiting for the next fresh water flush cycle to begin.

7 Days after the initial fresh water flush cycle completed, a secondary fresh water flush cycle will begin; the valve will re-open for 10 minutes allowing fresh water to flood the system once again. While the valve is open the fresh water flush indicator light on the panel door will remain steadily illuminated. After the 10 minute cycle has elapsed the control system will return to ‘Sleep Mode’.

This cycle will continue indefinitely, unless a system pump is started by the operator, or the operator cancels the fresh water flush sequence by pressing and holding the “Auto-Stop’ button for 2 seconds.

When the fresh water flush system is flushing; the control system examines the available fresh water pressure, if pressures are detected as being below the system set-point a performance warning notification is raised by the control system as shown below:

Page 144: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 144 of 155

Pressing ‘Highlight AlertMessage’ will highlight the first alarm item. Pressing ‘Scroll Up’ will scroll up through the alarm list Pressing ‘Scroll Down’ will scroll down through the alarm list Pressing ‘Accept This Notification’ will clear the listed alarm notifications and return you to the previous screen. Pressing ‘Back’ will exit the alarm list. Please note the ‘Back’ button is only active if no faults or errors are currently displayed, if errors or faults are displayed, press ‘Accept’ to exit this screen. Pressing ‘More Information On This Notice’will call up the on-line interactive help files associated with this alarm condition, these on-line help files will assist you in diagnosing and solving the problem (if installed) If fresh water pressure increases above the set-point, this warning screen will be canceled. The fresh water flush system will continue to operate while this warning is present.

Page 145: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 145 of 155

16. Activating Accessories

To access the accessory activation screen, press on the arrow next to the text ‘System Accessory Controls’ found on the system main menu screen, as shown below:

From this screen you can access all available system accessories, to switch on or off a system accessory press on the arrow next to the text describing your required accessory (Automatic UV Sterilizer selected during this example). Doing so will call up the accessory password request screen. If you do not have the password to your required accessory contact Danfoss Sea Recovery in order to obtain it (A surcharge for accessories may apply if your unit was not originally purchased with the currently selected accessory)

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Enter Password and press here

To cancel press here

Page 146: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 146 of 155

Once the correct password has been entered, the control system will pass you on to the accessory enable/disable screen, form this screen it is possible to activate or de-activate your selected accessory. The text within the control button reflects the accessories current state. To change the state press on the control button, as you do so the text within the control button will change to show the accessories new state as shown below:

Some accessory enable/disable control screens also offer additional abilities as seen here. These additional abilities relate directly to the functionality of accessory itself, as seen in this example you are given the option to test if the connected UV sterilizer system is actually functioning correctly or not by being given the ability to manually force the UV system into an ‘ON’ state. Please note however that these additional function buttons are only active once you have enabled the accessory. If you accidently leave the accessory in the ‘ON’ state, it will automatically be switched off when you exit this screen.

Once you have changed the accessory state to your requirements, press ‘Save Setting To EEPROM ’button in the lower right corner of the screen to store these changes into system EEPROM. Once the ‘Save Setting TO EEPROM’ button has been pressed the system will advise you that these changes are being stored, once the store is complete the system will return to the main splash screen as shown on the next page:

Press to change state

Press to save changes

Press for additional accessory functions

Page 147: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 147 of 155

Your accessory state has been saved and the system is now ready for operation.

Wait approx. 3 seconds

Page 148: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 148 of 155

17. Automatic Multi-Media Filter Functions

If your system is equipped with an automatic media filter you will be able to perform backwash and rinse cycles of your media filter at the press of a button, your control system will also perform these cleaning cycles automatically when needed.

17.1 Accessing Multi-Media Filter Options

To access the multi-media filter options screen, you will first need to access the accessory control menu, this can be done by pressing the arrow next to the text ‘System Accessory Controls’ found on the ‘System Main Menu’ screen as shown below:

Press on the arrow next to the text ‘Automatic Media Filter’. Doing so will call up the accessory password request screen. If you do not have the password to your required accessory contact Danfoss Sea Recovery in order to obtain it.

Press Here

Enter Password and press here

To cancel press here

Page 149: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 149 of 155

Entry of an incorrect password will result in the password prompt screen remaining visible. The password you have entered will be erased and the password screen will wait for you to attempt again. Press the ‘CAN’ key to cancel this request.

Once the correct password has been entered, the control system will pass you on to the multi-media enable/disable screen, form this screen it is possible to enter into the multi-media system settings screens. To do this, simply press on the button labeled ‘Multi-Media Filter Settings’ as shown below:

Pressing the indicated button will bring you to the following screen:

Press to change media settings

Press on value to change

Page 150: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 150 of 155

To change a value press on the currently entered value, a number entry pop up screen will be displayed. Enter the newly required set-point and press the ‘ENT’ button to complete entry, to cancel the request press the ‘CAN’ button as illustrated below:

From this screen it is possible to change the following system set-points:

17.2 Auto MMF Sequence Delay Time (Minutes) [Range = > 1]

This value stated in minutes determines how long the system will wait before initiating an automatic backwash cycle once the pre-determined differential pressure across the media filter housing has been detected. Once this time expires the controller will shutdown the water maker and prepare the system for an automatic backwash cycle.

Typical values entered here are 5 minutes in all applications

17.3 Auto MMF Backwashing Time (Minutes) [Range = > 1]

This value stated in minutes determines how long the system willbackwash the multi-media filter for. Once this time has expired the controller will shutdown the water maker booster pump and prepare the system for rinsing.

Typical values entered here are 5 minutes in all applications

17.4 Auto MMF Rinsing Time (Minutes) [Range = > 1]

This value stated in minutes determines how long the system will rinse the multi-media filter for. Once this time has expired the controller will shutdown the water maker booster pump and prepare the system for normal operation.

Typical values entered here are 15 minutes in all applications

Enter desired set-point value here

Enter Value and press here

To cancel press here

Page 151: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 151 of 155

17.5 Auto MMF Differential Pressure (PSI) [Range = > 15 &< 35]

This value stated in PSI determines at what differential pressure the controller will initiate an automatic backwashing of the multi-media filter assembly. Once the measured differential pressure reaches this set point the control system will initiate a shutdown timer (if operating in automatic mode) or display a performance warning (if operating in manual mode).

Typical values entered here are 25 PSI in all applications

17.6 Saving Multi-Media Filter Option Settings

Once you are finished inputting these settings press the arrow in the top left hand corner of the screen, doing so will return you to the enable/disable control screen as detailed below:

Once you have changed the multi-media system settings to your requirements, press ‘Save Settings To EEPROM’ button in the lower right corner of the screen to store these changes into system EEPROM. Once the ‘Save Settings To EEPROM’ button has been pressed the system will advise you that these changes are being stored, once the store is complete the system will return to the main splash screen as shown on the next page:

Press Here to Save Setting

Page 152: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 152 of 155

Your multi-media system settings have now been saved and the system is now ready for operation.

Wait approx. 3 seconds

Page 153: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 153 of 155

17.7 Activating the backwashcycle manually while operating the system in automatic mode

If your system is in operation the control system will automatically initiate multi-media backwashing cycles when needed, however you can still initiate these backwash cycles manually if you choose to do so. Please note that if you manually initiate a backwash cycle during automatic operation the system will see this as a manual intervention; hence once the backwash cycle has been completed the system will remain shut-down and will not automatically re-start and re-enter production mode by itself.

To manually initiate a backwashing cycle during automatic modepress panel button #11 ‘Back Wash Status’ (illustrated on page 7), once you press this button the controller touch screen will display the following screen:

If you wish to cancel your request to initiate the backwashing cycle at this time press the ‘No’ button, doing so will cancel the above screen and automatically schedule a backwashing cycle for the next time the system is shutdown normally, if you do not wish to initiate a backwash or schedule a backwash for later simply ignore this screen, after 60 seconds it will self-cancel. If you wish to initiate the backwashing procedure press the ‘Yes’ button on the touch screen or press panel button #11 ‘Back Wash Status’ again.

Once you press either panel button #11 or the ‘Yes’ button on the touch screen the system will begin an automatic shutdown of the water maker and enter the automatic backwashing sequence.

Press Here To Cancel Request

Press Here To Start Backwash

Current Media Filter Operation State Information

System Live Operation Data

Page 154: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 154 of 155

17.8 Automatic activation of the backwashcycle

If your system is in operation the control system will automatically initiate multi-media backwashing cycles when needed, when the control system initiates a backwashing cycle automatically it begins by shutting down the water maker, once the backwashing cycle has completed the control system will automatically re-start the water maker and place it back into production. The control system initiates an automatic backwashing cycle when it detects a high differential pressure across the multi-media filter assembly, before initiating the automatic shutdown procedure the control system will alert the system operator by displaying the following screen:

Once the indicated time has elapsed the system will begin an automatic shutdown of the water maker and enter the automatic backwashing sequence. Once the backwashing sequence has completed the system will re-start and re-enter production mode automatically.

If you wish to skip the countdown time and initiate a backwash cycle manually press the panel button #11 ‘Back Wash Status’ twice, pressing this button in this manner will abort the 5 minute count down and initiate the backwashing cycle immediately. Please note, as a manual intervention was detected the system will no longer automatically re-start and re-enter production mode, instead it will simply remain in shutdown mode once the backwashing cycle has completed.

Delay Before Backwash Starts

Current Media Filter Operation State Information

System Live Operation Data

Page 155: Peme… · Abbreviations: LPS: Low Pressure Switch HPS: High Pressure Switch PT: Pressure Transducer FT: Flow Transducer Analog CH: Variable PLC Input, ranging from 4-20mA mA: Milli-Ampers

[CONTROL SYSTEM OPERATIONS MANUAL] October, 2012

Project:

Doc: Version:

Danfoss Sea Recovery Atlantic Sea 1010032 01a Document Name: Author: Page:

Control System Operations Manual AGE Page 155 of 155

17.9 Activating the backwashcycle manually while in standby mode

If your system is currently in standby mode you can initiate a backwash cycle by pressingpanel button #11 ‘Back Wash Status’ (illustrated on page 7), once you press this button the controller touch screen will display the following screen as shown below:

If you wish to cancel your request to initiate the backwashing cycle at this time press the ‘Cancel Request’ button, doing so will cancel the above screen and return you to the previously displayed screen If you do not wish to initiate a backwash or cancel the request within 60 seconds this screen will self-cancel. If you wish to initiate the backwashing procedure press the ‘Backwash Now’ button on the touch screen or press panel button #11 ‘Back Wash Status’ again.

Once you press either panel button #11 or the ‘Yes’ button on the touch screen the system will begin an automatic backwashing sequence, once the sequence has completed the water maker will return to standby mode.

Last Known Media Filter Status Information

Press Here To Start Backwash

Press Here To Cancel Request