per unit system practice problem solved transformers
DESCRIPTION
Per unit calculationTRANSCRIPT
Per Unit System – Practice Problem
Solved For Easy Understanding
Let’s understand the concept of per unit system by solving an example. In the
one-line diagram below, the impedance of various components in a power
system, typically derived from their nameplates, are presented. The task now is
to normalize these values using a common base.
Figure 1: Oneline Diagram Of A Power System
Now that you have carefully examined the system and its parameters, the
equivalent impedance diagram for the above system would look something like
the following.
Recent Posts Tags
Enter your email address to
subscribe to this blog and
receive notifications of new
posts by email.
Join 429 other subscribers
Email Address
Subscribe
Try Google AdWords™google.com/AdWords
Get $75 Worth of Advertising
When You Spend $25 With
AdWords
Choosing Between
Resistor and Reactor
for Neutral Ground
Impedance
Power Cable Neutral
and System Grounding
Substation SCADA
System - Design Guide
Cable and Conduit Installation
in Substations - Best Practices
Substation Sub-
Surface Engineering:
Power Systems Engineering
Page 1 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
Figure 2: Impedance Diagram Of A Power System
Resistive impedance for most components have been ignored. Rotating machines
have been replaced with a voltage source behind their internal reactance.
Capacitive effects between lines and to ground are ignored as well.
To obtain the new normalized per unit impedances, first we need to figure out
the base values (Sbase, Vbase, Zbase) in the power system. Following steps will
lead you through the process.
Step 1: Assume a system base
Assume a system wide of 100MVA. This is a random assumption and chosen
to make calculations easy when calculating the per unit impedances.
So, = 100MVA
Step 2: Identify the voltage base
Voltage base in the system is determined by the transformer. For example, with
a 22/220kV voltage rating of T1 transformer, the on the primary side of T1 is
22kV while the secondary side is 220kV. It does not matter what the voltage
rating of the other components are that are encompassed by the zone.
See figure below for the voltage bases in the system.
Per Unit System -
Practice Problem
Solved For Easy
Understanding
Power Circuit Breaker
- Operation and
Control Scheme
What Do Symmetrical,
Asymmetrical,
Momentary,
Interrupting, Close &
Latch Ratings Mean?
How to Pass the Power
System PE exam
Power Cable Neutral
and System Grounding
An Overview of What a Geotech
Survey Reveals
Page 2 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
Figure 3: Voltage Base In The Power System
Step 3: Calculate the base impedance
The base impedance is calculated using the following formula:
Ohms…………………………………………………………………..(1)
For T-Line 1: = 484 Ohms
For T-Line 2: = 121 Ohms
For 3-phase load: = 1.21 Ohms
Step 4: Calculate the per unit impedance
The per unit impedance is calculated using the following formulas:
……………………………………………………………………………..(2)
……………………………….(3)
The voltage ratio in equation (3) is not equivalent to transformers voltage ratio.
It is the ratio of the transformer’s voltage rating on the primary or secondary
side to the system nominal voltage on the same side.
For T-line 1 using equation (2): = 0.1 pu
For T-line 2 using equation (2): = 0.5 pu
For 3-Phase load:
Power Factor:
Thus,
Page 3 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
= 1.1495+j1.53267 Ohms
Per unit impedance of 3-phase load using equation (2)= =
0.95+j1.2667 pu
For generator, the new per unit reactance using equation (3)
= 0.2 pu
For transformer T1: = 0.2 pu
For transformer T2: = 0.15 pu
For transformer T3: = 0.16 pu
For transformer T4: = 0.2 pu
For Motor, = 0.25 pu
The equivalent impedance network with all the impedances normalized to a
common system base and the appropriate voltage base is provided below.
Per Unit Impedance Diagram
Summary:
1. Assume a Sbase for the entire system.
2. The Vbase is defined by the transformer and any off-nominal tap setting it
may have.
3. Zbase is derived from the Sbase and Vbase.
4. The new per unit impedance is obtained by converting the old per unit
impedance on old base values to new ones. See equations (2) and (3).
* * * * *
Page 4 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
base values per unit per unit impedances per unit system per unit value Power
transformers
32 Responses to Per Unit System – Practice Problem Solved
For Easy Understanding
IJAJIJAJIJAJIJAJ says:
what do you mean by….. s*-??
anananan says:
Can we find the short circuit current at each end?
samuelsamuelsamuelsamuel says:
A load of 50mw at 0.8 power factor lagging is taken from the 33kv.
( taking a base MVA of 100mva), calculate the terminal voltage of
the synchronous machine? (Please help me solve this question)
thanks
NikhilNikhilNikhilNikhil says:
very useful thanks
alshaiaalshaiaalshaiaalshaia says:
Please subscribe to this blog to receive informative articles. You may also like:
Book Review:
Protective Relaying
- Principles and
Application by
Lewis Blackburn
and Thomas ...
It is hard to miss this
book if you have
been in the power
industry for a while.
You will find it on
the ...
Determine How To
Load Two Paralleled
Transformers
Two three phase
transformers with
ratings shown below
are paralleled on
their secondary
side.Transformer No.
1 - 1000kVA,
4160V/480V, Z =
5.0%Transformer No.
2 ...
Symmetrical
Components -
Demystified
Learning symmetrical
components can be
overwhelming if you
consider its
mathematical aspect
only. It is time to step
back and understand
this concept from ...
Choosing Between
Resistor and
Reactor for Neutral
Ground Impedance
Faults involving
ground produce high
fault current
magnitude especially
when the transformer
(s) neutral is solidly
grounded. The
neutral ground circuit
in the transformer
provides ...
Mounting
Provisions for Pole
Mounted
Transformers
Pole mounted
transformers for
station service in
substations or to feed
residential or
commercial buildings
are fitted with
mounting lugs that
are sized per ...
Page 5 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
How can we determine the voltage on the bus 1
BRianBRianBRianBRian says:
Do you know how to find the voltage at the bus?
Thanks
tahseentahseentahseentahseen says:
Hi
how we can find the voltage in bus1 in PU and in volte
noanoanoanoa says:
tanks alot save me alot of stress
abiabiabiabi says:
. Obtain the per unit impedance(reactance) diagram of the power
system shown in the fig
G1 : 30MVA , 10.5KV, X?=1.6 ?
G2 : 15MVA , 6.6KV, X?=1.2 ?
G3 : 25MVA , 6.6KV, X?=0.56 ?
T1 (3 phase): 15MVA , 33/11KV , X= 15.2 ? per phase on the high
tension side
T2 (3 phase): 15MVA , 33/6.2KV , X= 16 ? per phase on the high
tension side
Transmission line : 20.5 ohm per phase
Load A : 15MW , 11KV , 0.9 p.f lagging
Load B : 40MW , 6.6KV , 0.85 p.f lagging
5
abiabiabiabi says:
how to convert ohms value to per unit value
Lee TaylorLee TaylorLee TaylorLee Taylor says:
Hi, great article – thanks very much! I have a similar problem to
Page 6 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
solve but I am struggling with the Zact calculation. My inputs are
Vrated = 4.16kV, S = 2MVA <-36.87. Can you help?!
bhanubhanubhanubhanu says:
awesome
kaushik vastarparakaushik vastarparakaushik vastarparakaushik vastarpara says:
its really bcoz by reading this my confusion abut selection of base
nd other is very clear…sommust read it frend /…thank u
AdminAdminAdminAdmin says:
@Pavan @Mike: That’s a typo. Correct values are now shown in
the calculations. Since the ratio of Vbase_old/Vbase_new is the
same, the end result, therefore, does not change. Appreciate the
feedback.
PavanPavanPavanPavan says:
This is really helpful. I didn’t really got it when reading through
this, but when I saw the below comment by Mike, it seems like a
question worth answering. However the content is really clear and
understandable. Keep up the good work!
Thanks,
mikemikemikemike says:
I don’t understand one part: When calculating Xtl2 you are using
(22/22) which is reflected from where? Vbase in T2 is 220 primary
and 11 secondary, so where does 22 come from?
The same for Xtl4.
markmarkmarkmark says:
will the impedance or p.u impedance in each line will be like in
series? will the current for the PRIMARY AND SECONDARY of the
transformer now be equal??? how will i find the actual line current
for each line and for the whole system…
Page 7 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
chrischrischrischris says:
A single phase ,350 kva, 1380v generator has an internal
impedance Zg of j6 ohms. The generator is used to supply a load of
250kva/440v at power factor 0.78 lagging. determine: the turns
ratio of the transfomer, the impedance per km if the line between
the generator and the transformer is 5km, the voltage regulation
of the system.
Using the ratings of the generator as base values determine the
generated per unit voltage that is required to produce a full load
current under short circuit condition.
CAN SOMEONE HELP ME WIT THESE CALCULATION PLZ!!!
AdminAdminAdminAdmin says:
Kam,
Once you have the impedance network, use the current division
rule to determine the current flowing each line. I am not sure I
understand “voltage at 3″, if bus 3 is faulted (3ph) then it is zero
otherwise it should be the same as nominal voltage as seen on the
secondary side of the transformer.
I will solve one for the currents in the future but for now, you will
have to learn how to reduce a circuit (using KVL and KCL) to
determine the currents.
kamkamkamkam says:
sorry but i didnt get my reply yet, so could you pls help me
out???????? thanks a lot
karthikkarthikkarthikkarthik says:
very well explained but could you pls show me how to calculate
voltage and current in both lines, will be very greatful , thanks a
lot……….
kamkamkamkam says:
It is really well explained but could you pls show me how to
calculate voltage at but 3 and current in both lines, will be very
greatful , thanks a lot
Page 8 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
manishmanishmanishmanish says:
what if transformers are connected in star and delta connection?
AnayatAnayatAnayatAnayat says:
i am very new to Power side , so i really dont know abt all these
concepts , what we only have T1 and T2 , and all the rating given
are three phase line to line ? how we ll solve it then?
richaricharicharicha says:
very nicely explained….to the point and complete..thanks a lot
SanketSanketSanketSanket says:
VERY NICELY EXPLAINED THANK-YOU ………
I WILL VISIT WEBSITE AGAIN FOR FURTHER REFERENCES.
BABULS RAJBABULS RAJBABULS RAJBABULS RAJ says:
Thank u so much…..after searching for a proper explanation for
the same in so many sites, i got it finally from your site. Clear
explanation with proper diagrams with multi colour…….very nice
…..
AdminAdminAdminAdmin says:
Nice catch. Fixed it. Thanks.
Renjith MRenjith MRenjith MRenjith M says:
Commendable work. But there is a small error. The per-unit
system is the ratio of two quantities of the same units. Therefore
it is unitless. Well that is what I know. So accordingly we specify
the per-unit quatities as just ‘P.U’. So you need to remove the
‘Ohms’ from the text and insert ‘p.u’
Page 9 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
AlfredoAlfredoAlfredoAlfredo says:
It was very useful, but it is short because is necessary to get the
complete solution, any way I liked.
Abdul RauffAbdul RauffAbdul RauffAbdul Rauff says:
Very Good Info About PSA.Thanks Alot
HilaryHilaryHilaryHilary says:
Protection engieering, i have been give the reactance as Xd’ to
calculate faults on a system do i convert to Xd” how do i do this
Leave a Reply
ARCHIVES
January 2013
December 2012
September 2012
June 2012
May 2012
March 2012
January 2012
November 2011
August 2011
July 2011
June 2011
May 2011
April 2011
March 2011
September 2010
July 2010
June 2010
TAG CLOUD
AC system arc flash study arc flash test asymmetrical current base
values cable shield
grounding direct buried conduits
direct transfer trip FACT
generator swing Ground gridHVDC IEEE 1584 John Camara Juan
L. Bala Lewis Blackburn
lockout relays modern power system
momentary rating NCEES Professional
Engineering neutral
grounding NFPA 70EOSHA 1910 Pass PE Exam
permissive over reaching
transfer trip per unit system PE Sample Problems
pilot relayingpower blackout power flow power
system Power
transformers PPE
protective relayingreactive power support short
circuit rating steady state
stability substation conduit details
symmetrical components symmetrical current
system frequency thermal limitation
transformers voltage drop
limitation Zia A. Yamayee
BOOKS ON MY SHELF
Protective Relaying
NEC 2011 Handbook
Power System Analysis and
Design
WELCOME TO PE GURU
ABOUT CONTACT TERMS & CONDITIONS PRIVACY POLICY SITE MAP
Page 10 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems E...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...
Page 11 of 11Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems E...
10/10/2014http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi...