performance analysis of four-partition desiccant wheel and hybrid dehumidification air-conditioning...
TRANSCRIPT
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9
www. i ifi i r .org
ava i lab le at www.sc iencedi rec t .com
journa l homepage : www. e lsev ier . com/ loca te / i j re f r ig
Performance analysis of four-partition desiccant wheel andhybrid dehumidification air-conditioning system
Jongsoo Jeong*, Seiichi Yamaguchi, Kiyoshi Saito, Sunao Kawai
Department of Applied Mechanics and Aerospace Engineering, School of Fundamental Science and Engineering, Waseda University, 3-4-1-58-
210 Okubo, Shinjuku-ku, Tokyo 169-8555, Japan
a r t i c l e i n f o
Article history:
Received 14 July 2009
Received in revised form
8 October 2009
Accepted 2 December 2009
Available online 6 December 2009
Keywords:
Air conditioning
Desiccant system
Desiccant wheel
Geometry
Modelling
Simulation
Performance
Silica gel
* Corresponding author. Tel.: þ81 3 5286 324E-mail address: [email protected] (J.
0140-7007/$ – see front matter ª 2009 Elsevidoi:10.1016/j.ijrefrig.2009.12.001
a b s t r a c t
A desiccant dehumidification system with air can decrease energy consumption because it
can be driven by low-grade waste heat below 80 �C. If this system can be driven by low-
temperature heat sources whose temperature is below 50 �C, exhausted heat from fuel
cells or air conditioners that exist everywhere can be used as heat sources. This could lead
to considerable energy saving. This study provides a detailed evaluation of the perfor-
mance of a four-partition desiccant wheel to make a low-temperature driving heat source
possible and achieve considerable energy saving by the simulation and experiment.
Further, the study investigates the in-depth performance of a hybrid air-conditioning
system with a four-partition desiccant wheel by simulation. As a result, it was clear that
there exists an optimum rotational speed to maximize the dehumidification performance
and that the hybrid air-conditioning system improves COP by approximately 94% as
compared to the conventional vapour compression-type refrigerator.
ª 2009 Elsevier Ltd and IIR. All rights reserved.
Analyse de la performance d’une roue deshydratante a quatresegments et d’un systeme de conditionnement d’air adeshydratant hybride
Mots cles : Conditionnement d’air ; Systeme a deshydratant ; Roue deshydratante ; Geometrie ; Modelisation ; Simulation ; Performance ;
gel de silice
7; fax: þ81 3 5286 3259.Jeong).er Ltd and IIR. All rights reserved.
Nomenclature
Ab area of desiccant surface except for curve-shaped
desiccant surface in contact with air (m2)
Af area of curve-shaped desiccant surface in contact
with air (m2)
D diffusion coefficient (m2 s�1)
d diameter of desiccant wheel (m)
dh hydraulic diameter (m)
G mass flow rate (kg s�1)
h specific enthalpy (J kg�1)
hads adsorption heat (J kg�1)
hvap latent heat (J kg�1)
jm mass flux (kg m�2 s�1)
Kh overall heat transfer coefficient (W m�2 K�1)
Km overall mass transfer coefficient (kg m�2 s�1)
L desiccant length along air flow path (m)
le entrance region length (m)
lp length of plane in control volume (m)
lh pitch distance between flat walls (m)
ma mass fraction of water vapour in moist air
(kg kg�1)
mb mass fraction of water vapour in equilibrium of
the desiccant wall (kg kg�1)
N rotational speed (rph)
Nu Nusselt number (–)
qs heat flux (W m�2)
Q heat transfer rate (kW)
Pr Prandtl number (–)
Re Reynolds number (–)
RH relative humidity (–)
Sc Schmit number (–)
Sh Sherwood number (–)
T temperature (�C)
t thickness of corrugated sheet (m)
u velocity (m s�1)
V volume flow rate (m3 h�1)
Va volume of air flow path (m3)
Vb volume of desiccant bed (m3)
W power (kW)
X mass fraction of water in the desiccant (kg kg�1)
x humidity ratio (kg kg(DA)�1)
a heat transfer coefficient (W m�2 K�1)
b mass transfer coefficient (m s�1)
q angle of desiccant wheel (rad)
l thermal conductivity (W m�1 K�1)
hcom compressor efficiency (–)
hS content ratio of silica gel (–)
r density (kg m�3)
u angular speed of desiccant wheel (rad s�1)
z z axis of air flow path (m)
Subscripts
a moist air
ad adiabatic
ads adsorption
b desiccant bed
co cooling
com compressor
des desorption
eva evaporator
hyb hybrid system
i inlet
mde mechanical dehumidification
o outlet
p pure
pi process air at inlet
pro process air
r refrigerant
reg regeneration air
ri regeneration air at inlet
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9 497
1. Introduction
Since a desiccant dehumidification method can dehumidify
air by converting latent heat into sensible heat, it is unnec-
essary to supercool and to reheat the air on a mechanical
dehumidification system such as a compression-type refrig-
erator (ASHRAE, 2001). Therefore, this method attracts atten-
tion as the air-conditioning system from the view point of
energy saving and amenity. In the normal desiccant dehu-
midification system (Harriman, 1994; Meckler, 1994), an
approximately 80 �C heat source is directly required to dehu-
midify the outdoor air. If an electric heater or boiler is used as
this driving heat source, it runs counter to energy saving. In
order to solve this problem, we have investigated the desic-
cant wheel dehumidification method with the multistage
adsorption and regeneration process to make it possible to use
the low-temperature heat source that is approximately
40–50 �C from the compression-type refrigerator (Inagaki
et al., 2004; Shibao et al., 2006).
As a result, it turned out that we could construct a highly
efficient air-conditioning system by combining the multistage
desiccant dehumidification system with the compression-
type refrigerator. However, the system increased in size
because of the multiple desiccant wheels. Accordingly, in
a previous report (Shibao et al., 2007), we suggested the four-
partition desiccant wheel to downsize multiple desiccant
wheels. This wheel can realize the double-stage adsorption
and regeneration process in only one desiccant wheel. Lately,
Ge et al. (2008) also experimentally investigated its perfor-
mance under various operation conditions for a one-rotor
two-stage rotary desiccant cooling system. However, as it was
not discussed theoretically, the performance of the four-
partition desiccant wheel system was not totally evaluated
considering driving heat source.
For the hybrid air-conditioning system with desiccant,
Yadav (1995), Dhar and Singh, 2001 and Jia et al. (2006) inves-
tigated a performance of a hybrid desiccant cooling system
comprising the conventional vapour compression-type
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9498
refrigerator coupled with a desiccant dehumidifier. However,
as the conventional single stage desiccant was used for this
system, the condensation temperature of the vapour
compression-type refrigerator increases greatly. And, some-
times, an electric heater is also used to compensate the
shortage of the driving heat. This system can’t increase the
system performance. To accomplish high performance hybrid
desiccant air-conditioning system with only vapour
compression-type refrigerator, it needs to decrease the driving
heat source temperature for the desiccant regeneration.
Hence, the four-partition desiccant wheel has been investi-
gated to decrease the driving heat source temperature as
hybrid system.
To construct the hybrid system with the four-partition
desiccant wheel, this study investigates the in-depth perfor-
mance of the four-partition desiccant wheel with the simu-
lation and experiment to clearly evaluate the characteristics
of a four-partiton desiccant wheel; effect of the regeneration
temperature, rotational speed of desiccant wheel, cooling
temperature, process air flow rate, and humidity of the
ambient air. Moreover, to realize a high efficiency for the air-
conditioning system and amenity in the room at the same
time, we further discuss the performance of a new type of
hybrid air-conditioning system that combines the four-parti-
tion desiccant wheel with the compression-type refrigerator
by simulation as well.
2. Four-partition desiccant wheel and hybridair-conditioning system
Fig. 1 shows a hybrid air-conditioning system that combines
two conventional desiccant wheels with the compression
cycle, and Fig. 2 shows the hybrid air-conditioning system
with a four-partition desiccant wheel is divided by the equal
area ratio on each flow path. The four-partition desiccant
wheel used in the experiment is shown in Fig. 3. Fig. 4 illus-
trates the driving points of each cooling and dehumidification
system, such as mechanical dehumidification
including a reheat process with the
compression-type refrigerator, the normal type of desiccant
dehumidification that has one desiccant wheel
, and a two-stage dehu-
midification. The four-partition desiccant wheel that can
realize the double-stage adsorption and regeneration process
Fig. 1 – Hybrid air-conditioning syst
with only one desiccant wheel has the same air flow path as
two desiccant wheels – process air and
regeneration air , as shown in Fig. 4.
In the process , the process air precools before the
moisture of the process air is removed. Further, after the first-
stage dehumidification by the desiccant wheel process
, the process air at the process is cooled by
evaporator again. In the second-stage dehumidification
process , the moisture is removed by the desiccant
again, and then, the air cools down to the target process air
outlet temperature at point . Otherwise, the regeneration air
preheats in the process before the regeneration air
flows into the desiccant wheel. After the first-stage process
, the regeneration air heats up in the condenser of the
refrigerator in process as shown in Fig. 2. Then, the
regeneration air goes through the second-stage regeneration
process .
Surplus condensation heat is rejected to the ambient air, as
shown in Fig. 1 or Fig. 2 considering the entire heat balance of
the system. Thus, the temperature of the process air can be
lowered on the dehumidification air flow path so that the
regeneration temperature at point and can also be lower.
Consequently, the heat source temperature can be reduced
drastically. Further, as it is unnecessary to cool the process air
below the dew point temperature, this dehumidification
method with the four-partition desiccant wheel can save the
energy greatly. The refrigerant of the compression-type
refrigerator is R134a.
3. Detailed structure and mathematicalmodel of desiccant wheel, and model of otherelements
Fig. 5 shows the detailed structure and model of the desiccant
wheel. The structure of the wheel is usually realized by arrayal
made up of a corrugated lamina and a plane that are sheets of
the glass fiber impregnated with desiccant. The diameter of the
desiccant wheel that is made of silica gel is 250 mm, and the
thickness is 200 mm. These are the same as those of the actual
desiccant wheel; HY-SG. Specifications of this desiccant wheel
and property of desiccant are listed in Table 1. A mathematical
model of the desiccant wheel is based on the static simulation
model constructed by Yamaguchi et al. (2007).
em with two desiccant wheels.
Fig. 2 – Hybrid air-conditioning system with four-partition desiccant wheel.
Fig. 3 – Four-partition desiccant wheel.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9 499
3.1. Assumptions
Some assumptions are required to build the simulation
model. These assumptions are as follows:
� As the desiccant walls move along the q direction, the air
that flows in the channel also moves along the q direction.
However, the movement of the air along the q direction is
considerably slower than that in the z direction. Therefore,
the movement of the air in the q direction can be neglected.
� The resistance of heat and mass transfer in the z and q
directions inside the desiccant walls can be neglected. In
other words, heat and mass transfer are that by forced
convection transfer and the diffusion, respectively, between
air and desiccant wall, and are considered on only direction
of air – desiccant.
� The entrance region length can be neglected because it is
considerablyshorterthanthelengthof thedesiccantwheel (L).
3.2. Model of desiccant
For the air side, the continuity equation of the entire moist air is
VavðrauaÞ
vzþ jm
�Af þAb
�¼ 0 (1)
The continuity equation of the moisture vapour is
0 20 40 60 800
0.01
0.02
0.03
Temperature T oC
102030406080
5
15
1
Hum
idit
y ra
tio
x kg
/kg(
DA
) Four-partition dehumidification Process air Regeneration air
Conventional dehumidification Process air Regeneration air
Mechanical dehumidification
Cooling temperature Regeneration temperature
''
'
'
Fig. 4 – Air flow of aixr-conditioning systems.
12
NN-1 1 2 M
Z
zz
Inlet air
Inlet wheelOutlet wheel
Outlet air
0
Desiccant bed
qs jmAir
auaxa
b xb
Ab Af
Control volume
Va
VbVa
Vb
Air channelDesiccant wall
lp
Air channel
t
l h
t /2
Fig. 5 – Detailed structure and model of desiccant wheel.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9500
VavðrauaxaÞ
vzþ jm
�Af þ Ab
�¼ 0 (2)
The energy equation of the air is
VavðrauahaÞ
vzþ�jmhvap þ qs
��Af þ Ab
�¼ 0 (3)
For the desiccant, the continuity equation of the desiccant is
Vbuvrb
vq� jm
�Af þ Ab
�¼ 0 (4)
Table 1 – Specifications of this desiccant wheel andproperty values of desiccant.
Length of desiccant wheel L m 0.2
Diameter of desiccant wheel d m 0.25
Thickness of corrugated sheet t mm 0.2
Length of plane in control
volume
lp mm 3.8
Pitch distance between
flat walls
lh mm 1.9
Channel hydraulic
diameter
dh mm 1.5
Surface area per volume
of air flow path
(AbþAf)/Va m2 m�3 3000
Surface area per
volume of desiccant
(AbþAf)/Vb m2 m�3 6000
Area ratio of wheel on
regeneration air side
% 50 (each
part 25%)
Area ratio of wheel
on process air side
% 50 (each
part 25%)
Desiccant – Silica gel
Content ratio of
silica gel
hS – 0.7
Apparent density
of desiccant
kg m�3 800
Specific heat of
desiccant
J kg�1 K�1 980
The continuity equation of the water content in the desic-
cant is
VbuvðrbXbÞ
vq� jm
�Af þAb
�¼ 0 (5)
The energy equation of the desiccant is
VbuvðrbhbÞ
vq��jmhads þ qs
��Af þAb
�¼ 0 (6)
The mass and heat transfer rates are
jm ¼ Kmðma �mbÞ (7)
qs ¼ KhðTa � TbÞ (8)
The overall mass and heat transfer coefficients are
Km ¼ ShraDa
dh(9)
Kh ¼ Nula
dh(10)
When the simulation is carried out, the finite volume
method is adopted using the above model. The heat and mass
transfers between the air and the desiccant walls are divided
into the forced convection transfer and the diffusion,
respectively, on desiccant walls. Shah (1975) investigated the
forced convection heat transfer in a small air channel shown
in Fig. 5. According to his results, a Nusselt number is given for
laminar and fully developed conditions with a constant
surface temperature.
Nuhadh=la ¼ 2:12 (11)
Sherwood number is given by the analogy between the heat
and the mass transfers. The value is
Shhbdh=Da ¼ 2:12 (12)
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9 501
For laminar flow, the entrance region length (le) may be
expressed as follows:
le=dh ¼ 0:05Re ðPr or ScÞ (13)
Under the experimental conditions of this study, the
entrance region length is approximately 5% of the length of
the desiccant wheel. Therefore, the entrance region length
can be neglected.
Furthermore, for the heat and mass transfers, we investi-
gated the non-dimensional overall heat and mass transfer
coefficients that include both of the convective and conduc-
tive resistance derived from the experiment (Yamaguchi et al.,
2007) illustrated in Fig. 6. Hence, Fig. 6 also shows the only
convective heat and mass transfer performance for the air
side from the calculation. These are almost 2.12 as shown in
Eqs. (11) and (12) and almost agree with the convective
performances. This implies that the resistance of the heat and
mass transfers is controlled by the air side of the desiccant
wheel. This is attributed to the fact that the thickness of the
wall is considerably smaller than the size of the air channel.
3.3. Boundary conditions
For boundary conditions, the conditions of the regeneration
and process air (flow rate, humidity ratio, and temperature)
are given at the inlet of the desiccant wheel.
0 � q <p
2; p � q <
3p
2; z ¼ 0 ðProcess air at inletÞ
Tair ¼ Tpi; xair ¼ xpi; uair ¼ upi (14,15,16)
p
2� q < p;
3p
2� q < 2p; z ¼ L; ðRegeneration air at inletÞ
Tair ¼ Tri; xair ¼ xri; uair ¼ uri (17,18,19)
3.4. Properties of silica gel
Barlow (1982) described the adsorption heat and the adsorp-
tion isotherm of a silica gel.
The adsorption heat is expressed as a function of the mass
fraction Xp (pure silica gel) of water in the desiccant and the
latent heat hvap of evaporation. It follows that
Xp ¼ Xb=hS (20)
15 20 25 30 350.5
1
5
10
50
Non
-dim
ensi
onal
over
all h
eat t
rans
fer
coef
fici
ent
Rotational speed N rph
Regeneration temperature: 80 : 70 : 60
Fig. 6 – Non-dimensional overall hea
Xp < 0:1
hads=hvap ¼ 1:3� 1:75Xp (21)
Xp � 0:1
hads=hvap ¼ 1:14� 0:15Xp (22)
Adsorption isotherm is given by
RH ¼
�0:616238Xp þ 16:7916X2
p � 74:34228X3p þ 116:6834X4
p
�
f1� ðT� 40Þ=300g(23)
The desiccant wall does not contain only pure silica gel. The
mass fraction Xb of water in actual desiccant gives relation to
Xp of pure silica gel by the content ratio (hS) of silica gel as
shown in Eq. (20). Therefore, Eq. (23) can be expressed as pure
desiccant adsorption isotherm considering the content ratio
of the pure silica gel. Content ratio (hS) of silica gel is 0.7.
3.5. Model of other elements
Model of hybrid desiccant system and mechanical dehumid-
ification system with same elements is as below.
For the model of compressor, expansion valve, evaporator
and condenser in hybrid desiccant system, the continuity
equation of the refrigerant is
Gr�o � Gr�i ¼ 0 (24)
In compressor, the energy equation of the refrigerant is
Grho � Grhi �Wcom ¼ 0 (25)
The compressor efficiency is as follows
hcom ¼had � hi
ho � hi(26)
In expansion valve, the energy equation of the refrigerant is
Grho � Grhi ¼ 0 (27)
For the energy equation of evaporator and condenser, the
energy equation is
Grho � Grhi � Qr ¼ 0 ðin case of condenser :
þ Qr; in case of evaporator : � QrÞ (28)
15 20 25 30 350.5
1
5
10
50
Non
-dim
ensi
onal
over
all m
ass
tran
sfer
coe
ffic
ient
Rotational speed N rph
Regeneration temperature: 80 : 70 : 60
t and mass transfer coefficients.
Fig. 7 – Flow diagram of experimental setup.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9502
Heat transfer performance of heat exchanger is simply
decided by approach temperature, degree of superheat and
degree of subcooling. The approach temperature of evapo-
rator is decided with temperature difference between evapo-
ration temperature and heat exchanger outlet air
temperature. The approach temperature of condenser is
defined as temperature difference between condensation
temperature and heat exchanger outlet air temperature.
Degree of superheat in the evaporator and degree of sub-
cooling in the condenser are shown in Table 2.
4. Experimental method of four-partitiondesiccant wheel
We have conducted an experiment and simulation in order to
examine theactual performance of the four-partition desiccant
wheel and investigated the validity of the simulation model
with the experiment in detail by fully examining the effect of
many parameters – the regeneration temperature, rotational
speed, cooling temperature, process air volume flow rate, and
ambient air humidity ratio – on the performance of the four-
partition desiccant wheel. This is because the model and the
detailed performance of the four-partition desiccant wheel
have not been clarified yet. This experiment is carried out in
order to justify the assumption that the four-partition desic-
cant wheel can be used for the hybrid air-conditioning system.
Fig. 7 shows the flow diagram of the experimental facility for
the four-partition desiccant wheel and the measurement
points. For the regeneration air inlet temperature to the
desiccant wheel, the temperature at point is equivalent to
the temperature at point , and the process air inlet temper-
ature at point flowing into the desiccant wheel agrees with
temperature at point in Fig. 2. Fig. 8 shows the condition
generator of the air. Table 3 gives experimental conditions.
Simulation conditions are of course the same as these.
5. Simulation and experimental results forfour-partition desiccant wheel
5.1. Validity of experiment accuracy and definition ofparameters
Fig. 9 for example shows the total dehumidification rate of the
moisture in the dehumidification side and the regeneration
rate in the regeneration process. From this figure, the
Table 2 – Simulation conditions of conventionalcompression-type refrigerator.
Evaporator Approach temp. �C 5.0
Degree of superheat �C 5.0
Condenser Approach temp. �C 5.0
Degree of subcooling �C 0.0
Compressor Adiabatic efficiency – 0.8
Rotational speed rpm 2000
Process air Mass flow rate kg(DA)/s 0.04
Outdoor air Mass flow rate kg(DA)/s 0.04
experimental accuracy for the moisture balance of four-
partition desiccant wheel is satisfactory level in less than
approximately 10% error.
To show the simulation and experimental results, the
following parameters are used: cooling temperature Tco is the
temperature of the process air at the entrance of the desiccant
wheel (points 2 and 4 in Fig. 4). Regeneration temperature Treg
is a temperature of the regeneration air at the entrance of the
desiccant wheel (points 8 and 10 in Fig. 4). Dehumidification
performance Dx is defined by the difference between the inlet
and the outlet humidity ratio of the process air.
5.2. Effect of regeneration temperature
Fig. 10 shows the effect of the regeneration temperature on
the dehumidification performance and air states at each
measuring point with the fixed desiccant wheel rotational
speed, cooling temperature, ambient air inlet humidity ratio,
and process and regeneration air inlet velocity shown in Table
3. The most important point from this experiment is that the
target of dehumidification performance can be achieved by
the heat source below 50 �C.
5.3. Effect of rotational speed
Fig. 11 shows the effect of the rotational speed on the
dehumidification performance and air states at each
measuring point with the fixed cooling temperature, regen-
eration temperature, ambient air inlet humidity ratio, and
process and regeneration air inlet velocity shown in Table 3.
In this experiment, the humidity difference is maximized as
3.2 [g/kg(DA)] when the rotational speed is approximately 4
[rph]. Therefore, this system should be designed at the point
of maximum humidity difference.
Fig. 8 – Condition generator.
Table 3 – Simulation and experimental conditions.
Process air inlet (1 in Fig. 2) temp. �C 28.0
Process air inlet humidity ratio g/kg(DA) 11.9
Process air inlet relative humidity % 50.0
Regeneration air inlet (7 in Fig. 2) temp. �C 32.3
Regeneration air inlet humidity ratio g/kg(DA) 19.5
Regeneration air inlet relative humidity % 63.0
Cooling temp. (2 and 4 in Fig. 2) �C 18.0
Mass flow rate of process air kg(DA)/s 0.04
Mass flow rate of regeneration air kg(DA)/s 0.04
Rotation speed of desiccant wheel rph 4.0
Process and regeneration air inlet velocity m/s 2.0
0.00 0. 05 0. 10 0.15 0.20 0.25 0. 300.00
0.05
0.10
0.15
0.20
0.25
0.30+10%
-10%
+20%
-20%
0%
Adsorption mass flow rate Gads g s-1
Des
orpt
ion
mas
s fl
ow r
ate
Gde
sg
s-1
Wheel thickness: 200 mmRegeneration temp.: 35 - 55ºCRotational speed: 5rphSuperficial velocoty: 4m s-1
Fig. 9 – Moisture balance between the dehumidification
rate and the regeneration rate.
10
20
30
40
50
Tem
pera
ture
To C T4: : Fixed value
T5
6
8
10
12
14
Hum
idity
rat
iox
g/kg
(DA
)
10
20
30
40
50
Tem
pera
ture
To C
T2: Fixed valueT3
x2: Fixed valuex3
4
6
8
10
12
Hum
idity
rat
iox
g/kg
(DA
)
x4x5
0
2
4
6
8
10
Hum
idity
dif
fere
nce
xg/
kg(D
A)
0
2
4
6
8
Rot
atio
nal s
peed
Nrp
h
Simulation
Experiment
Rotational speed: Fixed value
30 40 50 60 7030
40
50
60
70
Regeneration temperature Treg regoC
Tem
pera
ture
To C T10
T11
18
20
22
24
26
Hum
idity
rat
iox
g/kg
(DA
)
30
40
50
60
70
Tem
pera
ture
To C
T8T9
x8: Fixed valuex9
30 40 50 60 7020
22
24
26
28
Regeneration temperature T oC
Hum
idity
rat
iox
g/kg
(DA
)
x10x11
Δ
Fig. 10 – Effect of regeneration temperature on the dehumidification performance and air states at each point.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9 503
0
10
20
30
40
Tem
pera
ture
To C
T4: Fixed valueT5
8
10
12
14
16
Hum
idity
rat
iox
g/kg
(DA
)
0
10
20
30
40
Tem
pera
ture
To C
T2: Fixed valueT3
x2: Fixed valuex3
Simulation
Experiment
6
8
10
12
14
Hum
idity
rat
iox
g/kg
(DA
)
x4
x5
0
2
4
6
8
10
Hum
idity
dif
fere
nce
xg/
kg(D
A)
0 5 10 15 2020
30
40
50
60
Rotational speed N rph
Tem
pera
ture
To C
T10: Fixed value T11
18
20
22
24
26
Hum
idity
rat
io
xg/
kg(D
A)
20
30
40
50
60
Tem
pera
ture
To C
T8: Fixed value T9
x8: Fixed value x9
0 5 10 15 2020
22
24
26
28
Rotational speed N rph
Hum
idity
rat
iox
g/kg
(DA
)
x10
x11
Fig. 11 – Effect of rotational speed on the dehumidification performance and air states at each point.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9504
5.4. Effect of cooling temperature
Fig. 12 shows the effect of the cooling temperature on the
dehumidification performance and air states at each
measuring point with the fixed desiccant wheel rotational
speed, regeneration temperature, ambient air inlet humidity
ratio, and process and regeneration air inlet velocity shown
in Table 3. The process air can be dehumidified by the
regeneration air whose temperature is approximately 43 �C,
even though the cooling temperature is 18 �C; this tempera-
ture is significantly higher than the cooling temperature
(approximately 10 �C) of the mechanical dehumidification
system. In addition, the tendency of the performance
changes when the cooling temperature is approximately
17 �C. This is because the temperature of the process air
reaches the dew point below approximately 17 �C so that
some water is removed from the air as the condensed water
in the first cooling process.
5.5. Effect of process air volume flow rate
Fig. 13shows the effect of the processair volumeflow rate on the
dehumidification performance. When the process air volume
flow rate of the process air path and regeneration air path is
10 15 20 25 3020
30
40
50
60
Cooling temperature TcooC
Tem
pera
ture
To C T10: Fixed value
T11
18
20
22
24
26
Hum
idity
rat
io
xg/
kg(D
A)
x8: Fixed valuex9
20
30
40
50
60
Tem
pera
ture
To C
T8: Fixed valueT9
10 15 20 25 3018
20
22
24
26
Cooling temperature TcooC
Hum
idity
rat
io
xg/
kg(D
A)
x10
x11
0
10
20
30
40
Tem
pera
ture
To C T4
T5
6
8
10
12
14
Hum
idity
rat
io
xg/
kg(D
A)
0
10
20
30
40
Tem
pera
ture
To C
T2
T3
x2
x3
4
6
8
10
12
Hum
idity
rat
io
xg/
kg(D
A)
x4
x5
0
2
4
6
8
10
Hum
idity
dif
fere
nce
xg/
kg(D
A)
0
2
4
6
8
Rot
atio
nal s
peed
Nrp
h
Simulation
Experiment
Rotational speed: Fixed value
Fig. 12 – Effect of cooling temperature on the dehumidification performance and air states at each point.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9 505
changed simultaneously, the rotational speed, cooling
temperature, regeneration temperature, ambient air inlet
humidity ratio shown in Table 3 is fixed, the humidity difference
has a maximum point as the effect of the fixed rotational speed.
5.6. Effect of ambient air inlet humidity
Fig. 14 shows the effect of the ambient air inlet humidity ratio
on the dehumidification performance with the fixed the
rotational speed, cooling temperature, regeneration temper-
ature, and process and regeneration air inlet velocity shown in
Table 3. The humidity difference between the process air inlet
and outlet state becomes wide as the inlet humidity ratio of
the ambient air decreases.
5.7. Validity of the model
The simulation results are in complete agreement with the
experimental results. Therefore, the validity of the model is
confirmed.
6. Simulation method of conventionalcompression-type refrigerator and hybridair-conditioning system
The performance of the hybrid air-conditioning system
with the four-partition desiccant wheel is compared with
the conventional vapour compression-type refrigerator by
0 50 100 150 2000
2
4
6
8
10
Process air volume flow rate V m3/h
Simulation Experiment
Hum
idity
dif
fere
nce
x g/
kg(D
A)
Δ
Fig. 13 – Effect of process air volume flow rate on the
dehumidification performance.
Processair
Exhaust air
Compressor
Condenser 1Condenser 2
Expansion valve
Supply air
Evaporator
Outdoorair
Fig. 15 – Schematic representation of compression-type
refrigerator as mechanical dehumidification.
hyb–eva hyb–proQ G h h (32)
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9506
the simulation. Fig. 15 shows the flow diagram of the
conventional compression-type refrigerator as mechanical
dehumidification, which reheats the process air by its
condensation heat. The numbers in Fig. 15 correspond with
the numbers in Fig. 4. To evaluate the performance of each
system, pressure drops in the evaporator and the condenser
of the compression-type refrigerator are not considered.
Further, the adiabatic efficiency of the compressor stays
constant at 0.8. Simulation conditions and input air condi-
tions of the compression-type refrigerator are given in Tables
2 and 3, respectively. The COP of the conventional
compression-type refrigerator and the hybrid air-condi-
tioning system is defined as
COPmde ¼Qmde�eva
Wmde�com(29)
COPhyb ¼Qhyb�eva
Whyb�com(30)
For the hybrid air-conditioning system, the regeneration
and the cooling temperatures of the desiccant wheel corre-
spond with the condensation and evaporation temperatures
with the approach temperature, respectively.
The cooling heat of the conventional compression-type
refrigerator as shown in Figs. 4 and 15 is
( )mde–eva mde–proQ G h h (31)
12 15 18 21 240
2
4
6
8
10
Ambient air humidity ratio x g/kg(DA)
Simulation Experiment
Hum
idity
dif
fere
nce
x g/
kg(D
A)
Δ
Fig. 14 – Effect of ambient air inlet humidity ratio on the
dehumidification performance.
The cooling heat of the hybrid air-conditioning system as
shown in Figs. 2 and 4 is Silica gel is used as the desiccant.
The rotational speed of the desiccant wheel has the optimum
point to maximize the system performance. The conditions of
the ambient air are assumed to be the one in summer in
Tokyo. Moreover, the approach temperature between the
refrigerant and the air in the heat exchanger remains
constant, for instance, the evaporator approach temperature,
evaporator superheat temperature, and condenser approach
temperature are 5 �C. SHF (sensible heat factor) is the sensible
heat load per all the heat load in the room. Exhaust air
temperature in Fig. 2 is also decided adopting the approach
temperature by ambient air.
7. Simulation results for hybridair-conditioning system
7.1. Effect of SHF
Fig. 16 shows the effect of SHF on the characteristics and
performance of the system, for instance, the refrigerant
condensation temperature, the regeneration air temperature,
the refrigerant evaporation temperature (the refrigerant evap-
oration temperature needed for the mechanical dehumidifica-
tion is also shown), the heat in the condenser and the
regeneration air, the compressor power, and COP (COP of the
mechanical dehumidification is also indicated). In this simula-
tion, SHF is changed by the humidity ratio of the process air
outlet, point . The temperature of points , , and is equal;
this temperature is 18 �C. When SHF is more than 0.59 (Region
A), the condensation temperature remains constant. This is
because the regeneration air temperature at points and is
lower than the setting temperature of the exhaust air at point .
Consequently, the condensation temperature cannot be
reduced even though the regeneration temperature decreases.
The evaporation temperature also remains constant to make
the temperature, point , of the process air constant. Hence, the
COP becomes constant.
30
40
50
60
Tem
pera
ture
To C Regeneration air ,
Exhaust air Condensation
0
5
10
15
20
Eva
pora
tion
tem
pera
ture
To C
Hybrid Mechanical
dehumidification
0.4 0.5 0.6 0.70
0.5
1
1.5
2
Hea
t tra
nsfe
r ra
teQ
kW
SHF
Condenser Regeneration air
Region ARegion B
0
0.1
0.2
0.3
0.4
0.5
Com
pres
sor
pow
er
Wco
mkW
2
3
4
5
6
7
8
CO
P
Hybrid Mechanical
dehumidification
0.4 0.5 0.6 0.720
40
60
80
100
SHF
Eff
icie
ncy
impr
ovem
ent
%
Region ARegion B
Fig. 16 – Effect of SHF.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9 507
In contrast, the COP of the mechanical dehumidification
increases with increasing SHF. Therefore, the efficiency
improvement of the hybrid air-conditioning system decreases
with increasing SHF. When SHF is less than 0.59 (Region B),
owing to the increase in the latent heat to regenerate the
desiccant, the regeneration and the condensation temperature
need to be raised. Thus, the compressor power increases, and
the COP decreases with decreasing SHF. The evaporation
temperature becomes lower on the mechanical dehumidifi-
cation as compared to the hybrid system when SHF decreases;
therefore, the COP of the mechanical dehumidification
decreases with decreasing SHF. Further, the efficiency
improvement of the hybrid system decreases. All the
condensers have sufficient heat to regenerate the desiccant.
This implies that the hybrid system can be driven by only the
waste heat from the compression-type refrigerator without
any other heat source. The COP of the hybrid system is higher
than the mechanical dehumidification shown in the psycho-
metric chart of Fig. 4 and flow diagram of Fig. 14. For example,
when SHF is 0.59, the COP of the hybrid system is approxi-
mately 94% higher than that of the conventional mechanical
dehumidification system.
7.2. Effect of process air cooling temperature
Fig. 17 shows the effect of the cooling temperature at points
and on the refrigerant condensation temperature, the
regeneration air temperature, the refrigerant evaporation
temperature, the heat transfer rate, the compressor power, and
the COP with SHF–0.5. When the cooling temperature at points
and increases to more than 18 �C (Region A) on the
condition that the evaporation temperature and the supply air
temperature at point remain constant, the condensation
temperature increases because the regeneration air tempera-
ture also rises by the influence of the cooling temperature at
points and . Thus, the compressor power increases and
COP decreases.
When the temperature at points and decreases, the
trend of each parameter in Fig. 17 shifts at the point of the
cooling temperature 18.0 �C. In region B, below the temperature
of the shift point, the cooling temperature is lower than the
supply air temperature to the room so that the evaporation
temperature is reduced with the decrease in the cooling
temperature. At the same time, the drop in the regeneration
temperature because of the influence of the fall in the cooling
temperature decreases the condensation temperature. Hence,
the COP and the efficiency improvement are almost constant. In
case ofregion C shiftedat the point of the cooling temperature of
approximately 17 �C, the cooling temperature at point rea-
ches the dew point temperature, and then, the moisture of the
process air is removed in evaporator 1. The regeneration
temperature at points and decreases because of the
reduction in the latent heat in the regeneration process of the
desiccant wheel. Therefore, the condensation temperature
further decreases, and the COP increases.
The trend of each parameter also changes at the point of
the cooling temperature of approximately 15.2 �C. The
regeneration air temperature is lower than the constant
30
40
50
60
Tem
pera
ture
To C
Regeneration air , Exhaust air Condensation
0
5
10
15
20
Eva
pora
tion
tem
pera
ture
To C
Hybrid Mechanical
dehumidification
14 16 18 20 22 24 26 280
0.5
1
1.5
2
Process air cooling temperature T ,oC
Condenser Regeneration air
Region A
Region CRegion B
Region D
Hea
t tra
nsfe
r ra
teQ
kW
0
0.1
0.2
0.3
0.4
0.5
Com
pres
sor
pow
erW
com
kW
2
3
4
5
6
7
8
CO
P
Hybrid Mechanical
dehumidification
14 16 18 20 22 24 26 2820
40
60
80
100
Process air cooling temperature T ,oC
Eff
icie
ncy
impr
ovem
ent
%
Region ARegion B
Region CRegion D
Fig. 17 – Effect of process air cooling temperature.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9508
exhaust air temperature below the cooling temperature of
approximately 15.2 �C. When the regeneration temperature
at points and decreases, the condensation temperature
cannot be reduced and remains constant because of the
constant exhaust air temperature. The COP decreases
because of the reduction in the evaporation temperature
with the decrease in the cooling temperature. When the
cooling temperature is approximately 15.2 �C, the COP of
the hybrid air-conditioning system becomes the highest. At
this point, the COP of the hybrid system is approximately
94% higher than that of the conventional compression-type
refrigerator whose COP is constant. Therefore, the COP of
the hybrid system improves considerably when the evapo-
rator removes a certain amount of the latent heat load.
This implies that the reduction in the condensation
temperature has more impact on the COP than the reduc-
tion in the evaporation temperature.
8. Conclusions
This paper evaluates the characteristics of the four-partition
desiccant wheel by experiment and simulation, and the
performance of the hybrid air-conditioning system that
combines the four-partition desiccant wheel with the
compression-type refrigerator by the simulation. The results
are summarized as follows:
1) Experimental results of the four-partition desiccant wheel
were in good agreement with the simulation results even
though the experimental conditions changed greatly.
Therefore, the validity of the simulation was confirmed.
2) The performance of the four-partition desiccant wheel was
clarified indetailby investigatingtheeffectof theregeneration
temperature, rotational speed, cooling temperature, process
air volume flow rate, and ambient air inlet humidity ratio.
3) The dehumidification technique using the hybrid system
with the four-partition desiccant wheel can be driven more
efficiently than the mechanical dehumidification using the
compression-type refrigerator. When the evaporator
burdens a certain amount of the latent heat, the COP of the
hybrid system improves considerably. For example, the COP
of the hybrid system is approximately 94% higher than that
of the conventional mechanical dehumidification system.
9. Future plan
The pressure drop of the hybrid system with four-partition
desiccant wheel is considered larger than the conventional
system due to multiple air flow paths. Therefore, it is necessary
to consider the pressure loss for the efficiency of the hybrid
system. Now, we are investigating the influence of pressure
drop. We will report a detailed effect of pressure drop on four-
partition desiccant system as well as the conventional system.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 3 ( 2 0 1 0 ) 4 9 6 – 5 0 9 509
r e f e r e n c e s
ASHRAE, 2001. ASHRAE Handbook – Fundamentals. AmericanSociety of Heating, Refrigerating and Air- ConditioningEngineers, Inc., Atlanta, GA, USA.
Barlow, R.S., 1982. Analysis of Adsorption Process and of DesiccantCooling System; a Pseudo-Steady-State Model for Coupled Heatand Mass Transfer. Solar Energy Research Institute. TR 631–1330.
Dhar, P.L., Singh, S.K., 2001. Studies on solid desiccant basedhybrid air-conditioning systems. Applied ThermalEngineering 21 (No 2), 119–134.
Ge, T.S., Dai, Y.J., Wang, R.Z., Li, Y., 2008. Experimentalinvestigation on a one-rotor two-stage rotary desiccantcooling system. Energy 33 (No 12), 1807–1815.
Harriman III, L.G., 1994. The basics of commercial desiccantsystems. Heating/Piping/Air Conditioning, 77–85.
Inagaki, K., Nakagawa, Y., Saito, K., Kawai, S., 2004. Nextgeneration gas driven air conditioning system under thecondition of the cooling mode and higher ventilation. In: The10th International Refrigeration and Air ConditioningConference at Purdue, Purdue University, R152, 1–8.
Jia, C.X., Dai, Y.J., Wu, J.Y., Wang, R.Z., 2006. Analysis on a hybriddesiccant air-conditioning system. Applied ThermalEngineering 26, 2393–2400.
Meckler, M., 1994. Desiccant-assisted air conditioner improvesIAQ and comfort. Heating/Piping/Air Conditioning,75–84.
Shah, R.K., 1975. Laminar flow friction and forced convection heattransfer in ducts of arbitrary geometry. International Journalof Heat and Mass Transfer 18, 849–862.
Shibao, Y., Yamaguchi, S., Saito, K., Kawai, S., 2006. Study onmultistage desiccant air-conditioning system driven bylower heat source temperature. Proceedings of the 2006JSRAE Annual Conference, 257–260 (in Japanese).
Shibao, Y., Yamaguchi, S., Saito, K., Kawai, S. 2007. Performanceanalysis of multi-partition desiccant wheel. In: The 22nd ICR,China, ICR07-E1-1011.
Yadav, Y.K., 1995. Vapour-compression and liquid-desiccanthybrid solar space-conditioning system for energyconservation. Renew Energy 7, 719–723.
Yamaguchi, S., Saito, K., Kawai, S., Oka, M., Murakami, T., Sasaki,H., 2007. Static analysis of desiccant wheel. In: Proceedings ofthe 22nd ICR, ICR07-E1-1008.