Optional Features
kVA kW kVA kW
Automatic load transfer panel Automatic syncronization and power sharing systems Soundproof canopy Container type enclosers Road trailer Job-site trailer
Remote type radiator
Protection circuit breaker Air start
Base fuel tank External type fuel tank Automatic fuel transfer system Residential silencer
CE certification
Charging alternator Battery charge redressor
Heavy duty type, 6 cylinder, water cooled engine 50°C tropical type radiator
ISO 9001:2000
This generator is available with
AMF, Automatic mains failure unit
Fan, fan drive, charging alternator drive and all rotating parts
Heavy duty, brushless type alternator
mechanical damages Fabricated and welded steel base frame
Flexible exhaust compensator
covered Radiator matrix covered by metal mesh against the
Block water heater unit Control panel with digital-automatic main control module
Starter motor
Base frame with anti-vibration units Industrial type silencers
Lead acid battery
Perkins 2506A-E15TAG1 diesel engine
Newage/Stamford HCI544C alternator Standard Generator Features
Prime
Anti-vibration mountings Engine and alternator manufacturer test reports Factory load, performance and function tests
ISO 9001:2000
464 370508 407
Standby
Gross Net Gross Net
%110 Load%100 Load
%75 Load %50 Load
%110 Load%100 Load
%75 Load %50 Load
Prime kW
ECM mounted on engine with wiring looms and sensors
435
Wet sump with filler and dipstick
395
Oil cooler integral with filter header
Type
459
Standby kW
419
Governor type Electronic, governing to ISO 8528-5
Pressurized
Lub oil pressure (min), kPa 20062
Fuel Consumption
liters per hour
grams per kWh
class G3
210 g/kWh
Optional Equipments
Closed circuit crankcase ventilation system
8
Additional speed sensor
Cooling System
219 g/kWh
Air filter rain hood
Gear-driven circulating pump
Twin starters/facility for second starter
459Fan Power, kWm 16
24,47
Compression Ratio
Cylinder arrangement Vertical in-lineDisplacement, Liters
16:1
15.2Bore X Stroke, mm 137 X 171
Direct injection
576 (at 50°C)
Mounted belt-driven pusher fan
50Ambient temperature, °C
Radiator supplied loose incorporating air-to-air charge cooler
Engine+Radiator coolant cap., Liters
System designed for ambients up to 50ºC
58
Tropical, heavy duty type
6
Delivery/hour at 1500rev/min, Liters
Jacket coolant flow, Liters / sec 5.2
Aspiration Turbocharged, air-to-air charge cooledRotation Anti-clockwise viewed on flywheelGross engine power, kWb
Cooling min airflow, m³ / min
Combustion System
Number of cylinders
Type
BMEP gross, barCombustion air flow, m³ / min
Mean piston speed, m / s
UK MOD, BS5750, ISO9001, BS5514/1-1982, ISO 3046/1, ISO 8528/1Standards
Temperature and pressure sensors for gauges
Support comes from a worldwide network of 4,000 distributors and dealers.
Exceptional power to weight ratio and compact size gives optimum powerFuel System
MEUIType of injection system MEUI
Designed to provide excellent service access for ease of maintenance.density for ease of installation and more cost effective transportation.
413
Compact, clean and efficient power
Fuel injecter
Lubricating System
203 g/kWh202 g/kWh
53.5 L
97 L 75 L
Full-flow replaceable ‘Ecoplus’ filter
4 cycle, water-cooled, diesel engine24 Volt
Type
24 Volt with integral regulator
Starter motor power 7.5 kWModel
Low oil usage and low wear rates. High compression ratio ensures clean rapid starting in all conditions.
Capacity, Liters
Economic power Mechanically operated unit fuel injectors with advanced electronic control,
Model
which leads to exceptional low fuel consumption.
Standard FeaturesPerkins 2506A-E15TAG1 Engine
combined with carefully matched turbocharging,give excellent fuel atomisation
Reliable power Developed and tested using the latest engineering techniques and finite element analysis for high reliability.
2506A-E15TAG1
2506A-E15TAG1Manufacturer PERKINS
Technical Specifications
Fuel cooler
107 L
Starter motor (DC)
3 level engine protection system
Alternator
Electrical System
authority electronic control Mechanically actuated electronically controlled unit fuel injectors with full
Replaceable ‘Ecoplus’ fuel filter elements with primary filter/water separator
514 °C30.5
Exhaust gas temp.(after turbo),Exhaust gas flow (after turbo), 81 m³ / min
تولید کنندهمدلتیپ
تعداد سیلندرهاآرایش سیلندرها
جا به جایىقطر سیلندر x کورس پیستون
نسبت تراکمسیستم احتراق
چرخشسیستم تنفس
قدرت ناخالص موتورقدرت فن
جریان هواى احتراقدماى گاز خروجى از اگزوز
جریان هواى خروجى از اگزوز میانگین سرعت پیستون
kVA kW kVA kW
Technical Specifications
Quaility Assurance
Other standards and certifications can be considered on request
MX321 (PMG) with 3 Phase Sensing and improved Regulation 0.5% MX341 (PMG) 1% Regulation with 2 Phase Sensing
supply to the excitation control systemBS5000,VDE0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359 Anti Condensation Heaters Air Filters
Optional Equipment
Coupling Flexible
Less than 50Insultion class HConstruction Single bearing, direct coupled
Newage Stamford industrial generators meet the requirements of BS EN Optional Permanent Magnet Generator (PMG) provides an isolated power
designed specifically to provide the high build required for static windings andAll wound components are impregnated with materials and processes
60034 and the relevent section of other international standards such as
Generators are manufactured using production procedures having a quaility assurance level to BS EN ISO 9001.
the high mechanical strength required for rotating components.
Standards
Frequency, Hz
Stator winding
Voltage Regulation, %
Overspeed, RpmShort circuit current
The insulation system is class 'H'Insulation / Impregnation
50
Voltage, V 380/415
416 500 400
Grade 2.5 for minimum vibration in operation. Two bearing generators arebalanced with a half key.
BS EN 61000-6-2 & BS EN 61000-6-4VDE0875G, VDE 0875N
Waveform distortion No Load <1.5% Non distorting balanced
Shaft&Keys
panels for easy access.
2/3 Pitch factorRegulation
generator. A sheet steel terminal box contains the AVR and provides ample the terminals, Which are mounted on a cover at the non-drive end of the
Voltage Regulator SX440
linear load<5.0%Dynamic balanced
± 1R.F.I Suppression
Excitation
Speed, Rpm 1500
Self excited
must be used.
Current Transformer (CT) to permit parallel operation with other ac generators.
All generator rotors are dynamically balanced to better than BS6861:Part 1
AVR, Automatic Voltage Regulator
< 300%TIF
2250Rotor
If 3-phase sensing is required with the self-excited system, the SX421 AVR
space for the customers wiring and gland arrangements.It has removable
The exciter rotor output is fed to the main rotor through a three-phase full-wavebridge rectifier. The rectifier is protected by a surge suppressor against surgescaused, for example, by short circuit or out-of-phase paralleling.
Standard generators are 3-phase reconnectable with 12 ends brought out to Terminals&Terminal Box
Cooling air volume,m³ / sec 1.035
HCI544C 520
PrimeModel
Standby
residual voltage.
The SX440 will support a range of electronic accessories, including a 'droop'
Newage/Stamford HCI544C AlternatorStandard Features
excessive neutral currents sometimes seen with higher winding pitches,
With this self-excited system the main stator provides power via the AutomaticVoltage Regulator (AVR) to the exciter stator. The high efficiency semi-conductors of the AVR ensure positive build-up from initial low levels of
SX440 AVR
oscillations during paralelling.This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion.
when in parallel with the mains.A fully connected damper winding reduces
Winding&Electrical PerformanceAll generator stators are wound to 2/3 pitch.This eliminates triplen (3rd, 9th, 15th...) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads.The 2/3 pitch design avoids
3
SX421 AVR with 3 Phase Sensing and improved Regulation 0.5%
%93.6Power factor 0.8Phase
Temperature Indication RTD’s
Efficiency, %
Double layer concentricConnection WYEProtection class IP23
Stator windings
4-Poles, Rotating Field, BrushlessStandby power at rated voltage, kVA 520
Winding Protection Thermistors
Manufacturer NEWAGE / STAMFORDModel HCI544CType
Quadrature Droop kit for Parallel Operation
تولید کنندهمدلتیپ
توان standby در ولتاژ نامىراندمان
ضریب قدرتفاز
فرکانسسرعت
ولتاژسیستم تحریک
تنظیم ولتاژرگوالتور ولتاژ
درصد تنظیم ولتاژ
روتورحداکثر سرعت مجاز
جریان اتصال کوتاه
کالس عایقنحوه کوپلینگ
کوپلینگ
اتصالکالس حفاظت
دبى هواى خنک کننده
Optional Input Functions
Selected timers and alarms can be altered by the user from the front panel.Reverse power
Specifications Environmental Testing Standards
The module also provides indication of operational status and fault conditionsautomaticly shutting down the genset and indicating failures by means of an
Alterations to the system are made using the 810 interface and a PC. This
LCD display, and appropriate flashing LED on the front panel.Generator phase rotation error
8Hz to 500Hz 2gn constant acceleration.
Electromagnetic Compatibility
Mains out of limits
Generator short-circuit protection
5Hz to @ +/-7.5mm constant displacement.
VibrationBS EN 60068-2-6 Ten sweeps (up and back down) at 1 octave/minute ineach of the three major axes.
Mains Volts Volts L1-N, L2-N, L3-NMains Volts
Cosφ L1, L2, L3,total
Humidity
LCD PAGE
Communication with MODEM
module from a remote location (P810 Software Kit necessary) Easy pushbutton controls
kVA,kW ve Cosφ measurements System parameters can be adjusted manually from the front panel
LED mimic diagram
AUTO, TEST, MANUAL
SMS messaging capability with suitable GSM Modem PC software is MS Windows based and allows the operator to control the
BS EN 2011 part 2.1 93% RH @ 40° for 48 hours
STOP / START
equipments, including electrical business equipment
BS EN 6068-2-27 Three half sine shocks in each of the three
High engine temperature
Under/over generator voltage
Engine Temperature
Over-currentUnder/over generator frequency
Alarm Channels
the Industrial EnvironmentEN 61000-6-2:1999 EMC, Immunity Standards for the Industrial Environment
240mm x 172mm dimensions
Loss of speed sensing signal
70mm x 40mm dimensions, 4 segment grafical LCD monitor Developed 16-bit Microprocessor design
Volts L1-L2, L2-L3, L3-L1
Easy comprehended display (Hid-Til-Lit SMD LED technology)
interface also provides real time diagnostic facilities
The model 5220 is an Automatic Mains Failure Control module. The modul is used to monitor a mains supply and automaticlly start a standby generator set.
Description
Generator power factor
Engine Hours RunGenerator total power
Plant Battery Volts
Generator total power
% °C
Emergency stop button
Voltmeter commutator Voltmeter
Deeapse 5220 digital automatic control module
Deepsea 5220 Control Module
Ampermeter commutator
Generator Frequency
Temperature
kW L1, L2, L3,total
Amps L1, L2, L3
Control Panel
Generator Volts Input Functions display on LCD
Under/over speedCharge failEmergency stopLow oil pressure
BS EN 50081-2:1992 and EN 61000-6-4:2000 EMC, Emission Standards for
Shock
Cold : BS EN 60068-2-1 to -30°CHot : BS EN 60068-2-2 to 70°C
Electrical Safety
Hour
Hz
Generator Volts Generator Amps
RPMHz
Engine Speed
Pushbutton Controls
BS EN 60950 Low Voltage Dirctive/Safety of information technology
Engine Oil pressure Hourmeter
Ampermeter
Fuel level
major axes 15gn amplitude.11mS duration.
Fail to start
kPa
Low/high DC battery voltage
Volts L1-N, L2-N, L3-N
Volts
Volts L1-L2, L2-L3, L3-L1
kVA L1, L2, L3,total
Mains Frequency
Standard Equipments
IO
Values
2500 Series, 6 cylinder
Acc. To ISO 3046/1, BS 5514, DIN6271
overload is permitted.
Power level
pf : Power factorE : Alternator efficiency
kWm: Mechanical PowerkWe : Electrical Power
kVA : Power
Genset engine
Air-to-air charge cooled
Turbocharged
Electronic, 15 liters
Continuous power rating is available for continuous full load operation.No
in true emergency power failure conditions.
Prime power rating is available for unlimited hours per year with a variableload of which the average engine load factor is 80% of the published powerrating, incorporation of a 10% overload for 1 hour in every 12 hours of
500 operating hours per year.Standby ratings should never be applied except sized for an avarage load factor of 80% based on published standby rating foroverload capacity is available at this rating.A standby rated engine should be
Electric Formulas
Standby power rating is for the supply of emergency power at variableload for the duration of the non-avalaibality of the mains power supply.No
Shaft Height in cm
Industrial
Power RatingsInformation
Core Length
Number of poles
Perkins 2500 Series Diesel Engine
operation which permitted
Formula
kWe kWm X E
Newage/Stamford Alternator
Generator type
Rpm: Revolutions per minute
U : Voltage (V)I : Current (A)
(kWe x 1000) / (U x 1.73 x pf) (kVA x 1000) / (U x 1.73)
Rpm
( Rpm x N°Pole) / (2 x 60)
kVA
kWe
I (Amp)
Frequency
(2 x 60 x Frequency) / N°Pole
(U x I x 1.73 x pf) / 1000 kVA x pf
(U x I x 1.73) / 1000 kWe / pf
2506A-E15 T A G 1 HC 54I 4 C