permit plancheck set #2 · sctn 907.2.2 : manual fire alarm system shall be installed in group b...
TRANSCRIPT
AIRCO BERKELEY TRANSFER STATION OFFICE
CITY OF BERKELEY, CA1947 CENTER STREET, 4TH FLOOR
BERKELEY, CA 94704
PERMIT PLANCHECK SET #206-05-2019
1201 SECOND STREET, BERKELEY, CA 94710
# 201320.19
PROJECT DESCRIPTION
SYMBOLS LEGEND
ABBREVIATIONS CODE ANALYSIS
1. THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER AND SHALL AT ONCE REPORT TO THE ARCHITECT ERRORS, INCONSISTENCIES OR OMISSIONS DISCOVERED. IF THE CONTRACTOR PERFORMS ANY CONSTRUCTION ACTIVITY KNOWING IT INVOLVES A RECOGNIZED ERROR, INCONSISTENCY OR OMISSION IN THE CONTRACT DOCUMENTS WITHOUT SUCH NOTICE TO THE ARCHITECT, THE CONTRACTOR SHALL ASSUME APPROPRIATE RESPONSIBILITY FOR SUCH PERFORMANCE AND SHALL BEAR AN APPROPRIATE AMOUNT OF THE ATTRIBUTABLE COSTS FOR CORRECTION.
2. WHERE NEW CONSTRUCTION ABUTS EXISTING CONSTRUCTION TO REMAIN, ALL CONDITIONS AFFECTING WORK PROGRESS AND CONFORMANCE TO PLANS AND SPECIFICATIONS SHALL BE VERIFIED BY CONTRACTOR PRIOR TO START OF WORK.
3. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED MEASUREMENTS. WHERE DISCREPANCIES IN DIMENSIONS OCCUR THEY SHALL BE REPORTED TO THE ARCHITECT FOR RESOLUTION.
4. ALL WORK AND MATERIALS SHALL BE IN ACCORD WITH THE LATEST RULES AND REGULATIONS OF ALL APPLICABLE STATE AND/OR LOCAL CODES, LAWS, ORDINANCES, STATUTES AND REGULATIONS. NOTHING IN THE DRAWINGS OR SPECIFICATIONS SHALL BE CONSTRUED AS REQUIRING OR PERMITTING WORK CONTRARY TO THESE RULES, REGULATIONS, AND CODES.
5. THE DRAWINGS INDICATE LOCATIONS, DIMENSIONS, AND TYPICAL DETAILS OF CONSTRUCTION. THE DRAWINGS DO NOT ILLUSTRATE EVERY CONDITION; WORK NOT EXPRESSLY DETAILED SHALL BE OF CONSTRUCTION SIMILAR TO PARTS THAT ARE DETAILED. WHERE DISCREPANCIES OCCUR, THEY SHALL BE REPORTED TO THE ARCHITECT FOR RESOLUTION.
6. SITE BOUNDARY LINES, BOUNDARY DIMENSIONS, BOUNDARY DECLINATIONS, AND EXISTING GRADES ARE BASED UPON THE SURVEY DRAWING. THE CONTRACTOR SHALL BE DEEMED TO HAVE INSPECTED THE SITE AND SATISFIED HIMSELF AS TO ACTUAL GRADES, LEVELS, DIMENSIONS, AND DECLINATIONS AND THE TRUE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED.
7. MASONRY DIMENSIONS ARE GIVEN TO THE NOMINAL FACE OF MASONRY. DIMENSIONS ARE TO BE FACE OF FINISH UNLESS OTHERWISE NOTED. DO NOT SCALE THE DRAWINGS. LAY OUT WORK FOLLOWING WRITTEN DIMENSIONS. IF WRITTEN DIMENSIONS ARE LACKING, NOTIFY THE ARCHITECT AT ONCE. IF NO LOCATING DIMENSIONS ARE SHOWN, DOOR OPENINGS ARE LOCATED BY THE DOOR DETAILS.
8. DIMENSIONS AND ELEVATIONS ON THESE DRAWINGS REFER TO BUILDING DATUM, UNLESS OTHERWISE NOTED.
9. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS BEFORE BIDDING.
10. ALL WORKS ARE NEW UNLESS NOTED AS EXISTING, (E).
HARDWOODHDWD.
ENAMELEDENAM.
CABINETCAB.
CEM. PLAS.
CLKG.
C.O.CLO.C.J.CH.
CER.
C.J.CLG.
C.I.
CEM.C.B.
CAULKING
CLEAN_OUTCLOSETCONSTRUCTION JOINTCOAT HOOK
CONTROL JOINTCEILING
CAST IRONCERAMICCEMENT PLASTERCEMENTCATCH BASIN
EXPO.
EXT.EXP.
E.W.E.W.C.
EQUIP.EQ.E.P.ENCL.
(E)EXPOSED
EXTERIOREXPANSION
ELECTRIC WATER COOLER
ELECTRICAL PANEL
EQUIPMENTEACH WAY
EXISTING
ENCLOSURE
EQUAL
INTERMEDIATEINTERIORINSULATIONINSIDE DIAMETER (DIMENSION)
HORIZONTALHOLLOW METALHARDWARE
INTERM.INT.INSUL.I.D.
HR.HT.
HORIZ.H.M.HDWE.
HOURHEIGHT
ADJUSTABLE, ADJACENTADJ.
B.O.
BOT.B.U.R.
B.O.C.B.R.B.S.
BLW.BM.
BLKG.BLK.BLDG.BITUM.BD.
BOTTOM OF
BOTTOM OF CURB
BUILT-UP ROOFINGBOTTOM
BOTTOM OR RISERBOTTOM OF SILL
BELOWBLOCKING
BUILDINGBITUMINOUSBOARD
BEAM
BLOCK
APPROX.
ASPH.
BTW.BSMT.BC
A.T.
ALT.
ARCH.
A.P.
ALUM.AGGR.A.F.F.
ASPHALT
BETWEENBASEMENTBOTTOM OF CURB
ASHTRAY
ARCHITECTAPPROXIMATEACCESS PANELALTERNATEALUMINUMAGGREGATEABOVE FINISH FLOOR
ACOUS.A.D.
A/C
A.B.
A.C.ABV.
(E)(N)
#
T∅
ANCHOR BOLT
AREA DRAINACOUSTICALAIR CONDITIONINGASPHALTIC CONCRETEABOVE
EXISTINGPOUND, NUMBERPERPENDICULARDIAMETER, ROUND
NEW
CL@
&PLd
CENTERLINE
PROPERTY LINEPENNY (NAIL)
ATANGLEAND
FLOOR SINKF.S.
DECK COATING TYPE 1 (ETC.)D.C. TYPE 1 (ETC.)
DOUGLAS FIR, DRINKING FOUNTAIN
DAVIT SOCKETD.S.
E.F.E.F.S.E.I.F.S.
EMER.ELEV.
ELECT.E.J.
EL.
E.B.
D.S.P.
EA.E.
EXHAUST FANEXTER. FINISH SYSTEMEXTER. INSUL. & FIN. SYST.EXPANSION JOINTELECTRICAL
EMERGENCYELEVATORELEVATION
EXPANSION BOLTEACHEAST
DRY STANDPIPE
DIM.
D.W.P.DWR.
DWG.DR.D.O.DN.DISP.
D.D
DIAG.DIAM.D.F.DET.DEPT.DEMO.
DIMENSION
DESIGN WORKING POINT
DOOR
DRAWER
DRAWING
DOOR OPENING
DISPENSERDOWN
DETAIL
DIAGONALDIAMETER
DECK DRAIN
DEPARTMENTDEMOLISH
GLASS FIBER REINF. CONC.G.F.R.C.
HOLLOW COREHANDICAPPEDHOSE BIBB
HAND RAIL
GLASS REINFORCED GYPSUM
GROUND
H.B.
HDR.H.C.HC.
H.H.R.
HEADER
HIGH
G.R.G.GYP.
GR.GND.GL.
GYPSUM
GRADE
GLASS
GROUND FAULT INTERRUPTERGALVANIZED IRONGYPSUM WALL BOARDGRAB BARGALVANIZED
FURRINGFOUNDATIONFOOTINGFOOT, FEET
G.B.
G.F.I.G.I.GWB.
GALV.GA. GAUGE
FURR.FUT.
FND.FTG.FT.
FUTURE
CUSP.
DBL.D.
C.T.
CTR.CPT.CNTR.CTSK.
CORR.CONT.CONST.
DOUBLEDEEP
CUSPIDORCENTERCARPETCOUNTERCOUNTERSINKCERAMIC TILECORRIDORCONTINUOUSCONSTRUCTION
CONN.C.M.U.CONC.COMP.COL.CLR.
CONCRETE MASONRY UNITCONNECTION
CONCRETECOMPOSITIONCOLUMNCLEAR
FACE OF
FIRE SPRINKLER RISERFRAMINGFIREPROOFFACE OF STUDSFACE OF FINISHFACE OF CONCRETE
FLUORESCENTFLASHING
FIRE HOSE CABINETFINISH FLOORFIRE HYDRANT
F.S.R.FRMG.FPRF.
F.O.
F.O.S.F.O.F.F.O.C.
FLUOR.FLASH.FLR.FIXT.FIN.F.H.C.F.F.F.H.
FLOORFIXTUREFINISH
FOOTBOARD
FIRE EXTINGUISHER CABINETFIRE EXTINGUISHERFOUNDATIONFLOOR DRAIN
FIRE ALARM
F.E.C.F.E.FDN.F.D.F.B.F.A.
OVERFLOW DRAINOD
WROUGHT IRONW.I.
WP. TYPE 1 (ETC.)
S.P.R.
S.N.R.S.N.D.S.M.D.
S.H.V.C.
CONTRACTOR INSTALLED
PLANTER DRAINPARTICLE BOARDPOLE AND SHELF
OWNER FURNISHED OUTSIDE DIAMETER
PLUMB.P.D.
PART'N.
P.B.P & SH.
PLUMBING
PARTITION
OFF.
OPP.OPNG.O.H.
O.F.C.I.O.D.
OFFICE
OPPOSITEOPENINGOVERHEAD
S.S.D.S.S.
SQ.
SPEC.
S.L.D.S.M.
SIM.SHT.SHR.
SEE LANDSCAPE DRAWINGS
SEE STRUCTURAL DRAWINGS
SQUARE FOOT, SQUARE FEET
SINGLE-PLY ROOFING
SANITARY NAPKIN RECEPTACLESANITARY NAPKIN DISPENSERSEE MECH. DRAWINGS
SURFACE MOUNTED HOSE
STAINLESS STEEL
SQUARE
SPECIFICATION
VALVE CABINET
SHEET METAL
SIMILARSHEETSHOWER
W.S.
W.W.F.WT.WSCT.
W/O
WR
WP.
W.F.W.O.
WD.
WATERPROOFING TYPE 1 (ETC.)
WOOD SCREW
WELDED WIRE FABRICWEIGHTWAINSCOT
WIDE FLANGEWHERE OCCURS
WATER RESISTANT
WATERPROOFWITHOUT
WOOD
T. & G.
RADIUSr.
MACHINEMACH.
S.C.D.
R.W.L.RDWD.
RESIL.
REQ'DREINF.
REFER.
MULLIONMUL.
NOT TO SCALE
NOT IN CONTRACT
NOMINALNOM.
O.C.OBSC.O.A.
N.T.S.
ON CENTEROBSCUREOVERALL
(N)
NO.N.I.C.N.
NEW
NUMBER
NORTH
SH.S.E.D.SECT.S.D.
S.
SCH.
S.C.
R.B.
R.O.RM.
METAL SIDINGMETAL TOILET PARTITION
MASONRY OPENINGMISCELLANEOUS
MANUFACTURER
MEDICINE CABINETMACHINE BOLT
MINIMUMMIN.
MTD.
MTL.MTP.MTL.
M.O.MISC.MIR.
MOUNTEDMETAL
MIRROR
MECH.
MH.MFR.MEMB.
M.C.M.B.MAX.
MECHANICAL
MANHOLE
MEMBRANE
MAXIMUM
REV.RET.
REF.
RGTR.
R.D.(R)R.
U.O.N.
SEE ELECTRICAL DRAWINGS
SEAT COVER DISPENSER
RAIN WATER LEADER
SHELF
SECTIONSOAP DISPENSERSCHEDULE
SOLID CORESOUTH
RUBBER BASE
REDWOODROUGH OPENINGROOM
V.I.F.
W
W.C.W/W.
VEST.VERT.V.T.
UR.
REQUIRED
REVISION, REVISEDRETAININGRESILIENT
REINFORCEDREGISTERREFRIGERATORREFERENCEROOF DRAINREMOVERISER
TRANSF.
UNF.
TYP.T.O.W.
T.O.B.T.O.C
T.P.D.T.O.S.
T.O.THR.THK.
PTN, PART.
PLYWD.
P. LAM.
PREFAB.PRCST.
LT.L.LOC.LKR.
LIGHTLONGLOCATIONLOCKER
LAV.LAM.L.B.
KIT.
LAVATORYLAMINATELAG BOLT
KITCHEN
Q.T.
P.T.R.
PTDPT.PR.PTP
JOIST HANGERJT.J.H.JST.JAN.
JOINT
JOISTJANITOR
PLAS.
PL.PTDF
PAPER TOWEL RECPTACLE
PLASTIC TOILET PARTITION
QUARRY TILE
PARTITIONPAINTEDPOINT, POINTPAIR
PLYWOOD
TER.
TEL.TEMP.
T.D.T.O.C.T.C.T.B.SYM.S.V.SATSUSP.
PRESSURE TREATED DOUGLAS FIR
PLASTERPLASTIC LAMINATEPLATE
PRE-FABRICATEDPRECAST
STRUCT.STOR.STL.STD,STA.S. SK.
TONGUE AND GROOVE
UNLESS OTHERWISE NOTED
VERIFY IN FIELD
WATER CLOSET
WIDE
WITHWEST
VESTIBULEVERTICALVINYL TILE
URINAL
TOILET PAPER DISPENSERTRANSFORMER
UNFINISHED
TYPICALTOP OF WALL
TOP OF BENCHTOP OF CONCRETE
TOP OF
TOP OF STRUCTURE
THRESHOLDTHICK
SUSPENDED ACOUSTICAL TILE
TERRAZZOTEMPEREDTELEPHONETIE DOWNTOP OF CONCRETETOP OF CURBTOWEL BARSYMMETRICALSHEET VINYL
SUSPENDEDSTRUCTURALSTORAGE
STANDARDSTATIONSERVICE SINK
STEEL
CW. CURTAIN WALL
GENERAL NOTES
ROOM KEY
SHEET NOTE
DETAIL PLAN KEY
INTERIOR ELEVATION
DRAWING TITLE
GRID LINE REFERENCE
SCALETITLE
DOOR NUMBER
3
GRID W - #
#
123
ROOM ROOM NAME
ROOM #
GRID
DRAWING REVISION
VIEW
4
3
SHEET 2
1
NO.SHEET
DETAIL SECTION KEY
NO.SHEET
WINDOW TYPE
101
PARTITION TYPE
TYPE
FIRE RATING (HRS)
ACOUSTICAL
P1 1 -
SHEET INDEX VICINITY MAP
PROJECT SITE
TENANT IMPROVEMENTS INCLUDE:■ TWO ALL GENDER TOILET ROOMS AND LAVATORIES■ PARTITION AND DOOR AT (E) CONFERENCE ROOM■ CARPET AND PAINT■ AUTO DOOR OPEN AT MAIN ENTRY
-------------------------------------------------------------------------------------------------------------------------------------------------■ NO CHANGES TO EXISTING LANDSCAPE, EXTERIORS, ROOF & BUILDING STRUCTURE(S).■ NO CHANGES TO TOTAL BUILDING AREA AND BUILDING USE.
DEFERRED SUBMITTALDESIGN BUILD FIRE-SPRINKLER SYSTEM SERVING AREA OF WORK
APPROXIMATE BUILDING AREA
OFFICE (AREA OF RENOVATION) : 3,424 SFADJACENT WORKSHOP : 3,179 SF -- (NOT IN SCOPE)OVERALL GROSS BUILDING AREA : 6,603 SF
OCCUPANCY GROUP
OFFICE (AREA OF RENOVATION) : BADJACENT WORKSHOP : F-1 -- (NOT IN SCOPE)
CBC CHAPTER 5: OCCUPANCY SEPARATIONS
TABLE 508.4 : NOT REQUIRED
CBC CHAPTER 5: GENERAL BUILDING HEIGHTS AND AREAS
EXISTING BUILDING IS FIRE SPRINKLED.
CBC CHAPTER 6: TYPES OF CONSTRUCTION
PERIMETER WALLS : (E) 8"-CONCRETE MASONRY UNITROOF : (E) WOOD FRAMINGINTERIOR WALLS : (E) WOOD FRAMING
TABLE 601 : TYPE V-B CONSTRUCTION
CBC CHAPTER 7: FIRE AND SMOKE PROTECTION FEATURES
(E) CONDITIONS : BLDG HAS (E) 8" CMU BLOCK WALLS BETWEEN OFFICES & WORKSHOP.
CBC CHAPTER 9: FIRE PROTECTION SYSTEMS
A FIRE ALARM SYSTEM IS NOT REQUIRED.
FIRE AREA:
SCTN 907.2.2 : MANUAL FIRE ALARM SYSTEM SHALL BE INSTALLED IN GROUP B OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
1. THE COMBINED GROUP B OCCUPANT LOAD OF ALL FLOORS IS 500 OR MORE.
2. THE GROUP B OCCUPANT LOAD IS MORE THAN 100 PERSONS ABOVE OR BELOW THE LOWEST LEVEL OF EXIT DISCHARGE.
3. THE FIRE AREA CONTAINS AN AMBULATORY CARE FACILITY.
4. GROUP B OCCUPANCIES CONTAINING EDUCATIONAL FACILITIES.
CBC CHAPTER 10: MEANS OF EGRESS
TABLE 1004.1.2 : ALLOWABLE AREAS PER OCCUPANT (SQUARE FEET) BUSINESS AREAS : 100 GROSS
TABLE 1020.2 : MINIMUM CORRIDOR WIDTH : 36”
TABLE 1006.2.1 : EXIT ACCESS TRAVEL DISTANCE : 100 FT (WITH SPRINKLER SYSTEM)
SCTION 1020.4 : DEAD END CORRIDOR: : 50’ MINIMUM (W/ SPRINKLER SYS)
PLUMBING FIXTURES REQUIREMENTS:
OCC LOAD = 3424 / 200 = 17 (9 MALES & 9 FEMALES)REQUIRED URINALS : 0
LAV : 1 + 1TOILETS : 2
DRINKING FOUNTAIN
2016 CALIFORNIA PLUMBING CODE, SECTION 415.2 DRINKING FOUNTAIN ALTERNATIVES : WHERE FOOD IS CONSUMED INDOORS, WATER STATIONS SHALL BE PERMITTED TO BE SUBSTITUTED FOR DRINKING FOUNTAINS. BOTTLE FILLING STATIONS SHALL BE PERMITTED TO BE SUBSTITUTED FOR DRINKING FOUNTAINS UP TO 50 PERCENT OF THE REQUIREMENTS FOR DRINKING FOUNTAINS. DRINKING FOUNTAINS SHALL NOT BE REQUIRED FOR AN OCCUPANT LOAD OF 30 OR LESS.
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
INDEX SHEET
A001
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
A000 COVER SHEETA001 INDEX SHEETA002 SITE MAP & ELEVATIONA003 EXITING PLAN / ACCESSIBLE PATH DIAGRAMA004 CALGREEN NON-RESIDENTIAL CHECKLISTA005 WASTE DIVERSIONA006 POLLUTION PREVENTION
MECHANICALM0.1 LEGEND, SYMBOLS AND GENERAL NOTESM0.2 MECHANICAL T-24M0.3 MECHANICAL T-24M1.1 MECHANICAL DEMOLITION PLANM2.1 MECHANICAL NEW PLAN
ELECTRICALE0.1 GENERAL NOTES, LEGENDS AND SHEET INDEXE0.2 LIGHTING T24 CALCULATIONSE1.0 POWER & LIGHTING PLAN
PLUMBINGP0.1 LEGENDS, SYMBOLS & GENERAL NOTESP1.1 PLUMBING DEMOLITION PLANP2.1 PLUMBING NEW PLAN
ARCHITECTUREA201 DEMOLITION & EXISTING PLANA202 FLOOR PLANA400 ENLARGED FLOOR PLAN & INTERIOR ELEVATIONSA600 REFLECTED CEILING PLAN - LEVEL 1A700 SCHEDULESA900 DETAILS
1
1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK
(E) BUILDING
(E) BUILDINGS
LEGEND
(E) CHAINLINK FENCE
SECOND STREET
(E) SIDE WALK
(E) GATE; 36" MIN.
(E) BUILDING ENTRY DOOR, PROVIDE AUTO DOOR OPENER & ACTUATORS
(E) ASPHALT
(E) PLANTER
1
AREA OF WORK
(E) OFFICE BUILDING
(E) CONCRETE LANDING
A0022A002 3
22
2
DC E
PUSH TO OPEN
48" M
AX.
46"36
"
6"
10"
AUTO DOOR ACTUATOR
(E) DOORS
(E) 1
0"
D CE
PUSH TO OPEN
48" M
AX.
46"
10"
36"
6"
AUTO DOOR ACTUATOR
(E) 1
0"
(E) DOORS
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
SITE MAP &ELEVATION
A002
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
N.T.S.1 SITE PLAN
1. THE EXISTING GATE AND PATH OF TRAVEL FROM THE SIDEWALK TO THE (E) BUILDING DOOR IS NOT COMPLIANT WITH ACESSIBILITY REQUIREMENTS AND EXCEEDS THE 1/4" PER FEET MAXIMUM CROSS SLOPE.
2. COST OF AUTOMATIC DOOR OPENER FOR MAIN ENTRY DOOR EXCEEDS 20% OF THE ADJUSTED CONSTRUCTION COST
GENERAL ACCESSIBLE PATH NOTES:1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK2 06-05-2019 PERMIT PLANCHECK #2
1/4" = 1'-0"2 PARTIAL EXTERIOR ELEVATION @ (E) ENTRY2
2
1/4" = 1'-0"3 PARTIAL INTERIOR ELEVATION @ (E) ENTRY
2
(E) EXIT► (E) DOOR WIDTH = 72"
LEGEND
EXIT LOCATIONS
(E) OFFICEAREA = 2,946 SF
(E) WORKSHOP(NO WORK)3,178 SF
TOILET RMS & LAV RM163 SF
(E) WOODEN SHELF TO REMAIN
251 SF
(E) LUNCHRM
131 SF
(E) MECHRM./JAN.CLOSET
(E) OPENOFFICE
433 SF(E) OFFICE
67 SF
(E) LOCKERRM
112 SF
(E) OFFICE1
114 SF
(E) OFFICE2
111 SF
(E) OFFICE3
172 SF
(E) OFFICE4
196 SF(E) HALL
1,327 SF
SEE SITE PLAN
(E) CLOSET(E) DATA
(E) CLOSET
(E) CLOSET
2
ACCESSIBLE PATH OF TRAVEL
LEGEND
(E) CLOSET(E) CLOSET
(E) WORKSHOP, NIC.
(E) CLOSET
ALL-GENDER ACC. TOILET ROOM ALL-GENDER TOILET ROOM
ADD AUTO DOOR OPENER TO (E) DOORS
SEE SITE PLAN
(E) WOODEN SHELF TO REMAIN
(E) LUNCHRM
(E) MECHRM./JAN.CLOSET
(E) OPENOFFICE
(E) LOCKERRM
(E) OFFICE1
(E) OFFICE2
(E) OFFICE3
(E) OFFICE4
(E) HALL
(E) DATA
(E) OFFICE
2
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
EXITING PLAN /ACCESSIBLE PATH
DIAGRAM
A003
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
3/32" = 1'-0"1 EXITING PLAN
3/32" = 1'-0"2 ACCESSIBLE PATH DIAGRAM
1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK2 06-05-2019 PERMIT PLANCHECK #2
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
CALGREENNON-RESIDENTIAL
CHECKLIST
A004
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
REVISION
NO. DATE DESCRIPTION
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
WASTE DIVERSION
A005
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
REVISION
NO. DATE DESCRIPTION
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
POLLUTIONPREVENTION
A006
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
REVISION
NO. DATE DESCRIPTION
UP
1 2 3 4 5 6
20' - 7" VIF. 19' - 5" VIF. 18' - 7" VIF. 16' - 5" VIF. 19' - 3" VIF.
41' - 1" VIF.
75' -
7" V
IF.
64' -
7" V
IF.
95' - 3" VIF.
A
B
D
F
H
11' -
0" V
IF.
G
C
E
16' -
10"
VIF
.11
' - 0
" VIF
.18
' - 8
" VIF
.16
' - 1
0" V
IF.
11' -
0" V
IF.
(E) EQUIPMENTTO REMAIN
(E) EP TO REMAIN
(E) ALARM BOXTO REMAIN
(E) MECH UNITTO REMAIN
(E) AIR SHAFT &WALL VENT TO REMAIN
(E) PIPE RUNNING FROM CEILING TO (ALMOST) GROUND TO REMAIN
13' - 7" VIF.
(E) CABINETS AND SINKTO REMAINA400
(E) FIRE EXT.TO REMAIN
(E) FIRE EXT.TO REMAIN
(E) LUNCH RM02
(E) MECHRM./JAN. CLOSET
03
ALL GENDERTOILET RM
04
(E) LOCKER RM08
(E) OFFICE 109
(E) OFFICE 210
(E) OFFICE 311
(E) OFFICE 412
RR.HALL13
(E) LCKR CLOS15
(E) OPEN OFFICE01
(E) HALL14
(E) CLOSET16
(E) OFFICE07
(E) WORKSHOP -NIC17
(E) ROOM18
EXISTING19
(E) ROOM20
(E) ROOM21
2
11
3
4
5
5
5
5
6
(E) LOCKERS TO REMAIN ALL GENDER
7
8
10
11
(E) CABINETTO BE REMOVED & RELOCATED TO NEW LOCATION PER OWNER'S DIRECTIVEAREA N.I.C.
13 12
13
(E) CLOSET
14
3
9 (E) WOODEN SHELF TO REMAIN 1
1
2
KEYNOTES:
2
3
4
1
DEMOLITION NOTESA. REPAIR & PATCH DAMAGED FLOOR, WALL,
CEILING AND ADJACENT ELEMENTS WHERE DEMOLITION/ REMOVAL WORKS HAVE BEEN PERFORMED.
B. NO WORK IN THE HATCHED AREA (N.I.C.).
C. REMOVE ALL SURFACE MTD CONDUITS THAT SUPPLIES UN-USED DEVICES. CONFIRM WALL SPACE W/ OWNER PRIOR TO DEMO WORK.
D. PROTECT ALL (E) FINISHES TO REMAIN.
E. SEE MECHANICAL DWGS FOR ADDITIONAL DEMOLITION.
DEMOLISH (E) PARTITION PORTION TO ENLARGE OPENING FOR DOOR.
REMOVE AND SAVAGE LIGHTING FOR RE-USE.
5REPAIR/ PATCH (E) SLAB FLOOR TO RECEIVE NEW FINISH.
REMOVE (E) TOILET PARTITION & INDICATED PARTIAL WALL, DR & FRM.
REMOVE (E) OVERHEAD CABINET
6 REMOVE (E) LOCKERS
LEGEND
REMOVE (E) DOOR
REMOVE (E) PARTITION/ WALL
REMOVE (E) ITEM
NIC, NO WORK AREA.
7 REMOVE (E) CLG TILES, SAVAGE FOR RE-USE
8 REMOVE (E) PLUMBING FIXTURES, S.P.D.
(E) DOOR TO BE REMAIN
(E) WALL/ PARTITION TO REMAIN
9 (E) WOODEN SHELF TO REMAIN
10 VIF WORKING CONDITION OF (E) ELECTRICAL DEVICE & REMOVE, INCLUDING WIRING TO BELOW CEILING
10 VIF WORKING CONDITION OF (E) ELECTRICAL DEVICE & REMOVE, INCLUDING WIRING TO JUST ABOVE CEILING
11 REMOVE & SAVAGE TV SET & SUPPORT
12 REMOVE (E) FLOOR TILE, BASE & MORTAR. REMOVE SLAB WHERE REQUIRED TO TRENCH FOR PLUMBING LOCATIONS & FLOOR DRAIN & PREP FOR FINISH FLOOR. SEE DET 13/A900 FOR CONC SLAB PATCH
13 REMOVE (E) WALL FINISH FOR PLUMBING & BLOCKING INSTALLATION.
14 REMOVE CONCRETE AS NECCESSARY FOR NEW PLUMBING LINES. S.P.D.
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
DEMOLITION &EXISTING PLAN
A201
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
3/16" = 1'-0"1 DEMOLITION & EXISTING PLAN
1
1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK2 06-05-2019 PERMIT PLANCHECK #2
DN
UP
1 2 3 4 5 6
A
B
D
F
H
G
C
E
VIF+/- 20' - 7"
VIF+/- 19' - 5"
VIF+/- 18' - 7"
VIF+/- 16' - 5"
VIF+/- 19' - 3"
VIF+/- 41' - 1"
+/- 7
5' -
7" V
IF.
VIF+/- 54' - 2"
VIF
64' -
7"
+/- 95' - 3" VIF.
VIF
+/-
16' -
10"
VIF
+/-
11' -
0"
VIF
+/-
18' -
8"
VIF
+/-
16' -
10"
VIF
+/-
11' -
0"
(E) EQUIPMENTTO REMAIN
(E) EP TO REMAIN
(E) ALARM BOXTO REMAIN
(E) MECH UNITTO REMAIN
(E) AIR SHAFT &WALL VENT TO REMAIN
(E) PIPE RUNNING FROM CEILING TO (ALMOST) GROUND TO REMAIN
(E) LUNCH RM02
(E) MECHRM./JAN. CLOSET
03
ALL GENDERTOILET RM
04
(E) LOCKER RM08
(E) OFFICE 109
(E) OFFICE 210
(E) OFFICE 311
(E) OFFICE 412
PRINTER / COPIER
FILES
FILES FILES
(E) CABINETS AND SINKTO REMAIN
RR.HALL13
A4001
(E) LCKR CLOS15
(E) OPEN OFFICE01
(E) HALL14
(E) CLOSET16
(E) OFFICE07
111213 10
15
09
07
01
08
(E) FIRE EXT.TO REMAIN
(E) FIRE EXT.TO REMAIN
04
(E) WORKSHOP -NIC17
(E) ROOM21
(E) ROOM20
(E) ROOM18
29
6
25
21
21
28
14
23
(E) LOCKERS TO REMAIN ALL GENDER
9' -
0"
6' - 0"
A
B
9
9
13
22
2
(E)
13
13(E)
LAV-RM22
(E)
13
25
25
18
(E) CABINETTO BE REMOVED & RELOCATED TO NEW LOCATION PER OWNER'S DIRECTIVE
26
AREA N.I.C.
8
194
10
11
7
15
A
A
29
20
(E) TEL/ DATA23
33 34
30
24
TYP.
(E) CLOSET
1
36
35
ALL GENDERACC. TOILET RM
25
JAN.CLO.
60" DIA.DA.CLR.FLR.
.
30x48 CLR.FLR.60
" DIA.
DA.CLR.FLR
..
A
A
A
(E) WOODEN SHELF TO REMAIN
3131 1
12
31
2
LEGEND(E) PARTITION NEW PARTITION & WALL TYPE TAG (EX: A)
(E) WALL OUTLETS , JACK,SWITCH, THERMOSTAT.(SEE ELEC. DWGS FOR NEWLOCATIONS) EXISTING DOOR & NEW DOOR
ADA 60" FLR. CLEARANCE CIRCLE& 30"x48" FLR. CLEARANCE RECT.
AREA NOT IN CONTRACT
(E)
N.I.C.
S T
A
KEYNOTES:
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
19
20
21
22
23
24
17
PROVIDE EXIT LIGHT & CONNECTING WIRING, SED.
PROVIDE VINYL INTEGRAL WALL BASE & VINYL TRANSITION STRIP
PROVIDE (2X) POWER POLES. SECURED TO CEILING AND FLOOR, S.E.D.
ALL ELECTRICAL OUTLETS, LIGHT SWITCHES, THERMOSTATS ARE EXISTING & SHOWN FOR REFERENCE ONLY, U.O.N.. SEE ELECTRICAL DRAWINGS FOR DETAILS & ADDITIONAL WORKS.
REPAIR, PATCH (E) FLOOR TILES TO INDICATED FLOOR TRANSITION.
INSTALL WALL, PATCH ADJ DAMAGED SURFACES.
RELOCATE LIGHT FIXTURES IN CONFLICT W/(N) WALL INSTALLATION
SANITARY CT COVE BASE @ NEW PARTITIONS IN LAV-ROOM 22
NOT ALL KEYNOTES ARE USED IN THIS DRAWING.
INSTALL WC, GRAB BARS, TOILET PAPER DISPENSERS, TOILET SEAT COVER DISPENSER, TOILET PARTITIONS/ DR/ HARDWARE, BLOCKING, LAV & FAUCETS, 24"W-MIRRORS, SOAP DISPENSER, PAPER TOWEL DISPENSER, TRASH RECEPTACLE WHERE SHOWN IN DRAWINGS.REFER TO SHEET A700 FOR CLEARANCES AND MOUNTING HEIGHTS OF FIXTURES.
REROUTE PIPING, PLUMBING VENTS.INSTALL FLOOR DRAIN, CONNECT TO (E) SYS.
PATCH AND PAINTS DAMAGED WALLS, FLOOR, CEILING TO MATCH SCH.
(E) CT BASE.
PROVIDE PRIVACY FILM TO (E) 52"X44" WINDOWS, ALL PANES. SEE A400.
PROVIDE DOOR & FRAME AT HALLWAY + SIGNAGE + HARDWARE. PUSH & PULL ONLY & NO LATCH
PROVIDE LIGHT SWITCH FOR CONF. RM., SED.
PROVIDE CARPET, RUBBER WALL BASE AND INDICATED TRANSITION STRIP
(E) FRAMES, RE-USE (E) HINGES OR PROVIDE NEW
PROVIDE HM FRAME & WOOD DOOR W/ GLASS,SEE DOOR SCH.
FURNITURE ARE NIC, SHOWN FOR REF. ONLY
PROVIDE ALUM OR SS SCHLUTER CORNER BASE TRIM
PROVIDE WALK OFF MAT, 6 FT. X 9 FT. INSERT CARPET TILE, FLUSH W/ ADJ CARPET TILE & SECURED TO FLOOR W/ ADHESIVE.
INSTALL 48" HT FRP FINISH AS INDICATED IN ELEVATION DWG; ALL WALLS IN STALLS
3'X4' - 3/4" PLYWOOD BOARD BEHIND RACK.COORD. W/ OWNER'S IT VENDOR.
25 PROVIDE CONDUIT FOR OPEN WIRE(S) & INSTALLNEATLY ON ADJ WALL SURFACE & PAINT.
26 ELECTRICAL/ DATA/ ETC. CLUSTER TO BE PROTECTED DURING WORK.
GENERAL NOTES: A. PROTECT ALL (E) BLDG COMPONENTS,
FINISHES & SURFACES TO REMAIN.
B. ALL CUTTING & PATCHING OF (E) FINISHES TO REMAIN REQUIRE PRIOR APPROVAL & COORDINATION BY GC/ OWNER.
C. PATCH ALL (E) SURFACES TO REMAIN AT AREAS OF DEMOLITION OF (E) CEILING, WALLS, PLUMBING, ELECTRICAL AND HVAC.
D. PAINT ALL WALLS, CEILINGS, DOORS, DOOR FRAMES AND EXPOSED EQUIPMENTS, U.O.N.
27 LIGHT FIXTURE, SED.
28 PROVIDE GYP BD FIN. AT OPENING
29 REMOVE/ REINSTALL SLAB, S.P.D. & 13/A900
30SEE DETAIL 7/A700 FOR DOOR/FLOOR CLEARANCE AND MANEUVERING WITHIN RESTROOM STALL.
31 AUTOMATIC DOOR OPENER & PSUH PLATE ACTUATORS AT (E) DOORS
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
FLOOR PLAN
A202
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
3/16" = 1'-0"1 FLOOR PLAN
1
1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK2 06-05-2019 PERMIT PLANCHECK #2
2
3 4
D
F
H
G
C
E
A400
10
9
13
8
A40015A400 14
A400 1211
6
7
(E) OFFICE07
ALL GENDERTOILET RM
04
(E) HALL14
(E) MECHRM./JAN. CLOSET
03
A400 2
5' - 0"
3
30
7
11
12 15
2LAV-RM
22
(E) LCKR CLOS15
(E) CLOSET16
3' - 10" VIF.
10
9' -
11 3
/4"
VIF.
VIF.
6' -
0"
VIF.
17' -
9 1
/2"
VIF.12' - 8"
14
(E) TEL/ DATA23
VIF.4' - 1"
18".
(E) CLOSET24
VIF.
5' -
3"
ALIGN
4
5' -
3 1/
4"4'
- 1"
1
3' -
1"3'
- 9"
30x48 CLR.FLR.
CLR
.4'
- 1"
5".3' - 5" VIF.
3
1' -
6"
9' -
9" V
IF.
4' - 11"
0' - 7 3/4"
VIF.4' - 5"
0' - 5" VIF.
VIF.4' - 8"
ALL GENDERACC. TOILET RM
25
2' -
10"
1
1
2
2 3 4
OPEN
28
12
2 4
OPEN
1
19
46
2 419 125 5
1
12
2 4
OPEN
5
12
4
2 4 19
OPEN
5 1
1
2 3 419
MIN
. TYP
.4'
- 0"
1
FG E
F GE
(E) DOOR FRAMES, TYP.
4
OPENOPEN
D
OPEN
27
KEYNOTES:
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
19
20
21
22
23
24
17
PROVIDE EXIT LIGHT & CONNECTING WIRING, SED.
PROVIDE VINYL INTEGRAL WALL BASE & VINYL TRANSITION STRIP
PROVIDE (2X) POWER POLES. SECURED TO CEILING AND FLOOR, S.E.D.
ALL ELECTRICAL OUTLETS, LIGHT SWITCHES, THERMOSTATS ARE EXISTING & SHOWN FOR REFERENCE ONLY, U.O.N.. SEE ELECTRICAL DRAWINGS FOR DETAILS & ADDITIONAL WORKS.
REPAIR, PATCH (E) FLOOR TILES TO INDICATED FLOOR TRANSITION.
INSTALL WALL, PATCH ADJ DAMAGED SURFACES.
RELOCATE LIGHT FIXTURES IN CONFLICT W/(N) WALL INSTALLATION
SANITARY CT COVE BASE @ NEW PARTITIONS IN LAV-ROOM 22
NOT ALL KEYNOTES ARE USED IN THIS DRAWING.
INSTALL WC, GRAB BARS, TOILET PAPER DISPENSERS, TOILET SEAT COVER DISPENSER, TOILET PARTITIONS/ DR/ HARDWARE, BLOCKING, LAV & FAUCETS, 24"W-MIRRORS, SOAP DISPENSER, PAPER TOWEL DISPENSER, TRASH RECEPTACLE WHERE SHOWN IN DRAWINGS.REFER TO SHEET A700 FOR CLEARANCES AND MOUNTING HEIGHTS OF FIXTURES.
REROUTE PIPING, PLUMBING VENTS.INSTALL FLOOR DRAIN, CONNECT TO (E) SYS.
PATCH AND PAINTS DAMAGED WALLS, FLOOR, CEILING TO MATCH SCH.
(E) CT BASE.
PROVIDE PRIVACY FILM TO (E) 52"X44" WINDOWS, ALL PANES. SEE A400.
PROVIDE DOOR & FRAME AT HALLWAY + SIGNAGE + HARDWARE. PUSH & PULL ONLY & NO LATCH
PROVIDE LIGHT SWITCH FOR CONF. RM., SED.
PROVIDE CARPET, RUBBER WALL BASE AND INDICATED TRANSITION STRIP
(E) FRAMES, RE-USE (E) HINGES OR PROVIDE NEW
PROVIDE HM FRAME & WOOD DOOR W/ GLASS,SEE DOOR SCH.
FURNITURE ARE NIC, SHOWN FOR REF. ONLY
PROVIDE ALUM OR SS SCHLUTER CORNER BASE TRIM
PROVIDE WALK OFF MAT, 6 FT. X 9 FT. INSERT CARPET TILE, FLUSH W/ ADJ CARPET TILE & SECURED TO FLOOR W/ ADHESIVE.
INSTALL 48" HT FRP FINISH AS INDICATED IN ELEVATION DWG; ALL WALLS IN STALLS
3'X4' - 3/4" PLYWOOD BOARD BEHIND RACK.COORD. W/ OWNER'S IT VENDOR.
25 PROVIDE CONDUIT FOR OPEN WIRE(S) & INSTALLNEATLY ON ADJ WALL SURFACE & PAINT.
26 ELECTRICAL/ DATA/ ETC. CLUSTER TO BE PROTECTED DURING WORK.
GENERAL NOTES: A. PROTECT ALL (E) BLDG COMPONENTS,
FINISHES & SURFACES TO REMAIN.
B. ALL CUTTING & PATCHING OF (E) FINISHES TO REMAIN REQUIRE PRIOR APPROVAL & COORDINATION BY GC/ OWNER.
C. PATCH ALL (E) SURFACES TO REMAIN AT AREAS OF DEMOLITION OF (E) CEILING, WALLS, PLUMBING, ELECTRICAL AND HVAC.
D. PAINT ALL WALLS, CEILINGS, DOORS, DOOR FRAMES AND EXPOSED EQUIPMENTS, U.O.N.
27 LIGHT FIXTURE, SED.
28 PROVIDE GYP BD FIN. AT OPENING
29 REMOVE/ REINSTALL SLAB, S.P.D. & 13/A900
30SEE DETAIL 7/A700 FOR DOOR/FLOOR CLEARANCE AND MANEUVERING WITHIN RESTROOM STALL.
31 AUTOMATIC DOOR OPENER & PSUH PLATE ACTUATORS AT (E) DOORS
1
19
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
ENLARGED FLOORPLAN & INTERIOR
ELEVATIONS
A400
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
1/4" = 1'-0"1 ENLARGED PLAN - (E) MEETING. RM, (E) LOCKER AREA & RESTROOM
1/4" = 1'-0"15 RESTRM ELEVATION
1/4" = 1'-0"14 RESTRM ELEVATION
1/4" = 1'-0"10 RESTRM ELEVATION
1/4" = 1'-0"9 RESTRM ELEVATION
1/4" = 1'-0"13 RESTRM ELEVATION1/4" = 1'-0"8 RESTRM ELEVATION
1/4" = 1'-0"12 (E) OFFICE ELEVATION1/4" = 1'-0"7 (E) OFFICE ELEVATION
1/4" = 1'-0"11 (E) OFFICE ELEVATION1/4" = 1'-0"6 (E) OFFICE ELEVATION
1/4" = 1'-0"4 LOCKER AREA
1/4" = 1'-0"2 HALLWAY 2 - ELEVATION1/4" = 1'-0"3 RESTRM ELEV.
1
11
1 1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK2 06-05-2019 PERMIT PLANCHECK #2
2
2
2
2
1 2 3 4 5 6
A
B
D
F
H
G
C
E
(E) ROOM21
(E) WORKSHOP -NIC17
(E) ROOM20
(E) ROOM18
(E) OFFICE07
(E) OPEN OFFICE01
(E) OFFICE 412
(E) OFFICE 311
(E) LOCKER RM08
(E) HALL14
ALL GENDERTOILET RM
04
(E) MECHRM./JAN. CLOSET
03(E) LUNCH RM
02
EXISTING19
(E) LCKR CLOS15
(E) CLOSET16
(E) OFFICE 109
(E) OFFICE 210
4
3
3
5
5
LAV-RM22
AREA N.I.C.
1
3
1
6
7
8
TYP, UON.
TYP, UON.
2
2
9
2' - 7"
10
EQEQ
EQ
1
ALL GENDERACC. TOILET RM
25
1
10
2
12" x 12" ACOUSTIC CEILING PANEL
REFLECTED CEILING PLAN LEGEND
(E) PLASTER OR GYPBD CEILING
(E) DIFFUSER, SUPPLY & RETURN, S.M.D.
(E) DIFFUSER, N.I.C.
(E) FLOUR. LIGHT FIXTUREAND (E) SWITCH, SED.
$
AREA NOT IN CONTRACT
F
N.I.C.
(E) ATTIC ACCESS, N.I.C. & DIFFUSER W/ FAN. S.M.D.
(E) SMOKE DETECTOR AND (E) SPRINKLER HEAD, NIC
KEYNOTES:
1
2
3
4
REPAIR, PATCH DAMAGED (E) CEILING TILES.REVIEW QTY. DURING SITE WALK.
RELOCATE LIGHT FIXTURES FROM CONFERENCE RM TO NEW LOCATIONS . S.E.D.
INSTALL LIGHT SWITCH & CONNECTING WIRING, SED.
RELOCATE LIGHT FIXTURE FROM (E) OFFICE AND LOCATE AT CENTER OF HALLWAY. S.E.D.
PROVIDE EXIT LIGHT & CONNECTING WIRING, SED.
INSTALL CEILING TILE AMSTRONG 12X12X5/8" CONCEALED K4C4 FINE FISSURED. SCREWED TO (E) CEILING JOISTS.
(E) LIGHTING.
(E) MECH DIFFUSER, PAINT TO MATCH CEILING.
RELOCATE (E) LIGHT FIXTURE TO NEW LOCATIONS. S.E.D.
EF AT CEILING, AT CENTER OF TOILET PARTITION BELOW. FLASH VENT STACK @ ROOF PER ROOFING RECOMMENDATIONS. S.M.D.
5
RCP GENERAL NOTES: A. REPAIR, PATCH DAMAGED (E) CEILING TILES.
USE CEILING TILES IN GOOD CONDITION FROM HALLWAY-2 TO REPLACE DAMAGED TILES IN OPEN OFFICE FOR TYPE MATCHING. AFTER THOSE ARE USED UP, THEN USE (N) TILE, SIM. 7/A900
B. ELECTRICAL AND CEILING DEVICES ARE SHOWN FOR REFERENCE ONLY. S.E.D.
C. NO WORK IN (E) LUNCH ROOM, UON.
D. PATCH CEILING TO MATCH ADJ. WHERE WALLS, LIGHTINS, MECHANICAL EQUIPMENT ETC RELOCATED.
6
7
8
9
10
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
REFLECTEDCEILING PLAN -
LEVEL 1
A600
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
3/16" = 1'-0"1 REFLECTED CEILING PLAN
1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK2 06-05-2019 PERMIT PLANCHECK #2
2
2
1. ALL THRESHOLDS SHALL HAVE 1/2" MAXIMUM OVERALL RISE AND SHALL BE BEVEALED WITH A SLOPE NOT STEEPER THAN 1:2 WITH A 1/4" MAX. VERTICAL. SEE THRESHOLD DETAIL ON SHEET A900 FOR MORE INFORMATION.
2. PROTECT ALL DOORS NOTED TO REMAIN DURING CONSTRUCTION, REPAIR AND REFINISH, TYPICAL.
3. AT (E) FRAMES TO BE REUSED OR LEFT IN PLACE, PROTECT DURING CONSTRUCTION, REPAIR AND REFINISH.
4. VERIFY IN FIELD ALL DOOR SIZES SHOWN. DOORS TO MATCH (E) DIMENSIONS AND MATERIALS, U.O.N.
5. MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 POUNDS FOR EXTERIOR AND INTERIOR DOORS. SUCH PULL OR PUSH EFFORT IS APPLIED AT RIGHT ANGLES TO HINGED DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET THE ABOVE STANDARDS.
6. REFINISH ALL (E) DOORS AND FRAMES TO MATCH (E) FINISH.7. HARDWARE OPERABLE W/ ONE HAND & W/O GRASPING, PINCHING, TWISTING OF HAND WRIST.
1. ALL CONCRETE FLOORS TO BE CLEANED BEFORE FINISH APPLICATION.2. SEE INTERIOR ELEVATIONS AND PLANS FOR ADDITIONAL FINISH INFORMATION.3. ALL NEW CEILING SHOULD MATCH EXISTING MATERIALS AND HEIGHTS, U.O.N.4. ALL NEW BASE SHOULD MATCH EXISTING MATERIALS AND HEIGHTS, U.O.N.5. PAINT ALL SURFACES (EXISTING AND NEW) AT INTERIOR SPACES.6. ALL CEILINGS ARE 9'-0", UON.
ACT : ACOUSTIC CEILING TILECPT : CARPET TILEGYB : GYPSUM BOARDPNT : PAINT PTD CONC : PAINTED CONCRETE(E) : EXISTINGV : VINYLR : RUBBER
HM : HOLLOW METALPTD : PAINTEDWD : WOODMPF : MANUF. PRE FINISHT : TEMPERED GLASS
(E) : EXISTING(N) : NEW
TOILET TISSUE DISPENSER
PAPERTOWELDISPENSER
GRAB BARSNAPKIN DISPOSALN/A
SEAT COVERDISPENSER
TOILET ROOM ACCESSORIES
1
2' -
9"
COAT HOOK
MIRROR
B. MOUNTING HEIGHT SCHEDULE
A. TYPICAL FIXTURE DIMENSIONS / MOUNTING HT.
FIN. FLR.
FLUSH CONTROL @ WIDE SIDE, TYP.
36" MIN.
17"-1
9" 33"
42" MIN.
33"
7"-9"
TOILET TISSUE DISPENSER1
2
3
4
5
6
7
8
2 3 5 6 7 8
ACCESSIBLE TOILET
17"-1
9"
1
NAPKIN DISPOSAL (NOT USE)
SEAT COVER DISPENSER
PAPER TOWEL DISPENSER, 4" DEPTH.
GRAB BARS
COAT HOOK/BUMPER AT EA. TOILET STALL
MIRROR
4
SOAP DISPENSER
MIN.
1' - 0"
FLEXIBLE VINYLPIPE WRAP, TYP.
18" MIN. TO SIDE WALL
34" T
.O. L
AV
WALL MOUNTED LAVATORY
SOAP DISPENSER (WALL MTD.)
40" M
AX.
54" MIN.
19" M
IN.
18" MIN.
6".1' - 0"
FLR MTD. TYPE WHERESCH'D
FLR MTD. TYPE WHERESCH'D
19" M
IN.
27" M
IN.
9" M
IN.
TOE CLEARANCE6" MAX.
1
1
1
1
1
8" MIN.
56"MIN. (WALL MTD. WC)59"MIN. (FLR MTD. WC)
DR SWINGS-N36" MIN. WHEN
MANEUVERING SPACE60" MIN.
60" M
IN. DOOR
ALLOWEDTO SWING OVER HATCHED PORTION
MANEUVERING SPACE 11B-604.3
60"DIA.ADA.CLR
. FLR.
1
12" MAX.
29" M
IN.
DEPTH17 MIN.
SYMBOL OF ACCESSIBILITY, TYP.
GRADE 2 BRAILLE, TYP.
RAISED LETTERS, TYP."ALL-GENDER"
SIGN TYPE "A"TOILET ROOM SIGN
ALL-GENDER RESTROOM
.: :: :. .:
.: :: :. .:
ALL GENDER
1' -
0"
6"
6"
SIGN TYPE "B"TOILET ROOM WALL SIGN
SIGN TYPE "C"ROOM SIGN 6"
6"
GRADE 2 BRAILLE, TYP.
MIN. 5/8" HIGH RAISED LETTERS, TYP.
FAMILYCHANGING
ROOM
FLUSH 1" HIGH CONTRASTING LETTERS, TYP. & PICTOGRAM
SIGN TYPE "A" SIGN TYPE "B" & "C"
6"DOOR LATCH SIDE
4' -
0" M
IN.
5' -
0" EQ. EQ.
TO B
.O. B
RAI
LLE
5'-0
" TYP
. M
AX. T
O
BASE
LIN
E H
IGH
EST
CH
ARAC
TER
5' -
0"4'
- 0"
2' - 0"
1' - 6"
1' - 0"
REFER TO CBC 1008.1 AND 11B-404 FOR ADDITIONAL INFORMATION ON DOORAND REQUIRED CLEARANCES
PROVIDE THIS ADDITIONAL CLEARANCE IF THE DOOR IS EQUIPPED WITH BOTH A LATCH AND CLOSER
PUSH SIDE
PULL SIDE
ADD 6" AT EXTERIOR SIDE OF EXTERIOR DOORS
APPR
OAC
H44
" HIN
GE
TYPE "A"FLUSH DOOR
TYPE "B"FLUSH DOOR
SEE SCHED.
SEE
SCH
ED.
SEE SCHED.
SEE
SCH
ED.
DOOR FRAMESEE SCH.
DOOR FRAMESEE SCH.
TYPE "C"FLUSH DOOR
SEE SCHED.
SEE
SCH
ED.
DOOR FRAMESEE SCH.
12".
6" MIN.
6" MIN.
EQ.
6".
12x24LOUVERWHERESCH.D
2' - 0"6".
6".
12".
12".
12".
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
SCHEDULES
A700
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
ROOM FINISH SCHEDULEROOM NO. ROOM NAME FLOOR FINISH BASE FINISH WALL FINISH CEILING FINISH COMMENTS
01 (E) OPEN OFFICE CPT R PNT (E) ACT - PNT02 (E) LUNCH RM (E) (E) PNT (E) ACT - PNT03 (E) MECH RM./JAN. CLOSET (E) (E) (E) (E) GYB04 ALL GENDER TOILET RM V V PNT (E) GYB - PNT FRP WAINSCOT (PARTIAL, SEE ELEVATIONS)07 (E) OFFICE CPT R PNT (E) ACT - PNT08 (E) LOCKER RM CPT R PNT (E) ACT - PNT09 (E) OFFICE 1 CPT R PNT (E) ACT - PNT10 (E) OFFICE 2 CPT R PNT (E) ACT - PNT11 (E) OFFICE 3 CPT R PNT (E) ACT - PNT12 (E) OFFICE 4 CPT R PNT (E) ACT - PNT13 RR.HALL (E) TILE R PNT (E) GYP - PNT (E) TILE FLOOR & BASE14 (E) HALL CPT R PNT ACT - PNT15 (E) LCKR CLOS CPT R PNT (E) GYB - PNT16 (E) CLOSET CPT R PNT (E) GYB - PNT22 LAV-RM (E) TILE (E) TILE PNT (E) GYB- PNT (E) TILE FLOOR & BASE23 (E) TEL/ DATA24 (E) CLOSET25 ALL GENDER ACC. TOILET RM V V PNT (E) GYB - PNT
DOOR SCHEDULE
DOOR #FIRERATE GLAZE
SIZES DOOR FRAME DETAILS
HDWR SIGNS COMMENTSWIDTH HEIGHTTHICKNE
SS TYPE MATERIAL FINISH TYPE MATL FINHEAD /JAMB
THRESHOLD
01 - T 3' - 0" 7' - 0" 1 3/4" C WD STAIN A HM PTD A900 N/A GRP.1 (N) DR W/ FULL GLASS04 - - 5' - 8" 6' - 8" 1 3/4" BB HM PTD (E) HM PTD A900 (E) GRP.3 (E) MECHANICAL RM07 - - 5' - 10" 7' - 5" (E) AL - (E) AL - (E) (E) GRP.7 (E) FRONT ENTRY W/ AUTO DOOR OPENER08 - - 3' - 0" 7' - 0" 1 3/4" (E) WD RE-STAIN (E) - PTD (E) (E) - (E) LUNCH RM09 (E) - 3' - 0" 7' - 0" 1 3/4" (E) HM PTD (E) HM PTD (E) (E) - TO/FR WORKSHOP. (E) FIRE RATED DR.10 - - 3' - 0" 7' - 0" 1 3/4" (E) WD RE-STAIN (E) - PTD (E) (E) - (E) OFFICE11 - - 3' - 0" 7' - 0" 1 3/4" (E) WD RE-STAIN (E) - PTD (E) (E) - (E) OFFICE12 - - 3' - 0" 7' - 0" 1 3/4" (E) WD RE-STAIN (E) - PTD (E) (E) - (E) OFFICE13 - - 3' - 0" 7' - 0" 1 3/4" (E) WD RE-STAIN (E) - PTD (E) (E) - (E) OFFICE14 - - 3' - 0" 7' - 0" 1 3/4" (E) WD RE-STAIN (E) - PTD (E) (E) - (E) LOCKER RM15 - - 4' - 0" 7' - 0" 1 3/4" (E) WD RE-STAIN (E) - PTD (E) (E) - (E) PAIR - CLOSET DR28 - - 3' - 0" 7' - 0" 1 3/4" A WD STAIN A - PTD A900 5/A900 GRP.2 A,B (N) DR @ RR HALLWAY. PUSH & PULL/ NO LATCH29 - - 3' - 0" 7' - 0" 1 3/4" (E) HM RE-STAIN (E) HM PTD (E) (E) (E) (E) MECHNICAL RM30 - - 2' - 2" 6' - 8" 1 3/4" A WD PTD A WD PTD A900 N/A GRP.5 N/A LAV RM CLOSET33 - - 5' - 8" 6' - 8" 1 3/4" BB WD STAIN A WD PTD A900 N/A GRP.4 N/A (E) TEL/ DATA34 - - 5' - 8" 6' - 8" 1 3/4" BB WD STAIN A WD PTD A900 N/A GRP.4 N/A (E) OFFICE CLOSET35 - - 2' - 10" 7' - 0" 1 3/4" A WD PTD A WD PTD A900 N/A GRP.6 C RESTRM, PRIVACY LATCH ONLY36 - - 3' - 0" 7' - 0" 1 3/4" A WD PTD A WD PTD A900 N/A GRP.6 A,B RESTRM, PRIVACY LATCH ONLY
DOOR SCHEDULE GENERAL NOTES
FINISH SCHEDULE GENERAL NOTESFINISH SCHEDULE ABBREVIATIONS
DOOR SCHEDULE ABBREVIATIONS
1 : 17 TYPICAL FIXTURE DIMENSIONS, MOUNTING HEIGHT & CLEARANCES
1 : 16 SIGN TYPES1 : 12 SIGN MOUNTING
1 : 11 ACCESSIBLE DOOR CLEARANCES1 : 15 DOOR & FRAME TYPES
1
1
1
1
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK2 06-05-2019 PERMIT PLANCHECK #2
2
2
2
2
2
(E) CLG TILES ON(E) PERP JST.
ACOUSTICAL INSULATION
5/8" GYP BDBOTH SIDES OF2x4 WD FRM.
PROVIDE 2x BLCKGBTWN (E) PARALLEL JST.
WALL HEAD WALL HEAD
(E) CLGVIF.
A
HM FRM, SEE SCHEDULE
WOOD DOOR,SEE SCHEDULE
(E) PARTITION & HEADER, VIFOR PROVIDE ONE AT (N) OPENING
2" M
IN.
2" M
IN.
(E) HM FRAME
(E) CONC. WALL
HOLLOW METAL DOOR, SEE DOOR SCHEDULE
CARPET TILE FLOORINGTRANSITION STRIP
(E) TILE FLOORING
(E) CONC. SLAB
1/4"
MAX
.
VINYL SHEET FLOORING O/MASTIC
TRANSITION STRIP(E) TILE FLOORING
(E) CONC. SLAB
C. TILE TO VINYL
D. TILE TO CARPET
SEE
NO
TE A
.1/
4" M
AX.
NOTE A:WHERE FIELD CONDITION REQUIRES MORE THAN 1/4" VERTICAL RISE, USE THIS TRANSITION TYPE
1/4", 2:1 SLOPE MAX.
1/4" MAX.
CARPET TILE FLOORINGTRANSITION STRIP
(E) CONC. SLAB
A. CONCRETE TO CARPET
1/4"
MAX
.
B. CARPET TO (E) CARPET
(E) CARPET
VINYL FLOORING & ROLL-UP BASE
MTL COVE STRIP
MATCH (E) TILE BASE HEIGHT
FRP & WAINSCOT TRIM
FRP WAINSCOT TRIM
VINYL INTEGRAL BASE
FRP VERTICAL JNT, NTS
FRP IC COVER, NTS
FRP LEG, NTS
5/8" GYPBRD O/2x4 FURRING WD FRM
(E) GYPBRD O/(E) WD FRM TO REMAIN
WALL HEAD
(E) GYPBRD CLG
3/8" CAULK ALL SIDESVIF (E) WALL HEAD CONDITION
B
REMOVE (E) GYPBRD
RESTRMLAV RM
VIF.
ATTACH TILES TO JOISTS W/ MIN. (6) 1-3/4" FLAT HEAD SCREWS
(E) ATTIC
(E) CLG JOISTS,VIF.
(E) CONC SLAB-ON-GRADEVIF.
(E) 6X6 #8 WELDED WIRE FABRIC
CONC PATCH, 28 DAY MIN COMPRESSIVE STRENGTH TO EQUAL 3,000 PSI
#4 x 12" ADHESIVELY GROUTED DOWELS @ 24" OC ALL EDGES @ MID-DEPTH OF SLAB AND#4 @ 18" OC (2 BARS MIN)
#4 @ 24" OC
2
1 1' -
0"
IDEALIZED INFLUENCE LINETRENCHING BELOW
PIPE TRENCH & BACKFILLPER SPEC. &PIPE PER PLUMBING DRAWINGS (E) FOOTING
WHERE OCCURS
SUBGRADE BELOW NEW CONCRETE TO MATCH (E) ADJACENT
ALIGN
ALIGN
1
ALIGN
1
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:CANYON CONSULTING ENGINEERS3150 HILLTOP MALL RD., STE. 18RICHMOND, CA 94806P: (510) 243-5987
DESNECIL TCE
TIHCRA
CALI FOR
NIA
STAT E OF
YAHAN OT
C-28902REN. 08/31/19
DIA N
PERMIT SET
DETAILS
A900
NOV. 16, 2018
CITY OF BERKELEY, CA1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEYTRANSFER
STATION OFFICE1201 Second Street, Berkeley, CA 94710
201320.19
1 : 11 PARTITION TYPE A AND WALL HEADS
1 : 14 INTERIOR HM DOOR - HEAD / JAMB
1 : 13 EXTERIOR HM DOOR - HEAD / JAMB
N.T.S.5 FLOOR TRANSITIONS
N.T.S.8 INTEGRAL VINYL WALL BASE, FRP & ACCESSORIES
1 : 12 PARTITION TYPE B (FURRING WALL) & WALL HEAD
N.T.S.7 CEILING TILE TO JOIST DETAIL
N.T.S.13 TYP SLAB-ON-GRADE PATCH
REVISION
NO. DATE DESCRIPTION
1 04-18-2019 PERMIT PLANCHECK
04-18-2019
04-18-2019
04-18-2019
04-18-2019
04-18-2019
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:
CANYON CONSULTING ENGINEERS
3150 HILLTOP MALL RD., STE. 18
RICHMOND, CA 94806
P: (510) 243-5987
PERMIT SET
NOV. 16, 2018
CITY OF BERKELEY, CA
1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEY
TRANSFER
STATION OFFICE
1201 Second Street, Berkeley, CA 94710
201320.19
REVISION
NO. DATE DESCRIPTION
1 PERMIT PLANCHECK
GENERAL NOTES,
LEGENDS AND
SHEET INDEX
CITY OF BERKELEY, CA
1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEY
TRANSFER
STATION OFFICE
1201 Second Street, Berkeley, CA 94710
201320.19
04-18-2019
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:
CANYON CONSULTING ENGINEERS
3150 HILLTOP MALL RD., STE. 18
RICHMOND, CA 94806
P: (510) 243-5987
PERMIT SET
NOV. 16, 2018
CITY OF BERKELEY, CA
1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEY
TRANSFER
STATION OFFICE
1201 Second Street, Berkeley, CA 94710
201320.19
REVISION
NO. DATE DESCRIPTION
1 PERMIT PLANCHECK
LIGHTING TITLE 24
CALCULATIONS
CITY OF BERKELEY, CA
1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEY
TRANSFER
STATION OFFICE
1201 Second Street, Berkeley, CA 94710
201320.19
04-18-2019
DN
UP
1 2 3 4 5 6
A
B
D
F
H
G
C
E
(E) EQUIPMENT
TO REMAIN
(E) EP TO REMAIN
(E) ALARM BOX
TO REMAIN
(E) MECH UNIT
TO REMAIN
(E) AIR SHAFT &
WALL VENT TO
REMAIN
(E) PIPE RUNNING
FROM CEILING TO
(ALMOST) GROUND TO
REMAIN
(E) LUNCH RM
02
(E) MECH RM.
03
RESTRM
04
(E) LOCKER RM
08
(E) OFFICE 1
09
(E) OFFICE 2
10
(E) OFFICE 3
11
(E) OFFICE 4
12
PRINTER / COPIER
FILES
FILES FILES
(E) CABINETS AND SINK
TO REMAIN
RR.HALL
13
(E) LCKR CLOS
15
(E) OPEN OFFICE
01
LCKR.HALL
14
CLOSET
16
CONFERENCE
RM.
07
(E) FIRE EXT.
TO REMAIN
(E) FIRE EXT.
TO REMAIN
(E) WORKSHOP -
NIC
17
(E) ROOM
21
(E) ROOM
20
(E) ROOM
18
(E) LOCKERS
TO REMAIN
LAV-RM
22
(E) CABINET
TO REMAIN
AREA N.I.C.
TEL/ DATA
23
CLOSET
DA RESTRM
25
JAN.
CLO.
(E) EP TO REMAIN
DATA STATION (FOR INFORMATION ONLY)
(TYP)
CKTS-1,3 CKTS-2,4
SHEET NUMBER:
PROJECT NUMBER:
DATE:
ISSUE:
SHEET TITLE:
PROJECT:
CLIENT:
CONSULTANTS:
MEP ENGINEER:
CANYON CONSULTING ENGINEERS
3150 HILLTOP MALL RD., STE. 18
RICHMOND, CA 94806
P: (510) 243-5987
PERMIT SET
NOV. 16, 2018
CITY OF BERKELEY, CA
1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEY
TRANSFER
STATION OFFICE
1201 Second Street, Berkeley, CA 94710
201320.19
REVISION
NO. DATE DESCRIPTION
1 PERMIT PLANCHECK
CONFERENCE &
RESTROOM
POWER AND
LIGHTING PLAN
CITY OF BERKELEY, CA
1947 Center Street, 4th Floor
Berkeley, CA 94704
AIRCO BERKELEY
TRANSFER
STATION OFFICE
1201 Second Street, Berkeley, CA 94710
201320.19
SHEET NOTES:
GENERAL NOTES:
04-18-2019
04-18-2019
04-18-2019
04-18-2019