Markus Freiburghaus Dipl. El. Ing. FH
Product Manager MV and GIS IT’s
PFIFFNER Instrument Transformers Ltd.
5042 Hirschthal / Schweiz
: +41 (0)62 739 28 65 : +41 (0)62 739 28 10
E-mail: [email protected]
Internet: www.pfiffner-group.com
PFIFFNER Medium Voltage
Ring Core Current Transformers
Product Portfolio
![Page 2: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/2.jpg)
Content
www.pfiffner-group.com / page 2 / 12.06.2017
• PFIFFNER general presentation:
![Page 3: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/3.jpg)
Content
www.pfiffner-group.com / page 3 / 12.06.2017
• The 2 main groups
1. CT’s for the distribution/transmission network (12kV … 800kV)
a) Bushing Type Current Transformers / Cable Current Transformers
• current range up to ~8’000A
• without primary conductor and without primary insulation of its own
• applicable for all voltage levels if fitted over a fully insulated bushing, busbar,
cable or other conductor
• available also in split-core design
2. CT’s for the power generation network (high-current CT’s)
a) Bushing Type Current Transformers
• all current ranges up to 50’000A
• without primary conductor and without primary insulation of its own
• applicable for all voltage levels if fitted over a fully insulated bushing, busbar,
cable or other conductor
b) Fully Insulated Type Current Transformer
• Current range up to 15’000A
• Insulation level up to Um=36kV
![Page 4: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/4.jpg)
www.pfiffner-group.com / page 4 / 12.06.2017
1. PFIFFNER Portfolio
JK
Indoor closed CT
JKS-S
JKS
Indoor split core CT
JK-F
JK-G
Outdoor closed CT
JKS-G
Outdoor split core CT
![Page 5: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/5.jpg)
www.pfiffner-group.com / page 5 / 12.06.2017
JK
Installation:
Indoor, resin encapsulated (PUR)
Mounting:
Over a fully insulated bushing, busbar, cable or
other conductor
Mounting position:
free
Primary insulation:
fulfilled by the insulated primary conductor
Primary current range:
up to ~8‘000A
Hole diameter:
Variable
Several cores in one CT is possible, maximum
number depends on the specification and the
limiting dimensions on site
• JK
![Page 6: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/6.jpg)
www.pfiffner-group.com / page 6 / 12.06.2017
JK
• Dimensions, standard shape
□230mm □300mm □350mm □400mm □450mm
• Hole diameter: variable
• Height: variable up to 300mm
![Page 7: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/7.jpg)
www.pfiffner-group.com / page 7 / 12.06.2017
JK
• Other shapes, customized
• Hole diameter: variable
• Height: variable
• A big variety of round outer dimensions can be realized according to
customer needs.
![Page 8: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/8.jpg)
www.pfiffner-group.com / page 8 / 12.06.2017
JK
• Secondary terminals
Cover (IP 20) Flexible wire Terminal box (IP 65)
M6 connection M6 connection
![Page 9: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/9.jpg)
www.pfiffner-group.com / page 9 / 12.06.2017
JK
• Installation material, option
Ground installation Ground installation Wall or head over installation
with angles with a plate with angles
Several customized installation material realized
![Page 10: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/10.jpg)
www.pfiffner-group.com / page 10 / 12.06.2017
JK
• Installations
Installation on bushings
Installation on
cables
![Page 11: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/11.jpg)
www.pfiffner-group.com / page 11 / 12.06.2017
JKS-S / JKS
JKS-S
JKS
• JKS-S / JKS Installation:
Indoor, split-core design, resin encapsulated (PUR)
Mounting:
Over a fully insulated bushing, busbar, cable or
other conductor
Mounting position:
free
Primary insulation:
fulfilled by the insulated primary conductor
Primary current range:
up to ~2‘500A
Hole diameter:
JKS-S: 90mm, 120mm, 150mm
JKS: Variable
Usually a single core design. If a two core design is
possible depends on the specification.
![Page 12: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/12.jpg)
www.pfiffner-group.com / page 12 / 12.06.2017
JKS-S / JKS
• Standard type JKS-S
• Hole diameter: 90mm, 120mm, 150mm
• Height: 130mm, 200mm, 270mm
• Secondary terminal M6
• Cover (IP20)
• For standard requirements
• Special type JKS
• Hole diameter: variable
• Height: variable
• Secondary terminal M6
• Not covered (IP00)
• For high accuracy requirements, if the
standard type JKS-S is not applicable
![Page 13: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/13.jpg)
www.pfiffner-group.com / page 13 / 12.06.2017
JK-F
Installation:
Outdoor, resin encapsulated (Epoxy)
Mounting:
Over a fully insulated bushing, busbar, cable or
other conductor
Mounting position:
free
Primary insulation:
fulfilled by the insulated primary conductor
Primary current range:
up to ~8‘000A
Hole diameter:
Variable
Several cores in one CT is possible, maximum
number depends on the specification and the
limiting dimensions on site
• JK-F
![Page 14: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/14.jpg)
www.pfiffner-group.com / page 14 / 12.06.2017
JK-F
• Dimensions, standard shape
• See JK, identical
• Other shapes, customized
• Hole diameter: variable
• Height: variable
• A big variety of round outer dimensions can be realized according to
customer needs.
![Page 15: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/15.jpg)
www.pfiffner-group.com / page 15 / 12.06.2017
JK-F
• Secondary terminals
Terminal box (IP 65)
M6 connection
![Page 16: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/16.jpg)
www.pfiffner-group.com / page 16 / 12.06.2017
JK-G
Installation:
Outdoor, with aluminium shell
Mounting:
Over a fully insulated bushing, busbar, cable or
other conductor
Mounting position:
Horizontal, with a maximum angle of 60°
Primary insulation:
fulfilled by the insulated primary conductor
Primary current range:
up to ~5‘000A
Hole diameter:
80mm, 110mm, 140mm, 220mm
Several cores in one CT is possible, maximum
number depends on the specification and the
limiting dimensions on site
• JK-G
![Page 17: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/17.jpg)
www.pfiffner-group.com / page 17 / 12.06.2017
JK-G
• Secondary terminal M6
• Terminal box and CT-housing (IP65)
• Two dimensions:
• Hole diameter: 80mm, 110mm, 140mm 220mm
• Height: ~320mm ~230mm
![Page 18: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/18.jpg)
www.pfiffner-group.com / page 18 / 12.06.2017
JKS-G
Installation:
Outdoor, spli-core design, with aluminium shell
Mounting:
Over a fully insulated bushing, busbar, cable or
other conductor
Mounting position:
Horizontal, with a maximum angle of 45°
Primary insulation:
fulfilled by the insulated primary conductor
Primary current range:
up to ~2‘500A
Hole diameter:
85mm, 115mm, 145mm, 225mm
Usually a single core design. If a two core design
is possible depends on the specification.
• JKS-G
![Page 19: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/19.jpg)
www.pfiffner-group.com / page 19 / 12.06.2017
JKS-G
• Secondary terminal M6
• Terminal box (IP65)
• CT-housing (IP53)
• Two dimensions:
• Hole diameter: 85mm, 115mm, 145mm 225mm
• Height: ~320mm ~230mm
![Page 20: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/20.jpg)
Indoor / Outdoor installation
Closed or split-core design (execution possibilities, costs)
Hole diameter
Degree of protection for secondary terminals (if required)
Limiting outer dimensions from the site (if existing)
Installation materiel (if needed)
Electrical specification
www.pfiffner-group.com / page 20 / 12.06.2017
1. Information needed
![Page 21: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/21.jpg)
Bushing manufacturers (like MGC)
Transformer manufacturers
Network operators
Switchgear/-yard manufacturers or contractors
New built projects
Replacement/Refurbishment projects
Special electrical specification
Special requirement to the dimensions/installation
If there is a mass product on the market, PFIFFNER has a cost
disadvantage
www.pfiffner-group.com / page 21 / 12.06.2017
1. Market from technical side
![Page 22: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/22.jpg)
www.pfiffner-group.com / page 22 / 12.06.2017
1. Impressions
![Page 23: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/23.jpg)
www.pfiffner-group.com / page 23 / 12.06.2017
1. Impressions
![Page 24: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/24.jpg)
www.pfiffner-group.com / page 24 / 12.06.2017
1. Impressions
![Page 25: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/25.jpg)
www.pfiffner-group.com / page 25 / 12.06.2017
2. Power plant layout
CT‘s for the
generator
bushing
CT‘s for the
generator circuit
breaker (GCB)
CT‘s for the non-isolated
busbar or the isolated
phase busduct (IPB)
![Page 26: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/26.jpg)
www.pfiffner-group.com / page 26 / 12.06.2017
2. PFIFFNER Portfolio
JKQ
Generator
circuit
breaker
(GCB)
AKA AKQ
Generator busduct / busbar
for non-isolated
busbar systems
or inside isolated
phase busduct
systems (IPB)
for non-isolated
busbar systems
(fully insulated
type CT) ALG
JK-GCT
Generator
bushing
![Page 27: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/27.jpg)
www.pfiffner-group.com / page 27 / 12.06.2017
ALG / JK-GCT
ALG
JK-GCT
Mounting:
Over generator bushing
Mounting position:
Horizontal
ALG: up to a max. angle of 30°
JK-GCT: up to a max. angle of 60°
Primary insulation:
fulfilled by the generator bushing
Primary current range:
up to 50‘000A
ATEX Certification:
ALG:
JK-GCT: in work
![Page 28: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/28.jpg)
Reference list
Main markets: Thermal power plants up to ~1200MW (coal and nuclear)
(new units and also important: renovations/refurbishments)
www.pfiffner-group.com / page 28 / 12.06.2017
Power plant Icth [A] Delivery
Oskarshamn / SWE 40’600 1995
Darlington / CAN 37’500 2007/2016
Bruce / CAN 35’000 2015
Leibstadt / CH 30’000 2009
Manjung / MYS 30’000 2012
Opole / POL 30’000 2016
Niederaussem / GER 28’000 2001
Lippendorf / GER 27’000 1997
Dabieshan / CHN 25’000 2006
Longshan / CHN 25’000 2007
PingWei / CHN 25’000 2007
Longview / USA 25’000 2008
Pingliang / CHN 25’000 2008
Eemshaven / NED 25’000 2011
ALG
![Page 29: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/29.jpg)
Reference list
Main markets: Thermal power plants up to ~1700MW (coal and nuclear)
(new units and also important: renovations/refurbishments)
www.pfiffner-group.com / page 29 / 12.06.2017
JK-GCT
Power plant Icth [A] Delivery
Duke McGuire / USA 40’000 2011
Haiyang / CHN 45’000 2011
Shidaowan / CHN 45’000 2016
Sanmen / CHN 45’000 2011
Taishan / CHN 45’000 2011
Almaraz / ESP 40’000 2011
Doel / BEL 35’000 2010
Diablo Canyon / USA 35’000 2016
NingDe / CHN 33’000 2009/2010
HongYanHe / CHN 33’000 2009/2010
Ling Ao / CHN 32’000 2007
Kuosheng / TWN 30’000 2015
![Page 30: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/30.jpg)
www.pfiffner-group.com / page 30 / 12.06.2017
AKA
AKA
Mounting:
Inside an IPB
or
over a non-isolated busbar
Mounting position:
free
Primary insulation:
Fullfilled with air distance
Primary current range:
up to 50‘000A
ATEX Certification:
AKA:
The minimum isolation air
distance between the
conductor and the CT depends
on the geometry of the primary
conductor and the insulation
voltage level
![Page 31: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/31.jpg)
Referenzliste
www.pfiffner-group.com / page 31 / 12.06.2017
AKA
Power plant Icth [A] Delivery
Quin Shan / CHN 35’000 2010
Fujian Fuqing / CHN 35’000 2010
Fang Cheng Gang / CHN 33’000 2012
Yangjiang / CHN 33’000 2011
Hong Yan He / CHN 33’000 2010
Ning De / CHN 33’000 2010
Three Georges / CHN 30’000 2010
Leibstadt / CH 30’000 2010
Neurath / GER 30’000 2007
Anhui Tianji / CHN 28’000 2012
GKM Mannheim / GER 27’000 2011
Moorburg / GER 26’000 2010
Eemshaven / NED 25’000 2011
Westfalen / GER 25’000 2009
![Page 32: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/32.jpg)
www.pfiffner-group.com / page 32 / 12.06.2017
JKQ
Mounting:
Inside a GCB
Mounting position:
Free between horizontal and vertical, but not over
head
Primary insulation:
Fulfilled with air distance
Primary current range:
up to 50‘000A
JKQ
![Page 33: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/33.jpg)
www.pfiffner-group.com / page 33 / 12.06.2017
AKQ
AKQ
Mounting:
Over a non-isolated busbar
Mounting position:
free
Primary insulation:
Fullfilled in the CT with resin
CT is a fully insulated medium voltage type
(Um up to 36 kV)
Primary current range:
up to ~15‘000 A
There is no need for a
minimum isolation air distance
between the primary
conductor and the CT
![Page 34: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/34.jpg)
www.pfiffner-group.com / page 34 / 12.06.2017
Power plant Icth
[A]
Delivery
Teles Pires / BRA 19’000 2013
Itaipu / BRA 13’000 2003/2017
Obervermunt II / AUT 12’000 2017
Boyabat / TUR 10’000 2011
Unknown, India 9’000 2010
Foz Tua / PRT 9’000 2015
Unknown, Iran 8’000 2009
Seitevare / SWE 8’000 2013
Grand Coulee / USA 8’000 2015
Laziska / POL 7’000 2011
Alqueva / PRT 6’000 2011
Grimsel / CH 5’000 2011
AKQ
Reference list
Main markets: Hydro power plants and thermal power plants up to ~350MW
(new units and also important: renovations)
![Page 35: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/35.jpg)
www.pfiffner-group.com / page 35 / 12.06.2017
2. Technical Know How
Ambient temperature:
Usually high
70°C – 90°C
must be clarified during the offer-time with the customer
Internal losses:
Ohmic resistances of the secondary windings can be high
losses about 100 … 200 W per core
temperatur rise must be calculated by the technical department
Effect of stray magnetic flux:
Neighbour phases create magnetic fields which can give influences on the
accuracy performance of the CT.
Accuracy class must be fulfilled under all conditions.
phase distance and / or distance to the next bend in the primary
bar must be clarified during the offer-time with the customer. Based on this
configuration the technical department has to calculate a sufficient shield
winding, if nescessary.
• Special requirements for high current CT‘s:
![Page 36: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/36.jpg)
Power plant manufacturers/contractors
Generator manufacturers
High-current phase bus manufacturers
Generator circuit breaker manufacturers
New built projects
Replacement/Refurbishment projects
Special technical know how required to do a proper design in the high-
current area
Special requirement to the dimensions/installation
CT’s will be sourced different (generator engineering site, local EPC office,
local contractor, phase bus manufacturer, etc.)
www.pfiffner-group.com / page 36 / 12.06.2017
2. Market from technical side
![Page 37: PFIFFNER Medium Voltage Ring Core Current · PDF fileor inside isolated phase busduct systems (IPB) for non-isolated busbar systems (fully insulated type CT) ALG JK-GCT bushing](https://reader033.vdocument.in/reader033/viewer/2022051202/5a78a09c7f8b9a273b8c3f65/html5/thumbnails/37.jpg)
www.pfiffner-group.com / page 37 / 12.06.2017
2. Impressions