P-05 ELEVATOR LOBBY TAFT AVENUE ERMITA, BRGY 670 ZONE 72, MANILA, 1000 METRO MANILA PHILIPPINE GENERAL HOSPITAL INFRASTRUCTURE PROJECTS FIRE PROTECTION SERVICES CONTRACT DOCUMENT JUNE 13, 2017
ABBREVIATIONS, LEGENDS & SYMBOLS,LOCATION PLAN AND VICINITY MAP
NTS
13JUN17 P05-FP0-01
OSCAR V. RELUCIOPROFESSIONAL MECHANICAL ENGINEER
7334199
JANUARY 05, 2017
MAKATI CITY
2886
CTD
FIRE PROTECTION SERVICES
JCV / JCB
112-191-886
AutoCAD SHX Text
LOCATION PLAN , VICINITY MAP AND SCHEMATIC DIAGRAM
AutoCAD SHX Text
P05-FP1-01
AutoCAD SHX Text
P05-FP0-01
AutoCAD SHX Text
DRAWING INDEX, GENERAL NOTES, ABBREVIATION, LEGENDS & SYMBOLS,
AutoCAD SHX Text
GROUND FLOOR FIRE PROTECTION LAYOUT
AutoCAD SHX Text
P05-FP2-01
AutoCAD SHX Text
MISCELLANEOUS DETAILS
AutoCAD SHX Text
P05-FP0-01
AutoCAD SHX Text
NTS
AutoCAD SHX Text
P05-FP0-01
AutoCAD SHX Text
NTS
AutoCAD SHX Text
P05-FP1-02
AutoCAD SHX Text
P05-FP1-03
AutoCAD SHX Text
SECOND FLOOR FIRE PROTECTION LAYOUT
AutoCAD SHX Text
P05-FP1-04
AutoCAD SHX Text
3.0 ALL FIRE PROTECTION WORKS SHALL CONFORM TO THE FIRE CODE OF THE PHILIPPINES, ALL FIRE PROTECTION WORKS SHALL CONFORM TO THE FIRE CODE OF THE PHILIPPINES, NFPA AND LOCAL ORDINANCES, AND ALL INSTALLATION SHALL BE SUPERVISED BY A LICENSED MECHANICAL ENGINEER. 4.0 PIPING TO BE SCH.# 40 BLACK IRON PIPE, FITTINGS 50mm AND SMALLER SHALL BE THREADED TYPE, 65mm AND LARGER SHALL BE MECHANICAL COUPLING. 5.0 CONTRACTOR TO VERIFY ACTUAL LOCATION OF ALL THE EXISTING FIRE SPRINKLER SUPPLY PIPES WITHIN THE AREA. 6.0 CONTRACTOR SHALL PROVIDE ALL ADDITIONAL SPRINKLER HEADS NECESSARY TO CONFORM TO THE APPLICABLE CODES AND ORDINANCES. 7.0 ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED. 8.0 CONTRACTOR TO VERIFY ACTUAL TAPPING POINTS(POINT OF CONNECTIONS), PIPE SIZES & OTHER DATA REQUIRED FOR THE COMPLETE OPERATION OF THE SYSTEM. 9.0 SPRINKLER HEAD TEMPERATURE RATING SHOULD BE SIMILAR TO THE EXISTING. 10.0 DISMANTLING OF ALL EXISTING SPRINKLER PIPING SHALL BE DONE BY SPRINKLER CONTRACTOR. 11.0 ALL PIPES PASSING THRU WALLS AND SLAB SHALL BE PROVIDED W/ PIPE SLEEVE AND FIRE RATED SEALANT. 12.0 ALL PENDENT AND UPRIGHT SPRINKLERS SHALL BE QUICK RESPONSE TYPE.
AutoCAD SHX Text
GENERAL NOTES: SPRINKLER SYSTEM 1.0 THE FIRE PROTECTION SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES & REGULATIONS: THE FIRE CODE OF THE PHILIPPINES & REGULATIONS NATIONAL BUILDING CODE OF THE PHILIPPINES PMC - PHILIPPINE MECHANICAL CODE 2012 NFPA 10 - STANDARD FOR PORTABLE FIRE EXTINGUISHER NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEM NFPA 14 - STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM NFPA 101 - LIFE SAFETY CODE UNDERWRITERS LABORATORIES, INC. (UL) FACTORY MUTUAL (FM) ASTM - AMERICAN SOCIETY FOR TESTING AND MATERIALS NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 2.0 DESIGN CRITERIA: TYPE OF OCCUPANCY AREA/LOADING DESIGN DENSITY AREA OF SPRINKLER OPERATION DURATION OF WATER SUPPLY SPRINKLER TEMPERATURE ORIFICE K-FACTOR (SPRINKLER) COMBINED IN/OUT HOSE STREAM ALLOWANCE
AutoCAD SHX Text
: LIGHT HAZARD : HALLWAY, LOBBY AND CORRIDOR : 0.10 GPM/FT (4.10 LPM/m) : 1500 FT (140 M ) 2 ) : 30 MINUTES MIN. : 165 °F (GLASS BULB)(QUICK RESPONSE) : 5.6 (80) : 100 GPM
AutoCAD SHX Text
FIRE HOSE CABINET (RECESSED TYPE)
AutoCAD SHX Text
FIRE FIGHTING PIPE
AutoCAD SHX Text
PIPE DOWN
AutoCAD SHX Text
CAPPED PIPE
AutoCAD SHX Text
CONTINUOUS PIPE
AutoCAD SHX Text
PIPE UP
AutoCAD SHX Text
PENDENT SPRINKLER
AutoCAD SHX Text
STANDARD RESPONSE UPRIGHT SPRINKLER
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
TO ABOVE
AutoCAD SHX Text
FIRE HOSE CABINET
AutoCAD SHX Text
FHC
AutoCAD SHX Text
T/B
AutoCAD SHX Text
TYP
AutoCAD SHX Text
T/A
AutoCAD SHX Text
F/A
AutoCAD SHX Text
F/B
AutoCAD SHX Text
FROM ABOVE
AutoCAD SHX Text
FROM BELOW
AutoCAD SHX Text
RN
AutoCAD SHX Text
RISER NIPPLE
AutoCAD SHX Text
LPS
AutoCAD SHX Text
LITERS PER SECOND
AutoCAD SHX Text
LPM
AutoCAD SHX Text
LITERS PER MINUTES
AutoCAD SHX Text
PORTABLE FIRE EXTINGUISHER
AutoCAD SHX Text
4.5KG FE ABC
AutoCAD SHX Text
TO BELOW
AutoCAD SHX Text
H/L
AutoCAD SHX Text
HIGH LEVEL
AutoCAD SHX Text
FC
AutoCAD SHX Text
FLUSHING CONNECTION
AutoCAD SHX Text
FS
AutoCAD SHX Text
FLOW SWITCH
AutoCAD SHX Text
CONTROL VALVE
AutoCAD SHX Text
14.0 NO ADDITIONAL COST WILL BE ENTERTAINED SHOULD THE FINAL POSITIONS BE RELOCATED WITHIN THE SAME ROOM
AutoCAD SHX Text
OF NOT MORE THAN THREE (3) METERS AWAY FROM THE ORIGINAL LOCATIONS.
AutoCAD SHX Text
13.0 AFTER SUBMITTAL APPROVALS AND PRIOR TO ORDERING OF ANY EQUIPMENT OR ACCESSORIES, OR BEFORE
AutoCAD SHX Text
FABRICATION AND/OR ASSEMBLY OF PIPING AND ANY DEVICES/COMPONENTS, THE CONTRACTOR SHALL ENSURE
AutoCAD SHX Text
THAT EVERYTHING HAS BEEN VERIFIED AT SITE AND COORDINATED WITH ALL OTHER DISCIPLINES AS TO
AutoCAD SHX Text
CONSTRUCTIBILITY AND MAINTAINABILITY OF THE EQUIPMENT AND UTILITIES. IF FOR ANY REASON, CONFLICTS
AutoCAD SHX Text
ARISE DUE TO CONTRACTOR'S FAILURE TO FOLLOW THE ABOVE OR HIS LACK OF DUE DILIGENCE, ALL REWORKS
AutoCAD SHX Text
AS NECESSITATED SHALL BE PERFORMED BY THE CONTRACTOR WITHOUT ADDITIONAL COST/CHANGE ORDER.
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
ADDITIONAL SCOPE OF WORKS FOR
AutoCAD SHX Text
THE EXISTING BUILDING:
AutoCAD SHX Text
1. DETAILED WORK REQUIREMENTS
AutoCAD SHX Text
1.1 SURVEY AND VERIFY THE EXISTING SITE CONDITION TO DETERMINE THE ACTUAL LOCATION OF THE
AutoCAD SHX Text
FOLLOWING :
AutoCAD SHX Text
a. FIRE PROTECTION MAIN PIPE LINE
AutoCAD SHX Text
b. ZONE CONTROL VALVE
AutoCAD SHX Text
1.2 IN CASE, THERE ARE OBSTRUCTION OR UTILITIES THAT MAY BE AFFECTED AND NEED TO BE RELOCATED,
AutoCAD SHX Text
DURING CONSTRUCTION. THIS SHOULD BE PART OF THE CONTRACTOR. FAILURE TO DO SO, SHALL MAKE
AutoCAD SHX Text
THE CONTRACTOR FULLY LIABLE AND RESPONSIBLE FOR ANY ABORTIVE WORKS AND OTHER INCIDENTAL
AutoCAD SHX Text
EXPENSES THAT MAY ARISE.
AutoCAD SHX Text
2. DEMOLITION AND RESTORATION WORK.
AutoCAD SHX Text
2.1 THE CONTRACTOR SHALL INCLUDE THE RESTORATION OF DAMAGED UTILITIES AND FINISHES (FLOOR, WALL
AutoCAD SHX Text
AND CEILING) AFFECTED DURING CONSTRUCTION.
AutoCAD SHX Text
2.2 THE CONTRCTOR SHALL SUBMIT SHOP DRAWINGS, MATERIAL SUBMITTALS FOR APPROVAL PRIOR TO
AutoCAD SHX Text
FABRICATION AND INSTALLATION AT SITE.
AutoCAD SHX Text
2.3 THE CONTRACTOR SHALL BE RESPONSIBLE IN COORDINATING WITH PROJECT CONSTRUCTION MANAGER
AutoCAD SHX Text
AND PGH OWNER FOR ANY OBSTRUCTION i.e. FIXTURE AND EQUIPMENT THAT NEED TO BE RELOCATED.
AutoCAD SHX Text
2.4 GOOD HOUSE KEEPING SHALL BE IMPLEMENTED BY THE CONTRACTOR.
1. THE USE OF CROSS FITTING IS NOT ACCEPTABLE. 2. THE USE OF NON-UL LISTED THREADOLET OR WELDOLET IS NOT APPLICABLE. 3. IF MECHANICAL CROSS TEE IS USED, RISER NIPPLE IS NOT NEEDED.
AutoCAD SHX Text
SCREWED TYPE FITTINGS FOR 50MM & SMALLERMECHANICAL GROOVED TEE FITTINGS FOR 65MMOR HIGHER.
AutoCAD SHX Text
MOUNTING PLATE
AutoCAD SHX Text
CLOSURE
AutoCAD SHX Text
25.4x12.7mm REDUCER TYPE INSTALLATION
AutoCAD SHX Text
RECESSED TYPE SPRINKLER HEAD
AutoCAD SHX Text
25 X 15 mmCOUPLING REDUCER
AutoCAD SHX Text
90 %%D ELBOW
AutoCAD SHX Text
RISE NIPPLE
AutoCAD SHX Text
BRANCH PIPE
AutoCAD SHX Text
DROP NIPPLE
AutoCAD SHX Text
19
AutoCAD SHX Text
100
AutoCAD SHX Text
150
AutoCAD SHX Text
200
AutoCAD SHX Text
75
AutoCAD SHX Text
4.8 x 32
AutoCAD SHX Text
4.8 x 32
AutoCAD SHX Text
4.8 x 32
AutoCAD SHX Text
4.8 x 32
AutoCAD SHX Text
6.4 X 32
AutoCAD SHX Text
6.4 X 32
AutoCAD SHX Text
6.4 X 32
AutoCAD SHX Text
4.8 x 32
AutoCAD SHX Text
FLAT BAR
AutoCAD SHX Text
LOWER
AutoCAD SHX Text
65
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
4.8 x 32
AutoCAD SHX Text
4.8 x 32
AutoCAD SHX Text
UPPER
AutoCAD SHX Text
15.9
AutoCAD SHX Text
25.4
AutoCAD SHX Text
12.7
AutoCAD SHX Text
FLAT BAR
AutoCAD SHX Text
12.7
AutoCAD SHX Text
ROUND BAR
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
ROUND BAR
AutoCAD SHX Text
BOTTOM OF SLAB
AutoCAD SHX Text
65 SCHEDULE 40 B.I. PIPE
AutoCAD SHX Text
FLEXIBLE OR RIGID TYPE COUPLING
AutoCAD SHX Text
PIPES JOINED W/ ROLL OR CUT GROOVE METHOD
AutoCAD SHX Text
GROOVE METHODS
AutoCAD SHX Text
ROLL GROOVE
AutoCAD SHX Text
CUT GROOVE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
P05-FP2-01
AutoCAD SHX Text
CROSSMAIN
AutoCAD SHX Text
END FLANGE
AutoCAD SHX Text
LAST BRANCHLINE OR (SPRINKLER HEAD) IN THE CASE OR BRANCHLINE