Sensors
EasySense
SNS010C
Ordering Information
Order Codes SNS010C,
12NC: 929001792613, 6NC: 525493
Full Product Name EasySense SNS010C
Electrical Information
Operating Voltage 10-28 VDC
Maximum Current Sink For 0-10V Control 10mA
Maximum Current Consumption From DC Power Supply 15mA
Sensing
Mounting Height 15 feet maximum
Detection Angle 120 degree
LED status indicator LED On: Occupancy detected
Environment and Approbation
Operating Temperature 0°C to 55°C
Agency Approbations UL, cUL
Warranty 5 years
Sensor Dimensions (mm)
Occupancy Sensing Coverage (ft)
Philips EasySense SNS010C Datasheet and Quick Install Guide The Philips EasySense SNS010C is an infrared bi-level occupancy sensor with
daylight harvesting capability. It is powered by the LED driver with Aux power supply
(12-24VDC) and provides control via 0-10V dimming. Different combinations of
lighting output and dimming profile can be configured using the eight dip-switches. It
also supports automatic daylight calibration with a patent-pending routine using the
electrical on-off switch for the light fixture.
Product DataAll specifications are typical and at 25°C Tcase unless otherwise specified.
Wiring Diagram The connection of the sensor to the LED driver is done with 4 wires 22AWG stranded and tinned
with 24 inches.
To view other product collaterals please scan the QR code.
Ø32.9 Ø23.1
Ø20.8
Ø24.8
56.7
41.
5
G1/2
17
G1/2
31.4
10’
0’
12’ 5’ 3’ 0’ 3’ 5’ 12’
Coverage Side View
15’
10’
5’
0’
5’
10’
15’15’ 10’ 5’ 0’ 5’ 10’ 15’
Coverage Top View
30’
LED driverViolet (Dim +)
Grey (Dim -)
Brown (Aux +)
Yellow (Aux -)
EasySense SNS010C
Maximum mounting use 15ft.
Recommended mounting use 8 - 12 ft.
The detection area for movement sensor can be roughly divided into two parts:
Minor movement (person moving < 3.0’/s or 0.9m/s)
Major movement (person moving > 3.0’/s or 0.9m/s)
© 2020 Signify Holding. All rights reserved. The information provided herein is subject to change, without notice. Signify does not give any representation or warranty as to the accuracy or completeness of the information included herein and shall not be liable for any action in reliance thereon. The information presented in this document is not intended as any commercial offer and does not form part of any≈quotation or contract,
unless otherwise agreed by Signify.
PLt-2002QG_EasySense SNS010C QIG 05/20 www.philips.com/easysense
Signify North America Corporation 200 Franklin Square Drive, Somerset, NJ 08873 Telephone 855-486-2216
Signify Canada Ltd. 281 Hillmount Road, Markham, ON, Canada L6C 2S3 Telephone 800-668-9008
Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.
Ø32.9 Ø23.1
Ø20.8
Ø24.8
56.7
41.
5
G1/2
17
G1/2
31.4
Configurable Parameters (Dip-switches)
Daylight Calibration Routine
Step-by-step for the electrical mains on-off switching routine for daylight calibration in the field.NOTE: The daylight calibration must be done when there is less or no sunlight in the area.
At the end (step 5) and after 3 seconds, the fixture light will blink three times to confirm the successful calibration of daylight sensing.
NOTE: If this confirmation blinks are not received, please restart the calibration process starting from Step 1.
ON
OFF
ON 20 secs
OFF until �xturelight is OFF
OFF until �xturelight is OFF
OFF until �xturelight is OFF
OFF until �xturelight is OFF
ON 3 secs ON 5 - 20 secs ON
Step 1 Step 2 Step 3 Step 4 Step 5
Step 1
Step 2 – Light ON for less than 3 seconds, Light OFF;
Step 3 – Light ON for more than 5 seconds but less than 20 seconds, Light OFF;
Step 4 – Light ON for less than 3 seconds, Light OFF;
Step 5 – Light ON.
> < ON 3 secs <
– Light ON for more than 20 seconds, Light OFF;
Task level Background level Hold time
Prolong time
Daylight Harvesting
3 4ON
OFF
70%80%90%100%
20%50%
6ON
OFF
Motion o�10 secs10 mins30 mins
1 2ON
OFF
5ON
OFF
DisableEnable
(Daylight sensor works during Hold time)
7 8ON
OFF
In�nite9 mins30 mins60 mins
Hold time(con�gurable)
Prolong time(con�gurable)
Switch-on sequence Switch-o� sequence
Time
Fix
ture
lig
ht
leve
l
Factory Defaults
*
*
*
*
*
*
secs - secondsmins - minutes
Task level(con�gurable)
Background level(con�gurable)
˜