06/10/2009 1 ALICE-PHOS Alexei.Kuryakin@cer n.ch PHOS Cooling status (1-6 Oct) Brief 28 Sep start cool down to 5°C (by cooling liquid) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical control valve) controller alarm raised due to battery fail (inside controller) Problem temporary fixed after 8 hours (switch ECV in manual control mode: work in non-optimal mode). Normal operation mode started after 3 days with battery alarm OFF (after some tests with controller). PHOS cooling now work in normal operation mode. Cooling liquid ~5°C, PWO ~7°C, FEE in 16÷20°C range, humidity in 10÷20% range. Liquid leak ~1 L per 5 days in PHOS-4.

Upload: len

Post on 13-Jan-2016

35 views

Category:

Documents


5 download

DESCRIPTION

PHOS Cooling status (1-6 Oct) Brief. 28 Sep start cool down to 5°C (by cooling liquid) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical control valve) controller alarm raised due to battery fail (inside controller) - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 1

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)Brief

28 Sep start cool down to 5°C (by cooling liquid)1 Oct at 5 Am cooling plant failure happened: ECV

(electrical control valve) controller alarm raised due to battery fail (inside controller)

Problem temporary fixed after 8 hours (switch ECV in manual control mode: work in non-optimal mode).

Normal operation mode started after 3 days with battery alarm OFF (after some tests with controller).

PHOS cooling now work in normal operation mode.Cooling liquid ~5°C, PWO ~7°C, FEE in 16÷20°C

range, humidity in 10÷20% range.Liquid leak ~1 L per 5 days in PHOS-4.

Page 2: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 2

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct) PHOS temperatures

ECV failure

Normaloperation

C6F14Temporaryoperation(manual mode)

FEE2 FEE3 FEE4

PWO2

PWO3

PWO4

Page 3: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 3

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)PHOS-2 humidity, 7÷15%

FEE2PWO2

%

Page 4: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 4

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)PHOS-3 humidity, PWO=20%, FEE=15%

FEE3

PWO3

%

Page 5: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 5

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)PHOS-4 humidity, PWO=12÷20%, FEE=15%

FEE3PWO3

This sensor looks strange,maybe damage?

Page 6: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 6

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)Liquid level going down, now 59 L

We have leak ~1 Liters per 5-6 days (inside PHOS-4, it seems)

Liquid filling

Page 7: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 7

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)Temperature of pump’s cover

Cooling plant have 2 pumps. 1st pump looks more “cold” (why?).During 1 Oct incident pump temperature raised up to 45°C.

Pump1 Pump2

Pumps works in “round-robin” mode to have equal resource (working time)

Page 8: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 8

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)Temperature of compressor’s cover

In normal operation mode cover have temp-re in 35÷58°C range.During 1 Oct incident compressor temp-re up to 70÷80°C.

Pump1 Pump2

In manual mode temp-re range more wide (20÷60 °C).

Compressors works in “round-robin” mode to have equal resource (working time)

Interlock on compressor’s cover temperature should be added to control software

Compressor-1

Compressor-2

Compressor-3

Compressor-4

Normal mode

Manual mode(not optimal)

Incident 1 Oct

Page 9: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 9

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct) What is ECV controller

Page 10: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 10

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct) ECV controller failure

Alarm: Battery failure

Page 11: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 11

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct) ECV controller problem fixed now

Battery Alarm switched OFF

as tests with controller show,

controller can work without battery if

battery alarm is OFF

Page 12: PHOS Cooling status (1-6 Oct) Brief

06/10/2009 12

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1-6 Oct)To Do

• ECV controller alarm signal should be connected to cooling control system

• Some additional program (software) blocking (interlocks) should be added

• Some investigations should be done to find optimal and fault-safe parameters of cooling control software

• Documentation should be updated after this changes

• PHOS-4: to be or not to be…After this will be done, we are ready to cool

down to -25 (?) It will takes about 2-3 weeks (?)