Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

PID and PIDE Getting Started Guide for ControlLogix and CompactLogixBruce KyerRA Technical Support Engineer

Page 2: PID ROCKWELL

Conference Call Information

US Dial 866-774-1453 Conference ID: 25089971

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 2

Page 3: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 3

Agenda

1. Introduction

2. Parameter Overview

3. Demos

Page 4: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 4

Adding the Ladder PID and Tags

• Enter the following for the ladder PID:

A backing tag of type PID for

internal storage

The tag that holds the PV value

The output tag that you’ll use to drive the process

(CV)

A Tag for operator manual control if desired, or leave

0 if not used

These are display values from PID backing tag

Set these three fields to zero if you don’t use them

Page 5: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 5

Configuring the PID - Scaling Tab

Engineering units: This is what the setpoint is

specified in and what the status below uses.

Unscaled Min/Max: This should match the range

from the input card

The range the PID will use for its output

This is the range the Tieback tag will use

If you change while the processor is running, you

must uncheck this box once

Page 6: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 6

Configuring the PID - Alarms Tab

• The PID has built-in alarming.– Can be used by the program to indicate that the PV is out of range.– Is not essential for PID operation - does not have to be used.

Specify alarm limit values if desired, or leave all 0 if

you don’t use.

Page 7: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 7

Configuring the PID - Configuration Tab

Choose independent or dependent equation form.

This affects tuning.

Choose the Control Action

PV–SP or SP-PV

Choose Derivative of PV or Error

Enter the desired Loop Update Time

Enter Deadband value. Freezes CV when PV is “close enough”. Can save on valve wear or help stabilize system. Leave 0 if not used.

Additional Options

Enter a range to limit the CV to. Enter 100

and 0 for no limit

Page 8: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 8

Configuring the PID - Tuning Tab

Setpoint is what the PID tries to drive the PV to.

Output bias, also known as feedforward, is directly added to the output.

Manual mode feeds the Tieback tag directly

to the PID output.

Enter the PID gains here. These numbers can be

adjusted to tune the loop.

Current values and status to monitor PID state.

Use Set Output to directly control the output when software manual is

checked.

Page 9: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 9

Adding the Ladder PID - Timing

• The Ladder PID is not self-regulated (timed). – Needs to be regulated with Timer or Periodic Task, otherwise, output will be wild.– PID should only be executed as fast as process needs to conserve CPU resources.– The period at which the PID is scanned true should be filled into the Loop Update

Time. Programmer must make sure that this is filled in manually or update programmatically PID_Backing_Tag.UPD.

Page 10: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 10

Adding a Function Block PIDE and Tags

• The Function Block PIDE Connect process measurement tag

Connect a tag for manual output

control

Set True for Program Control

Connect the process control tag

Set for the mode desired

Connect a tag for setpoint

Page 11: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 11

Configuring the PIDE – EUs/Limits Tab

Specify the range for CVEU to use (the PIDE

output).

Engineering units. This is the range the PV and SP

use. The PV input is assumed to be in EU.

Make sure status says “OK”

Limits the CV and SP to a sub-range. Make sure this

is filled in after setting scaling. Typically, SP limit

is same as PV.

Page 12: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 12

Configuring the PIDE – General Config Tab

Specify the gains.Usually best to leave mode periodic. In

that case, PIDE will regulate itself.

Choose control action and equation

type

More advanced settings, can normally

leave alone.

Page 13: PID ROCKWELL

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 13

Demos

• PID

• PIDE