plans7
TRANSCRIPT
Location Plan
scale 1:500 @ A3
Lot 1 DP 22526
GENERAL NOTES:
All work must be carried out to conform to
relevant sections of the New Zealand Building
Code and New Zealand Standards - in particular
NZS: 3604, NZS: 3602 & NZS: 4218.
All references to standards shall be taken as
reference to the latest revision including
amendments.
Ground bearing must be reconfirmed on site
following excavation but prior to placing
concrete and reinforcing.
Confirm site boundary's with survey. Fences
may not necessarily be on the legal boundary.
All work to be carried out to best trade practice.
Do not scale off building consent documentation
issued from TA's as the plans may have been
scanned and the scale distorted.
All habitable rooms to have 5% of their floor
area as opening windows or approved
alternative to achieve ventilation requirements.
WINDZONE high
The wind zone classification is to be confirmed
by all suppliers/manufacturers of any building
components to which this information is relevant,
prior to the design, fabrication / manufacture or
supply of any element to ensure full compliance.
DURABILITY : Zone C
Check NZS: 3604 - section 4 durability
for component selection.
Selected material shall be checked for
compatibility - see table 4.1,4.2, 4.3 -NZS:
3604:2011
WATER SUPPLY
Pipework generally in polybutylene
installed to the manufacturers
installation code of practice, use
standard connectors. Reticulation with
in house to be via ceiling void. Both
hot & cold water pipes to be tested to
1500kpa.
All hot/cold water branches to extend
via the ceiling void to the stud nearest
the fitting & dropped down to the
fitting. Clip to side of stud. Use (min) 2
no. clips per drop.
FITTINGS / FIXTURES
The plumber shall obtain & make
themselves familiar with the suppliers
current printed specification for all
fittings / fixtures as per schedule
agreed with builder / owner.
Where any fixture / fitting is not
suitable for the application or
intended, or requires the modification
of the structure to allow the correct
installation the plumber shall bring this
to the attention of the builder for
correction.
CLADDING NOTES:
Cladding to be installed to manufacturers
requirements in particular, fixing and ground
clearance.
Building wrap and window sealing systems to be
installed to manufacturers specifications and in
accordance to NZBC E2/AS1
Exposed metal flashings to be colorsteel and
colour matched to the cladding final colour. Metal
flashings to comply with the durability
requirements of section 4 NZS: 3604 & table 20
NZBC E2/AS1.
Sealants to be colour matched to the coatings.
Use manufacturer approved sealants only.
Windows to be installed with WANZ sill flashings
and support brackets as necessary.
Ensure all cut edges are sealed with approved
and compatable sealant before installing.
Provide control joints as specified by
manufacturer.
ALL NOTES TO BE READ IN CONJUNCTION WITH DRAWINGS AND SPECIFICATION
CARPENTRY/ FRAMES
Timber framing grade shall be SG8 pine min unless stated.
Allow for all incidentals required for 1st class result.
All frames to comply with NZBC E2/AS1, NZS: 3604, NZS:
3602, local authority bylaws & engineering requirements.
Verify all beam, stud, rafter & other member sizes to
confirm full compliance with NZBC B1/AS1, NZS: 3604.
Provide copies of all warrentees/producer statements
required to the local authority for code compliance
certification with the building code.
Insulate walls/ceiling voids, ensure full compliance to
NZS:3604.
Exterior walls - R2.8 insulation
Ceiling voids- R3.6 insulation
Pre-nailer to supply certification with NZBC & E2/AS1 &
NZS: 3604, NZS: 3602 for all roof trusses. supply
certificate to council, copy to designer, itemising full
compliance, job address & client details prior to fabrication.
Generally exterior framing to be 90x45 h3.1 at 400 crs.
Interior framing to be 90x45 h1.1 at 600 crs (400 crs to
load bearing int. walls) unless specified.
TIMBER TREATMENT
All treatment to comply with NZBC E2/AS1, NZS: 3604,
NZS: 3602 timber wood based products for use in building.
building element minimum treatment
Roofs including;
roof framing, trusses, ceiling joists H1.2
Sarking, enclosed flat roof framing H3.1
& associated supporting framing, valley boards,
boards supporting flashings/box gutters/flashing
penetrations/upstands to roof decks
Timber walls including;
interior wall framing
H1.2
Exterior walls H1.2
Any internal at risk framing, i.e. around
bathrooms H3.2
Prenailer to confirm against NZS: 3602:2003 requirements
The contractor is to be fully conversant with codes &
regulations, if in doubt refer to the codes stated. if in any
doubt ask & obtain further details.
FOUNDATION NOTES
All construction to comply with NZS: 3604,
NZBC and best possible trade practices.
All concrete to be 25mpa min or as per engineer
All reinforcing steel to be grade 500 min or as
specified by the engineer.
MINIMUM FINISHED FLOOR HEIGHT
Protected ground or permanent paving
- 150mm
Unprotected ground
- 225mm
Heights as per NZS: 3604 section 7
TOP PLATE FIXING
The fixing of top plates supporting roof trusses to wall
studs or lintels shall be in accordance with table 8.18, NZS:
3604:1999
Joints in top plates to comply with clause 8.7.3 & figures
8.14-8.16, NZS: 3604:1999
INTERNAL LININGS
Walls:
Generally - 10mm standard Gib board
Bathrooms & laundry - 10mm Gib Aqualine
Ceilings:
Generally - 13mm Gib Standard
Bathrooms - 13mm Gib Aqualine
Back block sheet joints and allow for control joints as
required by manufacturer.
Moulding:
Skirting - to match existing
Scotia - to match existing
DRAINAGE PLAN NOTES:
All plumbing and drainage to be in accordance with
AS/NZS: 3500 part 2.2 for ground floor systems
and for single stack systems.
Plumber/drainlayer to fill out producer statement
and return to council with an as built drainage plan.
Check PIM information for service connections.
Pipes to be inspected before covering with sand.
Builder to ensure that proposed floor level will allow
satisfactory fall of drains to main connections.
Pipe gradients
Minimum grades for drains and discharge pipes.
65ø & less = 1 in 40
80ø & 100ø = 1 in 60
Hot & cold water
All pipe work in house to be polybutylene.
20mm for main, to bath and to hwc
15mm to all other branches
15mm to exterior taps
Selected hot water system installed internally to
residence to manufacturers details. Allow to
provide overflow to extract externally.
Notes
Zone B and C
Locations - Exposed = open to weather (incl wetting by rain)
Sheltered = open to air but not rain (eg sub floor)
Closed = dry internal location
Fastener Location Material
All connections within All Stainless steel
600mm of ground
Other structural fixings more Exposed Stainless steel
than 600mm above ground
Nail plates, wire dogs & Closed Galvanised
bolts not included above
All fixings in contact with CCA Sheltered & Stainless steel
treated timber (incl nails) exposed
All fixings in contact with CCA Closed Galvanised
treated timber (incl nails)
Nails to non CCA framing Sheltered & Galvanised
exposed
Nails to non CCA framing Closed Mild steel
Nails to cladding Exposed Stainless steel
Note: See NZS3604:2011 for requirements if ACQ or CuAZ
preservatives area used
REFER TO NZS 3604:2011 SECTION 4, 'DURABILITY'
Proposed addition
Proposed garage
Proposed concrete courtyard
Proposed Site Plan
scale 1:200 @ A3
68 m²
Footpath
Karori Road
122 m²
Proposed timber retaining wall -
less than 1.5m height
Portion of existing
retained building
Existing Site Plan
scale 1:200 @ A3
Remove existing
garage
Remove existing
lean-to structure
Footpath
Karori Road
Portion of existing
retained building
12 m²
122 m²
Lot 1 DP 22526
0.0715 ha site area (715m2)
Existing Building 122.011m²
Proposed Addition 67.966m²
Proposed Garage 48.000m²
Site Coverage = 33.56%
bedroom 3
laundry
dining lounge
kitchen
bedroom 2
bathroom
master bedroom
hall
porch
w/r
w/r
sto
re
co
ats
carpet
carpet carpet
carpet
carpet
carpet
timber
timber/tiles
wc
timber
hall
timber
timber
retaining w
all
retaining w
all
fence
fence
Remove existing steps
and retaning wall
Remove existing
timber floor to reuse
Remove fireplace new
window to opening
Remove all existing
laundry fittings
Remove windows
Remove existing wallExisting wall
Remove windows
Remove all existing
bathroom fittings
key
Remove window to
be reused in kitchen
Existing Floor Plan
scale 1:100 @ A3
Remove existing
lean-to structure
Existing timber arch
feature to remain
Reuse door as D10
Allow to remove
kitchen joinery for
resale
Remove existing garage
notes
1 where linings are removed from existing
exterior walls insulate cavities to
match new walls
2 builder to ensure all work is sufficiently
propped & supported during demolition
and construction
3 Retain all character features where not
affected by demolition and replacement work
4 Carefully remove all existing architraves,
skirtings, cornices and panelling for possible
reuse
dining lounge
bedroom 2
master bedroom
hall
porch
carpetcarpet
carpet
carpet
hall
timber
timber
fence
fence
3965
6386
1090140
100
90
90
8600
3067
90
1990
90
600903526
3241
1000
861
1200
90
90
90
975
90
1000
90
1000
D1
W1
W2
W3
140x90 L 140x90 L
D3
D4
D5D6
D7
90x90 L90x90 L
bedroom 3
carpet
bedroom 4
carpet
hwc
Removed walls
New walls
Existing walls
Make opening to
match lounge
D8
D9
D10
D12
D11
D13
D14
D15
D16
5636 C.O.S.
90 90
bathroom
timber
bathroom
timber
wr
carpet
wr
carpet
store
store
carpet
kitchen
timber
family
room
timber
hall
carpet
laundry
timber
wr
carpet
wr
carpet
D2
timber
key
W4
W5
FFL 53.15
Window replaced with
extg kitchen window
140x90 L
Beam over (Eng.)
140x90 L
Proposed Floor Plan
scale 1:100 @ A3
Courtyard
concrete
140x90 LW6
S1S2
Custom toughened safety
glass screen around shower
140x90 L
923
1550
1962
1040
1104
5066
140x90 L
sink
90
1333 1040 2498 1040
1018 1040
Beam
over (E
ng.)
FFL 53.10
S3
Verandah beam
over
(E
ng.)
dining
bedroom 2
master bedroom
hall
carpet
carpet
D1
W1
W2
W3
D3
D4
D5D6
D7
bedroom 3
carpet
bedroom 4
carpet
hwc
D8
D9
D10
D12
D11
D13
D14
D15
D16
bathroom
timber
bathroom
timber
wr
carpet
wr
carpet
store
store
carpet
kitchen
timber
family
room
timber
hall
carpet
laundry
timber
wr
carpet
wr
carpet
D2
timber
W4
W5W6
S1S2
sink
S3
3067
3965
100
90
90
3241
1000
861
1200
90
90
90
975
90
1000
90
923
1550
1962
1040
1014
348
338
3280
140
199090600903526
1000
90
1333 1040 2498 1040
998 90
1090140 90 8600
5066
1018 1040
90
500
100
90
782090 90
Proposed East elevation
scale 1:100 @ A3
W3
W4
DP
Spouting to match existing
Timber framed windows to
match existing
Timber piles foundation behind
timber weatherboards
S3
Proposed West elevation
scale 1:100 @ A3
W6W5
S1
S2
140x19 H3.1 Treated
painted coverrboards
Proposed South elevation
scale 1:100 @ A3
W2W1
D1
DP DP
H3.1 Treated painted timber
weatherboards with bevel-beck
profile to match existing
Fix over breathable building
wrap to H1.2 treated framing
140x19 H3.1 Treated
painted coverrboards
Additions and Alterations
Lot 1 DP 22526
381 Karori Road, Karori, Wellington
Karori, Wellington
V/E HIGH
MEDIUM
LOW
HIGH
E2/AS1 : Building Envelope Risk Matrix.
Project Details.
Name
Street/No.
Lot/DP/No.
City/Town/District.
Definition of Risk [table 1 from E2/AS1]
Factor Risk Detail
Wind Zone
A
V.HIGH
MEDIUM
LOW
HIGH
B
V.HIGH
MEDIUM
LOW
HIGH
MEDIUM
LOW
HIGH
Roof / Wall
V.HIGH
MEDIUM
D
V.HIGH
MEDIUM
LOW
HIGH
Envelope
E
Deck design.
F
C
intersection
Design.
Complexity
VERY / EXTRA HIGH wind zone as described by NZS 3604
MEDIUM wind zone as described by NZS 3604
LOW wind zone as described by NZS 3604
HIGH wind zone as described by NZS 3604
More than two storey's
Two storey in part
One storey
Two storey's
Roof elements finished within the boundaries formed by
Roof / wall intersection - Partly exposed.
Roof / wall intersection - Fully protected.
Roof / wall intersection - Fully exposed. [eg. Parapets
exterior walls [eg. lower ends of aprons, chimney's etc.]
[eg. hip / gable roof with NO eaves.]
[eg. hip / gable roof with eaves.]
or eaves greater than 90° vertical with soffit linings.]
0 -100mm at first floor level, or 100-450mm at second floor level
450 - 600mm at first floor level, or 600mm at second floor level
Greater than 600mm at first floor level.
100-450mm at first floor level, or 450-600mm at second floor level
or 450 - 600mm at third floor level
LOW
As for high risk, but with junctions not covered in C or F on this Table
Complex angular or curved shape [eg. Y or arrow head]
More complex angular or curved shape [eg. Y or arrow head ]
Simple rectangular,L,T, or boomerang shape with single cladding type
with multiple cladding type.
HIGH
with single cladding type.
[eg. box windows, pergola's, multi storey re - entrant shapes etc.]
Enclosed deck exposed in plan or cantilevered at second floor level
Fully covered in plan by roof, or timber slat deck attached
None or timber slat deck or porch at ground level
Enclosed deck exposed in plan or cantilevered at first floor level
at first or second floor level.
or above.
NOTES
Risk Severity by Face
Selected Cladding Resulting from Risk Assessment
Cladding Selected from table 3
North
Risk score
from tables
above.
South
East
[ from tables on page 30 E2/AS1 ]
NA
DIRECT
FIXED
DRAINED
CAVITY
TICK SELECTED OPTION
5
5
No. of
storey's
Eaves width
(1.)
1. Eaves width measured from external face of the wall cladding to
outer edge of overhang including gutters and fascias
V.HIGH
A
B
D
E
F
C
-
A
B
D
E
F
C
A
B
D
E
F
C
South
Wind Zone
No. of storey's
Roof / Wall
intersection
Eaves width.
Envelope
Complexity
Deck design.
as NZS 3604
RISK
FACTOR
0
0
0
0
0
0
1
1
1
1
2
0
2
3
2
3
4
1
4
5
5
6
6
2
Total Risk Score for this Elevation
0
0
2
0
2
1
5
LOW Sub totals
for each
risk factor.
Score MED HIGH V.HIGHScore Score Score
East
Wind Zone
No. of storey's
Roof / Wall
intersection
Eaves width.
Envelope
Complexity
Deck design.
as NZS 3604
RISK
FACTOR
0
0
0
0
0
0
1
1
1
1
2
0
2
3
2
3
4
1
4
5
5
6
6
2
Total Risk Score for this Elevation
0
0
2
0
0
1
3
LOW Sub totals
for each
risk factor.
Score MED HIGH V.HIGHScore Score Score
West
Wind Zone
No. of storey's
Roof / Wall
intersection
Eaves width.
Envelope
Complexity
Deck design.
as NZS 3604
RISK
FACTOR
0
0
0
0
0
0
1
1
1
1
2
0
2
3
2
3
4
1
4
5
5
6
6
2
Total Risk Score for this Elevation
0
0
2
0
2
1
5
LOW Sub totals
for each
risk factor.
Score MED HIGH V.HIGHScore Score Score
West
3
Bevel-back timber weatherboards - to match existing
Bevel-back timber weatherboards - to match existing
Bevel-back timber weatherboards - to match existing
Concrete foundation to
garage floor refer detail
Ex 200x25 Fascia to
garage refer detail
D18
Garage North elevation
scale 1:100 @ A3
DP
Sectional slide over
garage door
Garage West elevation
scale 1:100 @ A3
DP
H3.1 Treated painted timber
weatherboards with bevel-beck
profile to match existing
Fix over breathable building
wrap to H1.2 treated framing
DP
Spouting to match existing
140x19 H3.1 Treated
painted coverrboards
D1
W1W2
17 C.O.S.
27
50
140x45 Ceiling joists @ 600 ctrs
Section aa
scale 1:50 @ A3
bedroom 4 bedroom 3 family room
17 C.O.S.
H1.2 Trusses @ 900 ctrs
designed by manufacturer
BO
UN
DA
RY
45
0 M
IN
H1.2 SG8 190x45 Floor joists
@ 400 ctrs
125x125 Piles @
1650 ctrs (max)
45°
Solid blocking midspan
R3.6 Insulation
Outline of skylight
shaft behind
450mm (Min) Crawl space to
underside of joists
90x45 Dwangs @ 1350
ctrs (max)
90x45 Framing @ 400 ctrs
R2.8 Wall insulation
H3.1 Treated painted timber
weatherboards with bevel-beck
profile to match existing
Fix over breathable building
wrap to H1.2 treated framing
D3D4D8D12
Section bb
scale 1:50 @ A3
laundry store bedroom 3
45
0 M
IN
20
0 M
IN
10
0 M
IN
140x45 String M12 bolt
to extg @ 1200 ctrs
190x90 Bearers
90x45 Dwangs @ 1350
ctrs (max)
90x45 Framing @ 400 ctrs
R2.8 Wall insulation
Line of extg roof
24
10
22
5
Section cc
scale 1:50 @ A3
garage
BO
UN
DA
RY
17 C.O.S.
45°45°
W7
90x45 purlins on flat
@ 900 ctrs
H1.2 Trusses @ 900 ctrs
Solid blocking midspan
H1.2 SG8 90x45 verticle
framing over end truss
to form abutment
Gable end detail
scale 1:10 @ A3
Horizontal weather board
to base of Abutment
Corrugated colorsteel roofing on
roof underlay and galv netting
Bevelback weather boards over
building paper to match existing
house
45 x 19mm eaves mould with 6
x 6mm weathergroove fitted
tight up against soffit lining
Ex 150x25 Fascia
Tongue and groove soffit
painted with profile to match
existing
Internal linings
as specified
R3.6 Insulation
H3.1 SG8 treated and painted
90x45 outriggers @900 ctrs over
gable end truss to form eaves
framing
Corrugated colorsteel
roofing on roof underlay
and galvenised netting
H1.2 SG8 90X45 Purlins
@900 ctrs
Bevelback weather boards over
building paper to match existing
house
45 x 19mm eaves mould with 6
x 6mm weathergroove fitted
tight up against soffit lining
H1.2 Exposed outriggers @
900 ctrs to match existing
house
Ex 200x25 Fascia
Tongue and groove soffit
painted with profile to
match existing
Spouting to
match existing
H1.2 Trusses @900 ctrs
Garage eaves detail
scale 1:10 @ A3
355
355
355 E
AV
ES
T
O M
AT
CH
E
XIS
TIN
G C
.O
.S
.
355
355
Make good existing
opening to chimney
New roof 17° to match
existing pitch c.o.s.
Exisiting roof outline.
Building outline.
New roof 17° to match
existing roof pitch c.o.s.
355 355
New spouting to roof
DP
DP
DP
DP
No change to balance of
roof
S1S2
S3
Corrugated colorsteel laid over
roof underlay and galvansied
netting
Corrugated colorsteel laid over
roof underlay and galvansied
netting
New concrete path
New reinforced concrete slab
to garage 100mm thick slab on
dpm 20mm sand blinding and
150mm hardfill as per 3604
7988
Allow 6mm overhang to studs
5988
Ramp up exposed
aggregate concrete
driveway to garage ffl
Existing house
766
7
6
6
4167
500e Mesh to concrete floor
5642
1200
1200
Confirm path setout onsite
as landscaping design
Slab Plan
scale 1:100 @ A3
Roof Plan
scale 1:100 @ A3
Existing floor
H1.2 S
G8 190x45 F
loor joists @
400 ctrs m
ax
Anchor pile
H1.2 SG8 190x45
joists @ 400 ctrs
140x45 stringer M
12 bolt to extg @
1200 ctrs
190x90 bearers
H5 125x125 P
iles @
1650 ctrs m
ax
Anchor piles
Anchor pile
Continuous blocking midspan (not shown
for clarity)
140x45 stringer M
12 bolt @
1200 ctrs
3006 3131125125
1520
125
125
1458
125
1458
125
1522
125
1235
125
1262
125
1200
125
Confirm condition of existing edge piles
and bearers onsite in regards to
suitability of stringer
Replace existing if in poor condition or
add in additional row of piles at edge for
new floor joist support
Floor Framing Plan
scale 1:50 @ A3
Existing house
100
min.
CGL
Earthquake
Wind
Bracing units
120
160
Bearers must not be joined at an anchor pile.
CGL = Cleared ground level.
See section 4 for durability requirements.
Connection for ordinary pile similar.
M12 bolt with 50 x 50 x 3 mm
washers connecting pile to
bearer (see 6.9.3)
Pile (see 6.4)
Bearer
400 min. dia. or
350 square min. x 100
thick concrete footing
(see 6.4.5.5)
6 kN joist / bearer
connection to each
side of pile to give
resistance in 2
directions
(see 6.9.3)
Solid blocking
@ 1800mm crs
Joist
300 min. (150 if DPC
used between pile
and bearer
(see 6.4.1.1(c))
1000
100 min.
600 max. CGL to
centre of fixing
(see 6.4.1.1(b)(iii))
NOTE -
(1)
(2)
(3)
(4)
300 max.
offset
A1.03
anchor pile
scale N.T.S
H1.2 Trusses @ 900 ctrs
H3.1 SG8 90x45
Outriggers @ 900 ctrs
Building outline Existing roof
Roof Framing Plan
scale 1:50 @ A3
Trimmers to skylights
as per detail
Beams under
suporting extg roof
Lintel under suporting
extg roof
Verandah beam
under by Eng.
FIXINGS SCHEDULE table 2.2 and 2.4.4.1 NZS 3604:2011
Type Description Alt fixing capacity (kN)
E 2/ 90x3.15 skew nails + 2 wire dogs 4.7
F 2/ 90x3.15 skew nails + strap fixing 7.0
S 2/ 90x3.15 gun nails 0.8
T 1/ 10g self-drilling screw, 80mm long 2.4
U 1/ 14g self-drilling srcew, 100mm long 5.5
Refer to NZS 3604:2011 Section 2 'General'. also refer to Table 2.2.
Refer to NZS 3604:2011 Section 4 ' Durability'. also refer to Table
4.1, 4.3.
Refer to NZS 3604:2011, 4.4.4 - copper based timber preservative
Note: capacities are associated with fixing type, not fasteners. See
individual selection tables for the appropriate fixing type for the
application.
Move switch to extg light
Move switch to
extg light
Wall mounted extraction fan
Ducted extraction
fan vented to roof
Rangehood extraction fan
Electrical Plan
scale 1:100 @ A3
GENERAL NOTES FOR ADDITIONS AND
ALTERATIONS - electrical
All notes to be read in conjunction with drawings
and specification
Contractor to confirm existing main switch board
and distribution board comply with current
standards. allow to modify/replace as required.
Allow for, as required, changing of light switches to
other side of door, when it is re-hung on other side.
Allow for reposition of light switch/s if wall that
switch is in is modified/removed.
Electrical drawings are indicative only. Refer to
client for final electrical requirements and setout.
Electrician to ensure work is carried out to comply
with current standards and the Electricity (Safety)
Requlations 2010
Contractor to allow for blocking, as required by
selected fittings. refer to client and Electrician for
selected fittings and their requirements and
specification.
All dryers to have separate extract vent thru external
wall of roof eaves.
Allow to reposition any alarm sensors, heat sensors,
smoke detectors etc, that are effect by proposed
changes, as required.
Allow to remove/re position existing power outlets
as required.
ELECTRICAL LAYOUT IS INDICATIVE ONLY
ELECTRICIAN TO CONSULT WITH CLIENT TO
CONFIRM EXACT LAYOUT AND FITTINGS
SELECTION BEFORE TENDER OR
CONSTRUCTION
Automatic garage
door switch
3280
22
00
D1 family room
FFL
window and door schedule
scale 1:50 @ A3
14
00
ma
tch
e
x sill
14
00
ma
tch
e
x sill
1550 1040
W1 bedroom 3
W5 dining
W2 bedroom 4
W3 bedroom 4
W4 bathroom
W6 kitchen
10
00
530
2060
10
00
W7 garage
FFL
D2, D3, D5h, D6,
D7, D8, D9, D11,
D17h
h = handed
850
20
00
1660
20
00
850
20
00
D12
700
20
00
D13
450
20
00
20
00
D14
20
00
850
10
00
600
S1 family room
S2 kitchen
S3 laundry
20
00
20
00
850
D17D4
Glazing
Double glazed
Double glazed Double glazed
Single glazed Double glazed
H3.1 treated painted timber joinery H3.1 treated painted timber joinery Velux Aluminum Skylight
New hardwood door
to match existing
New hardwood
panel door to
match existing
Painted mattPainted pine profiled
panel doors
Painted pine profiled
panel doors
Window and doors viewed from exterior
Windows to be DOUBLE GLAZED. Glazing to conform to NZS 4223:Part
3:1993, NZS 3604, NZS4203, NZS 4211.
All glazing to comply with human impact standards
All dimensions shown are to overall frame opening size - unless otherwise
stated.
All dimensions to be checked on site.
Window subcontractor is responsible for ensuring that all window and or door
components fit the structure and are appropriate for the overall opening size
Main contractor to ensure that all rough openings are correct as per details and
drawings. All discrepancies shall be pointed out to the Architect for clarification
before manufacturing
WINDOW AND DOOR NOTES
Window sub-contractor is to confirm hardware to be installed as part of
quote. (refer to hardware section in the specification)
Window and door installation including flashings to be in accordance with
construction details.
DOOR SCHEDULE
DOOR HUNG WIDTH HARDWARE NOTES
D1 BIFOLDING 3280 GLAZED
D2 LH 810
D3 LH 810
D4 DOUBLE 1620
D5 RH 810
D6 LH 810
D7 LH 810
D8 LH 810
D9 LH 810
D10 RH 810 Reuse existing door refer demo plan
D11 LH 810
D12 RH 660
D13 RH 410
D14 LH 810
D15 CAVITY SLIDER 810
D16 CAVITY SLIDER 810
D17 RH 810
D18 ROLLER DOOR 4800
bevel-back weatherboard
- profile to NZS 3617
wall underlay dressed into
opening with flexible flashing
tape over underlay at corners
head flashing with 15° fall,
stop-ended and extended 20
mm min beyond outer edge of
jamb
internal lining as specified
timber window head to NZS
3610
50 mm cladding cover
15° min
downturn on flashing
over-folded to fit tight to head
FLASHING DIMENSIONS
jamb facing and scriber
notched over head flashing
and fitted to underside of
weatherhead
weatherhead fixed over
weatherboard - shape to shed
water with drip to bottom edge
and thicker than jamb facings
by 6 mm min profile to match
existing
air seal over backing rod
10 mm stop-end
additional underlay or flexible
flashing tape lapped over
flashing
5
m
m
g
a
p
10 m
m m
in
full width sill tray flashing with
20 mm stop-ends
wall underlay dressed into
opening with flexible flashing
tape full width of sill turned up
100 mm at corners
bevel-back weatherboards -
profile to NZS 3617
sill board
timber trim to match
existing profile
continuous packing to
form air seal
internal lining as
specified
framing
sill to NZS 3610
to suit sill
angle to suit sill
FLASHING DIMENSIONS
line of jamb facing and scriber
5 mm kick-out where flashing
is left exposed (not covered
by sill facing)
sill flashing with 20 mm
stop-end
line of continuous
jamb packer
hem to back edge
35 m
m m
in flashing cover
H3.1 scriber
H3.1 treated and painted
bevel-back weatherboard -
profile to NZS 3617
timber jamb - profile to
NZS 3610
internal lining as specified
wall underlay dressed into
opening with flexible flashing
tape at corners
line of weatherhead and head
flashing over
line of sill flashing extending
to trimming studs
90 x 19 facing
19 mm min continuous
jamb packer
air seal over backing rod
line of head flashing extended
20 mm beyond outer edge of
jamb
line of sill
20 m
m
bevel-back weatherboard
- profile to NZS 3617
wall underlay dressed into
opening with flexible flashing
tape over underlay at corners
head flashing with 15° fall,
stop-ended and extended 20
mm min beyond outer edge of
jamb
internal lining as
specified
architrave to match
existing profile
timber door head to
NZS 3610
FLASHING DIMENSIONS
jamb facing notched over
head flashing and fitted to
underside of weatherhead
weatherhead fixed over
weatherboard - shape to shed water
with drip to bottom edge and thicker
than jamb facings by 6 mm min
profile to match existing
air seal over backing
rod
additional underlay or flexible
flashing tape lapped over
flashing
50 mm cladding cover
15° min
downturn on flashing
over-folded to fit tight to head
10 mm stop-end
5
m
m
g
a
p
10 m
m m
in
window head
scale 1:5 @A3
window jamb
scale 1:5 @A3
window sill
scale 1:5 @A3
door head
scale 1:5 @A3
H3.1 treated timber
window double glazed
paint finish
H3.1 treated timber
window double glazed
paint finish
H3.1 treated timber window
double glazed paint finish
H3.1 treated timber
door double glazed
paint finish
Painted pine architrave to
match existing profile
Corrugatd colorsteel roofing on
building paper to match existing
90X45 Purlins @900 ctrs run
between trusses
Bevelback weather boards over
building paper to match existing
45 x 19mm eaves mould with 6 x 6mm
weathergroove fitted tight up against
soffit lining
H3.2 Exposed outriggers @
1200 ctrs to match existing
Ex 150X25 Fascia
Tongue, groove and vee soffit
lining
Spouting to match
existing
Trusses @1200 ctrs
50
Eaves detail
scale 1:5 @ A3
2
0
0
Corrugated Colorsteel roofing on
building paper to match existing
2
0
0
Stop ends
Colorsteel ridge flashing
Soft edge to ridge flashing
90X45 Purlins @900 ctrs
Ridge detail
scale 1:5 @ A3
Bevelback weatherboard
DPC
Wall underlay
Wall plate to overhang slab edge by
6mm min
Base board to finish 50mm min
below floor level (and 175mm above
finished ground level or 100mm
above paving)
Bevelback base board
Internal lining
D12 Rod
DPM over 20mm sand blinding
150mm hardfill
22
5m
m
100MM Concrete slab
M12 Holding down bolts
@900 ctrs
165mm
10
0m
m
500e mesh 30mm cover
(min)
75
mm
D12 Rod 75mm cover
75mm
R10 @ 600 ctrs
Garage foundation
scale 1:5 @ A3
Corrugatd colorsteel roofing on
roof underlay and galv netting
H3.1 Painted exposed
outriggers @ 400 ctrs to
match existing
Bevelback weather boards over
building paper to match existing
45 x 19mm eaves mould with 6 x 6mm
weathergroove fitted tight up against
soffit lining
Ex 150X25 Fascia
Flashing to cover
two corrugates min
90X45 Packing
Tongue, groove and vee soffit
lining painted with profile to
match existing
70
Gable end detail
scale 1:5 @ A3
proprietary bath
installed to
manufacturer's
recommendations
silicon sealant
ceramic tiles
waterproof membrane
silicon sealant or
tile edge bead
gib Aqualine
5 - 1
0
gib Aqualine
ceramic tiles
waterproof membrane
required prior to tiling
tap body
silicon sealant
Note:
where impact noise from pipes is an issue
fix all pipes on resiliant brackets
silicon sealant required
see bath manufacturer's details
gib Aqualine
waterproof membrane
ceramic tiles
aluminium trim
impervious finish
silicon sealant between
basin and wall
basin top
silicon sealant
silicon sealant
ceramic tiles
gib Aqualine
acrylic liner over
unsealed gib Aqualine
bead of silicon sealant
or edge joiner
gib Aqualine
5 - 1
0
acrylic liner over
unsealed gib Aqualine
gib Aqualine
silicon sealant
proprietary shower tray
installed to manufacturer's
recommendations
gib Aqualine
tap body
silicon sealant
Note:
where impact noise
from pipes is an issue
fix all pipes on resiliant
brackets
acrylic liner over
unsealed gib Aqualine
bath/wall
scale 1:5 @A3
tiled penetration
scale 1:5 @A3
shower top
scale 1:5 @A3
shower base
scale 1:5 @A3
shower penetration
scale 1:5 @A3
basin/wall
scale 1:5 @A3
bath plinth
scale 1:5 @A3
Flashing soft edge
dressed into trough
Back flashing
Screw
to purlin
Extraction
fan from
laundry
Seal
and rivet
Colour match soft edge
prior to installation
Dektite flashing
diagonal to run
Colour match soft
edge prior to
installation
F
a
l
l
Seal under
Seal and fasten
Ridge
Corrugate profile
roofing
fixing detailflashing tape detail
insert flat packers between wall framing
and jamb liner at sill and jambs.
Do NOT use wedges
Unit must always rest on solid support. fix
through jamb liner andpackers into wall
framing with nails or use other approved
fixing methods such as a jamb tie
Note:
mechanical fixings only, 150mm
from corners and at 450 crs max.
Expandable foam is not an
approved fixing method
1
0
0
m
m
skylight width
80 m
m
75 m
m**
2
0
0
m
m
*
*
H
e
ig
h
t o
f u
p
s
ta
n
d
*
2 crests**
Height of upstand*
Trimmer
Lining
Purpose-made flashing
by flashing contractor
TrimmerInsulation material
Lining
Rafter
Purpose-made top cover flashing by flashing contractor
9mm plywood sarking
to support flashing
Insulation material
to comply with New
Zealand Building
Code Section H1
Battens to support
flashing
Section H1
Insulation material
to comply with New
Zealand Building
Code
9mm plywood
sarking to support
flashing
Insulation material
to comply with New
Zealand Building
Code Section H1
9mm plywood sarking
to support flashing
VELUX VS Skylight to
15 degrees min. angle
(check on site)
SECTION A-A
INSTALLATION GUIDELINES - FS FIXED SKYLIGHT IN METAL ROOFS (PITCH < 15 DEGREES)
SECTION B-B
A
A
BB
ELEVATION
NEW ZEALAND LTD.
0800 650 445
Name Date
Drawn by
Checked by
Drawing No.
June 11
June 11
FS - Fixed Skylight in Metal Roof (pitch <15 degrees)
This drawing is an instrument of service and is provided for informational use only.
© 2011 VELUX GROUP® VELUX is a registered trademark
VELUX FS Fixed Skylight installation guidelines for roofs
with roof pitch less than 15 degrees
For roofs with roof pitches less than 15 degrees, the VELUX
FS Fixed Skylight must be installed to a min.15 degrees.
A purpose made flashing designed to meet the conditions set
out in Section E2 of the New Zealand Building Code shall be
manufactured and installed by a specialist flashing contractor.
This flashing must be guaranteed against weather-tightness
by the specialist flashing contractor.
Insulation material meeting the requirements of NZBC/H1 is
required in the cavities of the lightwell structure.