plx iec 61850
TRANSCRIPT
PLX IEC 61850 PICS Statement
Version 1.3
September 20, 2011
PICS STATEMENT
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about our products, documentation, or support, please write or call us.
How to Contact Us
ProSoft Technology 5201 Truxtun Ave., 3rd Floor Bakersfield, CA 93309 +1 (661) 716-5100 +1 (661) 716-5101 (Fax) www.prosoft-technology.com [email protected]
Copyright © 2011 ProSoft Technology, Inc., all rights reserved.
IEC 61850 PICS Statement
September 20, 2011
ProSoft Technology ®, ProLinx
®, inRAx
®, ProTalk
®, and RadioLinx
® are Registered Trademarks of ProSoft
Technology, Inc. All other brand or product names are or may be trademarks of, and are used to identify products and services of, their respective owners.
ProSoft Technology® Product Documentation
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments. User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provided on the enclosed CD-ROM in Adobe
® Acrobat Reader file format (.PDFs). These product documentation files may also be freely downloaded from
our web site: www.prosoft-technology.com
PLX IEC 61850 ♦ PICS Statement Contents Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 5 of 21 September 21, 2011
Contents
Your Feedback Please ........................................................................................................................ 2 How to Contact Us .............................................................................................................................. 2 ProSoft Technology
® Product Documentation .................................................................................... 2
1 PICS – Protocol Implementation Conformance Statement 7
1.1 ACSI Basic Conformance Statement ........................................................................ 8 1.2 ACSI Models Conformance Statement ..................................................................... 9 1.3 ACSI Service Conformance Statement ................................................................... 10 1.4 Profile Conformance ................................................................................................ 12 1.5 SCL Conformance ................................................................................................... 13 1.6 Logical Nodes Conformance ................................................................................... 14
Index 21
Contents PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 6 of 21 ProSoft Technology, Inc.
September 21, 2011
PLX IEC 61850 ♦ PICS Statement PICS – Protocol Implementation Conformance Statement Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 7 of 21
September 21, 2011
1 PICS – Protocol Implementation Conformance Statement
In This Chapter
� ACSI Basic Conformance Statement ...................................................... 8
� ACSI Models Conformance Statement .................................................... 9
� ACSI Service Conformance Statement ................................................. 10
� Profile Conformance .............................................................................. 12
� SCL Conformance ................................................................................. 13
� Logical Nodes Conformance ................................................................. 14
This section describes the Protocol Implementation Conformance Statement (PICS) for the ProSoft IEC 61850 Protocol Driver.
The following ACSI Basic Conformance Statement and ACSI Service Conformance Statements shall be used to provide an overview and details about the 61850 driver’s claiming conformance with ACSI.
PICS – Protocol Implementation Conformance Statement PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 8 of 21 ProSoft Technology, Inc.
September 21, 2011
1.1 ACSI Basic Conformance Statement
Client / Subscriber
Server / Publisher
Value / Comments
Client-server roles
B11 Server side (of TWO-PARTY-APPLICATION-ASSOCIATION)
- F
B12 Client side (of TWO-PARTY-APPLICATION-ASSOCIATION)
Y
-
SCSMs supported
B21 SCSM: IEC 61850-8-1 used Y F
B22 SCSM: IEC 61850-9-1 used N N
B23 SCSM: IEC 61850-9-2 used F F
B24 SCSM: other - -
Generic substation event model (GSE)
B31 Publisher side N F
B32 Subscriber side Y F
Transmission of sampled value model (SVC)
B41 Publisher side - F
B42 Subscriber side F -
PLX IEC 61850 ♦ PICS Statement PICS – Protocol Implementation Conformance Statement Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 9 of 21
September 21, 2011
1.2 ACSI Models Conformance Statement
Client / Subscriber
Server / Publisher
Value / Comments
If Server side (B11) supported
M1 Logical device Y F
M2 Logical node Y F
M3 Data Y F
M4 Data set Y F
M5 Substitution - F
M6 Setting group control F F
Reporting
M7 Buffered report control Y F
M7-1 Sequence-number Y F
M7-2 Report-time-stamp Y F
M7-3 Reason-for-inclusion Y F
M7-4 Data-set-name Y F
M7-5 Data-reference Y F
M7-6 Buffer-overflow Y F
M7-7 entryID Y F
M7-8 BufTm Y F
M7-9 IntgPd Y F
M7-10 GI Y F
M8 Unbuffered report control
M8-1 Sequence-number Y F
M8-2 Report-time-stamp Y F
M8-3 Reason-for-inclusion Y F
M8-4 Data-set-name Y F
M8-5 Data-reference Y F
M8-6 BufTm Y F
M8-7 IntgPd Y F
M8-8 GI Y F
Logging
M9 Log control F F
M9-1 IntgPd F F
M10 Log F F
M11 Control Y F
If GSE (B31/B32) is supported
GOOSE
M12-1 entryID Y F
M12-2 DataReflnc Y F
M13 GSSE F F
If SVC (B41/B42) is supported
M14 Multicast SVC F F
M15 Unicast SVC F F
M16 Time F F
M17 File Transfer F F
PICS – Protocol Implementation Conformance Statement PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 10 of 21 ProSoft Technology, Inc.
September 21, 2011
1.3 ACSI Service Conformance Statement
Services AA: TP / MC
Client / Subscriber
Server / Publisher
Comments
Server (Clause 6)
S1 ServerDirectory TP Y F
Application association (Clause 7)
S2 Associate Y F
S3 Abort Y F
S4 Release Y F
Logical device (Clause 8)
S5 Logical Device Directory TP F F
Logical node (Clause 9)
S6 Logical Node Directory TP F F
S7 Get All Data Values TP F F
Data (Clause 10)
S8 GetDataValues TP Y F
S9 SetDataValues TP Y F
S10 GetDataDirectory TP F F
S11 GetDataDefinition TP F F
Data set (Clause 11)
S12 GetDataSetValues TP Y F
S13 SetDataSetValues TP Y F
S14 CreateDataSet TP F F
S15 DeleteDataSet TP F F
S16 GetDataSetDirectory TP Y F
Substitution (Clause 12)
S17 SetDataValues TP - F
Setting group control (Clause 13)
S18 SelectActiveSG TP F F
S19 SelectEditSG TP F F
S20 SetSGValues TP F F
S21 ConfirmEditSGValues TP F F
S22 GetSGValues TP F F
S23 GetSGCBValues TP F F
Reporting (Clause 14)
Buffered report control block (BRCB)
S24 Report TP Y F
S24-1 data-change (dchg) Y F
S24-2 qchg-change (qchg) Y F
S24-3 data-update (dupd) Y F
S25 GetBRCBValues TP Y F
S26 SetBRCBValues TP Y F
Unbuffered report control block (URCB)
S27 Report TP Y F
S27-1 data-change (dchg) Y F
S27-2 qchg-change (qchg) Y F
S27-3 data-update (dupd) Y F
S28 GetURCBValues TP Y F
PLX IEC 61850 ♦ PICS Statement PICS – Protocol Implementation Conformance Statement Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 11 of 21
September 21, 2011
Services AA: TP / MC
Client / Subscriber
Server / Publisher
Comments
S29 SetURCBValues TP Y F
Logging (Clause 14)
Log control block
S30 GetLCBValues TP F F
S31 SetLCBValues TP F F
Log
S32 QueryLogByTime TP F F
S33 QueryLogAfter TP F F
S34 GetLogStatusValues TP F F
Generic substation event model (GSE) (14.3.5.3.4)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage MC Y F
S36 GetGoReference TP F F
S37 GetGOOSEElementNumber TP F F
S38 GetGoCBValues TP Y F
S39 SetGoCBValues TP Y F
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage MC F F
S41 GetGsReference TP F F
S42 GetGSSEElementNumber TP F F
S43 GetGsCBValues TP F F
S44 SetGsCBValues TP F F
Transmission of sampled value model (SVC) (Clause 16)
Multicast SVC
S45 SendMSVMessage MC F F S46 GetMSVCBValues TP F F
S47 SetMSVCBValues TP F F Unicast SVC
S48 SendUSVMessage TP F F
S49 GetUSVCBValues TP F F
S50 SetUSVCBValues TP F F Control (17.5.1)
S51 Select F F
S52 SelectWithValue TP Y F S53 Cancel TP F F
S54 Operate TP Y F S55 Command-Termination TP F F
S56 TimeActivated-Operate TP F F File transfer (Clause 20)
S57 GetFile TP F F
S58 SetFile TP F F S59 DeleteFile TP F F
S60 GetFileAttributeValues TP F F Time (5.5)
T1 Time resolution of internal clock 1 ms F
T2 Time accuracy of internal clock +/- 0.1 ms F
T3 Supported TimeStamp resolution 1 ms F
PICS – Protocol Implementation Conformance Statement PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 12 of 21 ProSoft Technology, Inc.
September 21, 2011
1.4 Profile Conformance
Client / Subscriber
Server / Publisher
Value / Comments
PICS for A-Profile Support
A1 Client/Server A-Profile Y F
A2 GOOSE/GSE Management A-Profile Y F
A3 GSSE A-Profile F F
A4 TimeSync A-Profile Y F
PICS for T-Profile Support
T1 TCP/IP T-Profile Y F
T2 OSI T-Profile N N
T3 GOOSE/GSE T-Profile Y F
T4 GSSE T-Profile F F
T5 TimeSync T-Profile N N
PLX IEC 61850 ♦ PICS Statement PICS – Protocol Implementation Conformance Statement Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 13 of 21
September 21, 2011
1.5 SCL Conformance
Client / Subscriber
Server / Publisher
Value / Comments
SCL Conformance Degrees
SCL.1 SCL File for Implementation Available (offline)
Y F
SCL.2 SCL File available from implementation online
F F
SCL.3 SCL implementation reconfiguration supported online
F F
Supported ACSI services for SCL.2 and SCL.3
ACSI Services
GetFileAttributeValues N N
GetFile N N
SetFilE N N
DeleteFile N N
GetDataValues N N
SetDataValues N N
SCL Control Block N N
SCL File Structure N N
Remote Creation of SCL File N N
Additional MMS services for SCL.2 and SCL.3
MMS Services N F
GetCapabilityList N F
GetDomainAttributes N N
LoadDomainContent N N
StoreDomainContent N N
Definition of SCL control block
Validate N N
ValState N N
Activate N N
PICS – Protocol Implementation Conformance Statement PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 14 of 21 ProSoft Technology, Inc.
September 21, 2011
1.6 Logical Nodes Conformance
Client / Subscriber
Server / Publisher
Value / Comments
IEC61850-7-4 Logical Nodes Required for Servers
(L) System Logical Nodes
LLNO Common Logical Node Zero Y F
LPHD Physical Device Y F
(P) Protection Functions
PDIF Differential Y F
PDI Directional Y F
PDOP Directional Over Power Y F
PDUP Directional Under Power Y F
PFRC Rate of Frequency Change Y F
PHAR Harmonic Constraint Y F
PHIZ Ground Detection Y F
PIOC Instantaneous Over Current Y F
PMRI Motor Restart Inhibition Y F
PMSS Motor Starting Time Supervision Y F
POPF Over power Factor Y F
PPAM Phase Angle Measuring Y F
PSC Protection Scheme Y F
PSDE Sensitive Directional Earth Fault Y F
PTEF Transient Earth Fault Y F
PTOC Time Over Current Y F
PTOF Over Frequency Y F
PTOV Over Voltage Y F
PTRC Protection Trip Conditioning Y F
PTTR Thermal Overload Y F
PTUC Under Current Y F
PTUV Under Voltage Y F
PUPF Under Power Factor Y F
PTUF Under Frequency Y F
PVOC Voltage Controlled Time Over Current Y F
PVPH Volts per Hertz Y F
PZSU Zero Speed or Under Speed Y F
(R) Protection Related Functions
RDRE Disturbance Recorder Function Y F
RADR Disturbance Recorder Channel Analogue Y F
RBDR Disturbance Recorder Channel Binary Y F
RDRS Disturbance Record Handling Y F
RBRF Breaker Failure Y F
RDIR Directional Element Y F
RFLO Fault Locator Y F
RPSB Power Swing Detection/Blocking Y F
RREC Auto Reclosing Y F
RSYN Synchronism Check or Synchronizing Y F
(C) Control
CALH Alarm Handling Y F
PLX IEC 61850 ♦ PICS Statement PICS – Protocol Implementation Conformance Statement Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 15 of 21
September 21, 2011
Client / Subscriber
Server / Publisher
Value / Comments
CCGR Cooling Group Control Y F
CILO Interlocking Y F
CPOW Point on Wave Switching Y F
CSWI Switch Controller Y F
(G) Generic References
GAPC Generic Automatic Process Control Y F
GGIO Generic Process I/O Y F
GSAL Generic Security Application Y F
(I) Interfacing and Archiving
IARC Archiving Y F
IHMI Human Machine Interface Y F
ITCI Telecontrol Interface Y F
ITMI Telemonitoring Interface Y F
(A) Automatic Control
ANCR Neutral Current Regulator Y F
ARCO Reactive Power Control Y F
ATCC Automatic Tap Changer Controller Y F
AVCO Voltage Control Y F
(M) Metering and Measurement
MDIF Differential Measurements Y F
MHAI Harmonics or Interharmonics Y F
MHAN Non-Phase Related Harmonics or Interharmonics
Y F
MMTR Metering Y F
MMXU Measurement Y F
MSQI Sequence and Imbalance Y F
MSTA Metering Statistics Y F
(S) Sensors and Monitoring
SARC Monitoring and Diagnostics for arcs Y F
SIMG Insulation Medium Supervision (gas) Y F
SIML Insulation Medium Supervision (liquid) Y F
SPDC Monitoring and Diagnostics for Partial Discharges
Y F
(X) Switchgear
XCBR Circuit Breaker Y F
XSWI Circuit Switch Y F
(T) Instrument Transformers
TCTR Current Transformer Y F
TVTR Voltage Transformer Y F
(Y) Power Transformers
YEFN Earth Fault Neutralizer Y F
YLTC Tap Changer Y F
YPSH Power Shunt Y F
YPTR Power Transformer Y F
(Z) Further Power System Equipment
ZAXN Auxilliary Network Y F
ZBAT Battery Y F
PICS – Protocol Implementation Conformance Statement PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 16 of 21 ProSoft Technology, Inc.
September 21, 2011
Client / Subscriber
Server / Publisher
Value / Comments
ZBSN Bushing Y F
ZCAB Cable Y F
ZCAP Capacitor Bank Y F
ZCON Converter Y F
ZGEN Generator Y F
ZGIL Gas Insulated Line Y F
ZLIN Power Overhead Line Y F
ZMOT Motor Y F
ZREA Reactor Y F
ZTCF Thyristor Controlled Frequency Converter Y F
ZTCR Thyristor Controlled Reactive Component Y F
Logical Nodes for Hydro Power Plants
(LNs specific for Hydro are in bold text)
Hydro Power: Logical nodes for control functions
CALH Alarm handling Y F
CSWI Switch controller Y F
Hydro Power: Logical nodes representing functional blocks
FCNT Counter function Y F
FCSD Curve shape description Y F
FFIL Filter function Y F
FLIM Limiter function Y F
FPID Proportional, integral and derivative regulator function
Y F
FRMP Ramp control function Y F
FSPT Setpoint control function Y F
FXOT Action at over threshold Y F
FXUT Action at under threshold Y F
Hydro Power: Hydropower specific logical nodes
HBRG Turbine – generator shaft bearing Y F
HBRK Braking system for the generator shaft Y F
HCOM Combinator (3D-CAM or 2D-CAM) Y F
HDAM Hydropower dam, water reservoir Y F
HDLS Dam leakage supervision Y F
HGPI Gate position indicator Y F
HGTE Dam gate Y F
HITG Intake gate Y F
HJCL Power plant joint control function Y F
HLKG Leakage supervision Y F
HLVL Dam water level indicator Y F
HNDL Needle control Y F
HNHD Net head data Y F
HOTP Dam overtopping protection Y F
HSEQ Start / stop sequencer Y F
HSPD Speed monitoring Y F
HUNT Hydropower production unit Y F
HWCL Water control function Y F
Hydro Power: Logical nodes for interface and archiving
PLX IEC 61850 ♦ PICS Statement PICS – Protocol Implementation Conformance Statement Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 17 of 21
September 21, 2011
Client / Subscriber
Server / Publisher
Value / Comments
IARC Generic archiving function Y F
IHMI Generic human – machine interface Y F
ISAF Generic safety device Y F
Hydro Power: Logical nodes for mechanical and non-electric primary equipment
KFAN Fan Y F
KFIL Filter Y F
KPMP Pump Y F
KTNK Tank Y F
KVLV Valve or aperture gate Y F
Hydro Power: Logical nodes for metering and measurement
MDIF Differential current measurement Y F
MENV Environmental data Y F
MHAI Harmonics measurement Y F
MHYD Hydrological measurement Y F
MMDC DC current and voltage measurement Y F
MMET Meteorological measurement Y F
MMXN Single-phase measurement Y F
MMXU Three-phase measurement Y F
Hydro Power: Protection functions
PDIF Generator differential, restricted earth-fault Y F
PDOP Reverse power Y F
PDUP Loss of field (excitation system failure) Y F
PHIZ Residual over-voltage Y F
PIOC Phase over-current Y F
PPAM Phase angle, out-of-step Y F
PRTR Rotor protection Y F
PSDE Directional earth-fault Y F
PTHC Thyristor failure protection Y F
PTOC Time over-current, rotor earth-fault, bearing current, stator earth-fault
Y F
PTOF Over-frequency Y F
PTOV Over- / under-voltage Y F
PTUF Under-frequency Y F
PTTR Overload Y F
PVOC Under impedance Y F
PVPH Over-fluxing Y F
PZSU Energising at stand-still Y F
Hydro Power: Logical nodes for protection related functions
RBRF Breaker-fail protection Y F
RPSB Power swing detection Y F
RSYN Synchronizing Y F
Hydro Power: Logical nodes for supervision and monitoring
SPDC Partial discharge sensor Y F
STMP Temperature supervision Y F
SVBR Vibration supervision Y F
Hydro Power: Logical nodes for sensors
TANG Angle Y F
PICS – Protocol Implementation Conformance Statement PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 18 of 21 ProSoft Technology, Inc.
September 21, 2011
Client / Subscriber
Server / Publisher
Value / Comments
TAXD Axial displacement Y F
TCTR Current transformer Y F
TDIS Distance Y F
TFLW Liquid flow Y F
TFRQ Frequency Y F
THUM Humidity Y F
TLEV Media level Y F
TMGF Magnetic field Y F
TPOS Position indicator Y F
TPRS Pressure Y F
TRTN Rotation Y F
TSND Sound pressure Y F
TTMP Temperature Y F
TTNS Mechanical tension / stress Y F
TVBR Vibration sensor Y F
TVTR Voltage transformer Y F
TWPH Water acidity Y F
Hydro Power: Logical nodes for power system equipment
ZAXN Auxiliary network (power plant supply) Y F
ZBAT DC battery Y F
ZMOT Motor Y F
ZREA Reactor Y F
ZRES Neutral resistor Y F
ZSCR Semi-conductor controlled rectifier Y F
ZSMC Synchronous machine Y F
Logical Nodes for Wind Power Plants
(LNs specific for Wind Power are in bold text)
Wind Power specific logical nodes
WTUR Wind turbine general information Y F
WALM Wind power plan alarm information Y F
WMET Wind power plant meteorological information Y F
WAPC Wind power plant active power control information
Y F
WRPC Wind power plant reactive power control information
Y F
Wind Turbine specific logical nodes
WTUR Wind turbine general information Y F
WROT Wind turbine rotor information Y F
WTRM Wind turbine transmission information Y F
WGEN Wind turbine generator information Y F
WCNV Wind turbine converter information Y F
WTRF Wind turbine transformer information Y F
WNAC Wind turbine nacelle information Y F
WYAW Wind turbine yawing information Y F
WTOW Wind turbine tower information Y F
WALM Wind power plant alarm information Y F
WSLG Wind turbine state log information Y F
PLX IEC 61850 ♦ PICS Statement PICS – Protocol Implementation Conformance Statement Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 19 of 21
September 21, 2011
Client / Subscriber
Server / Publisher
Value / Comments
WALG Wind turbine analogue log information Y F
WREP Wind turbine report information Y F
PICS – Protocol Implementation Conformance Statement PLX IEC 61850 ♦ PICS Statement PICS Statement Version 1.3
Page 20 of 21 ProSoft Technology, Inc.
September 21, 2011
PLX IEC 61850 ♦ PICS Statement Index Version 1.3 PICS Statement
ProSoft Technology, Inc. Page 21 of 21
September 21, 2011
Index
A
ACSI Basic Conformance Statement • 8 ACSI Models Conformance Statement • 9 ACSI Service Conformance Statement • 10
H
How to Contact Us • 2
L
Logical Nodes Conformance • 14
P
PICS – Protocol Implementation Conformance Statement • 7
Profile Conformance • 12 ProSoft Technology® Product
Documentation • 2
S
SCL Conformance • 13
Y
Your Feedback Please • 2