pn 80505
TRANSCRIPT
-
5/28/2018 Pn 80505
1/76
TC 1818aControl Module
Operating Guide
SWM-015.5
-
5/28/2018 Pn 80505
2/76
This guide is intended solely for use by owners of Thermon HeatChekTMheattracing control and monitoring units. This manual describes operation forTC 1818 controllers with firmware released in 2010. Earlier versions of firmwaremay not include all features described in this manual. This manual is consideredproprietary and is protected by copyright. Use by others without expressedwritten consent of Thermon is strictly prohibited.
Thermon 1999, 2005, 2008, 2010
HeatChek and TraceView are tradenames of Thermon Manufacturing Company.
-
5/28/2018 Pn 80505
3/76
INDEX
The TC 1818a Module .................................................................... 4
TC 1818a Module Specifications .................................................. 8
Typical HeatChek Control andMonitoring Units ............................................................................ 9
Programming The TC 1818a ........................................................10
The TC 1818a in Operation ..........................................................37
Configuring the TC 1818a for AmbientSensing or Dual RTD Control .......................................................51
Programming and Operating the TC 1818a inan Ambient Sensing Control Mode .............................................55
Programming and Operating the TC 1818a with
Dual Input RTDs for a Single Control Circuit...............................60
Typical Control Applications ........................................................62
Communications ..........................................................................71
Options and Accessories .............................................................72
Help ...............................................................................................73
Attachment A: TC 1818a Command Flowchart
TC 1818aControl Module
-
5/28/2018 Pn 80505
4/76
4
TC 1818a Control Module
THE TC 1818a MODULE
The TC 1818a is a microprocessor-based temperature control and monitoring moduledeveloped specifically for heat tracing. The multi-circuit module can provide heat tracingcontrol, digital information display and alarms for high temperature, low temperature, highcurrent, low current, high ground leakage current, circuit fault, and damaged temperaturesensor for up to eighteen heat tracing circuits. Resettable minimum and maximum tem-peratures seen are retained for display on demand.
The TC 1818a module operates independently and can also be connected to a datahighway for remote systems communication functions through a personal computer or a
distributed control system (DCS).
-
5/28/2018 Pn 80505
5/76
5
Operating Guide
DATA DISPLAY
The TC 1818a module utilizes a backlit Liquid Crystal Display (LCD) for reporting tem-peratures, currents, and other operating parameters. Alarm LED's in conjunction with theinformation display indicate high temperature, low temperature, high heater current, lowheater current, high ground leakage, sensor fault, and circuit fault alarm status. AdditionalLEDs indicate status of power to the TC 1818a, power to the heat tracing circuits, CPUstatus, and the general controller alarm status.
DATA ENTRY
The TC 1818a has a 16 key "tactile feel" membrane switch keypad which provides formodification (with security key access) of all control parameters as well as permits inquiriesinto the status of any circuit being controlled or monitored.
ALARM RELAY
The TC 1818a module is provided with three independent normally open, close onalarm, solid state alarm relay contacts, rated 1A at 120/240 VAC. The first of theserelays activates in the event of any alarm. The second relay contact activates when any"trip" designated alarms occur. Inverse mode operation on either of these alarms is also
configurable. The third alarm contact provides information regarding the status of internalmodule CPU diagnostics.
CONTROL RELAY
The TC 1818a module can be configured with up to eighteen DC outputs each having a sinkcurrent capability of 100 mA @ 24 VDC for switching up to 18 solid state power relays.
MODULE POWER
The TC 1818a module is convertible from 120 VAC to 208/ to 240 VAC instrument voltage(50 to 60 HZ) from a slide selector switch.
COMMUNICATIONS
Each TC 1818a module is provided with an RS-485 communications port for connectionthrough a two wire twisted shielded pair network into a PC. The Modbus ASCII or RTUprotocol at 9600 baud rate communications streams may also be interfaced into thedistributed control system (DCS).
INPUT/OUTPUT MODULE INTERLINK
Each TC 1818a can be interlinked with up to three six point sensor input modules andthree six circuit power output modules through ribbon cable connections.
-
5/28/2018 Pn 80505
6/76
6
TC 1818a Control Module
The TC 1818a is designed to be an integral part of a HeatChekTMcontrol and monitoringunit. Each unit typically includes one or more TC 1818a modules, power output modules,and sensor input modules, all inter-connecting wiring and ribbon cables, and an electricalenclosure suitable for the environment.
POWER OUTPUT MODULES
Each TC 1818a power output module is configured with six solid state power relays. Thesingle switch SSR30 relays utilized are zero crossing solid state with a single cycle surgecapacity of 600A and a one second overcurrent capacity of 80A. The dual switch SSR15
relays are zero crossing solid state with a single cycle surge capacity of 500A and a onesecond overcurrent capacity of 80A. Design current rating limits for these power outputmodules are determined by the relay type, enclosure size, ambient conditions, and heatsink style (maximum of 30A per single switch relay and 15A for each switch in a dualswitch relay). See Table 1 for details.
Each power output module is provided complete with input/output terminal blocks forup to six heat tracing circuits, ribbon cable up to 15 ft (4.6 m) in length, connectors forlinking to the TC 1818a control module, and a "touch safe" polycarbonate cover mount-
ing assembly.
Table 1: Current Rating
Current ratings are based on outdoor ambients of 104oF (40oC) with solar loading. Contact thefactory for ratings at higher ambient conditions or for ratings in larger enclosure sizes.
The 6SSR30C includes six single switch solid state relays suitable for controlling up to 30 am-peres per switch.
The 6SSR15C includes six dual switch solid state relays suitable for controlling up to 15 amperes
per switch.
Maximum Total Heater CurrentThrough Solid State Relays
Per Enclosure
Enclosure Option
Heat Sink Style C
6SSR30C
Heat Sink Style C
6SSR15C
PS4, SS4 360A 180A
PS5, SS5 576A 288A
-
5/28/2018 Pn 80505
7/76
7
Operating Guide
CONTROL AND MONITORING UNIT
A HeatChek control and monitoring unit utilizing the TC 1818a module, solid state relaypower output modules, sensor input modules, and a NEMA 4 or 4X enclosure is ap-proved/certified for use in Class I, Division 2 Hazardous (classified) as well as Ordinary(non-classified) Locations.
These units include the following warning markings:
This marking intends that the user must disconnect all power sources to the panel priorto servicing.
This marking indicates a location that must be grounded in accordance with local andnational requirements.
CAUTION! CIRCUITS MAY BE ENERGIZED
-
5/28/2018 Pn 80505
8/76
8
TC 1818a Control Module
TC 1818A MODULE SPECIFICATIONS
The TC 1818a module has the general specifications as detailed below:
Control and Monitoring Capacity: Eighteen resistive heat tracing circuits up to 30amps per circuit (depending on switch type)
Module Supply Voltage: 110-120 VAC or 208-240 VAC
Operating Frequency: 50 to 60 Hz Nominal
Power Consumption: 40 watts per TC 1818a module
Module Operating Ambient: -40oF to +140oF (-40oC to +60oC)
Maximum Storage Ambient: 158oF (70oC)
Data Retention: Non volatile EEPROM
Power Clamp Function: Programmable for power levels from 20 to100% maximum power
Input: Up to eighteen 3 wire 100 ohms @ 32oF (0oC)platinum RTD's
Temperature Range (Control): -40oF to 932oF (-40oC to 500oC) with program-mable control band in increments of one degree
Control: On-Off, On-Off with Softstart, Proportional,Proportional Self-Adjust
Module Dimensions: 4-1/2" x 19" x 7-1/2"(114 mm x 482 mm x 191 mm)
Operating Current Alarm High:1.0 to 30.0 ALow:0.0 to 30.0 A
Ground Leakage Alarm/Trip: 30 to 150 mA
Self-Test Frequency: Programmable from 2 to 99 hours
-
5/28/2018 Pn 80505
9/76
9
Operating Guide
TYPICAL HEATCHEK CONTROL AND MONITORING UNITS
The TC 1818a is modular in construction and can be configured in a variety of HeatChekcontrol and monitoring units.
INFORMATION
Additional design selection and engineering information may be found inForm T-1008-E.
Specific wiring and equipment arrangement details are usually provided in drawings in-cluded within the HeatChek control and monitoring unit at time of shipment.
-
5/28/2018 Pn 80505
10/76
10
TC 1818a Control Module
PROGRAMMING THE TC 1818A MODULE
ACCESSING THE PROGRAM MODE
Turn the key to the vertical position and then press the PROG key to enter the program-ming mode.
The TC 1818a will then display the following message:
Then select the desired function key (e.g. MAINTAIN TEMP).
If the function key is not a global function (e.g. CONFIG, DATA HWY, etc.) then the fol-lowing message appears.
Select the desired circuit by pressing the UP or DOWN arrow keys and then pressingthe ENTER key.
In order to set all circuits to a common value, press the UP arrow key until "ALL THE
SAME VALUE" appears.
Press ENTER to globally set a control or operating parameter.
PROGRAM MODE ENABLED
SELECT FUNCTION KEY
PROGRAM CIRCUIT=1
PROGRAM = ALL THE
SAME VALUE
PROG
MAINTAIN
TEMP
-
5/28/2018 Pn 80505
11/76
11
Operating Guide
MAINTAIN TEMPERATURE (PROGRAM MODE)
The following is a typical message which might appear:
Momentarily pressing the UP or DOWN arrow keys will cause the NEW VALUE to change
by 1 degree increments. Holding the key down results in a 10 degree incremental change.If an upper or lower limit is reached, a MAX or MIN message will appear on the secondline. This indicates that either the absolute maximum or minimum value has been reachedor that the value has reached an alarm value.
Once the desired temperature value is set, press the ENTER key to save the value.
The controller will then exit the programming mode and return to the Scan Mode
MAINTAIN TEMP=104F
NEW VALUE=104F
RETURN TO SCAN MODE
MAINTAIN TEMP=104F
NEW VALUE=50F
-
5/28/2018 Pn 80505
12/76
12
TC 1818a Control Module
HIGH TEMPERATURE ALARM (PROGRAM MODE)
Pressing the HIGH TEMP ALARM function key results in a display message such as thefollowing:
The TC 1818a is set to alarm at 160oF on the current circuit number. Should the controltemperature reach 160oF, the red "ALARM ON" LED on the TC 1818a will begin toflash and the "HIGH TEMP" LED will illuminate when the circuit in alarm appears on theINFORMATION DISPLAY. In addition, the alarm relay contact will close (depending onconfiguration, inverse action may occur).
To change the current value, press the UP or DOWN arrow keys to increase or decreasethe current HIGH TEMP ALARM setpoint.
HIGH TEMP ALARM=160F
NEW VALUE=160F
HIGH
TEMP
ALARM
HIGH TEMP ALARM=160F
NEW VALUE=120F
-
5/28/2018 Pn 80505
13/76
13
Operating Guide
Once the desired temperature value is set, press the ENTER key to save the value.
Next, the following typical message will appear:
At some point since this controller was last reset, the temperature has attained 200F.Press the UP arrow key and ENTER to clear this value and begin anew at the current value.Pressing ENTER or PROG key results in the current value of 200F being retained.
Subsequently, the TC 1818a returns to the Scan Mode.
2 HIGH TEMP SEEN=200F
RESET? (Y/N)
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
14/76
14
TC 1818a Control Module
LOW TEMPERATURE ALARM (PROGRAM MODE)
Pressing the LOW TEMP ALARM function key results in a display message such as thefollowing:
The TC 1818a is set to alarm at 50oF on the current circuit number. Should the controltemperature drop to 50oF, the "ALARM ON" LED on the TC 1818a will begin to flash and the"LOW TEMP" LED will illuminate when the circuit in alarm appears on the INFORMATIONDISPLAY. In addition, the alarm relay contact will close (depending on configuration,inverse action may occur).
To change the present value, press the UP or DOWN arrow keys to increase or decreasethe present LOW TEMP ALARM setpoint.Once the desired temperature value is set, pressthe ENTER key to save the value.
LOW
TEMP
ALARM
LOW TEMP ALARM=50F
NEW VALUE=50F
LOW TEMP ALARM=50F
NEW VALUE=35F
-
5/28/2018 Pn 80505
15/76
15
Operating Guide
Next, the following typical message will appear:
At some point since this controller was last reset, the control temperature has dropped to40F. Pressing the ENTER key results in the present value of 40F being retained. Press theUP arrow key and ENTER to clear the stored value and begin anew at the current value.
Subsequently, the TC 1818a returns to the Scan Mode.
2 LOW TEMP SEEN=40F
RESET? (Y/N)
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
16/76
16
TC 1818a Control Module
HEATER CURRENT (PROGRAM MODE)
Pressing the HEATER CURRENT key (when the TC 1818a is configured with solid staterelays and is set for On-Off with Soft Start, Proportional, or Proportional with Self-Adjust)results in a display message as typically given below:
In this case, the power clamp function is currently in the active or enabled mode. In thismode, the TC 1818a will (through the zero crossing solid state relay provided) use cycleomission techniques to limit the maximum power available to the heater to the value shown(to some value less than the heater would ordinarily provide) at the temperature controlsetpoint. For more details, refer to pages 27 and 28.
Pressing the ENTER key will retain the current mode of operation. Pressing the UP orDOWN arrow key and pressing ENTER will result in the altering of the power percentageand hence result in the limiting of heater power when "ON" at the temperature controlsetpoint.
POWER AT MAINT TEMP=22%NEW VALUE=22%
HEATER
CURRENT
-
5/28/2018 Pn 80505
17/76
17
Operating Guide
The TC 1818a will now return to Scan Mode.
The TC 1818a is provided with a built-in "Soft Start" power up feature when configured inthe On-Off with Soft Start, Proportional, or Proportional Self-Adjust modes. This featurewill utilize cycle omission techniques to ramp up to maximum allowable heater power ina span of approximately 5.5 minutes. This ramp up feature is designed to specifically ad-dress a) cold start power surges associated with self limiting and power limiting heaters,and b) minimize overshoot which may sometimes be present when utilizing high outputheaters in low heat loss applications.
Should the TC 1818a be configured in the On-Off mode, no programming functionssuch as Power Clamping are available. In addition, no "Soft Start" control functions willbe active.
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
18/76
18
TC 1818a Control Module
GROUND CURRENT (PROGRAM MODE)
Pressing the GROUND CURRENT function key results in a display message such as thefollowing:
The TC 1818a is set to alarm at heater and associated wiring ground leakage current of40mA on the chosen circuit number. Should the ground leakage value reach 40mA, the"ALARM ON" LED on the TC 1818a will begin to flash and the "GROUND CURRENT"LED will illuminate when the circuit in alarm appears on the INFORMATION DISPLAY. Inaddition, the alarm relay contact will close (depending on configuration, inverse actionmay occur).
To change the value, press the UP or DOWN arrow keys to increase or decrease theGROUND CURRENT ALARM setpoint.
Once the desired new value is set, press the ENTER key to save the value.
Subsequently, the TC 1818a returns to the Scan Mode.
GROUND CURRENT ALARM=40mA
NEW VALUE=40mA
GROUND CURRENT ALARM=40mA
NEW VALUE=30mA
GROUND
CURRENT
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
19/76
19
Operating Guide
HIGH CURRENT ALARM (PROGRAM MODE)
Pressing the HIGH CURRENT ALARM function key results in a display message such asthe following:
The TC 1818a is set to alarm at heater current levels above 20 Amperes on the presentcircuit number. Should the heater current reach 20A, the "ALARM ON" LED on the TC1818a will begin to flash and the "HIGH CURRENT" LED will illuminate when the circuitin alarm appears on the INFORMATION DISPLAY. In addition, the alarm relay contact willclose (depending on configuration, inverse action may occur).
To change the value, press the UP or DOWN arrow keys to increase or decrease the HIGHCURRENT ALARM setpoint.
Once the desired new value is set, press the ENTER key to save the value.Subsequently, the TC 1818a returns to the Scan Mode.
HIGH CURRENT ALARM=20.0A
NEW VALUE=20.0A
HIGH CURRENT ALARM=20.0A
NEW VALUE=25.0A
HIGH
CURRENT
ALARM
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
20/76
20
TC 1818a Control Module
LOW CURRENT ALARM (PROGRAM MODE)
Pressing the LOW CURRENT ALARM function key results in a display message such asthe following:
The TC 1818a is set to alarm at heater current levels below 1 Ampere. Should the heatercurrent drop to 1A, the "ALARM ON" LED on the TC 1818a will begin to flash and the "LOWCURRENT" LED will illuminate when the circuit in alarm appears on the INFORMATIONDISPLAY. In addition, the alarm relay contact will close (depending on configuration,inverse action may occur).
To change the value, press the UP or DOWN arrow keys to increase or decrease the LOWCURRENT ALARM setpoint.
Once the desired new value is set, press the ENTER key to save the value.Subsequently, the TC 1818a returns to the Scan Mode.
LOW CURRENT ALARM=1.0A
NEW VALUE=1.0A
RETURN TO SCAN MODE
LOW
CURRENT
ALARM
LOW CURRENT ALARM=1.0A
NEW VALUE=2.0A
-
5/28/2018 Pn 80505
21/76
21
Operating Guide
CONFIG (PROGRAM MODE)
The CONFIG key provides access to setting all global control parameters on the TC 1818a.Pressing the CONFIG key results in the following display prompt:
A "Yes" entry will result in an "Open" relay condition in the event of a RTD sensor failure.Press the UP arrow key for "Yes" or DOWN arrow key for "No." Then press the ENTERkey to save. A "No" entry will result in a "Closed" relay condition in the event of a RTDsensor failure. Subsequently, the TC 1818a follows with the below message on the in-formation display:
The TC 1818a is currently set to NOT trip the heater circuits if a high ground leakagecondition occurs, but rather will only "flash" the "ALARM ON" LED and close the standardalarm relay (open in inverse operation).
To retain the present mode of GROUND CURRENT TRIP operation, press the ENTER key.
Pressing the UP arrow key and ENTER will result in the TC 1818a setting being changedto GROUND CURRENT TRIP ON.
RTD FAULT TURNS CKT ON
CHANGE? (Y/N)
GROUND CURRENT TRIP OFF
CHANGE? (Y/N)
-
5/28/2018 Pn 80505
22/76
22
TC 1818a Control Module
The TC 1818a will then prompt for the preferred HIGH CURRENT trip setting.
The TC 1818a is currently set to NOT trip the heater circuits if a high heater current alarmcondition occurs, but rather will only "flash" the "ALARM ON" LED and close the standardalarm relay (open in inverse operation).
To retain the present mode of HIGH CURRENT ALARM operation, press the ENTER key.Pressing the UP arrow key and ENTER will result in the TC 1818a setting being changedto HIGH CURRENT TRIP ON.
Once set in this manner, the heater circuits will trip (open heater relay contacts) should aheater current alarm condition occur. The TC 1818a will now require that the operator 1)press the ACKNOWLEDGE key, 2) and the high current alarm condition be cleared priorto automatic control being restored.
The TC 1818a next prompts for the HIGH TEMP ALARM trip setting.
HIGH CURRENT TRIP OFF
CHANGE? (Y/N)
HIGH TEMP TRIP OFF
CHANGE? (Y/N)
-
5/28/2018 Pn 80505
23/76
23
Operating Guide
The TC 1818a is currently set to NOT trip the heater circuits if a high temperature alarmcondition is reached, but rather to only "flash" the "ALARM ON" LED and close the stan-dard alarm relay (open in inverse operation).
To retain the present mode of HIGH TEMP ALARM operation, press the ENTER key.Pressing the UP arrow key and ENTER will result in the TC 1818a setting being changedto HIGH TEMP TRIP ON.
Once set in this manner, the heater circuits will trip (open heater relay contacts) should ahigh temperature alarm condition occur. The TC 1818a will now require that the operator1) press the ACKNOWLEDGE key, 2) and the high current alarm condition be clearedprior to automatic control being restored.
The TC 1818a is provided with On-Off, On-Off with Soft Start, Proportional, andProportional with Self-Adjust control options. The information display next prompts forthe type of control to be selected.
In the ON-OFF control mode, the heater circuit will turn on and off within the programmedcontrol band value.
Press the DOWN arrow and ENTER key to accept this control type. Otherwise, to change
the control type, press the UP arrow key and the ENTER key.
The ON-OFF with SOFT-START option allows the circuit to be gradually powered up byzero crossing cycle omission over a span of approximately 5.5 minutes. Thereafter, theheater circuit will turn on and off within the programmed control band value.
CONTROL = ON/OFF
CHANGE? (Y/N)
CONTROL = SOFT/START
CHANGE? (Y/N)
-
5/28/2018 Pn 80505
24/76
24
TC 1818a Control Module
To retain the present setting, press the ENTER key. To change the control type, press theUP arrow key and the ENTER key.
The PROPORTIONAL option will now control the heater within the programmed controlband using a proportional algorithm. This algorithm will adjust the power at maintain from20% - 100% (or programed value).
To retain the present setting, press the ENTER key. To change the control type, press theUP arrow key and the ENTER key.
With the SELF-ADJUST feature, the TC 1818a will measure the inherent system error and
will automatically adjust the proportional control parameters to decrease the deviationfrom setpoint to a minimal value.
To retain the present setting, press the ENTER key. To change the control type, press theUP arrow key and the ENTER key.
Note the SELF-ADJUST control option is only available in the SINGLE RTD controllerconfiguration.
CONTROL = PROPORTIONAL
CHANGE? (Y/N)
CONTROL = SELF ADJUST
CHANGE? (Y/N)
-
5/28/2018 Pn 80505
25/76
25
Operating Guide
The TC 1818a offers the option of setting the standard alarm relay switch to be "Closedon Alarm" or "Open on Alarm." The information display next prompts for alarmpreferences.
Press the ENTER key to retain the current setting. Press the UP arrow key and the ENTERkey to change the alarm switch action.
The TC 1818a also offers the option of setting the second TRIP alarm relay switch to be"Closed on Alarm" or "Open on Alarm." The information display next prompts for alarm
preferences.
STD ALARM CLOSED ON ALARM
CHANGE? (Y/N)
TRIP ALARM CLOSED ON ALARM
CHANGE? (Y/N)
-
5/28/2018 Pn 80505
26/76
26
TC 1818a Control Module
Press the ENTER key to retain the current setting. Press the UP arrow key and the ENTERkey to change the alarm switch action.
The TC 1818a is standardly provided with a SELF TEST function which turns each of theheater circuits "On" and "Off" and looks for the appropriate changes in the relay heatercurrent. During the heater "On" state, the TC 1818a also checks for the presence of both"LOW CURRENT" alarms and "GROUND CURRENT" alarms. The TC 1818a prompts forthe desired settings for the "SELF TEST."
The SELF TEST function is currently disabled. Press the ENTER key to retain this setting.Press the UP arrow key and the ENTER key to change to an automatic SELF TEST intervalfrom 2 to 99 hours.
Subsequently the TC 1818a returns to the Scan Mode.
AUTO SELF TEST = OFF
NEW VALUE = OFF MIN.
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
27/76
27
Operating Guide
CONTROL BAND (PROGRAM MODE)
Pressing the CONTROL BAND key results in the following display prompt:
If configured in the "On-Off" or "Soft Start" control mode, the TC 1818a will turn on theheater at the maintain temperature setpoint and will turn off at 3oF above this value.
If programmed to operate in the "Proportional Mode", and the "Power at MaintainTemperature" is set at 100%, the TC 1818a will operate at 100% power below the maintaintemperature setpoint and will ramp down in power within the control band and subsequentlyturn off when above the maintenance temperature plus control band.
CONTROL BAND=3oF
NEW VALUE=3oF
Maintain Temp
ON-OFF CONTROL WITH 100% POWER
100%
0%HeaterPower
ControlBand
Maintain Temp
PROPORTIONAL WITH 100% POWER
100%
0%HeaterPower
ControlBand
20%
-
5/28/2018 Pn 80505
28/76
28
TC 1818a Control Module
If the "Power at Maintain Temperature" has been programmed to some other value (forexample, 62%), the TC 1818a will operate at that power level value at the maintenancetemperature and the control band range will adjust as shown below.
When configured in the "Proportional with Self-Adjust" mode, the TC 1818a will initiallyoperate in the "Proportional Mode" and will subsequently begin to automatically adjustthe slope of the power ramp down. The "Power at Maintain Temperature" will decreaseuntil power output matches the demand.
Maintain Temp
PROPORTIONAL WITH SELF-ADJUST
100%
0%
HeaterPower
ControlBand
55%SteadyState
Maintain Temp
PROPORTIONAL WITH 62% POWER
100%
0%HeaterPower
AdjustedControlBand
20%
62%
ControlBand
-
5/28/2018 Pn 80505
29/76
29
Operating Guide
To retain present control band setting, press the ENTER key. Press the UP or DOWN arrowkey to increase or decrease the control band and press ENTER to save the new value.
Subsequently, the TC 1818a returns to the Scan Mode.
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
30/76
30
TC 1818a Control Module
HEATER ENABLE (PROGRAM MODE)
The TC 1818a can be factory configured for operation with a variety of pipe sensing, ambi-ent sensing, and RTD assignment configurations.
When programming the HEATER ENABLE settings in one of these control configurations,the following alternate prompt window messages may appear.
For the controller configuration SINGLE RTD INPUTS, the following message will appear
Prompt Window Message Explanation
ENABLED
CHANGE? (Y/N)
The ENABLED prompt will appear on all processsensing circuits. These circuits will turn on whenthe TC 1818a senses a process temperature belowthe maintain temperature setpoint.
The DISABLED prompt allows the option of dis-abling this control circuit for service work.
The FORCE HEATER ON prompt allows the optionof temporarily turning on the heater circuit for
diagnostic purposes.
Prompt Window Message Explanation
ENABLED (AMBIENT SENSE)
CHANGE? (Y/N)
ENABLED (PIPE SENSE)
CHANGE? (Y/N)
The ENABLED (AMBIENT SENSE) prompt willappear for all ambient sensed heater circuits.These heater circuits will turn on when the TC
1818a senses an ambient temperature on HeaterCircuit 1 which is below the maintain temperaturesetpoint. Other circuits may appear as ENABLED(PIPE SENSE). In that case, these heater circuitswill turn on when the TC 1818a senses a pipe orheated surface temperature which is below themaintain temperature setpoint. In this controllerconfiguration, CIRCUIT 1 must be set as AMBIENTSENSE.
The DISABLED prompt allows the option of dis-abling this control circuit for service work.
The FORCE HEATER ON prompt allows the optionof temporarily turning on the heater circuit fordiagnostic purposes.
For the controller configuration 1 AMB / SINGLE RTD INPUTS, the following messagewill appear.
DISABLED
CHANGE? (Y/N)
FORCE HEATER ON?
(Y/N)
DISABLED
CHANGE? (Y/N)
FORCE HEATER ON?
(Y/N)
-
5/28/2018 Pn 80505
31/76
31
Operating Guide
For the controller configuration 2 AMB/ SINGLE RTD INPUTS, the following messagewill appear.
Prompt Window Message Explanation
ENABLED (AMBIENT SENSE)
CHANGE? (Y/N)
ENABLED (PIPE SENSE)CHANGE? (Y/N)
The ENABLED (AMBIENT SENSE) prompt willappear for all ambient sensed heater circuits.These heater circuits will turn on when the TC1818a senses an ambient temperature on HeaterCircuit 1 or 2 which is below the maintain tem-perature setpoint. Other circuits may appear
as ENABLED (PIPE SENSE). In that case, theseheater circuits will turn on when the TC 1818asenses a process temperature which is below themaintain temperature setpoint. In this controllerconfiguration, CIRCUIT 1 and 2 must be set asAMBIENT SENSE.
The DISABLED prompt allows the option of dis-abling this control circuit for service work.
The FORCE HEATER ON prompt allows the optionof temporarily turning on the heater circuit fordiagnostic purposes.
For the controller configuration 1 or 2 RTD INPUTS, the following message will appear.
Prompt Window Message Explanation
ENABLED (ONE RTD)
CHANGE? (Y/N)
ENABLED (TWO RTD'S)
CHANGE? (Y/N)
These heater circuit prompts appear when usingdual RTD input controller configurations. In thesecases, the heater circuits will turn on when the TC1818a senses a process temperature (on one orboth RTD sensors) which is below the maintaintemperature setpoint.
The DISABLED prompt allows the option of dis-abling this control circuit for service work.
The FORCE HEATER ON prompt allows the optionof temporarily turning on the heater circuit fordiagnostic purposes.
DISABLED
CHANGE? (Y/N)
FORCE HEATER ON?
(Y/N)
DISABLED
CHANGE? (Y/N)
FORCE HEATER ON?
(Y/N)
-
5/28/2018 Pn 80505
32/76
32
TC 1818a Control Module
Prompt Window Message Explanation
ENABLED (AMBIENT SENSE)
CHANGE? (Y/N)
ENABLED (TWO RTD'S)
CHANGE? (Y/N)
ENABLED (ONE RTD)
CHANGE? (Y/N)
These prompts appear when using dual RTD processsensing as well as ambient sensing circuit controllerconfigurations. These heater circuits will turn onwhen the TC 1818a senses an ambient temperature(based on the value of the RTD reading in Circuit 1)which is below the maintain temperature setpoint.Other circuit prompts may appear as ENABLED
(ONE RTD or TWO RTD'S). In these cases, theheater circuits will turn on when the TC 1818asenses a process temperature (on one or both RTDsensors) which is below the maintain temperaturesetpoint. Except in the case of CIRCUIT 1 whichmust be AMBIENT SENSE in this factory configu-ration, all other circuits may be set as AMBIENTSENSE or ONE or TWO RTDS control.
The DISABLED prompt allows the option of dis-
abling this control circuit for service work. TheFORCE HEATER ON prompt allows the option oftemporarily turning on the heater circuit for diag-nostic purposes.
ENABLED (AMBIENT SENSED)CHANGE? (Y/N)
ENABLED (ONE RTD)
CHANGE? (Y/N)
ENABLED (TWO RTD)CHANGE? (Y/N)
Prompt Window Message Explanation
These prompts appear when using dual RTD process
sensing as well as ambient sensing circuit controllerconfigurations. These heater circuits will turn onwhen the TC 1818a senses an ambient tempera-ture (based on the lower value of the RTD readingin Circuit 1 and 2) which is below the maintaintemperature setpoint. Other circuit prompts mayappear as ENABLED (ONE RTD or TWO RTDS). Inthat case, these heater circuits will turn on whenthe TC 1818a senses a process temperature (on
one or both RTD sensors) which is below the main-tain temperature setpoint. Except in the case ofCIRCUIT 1 and 2 which must be AMBIENT SENSEin this controller configuration, all other circuitsmay be set as AMBIENT SENSE or ONE or TWORTDS control.
For the controller configuration 1 AMB/ 1 or 2 RTD INPUTS, the following message willappear.
For the controller configuration 2 AMB/ 1 or 2 RTD INPUTS, the following message willappear.
DISABLED
CHANGE? (Y/N)
FORCE HEATER ON?
(Y/N)
-
5/28/2018 Pn 80505
33/76
33
Operating Guide
Starting programming by pressing the PROG key.
Subsequently, press the HEATER ENABLE key.
Select the desired circuit by pressing the UP or DOWN arrow keys and then pressingthe ENTER key. Depending on the TC 1818a controller configuration, variations in theprompt message may be seen.
A prompt message as shown below will then appear.
This heater circuit is currently enabled and will turn on when the TC 1818a senses atemperature below the maintain temperature setpoint.
PROGRAM CIRCUIT = 1
HEATERENABLE
ENABLEDCHANGE? (Y/N)
Prompt Window Message Explanation
DISABLED
CHANGE? (Y/N)
FORCE HEATER ON?
(Y/N)
The DISABLED prompt allows the option of dis-abling this control circuit for service work.
The FORCE HEATER ON prompt allows the optionof temporarily turning on the heater circuit fordiagnostic purposes.
PROG
-
5/28/2018 Pn 80505
34/76
34
TC 1818a Control Module
If the TC 1818a is set for an ambient control configuration the following two enable promptmessages will appear.
Pressing the DOWN arrow key will leave the heater enabled in the ambient sense mode.Press the UP arrow key and the ENTER key.
The TC 1818a will now prompt as follows.
Pressing the DOWN arrow key and the ENTER key will result in enabling the heater as apipe sensing circuit. Pressing the UP arrow key will result in the following new prompt.
Pressing the DOWN arrow key and the ENTER key wil result in disabling the heater cir-cuit and thus result in the removal of external heat from the pipe or heated surface. TheTC 1818a will next prompt as follows.
Press the UP arrow key and the ENTER key to retain this setting. In this operating mode,
the heater will remain ON as long as no programmed alarm limits are exceeded.
Pressing the DOWN arrow and ENTER key will result in the TC 1818a returning to SCANMODE.
ENABLED (AMBIENT SENSE)
CHANGE? (Y/N)
DISABLED
CHANGE? (Y/N)
FORCE HEATER ON?
(Y/N)
ENABLED (PIPE SENSE)
CHANGE? (Y/N)
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
35/76
35
Operating Guide
DATA HIGHWAY (PROGRAM MODE)
Pressing the DATA HIGHWAY key results in the following display prompt:
DATA HIGHWAY=4
NEW VALUE=4
The TC 1818a is currently identified as address number 4. This unique address allows
the data highway communications software to identify the information being sent by thecontroller with a location and heater circuit number.
To retain the present address value, press the ENTER key. Press the UP or DOWN arrow keyto increase or decrease the address value and press ENTER to confirm the new address.
The TC 1818a has the capability to choose the Modbus ASCII or the Modbus RTUprotocols.
Pres the ENTER key to retain the current Modbus protocol. Press the UP arrow key tochange the protocols. Press the ENTER key to confirm the new settings.
MODBUS ASCII
CHANGE? Y/N
-
5/28/2018 Pn 80505
36/76
36
TC 1818a Control Module
The TC 1818a allows the successive numbering of circuit numbers for a group of modules.As shown below, the TC 1818a prompts for the beginning circuit number for the controlmodule being programmed.
Press the ENTER key to retain the current beginning circuit number. Press the UP arrowkey to arrive at the desired starting point and the ENTER key to confirm the new startingcircuit number.
The TC 1818a then returns to the Scan Mode.
1ST CIRCUIT NUMBER=1
NEW VALUE = 1 MIN.
-
5/28/2018 Pn 80505
37/76
37
Operating Guide
THE TC 1818A IN OPERATION
POWER UP (SCAN MODE)On power up, the TC 1818a will display the following two start-up screen messages.
This prompt message indicates that this TC 1818a controller has been configured to controleighteen heater circuits with eighteen individual RTD inputs. Depending on the TC 1818acontroller configuration, variations in the above message sequence may be seen.
Then the TC 1818a will go into Scan Mode.
THERMON TC 1818a
COPYRIGHT 1995-10
18 RTD INPUTS18 RELAY OUTPUTS
-
5/28/2018 Pn 80505
38/76
38
TC 1818a Control Module
Once in Scan Mode operation, in the standard factory configuration the TC 1818a willsequentially indicate the temperature reading along with the maintain temperature.
CKT 1 TEMP=51F
MAINTAIN TEMP=50oF
CKT 2 TEMP=122F
MAINTAIN TEMP=120F
CKT 3 TEMP=605F
MAINTAIN TEMP=600F
CKT 4 TEMP=51F
MAINTAIN TEMP=50F
CKT 5 TEMP=122F
MAINTAIN TEMP=120F
CKT 6 TEMP=605F
MAINTAIN TEMP=600F
Upon displaying all temperature information for all configured circuits, the TC 1818a willsubsequently return to the first circuit and repeat the display sequence.
Refer to page 53 for more details on alternate control options and prompt messages.
-
5/28/2018 Pn 80505
39/76
39
Operating Guide
WHEN IN ALARM (SCAN MODE)
Un-Acknowledged Alarms
When an alarm condition occurs, the "ALARM ON" LED will begin to flash, the "ALARMTYPE" LED's will illuminate when the specific circuit in alarm appears on the INFORMATIONDISPLAY, and the standard alarm relay will close.
Acknowledged Alarms
To acknowledge an alarm condition, press the ALARM ACK key. The first alarm conditionwill be indicated in the INFORMATION DISPLAY. Pressing the ALARM ACK key again
will acknowledge this alarm. Repeat this sequence to determine the nature of additionalalarms. Acknowledged alarms are indicated by the suffix Ack appearing when the alarmcondition is displayed. Acknowledged alarms will continue to be displayed until the alarmcondition clears. When all alarms have been acknowledged then the ALARM ON light onthe controller will cease flashing but will stay ON until all alarm conditions have cleared.
Manual Reset
If a TRIP option has been set on a circuit, then all alarms for that circuit must be acknowl-edged before they will clear. When TRIP has been triggered, the alarm for that trip must beacknowledged and the alarm condition must clear before automatic control is restored.
Automatic Reset
When no TRIP options have been set, the alarms will automatically clear when the alarmcondition has cleared.
-
5/28/2018 Pn 80505
40/76
40
TC 1818a Control Module
ACCESSING DATA (DISPLAY MODE)
Press the MAINTAIN TEMP key to display the Maintain Temperature for all circuits astypically shown.
Press the HEATER CURRENT key to display the Heater Amperage for all enabled circuitsas typically shown.
MAINTAIN TEMP
CIRCUIT 1=50F
MAINTAIN TEMP
CIRCUIT 2=120F
MAINTAIN TEMP
CIRCUIT 3=600F
RETURN TO SCAN MODE
MAINTAIN
TEMP
HEATER
CURRENT
MAINTAIN TEMP
CIRCUIT 4=50F
MAINTAIN TEMP
CIRCUIT 5=120F
MAINTAIN TEMP
CIRCUIT 6=600F
HEATER CURRENT
CIRCUIT 1=1.0A
HEATER CURRENT
CIRCUIT 2=5.0A
HEATER CURRENT
CIRCUIT 3=20.0A
RETURN TO SCAN MODE
HEATER CURRENT
CIRCUIT 4=1.0A
HEATER CURRENT
CIRCUIT 5=5.0A
HEATER CURRENT
CIRCUIT 6=20.0A
-
5/28/2018 Pn 80505
41/76
41
Operating Guide
Press the CONFIG key to display the global settings for all trip and control functions, toview the interval between self tests, and to do a manual SELF TEST on the circuits. Atypical display sequence is shown.
GROUND CURRENT TRIP ON
AUTO SELF TEST ON
INTERVAL 2 HOURS
* NOTE: This information screenonly appears when a circuit isconfigured for dual RTD inputs.
RETURN TO SCAN MODE
CIRCUIT TEST IN PROGRESS
TESTING CIRCUIT #1
CIRCUIT TEST IN PROGRESS
TESTING CIRCUIT #2
CIRCUIT TEST IN PROGRESS
TESTING CIRCUIT #3
CIRCUIT TEST IN PROGRESS
TESTING CIRCUIT #4
CIRCUIT TEST IN PROGRESS
TESTING CIRCUIT #5
CIRCUIT TEST IN PROGRESS
TESTING CIRCUIT #6
RTD FAULT TURNS CKT OFF
HIGH CURRENT TRIP OFF
HIGH TEMP TRIP ON
CONTROL = ON/OFF
STD ALM CLOSED ON ALARM
TRIP ALM CLOSED ON ALARM
2 RTD ALARM DEADBAND
TEMP = 1F *
-
5/28/2018 Pn 80505
42/76
42
TC 1818a Control Module
Press the CONTROL BAND key to display the control band settings for all circuits astypically shown.
Subsequently, the TC 1818a returns to Scan Mode.
CONTROL
BAND
CONTROL BAND
CIRCUIT 1=2F
CONTROL BAND
CIRCUIT 2= 3F
CONTROL BAND
CIRCUIT 3= 10F
CONTROL BAND
CIRCUIT 4=2F
CONTROL BAND
CIRCUIT 5=3F
CONTROL BAND
CIRCUIT 6=10F
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
43/76
43
Operating Guide
Press the GROUND CURRENT key to display ground leakage current from heater andassociated wiring on all circuits as typically shown.
Subsequently the Information display will begin displaying the ground leakage alarm/tripsettings for each circuit.
Upon completion of the display of the ground current alarm/trip values on all circuits, the
TC 1818a returns to Scan Mode.
GROUND
CURRENT
RETURN TO SCAN MODE
GROUND CURRENT
CIRCUIT 1=15mA
GROUND CURRENT
CIRCUIT 2=5mA
GROUND CURRENT
CIRCUIT 3=10mA
GROUND CURRENT
CIRCUIT 4=15mA
GROUND CURRENT
CIRCUIT 5=5mA
GROUND CURRENT
CIRCUIT 6=10mA
GROUND CURRENT ALARM
CIRCUIT 1=40mA
GROUND CURRENT ALARM
CIRCUIT 2=30mA
GROUND CURRENT ALARM
CIRCUIT 3=50mA
GROUND CURRENT ALARM
CIRCUIT 4=40mA
GROUND CURRENT ALARM
CIRCUIT 5=30mA
GROUND CURRENT ALARM
CIRCUIT 6=50mA
-
5/28/2018 Pn 80505
44/76
44
TC 1818a Control Module
Press the HEATER ENABLE key to display if the heater status is set as enabled. The heaterstatus can be enabled, disabled, forced on, or tripped.
Refer to page 54 for more details on alternate HEATER ENABLE prompt messages.
Subsequently, the TC 1818a returns to Scan Mode.
HEATER
ENABLE
RETURN TO SCAN MODE
HEATER
CIRCUIT 1= ENABLED
HEATER
CIRCUIT 2= ENABLED
HEATER
CIRCUIT 3= ENABLED
HEATER
CIRCUIT 4 = ENABLED
HEATER
CIRCUIT 5 = ENABLED
HEATER
CIRCUIT 6 = FORCED ON
-
5/28/2018 Pn 80505
45/76
45
Operating Guide
Press the HIGH TEMP ALARM key to display the High Temperature Alarm Setpoint andHighest Temperature Seen for all circuits as typically shown.
The TC 1818a will then begin to scroll through the highest stored value of temperaturefor each circuit.
Subsequently, the TC 1818a returns to Scan Mode.
RETURN TO SCAN MODE
HIGH TEMP ALARM
CIRCUIT 1=130F
HIGH TEMP ALARM
CIRCUIT 2=20F
HIGH TEMP ALARM
CIRCUIT 3=700F
HIGH TEMP ALARM
CIRCUIT 4=130F
HIGH TEMP ALARM
CIRCUIT 5=200F
HIGH TEMP ALARM
CIRCUIT 6= 700F
HIGH
TEMP
ALARM
HIGH TEMP SEEN
CIRCUIT 1=200F
HIGH TEMP SEEN
CIRCUIT 2=300F
HIGH TEMP SEEN
CIRCUIT 3=700F
HIGH TEMP SEEN
CIRCUIT 4=200F
HIGH TEMP SEEN
CIRCUIT 5=300F
HIGH TEMP SEEN
CIRCUIT 6=700F
-
5/28/2018 Pn 80505
46/76
46
TC 1818a Control Module
Press the HIGH CURRENT alarm key to display the High Heater Current Alarm setpointas typically shown.
The TC 1818a then returns to Scan Mode.
Press the DATA HWY key to display the Data Highway address setting for the module andcheck the data highway communication status (respectively).
A "COMM STATUS" of IN or OUT denotes direction of the message transmittals (theabsence of IN or OUT indicates that data highway communications link has not been
established). Subsequently, the TC 1818a then returns to Scan Mode.
HIGH
CURRENT
ALARM
HIGH CURRENT ALARM
CIRCUIT 1=5.0A
HIGH CURRENT ALARM
CIRCUIT 2= 10A
HIGH CURRENT ALARM
CIRCUIT 3=30A
HIGH CURRENT ALARM
CIRCUIT 4=5.0A
HIGH CURRENT ALARM
CIRCUIT 5=10A
HIGH CURRENT ALARM
CIRCUIT 6=30A
RETURN TO SCAN MODE
RETURN TO SCAN MODE
DATA
HWY
DATA HIGHWAY ADDRESS=18
COMM STATUS=IN
-
5/28/2018 Pn 80505
47/76
47
Operating Guide
Press the LOW TEMP ALARM key to display the Low Temperature Alarm Setpoint andLowest Temperature Seen for all circuits as typically shown.
The TC 1818a will then begin to scroll through the lowest stored value of temperaturefor each circuit.
Upon completing the display of all the LOW TEMP SEEN data, the TC 1818a returns toScan Mode.
LOW
TEMP
ALARM
LOW TEMP ALARM
CIRCUIT 1=35F
LOW TEMP ALARM
CIRCUIT 2=75F
LOW TEMP ALARM
CIRCUIT 3=450F
LOW TEMP ALARM
CIRCUIT 4=35F
LOW TEMP ALARM
CIRCUIT 5=75F
LOW TEMP ALARM
CIRCUIT 6=450F
LOW TEMP SEEN
CIRCUIT 1=37F
LOW TEMP SEEN
CIRCUIT 2=75F
LOW TEMP SEEN
CIRCUIT 3=550F
LOW TEMP SEEN
CIRCUIT 4=37F
LOW TEMP SEEN
CIRCUIT 5=75F
LOW TEMP SEEN
CIRCUIT 6=550F
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
48/76
48
TC 1818a Control Module
Press the LOW CURRENT alarm key to display the Low Heater Current Alarm setpoint forall circuits as typically shown.
After scanning through all circuits, the TC 1818a returns to Scan Mode.
LOW
CURRENT
ALARM
LOW CURRENT ALARM
CIRCUIT 1=1.0A
LOW CURRENT ALARM
CIRCUIT 2=8.0A
LOW CURRENT ALARM
CIRCUIT 3=12.0A
LOW CURRENT ALARM
CIRCUIT 4=1.0A
LOW CURRENT ALARM
CIRCUIT 5=8.0A
LOW CURRENT ALARM
CIRCUIT 6=12.0A
RETURN TO SCAN MODE
-
5/28/2018 Pn 80505
49/76
49
Operating Guide
UNDERSTANDING ALARM CONDITIONS
When temperature related alarm conditions do occur, the below information may be usefulin establishing the cause and appropriate action.
HIGH TEMPERATURE (HIGH TEMP)
Low Limit: Maintain temperature plus control band valueHigh Limit: 1100oF or 600oCRange: 0oF to 1100oF or 0oC to 600oCCause: Sensed temperature exceeds programmed high temperature
alarm setpointControllerAction Taken: Alarm Only or Alarm and Trip Heater (if trip is set)
LOW TEMPERATURE (LOW TEMP)
Low Limit: -40oF or -40oCHigh Limit: Maintain temperature valueRange: -40oF to 1099oF or -40oC to 599oC
Cause: Sensed temperature is below programmed low temperaturealarm setpointController
Action Taken: Alarm Only
RTD FAULT
Cause: RTD resistance not in the 70 to 300 ohms rangeController
Action Taken: Alarm and heater are energized or alarm and heater are turnedoff depending on programming configuration.
-
5/28/2018 Pn 80505
50/76
50
TC 1818a Control Module
When heater related alarms occur, the below information may be useful in establishing acause and an appropriate action.
HIGH CURRENT (HIGH CURRENT)
Low Limit: Low current alarm valueHigh Limit: 30.0ARange: 1 to 30.0ACause: Heater current is more than high current alarm valueControllerAction Taken: Alarm Only or Alarm and Trip Heater (if trip is set)
LOW CURRENT (LOW CURRENT)
Low Limit: 0.0AHigh Limit: High current alarm valueRange: 0 to 30.0ACause: Heater current is less then low current alarm valueControllerAction Taken: Alarm Only
HIGH GROUND CURRENT (HIGH GND CUR)
Low Limit: 30mAHigh Limit: 150mARange: 30 to 150mACause: An excessive heater/wiring leakage current is presentControllerAction Taken: Alarm Only or Alarm and Trip Heater (if trip is set)
CIRCUIT FAULT (CKT FAULT)
Checks For: Damaged relay or loss of current during "heater on" cycleCause: Relay locked open or closed, breaker off, or heater/wiring disconnectedControllerAction Taken: Alarm Only
POWER OFF
Cause: Loss of voltage to unitControllerAction Taken: NoneReset Procedure: Power off message will clear itself after 30 minutes or can be manually cleared with the ALARM ACK key
-
5/28/2018 Pn 80505
51/76
51
Operating Guide
CONFIGURING THE TC 1818A FOR AMBIENT SENSING OR DUAL RTD CONTROL
The TC 1818a is standardly configured for process sensing with one RTD input assignedto each relay output circuit. The operating descriptions in this manual to this point havecovered using the TC 1818a when set up as a "Standard Control" configuration. Dependingon the firmware level, the TC 1818a can also be factory or field configured for up to fiveother control configurations. The six possible control configurations are identified in thebelow list.
Configuration DescriptionSINGLE RTD INPUTS Conventional process sensing control - one RTD input for
each heat tracing circuit.1 AMB/SINGLE Ambient sensing RTD in Circuit 1 controlling allRTD INPUTS designated ambient sensing circuits with conventional process sensing control on all process sensing circuits (one RTD input for each heat tracing circuit).
2 AMB/SINGLE Ambient sensing RTD's in Circuit 1 and 2 and controllingRTD INPUTS all designated ambient sensing circuits based on the lowest RTD reading with conventional process sensing
control on all process sensing circuits (one RTD input for each heattracing circuit).
1 or 2 RTD INPUTS Single and dual RTD process sensing control - one or two RTD inputs for each heat tracing circuit as designated.
1 AMB/ 1 or 2 RTD INPUTS Ambient sensing RTD in Circuit 1 controlling alldesignated ambient sensing circuits with single or dualRTD process sensing control on all process
sensing circuits.
2 AMB/ 1 or 2 RTD INPUTS Ambient sensing RTD's in Circuit 1 and 2 and controllingl all designated ambient sensing circuits based on the lowest RTD reading with single or dual RTD process sensing control on all process sensing circuits.
-
5/28/2018 Pn 80505
52/76
52
TC 1818a Control Module
In order to factory or field program the TC 1818a for any configuration other than thestandard SINGLE RTD INPUTS, first momentarily press the DATA HWY key.
Next press and hold the MAINTAIN TEMP key for about 5 seconds.
The following prompt window message will next appear.
Press the CONFIG key.
The current setting for the TC 1818a control configuration will appear.
Press the UP arrow key and ENTER to change or press the DOWN arrow key and ENTERto accept the current configuration and then return to SCAN MODE.
DATA
HWY
RETURN TO SCAN MODE
MAINTAIN
TEMP
ITEM TO CONFIGURE
CONFIG
SINGLE RTD INPUTSCHANGE? (Y/N)
-
5/28/2018 Pn 80505
53/76
53
Operating Guide
It is intended that this configuration setting be set prior to programming in all heat tracingcircuit parameters. If it is necessary to change the settings once the unit is installed in thefield, it is recommended that all heat tracing circuit parameters be entered again.
ALTERNATE CONTROL CONFIGURATIONS IN OPERATION
Information screens will vary slightly depending on which alternate control configurationis enabled. A summary of the alternate message screens which may be seen during theSCAN MODE of operation are listed below:
Where a heater circuit on the TC 1818a controller hasbeen programmed for ambient sensing control opera-tion, this information screen indicates the temperaturebeing read by the RTD on this circuit number and alsoindicates the percentage of power being supplied tothe circuit. When the power clamping function orambient proportional control is utilized, the percentage
"time on" can vary from 100% to as low as 20%.This information screen indicates that the tempera-ture being read by the RTD on this circuit number is51oF and that the heater has been "forced on". Inthe "forced on" mode, the circuit will remain on aslong as no programmed alarm limits are exceeded.This programmed setting is primarily used for fielddiagnostic testing.
Where a heater circuit on the TC 1818a controllerhas been programmed for process temperaturesensing operation, this information screen indicatesthe temperature being read by the RTD on this circuitnumber as well as the actual maintain temperatureprogrammed.
Message Window Description
CKT 1 TEMP = 51F
HEATER POWER= 100% AMB
CKT 1 TEMP = 51F
HEATER FORCED ON
CKT 1 TEMP = 51F MAINTAIN TEMP = 50oF PS
-
5/28/2018 Pn 80505
54/76
54
TC 1818a Control Module
CKT 1 TEMP = 51F, 53F
HEATER FORCED ON
CKT 1 TEMP = 51F, 53F
MAINTAIN TEMP = 50F PS
CKT 1 TEMP = 51F, 53F
HEATER POWER=100% AMBWhere a heater circuit on the TC 1818a controller hasbeen programmed for ambient sensing control op-eration with dual RTD inputs, this information screenindicates the temperatures being read by the RTDs onthis circuit number and also indicates the percentageof power being supplied to the circuit. When thepower clamping function or ambient proportionalcontrol is utilized, the percentage "time on" can varyfrom 100% to as low as 20%.
This information screen indicates that the tempera-tures being read by the dual RTDs programmed tosense temperature for this circuit number and that theheater has been "forced on". This program setting isprimarily used for field diagnostic testing.
Where a heater circuit on the TC 1818a controllerhas been programmed for dual RTD process tem-perature sensing operation, this information screenindicates the temperatures being read by the RTDson this circuit number as well as the actual maintaintemperature programmed.
When inquiring as to the heater status (enabled, disabled, forced on, or tripped) by pressingthe HEATER ENABLE key, the following alternate message screens may be seen:
This information screen identifies the Circuit 3 as be-ing enabled as an ambient sensing RTD circuit.
This information screen identifies the Circuit 3 asbeing enabled as a process temperature sensingRTD circuit.
This information screen identifies the Circuit 4 asbeing enabled with one RTD sensor input.
This information screen identifies the Circuit 4 as be-ing enabled with dual RTD sensor inputs.
Message Window Description
HEATER
CIRCUIT 3= ENABLED AMB
Message Window Description
HEATER
CIRCUIT 3= ENABLED PS
HEATER
CIRCUIT 4= ENABLED 1RTD
HEATER
CIRCUIT 4= ENABLED 2RTD
-
5/28/2018 Pn 80505
55/76
55
Operating Guide
PROGRAMMING AND OPERATING THE TC 1818A IN AN AMBIENT
SENSING CONTROL MODEThe TC 1818a control module should first be configured to allow wide band proportionaltemperature control in ambient sensing control applications.
The simplest controller configuration to implement ambient sensing control are the singleRTD input controller configurations listed below:
When programmed for one of these controller configurations, the TC 1818a controlmodule will accept one ambient sensing RTD input (Circuit 1) or two ambient sensingRTD inputs (Circuit 1 and 2), and will read this input or the lower of the two values into allother ambient sense enabled circuits for control purposes. While most of the TC 1818aoperation in this mode is identical to that previously described (recognizing, of course,that the temperature being acted upon is the ambient value), there are a few differenceswhich are described in the following sections.
1 AMB/ SINGLE RTDINPUTS
2 AMB/ SINGLE RTD
INPUTS
-
5/28/2018 Pn 80505
56/76
56
TC 1818a Control Module
HEATER ENABLE (PROGRAM MODE)
To program the control mode of each circuit, press sequentially the PROG key and theHEATER ENABLE key. The TC 1818a will prompt for the selection of the desired circuit(or All the Same Value).
Press the UP or DOWN arrow key and ENTER. The TC 1818a will indicate the presentsetting (Ambient Sensing, Pipe Sensing, or Disabled). Press the UP arrow key to changethe value and then the ENTER key to accept the new value.
The configuration restrictions on combinations of process (pipe) sensing and ambientsensing circuits are:
Circuit 1 for single RTD sensor input must be retained as ambient sensing controlcircuit.
Circuit 1 and 2 for dual RTD sensor inputs must be retained as ambient sensingcontrol circuits.
Proportional control mode must be utilized on both ambient and process (pipe)
sensed circuits.
PROGRAM CIRCUIT=1
ENABLED (PIPE SENSE)
CHANGE? (Y/N)
ENABLED (AMBIENT SENSE)
CHANGE? (Y/N)
-
5/28/2018 Pn 80505
57/76
57
Operating Guide
MAINTAIN TEMP (PROGRAM MODE)
In order to set the maintain temperature when using ambient sensing control, press thePROG key. The TC 1818a will prompt for the function to program.
Press the MAINTAIN TEMP key. The TC 1818a will next prompt for the selection of thedesired circuit (or All the Same Value).
Press the UP or DOWN arrow key and ENTER. The TC 1818a will prompt for the maintaintemperature as follows:
When in ambient sensing control mode, the minimum ambient temperature should beentered here (this is the 100% heater power value in wide band proportional control). To
change the present maintain temperature value, press the UP or DOWN arrow key untilthe proper value is displayed.
Press the ENTER key to accept the new value. The TC 1818a will then return to the ScanMode operation.
PROGRAM MODE ENABLED
SELECT FUNCTION KEY
PROGRAM CIRCUIT=2
MAINTAIN TEMP=120F
NEW VALUE=120F
MAINTAIN TEMP=120F
NEW VALUE=-20F
-
5/28/2018 Pn 80505
58/76
58
TC 1818a Control Module
CONTROL BAND (PROGRAM MODE)
In order to set the control range for ambient sensing control, press the PROG key. TheTC 1818a will prompt for the function to program.
Press the CONTROL BAND key. The TC 1818a will next prompt for the selection of thedesired circuit (or All the Same Value).
Press the UP or DOWN arrow key and ENTER. The TC 1818a will prompt for the controlband as follows:
PROGRAM MODE ENABLED
SELECT FUNCTION KEY
PROGRAM CIRCUIT=1
CONTROL BAND=5F
NEW VALUE=5F
-
5/28/2018 Pn 80505
59/76
59
Operating Guide
When in wide band ambient sensing control mode, the control band will be between theminimum ambient temperature (the 100% heater power value) and the ambient temperatureat which power off is to occur (the process fluid minimum desired temperature value).To change the present control band value, press the UP or DOWN arrow key until theproper value is displayed.
Press the ENTER key to accept the new value. Note that with these settings, full powerto the heaters will occur at -20F and power will turn off at 50F. The TC 1818a will thenreturn to the Scan Mode operation.
SCANNING DATA (DISPLAY MODE)
When in the SCAN mode of operation, the TC 1818a will display the following screen onall ambient sensed control circuits in a single RTD controller configuration.
The TC 1818a thus indicates the RTD input temperature which represents the ambienttemperature values measured on Circuit 1 (and Circuit 2 if configured) and is additionallyindicating the power level that this particular circuit is operating at.
Circuit 1 Ambient
Sensing RTDor
Circuit 1and 2Ambient SensingRTD's
CONTROL BAND=5F
NEW VALUE=70F
RETURN TO SCAN MODE
CKT 3 TEMP= -20F, -19F
HEATER POWER=100% AMB
CKT 3 TEMP= -20F
HEATER POWER=100% AMB
-
5/28/2018 Pn 80505
60/76
60
TC 1818a Control Module
PROGRAMMING AND OPERATING THE TC 1818a WITH DUAL INPUT RTDS
FOR A SINGLE CONTROL CIRCUITThe TC 1818a control module may be factory or field configured to allow for using singleor dual RTD inputs on either ambient sensing or process sensing applications. The fol-lowing three controller configuration options are available for this purpose:
Controller Configuration Application
1or 2 RTD INPUTS Process sensing applications
1AMB/ 1 or 2 RTD INPUTS Process sensing applications and single ambientsensor in first circuit
2 AMB/ 1 or 2 RTD INPUTS Process sensing app lic ations and ambien tsensors in first and second circuit
The above factory configuration options are specifically designed for controlling a heattracing circuit with either single or dual RTD input sensor control circuits. When settingup circuit assignments for these factory configuration types, the heat tracing circuits thatare to be set up with dual RTD's will always be assigned in pairs. That is, the RTD's onCircuit 1 and 2, Circuit 3 and 4, Circuit 5 and 6, and so on should be considered as pairedcircuits. As one example, when dealing with dual RTD's with process sensing, if Circuit6 were to be programmed for a dual RTD input control the TC 1818a controller woulduse the RTD's in Circuit 5 and 6 in controlling the power relay for Circuit 6. The relayassociated with Circuit 5 could be disabled or could be used to control a second pass ofheater if Circuit 5 were also configured as a dual RTD process sensing input (using RTD
5 and RTD 6 for control).
-
5/28/2018 Pn 80505
61/76
61
Operating Guide
As another example, in a "1 AMB/ 1 or 2 RTD INPUTS" controller configuration, if Circuit6 were to be programmed for a dual RTD input control it would again use the RTD's inCircuit 5 and 6 in controlling the power relay for Circuit 6. In this case, however, the relayon Circuit 5 could additionally be used as a control power relay on an ambient sensedcircuit operating based on the RTD input from Circuit 1.
The specific control strategy for a dual RTD control circuit in any of these factory con-figuration types is as follows:
The heat tracing circuit controls off of the lowest RTD reading exceptin the event that a temperature value on either RTD falls within thealarm dead band of the high temperature alarm value. In this event,that RTD will become the controlling temperature reading.
The heat tracing circuit will go into low or high alarm if either RTDreading in the pair exceeds the programmed low or high alarmlimit value.
For more details on setting up a mixed single and dual RTD control mode, refer to Examples5 and 6.
-
5/28/2018 Pn 80505
62/76
62
TC 1818a Control Module
TYPICAL CONTROL APPLICATIONS
EXAMPLE 1 - AMBIENT SENSING FREEZE PROTECTION -PROPORTIONAL CONTROL WITH SOLID STATE RELAY OUTPUT
When configured with solid state relays, the TC 1818a may be used in ambient sensingwide band proportional control. This method of control is ideal in tracing designs wheresimple ambient sensing RTD's and freeze protection is required. In this mode of control,the TC 1818a will (by cycle omission techniques) proportionally increase the power tothe heat tracing as the ambient temperature drops. A typical application for this type ofcontrol might be the freeze protection of water lines in a water treatment facility. Assume
the following heat tracing operating design Heat Tracing Type: Self-Regulating Parallel Heater Cable Safety Factor: 30% Minimum Ambient: -20F Minimum Water Maintain Temp: 40F
A typical list of the key TC 1818a settings is as given below:
Control Parameter Setting
Controller Configuration 1 AMB/ SINGLE RTD INPUTS Control Method Proportional Maintain Temperature* -20F Percent Power at Maintain Temp. 100% Control Band 60F
* Note that the maintain temperature is the temperature where 100% power issupplied to the heater.
Having set in these values along with appropriate alarm settings, the following control cantypically be achieved.
PipeTemperature
100%
0%-20
Ambient Temperature (degF)
20%Power
40
55
35
75
Pipe
Power
-
5/28/2018 Pn 80505
63/76
63
Operating Guide
EXAMPLE 2 - FOUNDATION HEAVE PROTECTION - PROPORTIONAL WTH SELF-ADJUSTCONTROL WITH SOLID STATE RELAY OUTPUT
Cryogenic vessels and refrigerated rooms often utilize heating systems beneath to preventheaving due to the freezing of the soil/foundation base structure. A typical heat tracingapplication of this type might require an operating tracing design as follows:
Internal Room Temperature: -27F Minimum Maintain Temperature of Soil: 40F Maximum Foundation Temperature: 80F
Heater Cable Type: Constant Wattage Design Safety Margin: 42%
The TC 1818a control module using foundation temperature sensing RTD's in each heatingzone can be typically set at the control settings given below:
Control Parameter Setting
Controller Configuration SINGLE RTD INPUTS Control Method Proportional with Self-Adjust
Maintain Temperature 50F Control Band 30F High Alarm Temperature 90F High Temperature Trip On Low Alarm Temperature 38F
-
5/28/2018 Pn 80505
64/76
64
TC 1818a Control Module
These settings assume the system was designed with a 42% safety margin. By clampingthe power to the 70% value, the heater output should match the heat load. The heatershould be continually operating using cycle omission techniques in a warming mode(and will thus minimize condensation within the heating system). After attaining 50F,the TC 1818a will linearly reduce power (the minimum level of power is 20% after 9Frise) until an equilibrium value between 50F and 80F is obtained. In the unlikely eventthat the 80F setting is exceeded, the control will de-energize the heater circuit. A hightemperature alarm will activate should the RTD sensor detect a temperature above the90F value and the circuit will trip.
Having set in these values as well as the appropriate other limit/control values, the follow-ing typical control can be achieved.
100%
0%
50
Soil Temperature (degF)
20%
Typical ControlledSoil Temperature
Power
70%
805952
-
5/28/2018 Pn 80505
65/76
65
Operating Guide
EXAMPLE 3 - PROCESS TEMPERATURE MAINTENANCE - PROPORTIONAL CONTROLWITH SOLID STATE RELAY OUTPUT
The TC 1818a features the option of proportional control for those applications whereclose temperature control is required on process piping which may have varying processtemperature conditions. A typical heat traced piping application might be a corn syrupviscosity control application. Due to the sensitivity of the syrup to color degradation thesyrup must be maintained below 90F. Typical heat tracing design requirements are listedas follows:
Syrup Maintain Temperature: 80F
Heater Cable Type: Constant Wattage Maximum Syrup Temperature: 90F
The TC 1818a control module utilizing pipe sensing RTD's could be typically set as shownbelow:
Control Parameter Setting
Controller Configuration SINGLE RTD INPUTS Control Method Proportional
Maintain Temperature 80F Control Band 10F High Alarm Temperature 90F High Temperature Trip On Low Alarm Temperature 75F Power at Maintain Temperature 100%
Having set in these values as well as the appropriate other limit/control values, the follow-ing typical control can be achieved.
100%
0%
80Pipe Temperature (degF)
20%
PipeControlPoint
Power
9083
Controlband
-
5/28/2018 Pn 80505
66/76
66
TC 1818a Control Module
EXAMPLE 4 - PROCESS TEMPERATURE CONTROL - MECHANICAL RELAYS
Extremely versatile, the TC 1818a can be configured with RM-1 or RM-2 mechanical relayoutput options. This option is often selected in high heat output tracing applications whereeither high current or high voltage switching is required. One such tracing applicationmight be the temperature maintenance of a long sulfur transfer line. Typical tracing designrequirements are listed as follows:
Heater Cable Type: Mineral Insulated Series Cable Voltage Switched: 277 Vac Current Switched: 49A
Sulfur Maintenance Temperature: 282F Sulfur Freeze Point: 260F Sulfur Congeal Point: 320F
The TC 1818a control module with pipe sensing RTD's could be typically as shownbelow:
Control Parameter Setting
Controller Configuration SINGLE RTD INPUTS
Control Method On/Off Maintain Temperature 282F Control Band 5F High Alarm Temperature 300F Low Alarm Temperature 260F
Having set in these values as well as the appropriate other limit/control values, the follow-ing typical control can be achieved.
290
PipeTemperature(degF)
280
Time
-
5/28/2018 Pn 80505
67/76
67
Operating Guide
EXAMPLE 5 - PROCESS TEMPERATURE CONTROL - SINGLE AND DUAL RTD SENSING
It is sometimes considered advantageous to use dual RTD sensors on a critical heat tracingapplication such as a 50% caustic line. In this way, the power to the heater can be basedon the input of two discrete temperature inputs rather than one. In addition, in the eventof an RTD fault, the operator can be alarmed, the circuit can be acknowledged, and theRTD can be repaired without turning the heat tracing circuit OFF. For this application, thetypical design requirements are as listed below:
Product Maintenance Temperature: 80F Product Freeze Point: 54F
Heater Cable Type: Self Regulating Parallel Cable Maximum Caustic Temperature: 100F
The TC 1818a control module utilizing pipe sensing RTD's could be typically set as indi-cated below:
Control Parameter Setting
Controller Configuration 1 or 2 RTD INPUTS Control Method Proportional
Maintain Temperature 80F Control Band 5F High Alarm Temperature 90F High Temperature Trip ON Low Alarm Temperature 60F Power at Maintain Temperature 100%
-
5/28/2018 Pn 80505
68/76
68
TC 1818a Control Module
Considering that we have only three heat tracing circuits, the TC 1818a would be set upas a six point unit with a controller configuration of "1 or 2 RTD INPUTS".
The heat tracing circuit assignments would be as follows:
Circuit No. Setting
1 Enabled (2 RTD) 2 Disabled 3 Enabled (2 RTD)
4 Disabled 5 Enabled (2 RTD) 6 Disabled
In this case power relays on circuits 2, 4 and 6 will not be connected to the heattracing.
Alternately, in a case where both power relays were to be used to maximize the currentswitching capability, the following circuit assignments could also be used.
Circuit No. Setting
1 Enabled (2 RTD) 2 Enabled (2 RTD) 3 Enabled (2 RTD) 4 Enabled (2 RTD) 5 Enabled (2 RTD) 6 Enabled (2 RTD)
In this circuit assignment, all circuit relays are controlling off of dual RTD inputs. Notethat this configuration is also applicable in center feed arrangements for two heat tracingcircuits running in opposite directions from power.
-
5/28/2018 Pn 80505
69/76
69
Operating Guide
EXAMPLE 6 - PROCESS TEMPERATURE AND AMBIENT SENSING CONTROL - SINGLEAND DUAL RTD SENSING
In many applications there are a variety of control applications. Some may be the criticalapplications such as the 50% caustic in Example 5 and some may be simple water freezeprotection. For this combination application, the typical design requirements are as listedbelow:
50% Caustic Product Maintenance Temperature: 80F Product Freeze Point: 54F
Heater Cable Type: Self Regulating Parallel Cable Maximum Caustic Temperature: 100F Number of Circuits: Two Process Sensing
Water Product Maintenance Temperature: 50F Product Freeze Point: 32F Heater Cable Type: Self Regulating Parallel Cable Number of Circuits: Four Ambient Sensing
The TC 1818a control module utilizing pipe sensing RTD's could be typically set as indi-cated below:
Control Parameter Setting
Controller Configuration 1 AMB/ 1 or 2 RTD INPUTS Control Method On-Off Caustic Circuits Maintain Temperature 80F
Control Band 5F High Alarm Temperature 90F High Temperature Trip ON Low Alarm Temperature 60F Water Circuits Maintain Temperature 50F Control Band 5F High Alarm Temperature 120F High Temperature Trip Off
Low Alarm Temperature 40F
Considering that we have only six heat tracing circuits, the TC 1818a would be set up as asix point unit with a controller configuration of "1 AMB/ 1 or 2 RTD INPUTS".
-
5/28/2018 Pn 80505
70/76
70
TC 1818a Control Module
The heat tracing circuit assignments would be as follows:
Circuit No. Setting
1 Enabled (Ambient Sensed) 2 Enabled (Ambient Sensed) 3 Enabled (2 RTD) 4 Enabled (Ambient Sensed) 5 Enabled (2 RTD) 6 Enabled (Ambient Sensed)
In this case, power relays on circuits 1, 2, 4 and 6 will be controlling ambient sensed cir-cuits based on the RTD input on Circuit 1. Circuit 3 and its power relay will be controllingbased on the RTD inputs from Circuit 3 and Circuit 4. Circuit 5 and its power relay will becontrolling based on the RTD inputs from Circuit 5 and Circuit 6.
-
5/28/2018 Pn 80505
71/76
71
Operating Guide
COMMUNICATIONS
The TC 1818a is standardly provided with an RS485 communications port. This port allowsfor communication through a Modbus ASCII and RTU protocols to a PC workstation orto the facility distributed control system (DCS). Through this communications link, mostof the operating parameters which are programmable at the module can be accessible atthe central PC workstation or DCS system console.
For communications linking between the TC 1818a and a PC workstation, refer to theTraceViewTM Network Explorer Operating Guide.
For communications linking information between the TC 1818a and the facility distributed
control system (DCS), refer to DCS Operations Guide, SWM-008.X.
-
5/28/2018 Pn 80505
72/76
72
TC 1818a Control Module
OPTIONS AND ACCESSORIES
Thermon can provide a variety of options and accessories to complete the installation.Some typical accessories are listed below.
SW-TVNE
TraceViewTM Network Explorer is a PC-based communications software package developedspecifically for centralized control and monitoring of the various field mounted HeatChekTMunits. TraceView Network Explorer, operating within the Windows environment, allows thechanging of control and alarm setpoints, adjustment of controller operating parameters, and
acknowledgement of all alarms from the control room or motor control center. TraceViewNetwork Explorer permits the viewing of heat tracing isometrics on demand and allowsonline access to heat tracing and controller diagnostic information. Continuous data log-ging and reporting of heat tracing operations/alarm status as well as historical trend datastorage (for later retrieval to spreadsheet or database software) is also provided.
TraceView Network Explorer can be configured for up to sixteen communication ports(with each program instance allowing up to 247 HeatChek control and monitoring units1).Communications can be achieved at distances up to 4000 ft. (1220 m) on the RS485 two
wire twisted shielded communication link.
RTD-100
This three wire resistance temperature detector (RTD) is rated to 500F (260C). Providedwith a standard aluminum termination head, the RTD sensor is insulated with fiberglassand shielded with Type 316 stainless steel housing.
IM-1Interface module for linking RS485 two-wire twisted shielded pair into RS232 port ofPC.
DCALXX
Interposing DC alarm relays can be added for use in ordinary and hazardous locations tointerface to plant DCS systems.
1A minimum of one repeater module is recommended for every thirty-one control andmonitoring modules configured into a data highway.
-
5/28/2018 Pn 80505
73/76
73
Operating Guide
HELP
This HeatChek control and monitoring unit is intended to be used with only the supportof this instruction booklet. If special support needs do arise, Thermon provides localsupport through its area representatives and affiliate companies as well as through a tollfree user support line.
For toll free support dial 1-800-820-HEAT(4328). Information may also be obtained byaccessing the Thermon Website at www.Thermon.com.
-
5/28/2018 Pn 80505
74/76
74
TC 1818a Control Module
PROG
MAINTAIN TEMPERATURE
MAINTAIN
TEMP ENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
PROG
CONTROL BAND
CONTROL
BAND ENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
PROG
HIGH TEMPERATURE ALARM
HIGH
TEMP
ALARM
ENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
ENTER
RESET HIGH
TEMP SEEN
PROG
LOW TEMPERATURE ALARM
LOW
TEMP
ALARMENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
ENTER
RESET LOW
TEMP SEEN
PROG
HIGH CURRENT ALARM
HIGH
CURRENT
ALARMENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
PROG
LOW CURRENT ALARM
LOW
CURRENT
ALARMENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
ATTACHMENT A: TC 1818A COMMAND FLOWCHART
Note: Security key must be in the vertical position for the TC 1818 to allow programming.
-
5/28/2018 Pn 80505
75/76
75
Operating Guide
ATTACHMENT A: TC 1818A COMMAND FLOWCHART
Note: Security key must be in the vertical position for the TC 1818 to allow programming.
PROG
GROUND CURRENT ALARM
GROUND
CURRENT ENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
PROG
DATA HIGHWAYDATA
HWY ENTER ENTER
PROGRAM
CIRCUIT
NEW
VALUE
CIRCUIT #
REPORTED FAULT
CIRCUIT #
REPORTED FAULT ACK
ALARM
ACK
ALARM ACKNOWLEGE
ALARM
ACK
REPORTED FAULT HASBEEN ACKNOWLEDGED
PROG
HEATER ENABLE/DISABLE
HEATER
ENABLE ENTER
PROGRAM
CIRCUIT
FORCEHEATER ON
CIRCUIT #
ENABLE (PIPE SENSE)
YES YES
NO NO
CIRCUITFORCED ON
CIRCUITENABLED/DISABLED
CHANGE?
CIRCUIT #ENABLE (AMBIENT SENSE)
CIRCUIT #
DISABLE
-
5/28/2018 Pn 80505
76/76
THERMON. . . The Heat Tracing Specialists
100 Thermon Dr. P.O. Box 609 San Marcos, TX 78667-0609 Phone: (512) 396-5801Facsimile: (512) 396-3627 1-800-820-HEAThttp://www.thermon.com Part Number: 80505