pow sys ope & con - m rajkuamr - iii eee
TRANSCRIPT
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 1/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
UNIT-1
INTRODUCTION
1. What ! "#a$ %'()*
Load curve is the curve drawn between the variations of load on the power
station with reference to time.
+. What ! $a", "#a$ %'()*
Daily load curve is the curve drawn between the variations of load with
reference to various time period of day.
3. What ! #th", "#a$ %'()*
Monthly load curve is plotted from the average value of the power at a
month for a different time periods. It is obtained from daily load curve.
/. What ! ,)a'", "#a$ %'()*
Yearly load curve is obtained from monthly load curve which is used to find
annual load factor.
. What ! %#)%t)$ "#a$*
Connected load is the sum of continuous ratings of all the equipments
connected to supply systems.
6. What ! a $)a$*
Maximum demand is the greatest demand of load on the power station
during a given period.
2. What ! $)a$ a%t#'*
Demand factor is the ratio of maximum demand to connected load.
Demand factor !max demand"# !connected load"
4. What ! a()'a5) $)a$*
$verage demand is the average of loads occurring on the power station in a
given period !day or month or year".
Daily average demand !no of units generated per day"# !%& hours"
Monthly average demand !no of units generated in month"# !no of
hours in a month"
in the order of descending magnitudes.
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 1
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 2/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
;.What ! "#a$ a%t#'*
Load factor the ratio of average load to the maximum demand during a given
period.
10. What ! $()'!t, a%t#'*
Diversity factor is the ratio of the sum of individual maximum demand on power
station.
11. What ! %a<a%t, a%t#'*
Capacity factor is the ratio of actual energy produced to the maximum possible
energy that could have been produced during a given period.
1+. What ! <"at !) a%t#'*
'lant use factor is the ratio of units generated to the product of plant capacity and
the number of hours for which the plant was in operation.
13. What ! "#a$ $'at# %'()*
Load duration curve is the curve obtained when the load elements of a load curve are
arranged.
1/. D)) "#a$ a$ "!t #t th) t,<)! # "#a$!.
Load is a device that taps energy from networ(.
)ypes*
+. Lighting and heating loads.
%. Induction motors. ,. -lectronic devices
1. Wh, th) ')=)%, a$ (#"ta5) a') t# >) ')5"at)$ <#?)' !,!t)*
oltage regulation*
oltage regulation helps in maintaining the voltage at the load terminals within
prescribed limits under conditions/ by employing suitable voltage control equipment.
16.What ! )at >, ')) 5#()'#' #<)'at#*
0nly governor control is called as free governor action. It can be obtained by deactivating
the integral controller.
12.M)t# th) %#$t#! #' #<)'at5 t?# !,%h'##! a%h)! <a'a"")".
!i" )erminal voltage must be same.
!ii" 1ystem frequency must be same.
!iii" 'hase sequence must be same
14.D)) $a",8 #th",8 aa" "#a$ %'().$a", "#a$ %'().
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) +
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 3/19
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 4/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
3. What a') th) %#<#)t! # !<))$ 5#()'#' !,!t) # a a"t)'at#'* D)'() a
t'a!)' %t# a$ !9)t%h a >"#%9 $a5'a
Load frequency control
-conomic dispatch control
$utomatic voltage regulator
/. Wth )at !9)t%h $)!%'>) th) P- a$ - %#t'#" !t'%t')
- C0<)=0L L00'
'28 C0<)=0L L00'
'rimary $L8C
1econdary $L8C:
. B')", $!%!! th) %"a!!%at# # "#a$! a$ "!t #t th) <#'tat %ha'a%t)'!t%!
# (a'#! t,<)! # "#a$!
1ystem load variation
'lant Capacity 8actor*
'lant 7se 8actor
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) /
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 5/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
UNIT-II
REAL POWER –REUENCY CONTROL
1. What ! th) a#' %#t'#" "##<! !)$ "a'5) 5))'at#'!*
)he ma>or control loops used in large generators are
i. $utomatic voltage regulator !$="
ii. $utomatic load frequency control !$L8C".
+. What ! th) !) # !)%#$a', "##<*
1econdary loop is used to maintain the fine ad>ustment of the frequency/ and also
by reset action maintains proper M: interchange with other pool members. )his loop is
insensitive to rapid load and frequency changes but focuses instead on drift li(e changeswhich ta(e place over periods of minutes.
3. What ! th) a$(ata5) # AR "##< #()' ALC*
)he advantage of $= loop over $L8C is very fast and therefore there is a
tendency/ for the $= dynamics to settle down before they can ma(e themselves felt in
the slower load frequency control channel.
/. What ! th) $)')%) >)t?)) "a'5) a$ !a"" !5a" aa",!!*
)he difference between large and small signal analysis is given below.Large signal analysis is used where voltage and power may undergo sudden
changes of magnitude that may approach +44 percent of operating values.7sually this type of analysis leads to differential equations of non2linear type.
.What ! th) )%t)'*
)he exciter is the main component in $= loop. It delivers the DC power to the
generator field. It must have adequate power capacity and sufficient speed of response
!rise time less than 4.+ sec".
6. What ! th) %t# # AR*
)he function of the $= is to provide constancy of the generator terminal voltage
during normal/ small and slow changes in the load.
2. E<"a a>#t !tat% AR "##<.
In a static $= loop/ the execution power is obtained directly from the generator
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5)
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 6/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
terminals or from the station service bus. )he $C power is rectified by thyristor bridges
and fed into the main generator field via slip rings. 1tatic exciters are very fast and
contribute to improved transient stability.
4. W't) th) !tat% <)'#'a%) # AR "##<.
1tatic performance of $= loop is to regulate the terminal ?? to within required
static accuracy limit/ have sufficient speed of response and be stable.
;. What ! th) $!a$(ata5) # h5h "##< 5a* H#? t ! t# >) )"at)$*
)he disadvantage of high loop gain is that it causes undesirable dynamic
response/ possibly instability. 3y adding series $<D#0= feedbac( stability compensation
to the $= loop/ this conflicting situation can be resolved.
10. What a') th) ))%t! # 5))'at#' "#a$5 AR "##<*
-ffects of generator loading in $= loop is given below. $dded load does not change the basic
features of the $= loop@ it will however affect the values of both gain factor Af and the field
constant. Bigh loading will ma(e the generator wor( at higher magnetic saturation levels. )his
means smaller changes in ?-? for incremental increases in if/ translating into the reduction of A8.
)he field time constant will li(ewise decrease as generator loading closing the armature current
paths. )his circumstance permits the formation of transient stator currents the existence of which
yields a lower effective field induction
11. What a') th) %t#! # ALC*
8unction of $L8Cs is to maintain desired M: output of a generator unitand assist in controlling the frequency of large interconnection. )he $L8C also helps to
(eep the net interchange of power between pool members at predetermined values.
Control should be applied in such a fashion that highly differing response characteristics
of units of various types are recognied. $lso unnecessary power output changes should
be (ept at a minimum in order to reduce wear of control valves.
1+. S<)%, th) $!a$(ata5) # ALC "##<.
)he disadvantage of $L8C loop is that it will control only during normal changes
in load and frequency. It is unable to provide adequate control during emergency
situations/ when large M: imbalances occur.
13. H#? ! th) ')a" <#?)' a <#?)' !,!t) %#t'#"")$*
)he real power in a power system is being controlled by controlling the driving
torque of the individual turbines of the system.
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 6
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 7/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
1/. What ! th) ))$ #' "a'5) )%ha%a" #'%)! !<))$-5#()'5 !,!t)*
ery large mechanical forces are needed to position the main valve against the
high stream pressure and these forces are obtained via several stages of hydraulic
amplifiers
PART-B
1. U!5 a !<")$ %t#a" $a5'a )<"a th) #<)'at5 )at')! # a !<))$
5#()'5 !,!t).
+. D)()"#< a ")a' ath)at%a" #$)" # a !<))$ 5#()'5 !,!t).
3. E<"a th) t)%h=) (#"()$ "#a$ ')=)%, %#t'#" @LC# a !5") a')a
!,!t)./. E<"a th) <'%<")8 (#"()$ t) ") ')=)%, %#t'#" %a!) # t?# a')a
!,!t).
. D)t)') th) <'a', ALC "##< <a'a)t)' #' a %#t'#" a')a ha(5 th)
#""#?5
Data :
T#ta" 'at)$ a')a %a<a%t,8 P' F+000MW
N#'a" O<)'at5 L#a$8 P$F1000MW
I)'ta %#!tat8 HF !)%
RF+./HG<.. MW @a"" a')a 5))'at#'!
W) !ha"" a!!) that th) "#a$ ')=)%, $)<)$)%, a! ")a' )a5 that th) #"$ "#a$?#"$ %')a!) 1 #' 1 ')=)%, %')a!)!
UNIT-III
REACTIE POWER – OLTAE CONTROL
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 2
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 8/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
1. What a') th) !#'%)! # ')a%t() <#?)'* H#? t ! %#t'#"")$*
)he sources of reactive power are generators/ capacitors/ and reactors.
)hese are controlled by field excitation.
+. () !#) )%tat# !,!t) a<")'.
)he excitation system amplifiers are/
i. Magnetic amplifier
ii. =otating amplifier
iii. Modern electronic amplifier.
3. Wh) ! ))$>a%9 !ta>"t, %#<)!at# !)$*
8eedbac( stability compensation is used to resolve the effect of high loop gain in
$=. Bigh loop gain is needed for static accuracy but this causes undesirable dynamic
response/ possibly instability.
/. () th) %ha'a%t)'!t%! # ") %#<)!at#'!.
)he characteristics of line compensators are/
i. 8erranti effect is minimied.
ii. 7nder excited operation of synchronous generator is not required.
. What ! 9#? a! >a9 # %a<a%t#'!* H#? t ! a$!t)$*
3an( of capacitors is the arrangement of number of capacitors connected in
parallel to get the desired capacitance. )hese can be ad>usted in steps by switching
!mechanical".
6. What ! th) $!a$(ata5) # !?t%h)$ %a<a%t#'! a') )<"#,)$ #' %#<)!at#*
:hen switched capacitors are employed for compensation/ these should
be disconnected immediately under light load conditions to avoid excessive voltage rise
and 8erro resonance in presence of transformers.
2. What a') th) ))%t! # %a<a%t#' !)')! %#<)!at# %'%t*
)he effects of capacitor in series compensation circuit are/
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 4
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 9/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
i. oltage drop in the line reduces.
ii. 'revents voltage collapse.
iii. 1teady state power transfer increases.
iv. )ransient stability limit increases.
4. () t?# 9$! # %a<a%t#'! !)$ !ht %#<)!at#'.
)he two (inds of capacitors used in shunt compensator are/
i. 1tatic ar Compensator !1C"
ii. )hyristor 1witched Capacitor
;. What ! !,%h'##! %#$)!)'*
1ynchronous condenser is a synchronous motor running at no2load and having
excitation ad>ustable over a wide range. It feeds positive $=s into the line under
overexcited conditions and negative $=s when under excited.
10. W't) a>#t !tat% AR %#<)!at#' @SC.
1tatic $= Compensator !1C" comprise capacitor ban( fixed or switched or
fixed capacitor ban( and switched reactor ban( in parallel. )hese compensators draw
reactive power from the line thereby regulating voltage/ improve stability !steady state
and dynamic"/ control overvoltage and reduce voltage and current unbalances. In BDCapplication these compensators provide the required reactive power and damp out sub
harmonic oscillations.
11. What a') !tat% AR !?t%h)! #' !,!t)!*
1tatic $= switches or systems are 1tatic $= compensators which use
switching for $= control. It means that terminology wise 1C11.
1+. () !#) # th) !tat% %#<)!at#'! !%h))!.
1chemes of static compensators
i. 1aturated reactor
ii. )hyristor2 Controlled =eactor !)C="
iii. )hyristor 1witched capacitor !)1C"
iv. Combined )C= and )1C compensator.
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) ;
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 10/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
13. What ! ta< %ha55 t'a!#')'!*
)ap changing transformers are the power transformers and many distribution
transformers which have taps in one or more windings for changing the turns ratio.
1/. W't) th) t,<)! # ta< %ha55 t'a!#')'!.
)ypes of tap changing transformers
i. 0ff2 load tap changing transformers.
ii. )ap changing under load transformers.
1. What ! th) !) # #-"#a$ ta< %ha5)' a$ TCUL*
)he off2 load tap changers are used when it is expected that the ratio will need to be changed only infrequently/ because of load growth or some seasonal change. )C7L is
used when changes in ratio may be frequent or when it is undesirably to de2energie the
transformer to change the tap.
PART - B
1. D'a? th) %'%t $a5'a #' a t,<%a" )%tat# !,!t) a$ $)'() th) t'a!)'
%t# #$)" a$ $'a? th) >"#%9 $a5'a.
+. D!%!! 5))'at# a$ a>!#'<t# # ')a%t() <#?)'.
3. E<"a $)')t t,<)! # !tat% AR %#<)!at#'! ?th a <ha!#' $a5'a.
/. D!%!! a>#t th) (a'#! )th#$! # (#"ta5) %#t'#".
. D)'() th) ')"at#! >)t?)) (#"ta5)8 <#?)' a$ ')a%t() <#?)' at a #$) #'
a<<"%at#! <#?)' !,!t) %#t'#"
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 10
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 11/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
UNIT-I
UNIT COMMITMENT AND ECONOMIC DISPATCH
PART-A
1. D)) )%##% $!<at%h <'#>").
-conomic dispatch problem is defined as the problem which minimies the
operating cost of active power generation.
+. D)) %'))ta" %#!t.
Incremental cost is defined as the rate of change of fuel cost with active power generation.
3. W't) th) "#a$ >a"a%) )=at#.
Load balance equation is given below.
'g2'd2'L4.
/. D)) >a!) <#t.
3ase point is defined as the present operating point of the system.
. D)) <a't%<at# a%t#'.
'articipation factor is defined as the change in generation required to meet power
demand.
6. D)) h,$'#th)'a" !%h)$"5 <'#>").
Bydrothermal scheduling problem is defined as the problem of minimiing the
thermal generation cost with the constraints of water availability.
2. D)) t %#t)t.
7nit commitment is defined as the commitment of minimum generator to meet
the required demand.
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 11
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 12/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
4. D)) !<5 ')!)'().
1pinning =eserve is defined as the term that describes the total amount of
generation availability from all units synchronied on the system.
;. What ! )at >, !%h)$")$ ')!)'()*
1cheduled reserve include quic( start diesel turbine units as well as most
hydro units and pumped storage hydro units that can be brought online/ synchronied and
brought up to full capacity quic(ly.
10. What a') th) th)'a" t %#!t'at!*
)he thermal unit constraints are
i. Minimum up time
ii. Minimum down time
iii. Crew constraints.
11. What a') th) t?# a<<'#a%h)! t# t')at a th)'a" t t# #<)'at5 t)<)'at')*
)he two approaches to treat a thermal unit to operating temperature are given
below.
i. $llows the unit boiler to cool down and then heat bac(up to operating
temperature in time for a scheduled turn on.
ii. =equires that sufficient energy be input to the boiler to >ust maintain
operating temperature.
1+. What a') th) t)%h=)! #' th) !#"t# # th) t %#t)t <'#>")*
)he techniques for the solution of the unit commitment problem are
i. 'riority list method
ii. Dynamic programming
iii. Lagrange relation
13. What a') th) a!!<t#! a$) $,a% <'#5'a5 <'#>")*
)he assumptions made in dynamic programming problem are given
below.
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 1+
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 13/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
i. $ state consists of an array of units with specified units operating and the
rest of the time.
ii. )he startup cost of a unit is independent of the time it has been offline.
iii. )here are no costs for shutting down the units.
1/. D)) "#5 'a5) h,$'# !%h)$"5 <'#>").
Long range hydro scheduling problem is defined as the problem involves the long
range of water availability and scheduling of reservoir water releases. 8or an interval of
time that depends on the reservoir capacities.
1. What a') th) #<tGat# t)%h=)! #' "#5 'a5) h,$'# !%h)$"5 <'#>")*
)he optimiation techniques for long range hydro scheduling problem arei. Dynamic programming
ii. Composite hydraulic simulation methods
iii.1tatistical production cost
16. D)) !h#'t 'a5) h,$'# !%h)$"5 <'#>").
1hort range hydro scheduling problem is defined as the hour by hour scheduling
of all generators on a system to achieve minimum production condition for the given
time period.
12. D)) !,!t) >"a%9#t <'#>").
1ystem blac(out problem is defined as the event occurs on a system that leaves it
operating with limits violated@ the event may be followed by a series of further actions
that switch other equipment out of service. If the process of cascading failures continues/
the entire system of it may completely collapse.
14. What ! )at >, %a!%a$5 #ta5)!*
Cascading outages are the process if one of the remaining lines is now too heavily
loaded/ it may open due to relay action/ thereby causing even more load on the remaining
lines.
PART-B
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 13
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 14/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
1. D)'() th) %##'$at# )=at# ?th "#!!)! )5")%t)$.
+. D)'() th) %##'$at# )=at# # a JK >! <#?)' !,!t) ta95 t# a%%#t th)
))%t #
!,!t) "#!!)!.
3. D)'() th) )<')!!# #' >a!) <#t a$ <a't%<at# )th#$.
/. Stat) th) t %#t)t <'#>"). Wth th) h)"< # "#?%ha't )<"a #'?a'$
$,a%
<'#5'a5 !#"t# )th#$.
. E<"a P'#'t, "!t )th#$ !5 "" L#a$ a()'a5) <'#$%t# %#!t. Stat) th)
)'t! a$
$))'t!.
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 1/
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 15/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
UNIT-
COMPUTER CONTROL O POWER SYSTEM
1. What a') th) %t#! # %#t'#" %)t)'*
)he functions of control center are
. 1ystem monitoring
ii. Contingency analysis
iii. 1ecurity constrained optimal power flow.
+. What ! th) %t# # !,!t) #t#'5*
a. 8unction of system monitoring is to provide updated information about the power
system.
3. What ! SCADA !,!t)*
1C$D$ stands for supervisory control and data acquisition system. It allows a
few operators to monitor the generation and high voltage transmission systems and to
ta(e action to correct overloads.
/. What a') th) !tat)! # <#?)' !,!t)*
)he states of power system are
i. <ormal state
ii. $lert mode
iii. Contingency mode
iv. -mergency mode.
. D)) #'a" #$).
<ormal mode is defined as the mode of operation if the system is in secure even
the occurrence of all possible outages has been simulated the system remain secure.
6. D)) a")'t #$).
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 1
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 16/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
$lert mode is defined as the mode of operation of the system that it does not
remain in the secure for the occurrence of all possible outages.
2. What a') th) $!t'>t# a%t#'!*
)he distribution factors are
i. Line outage distribution factor
ii. 9eneration outage distribution factor.
4. D)) !tat) )!tat#.
1tate estimation is defined as the process of assigning a value to an un(nown
system state variable based on measurements from that system according to some criteria.
;. D)) a "9)"h##$ %'t)'#.
Maximum li(elihood criterion is defined as the problem of maximiing the
probability that estimate the state variable x/ is the true value of the state variable vector
!i.e/ to maximie the '!x" x".
10. D)) ?)5ht)$ ")a!t-!=a')! %'t)'#.
:eighted least2squares criterion is defined as the problem of minimiing the sumof the squares of the weighted deviations of the estimated measurements/ from the actual
measurement.
11. D)) (a'a%) %'t)'#.
Minimum variance criterion is defined as the problem of minimiing the expected
value of the squares of the deviations of the estimated components of the state variable
vector from the corresponding components of the true state variable vector.
1+. D)) !t ' %#!t'at.
Must run constraint is defined as the condition that some units are given a must
run status during certain times of the year for reason of voltage support on the
transmission networ(.
13. D)) )" %#!t'at.
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 16
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 17/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
8uel constrain is defined as the condition if a system in which some units have
limited fuel or else have constraints that require them to burn aspecified amount of fuel in
a given time.
1/. What a') th) a!!<t#! a$) <'#'t, "!t )th#$*
)he assumptions made in priority list method are
i. <o load cost is ero
ii. 7nit input2output characteristics are linear between ero output and full
load
iii. )here are no other restrictions startup cost are affixed amount.
1. Stat) th) a$(ata5)! # #'?a'$ $,a% <'#5'a5 a<<'#a%h.
$dvantage of forward D' approach is given below. If the start up cost of a unit is
a function of the unit is a function of the time it has been offline/ then a forward dynamic
program approach is more suitable since the previous history of the unit can be computed
at each stage.
16. Stat) th) $!a$(ata5)! # $,a% <'#5'a5 )th#$.
)he disadvantage of dynamic programming method is that it has the necessity of forcing the dynamic programming solution to search over a small number of commitment
states to reduce the number of combinations that must be tested in each period.
12. What a') th) 9#? (a")! !h#'t t)' h,$'# !%h)$"5 <'#>")*
Anown values in short term hydro scheduling problem are
i. )he load
ii. Bydraulic inflows
iii. 7nit availabilities.
14. What ! )at >, t)"))t', !,!t)*
)elemetry system is the process of measurement of state of the system and
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 12
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 18/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
transmission of these states to a control center.
1;. What a') th) %t#! # !)%'t, %#!t'a)$ #<ta" <#?)' "#?*
)he functions of security constrained optimal power flow are
i. Contingency analysis is combined with an optimal power flow which
see(s to ma(e changes to the optimal dispatch of generation
ii. $s well as other ad>ustments/ so that when a security analysis is run/ no
contingency result in violations.
+0. D)) th) !tat) # #<ta" $!<at%h.
)he state of optimal dispatch is defined as the state that the power system is in prior to any contingency. It is optimal with respect to economic operation but may not be
secure.
+1. D)) <#!t %#t5)%,.
'ost contingency is defined as the state of the power system after a contingency
has occurred.
++. D)) !)%') $!<at%h.
1ecure dispatch is defined as the state of the power system with no contingency
outages/ but with correction to the operating parameters to account for security violations.
'$=)23
1. B')", $!%!! th) (a'#! %t#! # ))'5, %#t'#" %)t')
+. E<"a th) $)')t #<)'at5 !tat)! # <#?)' !,!t) ?th !tat) t'a!t# $a5'a.
3. E<"a th) ha'$?a') %#<#)t! # SCADA ?th )at $a5'a a$ a"!# )t#
th) %t#! # t.
/. E<"a a>#t <#?)' !,!t) !)%'t,
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 14
7/21/2019 Pow Sys Ope & Con - M Rajkuamr - III EEE
http://slidepdf.com/reader/full/pow-sys-ope-con-m-rajkuamr-iii-eee 19/19
EE 6603 – POWER SYSTEM OPERATION AND CONTROL SEM & BRANCH: 06 & EEE
. What ! EMS* What a') t! a#' %t#! <#?)' !,!t) #<)'at# a$ %#t'#"*
M. RA7UMAR8 AP – EEE + & 16 Ma'9! & A Pa5) 1;