The DPA Modular vs Modular

Page 2: Power back up 2-14052012

13/04/23 Modular UPS challenge 3

Content

• Why Modular UPS and its requirements

• Application Field of Modular UPS solution

• True modular UPS architecture (DPA)

• The misconception of modular UPS architecture (CPA)

and its actors

• Summery : Advantages of systems with DPA

• Conclusion

Page 3: Power back up 2-14052012

13/04/23 Modular UPS challenge 4

Why Modular UPS

• Improvement in semiconductor technology

IGBT and Transformerless

• A climate of increasingly demanding business

High availability to reduce risk of downtime

Standardize product for service optimisation

Flexibility in changing configuration without third parties

• CAPEX optimization

Pay as you growth solution

Less footprint (saving space)

• OPEX optimization

Less spares, only UPS modules

UPS’s efficiency optimization

Page 4: Power back up 2-14052012

13/04/23 Modular UPS challenge 5

≥• The same functional blocks on each UPS module as per standalone UPS

• Higher efficiency ; -> Lower total cost of ownership (TCO)

• The same or better technical performances than on stand alone; -> True redundency

• Higher realibility availability ; -> Higher MTBF and low MTTR

• Easy scalability ; -> Flexibility for dynamic business environment

• Reduced footprint ; -> Less surface costs

• Hot swappability ; -> Wireless capability

• Front access only ; -> Easy maintenable, less operational surface needed)

Which Requirements people expect from a true Modular UPS system

Module 1

Module 2

Module 3

Extention

Page 5: Power back up 2-14052012

13/04/23 Modular UPS challenge 6

F-lexibility

A-vailability

T-CO

Non modular Modular

Power increase flexibility

Power decrease flexibility

Tier changes flexibility

Fast reconfiguration

On-Line UPS

Parallel redundant

Low MTTR

Hot-Swap technology

Pay as you grow

Vertical paralleling (low space)

Product standardisation

Optimized efficiency

Reusable modules

Main differences between stand alone andModular UPS

Page 6: Power back up 2-14052012

13/04/23 Modular UPS challenge 7

• The load is very critical (high availability is needed)

• The future amount of load is unknown (pay as you growth)

• A UPS efficiency’s optimization is required

• The available space for UPS is small (less surface and installation costs)

• The customer is looking for added value UPS (price/performance ratio)

• Big organizations are involved (homogeneous UPS offer)

• The customer is looking for a flexible solution w/o additional future

installation costs

• The customer is looking for a self made repair solution

Application Field of Modular UPS solution

Page 7: Power back up 2-14052012

13/04/23 Modular UPS challenge 8

Rectifier

Battery

Inverter

Static by-pass

LCD Display

Microprocessor

UPS’s functional block

A true modular UPS architecture(Standalone system)

Page 8: Power back up 2-14052012

13/04/23 Modular UPS challenge 9

A modular UPS is considered a TRUE modular only when each UPS module is equipped with all

functional blocks (rectifier, inverter,static by-pass, LCD display, microprocessor (CPU)) and

with dedicated battery capability in order to avoid Single Point of Failure

A true modular UPS architecture(Standalone system)

Page 9: Power back up 2-14052012

13/04/23 Modular UPS challenge 10

Input

Output

OutputInput

A true modular UPS architecture(Parallel system)

Page 10: Power back up 2-14052012

13/04/23 Modular UPS challenge 11

A modular UPS is considered a TRUE modular only when the UPS modules are

hot-swappable and the frame is full front accessible for service and maintenance

purpose.

An hot swappable UPS module is the one which can be removed from the frame while it is powered on and does not require a reboot of the system, load transfer to raw mains or load’s shut down

A true modular UPS architecture(Operational)

Page 11: Power back up 2-14052012

13/04/23 Modular UPS challenge 12

• Decentralized LCD display

• Decentralized microprocessor

• Decentralized battery

• Decentralized static by-pass

OutputInput

.

.

.

A true modular UPS uses DPA Decentralized Parallel Architecture

DPA

Page 12: Power back up 2-14052012

13/04/23 Modular UPS challenge 13

OutputInput

The misconception of modular UPS architecture : Centralized Parallel Architecture (CPA)

DPA

OutputInput

CPA

OutputInput

CPA

OutputInput

CPA

Page 13: Power back up 2-14052012

13/04/23 Modular UPS challenge 16

Centralized ParallelArchitecture (CPA)

Failure on CPU

The system is out of control and may: go on by-pass or stop the operation

No measurement, alarm, event log available

A technical specialist is required to recover the system

Single CPU based modular UPS are to a certain extend less reliable than a traditional parallel UPS systems

Output

Input

Why DPA is more reliable compared to CPA?

Page 14: Power back up 2-14052012

13/04/23 Modular UPS challenge 17

Centralized ParallelArchitecture (CPA)

Failure on battery

No back up in case of mains failure

Even with multiple battery’ strings the autonomy time is substantially reduced

Immediate intervention is needed

With single battery, a modular UPS is less reliable than a traditional parallel UPS systems

OutputInput

Why DPA is more reliable compared to CPA?

Page 15: Power back up 2-14052012

13/04/23 Modular UPS challenge 18

Centralized ParallelArchitecture (CPA)

Failure on LCD display

No measurement, alarm, event log available

A technical specialist is required to recover the communication and control of the UPS

With single LCD display, a modular UPS is less reliable than a traditional parallel UPS systems

LoadMains

Why DPA is more reliable compared to CPA?

Page 16: Power back up 2-14052012

13/04/23 Modular UPS challenge 19

Centralized ParallelArchitecture (CPA)

Failure on Static by-pass

In case of overload, long short circuit or inverter failure, the load transfer is not possible even in case with a centralized bypass in 2nd frames

A technical specialist is required to recover the UPS

The by-pass must be rated at its final load capability since the starting phase

No flexibility in case of configuration changes

With single static by-pass, a modular UPS is less reliable than a traditional parallel UPS systems

OutputInput

Why DPA is more reliable compared to CPA?

Page 17: Power back up 2-14052012

13/04/23 Modular UPS challenge 20

2006Newave launched the second

generation of three phase modular UPS

2009Newave launched the third generation of three phase

modular UPS

1%

99%

5%

95%

12%

88%

Modular

Traditional

1998

Newave launched the first three phase modular UPS

2010

Modular UPS’ market share & actors

Page 18: Power back up 2-14052012

13/04/23 Modular UPS challenge 21

Symmetra PX

APMBladeUPS

Power+

Mega Power +

Enertronic

C D C D C D C D C D C D C D

Archimode

C: Centralized CPA

D: Decentralized DPA

The “Modular” newcomers in the UPS worldDon’t worry

Page 19: Power back up 2-14052012

13/04/23 Modular UPS challenge 22

Modulys GreenPower

C D C D C D C D C D C D C D

Masterys EB

Protect3M

Protect3M 2.0

NHSeries

Phased outPhased out

MP-NETB8033

C: Centralized CPA

D: Decentralized DPA

The “Modular” newcomers in the UPS worldDon’t worry

Page 20: Power back up 2-14052012

13/04/23 Modular UPS challenge 23

Gripower90

C D C D C D C D C D C D

Multi Guard

Must

EPI

RX-MTR EA 660

C: Centralized CPA

D: Decentralized DPA

The “Modular” newcomers in the UPS worldDon’t worry

Page 21: Power back up 2-14052012

13/04/23 Modular UPS challenge 24

• Each critical component is redundant > no single point of failure

• Each module in case of any component failure can be isolated from the parallel system in a secured manner

• Quick shut-down of the module if front accessable

• Whatever the component failure, the system does not go overload but keep supplying the load with maximum safety, and that is on inverter

• Seperate battery configuration allows to exchange minimum quantity of battery in case of premature usage: Mix of battery (new / old) can be avoided

• Easy maintenance and repair (Safe swap)

SummeryAdvantages of systems with DPA

Page 22: Power back up 2-14052012

13/04/23 Modular UPS challenge 25

ConclusionSimple explanation of DPA versus CPA

Independent hookmeans DPA

Page 23: Power back up 2-14052012

13/04/23 Modular UPS challenge 26

Would you choose for a CPA solution?

CPA downgrade your UPS

ConclusionSimple explanation of DPA versus CPA