POWER DISTRIBUTION UNITS
Power Distribution Unit TechnologiesCyberPower Power Distribution Units (PDUs) are engineered to distribute network power to multiple devices. A PDU does not generate or condition power, but delivers AC power from a UPS (uninterruptible power supply), a generator, or utility power source to servers, network/telecom equipment, and other devices. Selecting the best PDU for your needs depends on the output voltage required, the number of outlets needed for connected devices, plug and outlet types, and mounting options.
Versatile. CyberPower PDUs are designed with as many as 38 outlets, positioned on the front and/or back of the units. Offered in 1U, 2U, or 0U form factors, each PDU includes the necessary hardware to be mounted vertically or horizontally for versatile placement inside a rack enclosure, on a wall, or under a shelf.
Scalable. In smaller networks, conditioned power can be distributed through a single PDU from a UPS, while a complex data center might require the connection of multiple PDUs to a large-capacity UPS system.
Understanding PDUs
Basic. Distributes unfiltered AC power from a UPS system, generator, and/or utility source to multiple connected devices.
Metered. Network-grade power distribution plus load meters (amps) to prevent overloads and safely optimize load levels.
Monitored. Network-grade power distribution with remote monitoring through an SNMP network interface and local management via a digital meter display to prevent down time due to overloads or other power events.
Switched. Intelligent, network-grade power distribution to control outlets individually or collectively to solve power issues such as shutdowns or to plan scheduled re-booting. A digital meter provides information on load and voltage, as well as local control of the outlets. An ethernet SNMP connection enables remote monitoring and control of the outlets to ensure complete control, regardless of location.
Metered ATS. Distributes unfiltered electrical pass-through from redundant plugs connected into separate power sources to provide redundancy to single-corded connected equipment. The LCD screen displays amperage and input and output voltages to diagnose potential issues with input AC power. Active power consumption (displayed in kilowatts) and hardware and firmware versions are also viewable on the LCD screen. A slot for an optional SNMP card enables expansion to a monitored device to provide real-time power information from the PDU over a network connection.
Switched ATS. Provides all the features of the standard switched PDU, plus the ability for plugs to be connected into separate power sources to provide redundancy to single-corded connected equipment. The LCD can displays amperage and input and output voltages to diagnose potential issues with input AC power. Active power consumption (displayed in kilowatts) and hardware and firmware versions are also viewable on the LCD screen. The standard SNMP card enables the PDU to be monitored and controlled over a network connection.
Rackbar™ Surge Protectors15 & 20 Amp Models. Industrial grade rackmount surge protectors designed for the most demanding electrical applications to safeguard systems and networking equipment against destructive power events that can cause equipment damage and loss of valuable data. Rackbars may be installed vertically or horizontally in racks or under benches for maximum flexibility.
Choosing The Right PDUFeatures Benefits Basic Metered Monitored Switched
Metered ATS
Switched ATS
Rackbar
Power Outlets Deliver AC power to connected equipment from a UPS system, generator, or other utility source • • • • • • •
Load Meter Monitor your power load in real-time to avoid overloads and efficiently balance load levels. • • • • •
Network Interface
Remotely monitor PDU status and prevent overloads that cause expensive downtime. • • Option •
Remote Outlet Control
Allows for remote management and monitoring of PDU vitals via the CyberPower Management Console. Reboot locked devices remotely and switch on or off devices to extend runtime during power outages.
• •
Auto Transfer Switch (ATS)
ATS provides redundancy for single corded connected equipment by allowing connection to two power sources. If one power source fails, the ATS PDU will automatically switch to the second power source instantly.
• •
Surge Protection Designed to safeguard your systems and networking equipment with network-grade surge and noise suppression. •
3cpsww.com
POWER DISTRIBUTION UNITS
Software ManagementPowerPanel® Business EditionPowerPanel Business Edition Client software provides IT managers the ability to view status of Monitored and Switched PDUs. For Switched PDUs, it allows for remote shutdown of any networked PC connected to the PDU. This ensures a proper shutdown when the Switched PDU is scheduled for a power cycle or to power down. PowerPanel Business Edition also works with CyberPower UPS systems to monitor and manage power across a network. This software is compatible with Windows XP, Windows Vista, Windows 7, Windows 8, Windows Server 2008, Windows Server 2012, and all versions of Windows 2K+, Linux, and OSX. It has achieved VMWare Ready status.
CyberPower Management ConsoleThe CyberPower Management Console is a Network Management System (NMS) that provides real-time remote power monitoring and control of PDUs. This useful hardware interface is built into CyberPower Switched and Monitored PDUs. For both Switched and Monitored PDUs, the Management Console enables administrators to perform operational tasks, such as load monitoring and event logging via email, text, or SNMP trap notifications. Additionally, a Switched PDU enables manual power cycling to restart unresponsive devices, allows for scheduled power cycling of outlets, and/or load shedding for specific devices connected to the PDU.
CyberPower PDU & Rackbar Model GuideCyberPower’s naming convention allows for quick model specifications for amperage, model type, rack mounting to plug type, quantity, and styling. Follow the example below to see what the letters and numbers represent for our Power Distribution Units and Rackbar Surge Protectors.
Amperage15A, 20A, and 30A
Network ManagementNET
Model TypeB = BasicM = Metered/MonitoredSW = Switched
Rear Outlet #Number of Outlets followed by “R” Example 8R
Rack SpaceNone = Horizontal (1U or 2U) V = Vertical (0U)
Front Outlet #Number of Outlets followed by “F” Example 8F
Input VoltageNone = 120V HV = 208V/230V or 200-240V
Plug TypeNone = NEMA 5-15P/5-20P T = Twist Lock (NEMA L5-L6 Plug)IEC = IEC C14/C20
PDU XX M V HV T F R NET
Amperage10A, 15A, 20A, and 30A
Surge Protection
Plug TypeNone = NEMA 5-15P/5-20P T = Twist Lock (NEMA L5 Plug)
Rear OutletsNumber of Outlets followed by “R” Example 8R
Front OutletsNumber of Outlets followed by “F” Example 2F
RKBS XX S T XF XR
5cpsww.com
POWER DISTRIBUTION UNITS
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Basic 0UPDU15BV14F 120V 15A (Derated to 12A) 5-15P 10ft. 14 NEMA 5-15R 24 x 1.75 x 1.5 0U
PDU15BV16F 120V 15A (Derated to 12A) 5-15P 10ft. 16 NEMA 5-15R 36 x 1.75 x 1.5 0U
PDU15BV20F 120V 15A (Derated to 12A) 5-15P 10ft. 20 NEMA 5-15R 48 x 1.75 x 1.5 0U
PDU15BV28F • 120V 15A (Derated to 12A) 5-15P 10ft. 28 NEMA 5-15R 60 x 1.75 x 1.5 0U
PDU15BV32F 120V 15A (Derated to 12A) 5-15P 10ft. 32 NEMA 5-15R 70 x 1.75 x 1.5 0U
PDU20BV14F 120V 20A (Derated to 16A) 5-20P 10ft. 14 NEMA 5-20R 24 x 1.75 x 1.5 0U
PDU20BV16F 120V 20A (Derated to 16A) 5-20P 10ft. 16 NEMA 5-20R 36 x 1.75 x 1.5 0U
PDU20BV20F 120V 20A (Derated to 16A) 5-20P 10ft. 20 NEMA 5-20R 48 x 1.75 x 1.5 0U
PDU20BV32F 120V 20A (Derated to 16A) 5-20P 10ft. 32 NEMA 5-20R 70 x 1.75 x 1.5 0U
PDU20BVT14F 120V 20A (Derated to 16A) L5-20P 10ft. 14 NEMA 5-20R 24 x 1.75 x 1.5 0U
PDU20BVT16F 120V 20A (Derated to 16A) L5-20P 10ft. 16 NEMA 5-20R 36 x 1.75 x 1.5 0U
PDU20BVT20F 120V 20A (Derated to 16A) L5-20P 10ft. 20 NEMA 5-20R 48 x 1.75 x 1.5 0U
PDU20BVT28F 120V 20A (Derated to 16A) L5-20P 10ft. 28 NEMA 5-20R 60 x 1.75 x 1.5 0U
PDU20BVT32F 120V 20A (Derated to 16A) L5-20P 10ft. 32 NEMA 5-20R 70 x 1.75 x 1.5 0U
PDU30BVT14F 120V 30A (Derated to 24A) L5-30P 10ft. 14 NEMA 5-20R 24 x 1.75 x 2.25 0U
PDU30BVT16F 120V 30A (Derated to 24A) L5-30P 10ft. 16 NEMA 5-20R 36 x 1.75 x 2.25 0U
PDU30BVT20F 120V 30A (Derated to 24A) L5-30P 10ft. 20 NEMA 5-20R 48 x 1.75 x 2.25 0U
PDU30BVT28F 120V 30A (Derated to 24A) L5-30P 10ft. 28 NEMA 5-20R 60 x 1.75 x 2.25 0U
PDU30BVT32F 120V 30A (Derated to 24A) L5-30P 10ft. 32 NEMA 5-20R 70 x 1.75 x 2.25 0U
PDU20BVHVT20F 200V/230V 20A (Derated to 16A) L6-20P 10ft. 20 IEC-320 C19/C13 36 x 1.75 x 1.5 0U
PDU20BVHVT24F 200V/230V 20A (Derated to 16A) L6-20P 10ft. 24 IEC-320 C19/C13 48 x 1.75 x 1.5 0U
PDU20BVHVT32F 200V/230V 20A (Derated to 16A) L6-20P 10ft. 32 IEC-320 C19/C13 60 x 1.75 x 1.5 0U
PDU30BVHVT16F 200V/230V 30A (Derated to 24A) L6-30P 10ft. 16 IEC-320 C13 24 x 1.75 x 1.5 0U
PDU30BVHVT20F 200V/230V 30A (Derated to 24A) L6-30P 10ft. 20 IEC-320 C19/C13 36 x 1.75 x 1.5 0U
PDU30BVHVT32F 200V/230V 30A (Derated to 24A) L6-30P 10ft. 32 IEC-320 C19/C13 60 x 1.75 x 1.5 0U
PDU30BVHVT38F 200V/230V 30A (Derated to 24A) L6-30P 10ft. 38 IEC-320 C19/C13 70 x 1.75 x 1.5 0U
PDU10BVHVIEC16F 200V/230V 10A IEC-320 C14 10ft. 16 IEC-320 C13 24 x 1.75 x 1.5 0U
PDU10BVHVIEC20F 200V/230V 10A IEC-320 C14 10ft. 16 IEC-320 C19/C13 36 x 1.75 x 1.5 0U
PDU20BVHVIEC16F • 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 16 IEC-320 C13 24 x 1.75 x 1.5 0U
PDU20BVHVIEC20F 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 20 IEC-320 C19/C13 36 x 1.75 x 1.5 0U
PDU20BVHVIEC24F 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 24 IEC-320 C19/C13 48 x 1.75 x 1.5 0U
PDU20BVHVIEC32F 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 32 IEC-320 C19/C13 60 x 1.75 x 1.5 0U
PDU20BVHVIEC38F 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 38 IEC-320 C19/C13 70 x 1.75 x 1.5 0U
A Basic PDU serves as a conduit of power from a single source to multiple devices. To ensure power availability, these units do not include features such as surge protection or line filtering that could interrupt the flow of power to critical connected equipment. Basic PDUs provide unfiltered AC output from a UPS system, generator, or utility source to power connected equipment and devices.
As the largest group of PDUs from CyberPower, the Basic Series includes models in 1U and 0U options, with versatile outlet arrangements on the front and/or back. All models include cord-retention trays to keep cords organized and securely in place.
Basic
Key User Benefits
• Switch-free design
• Network-grade plugs and outlets
• Long input power cord
• Durable metal housing
• Horizontal or vertical mounting
• Lifetime warranty
• = Photo Shown
6 1.877.297.6937
POWER DISTRIBUTION UNITS
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Basic 1UPDU15B8R 120V 15A (Derated to 12A) 5-15P 15ft. 8 NEMA 5-15R 1.75 x 17.5 x 1.5 1U
PDU15B10R 120V 15A (Derated to 12A) 5-15P 15ft. 10 NEMA 5-15R 1.75 x 17.5 x 1.5 1U
PDU15B12R 120V 15A (Derated to 12A) 5-15P 15ft. 12 NEMA 5-15R 1.75 x 17.5 x 1.5 1U
PDU20B8R 120V 20A (Derated to 16A) 5-20P 15ft. 8 NEMA 5-20R 1.75 x 17.5 x 1.5 1U
PDU20B10R 120V 20A (Derated to 16A) 5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 1.5 1U
PDU20B12R 120V 20A (Derated to 16A) 5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 1.5 1U
PDU20BT8R 120V 20A (Derated to 16A) L5-20P 15ft. 8 NEMA 5-20R 1.75 x 17.5 x 1.5 1U
PDU20BT10R 120V 20A (Derated to 16A) L5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 1.5 1U
PDU20BT12R 120V 20A (Derated to 16A) L5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 1.5 1U
PDU20BHVT8R 200V/230V 20A (Derated to 16A) L6-20P 10ft. 8 IEC-320 C19/C13 1.75 x 17.5 x 1.5 1U
PDU20BHVT10R 200V/230V 20A (Derated to 16A) L6-20P 10ft. 10 IEC-320 C19/C13 1.75 x 17.5 x 1.5 1U
PDU20BHVT12R 200V/230V 20A (Derated to 16A) L6-20P 10ft. 12 IEC-320 C13 1.75 x 17.5 x 1.5 1U
PDU30BHVT8R 200V/230V 30A (Derated to 24A) L6-30P 10ft. 8 IEC-320 C19/C13 1.75 x 17.5 x 1.5 1U
PDU30BHVT12R 200V/230V 30A (Derated to 24A) L6-30P 10ft. 12 IEC-320 C13 1.75 x 17.5 x 1.5 1U
PDU20BHVIEC8R 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 8 IEC-320 C13 1.75 x 17.5 x 1.5 1U
PDU20BHVIEC10R 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 10 IEC-320 C13 1.75 x 17.5 x 1.5 1U
PDU20BHVIEC12R 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 12 IEC-320 C13 1.75 x 17.5 x 1.5 1U
PDU20BHVIEC12Ra 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 12 IEC-320 C19/C13 1.75 x 17.5 x 1.5 1U
PDU15B2F8R 120V 15A (Derated to 12A) 5-15P 15ft. 10 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU15B2F10R 120V 15A (Derated to 12A) 5-15P 15ft. 12 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU15B2F12R 120V 15A (Derated to 12A) 5-15P 15ft. 14 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU20B2F8R 120V 20A (Derated to 16A) 5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU15B4F8R 120V 15A (Derated to 12A) 5-15P 15ft. 12 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU15B4F12R 120V 15A (Derated to 12A) 5-15P 15ft. 16 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU20B4F8R 120V 20A (Derated to 16A) 5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20B4F10R 120V 20A (Derated to 16A) 5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU15B6F8R • 120V 15A (Derated to 12A) 5-15P 15ft. 14 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU15B6F10R 120V 15A (Derated to 12A) 5-15P 15ft. 16 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU15B6F12R 120V 15A (Derated to 12A) 5-15P 15ft. 18 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU20B6F8R 120V 20A (Derated to 16A) 5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20B6F10R 120V 20A (Derated to 16A) 5-20P 15ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20B6F12R 120V 20A (Derated to 16A) 5-20P 15ft. 18 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT2F8R 120V 20A (Derated to 16A) L5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT2F10R 120V 20A (Derated to 16A) L5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT2F12R 120V 20A (Derated to 16A) L5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT4F8R 120V 20A (Derated to 16A) L5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT4F10R 120V 20A (Derated to 16A) L5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT4F12R 120V 20A (Derated to 16A) L5-20P 15ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT6F10R 120V 20A (Derated to 16A) L5-20P 15ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20BT6F12R 120V 20A (Derated to 16A) L5-20P 15ft. 18 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU30BT8F8R 120V 30A (Derated to 24A) L5-30P 12ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU30BT10F10R 120V 30A (Derated to 24A) L5-30P 12ft. 20 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
• = Photo Shown
7cpsww.com
POWER DISTRIBUTION UNITS
PDU20BVHVIEC16F
G
E
D
B
C
A
G
E
PDU15B6F8RPDU15BV28F
C
B
D
A
F
EC
A AC Outlets
D Power Cord
B Circuit Breaker
C Site Grounding Lug
E Bracket Screw Holes
F Cord Retention Tray Screw Holes
G Keyhole Mounting Peg Screw Holes
Front
Rear
Product Features
E D
B A E
G
8 1.877.297.6937
POWER DISTRIBUTION UNITS
• = Photo Shown
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Metered 1UPDU15M2F8R 120V 15A (Derated to 12A) 5-15P 15ft. 10 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU15M2F10R 120V 15A (Derated to 12A) 5-15P 15ft. 12 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU15M2F12R 120V 15A (Derated to 12A) 5-15P 15ft. 14 NEMA 5-15R 1.75 x 17.5 x 2.25 1U
PDU20M2F8R 120V 20A (Derated to 16A) 5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20M2F10R 120V 20A (Derated to 16A) 5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20M2F12R 120V 20A (Derated to 16A) 5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20MT2F8R 120V 20A (Derated to 16A) L5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20MT2F10R 120V 20A (Derated to 16A) L5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
PDU20MT2F12R • 120V 20A (Derated to 16A) L5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Metered 0UPDU15MV20F 120V 15A (Derated to 12A) 5-15P 10ft. 20 NEMA 5-15R 48 x 1.75 x 2.25 0U
PDU15MV26F • 120V 15A (Derated to 12A) 5-15P 10ft. 26 NEMA 5-15R 60 x 1.75 x 2.25 0U
PDU15MV32F 120V 15A (Derated to 12A) 5-15P 10ft. 32 NEMA 5-15R 70 x 1.75 x 2.25 0U
PDU20MV20F 120V 20A (Derated to 16A) 5-20P 10ft. 20 NEMA 5-20R 48 x 1.75 x 2.25 0U
PDU20MV26F 120V 20A (Derated to 16A) 5-20P 10ft. 26 NEMA 5-20R 60 x 1.75 x 2.25 0U
PDU20MV32F 120V 20A (Derated to 16A) 5-20P 10ft. 32 NEMA 5-20R 70 x 1.75 x 2.25 0U
PDU20MVT20F 120V 20A (Derated to 16A) L5-20P 10ft. 20 NEMA 5-20R 48 x 1.75 x 2.25 0U
PDU20MVT26F 120V 20A (Derated to 16A) L5-20P 10ft. 26 NEMA 5-20R 60 x 1.75 x 2.25 0U
PDU20MVT32F 120V 20A (Derated to 16A) L5-20P 10ft. 32 NEMA 5-20R 70 x 1.75 x 2.25 0U
PDU30MVT24F 120V 30A (Derated to 24A) L5-30P 10ft 24 NEMA 5-20R 60 x 1.75 x 2.25 0U
PDU30MVT32F 120V 30A (Derated to 24A) L5-30P 10ft 32 NEMA 5-20R 70 x 1.75 x 2.25 0U
PDU20MVHVT20F 200V/230V 20A (Derated to 16A) L6-20P 10ft. 20 IEC-320 C19/C13 48 x 1.75 x 2.25 0U
PDU20MVHVT30F 200V/230V 20A (Derated to 16A) L6-20P 10ft. 30 IEC-320 C19/C13 60 x 1.75 x 2.25 0U
PDU20MVHVT38F 200V/230V 20A (Derated to 16A) L6-20P 10ft. 38 IEC-320 C19/C13 70 x 1.75 x 2.25 0U
PDU30MVHVT20F 200V/230V 30A (Derated to 24A) L6-30P 10ft. 20 IEC-320 C19/C13 48 x 1.75 x 2.25 0U
PDU30MVHVT30F 200V/230V 30A (Derated to 24A) L6-30P 10ft. 32 IEC-320 C19/C13 60 x 1.75 x 2.25 0U
PDU30MVHVT38F • 200V/230V 30A (Derated to 24A) L6-30P 10ft. 38 IEC-320 C19/C13 70 x 1.75 x 2.25 0U
PDU20MVHVIEC24F 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 24 IEC-320 C19/C13 48 x 1.75 x 2.25 0U
PDU20MVHVIEC30F 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 30 IEC-320 C19/C13 60 x 1.75 x 2.25 0U
PDU20MVHVIEC38F 200V/230V 20A (Derated to 16A) IEC-320 C20 10ft. 38 IEC-320 C19/C13 70 x 1.75 x 2.25 0U
• = Photo Shown
Metered PDUs include all the features of the Basic Series, plus a front digital LCD meter for real-time load monitoring. When networks expand with the addition of new hardware, the power source can become overloaded, resulting in costly network downtime. Managers can avoid downtime by monitoring the current draw (the load) of connected equipment, displayed in amps on the digital meter, as equipment is added and then react to avoid overloads before they happen.
Metered
Key User Benefits
• Digital real-time load display
• Switch-free design
• Network-grade plugs and outlets
• Long input power cord
• Durable metal housing
• Horizontal or vertical mounting
• Lifetime warranty
PDU20MT2F12R
9cpsww.com
POWER DISTRIBUTION UNITS
A AC Outlets
D Power Cord
B Circuit Breaker
C Site Grounding Lug
E Bracket Screw Holes
F Cord Retention Tray Screw Holes
G Keyhole Mounting Peg Screw Holes
H LCD Meter Readout
Product Features
PDU20MT2F12RPDU30MVHVT38F
ED
B
B
C
A
F
H
GE
E
FAH
B
E
DC
E
PDU15MV26F
E
G
H
A
CB
H
D
10 1.877.297.6937
POWER DISTRIBUTION UNITS
A Monitored PDU has all the features of a Metered PDU, along with the addition of a RJ45 network connection for remote monitoring capabilities. The power status can be monitored over the network using the CyberPower Management Console and the RJ45 ethernet port for network connection—or locally by using the LCD.
The CyberPower Management Console offers real-time remote monitoring of PDU vitals of the outlets for networked clients. Event Logging is provided via a web browser/network connection to review history on power conditions, such as input voltages, load levels, and outlet status. Automatic event notifications via email, SMS text or SNMP Traps can be sent to designated users when specified power events occur.
The LCD can display input voltages to assist in diagnosing potential issues with input power. Power consumption can also be displayed, as well as the IP address of the network interface for easy management.
Monitored
Key User Benefits
• Digital display
• Remote monitoring
• SNMP network interface
• Upgradable firmware
• Email, SMS text, or SNMP Traps notification options
• Switch-free design
• Network-grade plugs and outlets
• Long input power cord
• Durable metal housing
• Horizontal or vertical mounting
• Three-year limited warranty
• = Photo Shown
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Monitored 1U & 2UPDU15M8FNET 100V/120V 15A (Derated to 12A) 5-15P 12ft. 8 NEMA 5-15R 1.75 x 17.05 x 4.41 1U
PDU20M8FNET • 100V/120V 20A (Derated to 16A) 5-20P 12ft. 8 NEMA 5-20R 1.75 x 17.05 x 4.41 1U
PDU20MT8FNET 100V/120V 20A (Derated to 16A) L5-20P 12ft. 8 NEMA 5-20R 1.75 x 17.05 x 4.41 1U
PDU15MHVIEC8FNET 200V/240V 15A (Derated to 12A) IEC-320 C14 10ft. 8 IEC-320 C13 1.75 x 17.05 x 4.41 1U
PDU20MHVIEC8FNET 200V/240V 20A (Derated to 16A) IEC-320 C20 10ft. 8 IEC-320 C13 1.75 x 17.05 x 4.41 1U
PDU30MT16FNET • 100V/120V 30A (Derated to 24A) L5-30P 12ft. 16 NEMA 5-20R 3.5 x 17.05 x 4.41 2U
PDU30MHVT16FNET 200V/240V 30A (Derated to 24A) L6-30P 12ft. 16 IEC-320 C13/C19 3.5 x 17.05 x 4.41 2U
• = Photo Shown
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Monitored 0UPDU15MV16FNET • 100V/120V 15A (Derated to 12A) 5-15P 10ft. 16 NEMA 5-15R 49 x 2.20 x 1.75 0U
PDU20MVT24FNET 100V/120V 20A (Derated to 16A) L5-20P 10ft. 24 NEMA 5-20R 66.5 x 2.20 x 1.75 0U
PDU30MVT24FNET 100V/120V 30A (Derated to 24A) L5-30P 10ft. 24 NEMA 5-20R 66.5 x 2.20 x 1.75 0U
PDU20MVHVT24FNET 200V/240V 20A (Derated to 16A) L6-20P 10ft. 24 IEC-320 C13/C19 66.5 x 2.20 x 1.75 0U
PDU30MVHVT24FNET • 200V/240V 30A (Derated to 24A) L6-30P 10ft. 24 IEC-320 C13/C19 66.5 x 2.20 x 1.75 0U
PDU20M8FNET
PDU30MT16FNET
11cpsww.com
POWER DISTRIBUTION UNITS
A AC Outlets
C Power Cord
B Circuit Breaker
D Current Draw
E Input Voltage
F Load Indicator
G Ethernet Port
H Tx/Rx / Link Indicator
I Serial / Sensor Port
J Select Button
K Reset Pinhole
K I
Product Features
HGED F
J
PDU30MVHVT24FNET
B
C
A
A
PDU15MV16FNET
C
A
PDU20M8FNET
2U display panel up close.
AC
12 1.877.297.6937
POWER DISTRIBUTION UNITS
A Switched PDU has all the features of a Monitored PDU with the addition of local and remote control of the outlets. This allows for remote management of the PDU, monitoring PDU vitals, and controlling outlets and networked clients.
Service interruptions can occur when network devices lock up. Rebooting a locked device by turning it off and back on again is easy when the manager is onsite, but becomes impractical when a network is dispersed over a wide geographic area.
Using the CyberPower Management Console, the PDU outlets can be switched on and off to reboot connected equipment remotely so that networks can be conveniently managed offsite, minimizing disruption. Additionally, you can do planned power cycling of your attached equipment by utilizing the scheduling features in the CyberPower Management Console software.
Switched
Key User Benefits
• Digital display
• Local and remote outlet control
• Remote monitoring
• SNMP network interface
• Email, SMS text, or SNMP Traps notification options
• Upgradable firmware
• Switch-free design
• Network-grade plugs and outlets
• Long input power cord
• Durable metal housing
• Horizontal or vertical mounting
• Three-year limited warranty
• = Photo Shown
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Switched 0UPDU15SWV16FNET • 100V/120V 15A (Derated to 12A) 5-15P 10ft. 16 NEMA 5-15R 49 x 2.2.0 x 1.75 0U
PDU20SWVT24FNET 100V/120V 20A (Derated to 16A) L5-20P 10ft. 24 NEMA 5-20R 66.5 x 2.20 x 1.75 0U
PDU30SWVT24FNET 100V/120V 30A (Derated to 24A) L5-30P 10ft. 24 NEMA 5-20R 70 x 2.20 x 1.75 0U
PDU20SWVHVT24FNET • 200V/240V 20A (Derated to 16A) L6-20P 10ft. 24 IEC-320 C13/C19 66.5 x 2.20 x 1.75 0U
PDU30SWVHVT24FNET 200V/240V 30A (Derated to 24A) L6-30P 10ft. 24 IEC-320 C13/C19 70 x 2.20 x 1.75 0U
• = Photo Shown
Model Volts Amps Plug Type Cord Length Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size
Switched 1U & 2UPDU20SW8RNET 120V 20A (Derated to 16A) 5-20P 10ft. 8 NEMA 5-20R 1.75 x 17.5 x 4 1U
PDU15SW8FNET 100V/120V 15A (Derated to 12A) 5-15P 12ft. 8 NEMA 5-15R 1.75 x 17.05 x 4.41 1U
PDU20SW8FNET • 100V/120V 20A (Derated to 16A) 5-20P 12ft. 8 NEMA 5-20R 1.75 x 17.05 x 4.41 1U
PDU20SWT8FNET 100V/120V 20A (Derated to 16A) L5-20P 12ft. 8 NEMA 5-20R 1.75 x 17.05 x 4.41 1U
PDU15SWHVIEC8FNET 200V/240V 15A (Derated to 12A) IEC-320 C14 10ft. 8 IEC-320 C13 1.75 x 17.05 x 4.41 1U
PDU20SWHVIEC8FNET 200V/240V 20A (Derated to 16A) IEC-320 C20 10ft. 8 IEC-320 C13 1.75 x 17.05 x 4.41 1U
PDU30SWT16FNET • 100V/120V 30A (Derated to 24A) L5-30P 10ft. 16 NEMA 5-20R 3.5 x 17.05 x 4.41 2U
PDU30SWHVT16FNET 200V/240V 30A (Derated to 24A) L6-30P 10ft. 16 IEC-320 C13 3.5 x 17.05 x 4.41 2U
PDU20SW8FNET
PDU30SWT16FNET
13cpsww.com
POWER DISTRIBUTION UNITS
PDU15SWV16FNET PDU30SWT16FNETPDU20SWVHVT24FNET
A AC Outlets
B Power Cord
C Current Draw
D Input Voltage
E Load Indicator
F Ethernet Port
G Tx/Rx / Link Indicator
H Outlet On/Off Indicator
I Serial / Sensor Port
J Select Button
K Reset Pinhole
Product Features
A
A
H
H
B
B
A
H
H
A
I
GDC E F
K J
0U display panel up close.
B
14 1.877.297.6937
POWER DISTRIBUTION UNITS
Model Volts Amps Plug Type Cord Length
Outlets(total) Outlet Type Dimensions
(H"xW"xD") Rack Size
Metered 1U & 2UPDU15M10AT • 120V 15A (2) NEMA 5-15P 10ft. 10 NEMA 5-15R 1.75 x 17.05 x 9.30 1U
PDU20M10AT 120V 20A (2) NEMA 5-20P 10ft. 10 NEMA 5-20R 1.75 x 17.05 x 9.30 1U
PDU20MT10AT 120V 20A (2) NEMA L5-20P 10ft. 10 NEMA 5-20R 1.75 x 17.05 x 9.30 1U
PDU30MT17AT • 120V 30A (2) NEMA L5-30P 10ft. 17 NEMA (16) 5-20R / (1) L5-30R 3.50 x 17.05 x 9.30 2U
PDU15MHVIEC12AT 208V 20A (2) IEC-320 C14 10ft. 12 IEC-320 C13 1.75 x 17.05 x 9.30 1U
PDU20MHVT10AT 208V 20A (2) NEMA L6-20P 10ft. 10 IEC-320 (8) C13 - (2) C19 1.75 x 17.05 x 9.30 1U
PDU20MHVIEC10AT 208V 20A (2) IEC-320 C20 10ft. 10 IEC-320 (8) C13 - (2) C19 1.75 x 17.05 x 9.30 1U
PDU30MHVT19AT • 208V 30A (2) NEMA L6-30P 10ft. 19 IEC-320 (16) C13 - (2) C19 / NEMA (1) L6-30R 3.50 x 17.05 x 9.30 2U
• = Photo Shown
Designed for data centers and other demanding electrical applications, Metered ATS PDUs can be connected to multiple power sources for redundancy using Auto Transfer Switching technology. This technology allows for devices to switch almost instantaneously from one power source to another in the event of a power failure. Power input and usage can be monitored either directly on the built-in digital display (Load, Voltage, and KW) or remotely with the addition of an SNMP card.
Metered Auto Transfer Switch (ATS)
Key User Benefits
• Digital display (Load, Voltage, and KW)
• 100V/120V or 200V/240V input
• 10 to 19 outlets
• 1U and 2U rack mount options
• Rugged, industrial-grade metal housing
• 10 ft. cord length
• SNMP/HTTP card slot
• Three-year warranty
PDU30MHVT19AT
15cpsww.com
POWER DISTRIBUTION UNITS
A AC Outlets
D Power Cord
B Circuit Breaker
C Site Grounding Lug
E Multi-Function LCD Screen
F SNMP Slot
G Serial Communication Port
H Status LEDs
I Envirosensor Port
J SNMP Communication Port
Product Features
PDU15M10AT
PDU30MT17AT
A
EH
EH
G
GJI
CD D
BD A A
CBD
16 1.877.297.6937
POWER DISTRIBUTION UNITS
Model Volts Amps Plug Type Cord Length
Outlets(total) Outlet Type Dimensions
(H"xW"xD") Rack Size
Switched 1U & 2UPDU15SW10ATNET • 120V 15A (2) NEMA 5-15P 12ft. 10 NEMA 5-15R 1.75 x 17.05 x 9.30 1U
PDU20SW10ATNET 120V 20A NEMA 5-20P 10ft. 10 NEMA 5-20R 1.75 x 17.05 x 9.30 1U
PDU20SWT10ATNET 120V 20A NEMA L5-20P 10ft. 10 NEMA 5-20R 1.75 x 17.05 x 9.30 1U
PDU30SWT17ATNET • 120V 30A NEMA L5-30P 10ft. 17 NEMA (16) 5-20R / (1) L5-30R 3.50 x 17.05 x 9.30 2U
PDU15SWHVIEC12ATNET 208V 20A (2) IEC-320 C14 10ft. 12 IEC-320 C13 1.75 x 17.05 x 9.30 1U
PDU20SWHVT10ATNET 208V 20A (2) NEMA L6-20P 10ft. 10 IEC-320 (8) C13 - (2) C19 1.75 x 17.05 x 9.30 1U
PDU20SWHVIEC10ATNET 208V 20A (2) IEC-320 C20 10ft. 10 IEC-320 (8) C13 - (2) C19 1.75 x 17.05 x 9.30 1U
PDU30SWHVT19ATNET • 208V 30A (2) NEMA L6-30P 10ft. 19 IEC-320 (16) C13 - (2) C19 / NEMA (1) L6-30R 3.50 x 17.05 x 9.30 2U
• = Photo Shown
Designed for critical electrical applications, Switched ATS PDUs can be connected to multiple power sources for redundancy using Auto Transfer Switching technology. ATS technology allows for devices to switch almost instantaneously from one power source to another in the event of a power failure. Power input and usage can be monitored either directly on the built-in digital display (Load, Voltage, and KW) or remotely by connecting them to your network via Ethernet cable. Additionally, Switched ATS PDUs have the ability to remotely power down individual outlets or the entire switch through the network interface.
Switched Auto Transfer Switch (ATS)
Key User Benefits
• SNMP/HTTP network interface w/user upgradeable firmware
• Local and Network Outlet Switching
• Digital display (Load, Voltage, and KW)
• 100V/120V or 200V/240V input
• 10 to 19 outlets
• 1U and 2U rack mount options
• Rugged, industrial-grade metal housing
• 10 ft. cord length
• Three-year warranty
PDU30SWHVT19ATNET
17cpsww.com
POWER DISTRIBUTION UNITS
PDU15SW10ATNET
PDU30SW17ATNET
AC KD D
BD A AK
C KBD
A AC Outlets
D Power Cord
B Circuit Breaker
C Site Grounding Lug
E Multi-Function LCD Screen
F SNMP Slot
G Serial Communication Port
H Status LEDs
I Envirosensor Port
J SNMP Communication Port
K Outlet On/Off Indicator
Product Features
E
E
H
H
G
G
J
J
I
I
18 1.877.297.6937
RACKBAR SURGE
Model Volts Amps Joules Plug Type Cord Length
Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size CEG
20A Rackbars RKBS20S2F8R 120V 20A 1,800J NEMA 5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S2F10R 120V 20A 1,800J NEMA 5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S2F12R 120V 20A 1,800J NEMA 5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S4F8R 120V 20A 1,800J NEMA 5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S4F10R 120V 20A 1,800J NEMA 5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S4F12R 120V 20A 1,800J NEMA 5-20P 15ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S6F8R 120V 20A 1,800J NEMA 5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S6F10R 120V 20A 1,800J NEMA 5-20P 15ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20S6F12R 120V 20A 1,800J NEMA 5-20P 15ft. 18 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST2F8R 120V 20A 1,800J NEMA L5-20P 15ft. 10 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST2F10R 120V 20A 1,800J NEMA L5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST2F12R 120V 20A 1,800J NEMA L5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST4F8R 120V 20A 1,800J NEMA L5-20P 15ft. 12 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST4F10R 120V 20A 1,800J NEMA L5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST4F12R 120V 20A 1,800J NEMA L5-20P 15ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST6F8R 120V 20A 1,800J NEMA L5-20P 15ft. 14 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST6F10R • 120V 20A 1,800J NEMA L5-20P 15ft. 16 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
RKBS20ST6F12R 120V 20A 1,800J NEMA L5-20P 15ft. 18 NEMA 5-20R 1.75 x 17.5 x 2.25 1U $150,000
• = Photo Shown
CyberPower Rackbars provide network-grade rack mounted surge suppression solutions in both 15A and 20A configurations.
Each Rackbar is designed with an industrial-grade metal housing to perform flawlessly in datacenters and other electrically demanding environments. Two sets of mounting brackets provide flexible options for installation including 1U (19”) rack mount, 0U vertical rack mount, wall, and under shelf/desktop mounting. A cord retention tray ships with all CyberPower PDUs to ensure a worry-free, organized installation.
Multiple configurations ensure CyberPower Rackbar surge suppressors are available for almost any application. Rackbars come in a wide selection of options ranging from 15A to 20A, front and rear outlets, and twist lock plugs. Flexible and reliable solutions for powering network telecommunications equipment, security devices, PCs, servers, and other stand alone or rack mounted equipment.
CyberPower is committed to superior craftsmanship. An industry-leading lifetime warranty for CyberPower Rackbars provides reassurance for any defects in design, assembly, materials, or workmanship. All Rackbars come with a Lifetime Connected Equipment Guarantee.
Rackbar™ Surge
Key User Benefits
• Always on, switch-free design
• Protected and Grounded indicators
• Durable metal housing
• Long input power cord
• Horizontal or vertical mounting
• Network-grade plugs and outlets
• A lifetime warranty
19cpsww.com
RACKBAR SURGE
Model Volts Amps Joules Plug Type Cord Length
Outlets(total) Outlet Type Dimensions
(H"xW"xD")Rack Size CEG
15A RackbarsRKBS15S2F8R • 120V 15A 3,600J NEMA 5-15P 15ft. 10 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S2F10R 120V 15A 3,600J NEMA 5-15P 15ft. 12 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S2F12R 120V 15A 3,600J NEMA 5-15P 15ft. 14 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S4F8R 120V 15A 3,600J NEMA 5-15P 15ft. 12 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S4F10R 120V 15A 3,600J NEMA 5-15P 15ft. 14 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S4F12R 120V 15A 3,600J NEMA 5-15P 15ft. 16 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S6F8R 120V 15A 3,600J NEMA 5-15P 15ft. 14 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S6F10R • 120V 15A 3,600J NEMA 5-15P 15ft. 16 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
RKBS15S6F12R 120V 15A 3,600J NEMA 5-15P 15ft. 18 NEMA 5-15R 1.75 x 17.5 x 2.25 1U $150,000
• = Photo Shown
A AC Outlets
D Power Cord
B Circuit Breaker
C Site Grounding Lug
E Bracket Screw Holes
F Cord Retention Tray Screw Holes
G Grounded Status LED
H Protected Status LED
RKBS15S2F8R
RKBS20ST6F10R
Product Features
RKBS15S6F10R
B
B
B
D
D
D
C
C
C
A
A
A
F
F
F
E
E
E
H
H
H
G
G
G
A
A
A
CPSWW.COM
Cyber Power Systems (USA), Inc. 4241 12th Avenue East Suite 400 Shakopee, MN 55379
© 2016 Cyber Power Systems (USA), Inc. CyberPower is a registered trademark and brand of Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners. CyberPower reserves the right to modify product information or specifications without notice. The information presented is accurate at the time of publication. 05-2016