power system interview question
TRANSCRIPT
-
7/28/2019 Power System Interview Question
1/10
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
ENGINEERING
POWER SYSTEM INTERVIEW QUESTION
Q1. What is the Power Station ?
A1. Power Station is a place where Power is Generated and
Transmitted , eg. Tharmal power station, Hydel power station,
Nuclear power station etc.
Q2. What is Slack Bus ?
A2. Slack Bus is the responsible for the delivering losses in the power
system. in this bus the magnitude of voltage and phase angle are
specified. This bus is first to respond to a changing load condition.
Q3. what is critical disruptive voltage.
A3. The minimum voltage at which the breakdown of the insulating
properties of air occurs and corona start is called D C V .
Q4. How many types of fault occurs in the 3 P power system ?
A4. Faults in the 3 P system can be classified under the following :-
a. single line to ground (LG) fault
b.line to line (LL) fault
c. Double line to ground (LLG) fault
d. Thee Phase short circuit (LLL) fault
e. three phase to ground (LLLG) fault
Q5. How many methods uses for the load flow solution ?
A5.
-
7/28/2019 Power System Interview Question
2/10
1. Gauss-seidel method using Ybus2. Newton- Raphson method (NR)3. Power flow through line and slack bus power4. Decouple load flow method5. Fast Decouple load flow method.
Q6. What is skin effect ?
A6. When the AC passed through the conductor the density of the
current is not uniform over the cross-section of the conductor, the
density of the current is very high near the surface of the conductor
and very low at middle this effect is called skin effect. this effect isonly in the ac.
Q7. What is the Bundle conductor and why is is used ?
A7. A bundle conductor consists of two more parallel subconductors
at a spacing of several diameters.this is use to reduce the corona and
skin effectQ8.What is meant by Tine Graded Protection?
A8.Time Graded protection is a scheme of over current protection, in
which the discrimination is incorporated i.e, the time setting of the
relays is so graded that in the event of the fault, the smallest part of
the system is disconnected
Q9What are the main elements of current carrier protection?
A9.The main elements of the carrier current protection are:Transmitter, Receiver, Coupling equipment and Line trap
Q10.Why Merz-Price Protection is not suitable beyond 33kV?
A10.:Difficulties are experienced in balancing the secondaries of the
CTs and this is why Merz-Price protection is not employed beyond
33kV
-
7/28/2019 Power System Interview Question
3/10
Q11.What types of relays are suitable for the protection of radial
feeders?
A11.Induction type IDMT relays are more suitable for protection of
the radial feeders because the time current characteristics are similar
in shape and in no case they cross each other at any time
Q12.What is the purpose of Line trap and Coupling capacitors in
carrier channels?
A12.Line trap is an LC network inserted between the busbar and
connection of coupling capacitors to the line and tuned to resonance at
the high frequency and are used to confine the carrier currents to the
protected section so as to avoid interference with or from adjacent
carrier current channel.Coupling capacitors is used to connect the high frequency (carrier)
equipment to one of the line conductors and simultaneously serves to
isolate the carrier equipment from high power line voltage
Q13.What is Unit Protection?
A13. Unit system of protection is one in which the protection
responds to the faults in the protected zone alone and it does not
respond to through faults (faults beyond the protected zone). Noneunit systems does not have zone boundry
Q14.What is the minimum time interval set for two adjacent circuit
breakers to operate in radial feeders?
A14.It will be usually around 0.4 sec
Q15.Why Over Current Protection is not necessary for modern
generators?A15. Over Current protection is not considered necessary for modern
alternators because these are capable of withstanding a complete short
circuit at their terminals for sufficient time without much over heating
and damage
Q16.What type of protection is provided for the generators against
over heating of the generator stator?
A16. Resistance temperature detector
-
7/28/2019 Power System Interview Question
4/10
Q17.Which type of relays are used for the Merz-Price protection
system for alternator?
A17.Merz-Price protection is differential protection provided for the
alternator. The relays used in the Merz-Price protection system of
alternator are instantaneous electro-magnetic type protection
Q18.Why large alternator is grounded with large resistance?
A18. Large capacity of alternators are typically provided with
resistance grounding. High value of resistor is connected to the neural
path to the ground. If the generator is delta connected, then it is
grounded with the help of zig-zag transformer or (Delta-Star)
transformer such that a high resistor is connected between the neutralpoint and the ground. Resistance grounding is provided so as to limit
the short circuit current flowing during earth fault to stator winding in
order to provide protection against mechanical stresses and melting of
winding during Line to Ground short circuit. In large generators fault
current is limited as low as 10 to 15 amperes during short circuit.
Q19.Why it is not necessary to provide protection for turn to turn fault
in alternator?A19. The coils of the modern alternators are single turn and therefore
it is not necessary to provide protection for turn to turn faults
Q20Why it is necessary to suppress field immediately after
disconnection of faulty alternator from the system?
A20. In the event of fault on the generator windings even though the
generator circuit breaker is tripped, the fault is continuous to fed as
long as the excitation will exist because the emf is induced in thegenerator. Hence it is necessary to suppress the field immediately
after disconnecting the faulty generator from the system
Q 21 Why it not necessary to provide over-voltage protection in
turbo-alternator?
-
7/28/2019 Power System Interview Question
5/10
A21. The over voltage occurs when the prime mover speed increases
due to sudden loss of the load on the generator and the speed control
governors in case of turbo-generators are very sensitive to the speed
variations and therefore generator over voltage of significant duration
or magnitude does not generally occur. This is the reason why
generators are not provided with over voltage protection
Q22.Where does Negative phase sequence relay is employed?
A22Negative sequence relay is employed for the protection of
generators and motors against unbalanced loading that may arise due
to phase to phase faults
Q23.What is the operation principle of differential relay?A23.A differential relay operates when the phasor difference of two
or more similar electrical quantities exceeds a pre-determined amount
Q24.Why distance protection is preferred as primary protection
compared to over current protection for transmission lines?
A24. Distance relay is superior to over current protection for the
protection of transmission lines. Some the reasons are faster
protection, simpler coordination, simpler application, permanentsettings without need for readjustment, less effect of the amount of
generation and fault levels, fault current magnitude, permits the high
line loading
Q25.Why biased differenial protection is preferred over simpledifferential protection?
A25. Biased differential relay is preferred because its operation is not
affected by the trouble arising out of the difference in the CTs ratios
for high values of external short circuit currents
Q26.Where Impedance relay, Reactance relay and Mho relays are
employed?
-
7/28/2019 Power System Interview Question
6/10
A26. The Impedance relay is suitable for the phase faults relaying for
the lines of moderate lengths Reactance type relays are employed for
the ground faults while Mho type of relays are best suited for the long
transmission lines and particularly where synchronizing power surge
may occur
Q27.What is percentage differential relay?
A27.It is a differential relay where the operating current required to
trip can be expressed as a percentage of load current
Q28.What are the main circuits in the Thermal Power Plant?
A28.Thermal Power plant consists of four main circuits, they are:
Feed water and steam flow circuit Coal and ash circuit Air and gas circuit Cooling water circuit
Q29.Steam power plant works on which cycle?
A29. Steam power plant works on the principle of Rankine Cycle
Q30.What is the Thermal efficiency of steam power plant?
A30. Thermal efficiency of steam power plant is defined as the ratio
of heat equivalent of mechanical energy transmitted to the turbine
shaft to the heat of combustion. Generally Thermal efficiency of the
steam power plant will be in the range of 30-35%
Q30.What is the overall efficiency of the Thermal Power Plant or
Steam Power Plant?
A30. Overall efficiency of the system is defined as the ratio of heat
equivalent of electrical output to the heat of combustion. Generally
Overall efficiency of the steam plant will always be less than the
thermal efficiency of the steam plant, it will be of the order of 29-33%
-
7/28/2019 Power System Interview Question
7/10
Overall efficiency of steam plant is determined by multiplying the
thermal efficiency of the plant with efficiency of the generator
(electrical efficiency)
Q31.Why the Thermal efficiency of the steam power plant is quitelow?
A31. In Steam power station, more than 50% of the total heat of
combustion is lost as heat rejected to the condenser and the loss is
unavoidable as the heat energy cannot be converted in to mechanical
energy with out a drop in temperature. Steam in the condenser is at
lowest temperature. This is the reason that the thermal efficiency of
the power plant is quite low.
Q32.On what factors efficiency (thermal) of the steam plant depends?
A32. Efficiency of the thermal plant depends on three factors, they are
1.pressure of steam entering the turbine2. temperature of the steam entering the turbine3.pressure in the condenser
Thermal efficiency increases with increase in temperature and
pressure of the steam entering the turbine. For this reason high
temperature and pressure are used. Thermal efficiency is effectively
increased by decreasing the pressure in the condenser, so pressure in
the condenser is kept as low as possible.
Thermal efficiency also increases by reheating the steam between
turbine stages
Q33. What for series and shunt compensation provided in EHV
transmission lines?
A33. Series capacitance is provided in EHV lines to artificially reduce
the series reactance of the line so as to improve stability, voltage
regulation and transmission efficiency
-
7/28/2019 Power System Interview Question
8/10
Shunt compensation is provided to artificially reduce the line
susceptance so as to improve the voltage regulation under light load
condition
Q34. What is the material used for overhead transmission lines?
A34. ACSR conductors are employed.
Q35. What are the problems associated with EHV transmission?
A35: The problems associated with EHV transmission are corona loss
and radio interference, requirement of heavy supporting structures and
insulation requirments
Q36 Why does surge impedance loading (SIL) increase with increasein voltage level?
A36: SIL varies as the square of the operating voltage, so SIL
inceases with increase in voltage level
Q37. What are the factors that limit the maximum power transfer
capability in a transmission line?
A37: Some of the factors which limits the maximum power transfer
are:
1.Electrical phase shift2.Voltage drop3.Thermal effects in the line
Q38. Explain some of the methods to improve the strength of
transmission system?A38.
Introducing or adding of new transmission lines in to the systemto avoid the overloading of the existing lines
Application of devices such as series capacitors in the rightlocation of power system which helps in increase in the power
transfer capability
Up gradation of the existing transmission system
-
7/28/2019 Power System Interview Question
9/10
Adoption of multi-voltage levels an multi-circuits in the existingac transmission system
Q39. Why phase shift is kept low for transmission of power for largedistances?
A39.
E1 X E2
Power delivered P = --------- Sin
X
Generally is kept low (around 30o) because any disturbance can
affect the stability of the system if value is high.
Q40.How energy is generated in Nuclear power plant?
A40. In Nuclear power plant energy is released by nuclear fission.
Nuclear fission is the process in which heavy nucleus such as233
92U,235
92U,and239
94Pu when bombarded by certain particles ( protons,
neutrons, X-rays), the heavy nucleus will split into two or more
smaller nuclei, ejection of two or more neutrons and liberation of vast
amount of energy. Therefore this split of heavy nucleus into two or
more smaller nuclei is calledfission process.
Q41.What are the particles used in nuclear fission?
A41. High energy alpha particles, protons, deuterons, X-rays as well
as neutrons can be used for the fission process. However neutrons are
chosen because neutrons are electrically neutral in nature and thusthey do not require high kinetic energy to overcome electrical
repulsion from the positively charged nuclei and can participate in
fission reaction.
Q42.What is fertile material and fissile material?
A42.Not all the Uranium extracted from the ore can be used as fuel
for plant for carrying out the fission reaction. Natural uranium
-
7/28/2019 Power System Interview Question
10/10