powerpoint presentation · 4/18/2016 3 explosion venting •a cover that opens at a given...
TRANSCRIPT
4/18/2016
1
Failing protective measures: what happened?
Dr. Scott G. Davis
617-407-3300
GexCon US
Bethesda, Maryland
Generally accepted protective safety measures
• Containment
• Explosion venting including flameless venting
• Suppression
• Isolation techniques
2
Standards protective systems in USA
NFPA 68
Vent sizing dust explosions
NFPA 68
Venting devices
NFPA 69
Explosion resistant products
NFPA 69
Explosion isolation
3
4/18/2016
2
Containment: explosion resistant equipment
• Designed to withstand maximum explosion pressure with or without allowance for deformation
• Possible design for lower overpressure when in combination with venting or suppression
• Shall allow for pressure piling in case of connected equipment
• Main reasons for failure: poor design and no isolation or design for pressure piling
4
Failure of containment: pressure piling
5
6
Pressure piling
4/18/2016
3
Explosion Venting
• a cover that opens at a given overpressure as a result of an explosion.
• leads to a “leakage” that stops the explosion pressure exceeding the maximum pressure that the process vessel can withstand.
Explosion vent panels
7
Explosion venting
8
Example of pressure development
9
4/18/2016
4
Explosion venting and what can cause it to fail
• Pros
• Passive system, low-cost, low maintenance
• Render the equipment effectively “explosion proof”
• Cons (things to look for in investigation)
• Should not be used in buildings
• If inside long vent ducts or quench pipes (reduce efficiency
• External blast and flames (can cause fires)
• Design
• Was adequate area utilized
• Passive - Maintenance forgotten
10
Calculation of necessary vent area
• Calculated using various methods, e.g.:
• NFPA 68, Standard on Explosion Protection by Deflagration Venting, 2013 Edition (USA)
• EN14491 Dust Explosion Venting Protective Systems (March 2006)
11
Necessary information for vent area calculation
• Explosion properties, Pmax and KSt-value (did the dust explosion properties change?)
• Geometry (volume, length, diameter, vent location, and presence of venting ducts if applicable) (were they all taken into account when designing the vent opening)
• Design/tolerance pressure of process vessel (Pred) (was there any calculation/assessment performed to determine the strength of the process vessel?)
• Opening pressure of the vent panels, (Pstat)
12
4/18/2016
5
Explosion venting – poor design
13
Trends and relationships
• Large volume large vent area
• Small volume small vent area
• Weak process vessel large vent area
• Strong process vessel small vent area
• High (dP/dt)max or KSt-value large vent area
• Low (dP/dt)max or KSt-value small vent area
• High opening pressure (Pstat) large vent area
• Low opening pressure (Pstat) small vent area
14
Cylindrical enclosures (silo)
• Venting device at end
High L/D ratio
• If venting device is located near the middle, the maximum flame length is reduced
Lower L/D ratio
• “Conclusion”: Position of vent panels (relative to ignition location) is IMPORTANT.
15
4/18/2016
6
16
17
Reduced venting efficiency
• Presence of flame arrester/dust retention
• Inertia of venting device
• Venting via ducts
• Blockage of vent area
18
4/18/2016
7
Influence of venting ducts
Reduces the efficiency of venting
0
0.5
1
1.5
2
2.5
0 1 2 3 4 5 6 7
pre
d(b
ar)
Vent duct length (m)
V=1m3; KSt = 200 bar-m/s, A = 0,196 m2
19
Bag filters can block the vent area
Proper venting arrangements: vertical filters
20
Improper venting arrangement: vertical filter
Reduce the effective vent area
21
4/18/2016
8
Examples of poor design: bag filter
22
Bag filter after explosion
Big damage in spite of explosion venting
23
Poor design: possible cause
Blockage of vent opening by filter bags
24
4/18/2016
9
External effects: flames
Flame length ejected from vent:
– K = 10 for metal dust; K = 8 for agricultural or chemical dusts
– when V = 50 m3, single vent, chemical dust LFH = 30 m
Flame deflector
𝐷 = 𝐾 ∙𝑉
𝑛
1 3
25
26
External effects: pressure waves & recoil forces
27
4/18/2016
10
Other important design related aspects to consider:
“Vacuum breakers”
(when using self closing panels)
28
Example – Implosion Damage Investigation
29
Background
30
Single burner, recirculating solids ring dryer
Not equipped with a vacuum breaker
4 deflagration incidents → each resulting from a unique chain of events
Similarities
observed overpressures
number of vent doors opened
Internal vacuum which collapsed sections of the dryer
4/18/2016
11
Model of the dryer
31
Ring recirculation portion
Solids introduced
Recirculation fan
Equipment imploded during three of the four incidents
32
1st Incident 2nd Incident 3rd Incident
33
Considered dust clouds located throughout the dryer
Downstream of burnerIn exhaust headerIn drying column
In pre-separator In section of ring In a cyclone
4/18/2016
12
34
Pressure and flame front development with ignition in the exhaust header
Not enough. Needed cooling to obtain Pmin 20 sec after incident.
Flameless venting devices
Allows explosion venting inside buildings
35
Potential causal factors with flameless venting devices into rooms
• Safety distance (combustion gases or hot)
• Increase of pressure inside building/room
• Reduced venting efficiency
36
4/18/2016
13
Venting into safe direction: hot combustion products are released
37
Improper venting into building/ blocking of vent
38
Possible reasons for deflagration vent failure
• Improper design
• Use of wrong explosion properties (e.g. no change of vent size after change of process)
• Strength protected vessel
• Geometrical aspects not taken into account• No account for external effects (pressure waves, flames,
safety zone)
• Blockage of vent opening (reduced efficiency)
• Other aspects
• Can lead to fires
• Passive system - maintenance is forgotten
Venting is not that easy – system must be evaluated
39
4/18/2016
14
Explosion suppression
• Fast-acting extinguishing systems that are activated at an early stage of an explosion thus quenching it.
• Requires fast and reliable detection system. Need to evaluate the design
• Often the only solution in many situations, e.g., Protection of coupled systems.
40
Explosion suppression
41
Pressure at
sensor
reaches
activation
levelIgnition
Opening of HRD Suppressant
reaches flame
Explosion
is
suppressed
time = 0 ms
pressure = 0
bar
time = 20 ms
pressure = 0.05
bar
time = 30 ms
pressure = 0.1
bar
time = 50 ms
pressure = 0.2
bar
time = 75 ms
pressure = 0.25
bar
Explosion suppression
42
4/18/2016
15
Venting vs. ….
43
….successful suppression
44
Successful suppression
45
4/18/2016
16
Explosion suppression in time
• Early detection of explosion
• Rapid identification of signal and action plan
• Rapid activation of suppressors
• Rapid distribution of suppressant
• Fast quenching of explosion flame
46
Prevention of false activation:
dynamic pressure detection
t
p t 0
t0
p = pt 0
p agw
t 0t
p
Explo
sio
n p
ressure
p [
bar]
time t [ms]
a
- t
- t
47
Failure due to explosion suppression: summary
• Improper design
• False activation
• Use of wrong explosion properties (e.g. no change of activation time after change of process)
• Strength protected vessel
• Geometrical aspects not taken into account
• Other aspects
• Active system - maintenance needs to be performed at least once every year; inspection every quarter
48
4/18/2016
17
• Problem: explosion will be able to propagate from one process unit to an interconnected one.
• “Pressure piling”, designing protective equipment for interconnected process units not possible with simple calculation methods (such as NFPA 68 for explosion venting)
• Result: uncontrollable explosion development and high explosion pressures may arise.
Explosion isolation
49
Cannot be used for interconnected vessels
50
Pressure piling in interconnected vented vessels
51
4/18/2016
18
Explosion isolation
52
53
Can it really happen?
Passive isolation devices
• Self-closing explosion isolation valves
–Ventex valves
–Flap valves
• Rotary valves
• Explosion diverters
54
4/18/2016
19
Self-closing explosion valves
Ventex-ESI-E/-D/-C
Ventex valve
55
Typical application: clean side of filter to protect fan
• Low dust concentrations only (< 50 g/m3); might fail at higher dust concentrations
• Should be placed horizontally, 5 m from where the explosion starts, shorter installation distances might make it fail
Ventex valve
56
Self-closing explosion valves
• Is especially used in combination with dust collectors/filters
• Open during normal process conditions, closes in case of explosion due to flow reversal
Explosion isolation flap valve
57
4/18/2016
20
Explosion isolation flap valve
58
Explosion isolation flap valve
59
Possible reasons for isolationflap valve failure• Is the valve at the correct distance - dependent on closing
time valve (weight, dimensions); typically a few meters (is dust explosion property dependent)
• Can the valve withstand the expected explosion pressure
• Possible issues: re-opening during explosion venting event and dust settling at seal
• Regular inspection
60
4/18/2016
21
Rotary valve
61
Rotary valve
62
Possible reasons for rotary valve failure
• Poor design (dust explosion properties, maximum expected explosion pressure vs. strength of housing or blades)
• Erosion of blades: increase of gap width beyondcritical gap width
63
4/18/2016
22
Explosion diverter
Protective catching device
Explosion venting device
Flow reversal
In combination with
extinguishing barrier64
• Reversal of flow from inner pipe by 1800
• No full explosion isolation possible but avoids flame jet ignition and allows
for “normal” design of protective measures of coupled equipment
Possible reasons for explosiondiverters failing
• Explosion pressures generated exceed mechanicalstrength (poor design)
• High static opening pressure or specific weight ofexplosion venting device
• Poor design (shall be in accordance with EN 16020)
65
Active explosion isolation systems
• Slam shut valves
• Extinguishing barriers
• Elements:
–Detection
–Control unit
– Isolation device
66
4/18/2016
23
Active isolation system using an extinguishing
barrier
Extinguishing
barrier
Infrared
detector
67
Extinguishing barrier
• Installation distance dependent on KSt-value, process conditions, detection principle, geometry aspects, deployment time barrier
• Suppressant concentration in barrier shall be sufficiently high during explosion event
68
Extinguishing barrier
69
4/18/2016
24
Extinguishing barrier
70
Failure of extinguishing barrier
• Improper design
• False activation
• Use of wrong explosion properties (e.g. no change of offset distance after change of process)
• Geometrical aspects not taken into account
• Other aspects
• Active system - maintenance needs to be performed regularly
71
Active isolation system using a slam
shut valve
72
4/18/2016
25
Slam shut valve
• Installation distance dependent on KSt-value, process conditions, detection principle, geometry aspects, closing time valve
• Valve shall be able to withstand maximum (reflected) pressure at valve location
73
Maximum installation distance
• Strength of ducting, valve
• DDT = Deflagration Detonation Transition
– DDT for gas = 40D
– DDT for dust = 80D
74
Explosion isolation: slam shut valve
75
4/18/2016
26
Explosion isolation: slam shut valve
76
Failure of slam shut valve
• Improper design
• False activation
• Use of wrong explosion properties (e.g. no change of offset distance after change of process)
• Geometrical aspects not taken into account
• Other aspects
• Active system - maintenance needs to be performed regularly
77
Failure of protective measures: summary
The main factors for protective measures failing include:
• Improper design
• No use of guidelines
• Use of wrong explosion properties (e.g. no change of vent size after change of process)
• Strength of protected equipment underestimated (incl. vacuum)
• Geometrical aspects not taken into account
• Blockage of vent openings (reduced efficiency)
• Other aspects
• Poor maintenance
• Safety zones
• Prevention of false activation of active systems
78