pre-engineered pipe supports, guides & anchors

16
1-800-443-9194 I Made in America 12 I www.AdvancedThermal.net Advanced Thermal Systems, Inc. Pre-Engineered Pipe Supports, Guides & Anchors

Upload: others

Post on 26-Dec-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Pre-Engineered Pipe Supports, Guides & Anchors

1 - 8 0 0 - 4 4 3 - 9 1 9 4 I M a d e i n A m e r i c a 12 I w w w . A d v a n c e d T h e r m a l . n e t

Advanced Thermal Systems, Inc.

Pre-Engineered Pipe Supports,Guides & Anchors

Page 2: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

2 12 Proudly Manufactured in the U.S.A.

1. The Primary and Intermediate Guide Spacings shown are for standard weight pipe and are satisfactory for above ground or tunnel installation. They are applicable to the following:

A. Single Expansion Joints with an integral anchor or Single Expansion Joints installed immediately adjacent to a line anchor.

B. Double Expansion Joints.

2. When a single expansion joint without base is installed in the center (or approximate center) of a pipe run, the primary guide spacing should be modified as follows:

A. Sizes 1-1/2” to 4” inclusive: Six (6) pipe diameters from each end of the expansion joint.

B. Sizes 5” to 24” inclusive: Three (3) pipe diameters from each end of the expansion joint. To preclude the possibility of cocking the slip of, heavier expansion joints, (sizes 6” and larger), a sliding support under the expansion joint body is recommended.

3. For buried conduit systems with expansion joints installed in manholes or vaults, a guide should be installed at the termination of the conduit pipe at the manhole wall (e.g.,gland or link seal). In addition, consideration should be given to providing a “Moment” guide within 10 feet of the manhole wall (not to be integrally attached to the manhole wall). LOW FRICTION NON-METALLIC “BRONZALON®” GUIDE INSERTS SHOULD BE SPECIFIED FOR THE EXPANSION JOINT.

4. GUIDE/SUPPORT SELECTION:

PRIMARY GUIDES: The preferred designs are those that guide the pipe radially such as the ATS Models “GA”. For low profile systems the ATS Low Friction Figure 100, 101, and 101 M Series Graphite Guides can be used, (consult factory for applications).

INTERMEDIATE GUIDES: The ATS Low Friction Figure 100,101 and 101 M Graphite Guides are recommended to reduce friction forces and eliminate corrosion of the sliding components.

INTERMEDIATE SUPPORTS: The ATS Low Friction Figure 200, 201 and 201 M Graphite Supports are recommended to reduce friction forces and eliminate corrosion of the sliding components.

5. The pipe guiding and support spacing shown in Table 1 is the suggested maximum span as specified by the ASME/ANSI Power Piping Code B31.1, and is applicable for horizontal straight runs of pipe without concentrated loads such as valves or heavy fittings between supports. The span distance applies to standard weight or heavier pipe operating at a maximum temperature of 750°F (400°C).

6. LATERAL FORCES ON GUIDES:

Pipe Alignment Guides and their support structure may be subjected to lateral forces in addition to the frictional forces along the longitudinal axis of the pipe. It is recommended that alignment guides be designed to resist a lateral force equal to 250 lb./inch of nominal pipe size.

General Guidelines for Guiding & Supporting Pipe

7. THERMALLY INDUCED CHANGES OF PIPELINES:

Pipelines will always change in length as the temperature of the pipeline changes. This change must be accommodated by some method, either by natural flexibility of the pipeline or by use of an expansion device. Advanced Thermal Systems “TP2” Thermal Pak Expansion Joints are the ideal selection when long straight runs of pipe are involved.

Table 2 is used to determine the total change in length of the pipe run based upon the maximum and minimum temperatures of the system. The net change in length of the pipe run per 100 ft. of piping is the algebraic difference between the expansion constant at the highest temperature and the expansion constant at the lowest temperature. This difference is then multiplied by the total length of the pipe run divided by 100.

EXAMPLE:Determine the total change in length of a 250 feet long pipe run that is designed for 300 psig saturated steam (422° F) and is being installed outside where the ambient temperature may reach 20° F.

Table 1: Pipe Alignment Guide and Support Spacing

NOMINAL PIPE SIZE

(NPS)

PRIMARY (1st) GUIDE FROM

END(S) OF SLIP (feet)

INTERMEDIATE GUIDE SPACING (feet) PIPE SUPPORT

SPACING (Feet)PRESSURE (psig)

100 150 300 400 WATER STEAM

1 1⁄2 1 1⁄2 8 8 7 7 8 102 2 9 9 8 8 10 13

2 1⁄2 2 12 12 11 11 11 143 3 15 15 12 12 12 154 4 20 20 18 16 14 175 6 28 27 25 22 16 186 6 35 33 30 27 17 218 8 48 45 40 35 19 24

10 8 65 60 55 50 22 2712 12 75 70 60 55 23 3014 12 80 75 65 60 25 3216 16 80 85 75 70 27 3518 20 100 95 85 80 28 3720 20 110 105 95 90 30 3924 25 130 125 110 100 32 42

(3.44 – 0.15) x (250⁄100) = 8.23 in.

NOTE:The minimum temperature may not be the installation temperature.

Page 3: Pre-Engineered Pipe Supports, Guides & Anchors

1-800-443-9194 Advanced Thermal Systems, Inc.

Pre-Engineered Pipe Supports, Guides & Anchors 12 3

Low Friction Graphite Pipe Guides and Pipe Supports

SATURATED STEAM VACUUM IN HG BELOW 212°F, PRESSURE,

PSIG ABOVE 212°FTEMP. °F CARBON & CARBON

MOLYBDENUM STEEL

0 0.0020 0.1540 0.30

29.39 60 0.4528.89 80 0.5827.99 100 0.7526.48 120 0.9124.04 140 1.0620.27 160 1.2014.63 180 1.366.45 200 1.520.0 212 1.612.5 220 1.68

10.3 240 1.8420.7 260 2.0234.5 280 2.1852.3 300 2.3574.9 320 2.53

103.3 340 2.70138.3 360 2.88150.0 366 2.93180.9 380 3.06232.4 400 3.23293.7 420 3.42300.0 422 3.44366.1 440 3.60451.3 460 3.78550.3 480 3.96664.3 500 4.15795.3 520 4.34945.3 540 4.531115 560 4.731308 580 4.931525 600 5.131768 620 5.332041 640 5.532346 660 5.752705 680 5.953080 700 6.16

720 6.36740 6.57780 7.00800 7.23820 7.45840 7.66880 8.10900 8.34

Table 2: Thermal Expansion of Steel Pipe (inches per 100 ft.)

PIPE SIZE (NPS) STYLE ATS FIG NO.

MOVEMENTAXIAL LATERAL

1 to 2 1⁄2 Not Insulated 100 8” 03 to 24 Not Insulated 101 8” 01 to 2 1⁄2 Not Insulated 200 8” ±3”3 to 24 Not Insulated 201 8” ±3”3 to 24 Pre-Insulated 101M ±4” 03 to 24 Pre-Insulated 201M ±4” ±3”

Table 3: ATS Low Friction Guide and Support Selection Table

FINISHCODE

FINISH TYPE

P One Coat Shop PrimerE EpoxyG Hot-Dip Galvanized

Table 4: Available Finishes

Finish (Table 4)Graphite Mechanical Attachment: A - > 350°F (omit for < 350°F)

Lateral Movement, in. (omit for Fig. 100, 101 and 101-M)

Axial Movement, in.Insulation Thickness, in.

Attachment: W - Weld, B - BoltFigure No. (Table 3)

Pipe Size, NPS

ORDER BY CATALOG NUMBER

24” Fig. 201 W 4 8 3 A P

** Specify Maximum Service Temperature

ATS QUALITY AND SERVICE FOR PROVEN RELIABILITY:

• Standard Designs for Welding or Bolting to support structure.

• 1/2” Thick Graphite on both upper and lower assemblies. Epoxy bonded for applications up to 350°F, epoxy bonded and mechanically attached for applications over 350°F.**

• Furnished standard with shop primer on all carbon steel components. Hot-Dip Galvanized or Epoxy Paint also available.

• Custom designs available with additional axial and/or lateral movement or to accommodate thicker insulation.

GRAPHITE PROPERTIESCompressive Strength 2000 psiTemperature Range -20°F to +750°FCoefficient of Friction 0.15

Page 4: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

4 12 Proudly Manufactured in the U.S.A.

Low Friction Guides and Supports for Use in Hot Service

FIG. 100-W

FIG. 200-W

1/2"

A

8"

11"

4"

C

C

C

±1/8

AXIAL MOVEMENT

PIPE SIZE

SUPPORTSTEEL8"

116

2" MAXIMUMINSULATIONTHICKNESS

LOWERBASEASSEMBLY

UPPERT-BARASSEMBLY

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

1414

11 -5211 -52

1414

11 -5211 -52

PIPE MOVEMENTCOLD TO HOT

"

1/2"

A

8"

11"

4"

±1/8

AXIAL MOVEMENT

PIPE SIZE

11 14

"±3" LATERAL MOVEMENT

2" MAXIMUMINSULATIONTHICKNESS

LOWERBASEASSEMBLY

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

1414

11 -5211 -52

1414

11 -5211 -52

PIPE MOVEMENTCOLD TO HOT

SUPPORTSTEEL

UPPERT-BARASSEMBLY

C

C C

Fig. 201-B Low Friction Support

1/2"

A

8"

11"

4"

C

C

C

±1/8

AXIAL MOVEMENT

PIPE SIZE

SUPPORTSTEEL8"

116

2" MAXIMUMINSULATIONTHICKNESS

LOWERBASEASSEMBLY

UPPERT-BARASSEMBLY

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

1414

11 -5211 -52

1414

11 -5211 -52

PIPE MOVEMENTCOLD TO HOT

"

1/2"

A

8"

11"

4"

±1/8

AXIAL MOVEMENT

PIPE SIZE

11 14

"±3" LATERAL MOVEMENT

2" MAXIMUMINSULATIONTHICKNESS

LOWERBASEASSEMBLY

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

1414

11 -5211 -52

1414

11 -5211 -52

PIPE MOVEMENTCOLD TO HOT

SUPPORTSTEEL

UPPERT-BARASSEMBLY

C

C C

Page 5: Pre-Engineered Pipe Supports, Guides & Anchors

1-800-443-9194 Advanced Thermal Systems, Inc.

Pre-Engineered Pipe Supports, Guides & Anchors 12 5

Low Friction Guides and Supports for Use in Hot ServiceLow Friction Guides and Supports for Use in Hot Service

FIG.100 and FIG. 200 Dimensions

PIPE SIZE

(NPS)

DIM. (in.)

GRAPHITE BEARING

AREA (Sq. in.)

WEIGHT(lbs.)

A

1 5 5⁄16 9 221 1⁄4 5 1⁄2 9 221 1⁄2 5 5⁄8 9 222 5 13⁄16 9 22

2 1⁄2 6 1⁄16 9 22

NOTES:1. See Page 2 for general

information pertaining to Figure 100 and Figure 200 Pipe Guides and Supports.

2. Dimension “A” is for maximum insulation thickness shown. For applications requiring thicker insulation, Dimension “A” will increase accordingly.

3. Graphite is epoxy bonded to steel for applications up to 350°F, epoxy bonded and mechanically attached for applications over 350°F.

FIG. 100-B

FIG. 200-B

1/2"

A

2" MAXIMUMINSULATIONTHICKNESS

8"

11"

4"

C

10"

C

CPIPE MOVEMENT

COLD TO HOT

UPPERT-BARASSEMBLY

±1/8AXIAL MOVEMENT

PIPE SIZE

8 1"2

116

5"8

DIA

2 HOLES

2"

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

LOWERBASEASSEMBLY

1414

11 -5211 -52

"

A

8"

11"

4"

±1/8

AXIAL MOVEMENT

PIPE SIZE

11 14

"

12 34

"

±3" LATERAL MOVEMENT2"

LOWERBASEASSEMBLY

2" MAXIMUMINSULATIONTHICKNESS

UPPERT-BARASSEMBLY

1414

11 -5211 -52

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

1/2"

5"8

DIA

2 HOLES

PIPE MOVEMENTCOLD TO HOTC

C C

Fig. 101-W Low Friction Support / Guide Fig. 101M-W Pre-Insulated Low Friction Support / Guide

Page 6: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

6 12 Proudly Manufactured in the U.S.A.

Weld Down Base Low Friction Graphite Guides and Supports for Use in Hot Service

FIG. 101-W

FIG. 201-W

PIPE SIZE

(NPS)

DIMENSION (inches)GRAPHITE BEARING AREA

(Sq. in.)

FIG NO. WEIGHT

A B C D E101-W 201-W 101-W 201-W

F F lbs. lbs.3 7 1⁄8 3 11 4 1⁄2 16 9 1⁄2 11 31 274 7 5⁄8 3 11 4 1⁄2 16 9 1⁄2 11 31 275 8 3⁄16 3 11 4 1⁄2 16 9 1⁄2 11 31 276 9 13⁄16 4 12 5 1⁄2 20 10 1⁄2 12 41 358 10 13⁄16 4 12 5 1⁄2 20 10 1⁄2 12 41 35

10 11 7⁄8 4 12 5 1⁄2 24 12 13 47 3912 12 7⁄8 4 12 5 1⁄2 24 12 13 47 4014 13 1⁄2 4 12 5 1⁄2 24 12 13 47 4016 14 1⁄2 4 12 5 1⁄2 24 12 14 47 4018 15 1⁄2 4 12 5 1⁄2 24 12 14 47 4020 16 1⁄2 4 12 5 1⁄2 24 12 14 51 4524 18 1⁄2 4 12 5 1⁄2 28 13 15 61 56

NOTES:1. See Page 2 for general information pertaining to Figure 101 and Figure 201 Pipe Guides and Supports.

2. Dimension “A” is for nominal insulation thickness shown (Dimension “B”). For applications requiring thicker insulation, Dimension “A” will increase accordingly.

3. Graphite is epoxy bonded to steel for applications up to 350°F, epoxy bonded and mechanically attached for applications over 350°F.

E

A

"PIPE SIZE"

LOWER BASE

B MAXIMUMINSULATION

PIPE MOVEMENT

8"AXIAL MOVEMENT

C

D

±1/8

UPPER CRADLE

F

116

1414

11 -5211 -52

1414

11 -5211 -52

ASSEMBLY

STEEL COMPONENTS

1/2" GRAPHITE PLATESEPOXY BONDED TO

SUPPORTSTEEL

ASSEMBLY

THICKNESS

COLD TO HOT

"

C

C C

E

A

"PIPE SIZE"

LOWER BASE

B MAXIMUMINSULATION

PIPE MOVEMENT

8"AXIAL MOVEMENT

C

D

±1/8

UPPER CRADLEASSEMBLY

F

±3" LATERAL MOVEMENT

STEEL COMPONENTS

1/2" GRAPHITE PLATESEPOXY BONDED TO

SUPPORTSTEEL

ASSEMBLY

THICKNESS

COLD TO HOT

1414

11 -5211 -52

1414

11 -5211 -52

C

C C

Page 7: Pre-Engineered Pipe Supports, Guides & Anchors

1-800-443-9194 Advanced Thermal Systems, Inc.

7Pre-Engineered Pipe Supports, Guides & Anchors 12

Bolt Down Base Low Friction Graphite Guides and Supports for Use in Hot Service

FIG. 101-B

FIG. 201-B

PIPE SIZE

(NPS)

DIMENSION (inches) GRAPHITE BEARING AREA (Sq. in.)

FIG NO. WEIGHT101-B 201-B 101-B 201-B

A B C D E F G H J H J lbs. lbs.

3 7 1⁄8 3 11 4 1⁄2 2 1⁄2 5⁄8 16 11 1⁄2 10 14 1⁄2 13 29 284 7 5⁄8 3 11 4 1⁄2 2 1⁄2 5⁄8 16 11 1⁄2 10 14 1⁄2 13 29 285 8 3⁄16 3 11 4 1⁄2 2 1⁄2 5⁄8 16 11 1⁄2 10 14 1⁄2 13 29 286 9 13⁄16 4 12 5 1⁄2 3 1⁄4 3⁄4 20 13 11 1⁄4 16 14 1⁄4 44 388 10 13⁄16 4 12 5 1⁄2 3 1⁄4 3⁄4 20 13 11 1⁄4 16 14 1⁄4 44 38

10 11 7⁄8 4 12 5 1⁄2 3 1⁄4 7⁄8 24 15 13 18 16 51 4312 12 7⁄8 4 12 5 1⁄2 3 1⁄4 7⁄8 24 15 13 18 16 51 4314 13 1⁄2 4 12 5 1⁄2 3 1⁄4 7⁄8 24 15 13 18 16 51 4316 14 1⁄2 4 12 5 1⁄2 3 1⁄4 7⁄8 24 15 13 18 16 51 4318 15 1⁄2 4 12 5 1⁄2 3 1⁄4 7⁄8 24 15 13 18 16 51 4320 16 1⁄2 4 12 5 1⁄2 3 1⁄4 7⁄8 24 15 13 18 16 55 4824 18 1⁄2 4 12 5 1⁄2 3 1 28 16 13 3⁄4 19 16 3⁄4 66 60

NOTES:1. See Page 2 for general information pertaining to Figure 101 and Figure 201 Pipe Guides and Supports.

2. Dimension “A” is for nominal insulation thickness shown (Dimension “B”). For applications requiring thicker insulation, Dimension “A” will increase accordingly.

3. Graphite is epoxy bonded to steel for applications up to 350°F, epoxy bonded and mechanically attached for applications over 350°F.

E

A

"PIPE SIZE"

B MAXIMUMINSULATION

PIPE MOVEMENT

8"AXIAL MOVEMENT

C

D

±1/8

UPPER CRADLEASSEMBLY

H

F

4 HOLESG DIA.

J

LOWERBASEASSEMBLY

COLD TO HOT

THICKNESS

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

1414

11 -5211 -52

116

"

C

C C

E

A

"PIPE SIZE"

PIPE MOVEMENT

8"AXIAL MOVEMENT

C

D

±1/8

H

F

4 HOLESG DIA

J

±3" LATERAL MOVEMENT

UPPER BASEASSEMBLY

COLD TO HOT

UPPER CRADLEASSEMBLY

1/2" GRAPHITE PLATES EPOXY BONDED TO STEEL COMPONENTS

1414

11 -5211 -52

B MAXIMUMINSULATIONTHICKNESS

C

C C

Page 8: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

8 12 Proudly Manufactured in the U.S.A.

NOTES:1. See Page 2 for general information pertaining to Figure 101M and Figure 201M Pipe Guides and Supports.

2. Units furnished standard with split line horizontal as shown, can be furnished with split line at 45° to permit pipe nesting.

3. Dimension “A” is for nominal insulation thickness shown. For applications requiring thicker insulation, Dimension “A” will increase accordingly.

4. Load rating shown is based on E.H. pipe filled with water spaced in accordance with ASME/ANSI B31.1 Power Piping Code. (Table 1). Guides and Supports with higher load ratings available on application.

Pre-Insulated Graphite Guides and Supports - Weld Down Base

FIG. 201-M-W

PIPE SIZE (NPS)

LOAD RATING

(lbs.)

DIMENSION (inches)GRAPHITE BEARING

AREA (Sq. in.)

FIG NO. WEIGHT

A B C D E101M-W 201M-W 101M-W 201M-W

F F lbs. lbs.3 1,100 7 1⁄4 11 1⁄2 8 1⁄8 4 10 12 8 1⁄2 11 50 464 1,500 7 3⁄4 12 1⁄2 9 1⁄8 4 10 12 8 1⁄2 11 54 495 1,800 8 1⁄4 13 1⁄2 10 1⁄8 4 10 12 8 1⁄2 11 56 506 2,600 9 1⁄8 14 5⁄8 11 1⁄4 5 12 20 9 1⁄2 12 71 668 3,400 10 1⁄8 17 1⁄8 13 1⁄4 5 12 20 9 1⁄2 12 85 80

10 4,300 11 1⁄4 19 3⁄8 15 1⁄2 5 12 20 10 1⁄2 12 88 87 12 5,100 12 1⁄4 21 3⁄8 17 1⁄2 5 12 20 10 1⁄2 12 100 92 14 5,600 13 22 3⁄8 18 1⁄2 5 12 24 11 1⁄2 13 104 97 16 6,400 14 1⁄8 24 7⁄8 20 5⁄8 5 12 32 13 1⁄2 15 124 117 18 7,200 15 1⁄8 26 7⁄8 22 5⁄8 5 12 32 14 1⁄2 15 134 126 20 8,000 16 1⁄8 28 7⁄8 24 5⁄8 5 12 32 14 1⁄2 15 141 139 24 11,200 18 1⁄8 32 7⁄8 28 5⁄8 5 14 40 15 1⁄2 17 174 180

FIG. 101-M-W

2

A

C

B2" NOMINALINSULATION

±1/8

±3/16

UPPER ASSEMBLY

DIA.

(160 PSI CALCIUM SILICATE INSUL.)

LOWER ASSEMBLY

E

1/2" GRAPHITE PLATESEPOXY BONDED TO

INSULATIONSUPPORT SHIELD .016" EMBOSSED

ALUMINUM JACKETWITH MOISTURE BARRIER

D

18"

F1/2"

CL4" 4"

ASTM A307 ZINCPLATED BOLTS.

14

14

SUPPORTSTEEL

1 -521

1 -51

AXIAL MOVEMENT

THICKNESS

STEEL COMPONENTS

C

C C

116

"

2

A

C

B2" NOMINALINSULATION

±1/8

±3/16

UPPER ASSEMBLY

DIA.

(160 PSI CALCIUM SILICATE INSUL.)

LOWERASSEMBLY

E

1/2" GRAPHITE PLATESEPOXY BONDED TO

INSULATIONSUPPORT SHIELD

±3" LATERAL MOVEMENT

.016" EMBOSSED ALUMINUM JACKETWITH MOISTURE BARRIER

D

18"

F

1/2"

CL4" 4"

ASTM A307 ZINCPLATED BOLTS.

14

14

SUPPORTSTEEL

1 -521

1 -51

AXIAL MOVEMENT

STEEL COMPONENTS

THICKNESS

C

C C

Page 9: Pre-Engineered Pipe Supports, Guides & Anchors

1-800-443-9194 Advanced Thermal Systems, Inc.

Pre-Engineered Pipe Supports, Guides & Anchors 12 9

Pre-Insulated Graphite Guides and Supports - Bolt Down Base

NOTES:1. See Page 2 for general information pertaining to Figure 101M and Figure 201M Pipe Guides and Supports.

2. Units furnished standard with split line horizontal as shown, can be furnished with split line at 45° to permit pipe nesting.

3. Dimension “A” is for nominal insulation thickness shown. For applications requiring thicker insulation, Dimension “A” will increase accordingly.

4. Load rating shown is based on E.H. pipe filled with water spaced in accordance with ASME/ANSI B31.1 Power Piping Code. (Table 1). Guides and Supports with higher load ratings available on application.

FIG. 101-M-B

FIG. 201-M-B

PIPE SIZE

(NPS)

LOAD RATING

(lbs.)

DIMENSION (inches)GRAPHITE BEARING

AREA (Sq. in.)

FIG NO. WEIGHT

A B C D E F G101M-B 201M-B 101M-B 201M-B

H J H J lbs. lbs.3 1,100 7 1⁄4 11 1⁄2 8 1⁄8 4 10 2 1⁄2 5⁄8 12 10 1⁄2 9 13 1⁄2 12 52 48 4 1,500 7 3⁄4 12 1⁄2 9 1⁄8 4 10 2 1⁄2 5⁄8 12 10 1⁄2 9 13 1⁄2 12 56 51 5 1,800 8 1⁄4 13 1⁄2 10 1⁄8 4 10 2 1⁄2 5⁄8 12 10 1⁄2 9 13 1⁄2 12 58 53 6 2,600 9 1⁄8 14 5⁄8 11 1⁄4 5 12 3 1⁄4 3⁄4 20 12 1⁄2 10 1⁄4 15 13 1⁄4 74 69 8 3,400 10 1⁄8 17 1⁄8 13 1⁄4 5 12 3 1⁄4 3⁄4 20 12 1⁄2 10 1⁄4 15 13 1⁄4 88 83

10 4,300 11 1⁄4 19 3⁄8 15 1⁄2 5 12 3 1⁄4 7⁄8 20 14 12 16 1⁄2 14 1⁄2 98 91 12 5,100 12 1⁄4 21 3⁄8 17 1⁄2 5 12 3 1⁄4 7⁄8 20 14 12 16 1⁄2 14 1⁄2 104 97 14 5,600 13 22 3⁄8 18 1⁄2 5 12 3 1⁄4 7⁄8 24 15 13 17 1⁄2 15 1⁄2 107 101 16 6,400 14 1⁄8 24 7⁄8 20 5⁄8 5 12 3 1⁄4 7⁄8 32 17 15 19 1⁄2 17 1⁄2 128 121 18 7,200 15 1⁄8 26 7⁄8 22 5⁄8 5 12 3 1⁄4 7⁄8 32 18 16 20 1⁄2 18 1⁄2 138 130 20 8,000 16 1⁄8 28 7⁄8 24 5⁄8 5 12 3 1⁄4 7⁄8 32 18 16 20 1⁄2 18 1⁄2 149 143 24 11,200 18 1⁄8 32 7⁄8 28 5⁄8 5 14 3 1 40 19 1⁄2 17 1⁄4 22 19 3⁄4 189 185

A

C

B

H

2" NOMINALINSULATION

±1/8

±3/16

UPPER ASSEMBLY

DIA.

(160 PSI CALCIUM SILICATE INSUL.)

LOWER ASSEMBLY

E

1/2" GRAPHITE PLATESEPOXY BONDED TO

INSULATIONSUPPORT SHIELD .016" EMBOSSED

ALUMINUM JACKETWITH MOISTURE BARRIER

D

18"

JF G DIA

4 HOLES1/2"

CL4" 4"

ASTM A307 ZINCPLATED BOLTS.

AXIAL MOVEMENT

THICKNESS

STEEL COMPONENTS

C

C C

116

"

A

C

B

H

2" NOMINALINSULATION

±1/8

±3/16

UPPER ASSEMBLY

DIA.

(160 PSI CALCIUM SILICATE INSUL.)

LOWER ASSEMBLY

E

1/2" GRAPHITE PLATESEPOXY BONDED TO

INSULATIONSUPPORT SHIELD

±3" LATERAL MOVEMENT

.016" EMBOSSED ALUMINUM JACKETWITH MOISTURE BARRIER

D

18"

JF G DIA

4 HOLES1/2"

CL4" 4"

ASTM A307 ZINCPLATED BOLTS.

AXIAL MOVEMENT

STEEL COMPONENTS

THICKNESS

C

C C

Page 10: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

10 12 Proudly Manufactured in the U.S.A.

Table 5: Body Size Selection Chart for GA Guides

BODY SIZE SELECTION

PIPE SIZE

(NPS)

INSULATION THICKNESS

1” 1 1⁄2” 2” 2 1⁄2” 3” 3 1⁄2” 4”

1⁄2 GA04 GA04 GA05 GA06 GA08 GA08 GA103⁄4 GA04 GA05 GA06 GA08 GA08 GA10 GA101 GA04 GA05 GA06 GA08 GA08 GA10 GA10

1 1⁄4 GA04 GA05 GA06 GA08 GA08 GA10 GA101 1⁄2 GA05 GA05 GA06 GA08 GA08 GA10 GA102 GA05 GA06 GA08 GA08 GA10 GA10 GA12

2 1⁄2 GA06 GA06 GA08 GA08 GA10 GA10 GA123 GA06 GA08 GA08 GA10 GA10 GA12 GA124 GA08 GA08 GA10 GA10 GA12 GA12 GA145 GA10 GA10 GA10 GA12 GA12 GA14 GA166 GA10 GA10 GA12 GA12 GA14 GA16 GA168 GA12 GA12 GA14 GA16 GA16 GA18 GA18

10 GA16 GA16 GA16 GA18 GA18 GA20 GA2012 GA18 GA18 GA18 GA20 GA20 GA22 GA2214 GA20 GA20 GA20 GA20 GA22 GA22 GA2416 GA22 GA22 GA22 GA22 GA24 GA24 GA2618 GA24 GA24 GA24 GA24 GA26 GA26 GA3020 GA26 GA26 GA26 GA26 GA30 GA30 GA3024 GA30 GA30 GA30 GA30 O/A O/A O/A

ATS Model “GA” Radial PipeAlignment Guides

NOTES:1. Material Carbon Steel ASTM A36.2. Guide body can be split at 45° to permit pipe nesting.3. Special guides available upon request.4. Body Size 14 and larger are supplied with four (4) bolts on the body.5. Position the guide spider at housing centerline at ambient temperatures.6. Pre-insulated models available for chilled/cold water applications.7. Weights are based on minimum traverse.8. Dielectric inserts are available.

• ATS Model “GA” Radial Pipe Alignment Guides ensure positive pipe alignment by restricting pipe movement in all directions except along the axis of the pipe.

• Recommended choice as the “Primary” guide in piping systems which utilize the ATS Thermal Pak “TP2” Expansion Joint. See Page 2 “General Guidelines for Guiding and Supporting Pipe” for recommended spacing and locations of pipe guides and supports.

• The “GA” Guide Assembly consists of a body cylinder which can be either bolted or welded to the support structure and a sliding spider that is attached to the pipe. The spider moves through the housing as the pipe expands and contracts.

Finish (Table 4, Page 3)Traverse (Table 6, Page 11)

Insulation Thickness, in.Body Size (Table 5)

Pipe Size, NPS

ORDER BY CATALOG NUMBER

6” GA12 2 4 P

ORDER BY CATALOG NUMBER

Page 11: Pre-Engineered Pipe Supports, Guides & Anchors

1-800-443-9194 Advanced Thermal Systems, Inc.

11Pre-Engineered Pipe Supports, Guides & Anchors 12

GA GUIDE

BODY SIZE

STANDARD TRAVERSE

4” 6” 8” 12”

04 X X X05 X X X06 X X X08 X X X10 X X X12 X X X14 X X X16 X X X18 X X X20 X X X22 X X24 X X26 X X28 X X30 X X

Table 6: Standard Traverse Table 7: Dimensions for Standard GA Guides

GUIDE SCHEDULE

BODY SIZEDIMENSION (inches)

WT (lbs.)H R W Y B C L S

04 5 7⁄8 3 1⁄2 6 4 3⁄8 5⁄8 1 3⁄4 3 6 1⁄8 605 6 3⁄4 4 7 4 3⁄4 5⁄8 1 3⁄4 3 6 3⁄8 7

06 7 5⁄8 4 3⁄8 8 5 3⁄8 5⁄8 1 3⁄4 3 7 8

08 9 1⁄4 5 1⁄4 10 6 3⁄8 5⁄8 1 3⁄4 3 8 1010 11 5⁄8 6 1⁄4 12 1⁄8 7 1⁄8 5⁄8 2 3⁄4 4 8 3⁄4 1512 13 3⁄8 7 14 1⁄8 8 3⁄8 5⁄8 2 3⁄4 4 9 7⁄8 2014 14 7⁄8 7 7⁄8 16 1⁄8 9 7⁄8 5⁄8 4 6 12 1⁄8 2516 16 7⁄8 8 7⁄8 18 1⁄8 10 7⁄8 3⁄4 4 6 13 3⁄16 4818 18 5⁄8 9 5⁄8 20 1⁄8 11 7⁄8 3⁄4 4 6 14 1⁄4 5420 20 7⁄8 10 7⁄8 22 1⁄8 11 3⁄4 3⁄4 4 6 14 1⁄8 6122 23 1⁄8 12 1⁄8 24 1⁄8 14 1⁄2 7⁄8 6 8 17 8924 24 7⁄8 13 26 1⁄8 15 1⁄2 7⁄8 6 8 18 10226 27 5⁄8 14 5⁄8 28 1⁄8 17 1⁄8 1 1⁄8 6 8 19 1⁄4 11028 29 1⁄2 15 1⁄2 30 1⁄8 18 1⁄2 1 1⁄8 6 8 20 3⁄8 13530 31 3⁄16 16 13⁄16 32 1⁄8 19 1⁄4 1 1⁄8 6 8 21 5⁄8 150

GA GUIDES ARE AVAILABLE WITH THICKER INSULATION AND LONGER TRAVERSE ON REQUEST.

ATS Model “GA” Radial PipeAlignment Guides

GA Guide Family

SEE INSTALLATION NOTE 5

Y

4 HOLESB DIA

T INSULATION

PIPE SIZE

NOM.

C

THICKNESS

W

R

C

PIPE MOVEMENTDIRECTION OF

SPIDER

GUIDE BODY(HOUSING) TRAVERSE

C

L

C

C

S±1/8

H

Page 12: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

12 12 Proudly Manufactured in the U.S.A.

All piping systems must be divided into individual expanding segments by means of anchors which are attached to the piping and in turn to a support structure. Machinery and equipment, such as turbines and pumps are also considered anchors, since their bases are fixed and resist all forces and moments imposed upon them.

The installation of a slip type expansion joint, like any other axial motion type expansion joint, introduces forces which must be resisted by the anchors. Anchors can be categorized as either main or intermediate type, depending upon the forces they must withstand.

The main anchors must resist forces which involve the internal pressure of the system as well as frictional resistance of pipe supports and expansion joint packing. Intermediate anchors usually involve only the frictional forces of the system.

In the below table the various forces acting on a Main Anchor have been summarized and totaled. The anchor force at two system pressures are shown. The support friction, (Fs) is based on a mean coefficient of friction of 0.35. The use of Low Friction Graphite Guides

Anchor Forces - Slip Joint Installations

PIPE SIZE (NPS)

THRUST AREA (in2)

FORCE TO COMPRESS

Fc, (lbs.)

PRESSURE THRUST Fp, (lbs.)

SUPPORT FRICTION Fs, (lbs. / 100 ft.)

MAIN ANCHOR LOAD Fma, (lbs.)

150 psi 300 psi STD XS 150 psi 300 psi1 1⁄2 2.8 1,500 420 840 126 154 2,455 2,9382 4.4 2,000 660 1,320 179 221 3,370 4,129

2 1⁄2 6.5 2,500 975 1,950 276 333 4,444 5,5663 9.6 3,000 1,440 2,880 458 554 5,664 7,3194 15.9 4,000 2,385 4,770 572 700 8,188 10,9315 24.3 5,000 3,645 7,290 816 1,005 11,098 15,2896 34.5 6,000 5,175 10,350 1,104 1,398 14,365 20,3158 58.4 8,000 8,760 17,520 1,761 2,215 21,609 31,683

10 90.8 10,000 13,620 27,240 2,617 3,053 30,613 46,27612 127.7 12,000 19,155 38,310 3,455 3,941 40,313 62,34114 153.9 14,000 23,085 46,170 4,007 4,543 47,823 74,37116 201.0 16,000 30,150 60,300 4,967 5,586 59,398 94,07018 245.5 18,000 38,175 76,350 6,023 6,723 72,318 116,21920 314.0 20,000 47,100 94,200 7,174 7,956 86,273 140,43824 452.0 24,000 67,000 135,600 9,762 10,707 117,036 195,926

Table 8: Dimensions for Standard GA Guides

ABOVE TABLE SHOWS FMA AT TWO SEPARATE PRESSURES AND INCLUDES 15% SAFETY FACTOR FOR TRANSIENT LOADS.

Fma = 1.15 x (Fc + Fs + Fc)

and Supports, (i.e., ATS Figure 101 and 201) will reduce the value of (Fs) shown by 55%. The expansion joint packing friction, (Fc) is based on the value of 1000 lb./nominal inch of pipe diameter, a value used by ATS. The pressure thrust, (Fp), is the product of the thrust area times the system design. The value of (Fma) shown is the sum of all the forces that can act on a Main Anchor simultaneously.

Intermediate anchors which are located in straight runs of pipe are not subjected to pressure thrust. However, if an isolation valve is located in the run, one or both of the anchors on either side of the valve may become a main anchor depending on the location of expansion joints.

The forces shown are for axial loads only. There are many cases in which forces will impose moments on a main anchor and must be considered in the anchor design. Moments can be due to branch connections, placement of the anchor at some distance from a change in direction, or other external forces. It is essential in anchor design that all forces and moments be considered.

GUIDE

Fs

MAIN ANCHOR

INTERMEDIATEANCHOR

Fp

Fma

100 ft.

Fc

Page 13: Pre-Engineered Pipe Supports, Guides & Anchors

1-800-443-9194 Advanced Thermal Systems, Inc.

Pre-Engineered Pipe Supports, Guides & Anchors 12 13

1 - No Branch Connection2 - Branch Connection (specify size and

location)B - Bolt Down / W - Weld Down

Rating - STD or SPC (see note 4)Figure No. 701 - With Spool (specify mating pipe)Figure No. 702 - Without Spool

Pipe Size, NPS

ORDER BY CATALOG NUMBER

24” Fig. 701 STD W 1 P

Finish (Table 4, Page 3)

ATS Pre-Engineered Main Anchors

ATS pre-engineered factory manufactured anchors offer the assurance of knowing the anchor will be properly designed and fabricated to meet the application requirements. Designs are easily modified to accommodate various centerline heights and load requirements. ATS can supply the anchor either attached to a spool section with ends to match the mating pipe, or as a loose assembly for field attachment to the pipeline. Branch connections up to the size of the pipeline can be incorporated for simplified field installations. All branch connections are forged steel Weld-0-Lets

PIPE SIZE (NPS)

DIMENSION, (inches)F (lbs.) WT. (lbs.)

A B C D E F G H J

1

CONTACT ATS SALES DEPARTMENT1 1⁄41 1⁄22

2 1⁄2 4 4 3⁄8 4 5 1⁄2 4 5 1⁄2 5⁄8 1⁄2 12 4,500 83 4 1⁄2 5 4 1⁄2 6 4 1⁄2 6 5⁄8 1⁄2 12 5,700 94 4 1⁄2 5 3⁄4 4 3⁄4 7 4 3⁄4 7 3⁄4 1⁄2 12 8,500 135 5 1⁄2 6 1⁄2 5 3⁄4 8 5 3⁄4 8 7⁄8 5⁄8 12 11,500 186 5 1⁄2 7 1⁄4 5 3⁄4 8 5 3⁄4 8 7⁄8 5⁄8 12 15,000 218 6 1⁄2 8 3⁄4 7 1⁄2 10 7 1⁄2 10 1 3⁄4 18 22,000 31

10 7 10 1⁄2 8 10 1⁄2 9 1⁄2 12 1 1⁄8 1 18 32,000 5012 8 1⁄2 11 1⁄4 8 1⁄2 12 11 1⁄2 14 1⁄2 1 3⁄8 1 18 40,000 7314 10 12 1⁄4 10 1⁄2 14 12 16 1 3⁄8 1 18 45,000 9016 10 13 1⁄2 10 1⁄2 14 12 1⁄2 16 1 1⁄2 1 1⁄4 18 55,000 10518 11 15 11 15 13 17 1 3⁄4 1 1⁄4 20 79,000 13520 12 16 1⁄4 13 1⁄2 18 13 1⁄2 18 1 7⁄8 1 1⁄4 22 89,000 16824 14 18 3⁄4 14 19 14 19 2 1⁄8 1 1⁄2 24 120,000 230

Table 9: Standard Anchors

to ensure code compliance. In many instances due to high load forces and moments imposed on a main anchor, it is desirable to have the anchor base assembly attached to a spool section that has a heavier wall thickness than that of the main pipe run, a feature that can be easily accommodated in an ATS pre-engineered factory manufactured anchor. In cases when the spool has a heavier wall thickness than the mating pipe, the ends of the spool are machined and beveled for welding to match the mating pipe.

Fig. 702-STD-W-1 Anchor

Fig. 701-STD-W-1 Anchor with Spool

NOTES: 1. Anchor Components are fabricated from ASTM A36 and A 106

material. Pipe spool for Fig. 701 anchors is X-heavy ASTM A 106 Gr. B Seamless Pipe with ends beveled to match the mating pipe.

2. Anchors for higher load requirements or branch connections, located other than as shown, are specially designed to suit the application. ATS must be provided with load requirements and branch locations when required. Drawings for special anchors shall be furnished for approval.

3. Load ratings are based upon the use of heavy hex anchor bolting (furnished by others) equal to ASTM A-325 Tensile Requirements. Bolt diameters are 1/8” less than the drilled hole, Dimension “G” shown in Table 9.

4. Anchors constructed to the load ratings and dimensions shown in Table 9 are designated “STD” rating in the catalog number. Special anchors as described in Note 2 above, are designated “SPC” rating in the catalog number.

C

C

B

C

E

H

G DIA4 HOLES

FCD

ANC HOR BASEFLOAD

J

ZZ F4 MAXXX

PIPE SPOOL(FIG. 701)

ABRANCH

CONNECTION

Page 14: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

14 12 Proudly Manufactured in the U.S.A.

NOTES

Page 15: Pre-Engineered Pipe Supports, Guides & Anchors

1-800-443-9194 Advanced Thermal Systems, Inc.

Pre-Engineered Pipe Supports, Guides & Anchors 12 15

ANSI B36.1 Carbon Steel Pipe Schedule

PIPE SIZE

(NPS)

OUTER DIAMETER

(in.)5 10 20 30 40 STD 60 80 E.H. 100 120 140 160 DBL.

E.H.

1⁄8 0.405 .035.138

.049.1863

.0682.447

.0682.447

.095.3145

.095.3145

1⁄4 0.540 .049.2570

.065.3297

.088.4248

.088.4248

.119.5351

.119.5351

3⁄8 0.675 .049.3276

.065.4235

.091.5676

.091.5676

.126.7388

.126.7388

1⁄2 0.840 .065.5383

.083.6710

.109.8510

.109.8510

.1471.088

.1471.088

.1871.304

.2941.714

3⁄4 1.050 .065.6838

.083.8572

.1131.131

.1131.131

.1541.474

.1541.474

.2181.937

.3082.441

1 1.315 .065.8678

.1901.404

.1331.679

.1331.679

.1792.172

.1792.172

.2502.844

.3583.659

1 1⁄4 1.660 .0651.107

.1091.806

.1402.273

.1402.273

.1912.997

.1912.997

.2503.765

.3825.214

1 1⁄2 1.900 .0651.274

.1092.638

.1452.718

.1452.718

.2003.631

.2003.631

.2814.859

.4006.408

2 2.375 .0651.604

.1092.638

.1543.653

.1543.653

.2185.022

.2185.022

.3437.444

.4369.029

2 1⁄2 2.875 .0832.475

.1203.531

.2035.793

.2035.793

.2767.661

.2767.661

.37510.01

.55213.70

3 3.500 .0833.029

.1204.332

.2167.576

.2167.576

.30010.25

.30010.25

.43714.32

.60018.58

3 1⁄2 4.000 .0833.472

.1204.973

.2269.109

.2269.109

.31812.51

.31812.51

.63622.85

4 4.500 .0833.915

.1205.613

.23710.79

.23710.79

.28112.66

.33714.98

.33714.98

.43719.01

.53122.51

.67427.54

4 1⁄2 5.000 .24712.53

.35517.61

.71032.53

5 5.563 .1096.349

.1347.770

.25814.62

.25814.62

.37520.78

.37520.78

.50027.04

.62532.96

.75038.55

6 6.625 .1097.585

.1349.289

.28018.97

.28018.97

.43228.57

.43228.57

.56236.39

.71845.30

.86453.16

7 7.625 .30123.57

.50038.05

.87563.08

8 8.625 .1099.914

.14813.40

.25022.36

.27724.70

.32228.55

.32228.55

.40635.64

.50043.39

.50043.39

.59350.87

.71860.63

.81267.76

.90674.69

.87572.42

9 9.625 .34233.90

.50048.72

10 10.750 .13415.19

.16518.65

.25028.04

.30734.24

.36540.48

.36540.48

.50054.74

.59364.33

.50054.74

.71876.93

.84389.20

1.000104.1

1.125115.7

11 11.750 .37545.55

.50060.07

12 12.750 .15621.07

.18024.20

.25033.38

.33043.77

.40653.53

.37549.56

.56273.16

.68788.51

.50065.42

.843107.2

1.000125.5

1.125139.7

1.312160.3

14 14.000 .15623.06

.25036.71

.31245.68

.37554.57

.43763.37

.37554.57

.59384.91

.750106.1

.50072.09

.937130.7

10.93150.7

1.250170.2

1.406189.1

16 16.000 .16527.90

.25042.05

.31252.36

.37562.58

.50082.77

.37562.58

.656107.5

.843136.5

.50082.77

1.031164.8

1.218192.3

1.437223.5

1.593245.1

18 18.000 .16531.43

.25047.39

.31259.03

.43782.06

.562104.8

.37570.59

.750138.2

.937170.8

.50093.45

1.156208.0

1.375244.1

1.562274.2

1.781308.5

20 20.000 .18839.78

.25052.73

.37578.60

.500104.1

.593122.9

.37578.60

.812166.4

1.031208.9

.500104.1

1.280256.1

1.500296.4

1.750341.1

1.968379.0

24 24.000 .21855.37

.25063.41

.37594.62

.562140.8

.687171.2

.37594.62

.968238.1

1.218296.4

.500125.5

1.531367.1

1.812429.4

2.062483.1

2.343541.9

Page 16: Pre-Engineered Pipe Supports, Guides & Anchors

www.AdvancedThermal.netAdvanced Thermal Systems, Inc.

16

1 - 8 0 0 - 4 4 3 - 9 1 9 4 I M a d e i n A m e r i c a 12 I w w w . A d v a n c e d T h e r m a l . n e t

Return for Credit

No returns for credit shall be accepted unless sellers permission has been obtained in each case in advance. Only sizes and designs taken from the sellers standard catalog line, which are in active demand, can be accepted for credit. Obsolete or specially manufactured products cannot be accepted for return or credit. For further information pertaining to Advanced Thermal Systems, Inc. Return Policy, please contact Customer Service.

Replacement Guarantee

In addition, ATS guarantees the satisfactory performance of ATS Pre-engineered Pipe Supports, Guides and Anchors for a period of one year from date of shipment. Provided only, that the Pre-engineered Pipe Supports, Guides and Anchors are installed and operated in accordance with ATS prescribed standards. ATS will either replace or repair, without charge, FOB ATS factory any Pre-engineered Pipe Support, Guide or Anchor which fail to give one years’ service under these prescribed conditions.

Warranty Terms

Advanced Thermal Systems, Inc. Pre-Engineered Pipe Supports, Guides and Anchors are sold subject to the mutual agreement that they are warranted by ATS to be free from defects in material and workmanship but ATS’s liability and the buyer’s exclusive remedy shall be limited to replacement without charge, at ATS’s factory, of any material defects which become apparent within one year of the date of shipment, and which shall be determined to be defective by ATS upon their return to the factory, freight prepaid. ATS may opt to provide a refund of the purchase price and that ATS shall have no liability for damages of any kind, direct or indirect, arising from an installation and/or use of any material and by accepting the material the buyer will assume all liability for any damages, direct or consequential, which may result from issue or misuse.

ATS Pre-Engineered Pipe Supports, Guides and Anchors1-Year Warranty and Replacement Guarantee

View Our Other Literature

“ The bitterness of poor quality remains long after the sweetness of a low price is forgotten”— Benjamin Franklin

Thermal Pak Flexible Ball Joints Thermal Pak TP2 Expansion Joints

SGA918