WHY PROVIDE
GUIDELINES?
• Past problems.
• Was tedious to keep track of variables.
• Was easy to make mistakes.
• Wanted a design tool to reduce
problems.
![Page 3: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/3.jpg)
TOPICS
• Minimum Structure Size.
• Maximum Angle into Rectangular
Structures.
• Minimum Angle between Pipes entering
Round Structures.
• Minimum Pipe Depth.
![Page 4: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/4.jpg)
MINIMUM
STRUCTURE SIZE
• The precast opening is typically 6 inches
larger than the pipe’s outside diameter.
Opening
Pipe
![Page 5: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/5.jpg)
Table 4-2
of
Storm Drain Handbook
August 2000
Values based on
Openings for Concrete Pipe
MINIMUM
STRUCTURE SIZE
Minimum Dimensions
For Structures
![Page 6: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/6.jpg)
Maximum Angle (Skew) into a
Rectangular Structure
![Page 7: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/7.jpg)
MAXIMUM ANGLE (SKEW)
INTO A RECTANGULAR STRUCTURE12
”
Pre
cast O
penin
g
6” OD Pipe
60
”
Pre
cast O
penin
g
54” OD Pipe
6”
Structure
Wall
![Page 8: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/8.jpg)
Structure Wall
Good practice to allow 2" ofcontruction tolerance.
Skew
Pip
e
Tolerance
TanxThckWally .=
.ThckWall
yTan = y
R
ODPipeCos =
Cos
ODPipeR = R
Tolerance = Precast Opening – R – y
MAXIMUM ANGLE (SKEW)
INTO A RECTANGULAR STRUCTURE
![Page 9: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/9.jpg)
Example:
Given: 24” Concrete Pipe at 17 degree skew
Structure Wall Thickness = 8”
A 24” concrete pipe has a 30” outside
diameter and a 36” precast opening.
Tolerance = Precast Opening – R – y
= 36” – (30”/Cos 17o) – 8” x Tan 17o
= 2.2”
MAXIMUM ANGLE (SKEW)
INTO A RECTANGULAR STRUCTURE
![Page 10: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/10.jpg)
Table 4-3 of
Storm Drain Handbook – August 2000
Values are based on 2 inches of construction tolerance,
structures with 8-inch walls and concrete pipe dimensions.
Use Round Structure or Rearrange Pipes
if these Angles are Exceeded.
MAXIMUM ANGLE (SKEW)
INTO A RECTANGULAR STRUCTURE
![Page 11: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/11.jpg)
Minimum Angle Between Pipes
Entering Round Structures
![Page 12: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/12.jpg)
Plan View
Structure
Pipe #1
Pip
e #
2
MINIMUM ANGLE BETWEEN PIPES
ENTERING ROUND STRUCTURE
![Page 13: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/13.jpg)
MINIMUM ANGLE BETWEEN PIPES
ENTERING ROUND STRUCTURE
![Page 14: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/14.jpg)
Pipe #1 Precast Opening
Pipe #2 Precast Opening
Plan ViewPipe #1 Half angle
Pipe #1 Half angle
..
/)(
RadStruct
Opening21AngleHalfSin =
Separation Angle
Yields 2” Inside
HALF ANGLE DIAGRAM
![Page 15: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/15.jpg)
Table 4-6
of
Storm Drain
Handbook
Partial View
Read Notes!
MINIMUM ANGLE BETWEEN PIPES
ENTERING ROUND STRUCTURE
![Page 16: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/16.jpg)
• Minimum Cover Requirements of Index
205.
• Strive to maintain a 6-inch precast
section above the pipe opening while
avoiding Grates, Inlet Tops and Top
Slabs.
MINIMUM DEPTH
![Page 17: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/17.jpg)
MINIMUM DEPTH
![Page 18: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/18.jpg)
MINIMUM DEPTH
![Page 19: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/19.jpg)
MINIMUM DEPTH
![Page 20: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/20.jpg)
MINIMUM DEPTH
![Page 21: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/21.jpg)
MINIMUM DEPTH
![Page 22: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/22.jpg)
MINIMUM DEPTH
![Page 23: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/23.jpg)
MINIMUM DEPTH
![Page 24: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/24.jpg)
Inlet Types B & G were not included due to
planned design changes.
Table 4-4 of Storm Drain Handbook (partial view)
*** Read Notes ***
MINIMUM DEPTH
![Page 25: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/25.jpg)
• Index 220: Inlet Type S; Recommended Max pipe
in long wall should be 30”, not 36”
• Index 221: Inlet Type V; Recommended Max pipe
in long wall should be 30”, not 36”
• Index 230: Inlet Type A; Recommended Max pipe
in long wall should be 18”, not 24”
FUTURE CHANGES TO THE ROADWAY
& TRAFFIC DESIGN STANDARDS
![Page 26: PRECAST CONCRETE PIPE](https://reader030.vdocument.in/reader030/viewer/2022020705/61fb892b2e268c58cd5f5457/html5/thumbnails/26.jpg)
• Index 232: Inlet Type C; Recommended Max pipe
in long wall should be 18”, not 24”
• Index 232: Inlet Type E; Recommended Max pipe
in long wall should be 36”, not 42”
• Index 234: Inlet Type J; Recommended Max pipe
in long wall should be 30”, not 36”
FUTURE CHANGES TO THE ROADWAY