premises cabling structures & telecommunication spaces.pdf
TRANSCRIPT
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
1/33
PREMISES CABLING STRUCTURESAND TELECOMMUNICATION SPACES
AMP NETCONNECT System Training
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
2/33
26 May 2011page 2 /Information is Tyco Electronics Confidential & Proprietary
Premises Cabling Structures
Cabling Subsystems Campus Backbone Cabling Subsystem
Building Backbone Cabling Subsystems Horizontal Cabling Subsystems
The subsystems provide the means to configure different topologieslike bus star or ring.
TerminalEquipment
Campus
BackboneCabling
Subsystem
Building
BackboneCabling
Subsystem
HorizontalCablingSubsystem
WorkAreaCabling
Generic Cabling Subsystem
CD/MC BD/IC FD/HC CP TO
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
3/33
26 May 2011page 3 /Information is Tyco Electronics Confidential & Proprietary
Campus Backbone Subsystem
The campus backbone cabling subsystem extends from the campusdistributor to the building distributor(s), usually located in separate
buildings.
FD/HC
BD/IC
FD/HC
CD/MC
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
4/33
26 May 2011page 4 /Information is Tyco Electronics Confidential & Proprietary
Building Backbone Subsystem
A building backbone cabling subsystem extends from buildingdistributor(s) to the floor distributor(s).
FD/HC
FD/HC
BD/IC
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
5/33
26 May 2011page 5 /Information is Tyco Electronics Confidential & Proprietary
Campus & Building Backbone Cabling
The backbone cabling provides interconnection betweentelecommunication rooms, equipment rooms and entrance facilities. It
consists of: the backbone cables, building cross-connects campus cross-connects mechanical terminations and patch cords or jumpers used for backbone-to-
backbone cross-connection. This includes: Vertical connection between floors (risers)
Horizontal connection within the same floor Cables between an equipment room and building cable entrance facilities
Cables between buildings (campus backbone) Shall not contain consolidation points
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
6/33
26 May 2011page 6 /Information is Tyco Electronics Confidential & Proprietary
Horizontal Cabling Subsystem
The horizontal cabling is the cabling that connects the FD to the TO.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
7/33
26 May 2011page 7 /Information is Tyco Electronics Confidential & Proprietary
Horizontal Cabling Subsystem
The horizontal cabling is the cabling that connects the FD to the TO.
T.O.Telecommunication Outlet
H.C.Horizontal Cabling
C.P.
Consolidation Point
Work Area Telecommunication Room
Floor Distributor
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
8/33
26 May 2011page 8 /Information is Tyco Electronics Confidential & Proprietary
Work Area (WA)
The WA is the space in a building where the occupants interact withtheir telecommunications devices. The WA cabling extends from the TO connector end of the horizontal
cabling system, to the terminal equipment.
CP MUTOA
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
9/33
26 May 2011page 9 /Information is Tyco Electronics Confidential & Proprietary
Work Area (WA) Cabling
A WA is usually approximately 10
square meters.
When planning a WA cabling :- 90m maximum horizontal cable length
is the assumption of 5m (maximum) of
WA cord.
When possible locate the TO no morethan 3m from equipments.
Patch cords should be factory
manufactured & commonly withidentical connectors on both ends.
Patch cords are constructed withstranded cable to provide flexibility.
Application-specific adapters (i.e.,baluns, modular adapters, etc.) shallbe install externally to the WA outlet.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
10/33
26 May 2011page 10 /Information is Tyco Electronics Confidential & Proprietary
Telecommunication Outlets (TO) Placement
Requirements 2 TO ports per WA Marked with visible permanent label Should be located within 1m from a power outlet and installed at the
same height. For areas where it is difficult to add more TO at a later date, a
minimum of 2 separate outlets should be provided in the initial design.
WA
FD
1metre
Max.
Work Area 10m
Voice : Cat 3
Data : Cat 5e62.5/125 MM (Optional)
50/125 MM (Optional)
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
11/33
26 May 2011page 11 /Information is Tyco Electronics Confidential & Proprietary
Routing To Work Area
The TO serves as the cabling system WA interface Aesthetic considerations
Understand the structural composition of the WAs
Vertically drop down from ceiling Vertically up from an under floor system Path needs to route to TO
Provides storage for cable slack
Dressed the cable to the connection point without exceeding minimum bend
radius.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
12/33
26 May 2011page 12 /Information is Tyco Electronics Confidential & Proprietary
Surface Mount Outlet Box
Raised/Access Floor Outlet Box MUTOA
Telecommunication Outlets (TO) Boxes
Wall Mount Outlet Box
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
13/33
26 May 2011page 13 /Information is Tyco Electronics Confidential & Proprietary
Multi-User Telecommunication Outlet
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
14/33
26 May 2011page 14 /Information is Tyco Electronics Confidential & Proprietary
Telecommunications Outlets (TO)
The drawing is one of the key
drawings in a design plan andshould include all of the components
(the respective manufacturer andpart number) required for the
installation and mounting of the TO.
TO shall not be more than 3 meterslong from the user equipment
Jacks installed shall match that ofthe installed horizontal cable.
Patch cords should be the same
category as the fixed cabling.
Optical fiber outlets shall be duplex
SC or SFF connectors such as MT-RJ or LC.
TO Elevation Drawing
Voice
Data AMP Cat 5e,P/N 406372-6Blue Color
AMP Cat 5e,P/N 406372-6Blue Color
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
15/33
26 May 2011page 15 /Information is Tyco Electronics Confidential & Proprietary
Telecommunications Outlet (TO)
Connectivity The installation and mounting of the outlet should include all the components (brand,
model and part number) required in the drawing. Designer should determine how the horizontal cables aesthetically pathway, i.e. directly
to the outlet box, through conduit (pipe), trunking, raceways, PVC casing etc.
SURFACE MOUNT RACEWAY & OUTLET DETAIL TYPICAL MODULAR FURNITURE SURFACE MOUNT DETAIL
Surface Mount Box
SIDE VIEW
Surface Mount Latching Duct
2x4 Hung Ceiling
Solid Wall
Plenum Area
Duck Slab
Stud/Clip TieWrap Assembly
Cat 5 & Cat 3 UTP
FRONT VIEWSurface Mount Outlet
Tie Wrap & AnchorCable Bundle
Hung Ceiling
Plenum AreaCat 5 UTP
Deck Slab
Stub/Clip Tie WrapAssembly
Use Latching Duct &Surface Box with grommeted
Faceplate only on solid wallsprovided Flush Mount Boxwith grommeted Faceplate
where ever possible
Use modular furniture communications
channel if available or drill & grommetaccess holes
Deck Slab
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
16/33
26 May 2011page 16 /Information is Tyco Electronics Confidential & Proprietary
Accommodation of Functional Elements
Accommodation of the functional elements and subsystems of ageneric cabling system is accomplished through pathways andspaces that include : Building Entrance Facilities
Telecommunications Room Equipment Room
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
17/33
26 May 2011page 17 /Information is Tyco Electronics Confidential & Proprietary
Telecommunications Room (TR)
A space that houses the
telecommunications cabling systemequipment. This includes :
Contains the telecommunicationsequipment,
cable terminations, and FD (cross-connect and/or
interconnect) for the horizontal andbackbone cabling system.
Each TR should have direct accessto the backbone cabling subsystemand contain the floor distributor.
If a TR serves more than one BD itshould be considered an ER.
Cable stress from tight bends, cable
ties, staples and tension should beavoided by well-designed cable
management.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
18/33
26 May 2011page 18 /Information is Tyco Electronics Confidential & Proprietary
Telecommunication Room (TR)
A TR is an enclosed space that provide all the facilities (electricalpower, grounding and bonding, environmental control etc.) for passivecomponents, active devices and external network interfaces housedwithin it.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
19/33
26 May 2011page 19 /Information is Tyco Electronics Confidential & Proprietary
TR Placement Consideration
Minimum of 1 FD per floor
The FD shall be located in a TR/TE
A single FD should not service morethan 1000 sq. meters (10,000 sq. ft.)
TR/TE placement depend: on the overall building layout and
construction size of room the customer is willing to
allow locations of the WAs being served.
TR/TE shall be located as close to
the centre of the area being served.
TR/TE shall only dedicated to thetelecommunications function andrelated support facilities.
Telecommunications room
(Floor Distributor)
Placement Requirements
1000 m 2
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
20/33
May 26, 2011page 20 /Information is Tyco Electronics Confidential & Proprietary
TR Design Consideration
Clearance of 1.2m (4 ft) to all faces
where access is required.
Minimum of 0.15m (0.5 ft) awayfrom a wall where access is not
required.
Horizontal cable should typically
enters from one side and thebackbone cable entering from theopposite side.
Minimum of two dedicated electrical
distribution source on a separatecircuit.
10 x 73000 x 22005,000500
10 x 93000 x 28008,000800
10 x 113000 x 340010,0001000
ft2mm2ft2m2
Room sizeServing area
Telecommunications Room size
Front
Rear
Front
Rear
1.2m (4 ft)
1.2m (4 ft)0.15m (0.5 ft)
ElectricalEquipment
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
21/33
26 May 2011page 21 /Information is Tyco Electronics Confidential & Proprietary
Floor Distributor Connectivity Plan
Horizontal cabling termination can be wall, cabinet or rack mounted,or a combination of the two.
Install plenty of cable support and management panels to dress cableto the termination port.
Horizontal cable should enter from one side of the room andbackbone cable from the opposite side.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
22/33
26 May 2011page 22 /Information is Tyco Electronics Confidential & Proprietary
Equipment Room
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
23/33
26 May 2011page 23 /Information is Tyco Electronics Confidential & Proprietary
Equipment Room (ER)
An ER is a large TR.
It is a geographical area that may contain the CDand/or BD and/or FD.
Some of the functions of a TR, BEF andCD may be combined with an ER so as
to share air conditioning, security, firecontrol, lighting and limited access.
The ER shall house only equipmentdirectly related to the telecommunicationssystem and its environmental supportsystems.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
24/33
26 May 2011page 24 /Information is Tyco Electronics Confidential & Proprietary
ER Placement Considerations
Space required for the installation oflarge telecommunication equipment.
Accessibility for the delivery of largeequipment.
Locate within the allowablebackbone distance from the FDs ina multi-storey building.
Close to and with ready access tothe backbone pathway and centralto the area been serve.
Locate away from sources ofelectromagnetic interference (lessthan 3 V/m across the frequencyspectrum).
Floor loading capacity.
Locate in a clean, dry space and
provide floor drains.
Equipment RoomPlacement Requirements
HALLWAY(BD/CD)
ER
TR
(FD)
TR (FD)
TR
(FD)
EF
LIFT
SP
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
25/33
26 May 2011page 25 /Information is Tyco Electronics Confidential & Proprietary
ER Design Considerations
Design considerations are similar to
requirements for TR
In addition ER shall be sized to meet the known
and possible future requirements ofspecific equipment.
HVAC should maintain the sametemperature as the adjacent officearea 24x7.
Considerations should also coversacoustics and vibration of the roomenvironment.
Static electricity also needs to be
carefully considered. Site security is very sensitivity and
intrusion detection/access control mayhave to be provided.
Voltage supply tolerances, neutral-to-earth voltages and phase balancinginstallations are critical in the properoperation of sensitive electronic
equipment. Provide 0.07 sq. meters (0.75 sq. ft.)
of ER space for every 10 sq. meters(100 sq. ft.) of work area space. With aminimum design of 14 sq. meters (150sq. ft.).
1200111801 to 1,200
80074401 to 800
40047101 to 400
15014Up to 100
(ft2)(m2)
AREASWORK AREAS
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
26/33
26 May 2011page 26 /Information is Tyco Electronics Confidential & Proprietary
Rack Elevation Drawing
The designer should be aware of how many rack units (RU) will be taken up by thepatch panels and cable management to leave the appropriate space for the networkelectronics, and that the appropriate number of racks may be specified.
1 rack unit (RU) is equal to 1.73 inches (44.25 mm) or 3 cavity-mounting slots. There is no requirements on how rack is specified/arranged.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
27/33
26 May 2011page 27 /Information is Tyco Electronics Confidential & Proprietary
Telecommunication Rack Planning
In a single rack implementation, specify the electronics down low andthe patch panels on top.
When more than one rack is needed, put the electronicson one rack and the patch panels on the other.
Keep the copper and fiber separated,
either different racks or put fiberpanels and devices on the top (easierto work with) and copper on thebottom.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
28/33
26 May 2011page 28 /Information is Tyco Electronics Confidential & Proprietary
Building Entrance Facility (BEF)
The BEF consists of the telecommunications service entrance to the building, includingthe entrance through the building wall and continuing to the entrance room or space.
Required whenever campus backbone, public and private network cables (includingfrom antenna) enter buildings and a transition is made to internal cables.
BEF include the pathways for outside carrier services, campus backbone and antennaeentrance pathways.
BEF consist of a termination field interfacing any outside cabling to the buildingbackbone cabling.
Service Entrance Pathway Methods:
Tunnel Underground Direct Buried Aerial
Service Entrance Facility Service Entrance
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
29/33
26 May 2011page 29 /Information is Tyco Electronics Confidential & Proprietary
Entrance facilities inside buildings
EF shall be located in dry area not subject to flooding.
Entrance space shall be sized to meet known requirements of specific
protectors.
Cables which do not comply with IEC 60332-1, eg. jelly filled cables,can be brought into facility to 50 ft; over this length they shall be
completely enclosed in suitable non-combustible building materials.
Lightning, over-voltage protection, if fitted, shall be sited withinentrance facility.
EF should be located close to building entrance point, next toelectrical service room to reduce length of equi-potential bondingconductors to electrical earthing system.
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
30/33
26 May 2011page 30 /Information is Tyco Electronics Confidential & Proprietary
Distributed Network Architecture
Telecommunications rooms are
distributed through the building.
Advantages of DNA includes: Low backbone cable count Efficient use of cable routing space
Lower cabling investment Allow for fault tolerant design
Disadvantages of DNA includes: Moves, Adds and Changes (MAC) are
more complicated
Patching and un-patching Inefficient equipment ports utilization
Complexities in equipmentmaintenance, servicing and inventorytracking
Additional cost involved in providingcomplementing equipments (HVAC,fire-protection and UPS etc)
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
31/33
26 May 2011page 31 /Information is Tyco Electronics Confidential & Proprietary
Centralized Network Architecture
Provide direct connections form the workareas to the centrally located equipmentroom.
Is most suitable for users in a single-tenant building
Advantages of CNA includes: Moves, adds, and changes (MACs) are
typically easier Patching and un-patching Increase equipment ports utilisation
efficiency Ease of equipment maintenance and
manageability Lower administration time and costs are
lower, Floor space saving in Telecommunication
Rooms Quick upgrade path for network migration
Disadvantages of CNA includes: Higher initial installation cost (especially
fibre solution) Maximum twisted pair link distance of 90
metre Network Equipments centralisation
perceived as a single point of failure
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
32/33
26 May 2011page 32 /Information is Tyco Electronics Confidential & Proprietary
Floor Distributor
Telecommunication
sRoom
Single-User
Cable & Outlets
Splice or PullThru for CNA
Distributor/Cross connect and
Electronics forDNA
Horizontal Distribution Systems
Single-User Distribution Systems or Home Run Cabling
-
7/27/2019 Premises Cabling Structures & Telecommunication Spaces.pdf
33/33
26 May 2011page 33 /Information is Tyco Electronics Confidential & Proprietary
Zone Distribution
Advantages of Zone cabling
includes: Reduced costs over life of cabling due
to less re-cabling (cabling from TC todistribution point stays permanent) Faster Moves, adds, and changes
(MACs) Less office disruption Less down-time and productivity loss
during MACs
Disadvantages of Zone cabling
includes: Initial installation costs
Perceived lower performance due toadditional connection point