PRESENTATION ON

RESTRICTED NEUTRAL SYSTEM OF POWER

SUPPLY FOR HV/EHV INSTALLATIONS.

BY

AJAY SINGHAJAY SINGH

DY. DIRECTOR OF MINES SAFETY(ELECTRICAL),

DIRECTORATE GENERAL OF MINES SAFETY, MINISTRY

OF LABOUR AND EMPLOYMENT, GOVT OF INDIA.

Page 2: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

REG 100: PROTECTIVE EQUIPMENT.-

(1) appropriate equipment shall be suitably placed in

the mines for automatically disconnecting supply to

any part of the system, where a fault, including an

earth fault, occurs and fault current shall not be more

than 750 milliampere in installations of voltage

exceeding 250 V and up to 1100 V for below groundexceeding 250 V and up to 1100 V for below ground

mines and oil fields and 50 ampere in installations of

voltage exceeding 1100 V and up to 11 kV in open cast

mines and the magnitude of the earth fault current

shall be limited to these specified values by

employing suitably designed, restricted neutral

system of power supply.

Page 3: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

WHAT IS RESTRICTED NEUTRAL SYSTEM

IEEE Standard 142-1991, Recommended Practice for

Grounding of Industrial and Commercial Power

Systems (Green Book), defines a high resistance

grounded system as follows:

A grounded system with a purposely inserted

resistance that limits ground-fault current which can

flow for an extended period without exacerbating

damage. This level of current is commonly thought to

be 10A or less.

Page 4: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

ADVANTAGES OF RESTRICTED NEUTRAL SYSTEM

• Reduced magnitude of transient over-voltages

• Improved functioning of protective

relays,

• Greater safety for personnel

• The limited fault current and fast response time • The limited fault current and fast response time

prevents overheating and mechanical stress on

conductors.

• Reducing equipment damage.

Page 5: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

The reason for limiting the current by resistance

grounding may be one or more of the following, as

indicated in IEEE Std. 142-1991, IEEE Recommended

Practice for Grounding of Industrial and Commercial

Power Systems.

(1) To reduce burning and melting effects in faulted

electric equipment, such as switchgear, transformers, electric equipment, such as switchgear, transformers,

cables, and rotating machines.

(2) To reduce mechanical stresses in circuits and

apparatus carrying fault currents.

(3) To reduce electric-shock hazards to personnel

caused by stray ground-fault currents in the ground

return path.

Page 6: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

(4) To reduce arc blast or flash hazard to personnel

who may have accidentally caused (or who happen

to be in close proximity) to the ground fault.

(5) To reduce the momentary line-voltage dip

occasioned by the occurrence and clearing of a

ground fault.

(6) To secure control of transient over voltages(6) To secure control of transient over voltages

while at the same time avoiding the shutdown of a

faulty circuit on the occurrence of the first ground

fault.

Page 7: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Body resistance= 1 ohm

SHOCK VOLTAGE = 317V

Flow of current through body=317ADeath almost certain.

Body resistance= 1 ohmBody resistance= 1 ohm

Extra resistance introduced in the path

of current = 423Ω

SHOCK VOLTAGE = 0.75V

Flow of current through body=0.750ASURE SHOT CHANCES OF SURVIVAL.

Page 8: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Electrocution

Page 9: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

UNGROUNDED POWER SYSTEM

the “ungrounded system” is, in reality, a “capacitively

grounded system” by virtue of the distributed

capacitance

Page 10: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Ungrounded power system

MAIN DISADVANTAGE OF

UNGROUNDED SYSTEM

Page 11: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Ungrounded System

A voltage 1.73 times the normal voltage is present on all

insulation on the ungrounded Phase, causes failures in older

motors and transformers, due to insulation breakdown

Page 12: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

As per IEEE 242-1986 7.2.5 the main

disadvantages of Ungrounded systems are

transient over-voltages, locating the first fault and

burn downs from a second ground fault.

Over-voltages caused by intermittent faults, can Over-voltages caused by intermittent faults, can

be eliminated by grounding the system neutral

through an impedance, which is generally a

resistance, which limits the ground current to a

value equal to or greater than the capacitive

charging current of the system.

Page 13: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

If this ground fault is intermittent or allowed to

continue, the system could be subjected to possible

severe over-voltages to ground (transient voltage),

which can be as high as six or eight times phase

voltage. This can puncture insulation and result in

additional ground faults.

A second ground fault occurring before the firstA second ground fault occurring before the first

fault is cleared will result in a phase to- ground-to-

phase fault, usually arcing, with a current

magnitude large enough to do damage, but

sometimes too small to activate over-current

devices in time to prevent or minimize damage.

Page 14: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

The voltage across a typical capacitor can’t change

instantaneously, hence while energisation of

capacitor, the voltage across capacitor will be zero

which is followed by a voltage recovery(overshoot)

in the form of oscillating transient voltage

superimposed on Fundamental waveform.

Page 15: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Grounded power system

Page 16: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Restricted neutral power system

Page 17: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 18: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Resistance-Grounded System

Page 19: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 20: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 21: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

PREACAUTIONS TO BE FOLLOWED WHILE ADOPTING

RESTRICTED NEUTRAL SYSTEM

The resistor must be sized in a manner as to

ensure that the ground fault current limit is greater

than the system's total capacitance-to-ground

charging current. If not, then transient over-charging current. If not, then transient over-

voltages can occur.

Sympathetic tripping can occur on an unfaulted

feeder if the operating value of the feeder’s

ground-fault relay is less than the feeder’s charging

current.

Page 22: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

TRIPPING RATIO AND NGR SELECTION

Tripping ratio is the ratio of prospective ground-

fault current to the operating value of the ground

fault protection.

An adequate tripping ratio ensures that

sufficient ground-fault current is available forsufficient ground-fault current is available for

detection when a ground fault occurs.

Tripping ratio of at least 7 is necessary to detect

a two phase- to-ground fault.

Page 23: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

METHOD TO MEASURE THE CHARGING CURRENT OF

A SYSTEM

Page 24: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

SYSTEM

VOLTAGE

(V)

CHARGING

CURRENT

(3IC0)

AMPS/1000

KVA OF

REMARKS

TYPICAL CHARGING CURRENTS

KVA OF

SYSTEM

CAPACITY

480 0.1- 2

600 0.1- 2

2400 2- 5

4160 2- 5

Page 25: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

SYSTEM

VOLTAGE

(V)

PHASE TO

PHASE

ESTIMATED LET

THROUGH

CURRENT

REMARKS

APPROXIMATE VALUES OF CHARGING CURRENT

PHASE

600 1A/2 MVA

2400 1A/1.5 MVA

4160 1A/1 MVA

Page 26: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

NUISANCE/SYMPATHETIC TRIPPING

• FOR EARTH FAULT IN THE OUTGOING SIDE OF 1,

THE BREAKERS BELONGING TO FEEDERS 2, 3, AND 5

ALSO TRIPS. SYMPATHETIC TRIPPING.

• THE SETTING OF EARTH FAULT RELAYS SHALL BE SET

AOVE THE CHARGING CURRENT SO AS TO PREVENT

NUISANCE TRIPPING.

Page 27: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

METHODS OF NGR MONITORING

Page 28: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 29: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 30: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 31: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 32: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

harmonic voltages: proper filtering circuits.

Charged clouds.

Inrush currents.

Presence of high resistance earth fault, making

FACTORS WHICH MAY CAUSE MAL-FUNCTIONING

OF MONITORS

Presence of high resistance earth fault, making

the circuit complete, fooling monitor to feel that

NGR is in order.

Presence of artificial neutral points: primary of

P.T. etc.

Page 33: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 34: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

COMMON MISTAKES WHILE ADOPTING

RESTRICTED NEUTRAL SYSTEM OF POWER SUPPLY

Page 35: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

BYPASSING OF NGR DUE TO POOR WORKMANSHIP

Page 36: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

PARTIAL BYPASSING OF NGR DUE TO PRESENCE OF ARTIFICIAL

NEUTRAL POINT

Page 37: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

POOR INSULATION RESISTANCE.

SETTING OF EARTH FAULT RELAY IN EXCESS OF

RESTRICTED EARTH FAULT CURRENT.

PRESENCE OF PERMANENT EARTH FAULT OF

HIGH IMPEDANCE. HIGH IMPEDANCE.

Page 38: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

REG44: USE OF ELECTRICITY AT VOLTAGE EXCEEDING

650 VOLTS: -

(vii) (b) provisions shall be made for suitable oil soak

pit and where use of more than 9000 litres of oil in

any one oil tank, receptacle or chamber is involved,

provision shall be made for the draining away or

removal of any oil which may leak or escape from theremoval of any oil which may leak or escape from the

tank, receptacle or chamber containing the same, and

special precautions shall be taken to prevent the

spread of any fire resulting from the ignition of the oil

from any cause and adequate provision shall be made

for extinguishing any fire which may occur;

Page 39: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

(ix) he shall ensure that the transformers of 10 MVA

and above rating or in case of oil filled transformers

with oil-capacity of more than 2000 ltrs are provided

with fire fighting system as per IS - 3034: 1993 or

with Nitrogen Injection Fire Protection system;

Page 40: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

INTRODUCTION: Power transformer may be

considered as a metal tank filled with oil i.e.

flammable liquid.

The inside active part of transformer can be

considered as “insulation materials under high

dielectric stress” & “conducting parts i.e. copper etc.

carrying very high current”.

Owing to this any internal or external fault on aOwing to this any internal or external fault on a

transformer may trigger a fire & the volume of oil in

the transformer is sufficient to cause a major fire

accident/explosion in spite of the safety devices like

pressure relief valve, Buccholz relay etc.

Page 41: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

REASONS OF FIRE:

•Internal arcing fault due to insulation failure.

•Internal Fault generated during external Short circuit

fault.

•Internal Fault generated during lightning/switching

impulse stroke.

•Improper preventive maintenance of transformer for•Improper preventive maintenance of transformer for

e.g. oil quality etc.

•Improper operation of transformer i.e. overloading,

over voltage etc.

•Bypassing the safety & protection devices.

•Inherent design/manufacturing defect.

•Ageing of transformer

Page 42: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 43: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

COMMAND FROM

VARIOUS RELAYS,

LIKE,

DIFFERENTIAL,

RAPID PRESSURE

RISE, BUCHOLZ,

PRESSURE RELIEF

VALVE

COMMAND

FOR DRAINING

OF OIL

INJECTION

OF

NITROGEN

FUNCTIOING OF AUTO FIRE SYSTEM

VALVE

Page 44: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

As soon as the fire is detected, immediately signal is sent to the

quick drain valve & within fractions of a second (0.2secs) drain

valve is opened to release the pressure & partially drain the oil.

The conservator oil is isolated from main transformer by closing

of automatic shutter valve so that the conservator oil does not

replenish the tank. Within 20 seconds the partial oil draining is

complete.

COURTESY: M/S CTR

Page 45: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

The nitrogen injection valve opens thereby injecting dry Nitrogen

into the transformer from bottom. Explosive gases released from

decomposition of oil/insulation are evacuated. Because of thermal

stirring, the surface temperature is dropped below the flash point &

fire is extinguished in approximately 5 minutes. The Nitrogen

injection is continued for approximately 45 minutes to sufficiently

cool the transformer & to prevent any recombustion.

1. BUCCHOLZ RELAY1. BUCCHOLZ RELAY

2. TEMPERATURE DETECTORS

3. SHUTTER VALVE

4. FIRE PROTECTION SYSTEM

5. TRANSFORMER QUICK DRAIN VALVE

6. NITROGEN CYLINDER

7. NITROGEN PYROTECHNIC VALVE

8. PRESSURE REDUCER

Page 46: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

USE OF NON INFLAMMABLE LIQUID IN TRANSFORMER

• LOOKING INTO THE FLAMMABLE NATURE OF

TRANSFORMER OIL, NON-INFLAMMABLE LIQUID I.E.

SILICONE OIL IS ALSO BEING USED FOR TRANSFORMERS.

• SILICONE OIL IS NON-HYDROCARBON, NON FIRE-

PROPAGATING OIL & IS USED IN ELECTROSTATICPROPAGATING OIL & IS USED IN ELECTROSTATIC

PRECIPITATOR TRANSFORMER INSTALLED OVER ROOFTOP

OF THERMAL POWER STATIONS .

• IN EVENT OF FIRE THE INSULATION OF TRANSFORMER

BURNS BUT QUENCHES DUE TO NON-HYDROCARBON

NATURE OF THIS OIL. THE FLASH POINT & FIRE POINT OF

THIS OIL IS VERY HIGH.

Page 47: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

DGA : By Vacuum Gas Extraction Apparatus and Gas

Chronographs first gasses are extracted from oil by stirring it

under vacuum. These extracted gasses are then introduced in

gas Chronographs for measurement of each component.

Generally it is found that hydrogen and methane are

produced in large quantity if internal temperature of power

transformer rises up to 150oC to 300oC due to abnormal

thermal stresses. If temperature goes above 300oC, thermal stresses. If temperature goes above 300 C,

ethylene(C2H4) are produced in large quantity. At the

temperature is higher than 700oC large amount of

hydrogen(H2) and ethylene(C2H4) are produced.

Ethylene(C2H4) is indication of very high temperature hot spot

inside electrical transformer. If during DGA test of

transformer oil, CO and CO2 are found in large quantity it is

predicted that there is decomposition of proper insulation.

Page 48: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

ELECTRICAL ACCIDENTS

Page 49: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

REG 19: HANDLING OF ELECTRIC SUPPLY LINES AND

APPARATUS: -

(1) Before any conductor or apparatus is handled,

adequate precautions shall be taken, by earthing or

other suitable means, to discharge electrically such

conductor or apparatus, and any adjacent conductorconductor or apparatus, and any adjacent conductor

or apparatus if there is danger there from, and to

prevent any conductor or apparatus from being

accidentally or inadvertently electrically charged

when persons are working thereon.

Page 50: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

(2) Every person who is working on an electric supply

line or apparatus or both shall be provided with tools

and devices such as gloves, rubber shoes, safety belts,

ladders, earthing devices, helmets, line testers,

hand lines and the like for protecting him from

mechanical and electrical injury and such tools andmechanical and electrical injury and such tools and

devices shall always be maintained in sound and

efficient working condition.

Page 51: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

NO USE OF SAFETY GADGETS

•LINE TESTER.

•SAFETY ROPE.

•HALMET.

•SAFETY GLOVES.

Page 52: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

NO PROVISION OF INTERLOCKING

• SHUTDOWN OF BREAKER 1 WAS

TAKEN WHEREAS 2 WAS STILL ENERGISED.

• NO PROVISION OF INTERLOCKING

BETWEEN 1 & 2.

•LINE TESTER.

•SAFETY ROPE.•SAFETY ROPE.

•HALMET.

•SAFETY GLOVES.

Page 53: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 54: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 55: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

REG 74: PROTECTION AGAINST LIGHTNING.-

(1) every overhead line, sub-station or generating

station which is exposed to lightning shall be

equipped with efficient means for diverting to

earth any electrical surges due to lightning which

may result into injuries.

(2) The earthing lead for any lightning arrestor shall (2) The earthing lead for any lightning arrestor shall

not pass through any iron or steel pipe, but shall

be taken as directly as possible from the lightning

arrestor "without touching any metal part to a

separate-vertical ground electrode

Page 56: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Remedial Approach

Conventional air terminal (Franklin Rod)

Faraday Cage:

metallic material completely surrounding the protected

structure and resulting in its electrostatic shielding.

conductors are spaced in a criss-crossed fashion across the

roof structure and sides.roof structure and sides.

IONIZING AIR TERMINAL:

streamer emission system employs either a terminal of

specific shape (Sphere as in the case of Dynasphere) or

enhanced ionizing radioactive air terminal for the

generation of ions. Air terminal is connected to a special

down conductor attached to an earthing system.

Page 57: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

G

Page 58: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

LIGHTNING STRIKE TO LAUNCH COMPLEX 39, KENNEDY SPACE CENTER,

FLORIDA. THE AIR TERMINAL PROTECTING THE SHUTTLE ON THE PAD

INTERCEPTED THE STRIKE

Page 59: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

FARADAY CAGE

Page 60: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

LASER BEAM:

The laser beam would produce multi-photon ionization.

The laser beam could thus intercept a leader as it

developed towards the earth, and act as a conductor from

the cloud to the ground and then be terminated to a down

conductor and the earth mass.

Page 61: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Preventive Approach

preventing build-up of charge

in the area to be protected.

The system shall be able to

reduce the potential between

the protected area and the

charged clouds, so that thecharged clouds, so that the

potential difference is not

high enough to enable the

generation of a leader to the

earth within the protected

area.

Page 62: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 63: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 64: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 65: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 66: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

ESTIMATION OF EXPOSURE RISK

Expected number of lightning flashes per square kilometre

per year.

For either polarity, however, the current flow is

unidirectional with a rise time of less than 10 μs for the

negative flash (but considerably longer for positive flash)

and then decays to a low value, for a simple single stroke,

in 100 μs or less.in 100 μs or less.

Page 67: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Assuming the charge in the cell to be 100 C and the radius of an equivalent spherical cell to

be 1 km. The capacitance of the cell is, therefore, about 10-7 F and from Q == CV the

potential is estimated to be 109 V. It is reasonable, therefore, to assume that the cloud

potential is more than 100 MV. This potential is high enough to ensure that the potentials

sustained by whatever is struck will be controlled by the product of current and

impedance, because this product will never be high enough in comparison with the cloud

potential to modify the current magnitude.

The lightning stroke starts by the step by step descent from the cloud of a leader stroke

stepping some tens of metres at a time. When the last step brings the tip of the leader

sufficiently close to earth an upward streamer leaves the earth to join the tip of downward

leader.

The initiation of this upward streamer depends on a critical field being exceeded at the

earth emission point and so is a function of the charge deposited by the down-coming

leader and any enhancement of the field caused by the geometry of the earth. The

length of the upward streamer will be greater for greater charges and hence high

current flashes will start preferentially from high structures for which the field

enhancement is high.

Page 68: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Electrical Effect

As the current is discharged through the resistance of the earth electrode of the lightning

protective system, it produces a resistive voltage drop which may momentarily raise the

potential of the protective system to a high value relative to true earth. It may also produce

around the earth electrodes a high potential gradient dangerous to persons and animals.

Side Flashing,

The point of strike on the protective system may be raised to a high potential with respect to

adjacent metal. There is. therefore, a risk of flash. over from the protective system to any

other metal on or in the structure. If such flashover occurs, part of the lightning current is

discharged through internal installations, such as pipes and wiring, and so this flashover

constitutes a risk to the occupants and fabric of the structure.

ThermalThermal

As far as it affects lightning protection, the effects of a lightning discharge is confined to the

temperature rise of the conductor through which the current passes. Although the current is

high, its duration is short, and the thermal effect on the protective system is usually

negligible. In general, the cross-sectional area of a lightning conductor is chosen primarily to

satisfy the requirements of mechanical strength, which means that it is large enough to keep

the rise in temperature to 1°C . For example, with a copper conductor of 50 mm2 cross section

a severe stroke of 100 kA with a duration of 100 μs dissipates less than 400 J per metre of

conductor resulting in a temperature rise of about 1°C. The substitution of steel for copper

results in a rise of less than 10°C.

Page 69: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Mechanical Effects

Where a high current is discharged along parallel conductors at close proximity, or along a

single conductor with sharp bends, considerable mechanical forces are produced. Secure

mechanical fittings are, therefore, essential.

A different mechanical effect exerted by a lightning flash is due to the sudden rise in air

temperature to 30 000 K and the resulting explosive expansion of the adjacent air in the

channel along which the charge is propagated. This is because, when the conductivity of

the metal is replaced by that of an arc path, the energy increases about one hundredfold. A

peak power of about 100 MW/m can be attained in the return stroke and the shock wave

close to this stroke readily dislodges tiles from a roof .

Page 70: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

BASIC CONSIDERATIONS FOR PROTECTION

• Decide whether or not the structure needs protection

Need for Protection

Structures with inherent explosive risks; for example, explosives factories, stores and

dumps and fuel tanks; usually need the highest possible class of lightning protective

system.

- where large numbers of people congregate;

- where essential public services are concerned;

- where the area is one in which lightning strokes are prevalent- where the area is one in which lightning strokes are prevalent

- where there are very tall or isolated structures;

- where there are structures of historic or cultural importance,

Page 71: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

assessment can be made taking account of the exposure risk ( that is the risk of

the structure being struck) and the following factors:

• Use to which the structure is put,

• Nature of its construction,

• Value of its contents or consequential effects,

• The location of the structure, and

• The height of the structure ( in the case of composite structures the overall height).

Estimation of Exposur Risk

The probability of a. structure or building being struck by lightning in anyone year is the The probability of a. structure or building being struck by lightning in anyone year is the

product of the 'lightning flash density' and the 'effective collection area' of the structure.

The lightning flash density, Ng is the number of ( flashes to ground ) per km2 per year.

Page 72: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 73: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 74: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

The effective collection area of a structure is the area on the plan of the structure extended in

all directions to take account of its height. The edge of the effective collection area is displaced

from the edge of the structure by an amount equal to the height of the structure at that point,

Hence. for a simple rectangular building of length L, width W and height H metres, the collection

area has length (L + 2H) metres and width ( W + 2H) metres with four rounded corners formed

by quarter circles of radius H metres.

This gives a collection area, Ao (in m2) of:

Ao = ( L X W) + 2 ( L X H) + 2 ( W X H) + пH2

The probable number of strikes ( risk) to the structure per year is,

P = Ao X Ng X 10-6P = Ao X Ng X 10-6

Ng: is lightning flash density , the number of ( flashes to ground )

per km2 per year,

Ao (in m2): collection area

Suggested Acceptable Risk

For the purposes of this Code, the acceptable risk figure has been taken as

10-5, that is, 1 in 1,00,000 per year.

Page 75: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 76: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Overall Assessment of Risk

Having established the value of P, the probable number of

strikes to the structure per year the next step is to apply the

'weighting, factors',

This is done by multiplying P by the appropriate factors to

see whether the result, the overall weighting factors,

exceeds the acceptable risk of P = 10-5 per year.

Interpretation of Overall Risk FactorInterpretation of Overall Risk Factor

If the result obtained is considerably less than 10-5 ( 1 in

100,000 ) then, in the absence of other overriding

considerations, protection does not appear necessary; if

the result is greater than 10-5, say for example 10-4( 1 in 10

000 ) then sound reasons would be needed to support a

decision not to give protection.

Page 77: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Zone or Protection

CONE CONCEPT: volume within which a lightning conductor gives protection against a direct

lightning stroke by directing the stroke to itself. For a vertical conductor rising from ground

level, the zone has been defined as a cone with its apex at the tip of the conductor its base

on the ground. For a horizontal conductor the zone has been defined as the volume

generated by a cone with its apex on the horizontal conductor moving from end to end.

Protection angle

Page 78: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 79: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

AIR TERMINATION AND ZONE OF PROTECTION FOR SIMPLE STRUCTURE WITH EXPLOSIVE OR

HIGHLY IMFLAMMABLE CONTENT

Page 80: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Where a structure is simply a continuous metal frame, it requires no air termination or down

conductor. It is sufficient to ensure that the conducting path is electrically and mechanically

continuous and that the requirements of the code in respect of the connection to the general

mass of the earth are met.

Fences Surrounding Structures Containing Flammable Liquids or Gas

Earthing of All Metal Fences

Where fences which surround hazardous locations, are of the all-metal type, no particular

problems arise, and they can be earthed at intervals not exceeding 75 m.

The temperatures of lightning are 15,000-60,000°FThe temperatures of lightning are 15,000-60,000°F

Lightning strokes can heat the air through which they travel to an amazing 30,000 degrees

Celsius (54,000F).

This extreme heating causes the air to explosively expand, creating a shockwave that travels

outwards through the air as the booming sound that we call "thunder."

Lightning forms through the electrification of clouds, and the most popular theory is that this

comes about through graupel and hail falling through the region of the cloud containing

supercooled water droplets and ice crystals.

Page 81: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

As liquid droplets collide with hailstones and freeze on contact, the latent heat

released keeps the surface of the hailstones warmer than the surfaces of the

surrounding ice crystals. When the hailstones collide with the colder ice crystals, there

is a net transfer of positive ions from the warmer hailstones to the colder ice crystals.

The hailstones therefore acquire a negative charge, and the ice crystals become

positively charged. The lighter ice crystals get carried upwards into the cold part of the

thunderstorm by strong updrafts, causing the upper part of the cloud to become

positively charged. The heavier hailstones fall toward the bottom of the cloud, causing

the middle part of the cloud to become negatively charged. The lower part of the cloud

is generally of negative and mixed charge, with some positive charged areas where

precipitation is leaving the cloud.

Page 82: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

C: A second surge of negative

charge descends along the

ionized path of the previous

stroke creating the Dart

Leader.

D: A second return stroke follows

the first.

The whole process repeats until the cloud is discharged.

This all happen in 10 microseconds. Your eyes can’t see

any of this details.

Page 83: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 84: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Other types of cloud-to-ground lightning strokes 1

• Between anvil and ground

• Positive charges travel downward to

the ground

• 8% of all cloud-to-ground lightning

stroke are of this type.

• More dangerous

• Exits from the side of a

thundercloud and comes to the

ground away from the thundercloud

• The ground strike can be over 10 km

from the cloud boundary, arriving at

the ground in an area where the sky

is blue.

Page 85: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 86: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Lightning Safety• Signs of lightning stroke: Sizzling sound or

hair standing up indicates a strong field

• 5 s gap between flash and thunder implies a

1 mi range

• 30-30 rule (conservative)

– 30s lag 6 mi range

– Wait 30 min

• Take refuge in a car or a building with • Take refuge in a car or a building with

plumbing and wiring

• Not under trees

• Assume a low crouch with only feet in

contact with the ground

• Avoid holding elongated metal objects, like

rifles or golf clubs; avoid open water outdoors

Page 87: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

• In june 1998, 13 people were badly injured during a rock

concert in Baltimore.

This stadium was provided with LP.

• In Oct 1998, republic of congo, 11 team members were

killed by lightning.

• Empire building was struck 25 times in one year by

lightning.

• A direct lightning on your car will flow through metal• A direct lightning on your car will flow through metal

frame and usually may flat one or more tires and

concurrently may result in damage to the electrical

system but no injury to the occupant.

But the strike may ignite the fuel hence we should get out

of the car as soon as possible.

Page 88: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

Because opposite charges attract each other, the negatively charged bottom of the cloud

causes positive charges to build in the ground directly beneath it. These positive charges

will follow the cloud wherever it goes. The largest buildup of positive charges will occur in

protruding objects such as houses, trees, and poles, which reach up toward the sky. The

difference in charges causes an electric potential to build between the cloud and the

ground, but in dry air, a flow current does not occur because air is a good electrical

insulator. However, as the electrical potential gradient gradually builds, it will eventually

become large enough (on the order of a million volts per meter) to overcome the

insulating properties of the air, causing a current to flow, and lightning occurs. Cloud-to-

ground lightning begins within a cloud when a sufficiently strong localized electric

potential gradient causes a discharge of electrons to surge towards the cloud base and

then towards the ground. This discharge proceeds in a series of steps, each about 50-then towards the ground. This discharge proceeds in a series of steps, each about 50-

100m long, with pauses of about 50 millionths of a second between each step. This is

called a "stepped leader," and is usually quite faint, sometimes too faint to see with the

naked eye.

As the tip of the stepped leader nears the ground, the electric potential gradient

increases sharply, and a current of positive charge starts upward from the ground to

meet it. Once they meet, a surge of electrons flows to the ground, and then a much more

intense "return stroke" races upward towards the cloud along the same path traced by

the stepped leader. This return stroke is what causes the bright flashes that we see as

lightning, and the transfer from ground to cloud is so fast that it is imperceptible to the

human eye, and thus we see it as just a continuous flash of light.

Page 89: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

The charges on the ground are influenced by the charge build up in the clouds. Normally,

the ground has a slight negative charge however, when a thunderstorm is directly

overhead, the large negative charge in the middle of the storm cloud repels negative

charges on the ground underneath the storm. This causes the ground and any objects (or

people) on the ground directly underneath the storm to become positively charged

Lightning Formation

The sky is filled with electric charge. In a calm sky, the positive (+) and negative (-) charges are

evenly spaced throughout the atmosphere. Therefore, a calm sky has a neutral charge.

Inside a thunderstorm, the electric charge is spread out differently. A thunderstorm is made up of

ice crystals and hailstones. The ice crystals have a positive charge, and the hailstones have a

negative charge. An updraft pushes the ice crystals to the top of the thunderstorm cloud. At the

same time, the hailstones are pushed to the bottom of the thunderstorm by its downdraft. These same time, the hailstones are pushed to the bottom of the thunderstorm by its downdraft. These

processes separate the positive and negative charges of the cloud into two levels: the positive

charge at the top and the negative charge at the bottom.

During a thunderstorm, the Earth's surface has a positive charge. Because opposites attract, the

negative charge at the bottom of the thunder cloud wants to link up with the positive charge of

the Earth's surface.

Once the negative charge at the bottom of the cloud gets large enough, a flow of negative charge

rushes toward the Earth. This is known as a stepped leader. The positive charges of the Earth are

attracted to this stepped leader, so a flow of positive charge moves into the air. When the

stepped leader and the positive charge from the earth meet, a strong electric current carries

positive charge up into the cloud. This electric current is known as the return stroke and humans

can see it as lightning.

Page 90: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault
Page 91: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault

ANY QUESTIONS PLEASE

Page 92: PRESENTATION ON RESTRICTED NEUTRAL SYSTEM … II_Ajay Singh.pdf · presentation on restricted neutral system of power ... 600 1a/2 mva 2400 1a/1.5 mva 4160 ... •for earth fault