Page 1: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Presenter: Frank Kurz

ANUBIS systems technologies

“Security for Life”

Page 2: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

How to Help Your Boss With Hair Loss!

CFAA BC Chapter Technical Seminar April 15, 2015 – Vancouver, B. C.

Page 3: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

THE BUILDING CODE Division B Parts 2 & 3 THE FIRE CODE Division B Part 6 Division C Part 2

GOVERNING DOCUMENTS ULC CSA ONSITE DOCUMENTATION

FIRE ALARM/EVC SYSTEMS TESTING NBC Requirements NFC Requirements High Rise Testing Visual Inspection Supervision - Addressable versus Conventional End-of-Line Resistors Isolator Modules Stand-alone Capability Audibility Zoning & Annunciation CAN/ULC-S536 Appendix “E” Form CAN/ULC-S537 Appendix “C” Form

Page 4: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

COMMUNICATORS Monthly Testing Requirements: CAN/ULC-S536 Periodic Testing Requirements: NFPA 25 Annual Testing Requirements: CAN/ULC-S536 Appendix “E” CAN/ULC-S561 Appendix “C” Acceptable Installations Acceptable Testing Agencies ULC’s Role: Shared Station Certificate Full Service Certificate

ASTTBC

Page 5: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

B Design, Construction & Retrofit of Buildings: N Public Health & Safety N Fire Protection, and N Structural Sufficiency

FIRE PROTECTION IS ACHIEVED THROUGH THE REGULATION OF THREE DISCIPLINES: l Architectural:

N Containment, fire resistance rating of the structure, and means of egress

fMechanical: N Automatic extinguishing systems, standpipe and hose systems, and

smoke control/smoke removal systems dElectrical:

N Fire detection, alarm & suppression systems, exit and emergency lighting units, emergency power, voice communication systems and elevator operation

Page 6: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Z Provides the particular year or edition of the referenced Code or Standard that is to apply.

Z All parts of the system must be installed and must operate as intended by applicable Standards and all devices must be compatible and not restrict the operation of any other device.

Z CAN/ULC-S524 (The Installation Standard) details operational requirements for integrating systems with voice capability, how to operate ancillary devices, and power requirements for proper operation.

Z CAN/ULC-S524 (The Installation Standard) also specifies the need for certification of all devices and equipment and details the installation requirements pertaining to the various system components such as manual stations, detectors and signals.

Z CAN/ULC-S537 (The Verification Standard) ensures all components that make up a fire alarm system comply with CAN/ULC-S524 (The Installation Standard) and the DESIGN.

Z CAN/ULC-S1001 (The Commissioning Standard) ensures that all components that integrate the fire alarm system with the building’s related life safety systems complies with the objectives of the Building Code and the DESIGN.

Division B, Part 2 of the Building Code

Page 7: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Aside from Section 3.2.4 (which deals specifically with Fire Alarm and Detection Systems), there are many requirements in other parts, sections, subsections or articles which have fire detection, alarm & suppression system requirements.

Examples of Building Code Sections which must be referenced include:

N Subsection 3.1.8.12 Hold-Open Devices outlines requirements relating to door hold-

open devices and their relationship with the Fire Detection, Alarm & Suppression system;

N Subsection 3.1.9 Building Services in Fire Separations and Fire Rated Assemblies documents the requirements for maintenance of the integrity of required fire separations when electrical conduits must penetrate those fire separations;

N Subsection 3.2.6 Additional Requirements for High Buildings calls for voice communications systems, central alarm and control facilities, and smoke control measures;

N Article 3.2.7.8 Emergency Power for Fire Alarm Systems; N Article 3.2.7.10 Protection of Electrical Conductors

Division B, Part 3 of the Building Code

Page 8: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Z The Building Code regulates where a fire alarm system is required, and its operation. The Installation Standard details how the devices are installed.

Z The Building Code also details where automatic detection devices are required, the monitoring of sprinkler systems and where fire sprinklers can perform automatic fire detection for the fire alarm system.

Z The Building Code defines the need for signals, signal duration and off-site alarm transmission. The Installation Standard details their installation and interconnection.

Z The zoning of the system is defined in the Building Code as well as annunciation and the requirements for emergency voice communication systems. Installation & operation (including degraded operation of networked systems) is specified in the Installation Standard.

Page 9: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

N The system must use only devices and components that have been inspected, tested and listed by a nationally recognized testing authority. In Canada this is Underwriters Laboratories of Canada (ULC).

N Fire alarm field devices must specifically be designed and manufactured in accordance with one of the several ULC Standards.

N The application and installation of each device must meet the requirements of both the Building Code and the CAN/ULC-S524 Standard for the Installation of Fire Alarm Systems.

N Installation materials and methods must follow applicable rules in the Canadian Electrical Code Part 1 Section 32 and related sections.

Page 10: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

B The installation must be Verified in accordance with CAN/ULC-S537 Standard For The Verification of Fire Alarm Systems, and Commissioned as part of an Integrated System

B All work performed during these various stages, must be performed by qualified personnel.

B No single source shall be involved in the design, installation and Verification of a fire alarm system.

B IT IS VITAL THAT you ensure the Codes and Standards used in the

design and installation of a life safety system are the ones currently referenced.

Page 11: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Referenced Standards: ACSA:

CAN/CSA-C282-05 – Emergency Electrical Power for Buildings Z32-04 – Electrical Safety and Essential Electrical Systems in Health Care Facilities B44-07 – Safety Code for Elevators and Escalators

AULC:

CAN/ULC-S524-06 – Standard for Installation of Fire Alarm Systems CAN/ULC-S536-04 – Standard for Inspection and Testing of Fire Alarm Systems CAN/ULC-S537-04 – Standard for Verification of Fire Alarm Systems CAN/ULC-S1001-11 – Standard for Integrated Systems Testing of Fire Protection and Life Safety Systems CAN/ULC-S552-02 – Standard for Maintenance and Testing of Smoke Alarms CAN/ULC-S553-02 – Standard for Installation of Smoke Alarms CAN/ULC-S561-03 – Standard for Installation and Services for Fire Signal Receiving Centres and Systems

AASTTBC: Practice Guideline Stamp Guideline

Jurisdictional Authority Via Formal Bylaw or Bulletin

ACity of Vancouver: Bulletin 2003-009-EL Bulletin 2000-021-EL

Page 12: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Monthly Test Reports

ONSITE DOCUMENTATION

Plans and Specifications Fire Alarm Riser Drawing Manufacturer’s Installation & Operating Instructions Verification Appendix “C” Report(s)

Annual Appendix “E” Reports Fire Safety Plan Manual

Commissioning Report(s)

Page 13: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Building Code Requirements

Reference Standards: CAN/ULC-S537-04

Standard for Verification of Fire Alarm Systems

Z Verification Appendix “C” Form

Z Commissioning ???

Vancouver Building Bylaw (VBBL)

Page 14: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Fire Code Requirements

Reference Standard: CAN/ULC-S536-04

Standard for Inspection and Testing of Fire Alarm Systems

oPeriodic Testing Daily

Monthly

Visual

Visual & Operational

Monthly Test Report

Z Annual Testing Appendix “E” Form

Page 15: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

6.1.1.1 Application 1) This Part includes requirements for the inspection, testing, maintenance, and operation of portable extinguishers, water-based fire protection systems, special extinguishing systems, fire alarm systems, emergency electrical power supply systems, and emergency lighting. Appendix “A” contains wording that presupposes that the fire protection equipment “whether required by Code or voluntarily installed, will be designed in conformance with good fire protection engineering practice and will meet the appropriate installation requirements in the relevant Standards”.

Fire Code Requirements

Page 16: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Fire Code Requirements

Division “C” Part 2

Administrative Provisions

2.2.1.2 Records

1) Where this Code requires that tests, inspections, maintenance or operational procedures be performed on a fire safety system, records shall be made and the original or a copy shall be retained at the premises for examination by the authority having jurisdiction.

2) The initial verification or test reports for each system shall be retained throughout the life of the systems.

3) Records of tests, inspections, maintenance or operational procedures undertaken after the initial tests referred to in Sentence (2) shall be retained so that at least the current and immediately preceding records are available.

4) Notwithstanding the conditions stated in Sentence (3), no record shall be destroyed within two years of having been prepared.

Page 17: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Z the installation of smoke control measures, Z provision of areas of refuge, Z emergency operation of elevators, Z venting to aid fire fighting, Z additional sprinkler coverage, Z provision of a Central Alarm and Control Facility, Z provision of voice communication systems, and Z protection of electrical conductors.

What does the Testing Standard require you to do? What does ASTTBC’s Practice Guideline require you to do? What would a Life Safety Professional be expected to do?

Page 18: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Smoke & Fume Control

Page 19: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Where are you going to find this information?

B Building Plans and Specifications

B Fire Safety Plan Manual

Page 20: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

VISUAL INSPECTION

Page 21: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

VISUAL INSPECTION

Page 22: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

VISUAL INSPECTION

Page 23: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

VISUAL INSPECTION

Page 24: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION
Page 25: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION
Page 26: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

1800mm?

??

Page 27: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION
Page 28: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Calculating Battery Capacity! Supervisory Capacity:

0.740 Amps x 24

17.16 AH 4 x 6v-12AH

Page 29: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Supervision

Page 30: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Supervision

Page 31: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION
Page 32: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Supervision

5.7.11 Conventional Circuit End-of-Line Device 5.7.11.1 Each input circuit end-of-line device shall be tested for open circuit fault, short circuit fault and ground fault conditions. The results shall be recorded in the Inspection Report. 5.7.11.2 Each output circuit end-of-line device shall be tested for open circuit fault, short circuit fault and ground fault conditions. The results shall be recorded in the Inspection Report. Should you check the voltage while you’ve got the device down?

Page 33: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Addressable Systems

Page 34: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Addressable Devices

Page 35: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Addressable Systems

Isolators!

Z Data Communications Loop DCL (Signal Line Circuit - SLC)

Z Power Buss Z Audio Buss Z Signal Buss

Z Suite Signal Isolators

Page 36: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Addressable Systems Isolators!

Class “A” Circuit Installation

ONLY ONE WIRE UNDER EACH TERMINAL SCREW

+ IN (from FACP or previous isolator) - IN (from FACP or previous isolator) + OUT (to devices in area) - OUT (to devices in area)

IS THIS A “T” – TAP??

Page 37: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Addressable Systems Isolators!

Page 38: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Addressable Systems Isolators!

Page 39: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Addressable Systems Isolators!

Page 40: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

SUITE SIGNAL ISOLATORS

Page 41: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

STAND-ALONE CAPABILITY

Clause 4.3.4.6 (it’s Clause 3.3.4.6 in the “04” version) “Where fault isolation in data communication links is provided between control units or transponders, the field wiring shall be shorted between each pair of control units or transponders, in turn, annunciation of the fault confirmed and operation outside the shorted section confirmed.” Section 5.3 (it’s Section 4.3 in the “04” version) deals with the Verification requirements of Large Area Networks What is a Large Area Network? What’s the “magic number”?

1000 Devices!

CAN/ULC-S537-13

Page 42: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

STAND-ALONE CAPABILITY

Clause 6.6.3 (it’s 5.6.3 in the “04” version) Where fault isolation in data communication links is provided between control units or transponders and between transponders, introduce a short circuit fault and confirm annunciation of the fault and operation outside the shorted section between each pair of: A. Control unit to control unit;

B. Control unit to transponder; and

C. Transponder to transponder

CAN/ULC-S536-13

Page 43: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Individual Device Testing

5.7.1.2 Each enabled function/feature of the field device shall be tested and annunciation confirmed while connected to the control unit or transponder. 5.7.1.3 All field devices shall be tested on a yearly basis, except in the event that a device cannot reasonably be made accessible for safety considerations (for example, continuous process operations, energized electrical equipment, radiation, and height), the device and its location shall be recorded and identified as “inaccessible” in the remarks column of the report similar to that shown in Appendix E3.2, Individual Device Record. The last test date shall also be recorded in the remarks column of E3.2. Those field devices identified as being inaccessible as noted in the remarks column of E3.2, shall be tested at least once every two years.

Page 44: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Elevator Shaft Fire Detectors? Schedule testing on the same day as the Elevator Monthly Inspection! Insuite Signalling Appliances? Owner MUST arrange for access. THIS IS A BILLABLE EXTRA!! High heat detectors – What’s “high” and what’s considered “unsafely high”? What size ladder do you need? Is a man-lift required?

Individual Device Testing (Inaccessible Devices)

Page 45: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

150mm??

Is an audibility meter required? For a Verification? For an Annual Test? Required NBCC Audibility Levels: 65 dBA Minimum 10 dBA Above Ambient 75 dBA at the pillow At what level are VISUAL Devices Required? Ambient greater than 87 dBA (in areas where hearing protection is required, in an audiometric booth, or inside a sound proof room)

Page 46: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

AUDIBILITY

5.7.9.1 Each audible signal device and visible signal device shall be inspected and tested for operability, including the following functions, as applicable: A. Proper installation and tightness of shell or housing and

evidence of tampering, such as physical obstruction of moving mechanical parts.

B. …

C. The audibility of the alert signal and/or alarm signal and of voice messages shall function as intended throughout the area served by the device.

D. …

CAN/ULC-S536-04

Page 47: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

AUDIBILITY

5.7.9.2 Each audible signal device for use in suites of residential occupancy shall be inspected and tested for the following, as applicable: A. Proper installation and tightness of shell or housing and

evidence of tampering or physical obstruction;

B. …

C. The audibility of the alert signal and/or alarm signal and of voice messages throughout the area served by the device.

D. Silencing means provided for in-suite devices is accessible and clearly identified; and

E. Operation of the switch silences in-suite signal(s).

CAN/ULC-S536-04

Page 48: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

INTELLIGIBLITY

NBCC 2010 (BCBC 2012) Clause 3.2.4.22 (2) “The voice communication system described in Clause (1)(b) shall be capable of broadcasting prerecorded, synthesized, or live messages with voice intelligibility meeting or exceeding the equivalent of common intelligibility scale score of 0.70 (See Appendix A)”

CIS – Common Intelligiblity Scale STI – Speech Transmission Index

Clause 1.10.1(C) of CAN/ULC-S537-13 states: “The intelligibility of voice messages shall function as intended throughout the area served by the device as specified in accordance with Section 3.2.4.22.[2] of the National Building Code [CIS 0.70]. (Refer to Appendix C6.4, Signalling Device Intelligibility Measurement; and Appendix H, Intelligibility Measurements);”

Page 49: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

Zoning & Annunciation

Page 50: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

CAN/ULC-S536-04 APPENDIX “E” CAN/ULC-S537-04 APPENDIX “C”

How many pages? What’s wrong with the ASTTBC Forms? - Formatting - Errors - MISSING!

Page 51: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

COMMUNICATORS Verification Testing Requirements: CAN/ULC-S537 Monthly Testing Requirements: CAN/ULC-S536 Annual Testing Requirements: CAN/ULC-S536 Appendix “E” CAN/ULC-S561 Appendix “C” Acceptable Installations Acceptable Testing Agencies ULC’s Role

Page 52: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

COMMUNICATORS

Page 53: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

COMMUNICATORS

Page 54: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

ULC’s ROLE Z Certification of Installed Premises Equipment

Z Certification of Installation Providers

Z Certification of Monitoring Facilities

Z Field Installation Inspection (Randomly Selected)

Z Monitoring Facilities Inspection (Annually)

Shared Station Certificate Issued to an installation where two separate agencies are involved: Installation Provider Monitoring Centre

Full Service Certificate Issued to an installation where the Monitoring Centre employs their own installers

Page 55: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

What kind of certificate to submit? There are two options: 1. A document that is acceptable to the Authority Having Jurisdiction, your local Building

Official for new construction/installation and your Fire Official for existing buildings/installations. (This presupposes that they’re also willing to accept an alternate individual or agency’s judgement!)

2. A ULC Protective Signalling System Certification – provided through ULC Listed Alarm Company. Companies that are certified to CAN/ULC-S561 can be found in our ULC Online Directory at http://database.ul.com/cgi-bin/XYV/template/LISCANADA/FRAME/index.html and using the following ULC Category Codes:

DAYRC – CAN/ULC-S559-04 - Equipment DAYYC – CAN/ULC-S561-03 – Shared Installation Co. DAYIC – CAN/ULC-S561-03 – Shared and Full Service Fire Signal Receiving Centres

Quoted From an article by Frank Donati and Alan Cavers in the March 2015 CFAA Journal

COMMUNICATORS

Page 56: Presenter: Frank Kurz ANUBIS - Welcome to Canadian Fire ... Kurz ElementsofTesting.pdf · ONSITE DOCUMENTATION FIRE ALARM/EVC ... Monthly Test Reports . ONSITE DOCUMENTATION

What makes a fire alarm technician a true LIFE SAFETY EXPERT?

Adopt the principals of a professional Practice Guideline (such as the one published by ASTTBC)

READ THE BLOOMIN’ THING!!!

Gain in Knowledge

Remain Vigilant

Never Compromise Your Integrity