prestige Water Boiler Excellence Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa- tion in order to gain warranty coverage. When receiving the PRESTIGE Excellence unit, any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee. Leave all documentation received with appliance with owner for future reference. * I N S T A L L A T I O N A N D M A I N T E N A N C E * * I N S T A L L A T I O N A N D M A I N T E N A N C E * M A N U A L M A N U A L 2011-61 Manual PRESTIGE Excellence - Revised 2/6/14 If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS - Do not try to light any appliance - Do not touch any electrical switch; do not use any phone in your building. - Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. - If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. L I S T E D WARNING NOTICE Part 1 of 2 (Part 2 begins on page 82)

Upload: phamcong

Post on 03-Apr-2018

218 views

Category:

Documents


3 download

TRANSCRIPT

prestige

Water Boiler Excellence

Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa-tion in order to gain warranty coverage.

When receiving the PRESTIGE Excellence unit, any claims for damage or shortage in shipment must befiled immediately against the transportation company by the consignee.

Leave all documentation received with appliance with owner for future reference.

* I N S T A L L A T I O N A N D M A I N T E N A N C E ** I N S T A L L A T I O N A N D M A I N T E N A N C E *M A N U A LM A N U A L

2011-61 Manual PRESTIGE Excellence - Revised 2/6/14

If the information in this manual is not followed exactly, a fire or explosion mayresult causing property damage, personal injury or death.

FOR YOUR SAFETY• Do not store or use gasoline or other flammable vapors and liquids in the vicinity ofthis or any other appliance.

• WHAT TO DO IF YOU SMELL GAS- Do not try to light any appliance- Do not touch any electrical switch; do not use any phone in your building.- Immediately call your gas supplier from a neighbor’s phone. Follow the gassupplier’s instructions.

- If you cannot reach your gas supplier, call the fire department.Installation and service must be performed by a qualified installer, service agency or thegas supplier.

L I S T E D

WARNING

NOTICE

Part 1 of 2(Part 2 begins on page 82)

This manual outlines the requirements for installation of the PRESTIGE Excellence.Those requirements include Boiler Piping, Venting/Combustion Air, Start-Up andMaintenance.- For detailed instructions regarding the installation of the vent/combustion air systemreference the PRESTIGE Vent Supplement and/or the various optional vent kitinstructions.

- For instructions regarding the PRESTIGE Excellence Domestic Water HeaterInstallation requirements and piping, reference the PRESTIGE Excellence IndirectWater Heater Manual beginning after page 82 of PRESTIGE Excellence WaterBoiler Manual.

The PRESTIGE Vent Supplement is included in the unit’s installation envelope. Forinstructions or information regarding the various optional vent kits contact ACV-Triangle Tube Technical Support.

WARNING

Table of Contents

i

PRODUCT AND SAFETY INFORMATION

Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Product and Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

SECTION I - PRE-INSTALLATION ITEMS

Code Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Determining Product Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Boiler Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Recommended Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Residential Garage Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Boiler Freeze Protection Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

SECTION II - COMBUSTION AIR AND VENTING

Combustion Air Contamination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Ventilation and Combustion Air Requirements - Direct Vent . . . . . . . . . . . 6Ventilation and Combustion Air Requirements - Category IV . . . . . . . . . . 6Methods of Accessing Combustion Air into a Space - Category IV . . . . . . 7

- Indoor Combustion Air. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- Outdoor Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8- Combination of Indoor and Outdoor Combustion Air. . . . . . . . . . 9

Combustion Air and Vent Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Removal of an Existing Boiler from a Common Vent System . . . . . . . . . . 10Commonwealth of Massachusetts Installation . . . . . . . . . . . . . . . . . . . . . . . 11

SECTION III - UNIT PREPARATIONS

Handling Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Wall Mounting Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Wall Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Wall Bracket Installation - Stud Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Wall Bracket Installation - Solid Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Boiler Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

SECTION IV - BOILER PIPING

General Piping Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Low Water Cut Off Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Boiler Air Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Additional Limit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Table of Contents

ii

Backflow Preventer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Boiler System Piping Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Expansion Tank and Makeup Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-17

Diaphragm Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Closed-Type Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Circulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Sizing Primary Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17System Piping - Zone Circulators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17System Piping - Zone Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17System Piping - Through Boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17System Piping - Radiant Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18System Piping - Special Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18System Piping - Multiple Units Installation . . . . . . . . . . . . . . . . . . . . . . . . . 18Piping Component Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19System Piping Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-21

SECTION V - INSTALLING VENT / COMBUSTION AIR & CONDENSATE DRAIN

Installing Vent and Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Installing Condensate Drain Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-23

SECTION VI - GAS PIPING

Gas Supply Piping Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Natural Gas

Pipe Sizing -Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Natural Gas Supply Pressure Requirements. . . . . . . . . . . . . . . . . . . 25

Propane GasPipe Sizing - Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Propane Gas Supply Pressure Requirements . . . . . . . . . . . . . . . . . . 26Gas Valve/Venturi Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

SECTION VII - INTERNAL WIRING

General Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Fuse Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Internal Factory Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

SECTION VIII - EXTERNAL WIRING

Installation Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Line Voltage Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Circulator & Diverter Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Alarm Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

iii

Table of Contents

Low Voltage Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Outdoor Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Domestic Hot Water Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Additional Boiler Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32External Modulation Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32System Sensor Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Cascade Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Modbus Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Zone Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Zone Circulator Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34System Piping Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-36

SECTION IX - TRIMAX OPERATION

Trimax User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Trimax Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Trimax Menu Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Home Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Status Line Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42EZ Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Heating EZ Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43-44Domestic Hot Water EZ Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45EZ Setup Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Display EZ Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46CH/DHW Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Boiler Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Information Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Lockout History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Lockout Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Manual Reset Hard Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Automatic Reset Soft Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

SECTION X - START-UP PREPARATION

Check Boiler System Fluid ChemistryBoiler Fluid pH Level 6.0 to 8.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Boiler Fluid Hardness Less Than 7 Grains . . . . . . . . . . . . . . . . . . . 53Chlorinated Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Flush Boiler System to Remove Sediment. . . . . . . . . . . . . . . . . . . . . . . . . . 53Cleaning of Old Boiler/System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

iv

Table of Contents

Cleaning of New Boiler/System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Check and Test Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Use of Antifreeze in the Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Filling the Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Check Low Water Cut-Off Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Check for Gas Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Check Thermostat Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Inspection of Condensate Drain Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 55

SECTION XI- START-UP PROCEDURES

Final Checks Before Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56PRESTIGE Excellence Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56If PRESTIGE Excellence does Not Start Correctly . . . . . . . . . . . . . . . . . . . 56Check the PRESTIGE Excellence and System . . . . . . . . . . . . . . . . . . . . . . 56-59Operating Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

SECTION XII - OUTDOOR RESET CONTROL

Mounting the Outdoor Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Wiring the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

SECTION XIII - EXTERNAL MODULATING CONTROL

Wiring the Modulating Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Trimax Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Programming of External Modulating Control . . . . . . . . . . . . . . . . . . . . . . 62Factory Trimax Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

SECTION XIV - CHECK-OUT PROCEDURES

Check-Out Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

SECTION XV - INSTALLATION RECORD

Installation Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

SECTIONS XVI - MAINTENANCE SCHEDULE

Service Technician - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Owner Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

v

Table of Contents

SECTION XVII - MAINTENANCE PROCEDURES

Maintenance ProceduresReported Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Check Surrounding Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Inspect Burner Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Check System Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Clean Condensate Drain Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 68Check Ventilation Air Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Inspect Vent and Combustion Air Piping . . . . . . . . . . . . . . . . . . . . . 68Check Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Check Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Check Boiler Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Inspection of Ignition Electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Check Ignition Wiring and Ground Wiring . . . . . . . . . . . . . . . . . . . 69Check Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70Check Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70Perform Start-Up and Checkout Procedure . . . . . . . . . . . . . . . . . . . 70Check Burner Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70Check Flame Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Check Combustion Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Check Flue Gas Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Clean Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Review with Owner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72Handling Previously Fired Combustion Chamber Insulation . . . . . 72

REPLACEMENT PARTS

Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73-76

PRODUCT SPECIFICATIONS

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77-81

Product & Safety Information

1

Indicates the presence of a hazardoussituation which, if ignored, will result indeath, serious injury or substantialproperty damage.

Indicates a potentially hazardous situa-tion which, if ignored, can result indeath, serious injury or substantialproperty damage.

Indicates a potentially hazardous situa-tion which, if ignored, may result inminor injury or property damage.

Indicates special instructions on installa-tion, operation or maintenance, whichare important to equipment but notrelated to personal injury hazards.

Indicates recommendations made byACV-Triangle Tube for the installerswhich will help to ensure optimum oper-ation and longevity of the equipment

NOTICE

WARNING

CAUTION

BEST PRACTICE

DANGER

The following terms are used throughout this manual to bring attention to the presence ofpotential hazards or important information concerning the product.

ACV-Triangle Tube reserves the right to modify the technical specifications and compo-nents of its products without prior notice.

NOTICE

Definitions

2

Product & Safety Information

Do not use this appliance if any part hasbeen under water. Immediately call aqualified service technician to inspectthe appliance and to replace any part ofthe control system which has beenunder water.

WHAT TO DO IF YOU SMELL GAS- Do not try to light any appliance- Do not touch any electrical switch; donot use any phone in your building.

- Immediately call your gas supplierfrom a neighbor’s phone. Follow thegas supplier’s instructions.

- If you cannot reach your gas suppli-er, call the fire department.

Installation and service must be per-formed by a qualified installer, serviceagency or the gas supplier.

Should overheating occur or the gassupply fails to shut off, turn OFF themanual gas control valve external to theappliance.

DO NOT add cold make up water whenthe appliance is hot. Thermal shock cancause potential cracks in the heatexchanger.

When servicing the appliance:- Avoid electrical shock by discon-necting the electrical supply prior toperforming maintenance.

Qualified Installer:Prior to installing this product read all instruc-tions included in this manual and all accompa-nying manuals/documents with this appliance.Perform all installation steps required in thesemanuals in the proper order given. Failure toadhere to the guidelines within these manualscan result in severe personal injury, death orsubstantial property damage.

Homeowner:- This product should be maintained /serviced and inspected annually by aqualified service technician.

- This manual is intended for use by aqualified Installer/Service Technician.

Please reference the unit’s model numberand the serial number from the ratinglabel, on the control panel when inquiringabout service or troubleshooting.

ACV-Triangle Tube accepts no liability forany damage, injury or loss of life resultingfrom incorrect installation, from alterationof any factory supplied parts or from theuse of parts or fittings not specified byACV-Triangle Tube. If there is a conflict ordoubt about the proper installation of theunit or any factory supplied or replacementparts please contact ACV-Triangle TubeTechnical Support.

A byproduct of any gas fired appliance(stove, fire place, clothes dryer, waterheater, furnace, boiler, etc.) is carbonmonoxide. In the absence of any state orlocal codes requiring the installation ofcarbon monoxide detector and alarms,ACV-Triangle Tube’s recommendationis to follow the requirements of theCommonwealth of Massachusetts, seepage 11.

WARNING

WARNING

WARNING

CAUTION

DANGER WARNING

NOTICE

WARNING

WARNING

Pre-Installation Items

3

SECTION I - Pre-Installation ItemsCode ComplianceThis product must be installed in accordance tothe following:

- All applicable local, state, national andprovincial codes, ordinances, regula-tions and laws.

- For installations in Massachusetts, coderequires the boiler to be installed by alicensed plumber or gas fitter, and ifantifreeze is utilized, the installation ofa reduced pressure backflow preventerdevice is required in the boiler’s coldwater fill or make up water supply line.

- For installation in Massachusetts all directvented appliances must comply with theguidelines as outlined on page 11.

- The National Fuel Gas Code NFPA54/ANSI Z 223.1 - Latest edition.

- National Electric Code ANSI/NFPA 70.- For installations in Canada -“Installation

Code for Gas Burning Equipment”CGA/B149.1 or B149.2 CanadianElectrical Code Part 1 CSA C22.1.

- Standards for Controls and SafetyDevices for Automatically Fired Boilers,ANSI/ASME CSD-1, when required.

The PRESTIGE Excellence boiler gasmanifold and gas controls meet the safelighting and other performance require-ments as specified in ANSI Z21.13 latestedition.

Determining Product Location

The PRESTIGE boiler is certified forindoor, conditioned space installationsONLY.

Before locating the PRESTIGE Excellencecheck for convenient locations to:

- Heating system piping- Venting - Gas supply piping- Electrical service

Ensure the boiler location allows the combus-tion air/vent piping to be routed directly throughthe building and terminate properly outside witha minimum amount of length and bends.

Ensure the area chosen for the installation of thePRESTIGE Excellence is free of any com-bustible materials, gasoline and other flammableliquids.

Failure to remove or maintain the areafree of combustible materials, gasolineand other flammable liquids or vaporscan result in severe personal injury,death or substantial property damage.

Ensure the PRESTIGE Excellence and its con-trols are protected from dripping or sprayingwater during normal operation or service.

The PRESTIGE Excellence should beinstalled in a location so that any water leakingfrom the boiler or piping connections or reliefvalve will not cause damage to the area sur-rounding the unit or any lower floors in thestructure.

Boiler ReplacementIf the PRESTIGE Excellence is replacing anexisting boiler, the following items should bechecked and corrected prior to installation:

- Boiler piping leaks and corrosion.- Improper location and sizing of the

expansion tank on the boiler heatingloop.

- If applicable, level and quality of freezeprotection within the boiler system.

NOTICE

WARNING

NOTICE

Pre-Installation ItemsRecommended ClearancesThe PRESTIGE Excellence is approved forzero clearance to combustibles, excludingvent and boiler piping.

- Boiler Piping - 1/4 inch from com-bustible materials.

- Reference the appropriate vent supple-ment for clearance requirements.

To provide serviceability to the unit it isrecommended that the following clear-ances be maintained:Top boiler jacket - 24 inches [610 mm].Front - 24 inches [610 mm].Bottom boiler piping - 24 inches [610 mm].Rear - 0 inchesSides - 6 inches [153 mm]

If the clearances listed above cannot bemaintained or the enclosure in which theboiler is installed is less than 85 cubic feet,the space must be ventilated. See page 6for ventilation requirements.

When maintaining zero clearance or lessthan recommended clearances, someproduct labeling may become hiddenand unreadable.

When installing the PRESTIGEExcellence in a confined space, sufficientair must be provided for proper combus-tion and venting and to allow, undernormal operating conditions, proper airflow around the product to maintainambient temperatures within safe limitsto comply with the National Fuel GasCode NFPA 54 - latest edition.

Residential Garage InstallationsWhen installing the PRESTIGE Excellence in aresidential garage, the following special precau-tions per NFPA 54/ANSI Z223.1 must be taken:

- Mount the unit a minimum 18 inches[458 mm] above the floor level of thegarage. Ensure the burner and ignitiondevices / controls are no less than 18inches [458 mm] above the floor level.

- Locate or protect the unit in a manner so itcannot be damaged by a moving vehicle.

Boiler Freeze Protection FeatureThe Trimax boiler management system has afreeze protection feature built in. This featuremonitors the boiler temperature and responds asfollows when no call for heat is present:

- 46ºF [8ºC] CH (1) & Auxiliary BoilerPumps ON

- 42ºF [6ºC] CH (1), Auxiliary Boiler &System Pumps ON, Burner operates atlow fire

- 60ºF [15ºC] Freeze protection ends.Burner & all pumps OFF after complet-ing CH Post Pump Time.

The boiler freeze protection feature isdisabled during a hard lockout, howeverthe circulators will operate.

The boiler freeze protection feature isdesigned to protect the boiler. The boilershould be installed in a primary/sec-ondary piping arrangement if it isinstalled in an unheated space orexposed to water temperatures of 46ºF orless. See Section IV for primary/sec-ondary piping examples. See Section Xfor antifreeze guides.

NOTICE

WARNING

WARNING

CAUTION

CAUTION

BEST PRACTICE

4

Combustion Air and Venting

5

SECTION II - Combustion Air andVentingCombustion Air Contamination

If the PRESTIGE Excellence combus-tion air inlet is located in any area likelyto cause or contain contamination, or ifproducts, which would contaminate theair cannot be removed, the combustionair must be repiped and terminated toanother location. Contaminated com-bustion air will damage the unit and itsburner system, resulting in possiblesevere personal injury, death or substan-tial property damage.

Do not operate a PRESTIGE Excellenceif its combustion air inlet is located neara laundry room or pool facility. Theseareas will always contain hazardous con-taminants.Pool and laundry products and commonhousehold and hobby products oftencontain fluorine or chlorine compounds.When these chemicals pass through theburner and vent system, they can formstrong acids. These acids can create cor-rosion of the heat exchanger, burnercomponents and vent system, causingserious damage and presenting a possi-ble threat of flue gas spillage or waterleakage into the surrounding area.Please read the information listed below.If contaminating chemicals are locatednear the area of the combustion air inlet,the installer should pipe the combustionair inlet to an outside area free of thesechemicals per SECTION V of thisinstallation manual.

Potential contaminating products- Spray cans containing chloro/fluorocar-

bons- Permanent Wave Solutions- Chlorinated wax - Chlorine - based swimming pool chem-

icals / cleaners- Calcium Chloride used for thawing ice- Sodium Chloride used for water soft-

ening- Refrigerant leaks- Paint or varnish removers- Hydrochloric acid / muriatic acid- Cements and glues- Antistatic fabric softeners used in

clothes dryers- Chlorine-type bleaches, detergents, and

cleaning solvents found in householdlaundry rooms

- Adhesives used to fasten building prod-ucts and other similar products

Areas likely to contain these products- Dry cleaning / laundry areas and estab-

lishments- Beauty salons- Metal fabrication shops- Swimming pools and health spas- Refrigeration Repair shops- Photo processing plants- Auto body shops- Plastic manufacturing plants- Furniture refinishing areas and estab-

lishments- New building construction- Remodeling areas- Garages with workshops

WARNING

WARNING

6

Combustion Air and Venting

Ventilation and Combustion AirRequirements - Direct VentA Direct Vent appliance utilizes uncontaminat-ed outdoor air (piped directly to the appliance)for combustion.

For Direct Vent installations, involving onlythe PRESTIGE Excellence, in which the mini-mum service clearances are maintained as list-ed on page 4, no ventilation openings arerequired.For Direct Vent, zero clearance installationsinvolving only the PRESTIGE Excellence, thespace / enclosure must provide two openingsfor ventilation. The openings must be sized toprovide 1 square inch of free area per 1,000BTUH of boiler input. The openings shall beplaced 12 inches from the top of the space and12 inches from the floor of the space.

For installations in which the PRESTIGEExcellence shares the space with air movers(exhaust fan, clothes dryers, fireplaces, etc.)and other combustion equipment (gas or oil)the space must be provided with adequate airopenings to provide ventilation and combus-tion air to the equipment. To properly size theventilation / combustion air openings, theinstaller must comply with the National FuelGas Code NFPA 54, ANSI Z223.1 for installa-tions in the U.S or CSA B149.1 and B149.2 forinstallations in Canada.

The space must be provided with venti-lation / combustion air openings proper-ly sized for all make-up air requirements(exhaust fans, clothes dryers, fireplaces,etc.) and the total input of all applianceslocated in the same space as the PRES-TIGE Excellence, excluding the input ofa Direct Vent PRESTIGE Excellencewhich uses combustion air directly fromthe outside, thus additional free area forthe openings is not required. Failure toprovide or properly size the openingscould result in severe personal injury,death or substantial property damage.

Ventilation and Combustion AirRequirements - Category IVA Category IV appliance utilizes uncontami-nated indoor or outdoor air (surrounding theappliance) for combustion.

In order to reduce the potential risksassociated with indoor contaminates(listed on page 5), flammable vapors andtight housing construction (little or noinfiltration air), it is recommended topipe uncontaminated combustion airdirectly from the outdoors to the appli-ance. This practice also promotes highersystem efficiency by reducing heatedindoor air from being exhausted fromthe house and replaced by cold infiltra-tion air into the house.

For installations in which the PRESTIGEExcellence shares the space with air movers(exhaust fan, clothes dryers, fireplaces, etc.) andother combustion equipment (gas or oil) thespace must be provided with adequate air open-ings to provide ventilation and combustion air tothe equipment. To properly size the ventilation/ combustion air openings, the installer mustcomply with the National Fuel Gas Code NFPA54, ANSI Z223.1 for installations in the U.S orCSA B149.1 and B149.2 for installations inCanada, as referenced in this section of the man-ual and titled Methods of AccessingCombustion Air into a Space.

The space must be provided with venti-lation / combustion air openings proper-ly sized for all make-up air requirements(exhaust fans, clothes dryers, fireplaces,etc.) and the total input of all appliances,including the PRESTIGE Excellencewhen located in the same space. Failureto provide or properly size the openingscould result in severe personal injury,death or substantial property damage.

WARNING

WARNING

BEST PRACTICE

7

Combustion Air and VentingMethods of Accessing Combustion Air Into ASpace - Category IV

Indoor Combustion Air

The methods listed in this section foraccessing Indoor Combustion Airassume that the infiltration rate is ade-quate and not less than .40 ACH. Forinfiltration rates less than .40 ACH, ref-erence the NFPA 54 National Fuel GasCode for additional guidance.

Opening Size and Location

Openings used to connect indoor spaces shallbe sized and located in accordance with thefollowing see Fig. 1:

- Combining spaces on the same story.Each opening shall have a minimumfree area of 1 sq. in./1000 Btu/hr of thetotal input rating of all gas utilizationequipment in the space, but not less than100 sq. inches. One opening shall com-mence within 12 inches of the top, andone opening shall commence within 12inches of the bottom of the enclosure.

The minimum dimension of air open-ings shall be not less than 3 inches.

- Combining spaces in different stories.The volumes of spaces in different sto-ries shall be considered as communicat-ing spaces where such spaces are con-nected by one or more openings indoors or floors having a total minimumfree area of 2 sq. in./1000 Btu/hr oftotal input rating of all gas utilizationequipment.

Outdoor Combustion Air

Isolating the combustion appliance roomfrom the rest of the building and bring-ing in uncontaminated outside air forcombustion and ventilation is alwayspreferred.

Opening Size and Location

The minimum dimension of air openings shallbe not less than 3 inches

Openings used to supply combustion and ven-tilation air shall be sized and located in accor-dance with the following:

One Permanent Opening Method. See Fig. 2One permanent opening, commencing within 12in. of the top of the enclosure, shall be provided.The equipment shall have clearances of at least 1inch from the sides and 6 in. from the front of theappliance. The opening shall directly communi-cate with the outdoors or shall communicatethrough a vertical or horizontal duct to the out-doors or spaces that freely communicate with theoutdoors and shall have a minimum free area ofthe following:

- 1sq. in./3000 Btu/hr of the total inputrating of all equipment located in theenclosures, and

NOTICE

BEST PRACTICE

All Combustion Air from AdjacentIndoor Spaces Through IndoorCombustion Openings

Fig. 1:

8

Combustion Air and Venting

- Not less than the sum of the areas of allvent connectors in the space.

Two Permanent Openings Method. Two permanent openings, one commencingwithin 12 in. of the top and one commencingwithin 12 in. of the bottom of the enclosure,shall be provided. The openings shall commu-nicate directly, or by ducts, with the outdoorsor spaces that freely communicate with the out-doors, as follows:

- Where directly communicating with theoutdoors or where communication to theoutdoors is through vertical ducts, eachopening shall have a minimum free areaof 1 sq. in./4000 Btu/hr of total input rat-ing of all equipment in the enclosure.See Fig.3.

- Where communicating with the out-doors is through horizontal ducts, eachopening shall have a minimum freearea of not less than 1 sq.in./2000Btu/hr of total input rating of all equip-ment in the enclosure. See Fig. 4.

All Combustion Air from OutdoorsThrough One Permanent AirOpening

Fig. 2: All Combustion Air from OutdoorsThrough Ventilated Attic

Fig. 3:

All Combustion Air from OutdoorsThrough Horizontal Ducts

Fig. 4:

9

Combustion Air and VentingCombination of Indoor and OutdoorCombustion Air

Indoor Openings: Where used, openings con-necting the interior spaces shall comply withthe Indoor Combustion Air section on page 7.

Outdoor Opening(s) Location. Outdoor open-ing(s) shall be located in accordance with theOutdoor Combustion Air section.

Outdoor Opening(s) Size. Outdoor opening(s) shallbe calculated in accordance with the following:

- The ratio of the interior spaces shall bethe available volume of all communi-cating spaces divided by the requiredvolume.

- The outdoor size reduction factor shallbe 1 minus the ratio of interior spaces.

- The minimum size of outdoor open-ing(s) calculated in accordance with theabove outdoor air section multiplied bythe reduction factor. The minimumdimension of air openings shall not beless than 3 in.

Do not install the PRESTIGE Excellenceinto a common vent with other gas or oilappliances. This may cause flue gasspillage or appliance malfunction, result-ing in possible severe personal injury,death or substantial property damage.

Combustion Air and Vent PipingThe PRESTIGE Excellence requires aCategory IV venting system, which is designedfor pressurized venting and condensate.

The PRESTIGE Excellence is certified perANSI Z21.13 as a Category IV or Direct Vent(sealed combustion) appliance. A Category IVappliance utilizes uncontaminated indoor oroutdoor air (surrounding the appliance) forcombustion. A Direct Vent appliance utilizesuncontaminated outdoor air (piped directly tothe appliance) for combustion.

In order to reduce the potential risksassociated with indoor contaminates(listed on page 5), flammable vapors andtight housing construction (little or noinfiltration air), it is recommended topipe uncontaminated combustion airdirectly from the outdoors to the appli-ance. This practice also promotes highersystem efficiency by reducing heatedindoor air from being exhausted fromthe house and replaced by cold infiltra-tion air into the house.

Install combustion air and vent pipe asdetailed in the PRESTIGE VentSupplement included in the boiler installa-tion envelope. Refer to optional vent kitinstructions for addition vent installationinstructions.

Verify installed combustion air and ventpiping are sealed gas tight and meet allprovided instructions and applicablecodes, failure to comply will result insevere personal injury of death.

NOTICE

BEST PRACTICE

DANGER

DANGER

10

Combustion Air and VentingRemoval of an Existing Boiler from aCommon Vent System

When an existing boiler is removed from acommon venting system, the common ventingsystem is likely to be too large for properventing of the remaining appliances. At thetime of removal of an existing boiler, the fol-lowing steps shall be followed with eachappliance remaining connected to the com-mon venting system placed in operation,while the other appliances remaining con-nected to the common venting system are notin operation.1. Seal any unused openings in the common

venting system.2. Visually inspect the venting system for

proper size and horizontal pitch and deter-mine there is no blockage or restriction,leakage, corrosion and other deficiencieswhich could cause an unsafe condition.

3. Insofar as is practical, close all buildingdoors and windows and all doors betweenthe space in which the appliances remain-ing connected to the common venting sys-tem are located and other spaces of thebuilding. Turn on clothes dryers and anyappliance not connected to the commonventing system. Turn on any exhaust fans,such as range hoods and bathroomexhausts, so they will operate at maximumspeed. Do not operate a summer exhaustfan. Close fireplace dampers.

4. Place in operation the appliance beinginspected. Follow the lighting instructions.Adjust thermostat so appliance will operatecontinuously.

5. Test for spillage at the draft hood reliefopening after 5 minutes of main burneroperation. Use the flame of a match or can-dle, or smoke from a cigarette, cigar or pipe.

6. After it has been determined that eachappliance remaining connected to the com-mon venting system properly vents whentested as outlined above, return doors, win-dows, exhaust fans, fireplace dampers, andany other gas-burning appliance to theirprevious condition of use.

7. Any improper operation of the commonventing system should be corrected so theinstallation conforms with the NationalFuel Gas Code, ANSI Z223.1/NFPA 54and/or CAN/CGA B149, Installation codes.When resizing any portion of the commonventing system, the common venting sys-tem should be resized to approach the min-imum size as determined using the appro-priate tables in Part II of the National FuelGas Code ANSI Z223.1/NFPA 54 and/orCAN/CGA B149, Installation codes.

Do not install the PRESTIGE Excellenceinto a common vent with other gas or oilappliances. This may cause flue gasspillage or appliance malfunction, result-ing in possible severe personal injury,death or substantial property damage.

BEST PRACTICE

DANGER

11

Combustion Air and Venting

For direct-vent appliances, mechanical-vent heating appliances or domestic hotwater equipment, where the bottom of thevent terminal and the air intake is installedbelow four feet above grade the followingrequirements must be satisfied:

1. If there is not one already present, oneach floor level where there are bed-room(s), a carbon monoxide detectorand alarm shall be placed in the livingarea outside the bedroom(s). The car-bon monoxide detector shall complywith NFPA 720 (2005 Edition).

2. A carbon monoxide detector shall alsobe located in the room that houses theappliance or equipment and shall:

a. Be powered by the same electrical cir-cuit as the appliance or equipment suchthat only one service switch servicesboth the appliance and the carbonmonoxide detector;

b. Have battery back-up power;

c. Meet ANSI/UL 2034 Standards andcomply with NFPA 720 (2005 Edition);and

d.Have been approved and listed by theNationally Recognized TestingLaboratory as recognized under 527CMR.

3. A Product-approved vent terminal mustbe used, and if applicable, a Product-approved air intake must be used.Installation shall be in strict compliancewith the manufacturer’s instructions. Acopy of the installation instructionsshall remain with the appliance orequipment at the completion of theinstallation.

4. A metal or plastic identification plateshall be mounted at the exterior of thebuilding, four feet directly above thelocation of vent terminal. The plateshall be of sufficient size to be easilyread from a distance of eight feet away,and read “Gas Vent Directly Below”.

Installer must provide tag identificationplate and ensure the lettering meets coderequirements.For direct-vent appliances, mechanical-vent heating appliances or domestic hotwater equipment, where the bottom of thevent terminal and the air intake are installedabove four feet above grade the followingrequirements must be satisfied:1. If there is not one already present, on

each floor level where there are bed-room(s), a carbon monoxide detectorand alarm shall be placed in the livingarea outside the bedroom(s). The car-bon monoxide detector shall complywith NFPA 720 (2005 Edition).

2. A carbon monoxide detector shall: a. Be located in the room that houses theappliances or equipment;

b.Be either hard wired or battery poweredor both; and

c. Shall comply with NFPA 720 (2005Edition)

3. A Product-approved vent terminal mustbe used, and if applicable, a Product-approved air intake must be used.Installation shall be in strict compliancewith the manufacturer’s instructions. Acopy of the installation instructionsshall remain with the appliance orequipment at the completion of theinstallation.

NOTICE

Commonwealth of Massachusetts Installations Only

12

Unit PreparationsSECTION III - Unit PreparationsHandling InstructionsThe PRESTIGE Excellence is generally easierto handle and maneuver once removed fromthe shipping carton.

To remove the shipping carton:

Use care not to drop, bump or rotate theboiler upside down, as damage to theboiler will result.

1. Remove any shipping straps and open theside of the shipping carton.

2. Slide the unit with the foam inserts out ofthe carton.

3. Discard all packing materials.

Wall Mounting InstallationThe PRESTIGE Excellence should be wallmounted using the bracket provided with theboiler. The PRESTIGE Excellence is notdesigned for floor installation. If floor installa-tion is required an optional floor stand is avail-able through ACV-Triangle Tube.

The wall used for mounting the PRES-TIGE Excellence must be verticallyplumbed and capable of supporting aminimum 250 pounds [115 kg]. Failureto comply with these requirements couldresult in personal injury, death or sub-stantial property damage.

Wall Mounting Guidelines1. The wall-mounting bracket is designed for

stud spacing of 12 inch or 16 inch on cen-ters. For unconventional stud spacing, asolid / secure mounting surface must beprovided for installation of the bracket.

2. DO NOT mount or attempt to mount thewall bracket to hollow sheet rock or lathwalls using anchors. Only install boiler tostuds or equivalent wood structure.

3. For applications using solid walls (rock,concrete, brick, cinder block, etc.), installthe wall bracket using anchors (doubleexpansion shields) and bolts with washersprovided with the boiler.

4. The boiler is too heavy and bulky for a sin-gle person to lift and attempt to mount; aminimum of 2 people are required formounting the boiler.

Use extreme care not to drop the boileror cause bodily injury while lifting ormounting the boiler onto the bracket.Once mounted verify that the boiler issecurely attached to the bracket andwall. Failure to comply with the aboveguidelines could result in property dam-age, personal injury or death.

NOTICE

NOTICE

CAUTION

13

Unit PreparationsWall Bracket Installation - Stud Walls1. To distribute the weight of the boiler even-

ly when mounting onto a stud wall it is rec-ommended to use the PRESTIGE WallFrame kit.

2. When using the wall frame to mount theboiler reference the kit installation instruc-tions and ensure the frame is securely fas-tened to the wall.

3. If the structure of wall is questionable, insupporting a minimum weight of 250pounds [115 kg.], it is recommended to usethe optional floor stand.

Wall Bracket Installation - Solid Walls1. Locate the general area of the boiler place-

ment.2. Place the wall-mounting bracket on the

wall ensuring the upper edge of the bracketis away from the wall.

3. Level the bracket and use a pencil to markthe location of the mounting slots on thewall.

4. Remove the bracket from the wall and drilla 5/8” diameter hole by 1-3/8” deep posi-tioned in the center of each mark.

5. Install the anchors (provided) flush orslightly recessed in the drilled holes withthreaded side facing down.

6. Reposition the bracket on the wall andalign mounting slots/holes. Insert the twobolts (provided) through the mountingslots/holes and loosely tighten.

7. Level bracket and tighten bolts securely.

Boiler Mounting1. Obtain assistance in lifting the boiler onto

the wall bracket.2. Install the boiler making sure the boiler

mounting lip located along the upper edgeof the rear jacket panel engages the wall-mounting bracket. Ensure the boiler isseated properly and is secure.

Boiler Piping

SECTION IV - Boiler PipingGeneral Piping Requirements- All plumbing must meet or exceed all local,

state and national plumbing codes.- Support all piping using hangers. DO NOT

support piping by the unit or its components.- Use isolation valves to isolate system com-

ponents.- Install unions for easy removal of the

PRESTIGE Excellence from the systempiping.

- If plastic pipe is used for boiler piping, itmust have a maximum oxygen diffusionrate of 0.1 mg/liter per day for boiler andwater heater protection.

Use a two wrench method when tighten-ing piping onto the boiler connections.Use one wrench to prevent the boilerpiping from turning / twisting. Failureto support the boiler piping and connec-tions in this manner could cause damageto the boiler and its components.

Pressure Relief Valve1. The PRESTIGE Excellence is supplied

with a 30 psi pressure relief valve and mustbe piped using the PRV connection asshown in Fig. 5 page 15.

2. To avoid potential water damage to the sur-rounding area or potential scalding hazarddue to the operation of the relief valve, thedischarge piping:- Must be connected to the discharge out-

let of the relief valve and directed to asafe place of disposal.

- Length should be as short and direct aspossible. The size of the discharge lineshould not be reduced, maintain thesame size as the outlet of the relief valve.

- Should be directed downward towardsthe floor at all times. The piping shouldterminate at least 6 inches [153 mm]above any drain connection to allowclear visibility of the discharge.

- Should terminate with a plain end, notwith a threaded end. The material ofthe piping should have a serviceabletemperature rating of 250ºF or greater.

- Should not be subject to conditionswhere freezing could occur.

- Should not contain any shut-off valves orobstructions. No shut-off valve should bepiped between the boiler and relief valve.

Failure to comply with the guidelines oninstalling the pressure relief valve and dis-charge piping can result in personal injury,death or substantial property damage.

Low Water Cutoff Device- The PRESTIGE Excellence is equipped with

a factory installed pressure switch type LowWater Cut Off device.

- The minimum operating system pressureallowable with this device is 10 psig.

- Check local codes if a Low Water CutoffDevice is required. If so, determine if this devicemeets the requirements of the local codes.

The PRESTIGE Excellence control sys-tem also senses the system water tempera-tures entering and exiting the heatexchanger to provide protection againstlow water conditions Where local codesand jurisdiction do not accept a pressuredevice for low water protection, the juris-dictions may accept these PRESTIGEExcellence integral control functions as ameans of providing low water protection.

WARNING

WARNING

NOTICE

14

15

Boiler Piping

Boiler Return Connection

Boiler Drain Valve(field supplied)

Boiler Supply Connection

Pressure Relief Valve(Supplied with Boiler)

3/4" Street ElbowAir Vent

Drain Piping Directedto a Suitable

Place of Drainage

Fig. 5: Pressure Relief Valve and Boiler Drain Valve Installation

Boiler Air Vent

This boiler is supplied with a specialautomatic air vent that will provide reli-able operation in purging air from theboiler. The hygroscopic cap suppliedwith the automatic air vent MUSTremain tight at all times on the air ventbody. The hygroscopic cap has a mem-brane which expands upon contact withwater and seals the air vent until themembrane dries up due to new airforming in the air vent.

1. Make sure to fully tighten the cap on the airvent on initial installation.

2. Never loosen the hygroscopic cap to allowair to escape the air vent. Air will exit withthe cap fully tightened in place.

3. If the hygroscopic cap is not fully tight-ened, water may leak from the cap. Simplytighten the cap securely.

NOTICE

Boiler Piping

Additional Limit ControlIf a separate LWCO device is required by cer-tain local jurisdictions or when the boiler isinstalled above the system piping, the follow-ing guidelines must be followed:

- The LWCO device must be designedfor water installations, electrode probe-type is recommended.

- The LWCO device must be installed ina tee connection on the boiler supplypiping above the boiler.

- Wiring of the LWCO device to the PRES-TIGE Excellence is done directly onto thelow voltage terminal strip, reference Fig.19 page 29 for available terminals for anexternal limit (manual or auto reset).

If the installation is to comply with ASME orCanadian requirements, an additional hightemperature limit may be needed. Consultlocal code requirements to determine compli-ance. The limit should be installed as follows:

- Install the limit in the boiler supply pip-ing between the boiler and any isolationvalve.

- Consult heat exchanger for maximumset point of limit.

- For wiring of the limit reference Fig. 19,page 29, using the external limit/manualreset terminals on the low voltage termi-nal strip. This will provide a "hard" lock-out requiring a manual reset of the control.

Backflow Preventer- Use a backflow preventer valve in the

make-up water supply to the unit asrequired by local codes.

Boiler System Piping Applications

It is recommended on all piping applica-tions to utilize a primary/secondary pip-ing arrangement as a means to providefreeze protection of the boiler, which isan integral function of the boiler control.Maintain the minimum boiler flow rate,see Graph 2 on page 81. For other pip-ing arrangements, contact ACV-TriangleTube Technical Support or consult otherapproved/recognized design arrange-ments.

On piping applications utilizing a singlezone or other recognized piping designarrangements, it is recommended that theinstaller uses flow/check valves withweighted seats at or near the appliance toprevent gravity circulation.

Expansion Tank and Makeup WaterEnsure the expansion tank is properly sized forthe boiler volume (5 gallons [19 L]) and thesystem volume and temperature.

Undersized expansion tanks will causesystem water to be lost through the pres-sure relief valve and cause additionalmakeup water to be added to the system.Eventual boiler heat exchanger failurecan result due to this excessive makeupwater addition.

The expansion tank must be located as shownin Figs. 9 through 12 on pages 20 and 21 or asper recognized design methods. Refer to theexpansion tank manufacturer instructions foradditional installation details.

CAUTION

BEST PRACTICE

BEST PRACTICE

16

Boiler Piping

Connect the expansion tank to an air separatoronly if the air separator is located on the suc-tion side (inlet) of the system circulator.Always locate and install the system fill con-nection at the same location as the expansiontank connection to the system.

Diaphragm Expansion TankAlways install an automatic air vent on the topof the air separator to remove residual air fromthe system.

Closed-Type Expansion TankIt is recommended to pitch any horizontal pip-ing upwards toward the expansion tank 1 inchper 5 feet of piping. Use 3/4” piping for theexpansion tank to allow air within the systemto rise.

DO NOT install automatic air vents on aclosed-type expansion tank system. Airmust remain in the system and bereturned to the expansion tank to pro-vide an air cushion. An automatic airvent would cause air to be vented fromthe system resulting in a water-loggedexpansion tank.

CirculatorThe PRESTIGE Excellence is supplied with aBoiler circulator that provides circulation forcentral/space heating (CH) and domestic hotwater (DHW) production. See Graph 2 on page81 for pressure drop and minimum flow ratethrough the boiler.

Sizing Primary PipingSee Figs. 9 through 12 on pages 20 and 21, forrecommended piping arrangements based onvarious applications. Size the piping and sys-tem components required in the space heatingsystem, using recognized design methods.

System Piping - Zone CirculatorsConnect the PRESTIGE Excellence to the sys-tem piping as shown in Fig. 9 page 20 whenzoning with zone circulators.

The installer must provide a separate circulatorfor each zone of space heating.

To ensure an adequate flow rate throughthe PRESTIGE Excellence, the boilersupply and return piping size must be aminimum of 1 inch.

System Piping - Zone ValvesConnect the PRESTIGE Excellence to the systempiping as shown in Fig. 10 page 20 when zoningwith zone valves. The primary / secondary pipingensures that the boiler loop has sufficient flow.

To ensure an adequate flow rate throughthe PRESTIGE Excellence, the boiler sup-ply and return piping size must be a min-imum of 1 inch.

System Piping - Through BoilerIn new or retrofit applications in whichprimary/secondary arrangement is not utilized, thePRESTIGE Excellence allows this flexibility dueto a lower boiler pressure drop, see Graph 2 onpage 81.Figure 11, page 21 illustrates a multiple zonevalve system with a single system/boiler circu-lator. A by-pass loop with a pressure differentialvalve must be installed on the system piping.Figure 12, page 21 illustrates a single zone utiliz-ing the boiler circulator as the system circulator.

NOTICE

CAUTIONNOTICE

17

18

Boiler PipingSystem Piping - Radiant HeatingThe heat exchanger design of the PRESTIGEallows operation in a condensing mode. This fea-ture requires no regulation of the return temperatureback to the boiler in radiant heating applications.

Due to the construction of the waterheater, do not install the PRESTIGEExcellence if the boiler piping containsnon-oxygen barrier tubing if the boilerpiping is considered an “open system”.Exposing the outer tank of the PRES-TIGE Excellence water heater to oxygencontamination will lead to prematuretank failure and denial of the warranty.

The boiler water supply temperature can bemaintained by the PRESTIGE, eliminatingthe need for a mix system to achieve thedesired temperature.

It is recommended for the installer to install ahigh temperature limit to ensure that the primarysupply temperature does not exceed the maxi-mum allowable temperature for the radiant tub-ing.

Size the system piping and circulator to pro-vide the flow needed for the radiant system.

To ensure an adequate flow rate throughthe PRESTIGE Excellence, the boilersupply and return piping size must be aminimum of 1 inch.

The addition of the high temperature limitis important when the PRESTIGEExcellence has completed a DHW call,which requires a high primary supplywater temperature.

System Piping - Special ApplicationIf the boiler is used in conjunction with achilled water/medium system, the boiler andchiller must be piped in parallel. Installflow/check valves to prevent the chilled medi-um from entering into the boiler.

If the boiler is used to supply hot water to theheating coils of an air handler where they maybe exposed to chilled air circulation, installflow/check valves or other automatic meansto prevent gravity circulation of the boilerwater during cooling cycles.

System Piping - Multiple Units InstallationIt is recommended to use a balanced manifoldsystem as the primary / secondary connectionto the space heating piping.

Maintain a minimum of 6 inches [153 mm] ofclearance between units to allow for servicing.For the space heating piping refer to the appli-cations mentioned in this manual or use recog-nized design methods.

CAUTION

NOTICE

NOTICE

19

Boiler Piping

Fig. 6: Piping Component Legend

20

Boiler Piping

AUX(Inside cabinet)

ZC2ZC1

D.V.

Z.V.

Z.V. SC1

BC1

prestige

AUX(Inside cabinet)

SYS

Fig. 9: System Piping - Zoning with Zone Circulators

Fig. 10: System Piping - Zoning with Zone Valves

The boiler system piping shown must be a “closed” system to avoid anyoxygen contamination and potential failure of the outer tank of the waterheater

NOTICE

Note: Reference Fig. 23, page 35 forPrestige Wiring.

Note: Reference Fig. 24, page 35 forPrestige Wiring.

Note: ZC1 and ZC2 circulatorscontrolled by SZC5 Zone Panel.

21

Boiler Piping

Z.V.

Z.V.

D.V.

BC1

prestige

AUX(Inside cabinet)

AUX(Inside Cabinet)

Fig. 11: System Piping - Multiple Zone Valve with Single System/Boiler Circulator

Fig. 12: System Piping - Single Zone System with Single System/Boiler Circulator

Note: Verify AUX circulator isproperly sized to overcome thesystem pressure drop and pro-vide adequate flow through theboiler system.

Note: Verify AUX circulatoris properly sized to overcomethe system pressure drop andprovide adequate flowthrough the boiler system.

The boiler system piping shown must be a “closed” system to avoid anyoxygen contamination and potential failure of the outer tank of the waterheater.

NOTICE

Note: Reference Fig. 25, page 36 forPrestige Wiring.

Note: Reference Fig. 26, page 36 forPrestige Wiring.

22

Installing Vent/Combustion Air & Condensate Drain

SECTION V - Installing Vent /Combustion Air & Condensate DrainInstalling Vent and Combustion Air

The PRESTIGE Excellence must be vent-ed and supplied with combustion air asshown in the PRESTIGE VentSupplement, included in the boiler instal-lation envelope. Refer to optional vent kitinstructions for additional vent installa-tion instructions. Once installation iscompleted, inspect the vent and combus-tion air system thoroughly to ensure sys-tems are airtight and comply with theinstructions given in the venting supple-ment and are within all requirements ofapplicable codes. Failure to comply withthe installation requirements on the vent-ing and combustion air piping will causesevere personal injury or death.

Installing Condensate Drain Assembly1. Locate the condensate drain assembly and

install as shown in Fig. 14 page 23.2. Remove the retaining nut, metal washer

and rubber seals from the condensate drainassembly. The metal washer must first becut using a pair of diagonal cutting pliers tomake it into a split washer. Insert themetal washer into the retaining nut andscrew onto the condensate drain assemblywithout rubber gaskets. Use the condensatedrain assembly as a tool to press the retain-ing nut with metal washer onto thepolypropylene condensate pan.

The installer may want to fill the con-densate trap with water prior to assem-bling on the unit.

3. Reassemble the condensate drain assemblyonto the boiler by tightening the retainingnut with rubber seal onto the boiler.

Ensure installation of the condensatedrain assembly included the metal wash-er. Failure to comply could result in thetrap assembly dislocating from the boiler.

Ensure the condensate drain assemblycontains the plastic seated ball. Do notinstall the condensate drain assembly ifthe ball is lost or missing, replace theentire assembly.

4. Remove the compression nut and rubberseal from the drain outlet.

5. Using 3/4” x 2’ flexible PVC tube provid-ed, slide the compression nut and rubberseal over the pipe

The use of 3/4” PVC or CPVC pipe isalso acceptable. If 3/4” pipe is useddeburr and chamfer pipe to allow mat-ing onto the drain assembly.

6. Thread the rubber seal into the compres-sion nut to ease installation of the pipe tothe drain assembly.

7. Seat the pipe onto the drain assembly andtighten the compression nut. Hand tightonly!

The installer may opt to using 13/16" IDtubing in lieu of rigid piping.

DANGER

WARNING

WARNING

NOTICE

NOTICE

NOTICE

Flexible Tubing(or 3/4 PVC/ CPVC Piping

to Drain)

CompressionNut with Rubber Seal

Fill Plugwith VacuumBreak Port

CondensateDrain Assembly

Plastic Ball(Not shown)

Retaining Nut(Hand Tight Only)

Place the Metal Washerand (2) Rubber Gaskets

in this Order for ProperSeal.

23

Installing Vent/Combustion Air & Condensate Drain

The drain line materials must be anapproved material by the authority hav-ing jurisdiction. In absence of suchauthority, PVC and CPVC piping mustcomply with ASTM D1785 or D2845.The cement and primer used on the pip-ing must comply with ASME D2564 orF493. For installations in Canada, useCSA or ULC certified PVC or CPVCpipe, fittings and cement/primer.

8. Continue the pipe from the drain assemblyto a floor drain or condensate pump.

When selecting and installing a conden-sate pump, ensure the pump is approvedfor use with condensing boilers and fur-naces. The pump should be equippedwith an overflow switch to prevent prop-erty damage from potential condensatespillage.

9. The PRESTIGE Solo will typically producea condensate that is considered slightlyacidic with a pH content below 3.0. Installa neutralizing filter if required by authorityhaving jurisdiction.

The condensate drain must remain filledand unobstructed and allow unrestrictedflow of condensate. The condensateshould not be subject to conditionswhere freezing could occur. If the con-densate is subjected to freezing orbecomes obstructed , it can leak, result-ing in potential water damage to the boil-er and surrounding area.NOTICE

CAUTION

NOTICE

Fig. 14: Condensate Drain Assembly

24

Gas PipingSECTION VI - Gas PipingGas Supply Piping Connection

The gas supply piping must be installedin accordance to all applicable local,state and national codes and utilityrequirements.

1. Install a 1/2” NPT pipe union at the factorysupplied gas nipple, for ease of service.

2. Install a manual shutoff valve in the gassupply piping as shown in Fig. 15. Forinstallations in Canada the installer musttag and identify the main shutoff valve.

3. Install a sediment trap (drip leg) on the gassupply line prior to connecting to the PRES-TIGE Excellence gas train as shown in Fig.15.

4. Support the gas piping using hangers. Donot support the piping by the unit or itscomponents.

5. Purge all air from the gas supply piping.6. Before placing the PRESTIGE Excellence

into operation, check and test all connec-tions for leaks.- Close the manual shutoff valve during

any pressure test with less than 13”w.c.. - Disconnect the PRESTIGE Excellence

and its gas valve from the gas supplypiping during any pressure test greaterthan 13”w.c..

Do not check for gas leaks with an openflame. Use a gas detection device or bub-ble test. Failure to check for gas leakscan cause severe personal injury, deathor substantial property damage.

7. Use pipe dope compatible with natural andpropane gases. Apply sparingly only to themale threads of pipe joints so that pipedope does not block gas flow.

Failure to apply pipe dope as detailedabove can result in severe personalinjury, death or substantial propertydamage.

Use a two-wrench method of tighteninggas piping near the unit and its gas pip-ing connection. Use one wrench to pre-vent the boiler gas line connection fromturning and the second to tighten adja-cent piping. Failure to support the boil-er gas piping connection could damagethe gas line components.

WARNING

WARNING

WARNING

NOTICE

Sediment Trap Min. Length of 3"

Union Fitting Cap

Tee Fitting

External Manual Gas Shut Off Valve (Must Be Within 6' of the Boiler)

Gas Flow

Fig. 15: Recommended Gas Supply Piping

25

Gas PipingNATURAL GASPipe Sizing - Natural GasRefer to Table 1 for schedule 40 metallic pipelength and diameter requirements for naturalgas, based on rated PRESTIGE Excellenceinput (divide by 1,000 to obtain cubic feet perhour).- Table 1 is based on Natural Gas with a spe-

cific gravity of 0.60 and a pressure dropthrough the gas piping of 0.30”w.c..

- For additional gas piping sizing informa-tion, refer to ANSI Z223.1. For Canadianinstallations refer to B149.1 or B149.2.

Natural Gas Supply Pressure Requirements1. Pressure required at the gas valve inlet

supply pressure port:- Maximum 13”w.c. at flow or no flow

conditions to the burner.- Minimum 5”w.c. during flow conditions

to the burner. Must be verified duringstart up and with all other gas appliancesoperating within the building.

2. Install 100% lockup gas pressure regulatorin the gas supply line if inlet pressure canexceed 13”w.c at any time. Adjust the lock-up pressure regulator for 13”w.c maximum.

DO NOT adjust or attempt to measuregas valve outlet pressure. The gas valveis factory-set for the correct outlet pres-sure. This setting is suitable for naturalgas and propane and requires no fieldadjustment. Attempts by the installer toadjust or measure the gas valve outletpressure could result in damage to thevalve, causing potential severe personalinjury, death or substantial propertydamage.

WARNING

Table 1: Gas Piping Sizing - Natural Gas

Length of Pipe inFeet

Capacity of Schedule 40 Metallic Pipe in Cubic Feet of Natural Gas PerHour (based on 0.60 specific gravity, 0.30" w.c. pressure drop)

SCH 40 1/2" 3/4" 1" 1-1/4" 1-1/2"10 132 278 520 1050 160020 92 190 350 730 110030 73 152 285 590 89040 63 130 245 500 76050 56 115 215 440 67075 45 93 175 360 545100 38 79 150 305 460150 31 64 120 250 380

26

Gas Piping

PROPANE GAS

Pipe Sizing - Propane Gas

Prior to start up, ensure the unit is set tofire propane. Check the rating label forthe type of fuel. Check the gas valve forpropane conversion label. If there is aconflict or doubt on the burner set up,remove the gas valve and check for thepropane orifice, see Fig. 16, page 27.Failure to ensure proper burner setupcould result in severe personal injury,death or substantial property damage.

Contact the local propane gas supplier for rec-ommended sizing of piping, tanks and 100%lockup gas regulator.

Propane Gas Supply Pressure Requirements

1. Adjust the propane supply regulator pro-vided by the gas supplier for 13”w.c. max-imum pressure

2. Pressure required at the gas valve inlet sup-ply pressure port:- Maximum 13”w.c. at flow or no flow

conditions to the burner- Minimum 5”w.c. during flow conditions

to the burner. Must be verified duringstart up and with all other gas appliancesoperating within the building.

DO NOT adjust or attempt to measuregas valve outlet pressure. The gas valveis factory-set for the correct outlet pres-sure. This setting is suitable for naturalgas and propane and requires no fieldadjustment. Attempts by the installer toadjust or measure the gas valve outletpressure could result in damage to thevalve, causing potential severe personalinjury, death or substantial propertydamage.

The propane orifice requirements are:PRESTIGE Excellence: 0.204” (5.2 mm)

WARNING

WARNING

NOTICE

27

Gas Piping

Venturi

LP Orifice(if required)Throttle

Screw

Gas ValveGasket

Gas Valve

Offset PressureCover Screw

Inlet GasPressure Port

Fig. 16: Gas Valve / Venturi Assembly - PRESTIGE Excellence

28

Internal WiringSECTION VII - Internal Wiring

ELECTRICAL SHOCK HAZARD. Foryour safety, disconnect electrical powersupply to the unit before servicing ormaking any electrical connections toavoid possible electric shock hazard.Failure to do so can cause severe person-al injury or death.

Prior to servicing, label all wires beforedisconnecting. Wiring errors can causeimproper and dangerous operation.Verify proper wiring and operation afterservicing.

General Requirements- Wiring must be N.E.C Class 1.- If original wiring as supplied with the unit

must be replaced, use only Type T 194ºF[90ºC] wire or equivalent as a minimum.

- The PRESTIGE must be electricallygrounded as required by NationalElectrical Code ANSI/NFPA 70 - latest edi-tion and / or the Canadian Electrical CodePart 1, CSA C22.1, Electrical Code.

Fuse LocationsThe TriMax control module contains 2 internalreplaceable 5A fuses as shown in Figure 18.

Additional fuses are also located on the linevoltage terminals as shown in Fig. 18A andFig. 19.

TriMax Line Voltage Fuses

CAUTION

WARNING

Locationof Fuses

Fig. 18: TriMax Control Module Fuse Location

TriMax Line VoltageFuse Location

Fig. 18A: Fuse Location on the line volt-age Terminals

Fuse Size Terminals Purpose

2.5A 23,24,25 CH2 /System Pump

2.5A 26,27,28 Auxiliary Boiler Pump

2.5A 29,30,31 DHW Pump / Diverter Valve

2.5A 32,33,34 CH1 Pump/Diverter Valve

8.0A 35,36,37 Power Supply

2.5A 38,39,40 Alarm

29

Internal Wiring

Fig. 19: PRESTIGE Excellence Boiler Factory Wiring

30

External WiringSECTION VIII- External WiringInstallation ComplianceAll field wiring made during installation mustcomply with:

- National Electrical Code NFPA 70 andany other national, state, provincial orlocal codes or requirements.

- In Canada, CSA C22.1 Canadian ElectricalCode Part 1, and any other local codes.

ELECTRICAL SHOCK HAZARD.Before making any electrical connec-tions to the PRESTIGE, disconnect elec-trical power supply at the service panel.Failure to comply can cause severe per-sonal injury or death.

The line voltage terminals are located onthe right set of terminals 23 through 40.The low voltage terminals are located onthe left set of terminals 1 through 22.

Line Voltage Connections1. Connect a dedicated 120 VAC/15A service

to the line voltage terminal strip on thewiring panel below the PRESTIGE controlmodule, as shown in Fig. 19, page 29.

2. Route the incoming 120 VAC power wirethrough the provided openings in the bot-tom jacket panel.

3. The unit is provided with a service switchlocated on the front panel, check local coderequirements for compliance.

If local electrical codes or conditionsrequire an additional service switch, theinstaller must provide and install a fuseddisconnect or 15 amp (minimum) serviceswitch.

Circulator & Diverter Valve WiringThe PRESTIGE Excellence contains aprewired Boiler circulator as well as a DiverterValve. The Boiler circulator is enabled for anyCH1, CH2, or DHW call. The Diverter Valvewill direct water flow to the CH SupplyConnection at the bottom of the boiler during aCH1 or CH2 call or to the internal IndirectWater Heater during a DHW call.1. The Boiler circulator is prewired to the line

voltage terminal strip on the wiring panelbelow the PRESTIGE control module, asshown in Fig. 19 on page 29. The Boilercirculator is enabled for any CH1, CH2, orDHW call. This circulators is used to sup-ply heat to the central/space heating loop aswell as the internal Indirect Water Heater.

2. The Diverter Valve is prewired to the linevoltage terminal strip on the wiring panelbelow the PRESTIGE control module, asshown in Fig. 19 on page 29. The DiverterValve will direct water flow to the CHSupply Connection at the bottom of theboiler during a CH1 or CH2 call or to theinternal Indirect Water Heater during aDHW call.

3. Connect the System circulator to the linevoltage terminal strip on the wiring panelbelow the PRESTIGE control module, asshown in Fig. 19 on page 29. The Systemcirculator is enabled during a CH1 or CH2call with the factory default TrimaxSettings. This circulator is typically used tocirculate water in the secondary CH loopwhen zoning with zone valves.

Each circulator/diverter valve output isindividually fused with a 2.5A fuse locat-ed in the terminal strip. Use an isolationrelay if the circulator amp draw exceeds2.5A.

NOTICE

NOTICE

WARNING

NOTICE

31

External WiringAlarm WiringThe alarm contact closes whenever thePrestige is in a soft or hard lockout. Thisdry contact can be connected to an externalmonitoring system or other indicator to alertthe operator that the Prestige is locked out.1. Connect the external monitoring device to

the line voltage terminal strip on the wiringpanel below the PRESTIGE control mod-ule, as shown in Fig. 19 on page 29.

The alarm contact is fused with a 2.5Afuse located in the terminal strip. An iso-lation relay is required if the externalmonitoring device draws more than 2.5A.

Low Voltage Connections

Line and Low Voltage wiring should beseparated to prevent possible electricalnoise on the low voltage circuits. Lineand Low Voltage wiring should use sepa-rate electrical knockouts on the PRES-TIGE cabinet and should remain sepa-rated inside the PRESTIGE.

CH call connections to the PRESTIGErequire a dry contact with no externalvoltage present. Ensure no external volt-age is present on each set of wires beforeconnecting to the PRESTIGE. If externalvoltage is present, the use of an isolationrelay is required to prevent damage to theTrimax controller.

Thermostat Wiring

The Trimax control has two thermostat call inputsfor multiple zone / temperature systems. Thisallows each call to have its own outdoor resetcurve and maximizes the efficiency of the system.

Simultaneous CH1 and CH2 calls willresult in the PRESTIGE operating at thehighest target temperature. The use of amixing device on the lower temperaturezones such as the ACV-Triangle TubeOptima Series SMV Control may berequired to protect the lower tempera-ture zones from damage.

1. Connect the room thermostat or dry contactend switch to the low voltage terminal stripon the wiring panel below the PRESTIGEcontrol module, as shown in Fig. 19 onpage 29.

2. Follow thermostat manufacturer’s instruc-tions for proper installation. Thermostatshould be located on an inside wall awayfrom any heat or cold influences such asdrafts, lights, fireplaces, etc.

3. Set the thermostat anticipator (If applica-ble) as follows:- Set for 0.2 amps when wired directly to

the PRESTIGE.- Set to match the electrical power

requirements of the connected devicewhen wired to zone relays or otherdevices. Refer to the relay manufactur-er’s specifications and the thermostatinstructions for additional informationon anticipator setting.

The use of power stealing thermostatswhich draw their power from the PRES-TIGE can lead to erratic or unpre-dictable operation.

WARNING

NOTICE

NOTICE

NOTICE

NOTICE

32

External WiringOutdoor Sensor Wiring

The Outdoor Reset function and WarmWeather Shutdown (WWSD) features requirethe connection of the included outdoor temper-ature sensor. See page 61 for outdoor sensorinstallation and setup.

Domestic Hot Water WiringAn indirect water heater sensor is prewired tothe low voltage terminal strip on the wiringpanel below the PRESTIGE control module.Additional Boiler Limits

Additional boiler limits (High Limit, LWCO,etc.) can be wired into either the Manual ResetLimit or Auto Reset Limit terminals of thePRESTIGE. These limit connections will pro-vide a “hard” lockout requiring a manual resetof the PRESTIGE or a “soft” lockout in whichthe PRESTIGE will automatically reset whenthe limit resets.

Manual Reset Limit and Auto ResetLimit connections to the PRESTIGErequire a dry contact with no externalvoltage present. Ensure no external volt-age is present on each set of wires beforeconnecting to the PRESTIGE. If exter-nal voltage is present, the use of an isola-tion relay is required to prevent damageto the Trimax controller.

1. Remove the factory installed jumper wireon the Manual Reset or Auto Reset termi-nals that will accept the additional boilerlimit.

2. Connect the additional boiler limit to thelow voltage terminal strip on the wiringpanel below the PRESTIGE control mod-ule, as shown in Fig. 19 on page 29.

External Modulation ControlThe PRESTIGE firing rate can be controlled byan external modulating boiler controller. Seepage 62 for external modulation signal wiringand setup.System Sensor Wiring

An optional system temperature sensor can beplaced on the central heating loop to control thetemperature in the central heating loop insteadof the boiler loop. When connected, the PRES-TIGE will automatically modulate to maintainthe target temperature in the central heatingloop. The boiler supply temperature sensor willcontinue to be used as a high temperature limit.

Locate the system temperature sensorwhere it can accurately measure the sup-ply temperature to the heating system.Inaccurate system temperature readingscould lead to overheating or under heat-ing resulting in property damage.

1. Connect the system temperature sensor tothe low voltage terminal strip on the wiringpanel below the PRESTIGE control mod-ule, as shown in Fig. 19 on page 29.

Cascade WiringThe Trimax control includes the ability to oper-ate up to six boilers together as one without theneed for external controllers. Consult thePRESTIGE Trimax Control Supplement formore information.Modbus WiringThe Trimax control includes the ability to com-municate with building management systems(BMS) through a Modbus interface. Consultthe PRESTIGE Trimax Control Supplementfor more information.

NOTICE

CAUTION

33

External Wiring

Div

erte

r Val

veCH

(1) P

ump

AUX

Fig. 20: Multiple Zone Field Wiring Using Zone Valves

34

External Wiring

Div

erte

r Val

veCH

(1) P

ump

AUX

Fig. 21: Multiple Zone Field Wiring using Zone Circulators

35

External Wiring

Diverter ValveCH (1) Pump

AUXSYS

Diverter ValveCH (1) Pump

AUX

ZC1 ZC2

Fig. 23: Prestige Wiring - Zoning with Zone Circulators

Fig. 24: Prestige Wiring - Zoning with Zone Valves

Note: Reference Fig. 9, page 20 forSystem Piping.

Note: Reference Fig. 10, page 20 forSystem Piping.

36

External Wiring

Diverter ValveCH (1) Pump

AUX

Diverter ValveCH (1) Pump

AUX

Fig. 25: Prestige Wiring - Multiple Zone Valve with Single System/Boiler Circulator

Fig. 26: Prestige Wiring - Single Zone System with Single System/Boiler Circulator

Note: Reference Fig. 11, page 21 forSystem Piping.

Note: Reference Fig. 12, page 21 forSystem Piping.

37

Trimax Operation

SECTION IX- Trimax OperationThe Trimax Boiler Management System is designed to be flexible yet easy to use. Trimax mon-itors and controls the Prestige to provide heat as efficiently as possible. Trimax includes manyadvanced features which previously were not available in the Prestige.• Two central/space heating (CH) call inputs with separate outdoor reset curves.• Domestic Hot Water (DHW) call input with optional priority.• EZ Setup feature allows the installer to quickly customize Trimax for each installation.• Cascade function allows up to six Prestige boilers to operate together in a single heating system.• Modbus interface for integrating with building management systems.

All Trimax features are easy to use through a graphical display where information is presentedeither graphically or in plain English, so code charts are not required. Figure 30 shows a Trimaxdisplay example of the Prestige fired for a domestic hot water demand.

Fig. 30: Trimax User Interface

38

Trimax Operation

Trimax NavigationNavigation is performed through four arrow buttons UP, DOWN, LEFT, RIGHT with a centerOK button for making selections and entering information. The INSTALLER button (the smallround button) provides the installing contractor with full access to all available features afterentering a password. Reference the Trimax Control Supplement for Installer level functions.

Figure 31 – Trimax Navigation Buttons

The Main Menu can be entered from the Home Screen by pressing the OK button. The menusystem utilizes icons to represent each selection. The currently selected menu is displayed as areversed image with a text description shown at the top of the display. Menus can be entered byhighlighting the desired icon and pressing the OK button. The Home Screen icon at the bot-tom of each screen returns to the Home Screen when selected. The Previous Screen icon atthe bottom of each screen returns to the previous screen when selected.

39

Trimax Operation

abc de f bbb b

abc de f bb

abc de

abc de f bbb b

abc de f bb

abc d

abc de f bbb b

abc de f bbabc de

abc de f bbb b

abc de f bb

f bg abc d

Boiler Information

Boiler Information MenuCH/DHW Operation MenuEZ Setup Menu

Main Menu

Home Screen

Heating Enabled

Trimax Menu Structure

40

Trimax Operation

The status line displays the current operating state of the Prestige.See page 41 for a list of all Status Line Messages.

The radiator icon indicates that a central heating call has been received.A small number 1 or 2 indicateswhich CH calls are active.

Circulator icons indicate which circulators are currently powered.

The faucet icon indicates that a domestic hot water call has beenreceived.

The percentage icon indicates that an external modulation call has been received.

This line provides basic information. The user can press the LEFT or RIGHT arrow buttons to view Target, Supply, Return, Domestic, Outdoor and SystemTemperatures.

The Prestige is represented in the center of the Home Screen. Basic operating information such as supply and return temperatures are displayed as well as current burner status. A flame symbol is displayed when the unit is fired. The flame size changes to indicate the current firing rate.

1

2

Home ScreenThe Home Screen presents status information in a very user friendly way so that the currentstate of the boiler can be quickly accessed.

The screen backlight will illuminate when any button is pressed and remain illuminated for fiveminutes. Press the UP or DOWN buttons to turn on the backlight while at the Home Screenwithout making any changes.

The screen contrast can be adjusted at the Home Screen by pressing and holding the OK but-ton then pressing and holding the LEFT arrow along with the OK button. The contrast canthen be increased by pressing the UP button or decreased by pressing the DOWN button whileholding in the OK button and LEFT arrow. All buttons must be released and the procedureperformed again to switch between increasing and decreasing contrast.

41

Trimax OperationStatus Line Messages

Status Line Message Description

Standby Indicates that the Prestige is ready to respond when a demand is received.

CH Demand A central heating call has been received.

DHW Demand A domestic hot water call has been received.

DHW PriorityCentral heating and domestic hot water calls are being received simultane-ously. Domestic hot water call is being satisfied first because it has priorityover central heating calls.

Priority Timeout

Central heating and domestic hot water calls are being received simultane-ously. The domestic hot water priority time limit has been exceeded.Priority will now switch back and forth between central heating and domes-tic hot water calls until one call is satisfied.

External Demand An external modulation call has been received.

Slave Operation The Prestige is a slave in a cascade system.

Manual Operation The burner or circulators have manually been enabled in the Installer Menu.

CH Burner Delay The burner will not fire until the call blocking time has elapsed.

DHW Burner Delay The burner will not fire until the call blocking time has elapsed.

CH Setpoint Reached

The burner is not fired because the supply/system water temperatureexceeds the setpoint. The central heating circulator continues to operateand the burner will fire again once the supply/system water temperaturedrops below the setpoint.

DHW Setpoint Reached

The burner is not fired because the supply/system water temperatureexceeds the setpoint. The domestic circulator continues to operate and theburner will fire again once the supply/system water temperature dropsbelow the setpoint.

CH Post Pump The central heating circulator is running to remove heat from the Prestige atthe completion of a call.

DHW Post Pump The domestic hot water circulator is running to remove heat from thePrestige at the completion of a call.

Freeze ProtectionThe burner is fired because the freeze protection feature has been activated.Freeze protection will end once the supply/system water temperature israised to 60ºF [16ºC].

Boiler ProtectionThe burner firing rate is being reduced because of an excessive differencebetween the boiler supply and return temperatures. The firing rate willbegin increasing once the temperature difference is less than 45ºF [25ºC].

Lockout Description The lockout which currently has the Prestige shut down is displayed.

42

Trimax Operation

Press OK Button

The EZ Setup menu canbe accessed by selectingthis icon.

The CH / DHW Operation Menu can be accessed by selecting this icon.

Currently selected menu

The Boiler InformationMenu can be accessed by selecting this icon.

The Home Screen icon at the bottom of each screen returns to the Home Screen when selected.

The Previous Screen icon at thebottom of each screen returns to the previous screen when selected.

Main MenuThe Main Menu can be entered from the Home Screen by pressing the OK button. The menusystem utilizes icons to represent each selection. The currently selected menu is displayedas a reversed image with a text description shown at the top of the display. Menus can beentered by highlighting the desired icon and pressing the OK button.

43

Trimax Operation

EZ Setup Navigation: Home Screen>Main Menu>EZ SetupThe EZ Setup menus provide a simple way to quickly customize theTrimax for each installation. EZ Setup prompts the user to make selectionswhich allows the Prestige to be setup very quickly without searchingthrough long lists of settings and manually making adjustments.

Heating EZ Setup Navigation: Home Screen>Main Menu>EZ Setup>Heating EZ SetupHeating EZ Setup allows the installer to quickly customize the central heat-ing settings for the application.

Select CH Demand Default: Switch & Outdoor ResetSelect CH Demand prompts the installer to select how a CH Demand is gen-erated. Press the UP or DOWN buttons to select the CH Demand type thenpress the OK button to store the setting. The Select CH Demand options are:• Switch & Outdoor Reset – This option is only displayed when the

outdoor temperature sensor is connected. A central heating call from athermostat or zone panel will enable the Prestige and the setpoint willvary with the outdoor temperature for central heating calls.

• Switch & Setpoint - This option is only displayed when the outdoortemperature sensor is not connected. A central heating call from a ther-mostat or zone panel will enable the Prestige and the setpoint will befixed for central heating calls

• Constant & Outdoor Reset - This option is only displayed when theoutdoor temperature sensor is connected. The Prestige will maintain set-point without an external call from a thermostat or zone panel. The set-point will vary with the outdoor temperature for central heating calls.

• Constant & Setpoint - The Prestige will maintain setpoint without anexternal call from a thermostat or zone panel. The setpoint will be fixedfor central heating calls.

• 0-10V Modulation Signal – This option allows the Prestige firing rateto be controlled by an external control system.

CH1 Setpoint Default: 180°F [82°C]CH1 Setpoint prompts the installer to enter the fixed setpoint for a CH1heating call when a Setpoint option is chosen in Select CH Demand. Pressthe LEFT or RIGHT buttons to adjust the CH1 Setpoint then press theOK button to store the setting.CH2 Setpoint Default: 140°F [60°C]CH2 Setpoint prompts the installer to enter the fixed setpoint for a CH2heating call when a Setpoint option is chosen in Select CH Demand. Pressthe LEFT or RIGHT buttons to adjust the CH2 Setpoint then press theOK button to store the setting.

Select CH Demand

Switch & Outdoor ResetConstant & Outdoor Reset

Constant & Setpoint0-10V Modulation Signal

Switch & Outdoor Reset

Select CH Demand

Switch & SetpointConstant & Setpoint

0-10V Modulation Signal

OR

Switch & Setpoint

68ºF 188ºF

180ºF

CH1 Setpoint

44

Trimax OperationSelect CH1 Reset Curve Default: Finned Tube BaseboardSelect CH1 Reset Curve prompts the installer to select an outdoor reset curvefor a CH1 heating call when an Outdoor Reset option is chosen in Select CHDemand. Outdoor reset curve presets are available to cover most applica-tions. The outdoor reset curve can also be adjusted to any desired settings inthe Installer Menu. Press the UP or DOWN buttons to select the outdoorreset curve appropriate for the type of heating system then press the OK but-ton to store the setting.

Select CH2 Reset Curve Default: Low Mass RadiantSelect CH2 Reset Curve prompts the installer to select an outdoor reset curvefor a CH2 heating call when an Outdoor Reset option is chosen in Select CHDemand. Outdoor reset curve presets are available to cover most applica-tions. The outdoor reset curve can also be adjusted to any desired settings inthe Installer Menu. Press the UP or DOWN buttons to select the outdoorreset curve appropriate for the type of heating system then press the OK but-ton to store the setting.

Set Warm Weather Shutdown Temperature Default: OFFWarm Weather Shutdown prompts the installer to enter an optional outdoortemperature at which to disable the central heating function and any circu-lators placed into constant circulation with the pump constant circulationsetting. The Prestige will continue to respond to a domestic hot water callor a 0-10V Modulation Signal when the outdoor temperature exceeds theWarm Weather Shutdown Temperature setting. Press the LEFT orRIGHT buttons to adjust the Warm Weather Shutdown Temperature thenpress the OK button to store the setting. The Warm Weather Shutdownicon is displayed on the home screen when the outdoor temperaturereaches the Warm Weather Shutdown Temperature.

180ºF

120ºF

64ºF 0ºF

Current Settings

Table 3: Outdoor Reset Preset Selections

Preset Minimum Setpoint Maximum Setpoint

Low Mass Radiant 80ºF [27ºC] 140ºF [60ºC]

High Mass Radiant 80ºF [27ºC] 120ºF [49ºC]

Cast Iron Baseboard 100ºF [38ºC] 170ºF [77ºC]

Finned Tube Baseboard 120ºF [49ºC] 180ºF [82ºC]

Radiators 120ºF [49ºC] 170ºF [77ºC]

Fan Coil 140ºF [60ºC] 180ºF [82ºC]

Off 78ºF

Off

Warm Weather Shutdown

45

Trimax Operation

Navigation: Home Screen>Main Menu>EZ Setup>DHW EZ SetupDomestic Hot Water EZ Setup allows the installer to quickly customize thedomestic hot water settings for the application.

Select DHW Demand Default: SensorSelect DHW Demand prompts the installer to select the type of device whichwill generate a DHW call. Press the UP or DOWN buttons to select theDHW Demand type then press the OK button to store the setting. The SelectDHW Demand options are:• Switch – A domestic hot water call from an aquastat or dry contact

switch will enable the Prestige with a fixed setpoint for a domestic hotwater call.

• Sensor – The Prestige Excellence utilizes an Indirect Water HeaterSensor. The Prestige will monitor the DHW storage temperature andgenerate a domestic hot water call when the temperature drops belowthe DHW Storage Setpoint by 6ºF [3ºC].

DHW Storage Setpoint Default: 140°F [60°C]DHW Storage Setpoint prompts the installer to enter the domestic hot waterstorage setpoint temperature when the Sensor option is chosen in SelectDHW Demand. Press the LEFT or RIGHT buttons to adjust the DHWStorage Setpoint then press the OK button to store the setting.

The Boiler DHW Setpoint will automatically be set 46°F [25°C]higher than the DHW Storage Setpoint setting.

DHW Priority Timeout Default: OffDHW Priority Timeout prompts the installer to enter an optional time limitthat a domestic hot water call has priority over a central heating call. Pressthe LEFT or RIGHT buttons to adjust the DHW Priority Timeout then pressthe OK button to store the setting.

NOTICE

Domestic Hot Water EZ Setup

Select DHW Demand

SwitchSensorSensor

68ºF 150ºF

140ºF

DHW Storage Setpoint

Off 120 min.

Off

DHW Priority Timeout

46

Trimax Operation

Navigation: Home Screen>Main Menu>EZ Setup>EZ Setup ResetEZ Setup Reset allows the installer to reset all EZ Setup settings back tothe original factory defaults. Follow the on screen instructions to reset allEZ Setup settings back to the original factory defaults.

The EZ Setup Reset function will set Select DHW Demand toSwitch. Use Domestic Hot Water EZ Setup to change back to a sen-sor demand.

Navigation: Home Screen>Main Menu>EZ Setup>Display EZ SetupDisplay EZ Setup allows the installer to select the type of temperatureunits displayed as well as the language used for all text. Press the UP orDOWN buttons to select then press the OK button to store the setting.

NOTICE

EZ Setup Reset

EZ Setup Reset

Press OK buttonto restore factory settings.

Any other buttonto keep current settings.

Display EZ Setup

Select Units

FahrenheitCelsius

Fahrenheit

47

Trimax Operation

CH/DHW Operation

Heating EnabledNavigation: Home Screen>Main Menu>CH / DHW OperationCH / DHW Operation provides a simple way to disable either the centralheating or domestic hot water functions of the Prestige. Operation can beenabled and disabled by selecting the central heating or domestic hot watericon then pressing the OK button to toggle between enabled and disabled.An icon with an X through it indicates that function has been disabled. Thedisabled icon is also displayed on the home screen when a function hasbeen disabled.

Navigation: Home Screen>Main Menu>Boiler Information>BoilerInformationBoiler Information provides real time operating information of thePrestige. Each line contains an information item followed by its currentvalue. Six information items are displayed on the screen at one time. Pressthe UP or DOWN buttons to scroll through additional information items.See page 48 for a list of all information items.

Boiler Information LoggingSome information items include a logging function which records one sam-ple every 12 minutes to produce a graph of the last 24 hours. Select the infor-mation item in Boiler Information then press the OK button to view itsgraph. The following items have a logging function:

• Boiler Firing Rate• Flame Ionization Current• Boiler Setpoint• Boiler Supply Temperature• Boiler Return Temperature• Boiler Flue Temperature• Outdoor Temperature• DHW Storage Temperature• External Modulation Signal

Boiler Information

Boiler Information

Boiler StatusHeating CallDHW CallBoiler Firing RateFlame Ionization CurrentBoiler Setpoint

StandbyNoNo__

OuA__

Boiler Status Standby

194

68

-24.00 -16.00 -8.00 0.00

Boiler Setpoint

48

Trimax Operation

Information Item Description

Boiler Status Displays the current operating state of the Prestige. This is the same asthe status line on the home screen.

Heating Call Displays if a central heating call is present.

DHW Call Displays if a domestic hot water call is present

Boiler Firing Rate Displays the current firing rate of the Prestige.

Flame Ionization Current Displays the current flame ionization current from the ignitor.

Boiler Setpoint Displays the current setpoint of the Prestige.

Boiler Supply Temperature Displays the current supply temperature of the Prestige.

Boiler Return Temperature Displays the current return temperature of the Prestige.

Boiler Flue Temperature Displays the current flue temperature of the Prestige.

Outdoor Temperature Displays the current outdoor temperature.

DHW Storage Temperature Displays the current DHW storage temperature.

External Modulation Signal Displays the current external modulation signal being received from anexternal controller.

CH Ignitions Displays the number of central heating ignitions since the unit wasinstalled. This counter increases in increments of twenty.

CH Runtime Displays the number of hours the Prestige has run for a central heatingcall since the unit was installed.

DHW Ignitions Displays the number of domestic hot water ignitions since the unit wasinstalled. This counter increases in increments of twenty.

DHW Runtime Displays the number of hours the Prestige has run for a domestic hot watercall since the unit was installed.

Information Items

49

Trimax Operation

Navigation: Home Screen>Main Menu>Boiler Information>LockoutHistoryLockout History records the last eight lockouts. Each line contains a lock-out description followed by how long ago the lockout occurred. Six lock-outs are displayed on the screen at one time. Press the UP or DOWN but-tons to scroll through additional lockouts. See pages 51 & 52 for a list oflockouts and descriptions.

Lockout DetailsSome information items are recorded at the time of a lockout to aid in diag-nosing the cause of the lockout. Select the lockout description in LockoutHistory then press the OK button to view the recorded information. Press theUP or DOWN buttons to scroll through the recorded information. The fol-lowing information items are recorded at the time of a lockout:

• Boiler Status• Heating Call• Domestic Call• Boiler Firing Rate• Flame Ionization Current• Boiler Setpoint• Boiler Supply Temperature• Boiler Return Temperature• Boiler Flue Temperature• Outdoor Temperature• System Temperature

Lockout History Lockout History

1: Low water2: No error3: No error4: No error5: No error6: No error

5h ago25h ago25h ago25h ago25h ago25h ago

1: Low water 5h ago

Lockout DetailsLow Water

Boiler StatusHeating CallDHW CallBoiler Firing RateFlame ionization Current

StandbyNoNo__

OuA

Boiler Status Standby

abc de f bbb b

abc de f bb

abc de

abc de f bbb b

abc de f bb

abc d

abc de f bbb b

abc de f bbabc de

abc de f bbb b

abc de f bb

f bg abc d

50

Trimax Operation

Press any ARROW Button

The status line now displays the lockout

The lockout message is displayed at the top of the screen

The lower right cornerdisplays the lockoutreference code.

The second sentence gives a possible cure for the lockout.

The first sentence givesa description of the lockout.

The third sentence tells how to reset the lockout.

Press any ARROW buttonto return to the Home Screen whilelocked out.The main menu can thenbe entered from the Home Screen to help diagnose the problem. Selectthe Home Screen icon at the bottomof any menu screen to return to the Lockout Screen.

Water level has fallen below an acceptable operating

level. Increase pressure to normal range. Boiler will automatically reset once

water level returns to normal

Low Water

If problem persists, call for service

E37

--

Lockout ScreenThe Lockout Screen replaces the Home Screen if a lockout occurs. The screen backlight willalso illuminate constantly while the Prestige is locked out. Pressing any arrow button willreturn to the Home Screen so that additional troubleshooting can be performed. See pages 51and 52 for a list of lockouts and descriptions.

51

Trimax Operation

Manual Reset Hard Lockouts

Code Lockout Message Description

E1 Failed Ignition The burner failed to light after 5 ignition attempts.

E2 False Flame A flame is being detected prior to ignition.

E3 High Boiler Temperature Boiler temperature has reached 210°F [99ºC]

E5 Blower Speed Blower is not at correct speed or speed signal is not being receivedby control module.

E8 Flame Circuit Error Flame circuit test failed.

E9 Gas Valve Circuit Error Gas valve circuit test failed.

E13 Reset Limit Reached Resets are limited to 5 every 15 minutes.

E15 Sensor Drift Supply or return sensor reading has drifted.

E16 Supply Sensor Stuck Supply sensor reading is not changing.

E17 Return Sensor Stuck Return sensor reading is not changing.

E18 Sensor Failure Supply or return sensor reading changed very rapidly.

E21 Internal Control Fault A / D conversion error.

E30 Supply Sensor Shorted A short circuit has been detected in the boiler supply temperaturesensor circuit.

E31 Supply Sensor Open An open circuit has been detected in the boiler supply temperaturesensor circuit.

E43 Return Sensor Shorted A short circuit has been detected in the boiler return temperaturesensor circuit.

E44 Return Sensor Open An open circuit has been detected in the boiler return temperaturesensor circuit.

E80 Return > Supply Return temperature is higher than supply temperature.

E87 External Limit Open An external manual reset limit has opened

52

Trimax Operation

Automatic Reset Soft LockoutsCode Lockout Message Description

E7 High Flue Temperature Flue temperature exceeds high limit.

E12 Internal Control Fault EEPROM misconfiguration

E25 Internal Control Fault CRC check error.

E32 DHW Sensor Shorted A short circuit has been detected in the DHW temperature sensor circuit.

E33 DHW Sensor Open An open circuit has been detected in the DHW temperature sensor circuit.

E34 Low Voltage Line voltage has fallen below an acceptable operating level.

E37 Low Water Water level has fallen below an acceptable operating level.

E45 Flue Sensor Shorted A short circuit has been detected in the boiler flue temperature sensorcircuit.

E46 Flue Sensor Open An open circuit has been detected in the boiler flue temperature sensorcircuit.

E76 External Limit Open An external automatic reset boiler limit has opened.

E81 Sensor Drift Supply and return temperatures are not equal.

E89 Incorrect Setting A parameter setting is in conflict with another setting.

E90 Firmware Mismatch Control module and display firmware versions are incompatible.

E91 System Sensor Shorted A short circuit has been detected in the system temperature sensor circuit.

E92 System Sensor Open An open circuit has been detected in the system temperature sensor circuit.

E93 Outdoor Sensor Shorted A short circuit has been detected in the outdoor temperature sensor circuit.

E94 Internal Display Fault Display memory error.

E95 Supply Sensor Error Supply sensor reading is invalid.

E96 Outdoor Sensor Open An open circuit has been detected in the outdoor temperature sensorcircuit.

E97 Cascade Mismatch Cascade configuration has changed.

E98 Cascade Bus Error Communication with other boilers has been lost.

E99 Controller Bus Error Communication between boiler display and control module has beenlost.

53

Start-Up Preparation

SECTION X - Start-Up Preparation

Requirements below must be met forwarranty coverage of Prestige heatexchangers. A thorough cleaning of anyexisting system, using approved heatingsystem cleaning agents is required priorto installation of the Prestige boiler.System should be treated with anapproved inhibitor after filling for longterm protection.

Check Boiler System Fluid Chemistry

Do not use petroleum-based cleaning orsealing compounds in the boiler system.Damage to seals and gaskets in the sys-tem components could occur, resulting insubstantial property damage.

System fluid including additives must bepractically non-toxic, having a toxicityrating or Class of 1, as listed in ClinicalToxicology of Commercial Products.

Boiler Fluid pH Level 6.0 to 8.0Maintain the boiler fluid pH between 6.0 and8.0. Check using litmus paper or contact a watertreatment company for a chemical analysis.

If the pH does not meet this requirement, donot operate the PRESTIGE Excellence or leavethe unit filled until the condition is corrected.

Boiler Fluid Hardness Less Than 7 GrainsFor areas with unusually hard water (hardnessabove 7 grains) consult a water treatmentcompany.

Chlorinated WaterDo not use the PRESTIGE Excellence to heat aswimming pool or spa directly.

Maintain the chlorine level of the water at lev-els considered safe for drinking.

Flush Boiler to Remove SedimentThe installer must flush the boiler system toremove any sediment to allow proper operationof the PRESTIGE Excellence .

Flush the systems until the water runs cleanand is free of sediment.

For zoned systems, each zone should beflushed through a purge valve. Purge valvesand isolation valves should be installed on eachzone to allow proper flushing of the system.

Cleaning of Old Boiler/System: • Drain the existing system.• Fill system with fresh water and cleaner,

place existing boiler in operation and r unall zones.

• Follow manufacturer’s instructions forproper cleaner concentration and propercleaning time.

• Thoroughly drain and flush system withfresh water after cleaning.

• Install new boiler, fill system with freshwater and proper amount of inhibitor.

• Verify pH and inhibitor level per inhibitormanufacturer’s specs; add inhibitor ifnecessary.

Cleaning of New Boiler/System: • Install new boiler and flush system with

cleaner water to remove any debris.• Fill system with fresh water and proper

amount of inhibitor.

NOTICE

WARNING

NOTICE

54

Start-Up Preparation• Verify pH and inhibitor level per inhibitor

manufacturer’s specs; add inhibitor ifnecessary.

Check and Test AntifreezeFor boiler systems containing antifreeze solu-tions, follow the antifreeze manufacturer’sinstructions in verifying the inhibitor level andto ensure the fluid characteristics are withinspecification requirements.

Due to the degradation of inhibitors over time,antifreeze fluids must be periodically replaced.Refer to the manufacturer of the antifreeze foradditional instructions.

Use of Antifreeze in the Boiler System

NEVER use automotive or ethylene gly-col antifreeze or undiluted antifreeze inthe primary system as freeze protection.This can cause severe personal injury,death or substantial property damage ifignored.

Determine the antifreeze fluid quantity usingthe system water content volume and followingthe antifreeze manufacturer instructions.

The water volume of the PRESTIGE Excellenceis approximately 5 gallons [19 L]. Remember toinclude the volume of the expansion tank.

Check with local codes requirements for theinstallation of backflow preventers or actualdisconnection from the boiler’s cold water fillor make up water supply line.

Massachusetts Code requires the installa-tion of a backflow preventer if antifreezeis used.

Ensure the concentration of antifreeze to waterdoes not exceed a 50/50 ratio.

System fluid, including additives, must bepractically non-toxic, having a toxicityrating or Class of 1, as listed in ClinicalToxicology of Commercial Products.

Ensure the domestic inner tank of thePRESTIGE Excellence water heater isproperly filled and pressurized prior tofilling the boiler system. Reference thePRESTIGE Excellence water heater forproper guidelines on filling the innertank. Failure to comply could result indamage of the inner tank.

Filling the Boiler System1. Close the boiler drain valve located on the

bottom of the unit and any manual or auto-matic air vent in the system.

2. Open all system isolation valves.3. Fill the boiler system to correct system

pressure. Correct pressure will vary witheach application.

Typical residential system fill pressure is12 psi. System pressure will increasewhen system temperature increases.Operating pressure of the system shouldnever exceed 25 psi.

4. Purge air and sediment in each zone of theboiler system through the purge valve. Openair vents to allow air to be purged in the zones.

5. Once the system is completely filled andpurged of all air and sediment, check thesystem pressure and check/repair any leaks.

For proper operation of the air ventsensure vent cap are tightened at alltimes. The air vents are provided withhydroscopic cap that prevents leakage ofwater due to internal membrane.

NOTICE

CAUTION

WARNING

NOTICE

NOTICE

NOTICE

55

Start-Up Preparation

Unrepaired system leaks will cause con-tinual makeup water to be added to theboiler. Continual makeup water willcause mineral buildup within the heatexchanger, reducing the heat transfer,causing possible heat buildup and even-tual heat exchanger failure.

Check Low Water Cut-Off Device- The PRESTIGE Excellence is provided with

a factory installed LWCO device that mea-sures system pressure of more than 10 psi.

- Remove the front jacket panel and check forcontinuity across the low water cut-offdevice wire terminals. The contacts shouldbe closed when system pressure is greaterthan 10 psi. See item 6, on Fig. 34 page 74for location of the LWCO.

Check For Gas Leaks

Prior to start-up and during initial opera-tion, smell near the floor and around theunit for gas odorant or any unusual odor.Do not proceed with the start-up if thereis any indication of a gas leak. Any leaksfound must be repaired immediately.

Propane installations only - The propanesupplier mixes an odorant with thepropane to make its presence detectable.In some cases the odorant can fade andthe gas may no longer have an odor.Prior to start-up of the unit and periodi-cally after start-up have the propanesupplier check and verify the odorantlevel.

Check Thermostat Circuit- Disconnect the external thermostat wires

from the low voltage terminal strip.

- Connect a voltmeter across the wire ends ofthe external thermostat wiring.

- Close each thermostat, zone valve andrelay in the external circuit one zone at atime and check the voltage reading acrossthe wire ends.

- There should NEVER be voltage measuredat the wire ends.

- If voltage is measured at the panel under anycondition, check and correct the externalwiring.

In systems using 3-wire zone valves,backfeed of voltage to the unit is a com-mon problem. Use an isolation relay toprevent voltage from the external circuitentering the PRESTIGE Excellence con-trol panel.- Reconnect the external thermostat

wires to the low voltage terminal strip.

Inspection of Condensate Drain Assembly1. Inspect and ensure the Condensate Drain

Assembly is properly installed as describedon page 22 and shown in Fig. 14 on page 23.

2. Remove the plug from the CondensateDrain Assembly and fill with fresh water.

The condensate drain assembly must befilled with water when the PRESTIGEExcellence is in operation. The conden-sate drain assembly prevents flue gasemissions from entering the condensateline. Failure to ensure trap is filled withwater could result in severe personalinjury or death.

3. Re-Install plug in condensate drain assem-bly.

NOTICE

NOTICE

WARNING

WARNING

WARNING

56

Start-Up Procedures

SECTION XI - Start-Up ProceduresFinal Checks Before Start-Upc Read page 37 through 52 regarding the

operation of the Trimax BoilerManagement System.

c Verify the PRESTIGE Excellence and theboiler system are full of water and all sys-tem components are correctly set for oper-ation, including the minimum flow ratethrough the boiler, see page 81.

c Verify Start-up Preparation items outlined onpages 53 thru 55 have been completed.

c Verify all electrical connections are correctand securely fastened.

c Inspect vent and combustion air piping forsigns of deterioration from corrosion, physicaldamage or sagging. Verify combustion airand vent piping are intact and correctlyinstalled and supported. Reference the PRES-TIGE Vent Supplement.

c Verify burner configuration - Propane only.- Check for proper labeling on the gasvalve and the rating label for propaneconfiguration.- If there is doubt on the burner configura-tion, remove the gas valve and check forproper propane gas orifice size: 0.204”(5.2 mm). Refer to Fig. 16, page 27 forlocation of the propane gas orifice.

c Ensure the vent Condensate DrainAssembly is filled with water.

PRESTIGE Excellence Start-Up1. Press the ON-OFF button located on the

front control panel to the OFF position. TurnON the electrical supply/service to the unit.

2. Read and follow the Operating Instructionsoutlined on page 60.

If PRESTIGE Excellence Does Not StartCorrectly1. Check for loose electrical connections,

blown fuses, (on control module and in ter-minals) or an open service switch.

2. Verify CH and DHW operation is enabled.A radiator or faucet icon with an X throughit indicates that function is disabled.

3. Check continuity across the LWCO devicefor a closed circuit. See item 6 on Fig. 34,page 74.

4. Is an external limit control (if applicable)open? Ensure the external limit is reset tothe closed position.

5. Are the gas supply valves open at the unitand meter?

6. Is incoming gas supply pressure at the unitmore than 5”w.c. and less than 13” w.c. fornatural or propane with all gas appliancesON or OFF.

7. Are the heating thermostats set above roomtemperature?

If none of these conditions correct the problem,refer to the PRESTIGE Excellence Trouble-Shooting Guide or contact ACV-Triangle TubeTechnical Support.

Check the PRESTIGE Excellence and Systemc Check Boiler Piping.

Check Boiler system piping and com-ponents for leaks. If found, shut downthe unit and repair immediately.Purge any remaining air from the systempiping. Air in the system piping willinterfere with circulation creating heatdistribution problems and system noise.

57

Start-Up Proceduresc Check Vent Piping and Combustion Air

Piping.Check for gas-tight seal at every con-nection and seam of the venting andcombustion air piping.

Venting system must be sealed gas-tightto prevent flue gas spillage and potentialcarbon monoxide emissions, which willresult in severe personal injury or death.

c Check Gas PipingCheck around the unit for gas odor fol-lowing the procedure outlined in thismanual on Page 55.

If any gas leaks are found or suspected,shut the unit down immediately. Use agas detection device or bubble test tolocate the source of the gas leak andrepair at once. Do not operate the unituntil the leak is corrected. Failure tocomply with this procedure could resultin severe personal injury, death or sub-stantial property damage.

c Verify Flame Pattern and Combustion1. Check the flame pattern through the

inspection port of the heat exchanger.The flame should be blue and stable.The flame should be the length of theburner head openings.

The combustion testing and adjustmentsmust be performed by a qualifiedinstaller, service agency or the gas suppli-er. All combustion measurements must beperformed with calibrated equipment toensure proper reading and accuracy.

2. Test for CO2 or O2 and for CO duringhigh firing rate. The combustion read-ings should be within the range listed inTable 4. The CO level should notexceed 100 ppm when combustion iscorrect. Perform the following proce-dure to manually place the burner intohigh fire.

a. Press the round INSTALLER button.Reference Fig. 31, page 38.

b. Enter the installer access code “054” byusing the LEFT and RIGHT buttons toselect a digit and the UP and DOWNbuttons to change the digit. Press theOK button to enter the access code.

c. Press the RIGHT button to highlightthe Manual Operation icon thenpress the OK button.

d. Press the OK button while the FANicon is highlighted to manually fire theburner and power the CH circulator.

An adequate CH load must be present todissipate the heat generated during thecombustion test. If an adequate CH loadis not available, an indirect water heatercan be used to dissipate the heat by cre-ating a DHW call which will enable theDHW circulator.

WARNING

WARNING

WARNING

NOTICE

Manual Operation

Released

O!

O!

O!

CHCH1

FAN

DHW

SYSCH2

58

Start-Up Procedurese. Press the LEFT and RIGHT buttons toadjust the firing rate from 1% to 100%.Hold down the LEFT or RIGHT but-ton to rapidly increase or decrease thefiring rate.

f. Press the OK button while the FANicon is highlighted to shutdown theburner.

g. Cycle power to the Prestige once com-bustion testing is complete to return tonormal operation.

The combustion levels should be mea-sured at high firing rate. If the combus-tion levels are not within the range givenin Table 4 for the firing rate, shut theboiler down and contact ACV-TriangleTube Technical Support. Failure to com-ply with this requirement could result insevere personal injury, death or substan-tial property damage.

If the combustion levels during high fire(100%) is outside the recommended combus-tion settings adjust the THROTTLE SCREW(see Fig. 16. page 27) as follows:

Counter-clockwise adjustment of the throt-tle screw at High Fire:

O2 decreases and CO2 increases

Clockwise adjustment of the throttle screwat High Fire:

O2 increases and CO2 decreases

3. Once the combustion level is set at high fire(100%), manually place the boiler into lowfire (1%) mode by pressing the LEFT but-ton to adjust firing rate down.

4. If the CO2 combustion level during lowfire (1%) is not within +/- 0.2 of the com-bustion level measured at high fire, adjustthe plastic OFFSET SCREW under thecover screw on the top of the gas valve (seeFig. 16, page 27).

Counter-clockwise adjustment of the OFF-SET SCREW at Low Fire:

O2 increases and CO2 decreases

Clockwise adjustment of the OFFSETSCREW at Low Fire:

O2 decreases and CO2 increasesc Measure Input - Natural Gas Only1. Ensure the boiler is firing at maximum firing

rate. To manually place the boiler into highfire mode, reference page 57.

2. Operate the unit for approximately 10minutes.

3. Turn off all gas appliances within the build-ing, except the PRESTIGE Excellence.

4. At the gas meter, record the time requiredto use one cubic foot of gas.

5. Calculate Natural gas input using the fol-lowing equation:3600 x 1000 / number of second recordedfor one cubic foot of gas = BTU/H.

6. The BTU/H calculated should approximatethe input rating listed on the unit.

WARNING

Table 4: Recommended Combustion LevelsNatural Gas Propane

O2 Min. 2.30% 2.70%

O2 Max. 5.30% 4.70%

CO2 Min. 8.80% 10.70%

CO2 Max. 10.50% 12.00%

CO Max. 100 ppm 100 ppm

59

Start-Up Procedures

c Test High Temperature LimitThe high temperature limit can be temporarilylowered from 210ºF [99ºC] to 102ºF [39ºC] fortesting.1. Press the round INSTALLER button.

Reference Fig. 31, page 38.2. Enter the installer access code “054” by

using LEFT and RIGHT buttons to selecta digit and the UP and DOWN buttons tochange the digit. Press the OK button toenter the access code.

3. Press the OK button while CH & DHWSettings icon is highlighted.

4. Press the DOWN button to highlight theBoiler Settings icon then press the OKbutton.

5. Press the DOWN button to highlightLockout Temperature then press the OKbutton.

6. Press the UP button to highlight 102ºF[39ºC] then press the OK button.

7. Press the DOWN button twice to highlightthe Home Screen icon then press theOK button.

8. Initiate a CH or DHW call and confirm thata High Boiler Temperature lockout occursonce the supply temperature reaches 102ºF[39ºC].

9. Press any ARROW button to return to theHome Screen.

10. Press the round INSTALLER button.11. Press the OK button while the CH & DHW

Settings icon is highlighted.12. Press the DOWN button to highlight the

Boiler Settings icon then press the OKbutton.

13. Press the DOWN button to highlightLockout Temperature, then press the OKbutton.

14. Press the DOWN button to highlight 210ºF[99ºC] then press the OK button.

15. Press the DOWN button twice to highlightthe Home Screen icon then press theOK button.

16. Press the OK button to reset the lockoutand return the unit to service.

60

Start-Up Procedures

WARNING

FOR YOUR SAFETY READ BEFORE LIGHTING

OPERATING INSTRUCTIONS

TO TURN OFF GAS TO APPLIANCE

1. STOP! Read the safety information above. Thisappliance is equipped with an ignition devicewhich automatically lights the burner. DO NOTtry to light the burner by hand.

2. Set room thermostat(s) to lowest setting. Turn theexternal manual gas valve handle clockwise

“CLOSE” (valve handle shall be per-pendicular to gas piping).

3. Turn the service switch on the PRESTIGE con-trol panel OFF.

4. Remove the front jacket panel on the unit.5. Turn the external manual gas valve handle

counter clockwise to “OPEN” gas sup-ply (valve handle shall be parallel to gas piping).

6. Wait five (5) minutes to clear out any gas. If youthen smell gas in the jacket enclosure or aroundthe unit, STOP! Follow “B” in the safety infor-mation above. If you don’t smell gas, go to thenext step.

7. Turn the service switch on the PRESTIGE con-trol panel “ON”.

8. Set room thermostat(s) to desired setting(s).

9. The PRESTIGE control panel display will showthe current operating status on the Status Line atthe bottom of the screen. “Standby” means there isno call for heat (all thermostats are satisfied). “CHDemand” indicates a space heating call has beenreceived. “DHW Demand” indicates a domestichot water call has been received. A flame icon willbe displayed when the unit is fired.

10. If the unit will not operate with a call for heat and thesystem piping is not hot, follow the instructions “ToTurn Off Gas to Appliance”, below and call yourservice technician or gas supplier.

11. Replace the front jacket panel. Make sure the panel isseated firmly in place and all mounting screws aretightened.

If you do not follow these instructions exactly, a fire or explosion mayresult causing property damage, personal injury or loss of life.

1. Set the room thermostat to lowest setting.

2. Turn the service switch on the PRESTIGE con-trol panel to “OFF”

3. Turn the external manual gas valve handle clock-wise to “CLOSE”.

A. This appliance does not have a pilot. It isequipped with an ignition device which automat-ically lights the burner. DO NOT try to light theburner by hand.

B. BEFORE OPERATING, smell all around theappliance area for gas. Be sure to smell next tothe floor because some gas is heavier than air andwill settle on the floor.WHAT TO DO IF YOU SMELL GAS• Do not try to light any appliance.

• Do not touch any electric switch; do not useany phone in your building

• Immediately call your gas supplier from aneighbor’s phone. Follow the gas supplier’sinstructions.

• If you cannot reach your gas supplier, call thefire department.

C. Use only your hand to turn the external manual gasvalve. Never use tools. If the valve will not turn byhand, don’t try to repair it; call a qualified servicetechnician. Force or attempted repair may result ina fire or explosion.

D. Do not use this appliance if any part has beenunder water. Immediately call a qualified servicetechnician to inspect the appliance and to replaceany part of the control system and any gas controlwhich has been under water.

61

Outdoor Reset Control

SECTION XII - Outdoor Reset ControlThe use of the outdoor reset function isrequired to optimize boiler efficiency, seenotice below. If the outdoor sensor is notinstalled before turning on the boiler, anOutdoor Sensor Open error (E96) will be dis-played. The error will not prevent the boilerfrom operating. The error will automaticallyreset once the outdoor sensor is installed or ifthe outdoor reset function is disabled.Reference TriMax Operation - EZ Setup sec-tion for information on disabling the outdoorreset function. The outdoor reset function canonly be disabled if the boiler installation meetsone of the exceptions listed in the notice.

Mounting the Outdoor Sensor1. The exterior wall selected for mounting the

outdoor sensor should represent the heatload of the building. Typically a northernor northeastern wall will suit most build-ings. A southern facing wall for thosebuildings, which may have large glasswalls or windows on the southern face.

2. Ensure the outdoor sensor is shielded fromdirect sunlight or the effects of heat or coldfrom other sources (exhaust fans, appliancevents...) to prevent false temperature sensing.

3. Mount the outdoor sensor at an elevationon the exterior wall to prevent accidentaldamage or tampering.

4. Avoid mounting the outdoor sensor in areassubjected to excessive moisture.

5. Once an area on the exterior wall has beendetermined, follow the mounting instruc-tions included with the outdoor sensor.

Wiring the Sensor1. Connect 18 AWG 2-wire cable or similar

cable to the outdoor sensor.2. Route the cable back to the PRESTIGE

Excellence, ensuring the wires are not runparallel to telephone or power cables.

If the sensor wires are located in an areawith sources of potential electromagneticinterference (EMI) the sensor wiresshould be shielded or the wires should berouted in a grounded metal conduit. Ifusing shielded cable, the shielding shouldbe connected to the common ground ofthe unit.

3. Connect the outdoor sensor wires to the out-door sensor terminals on the low voltage ter-minal strip located inside the boiler enclo-sure (see Fig. 19 page 29). The outdoor sen-sor wires do not have polarity.

NOTICE

IMPORTANTIn accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boil-er is equipped with a feature that saves energy by reducing the boiler water temperature as theheating load decreases. This feature is equipped with an override which is provided primari-ly to permit the use of an external energy management system that serves the same function.

THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOL-LOWING CONDITIONS IS TRUE.

• An external energy management system is installed that reduces the boiler water tem-perature as the heating load decreases.

• This boiler is not used for any space heating• This boiler is part of a modular or multiple boiler system having a total input of

300,000 BTU/hr or greater.• This boiler is equipped with a tankless coil.

62

External Modulating ControlSECTION XIII - External ModulatingControlThe boiler can directly accept an analog 0-10VDC signal to control the firing rate from anexternal modulating boiler controller such asthe Optima SCC4.

Wiring the Modulating ControllerRun two 18 gauge wires from the externalmodulating boiler controller’s 0-10 VDC boil-er output to the modulation signal terminals onthe low voltage terminal strip inside the boiler.(see boiler wiring diagram, Fig. 19 page 29).This signal will both enable and modulate theboiler. No wiring is required at the thermostatterminals.

Ensure that the polarity of the connec-tions from the external modulating boil-er controller to the boiler are correct.Reversed polarity will lead to noresponse from the boiler.

Trimax AdjustmentThe Trimax control must be programmed toaccept the 0-10 VDC signal from the externalmodulating boiler control.

1. Use the Heating EZ Setup function to setthe CH Demand to 0-10V ModulationSignal. Reference page 43 for the HeatingEZ Setup function.

Programming of External ModulatingControlThe external modulating control must be pro-grammed to send 2 VDC to enable the boilerand run it at low fire, and 10 VDC to run theboiler at high fire. Once the control enables theboiler, it must wait 30 seconds to allow the burn-er to stabilize before modulating the boiler.NOTICE

63

External Modulating ControlFactory Trimax Setting

Note 1: The Installer Reset function will set Prestige Model to Solo. Prestige Model must be changed backto Excellence in Boiler settings.

Note 2: The Installer & EZ Setup Reset functions will set DHW Demand to switch. Use Domestic HotWater EZ Setup to change back to a sensor demand.

HEATING SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESETHeating Operation Enabled

Demand Switch & Outdoor ResetAbsolute Max CH Setpoint 188°F [87°C]

CH1 Maximum Setpoint 180°F [82°C]

CH1 Minimum Setpoint 120°F [49°C]Reset Curve Coldest Day 0°F [-18°C]

Reset Curve Warmest Day 64°F [18°C]CH2 Circuit Enabled

CH2 Maximum Setpoint 140°F 60°C]CH2 Minimum Setpoint 80°F [27°C]

Warm Weather Shutdown OFF

Pump Constant Circulation Disabled

CH Post Pump Time 1 minuteFreeze Protection Enabled

Frost Protection Setpoint -22°F [-30°C]

Parallel Shift Value 0°F [0°C]CH Call Blocking 1 minute

System Pump CH1/CH2

DOMESTIC SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESETDHW Operation EnabledDemand (Note 2) Sensor

Boiler DHW Setpoint 186°F [86°C]DHW Storage Setpoint 140°F [60°C]DHW On Differential 6°F [3°C]DHW Storage Adder 46°F [25°C]

DHW Post Pump Time 1 minuteDHW Priority Timeout OFF

DHW Priority EnabledDHW Call Blocking 0 minute

DHW to CH Call Blocking 1 minuteAntilegionella Function Disabled

BOILER SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESETPrestige Model (Note 1) ExcellenceLockout Temperature 210°F [99°C]

Modbus Address 0=BCST

64

Check-Out Procedures

SECTION XIV- Check-Out Procedures

Perform the following check-out proce-dures as outlined and check off items ascompleted. When procedures are com-pleted, the installer should complete theinstallation record on page 65.

Check-Out Proceduresc Boiler system fluid chemistry checked and

verified as outlined on page 53.c Boiler system was completely flushed to

remove any debris/sediment.c Any automatic air vents placed within the

system are open one full turn.c Air is purged from the heating zones and

boiler system piping.c If applicable, confirm that the burner has

been properly configured for Propane asoutlined on page 26.

c Thermostat circuit wiring checked and ver-ified that no voltage is present to the lowvoltage terminals as outlined on page 55.

c Operating Instructions on page 60 were fol-lowed during start-up.

c Combustion levels and flame pattern veri-fied as outlined on page 57.

c Measured the rate of input on Natural Gasas outlined on page 58.

c Test high temperature limit as outlined onpage 59.

c Checked the incoming gas pressure to thePRESTIGE Excellence to ensure a mini-mum pressure of 5”w.c during flow condi-tions to all gas appliances and a maximumpressure of 13”w.c during non-flow condi-tions for Natural and Propane.

c Adjusted balancing valves and system limitcontrols to provide design temperatures tothe primary space heating system.

c In multiple zone applications, adjusted forcorrect flow of boiler water to each zone.

c Checked and verified room thermostat(s)function properly and the thermostat(s)heat anticipator (if used) was properly set.

c Observed several operating cycles forproper operation of the PRESTIGEExcellence and the system.

c Set the room thermostat(s) to the desiredroom temperature.

c Reviewed all instructions shipped with thePRESTIGE Excellence with the homeown-er or maintenance personnel.

c Completed the Installation Record on page65.

c Ensure all manuals and other documentsare returned to the Installation envelopeand given to the owner for safekeeping.

NOTICE

65

Installation RecordSECTION XV - Installation Record

PRESTIGE Model Number:

Serial Number:

Date of Installation:

Fuel: Natural Gas Propane

Measured Rate of Input:

Combustion Readings:

CO2

O2

CO

The following items were completed during installation:

Installation instructions have been followed and completed

Check-out procedures have been followed and completed

Information regarding the unit and installation received and left with owner / maintenance personnel.

Installer Information

(Company)

(Address)

(Address)

(Phone Number)

Btu/hr

____________________________________________________________________

____________________________________________________________________

____________________________________________________________________

_________________________________________________________________

%

%

ppm

66

Maintenance Schedules

SECTION XVI - Maintenance ScheduleService TechnicianAt least on an annual basis the following main-tenance should be performed by a qualified ser-vice technician:General- Attend to any reported problems.- Inspect the interior of the boiler jacket area;

clean and vacuum if necessary.- Clean the condensate drain assembly and

fill with fresh water.- Check boiler fluid pH on systems.- Check for leaks: water, gas, flue and con-

densate.- Verify flue vent piping/gaskets and air inlet

piping are in good condition, sealed tightand properly supported.

- Check boiler water pressure, piping andexpansion tank.

- Check control settings.- Check ignition electrode (sand off any

white oxide; clean and reposition).- Check ignition wiring and ground wiring.- Check all control wiring and connections.- Check burner flame pattern (stable and uni-

form).

Additional items if combustion or performanceis poor:- Clean heat exchanger and flue ways.- Remove burner assembly and clean burner

head using compressed air only.

Once the maintenance items are completed,review the service with the owner.

Owner MaintenancePeriodically:- Check the area around the unit. - Check and remove any blockage from the

combustion air inlet and ventilation open-ings.

- Check the temperature and pressuregauges.

Monthly:- Check vent piping.- Check combustion air inlet piping.- Check the pressure relief valve.- Check the condensate drain system.

Every 6 months:- Check boiler piping and gas supply piping

for corrosion or potential signs of leakage.- Operate the pressure relief valve.

Follow the maintenance proceduresgiven throughout this manual. Failureto perform the service and maintenanceor follow the directions in this manualcould result in damage to the PRES-TIGE Excellence or in system compo-nents, resulting in severe personalinjury, death or substantial propertydamage.

WARNING

67

Maintenance Procedures

SECTION XVII- MaintenanceProceduresMaintenance Procedures

The PRESTIGE Excellence should beinspected and serviced annually, prefer-ably at the start of the heating season, bya qualified service technician. In addi-tion, the maintenance and care of theunit as outlined on page 66 and furtherexplained on pages 67 through 72 shouldbe performed to assure maximum effi-ciency and reliability of the unit. Failureto service and maintain the PRESTIGEExcellence and the system componentscould result in equipment failure, caus-ing possible severe personal injury,death or substantial property damage.

The following information providesdetailed instruction for completing themaintenance items outline in the mainte-nance schedule on page 66. In additionto this maintenance, the PRESTIGEExcellence should be serviced at thebeginning of the heating season by aqualified service technician.

Reported ProblemsAny problems reported by the owner should bechecked, verified and corrected before pro-ceeding with any maintenance procedures.

Check Surrounding Area Verify that the area surrounding the PRES-TIGE Excellence is free of combustible / flam-mable materials or flammable vapors or liq-uids. Remove immediately if found.

Verify that combustion air inlet area is free ofany contaminates. Refer to the materials listedon page 5 of this manual. If any of these prod-ucts are in the area from which the unit takesits combustion air, they must be removedimmediately or the combustion air intake mustbe relocated to another area.

Inspect Burner AreaRemove the boiler front jacket panel and ven-turi inlet elbow.

Vacuum any dirt or debris from theburner/blower components.

Check the burner plate mounting nuts for tightness.

Check burner plate gasket for discoloration ordamage.

Re-install venturi inlet elbow and front jacketpanel when completed.

Do not use solvents to clean any of theburner components. The componentscould be damaged, resulting in unreli-able or unsafe operation.

Check System PipingInspect all piping (water and gas) on the boilersystem for leaks and verify that the piping isleak free and properly supported.

Inspect the fittings and components on the unitand verify they are leak free.

Eliminate all boiler water system leaks.Continual fresh make-up water willreduce the heat exchanger life causingboiler failure. Leaking water may alsocause severe property damage to the sur-rounding area. Inspect the gas supplypiping using the procedure outlined onPage 57.

NOTICE

WARNING

WARNING

WARNING

68

Maintenance Procedures

Clean Condensate Drain Assembly1. Loosen the retaining nut from the conden-

sate drain assembly and disconnect theassembly from the boiler.

2. Empty any water from the trap and drainassembly. Flush with fresh water as neces-sary to clean.

3. Check the drain piping from the condensatedrain assembly to the drain. Flush to cleanas necessary.

4. Reassemble the condensate drain assemblyonto the boiler by tightening the retainingnut with rubber seal onto the boiler. Handtight only.

5. Remove the fill plug on the condensate drainassembly and fill with water. See Fig. 14 onpage 23.

6. Replace the fill plug on drain assembly.

Check Ventilation Air Openings

Verify that all ventilation openings to themechanical room or building are open andunobstructed. Check the operation and wiringof any automatic ventilation dampers.

Check and verify the vent discharge and thecombustion air intake are free of debris andobstructions.

Inspect Vent and Combustion Air PipingVisually inspect the venting system and com-bustion air piping for blockage, deteriorationof gaskets or leakage. Repair any deficiencies.

Verify that the combustion air inlet piping isconnected, sealed and properly supported.

Failure to inspect the vent system andcombustion air inlet piping and to haveany conditions repaired, can result insevere personal injury or death.

Check Boiler SystemVerify all system components are correctlyinstalled and operating properly.

Check the cold fill pressure for the system, typ-ical cold water fill pressure is 12 psig.

Verify the system pressure, as the unit operates athigh temperature, to ensure the pressure does notexceed 25 psig. Excessive pressure reading indi-cates expansion tank sizing is incorrect or systemperformance problems.

Inspect air vent and air separators in the sys-tem. Remove the caps on automatic air ventsand briefly depress the valve stem to flushvent. Replace the cap when completed. Ensurevents do not leak, replace any leaking vents.

Verify boiler fluid pH level is between 6.0 and8.0.

Check and verify inhibitor /antifreeze concen-tration within the boiler water meetsinhibitor/antifreeze manuafacturer’s specifica-tions.

If necessary contact a boiler water treatmentcompany for a chemical analysis.

WARNING

69

Maintenance Procedures

Check Expansion TankRefer to Section IV - Boiler Piping for rec-ommended location of the expansion tankand air eliminators.Closed -Type Tank:

- Ensure tank is partially filled withwater leaving an air gap as a cushion.Refer to the manufacturer’s instructionfor proper fill level.

- Ensure the tank is fitted with a devicethat reduces gravity circulation of air-saturated tank water back into the sys-tem. This device prevents air frombubbling up through the water as itreturns from the system.

- Ensure no automatic air vents are usedin the system. This will allow air toescape from the system instead ofreturning to the tank.

Diaphragm Tank:- Ensure the system contains a minimum of

one automatic air vent. Recommendedlocation of the air vent should be atop anair eliminator.

- Remove the tank from the system andcheck the charge pressure. For residen-tial applications the charge pressure istypically 12 psig. If tank does not holda charge pressure, then the membrane isdamaged and the tank should bereplaced.

Check Boiler Relief ValveInspect the relief valve and lift the lever to ver-ify flow at least annually or as recommendedon the warning tag of the valve.

Before manually operating the pressurerelief valve, ensure the discharge piping isdirected to a suitable place of disposal toavoid a potential scald hazard. The dis-charge piping must be full size withoutrestriction and installed to permit com-plete drainage of both the valve and line.

If after closing the valve, the valve fails to seatproperly or continually weeps, replace therelief valve. Ensure the cause of the reliefvalve to weep is the valve itself, not due to sys-tem over-pressurization caused by an expan-sion tank that is waterlogged or undersized.

Inspection of Ignition ElectrodeRemove the ignition electrode from the burnermounting plate.

Remove any white oxides accumulated on theelectrode using fine grit sandpaper or steel wool.If the electrode does not clean to a satisfactorycondition, replace the ignitor .

When replacing the ignition electrode, ensurethe gasket is in good condition and correctlypositioned, replace gasket if necessary.

Check Ignition Wiring and Ground WiringInspect the ignition cable from the ignitor tothe Trimax control module.

Inspect the ground wire from the ignitor to theboiler jacket ground terminals.

Ensure wiring is in good condition and secure-ly connected.

Check ground continuity of the wiring to theboiler jacket or piping using a continuity meter.

Replace and correct ground wire if ground con-tinuity is not completed and satisfactory.

WARNING

70

Maintenance Procedures

Check Control WiringInspect all control wiring. Ensure wiring is ingood condition and properly connected.

Check Control Settings1. Review all boiler settings in the Heating &

DHW EZ Setup menus. Adjust settings asnecessary, see page 43-45

2. Check any external limit control settings (ifused). Adjust settings as necessary.

Perform Start-up and Checkout ProceduresStart the unit and perform the start-up proce-dure as listed in this manual.

Verify the cold water fill pressure is correct andthe operating pressure of the boiler is withinnormal operating range.

Complete the checkout procedures as refer-enced in this manual.

Check Burner FlameInspect the burner flame through the observa-tion port on the heat exchanger.

If flame pattern is not fully blue and covers theentire burner surface during high fire, shut theunit down and allow it to cool thoroughly beforedisassembly.

Close the external manual gas valve on the gassupply line and disconnect the gas piping andgas valve wire harness connector.

Disconnect the wiring harness connectors fromthe blower and remove the blower retainingscrews or nuts. Remove the blower from theunit.

Remove the mounting nuts securing the burnermounting plate to the heat exchanger and setaside.

Carefully remove the burner mounting plateassembly from the heat exchanger. Ensurecombustion chamber insulation is not damagedduring removal of burner mounting plateassembly. See WARNING on page 72.

Remove the burner head mounting screws andremove the burner head. Inspect the burnerhead for deterioration. Use compressed air ora vacuum to clean the burner head.

Remove the venturi and gas valve assemblyfrom the blower.

Use a vacuum cleaner or compressed air toclean the interior of the blower assembly.Inspect the blower blades to ensure they areclean and not damaged.

Re-assemble the venturi and gas valve onto theblower. Ensure the venturi gasket is in goodcondition, positioned correctly and replace gas-ket if necessary.

Re-assemble the burner head onto the burnermounting plate. Ensure the burner head gasketis in good condition, positioned correctly andreplace gasket if necessary.

Re-assemble the burner mounting plate assem-bly onto the heat exchanger. Ensure the burnerplate gasket and combustion chamber insula-tion is in place and not damaged, replace gas-ket and insulation if necessary. See WARNINGon page 72.

Re-assemble the blower onto the burnermounting plate and reconnect the wiring har-ness connectors.

Re-assemble the gas supply connection andwire harness to gas valve. Open the externalmanual gas valve. Check gas piping for anyleaks as outlined on page 55 and repair if nec-essary. Place the unit back into service.

71

Maintenance Procedures

Check Flame SignalThe flame signal can be read from the BoilerInformation screen. It should be a min. 1μ Α−DC.

Check the ignitor for fouling or damagedinsulation if a low flame signal is read.

Check ground wiring and continuity as a causefor low flame signal. Replace ignitor if condi-tions are satisfactory.

Check Combustion LevelsRefer to page 57 of this manual for measuringcombustion levels and burner adjustments.

Check Flue Gas Temperature

1. Manually place the boiler into high fire.See page 57 for procedure.

2. Navigate to the Boiler Information Menuto observe the flue gas temperature. Seepage 47 for procedure.

3. If the flue gas temperature is more than 54°F[30°C] above the supply water temperature,shut the boiler down and follow the heatexchanger cleaning procedure below.

Clean Heat Exchanger1. Shut down the boiler:

- Follow the instructions on Page 60 "ToTurn Off Gas to Appliance"

- Do not drain the boiler unless the boil-er will be subject to freezing condi-tions.

- Do not drain the boiler if freeze protec-tion fluid is used in the system.

2. Allow the boiler to cool down to room tem-perature before servicing.

3. Disconnect the gas piping and gas valvewire harness connector.

4. Disconnect the wiring harness connectorsfrom the blower and remove the blowerretaining screws or nuts. Remove the blow-er from the unit.

5. Remove the mounting nuts securing theburner mounting plate to the heat exchang-er and set aside.

6. Carefully remove the burner mountingplate assembly from the heat exchanger.Ensure combustion chamber insulation isnot damaged during removal of burnermounting plate assembly. See WARNINGon page 72.

7. Carefully remove the combustion chamberinsulation from the heat exchanger and setaside. See WARNING on page 72.

8. Use compressed air or water to remove anyaccumulation from the heat exchanger flueways.

9. Re-install the combustion chamber insula-tion onto the heat exchanger.

10. Re-assemble the burner mounting plateassembly onto the heat exchanger. Ensurethe burner plate gasket and combustionchamber insulation is in place and not dam-aged, replace gasket and insulation if nec-essary. See WARNING on page 72.

11. Re-assemble the blower onto the burnermounting plate and reconnect the wiringharness connectors.

12. Reconnect the gas piping and wire harnessto gas valve. Check for leaks, repair if nec-essary.

13. Close isolation valves on the boiler waterpiping to isolate the boiler from the heatingsystem.

14. Attach a hose to the boiler drain valve andflush the boiler thoroughly with freshwater by using the purge valves to allowwater to enter through the make-up waterline to the boiler.

72

Maintenance Procedures

The combustion chamber insulationcontains ceramic fibers, which are clas-sified as a possible human carcinogen.When exposed to extremely high tem-peratures, the ceramic fibers, whichcontain crystalline silica, can be con-verted into cristobalite.

Avoid Breathing and Contact with Skinand EyesWhen removing or repairing the combustionchamber insulation follow these precautionmeasures:1. Use a NIOSH approved respirator which

meets OSHA requirements for cristobalitedust, similar to N95. Contact NIOSH at1-800-356-4676 or on the web atwww.cdc.gov/niosh for latest recommen-dations.

2. Wear long sleeved, loose fitting clothing,gloves and eyes protection.

3. Assure adequate ventilation.4. Wash with soap and water after contact.5. Wash potentially contaminated clothes

separately from other laundry and rinsewashing machine thoroughly.

6. Discard used insulation in an air tightplastic bag.

NIOSH Stated First Aid:Eye/Skin: Immediately irrigateBreathing: Clean fresh air

WARNING

Handling Previously Fired Combustion Chamber Insulation

15. Once the boiler has been completelyflushed, return the boiler and system pipingback to operation.

16. Perform the required startup and checkoutprocedures as outlined on pages 53 to 64.

Review With OwnerEnsure the owner understands the impor-tance to perform the maintenance schedulespecified in this manual.Remind the owner of the importance to calla licensed contractor should the unit or sys-tem exhibit any unusual behavior.

73

Replacement Parts

4

9

3

4

2

5

1

6

8

7

Fig. 33: PRESTIGE Excellence Jacket Components

Item Part # Description1 PTJKT11R Rear Panel

2 PTJKT09F Front Jacket Panel

3 PTRKIT129 Control Enclosure Bezel4 PTJKT23S Side Jacket Panel (Left or Right)5 PTJKT15T Top Jacket Panel6 PTJKT19T Top Jacket Panel - Blower Access7 PEJKT03T Top Jacket Panel - IDWH Access8 PSRKIT21 Wall Mounting Bracket with Hardware9 PTJKTSUP03 Support - Boiler Return Piping

Replacement parts must be purchasedthrough a local ACV-Triangle Tube dis-tributor. When ordering part please pro-vide the model number and descriptionand/or part number of replacement part.

Use only genuine ACV-Triangle Tubereplacement parts to ensure warrantycoverage and to avoid damage to appli-ance and improper operation of appli-ance. Contact ACV-Triangle Tube at856-228-8881 or www.triangletube.comfor list of distributors nearest you.

WARNING

74

Replacement Parts

8

5

15

16

9

6

4

4

10

11

13

14

12

7

1

3

2

Item Part # Description

1PTRKIT124 Heat Exchanger Body - NaturalPTRKIT125 Heat Exchanger Body - Propane

2 PTADPT07 Vent Outlet/ Combustion Air Inlet Adapter3 PTRKIT118 Polypropylene Vent Pipe4 PTRKIT122 Supply / Return Temperature Sensor5 PTRKIT123 Flue Temperature Sensor6 PGRKIT20 LWCO Pressure Device7 PSRKIT05 Condensate Drain Assembly8 PSRKIT59 Boiler Piping - Return Assembly9 PSRKIT60 Boiler Piping - Supply Outlet Assembly10 PSRKIT61 Boiler Piping - Supply Long Assembly11 PSRKIT54 Boiler Piping - Supply Short Assembly12 PSRKIT62 Boiler Piping - Relief Valve Assembly13 HMCIR01 Circulator14 PSRKIT56 EXCELLENCE Water Heater Tank15 PSRKIT57 Valve Actuator16 PEVLV01 Valve Body

Fig. 34: PRESTIGE Excellence Internal Components

75

7

2

5

4

1

3

9

6

8

Fig. 35: PRESTIGE Excellence Burner Components

Replacement Parts

Item Part # Description

1 PSRKIT09 Combustion Chamber Insulation

2PSRKIT10 Burner Head with Gasket - Natural

PSRKIT11 Burner Head with Gasket - Propane

3 PTRKIT114 Blower with Gasket

4 PSRKIT12 Burner Plate

5 PSGSK15 Burner Plate Gasket

6 PTRKIT111 Gas Valve

7 PSRKIT81 Venturi - 002

8 PTRKIT313 Igniter and Cable with Gasket

9 PSRKIT16 Sight Glass Assembly (Glass, Gasket and Bracket)

76

8

3

4

1

6

5

2

7

Fig. 36: PRESTIGE Excellence Control Enclosure

Replacement Parts

Item Part # Description1 PTRKIT109 Pressure Gauge and Fitting

2 PTSWI01 Power Switch

3 PTSWI02 Power Switch Cover

4 PTRKIT108 Control Enclosure

5 PTRKIT205 TriMax Control Module

6 PTRKIT207 TriMax Display Module

7 PTCON19 Control Enclosure Cover

8 PTGRO01 Igniter Cable Grommet

9 PTFUSE02 TriMax Control Module 5A Fuse (Not Shown)

10 PTFUSE01 Circulator 2.5A Fuses (Not Shown)

11 PTFUSE03 In-Line Voltage 8A Fuse (Not Shown)

77

Product Specifications

37 1

/2” [

953

mm

]

24 3/4” [628 mm]

14 3/4” [377 mm]

12 1/4” [310 mm]

21 1/4” [540 mm]

16” [405 mm]

1/2 ” NPSC Boiler Drain

1/2” NPT Gas Connection

3/4” NPSC Pressure Relief Valve

3” Combustion Air Inlet

3” Vent Outlet

19” [479 mm]

11 3/4” [300 mm]

7 1/2” [190 mm]

1” NPT Boiler Return

1” NPT Boiler Supply

Front View PRESTIGE Excellence 110

78

Product Specifications

11 3/4” [300 mm]

2 3/4” [70mm]

16 3/8” [416 mm]

7 3/4” [200 mm]

15 1/4” [390 mm]

1/2” NPT Gas Connection

1” NPT Boiler Supply1” NPT Boiler Return

1/2” NPSC Boiler Drain

3” Vent Outlet3” Combustion AIr Inlet

3/4” NPSC Pressure Relief Valve

21 1/4” [540 mm]

Side View PRESTIGE Excellence 110

79

Product Specifications

3/4” NPT DHW Inlet

3/4” NPSC Aux. Connection (Rear)1/2” NPSC Air Vent Connection

3/4” NPT DHW Outlet11.1/4" [286 mm]

7 1/2" [190 mm]

3 1/2" [87 mm]

8 1/2"

[216

mm]4 3

/8"

[110 m

m]

Top View PRESTIGE Excellence 110

80

Product Specifications

DOE

Fuel DOE

Heating Capacity Note 1 & 4

Input Note 4

DOE Seasonal Efficiency AFUE

Note 3

Net AHRIRatingNote 2

99,000 110,000 95%

Shipping Weight Lbs/Kg

190/86Natural

Boiler Model

Excellence 86,000

87,000 97,000 95% 190/86Propane Excellence 76,000

Note 1: The heating capacity of the PRESTIGEExcellence is based on the test requirementsof the U.S. Department of Energy.

Note 2: The AHRI rating is based on a piping andpick up allowance of 1.15. This allowanceshould be sufficient for the standard radiationrequirements for a building load.

Note 3: Based on the given AFUE the PRESTIGEExcellence meets the energy efficiencyguidelines established by Energy Star.

Note 4: Input and output ratings are shown for sealevel applications. The PRESTIGEExcellence automatically derates the input atapproximately 2% for every 1,000 Ft. of alti-tude. No alterations to the boiler or burnersystem is required.

81

Product Specifications

Note: Minimum allowable flow rate at full input: 5 gpm

Graph 2: Pressure Drop Comparison Excellence vs Grundfos UPS 15-58F

* I N S T A L L A T I O N A N D M A I N T E N A N C E * * I N S T A L L A T I O N A N D M A I N T E N A N C E * M A N U A LM A N U A L

2011-61 Manual Prestige Excellence_IWH

prestige Excellence Indirect Water Heater

Revised 1/7/14

• Before proceeding with installation and operation, read entire manual care-fully. Failure to do so can cause injury or property damage.

• When receiving the PRESTIGE Excellence, any claims for damage orshortage in shipment must be filed immediately against the transporta-tion company by the consignee.

• Warranty Registration Card must be filled out by the customer and mailedwithin thirty (30) days of installation in order to gain warranty coverage.

• Retain and affix this manual near the water heater for future reference• Installation and service should only be performed by a qualified installer or

service technician.• Installations and service should be performed by a license plumber or gas

fitter in the Commonwealth of Massachusetts.

Part 2 of 2

WARNING

IMPORTANT

L I S T E D

Tables of Contents

Product & Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

Installation - Domestic PipingTemperature & Pressure (T&P) Relief Valve . . . . . . . . . . . . . . . . . .5Drain Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Automatic Air Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Thermal Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Water Hammer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Vacuum Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6General Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Domestic Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Thermostatic Mixing Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Recirculation Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Storage Tank Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

Installation - Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10

Water Heater Start-UpFilling the Inner (Domestic Water) Tank . . . . . . . . . . . . . . . . . . . . .11Filling the Outer (Boiler Water) Tank . . . . . . . . . . . . . . . . . . . . . . .11Setting the Thermostatic Mixing Valve . . . . . . . . . . . . . . . . . . . . . .11General Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Domestic Hot Water EZ Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Additional DHW Feature

DHW Frost Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Factory Trimax Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

Water Heater MaintenanceMaintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Filling Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Draining Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17Draining Outer (Boiler Water) Tank . . . . . . . . . . . . . . . . . . . . . . . . .17Draining Inner (Domestic Water) Tank . . . . . . . . . . . . . . . . . . . . . . .17

Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18Water Heater Specifications

Excellence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-21Performance

Excellence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

i

Product & Safety Information

Indicates the presence of a hazardous situ-ation which, if ignored, will result in death,serious injury or substantial propertydamage.

Indicates a potentially hazardous situationwhich, if ignored, can result in death, seri-ous injury or substantial property damage.

Indicates a potentially hazardous situationwhich, if ignored, may result in minorinjury or property damage.

Indicates special instructions on installa-tion, operation or maintenance, which areimportant to equipment but not related topersonal injury hazards.

Indicates recommendations made by ACV-Triangle Tube for the installers which willhelp to ensure optimum operation andlongevity of the equipment

WARNING

NOTICE

CAUTION

DANGER

BEST PRACTICE

The following terms are used throughout this manual to bring attention to the presence of poten-tial hazards or important information concerning the product.

Definitions

1

ACV-Triangle Tube reserves the right to modify the technical specifications and components of itsproducts without prior notice.

NOTICE

ACV-Triangle Tube accepts no liability for any damage, injury or loss of life resulting from incorrectinstallation, from alteration of any factory supplied parts or from the use of parts or fittings not spec-ified by ACV-Triangle Tube. If there is a conflict or doubt about the proper installation of the unit orany factory supplied or replacement parts please contact ACV-Triangle Tube Technical Support.

WARNING

Product & Safety Information

Bacteria can develop in the domestic watersystem if certain minimum water tempera-tures are not maintained.

HOT WATER CAN SCALD!Water temperature over 125ºF can causesevere burns instantly or death from scalds.• Children, disabled and elderly are at highest

risk of being scalded. - Never leave them unattended in ornear shower, bathtub or sink.

- Never allow small children to use a hotwater faucet or draw their own bath.

• To avoid any potential scald hazard or ifcodes require specific water temperatures atthe hot water faucet, the installer must:- Install the factory supplied thermostatic

mixing valve at this appliance and ensure itis working propertyand

- Set the domestic storage temperature to thelowest temperature which satisfies yourhot water needs.

- Feel and adjust water temperature beforebathing or showering.

- Water drained from the system drainvalves may be extremely hot.

TO AVOID INJURY:- Make sure all connections are tight.- Direct water flow away from any person.

Protection must be taken against exces-sive temperature and pressure!

TO PROTECT AGAINST EXCESSIVETEMPERATURE AND PRESSURE• Check if the Temperature & Pressure

(T&P) relief valve is installed in the loca-tion provided (DHW Side).

• Check if the 30 psi relief valve suppliedis installed in the location provided (CHSide)

• To avoid injury, install the relief devicesto comply with local code requirements.

To prevent damage to the inner tank, theInstaller must:

• Always fill inner tank prior to outertank and always drain outer tank priorto inner tank.

• Relieve primary system pressurebelow 15 psig prior to draining innertank.

WARNING CAUTION

CAUTION

DANGER

2

3

Codes ComplianceInstallation of the Excellence Water Heater mustconform with the instructions in this manual andwhere applicable:

• local, state, provincial, and national codes,laws, regulations and ordinances.

• in Canada - CAN / CGA B149.1 or B149.2Installation Code.

Excellence water heater is exempt from ASMESection VIII, Division 1 Code construction perInterpretation VIII-86-136. Check with local codesfor applicability.

The Excellence water heater will absorb lessthan 200,000 BTU/hr when domestic wateroutlet temperature is 194ºF and boiler watersupply temperature is 240ºF. Listed outputsare based on ASME Section VIIIInterpretation VIII-1-86-136.

Where recommendations in this manual differfrom local, or national codes, the local or nationalcodes take precedence.

Codes RestrictionsSingle wall heat exchanger in the Excellence waterheater complies with National Standard PlumbingCode, provided that:

– boiler water (including additives) is practicallynon-toxic, having toxicity rating or class of 1,as listed in Clinical Toxicology of CommercialProducts, and

– boiler water pressure is limited to maximum30 psig by approved relief valve.

Single wall heat exchangers are permitted under theUniform Plumbing Code - Paragraph L3.2. and L3.3if they satisfy all of the following requirements.

1. The heat transfer medium is potable water orcontains only substances which are recog-nized as safe by the U.S. Food and DrugAdministration.

2. The pressure of the heat transfer medium ismaintained less than the normal minimumoperating pressure of the potable water system

Exception: Steam complying with sec-tion #1 above.

3. The equipment is permanently labeled toindicate that only additives recognized assafe by the FDA shall be used in the heattransfer medium.

Other heat exchanger designs may be permittedwhere approved by the Administrative Authority.Operating Restrictions

• Maximum DHW outlet temperature is120ºF, when factory supplied mixing valveis installed.

• Maximum boiler water temperature ratingis 210ºF.

• Maximum working pressure for inner(domestic water) tank is 150 psig.

• Maximum working pressure for outer(boiler water) tank is 30 psig.

• Water quality limitations (based on E.P.ANational Secondary Drinking WaterRegulations):- Chloride, less than 150 ppm or mg/l- pH value min. 6, max. 8 - Total hardness 3 - 7 grains/gallon or 50-120

ppm or mg/l.- Total Dissolved Solids (TDS), less than

120 ppm or mg/l.- Iron less than 0.3 ppm or mg/l.- Aluminum, less than 0.2 ppm or mg/l.- Copper, less than 1 ppm or mg/l.- Manganese, less than 0.05 ppm or mg/l.- Zinc, less than 5 ppm or mg/l.

NOTICE

Pre-Installation

4

Pre-Installation

In hard water areas (more than 7 grains ofhardness) soften the cold domestic supplywater to the appliance to prevent scaling.

Any water conditioning system must beinstalled and maintained in accordance withmanufacturer’s specifications.

Do not install the Excellence water heater onany application if the boiler piping containsnon-oxygen barrier tubing or if the boilerpiping is considered an “open system”.Exposing the outer tank of the Excellencewater heater to oxygen contamination willlead to premature tank failure and denial ofthe warranty.

Locating Water Heater• The Excellence is not intended for outdoor

installations.• Locate Excellence so that any leakage from the

tank or water connections will not cause dam-age to the area adjoining the water heater or tolower floors in the structure.

Recommended ClearancesThe Excellence is approved for zero clearance tocombustibles, excluding vent and boiler piping.

- Vent & Boiler Piping - 1/4 inch from com-bustible materials.

To provide serviceability to the unit it is rec-ommended that the following clearances bemaintained:Top boiler jacket - 24 inches.Front - 24 inches.Bottom boiler piping - 24 inches.Rear - 0 inchesSides - 6 inches

When maintaining zero clearance or lessthan recommended clearances, some prod-uct labeling may become hidden andunreadable

When installing the Excellence in a confinedspace, sufficient air must be provided forproper combustion and venting and toallow, under normal operating conditions,proper air flow around the product to main-tain ambient temperatures within safe limitsto comply with the National Fuel Gas CodeNFPA 54 - latest edition. Reference theExcellence Boiler Manual for additionalguidelines.

Residential Garage InstallationsWhen installing the Excellence in a residentialgarage, the following special precautions per NFPA54/ANSI Z223.1 must be taken:

- Mount the unit with a minimum 18 inchesabove the floor level of the garage. Ensurethe burner and ignition devices / controlsare no less than 18 inches above the floorlevel.

- Locate or protect the unit in a matter so itcannot be damaged by a moving vehicle.

WARNING

NOTICE

BEST PRACTICE

NOTICE

NOTICE

BEST PRACTICE

5

Installation - Domestic PipingTemperature & Pressure (T&P) Relief Valve

To reduce risk of excessive pressures and tem-peratures in the water heater, install tempera-ture and pressure protective equipmentrequired by local codes, but no less than a com-bination temperature and pressure relief valvecertified by a nationally recognized testing lab-oratory that maintains periodic inspection ofproduction of listed equipment or materials, asmeeting the requirements for Relief Valves andAutomatic Gas Shutoff Devices for Hot WaterSupply Systems, ANSI Z21.22. This valve mustbe marked with a maximum working pressureof the water heater.• The Excellence water heater must be protected

with a T&P relief valve.

• Size the Excellence T&P relief valve by thefollowing specifications, unless they conflictwith local codes: 3/4” NPT with an AGARating of 100,000 BTU/hr (Watts 100XL-8 orequivalent).

For proper operation of the T&P and to pre-vent the T&P from activating due to boilerwater temperature, use a T&P relief valvewith extended element. A 8” minimumlength is recommended.

Standard Installation• Install T&P relief valve in the Auxiliary con-

nection located behind the air vent on the top ofthe water heater as shown Fig. 2 page 8.

Commonwealth of Massachusetts InstallationFollow this procedure for jurisdictions requiring avacuum breaker to be installed on the domesticcold water inlet.

• Install the T&P in the run (straight through leg)of a tee located at the domestic hot water out-let. Use a long element T&P relief valve, asshown in Fig. 3 page 8.

T&P Relief Valve Discharge PipingT&P relief valve discharge piping must be:- made of material serviceable for tempera-tures of 250ºF or greater.

- directed so that hot water flows away fromall persons.

- directed to a suitable place for disposal.- installed so as to allow complete drainingof the T&P relief valve and discharge line.

T&P relief valve discharge piping must not be:- excessively long. Using more than 2elbows or 15 feet of piping can reduce dis-charge capacity.

- directly connected to a drain. Terminatedischarge piping within 6” from drain.Refer to local codes.

- plugged, reduced or restricted.- subject to freezing.

Do not install any valve between T&P reliefvalve and tank connection or on T&P reliefvalve discharge piping. Do not plug T&Prelief valve or discharge piping. Improperplacement and piping of T&P relief valvecan cause severe personal injury, death orsubstantial property damage.

WARNING

NOTICE

CAUTION

6

Installation - Domestic PipingDrain ValveDrain valve and fittings are supplied by others.Standard Installation• Install a tee connection at the domestic cold

water inlet, as shown in Fig. 4, pages 9.• Pipe the drain piping with drain valve from

the tee connection to:- a suitable place for disposalor- terminate within 12” of the floor

Commonwealth of Massachusetts Installation• Thread a 3/4” close nipple onto the

Auxiliary connection and insert an open-end dip tube into the Auxiliary connectionon top of water heater. As shown in Fig. 3,page 8.

• Install a 3/4” NPT elbow to the Auxiliaryconnection.

• Pipe the drain piping with drain valve fromthe elbow connection to:- a suitable place for disposalor- terminate within 12” of the floor

Automatic Air Vent 1.Remove plastic shipping cap from 1/2” NPT

pipe fitting on top center of water heater.2. Install automatic air vent provided with water

heater, using only the supplied sealant.3.Once the tank is full and air has stop escaping and

air vent is seated and closed, screw the vent capcompletely close.

For proper operation of the air vent ensurevent cap is tighten at all times. The air vent isprovided both a hygroscopic cap that preventsleakage of water due to an internal membrane.

Thermal ExpansionIf a backflow preventer, check valve or pressurereducing valve is piped on cold water supply pipingof water heater, install an expansion tank on coldwater supply line to prevent normal thermal expan-sion from repeatedly forcing open T&P relief valve.

T&P relief valve is not intended for constantduty, such as relief of pressure due torepeated normal system expansion. Correctthis condition by installing a properly sizedexpansion tank in domestic water system.Refer to expansion tank manufacturer’sinstallation instructions for proper sizing.

Water HammerDishwashers, clothes washers and fast-closing pos-itive shut-off valves incorporated in the system allcontribute to creating water shock. Install a waterhammer arrester to prevent damage to pipes andappliances. See device manufacturer’s instructionsfor application and installation.

Water hammering within the domestic pip-ing system can cause premature failure ofthe inner tank of the water heater. This typeof failure is NOT covered under warranty.

Vacuum BreakerInstalling a vacuum breaker on the domestic coldwater outlet will prevent damage to the inner tankif a negative pressure is developed in the domesticsupply line. See manufacturer’s instructions forapplication and installation of the vacuum breaker.

General Piping• For domestic water piping diagrams, see pages

9 and 10.

NOTICE

CAUTION

NOTICE

7

Installation - Domestic Piping• All plumbing must meet or exceed all local,

state and national plumbing codes.• Use pipe dope or tape suitable for potable

water systems.• Use isolation valves to isolate system components.Domestic Piping• Union on domestic hot water outlet should be

piped at a higher elevation than domestic waterdrain valve. This will make draining the waterheater easier.

• Use dielectric unions or couplings to protecthot and cold water fittings from corrosionwhen connecting dissimilar materials such ascopper and galvanized iron pipe.

• If copper pipe is used for domestic water con-nections, first solder pipe to a threaded adapterand then screw adapter into cold water inlet ontop of Excellence. Cold Water Inlet containsan internal plastic dip tube which can be dam-aged by heat from soldering.

Do not apply heat to the cold water inlet whenmaking sweat connections to water heater.Sweat tubing to adapter before fitting adapterto cold water inlet of heater. It is imperativethat no heat be applied to the cold water inlet,as it contains a non metallic dip tube.

• When the water supply pressure is higher than70 psig, it is recommended to install a pressurereducing valve on cold water supply line toprevent water loss through T&P relief valve.

Thermostatic Mixing ValveThe Excellence is factory supplied with a thermo-static mixing valve with built-in check valve. Themixing valve must be installed as shown in Fig. 1.

The operating range of the thermostatic mixing is85ºF [30ºC] to 150ºF [65ºC].

For applications with a domestic recirculationloop, the recirculation pump should be controlled

by an aquastat. The maximum recommended set-ting of the aquastat is 10ºF lower than the thermo-static mixing valve setting.

For proper operation of the thermostaticmixing valve and to prevent potential scald-ing hazards, the recirculation loop shouldbe controlled by an aquastat. DO NOT usecontinuous recirculation.

Recirculation Piping• Recirculation piping must be installed in the

cold water inlet as shown Fig. 5, page 9. • A stainless steel or bronze circulator is recom-

mended.

Storage Tank ApplicationFor applications requiring large volumes of domes-tic hot water in a relative short period, the installermay include a storage type tank (see Fig. 6 page 10)in the domestic piping.The installer must:

1. Relocate the thermostatic mixing valve fromthe Excellence to the outlet of the storage tank.

2. Provide recirculation from the storage tankback to the Excellence using a bronze typecirculator. Maximum recommended recircu-lation flow rate is 1 gpm.

NOTICE

DANGER

Cold

Hot Adapter

Check Valve

MixedFig. 1: Mixing Valve Assembly

Installation - Domestic Piping

8

DHW Aux. Connection

DHW Cold Water Inlet

Air Vent Connection

DHWHot Water

Outlet

T&P Valve (Drain Piping Not Shown)

Fig. 2: Standard Installation of the T&P Relief Valve

Drain Dip Tube

3/4” Brass Close Nipple

DHW Aux. Connection

DHW Hot Water Outlet

DHW Cold Water Inlet

Air VentConnection

3/4” BrassTee

T&P Valve (Drain Piping Not Shown)

Fig. 3: Commonwealth of Massachusetts Installation

9

Installation - Piping Diagrams

1. Shut-off valve2. Flow check valve3. Mixing valve with check valve4. Vacuum Breaker *5. Unions

6. Backflow preventer or pressure reducing valve(*)7. Circulator (controlled by aquastat)8 Domestic drain valve9. Thermal expansion tank (potable)

(*) Optional devices may be required by local codes.

Standard Installation Domestic Piping Excellence SeriesFig. 4:

Standard Installation Domestic Piping with Optional Recirculation Excellence SeriesFig. 5:

Installation - Piping Diagrams

10

1. Mixing valve with check valve 2. Flow check valve3. Shut-off valve4. Backflow preventer or pressure reducing valve(*)

6. Thermal expansion tank 7. Circulator (controlled by aquastat)8 Domestic drain valve9. Vacuum Breaker *

(*) Optional devices may be required by local codes.

Domestic Piping with Optional Storage TankFig. 6:

11

Filling the Inner (Domestic Water) Tank

• Never use the Excellence unless inner andouter tank of the water heater is completelyfilled with water.

• Inner tank of the Excellence water heatermust be completely filled and pressurizedbefore pressurizing outer tank.

1. Close domestic water drain valve.2. Open domestic water isolation valves on the

water heater piping.3. Vent air from inner (domestic water) tank by

opening nearest hot water faucet. Fill domes-tic water tank completely by allowing water torun until there is a constant flow of water.

4. Close hot water faucet.

Filling the Outer (Boiler Water) Tank

• Never use the Excellence unless inner andouter tank of the water heater is completelyfilled with water.

• Inner tank of the Excellence water heatermust be completely filled and pressurizedbefore pressurizing outer tank.

Reference the PRESTIGE Excellence boilermanual for boiler start-up and guidelines forfilling the boiler.

If antifreeze is used in boiler water, check concen-tration. Boiler water (including additives) must bepractically non-toxic, having toxicity rating or classof 1, as listed in Clinical Toxicology of CommercialProducts.

Do not use automotive, ethylene glycol orpetroleum-based antifreeze. Do not use anyundiluted antifreeze. This can cause severepersonal injury, death or substantial propertydamage.

Setting the Thermostatic Mixing Valve

The thermostatic mixing valve controls theoutlet hot water temperature delivered tothe faucets.

POTENTIAL SCALD HAZARD. The mix-ing valve must be installed on the Excellence.Removal or adjustment of the mixing valvewill create a potential scald hazard resultingin severe personal injury or death.

If any adjustment needs to be made to the valve’stemperature setpoint refer to the manufacturer’sinstructions included with the valve.

CAUTION

CAUTION

NOTICE

WARNING

NOTICE

WARNING

Water Heater Start-Up

12

Water Heater Start-Up

HOT WATER CAN SCALD!• Water temperatures over 125ºF can cause

severe burns instantly, or death from scalds.• Feel water before bathing or showering.• Consumer Product Safety Commission and

some states recommend temperatures settings of130ºF or less. Setting thermostat higher than130ºF will increase risk of scald injury andcause severe personal injury or death.

• Water heated to a temperature suitable forclothes washing, dish washing and other sanitiz-ing needs will scald and cause permanent injury.

• Children and elderly, infirm, or physicallyhandicapped persons are more likely to beinjured by hot water. Never leave them unat-tended in or near a bathtub. If anyone using hotwater in the building fits this description, or ifstate laws or local codes require certain watertemperatures at hot water faucets, take specialprecautions.- Install the factory supplied automatic mix-ing valve at water heater and/or install apoint of use mixing valve at each hot waterfaucet, bath and shower outlet. Selectionand installation of point of use mixingvalves must comply with valve manufactur-er’s recommendation and instructions.

- Use the lowest practical temperature setting.- Check water temperature after any adjust-ment of the mixing valve.

General Notes• Household water usage patterns will affect

water temperature at any faucet or shower.Occasionally check temperature at each pointof use, then adjust the mixing valve settingaccordingly. Always recheck temperature afteradjusting the mixing valve.

• Lowering the automatic mixing valve as indicat-ed in these instructions will reduce water tem-perature levels. Consult your installer or servicetechnician.

DANGER

13

Water Heater Start-Up

Navigation: Home Screen>Main Menu>EZ Setup>DHW EZ SetupDomestic Hot Water EZ Setup allows the installer to quickly customize thedomestic hot water settings for the application.

Select DHW Demand Default: SensorSelect DHW Demand prompts the installer to select the type of device which willgenerate a DHW call. Press the UP or DOWN buttons to select the DHW Demandtype then press the OK button to store the setting. The Select DHW Demandoptions are:• Switch – A domestic hot water call from an aquastat or dry contact switch will

enable the Prestige with a fixed setpoint for a domestic hot water call.• Sensor – The Prestige Excellence utilizes an Indirect Water Heater Sensor.

The Prestige will monitor the DHW storage temperature and generate adomestic hot water call when the temperature drops below the DHW StorageSetpoint by 6ºF [3ºC].

DHW Storage Setpoint Default: 140°F [60°C]DHW Storage Setpoint prompts the installer to enter the domestic hot water storagesetpoint temperature when the Sensor option is chosen in Select DHW Demand.Press the LEFT or RIGHT buttons to adjust the DHW Storage Setpoint then pressthe OK button to store the setting.

The Boiler DHW Setpoint will automatically be set 46°F [25°C] higherthan the DHW Storage Setpoint setting.

DHW Priority Timeout Default: OffDHW Priority Timeout prompts the installer to enter an optional time limit that adomestic hot water call has priority over a central heating call. Press the LEFT orRIGHT buttons to adjust the DHW Priority Timeout then press the OK button tostore the setting.

NOTICE

Domestic Hot Water EZ Setup

Select DHW Demand

SwitchSensorSensor

68ºF 150ºF

140ºF

DHW Storage Setpoint

Off 120 min.

Off

DHW Priority Timeout

14

Additional DHW Feature

DHW Frost ProtectionThe Indirect Water Heater (IDWH) Sensor used in the Prestige Excellence providesa Frost Protection feature to the water heater. The Frost Protection feature isdesigned to protect the Excellence water heater from a potential freeze up. FrostProtection will generate a DHW call once the IDWH temperature falls below 42º F[6ºC]. Once Frost Protection is activated, the internal circulator and diverter valvewill direct water flow to the water heater and the burner will fire. Frost Protectionwill end once the IDWH temperature is raised to 60ºF [16ºC]. This feature is alwaysactive and cannot be disabled. Frost Protection is still active even if DHW opera-tion has been disabled.

Additional DHW Feature

15

Factory Trimax Setting

Note 1: The Installer Reset function will set Prestige Model to Solo. Prestige Model must be changed backto Excellence in Boiler settings.

Note 2: The Installer & EZ Setup Reset functions will set DHW Demand to switch. Use Domestic HotWater EZ Setup to change back to a sensor demand.

DOMESTIC SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESETDHW Operation EnabledDemand (Note 2) Sensor

Boiler DHW Setpoint 186°F [86°C]DHW Storage Setpoint 140°F [60°C]DHW On Differential 6°F [3°C]DHW Storage Adder 46°F [25°C]DHW Post Pump Time 1 minuteDHW Priority Timeout OFF

DHW Priority EnabledDHW Call Blocking 0 minute

DHW to CH Call Blocking 1 minuteAntilegionella Function Disabled

BOILER SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESETPrestige Model (Note 1) ExcellenceLockout Temperature 210°F [99°C]Modbus Address 0=BCST

HEATING SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESETHeating Operation Enabled

Demand Switch & Outdoor ResetAbsolute Max CH Setpoint 188°F [87°C]

CH1 Maximum Setpoint 180°F [82°C]

CH1 Minimum Setpoint 120°F [49°C]Reset Curve Coldest Day 0°F [-18°C]Reset Curve Warmest Day 64°F [18°C]

CH2 Circuit EnabledCH2 Maximum Setpoint 140°F 60°C]CH2 Minimum Setpoint 80°F [27°C]Warm Weather Shutdown OFF

Pump Constant Circulation Disabled

CH Post Pump Time 1 minuteFreeze Protection Enabled

Frost Protection Setpoint -22°F [-30°C]

Parallel Shift Value 0°F [0°C]CH Call Blocking 1 minuteSystem Pump CH1/CH2

16

Water Heater MaintenanceMaintenance ScheduleAnnual service by qualified service technicianshould include the following:

Any procedure required by local codes.Check air vent operation.Verify system pressure. Air venting proce-dure may require adding water to bring sys-tem up to pressure, typically 12 psig.Manually operate T&P relief valve at leastonce a year. This will release some hotwater.

Before operating T&P relief valve, makesure no one is in front of or around T&Prelief valve discharge piping. Hot dischargewater can cause severe personal injury orsubstantial property damage.Move operating lever to open position for afew seconds and then move it back, allowingit to snap closed. After T&P relief valve isoperated, if it continues to release water,close cold water inlet to water heater imme-diately. Follow draining instructions, andreplace T&P relief valve. If T&P relief valveweeps periodically, it may be due to thermalexpansion see Thermal Expansion, page 6.Do not plug T&P relief valve or dischargepiping.

Plugging T&P relief valve or discharge pip-ing can cause excessive pressure in waterheater, resulting in severe personal injury,death, or substantial property damage.Follow instructions on circulator to oil it, ifrequired.Check mixing valve, valves, pipes and fit-tings for leaks.

Check function of field-installed controlsand valves. See component manufacturer’sinstructions.Review homeowner’s maintenance responsi-bilities and their frequencies, including anynot listed in the following section.

Homeowner monthly maintenance to include:Check air vent operation.

• Automatic air vent - remove cap. Brieflypush in valve and release it to clean valveseat. Screw cap on completely, thenunscrew one full turn. If air vent does notoperate, call qualified service technician.

Visually check valves, pipes and fittings forleaks. Call qualified service technician torepair leaks.

Filling Water HeaterSee “Filling the Outer (Boiler Water) Tank” and“Filling the Inner (Domestic Water) Tank on page11.

Draining Water HeaterDrain water heater if it will be shut off and exposedto freezing temperatures. Freezing water willexpand and damage water heater.

• If boiler water contains sufficientantifreeze, then only the domestic waterneeds to be drained.

Close boiler water isolation valves andrelieve system pressure to below 15 psig inouter tank before draining inner tank toprevent damage to inner tank.• If boiler water does not contain sufficient

antifreeze, then the boiler water anddomestic water must be drained.

WARNINGWARNING

WARNING

17

If antifreeze is used in boiler water, check concen-tration. Boiler water (including additives) must bepractically non-toxic, having toxicity rating orclass of 1, as listed in Clinical Toxicology ofCommercial Products. A maximum 50/50 mixtureof inhibited propylene glycol is recommended.Follow antifreeze manufacturer’s instruction.

Do not use automotive, ethylene glycol orpetroleum-based antifreeze. Do not useany undiluted antifreeze. This can causesevere personal injury, death or substantialproperty damage.

Water from opened drain valves, unionsand other connections may be extremelyhot. To avoid severe personal injury, deathor substantial property damage:- Tighten all drain hose connections.- Direct hot water away from all persons.

Draining Outer (Boiler Water) Tank1. Disconnect power supply to water heater.2. Close boiler water isolation valves between

boiler and water heater.3. Connect hose to boiler water drain valve at

water heater. Open and drain water to a safeplace.

4. To speed draining procedure, loosen air venton top of tank.

5. When draining is complete, close drain valveand retighten air vent.

Draining Inner (Domestic Water) Tank(See Domestic Piping Fig. 4 page 9)

1. Disconnect power supply to water heater.

- If outer (boiler water) tank pressure isgreater than 15 psig, relieve boiler pres-sure and close isolation valves before pro-ceeding.

2. Close system supply isolation valve.3. Connect a hose to domestic water drain valve

at cold water inlet. Hose should extend todrain at floor level to allow siphoning ofdomestic water tank.

4. Open hot water faucet at highest point aboveheater.

5. Open domestic water drain valve to startsiphoning.

6. When draining is complete, close hot waterfaucet and domestic water drain valve.

WARNING

WARNING

Water Heater Maintenance

18

Replacement Parts

3

2

1

Fig. 7: Excellence Domestic Components

Part Description Part Number

1 Drywell P3DW05

2 DHW Temp. Sensor PSRKIT63

3 Dip Tube P3WKITDT01

Replacement parts must be purchasedthrough a local ACV-Triangle Tube distrib-utor. When ordering part please provide themodel number and description and/or partnumber of replacement part. Use only gen-

uine ACV-Triangle Tube replacement partsto ensure warranty coverage and to avoiddamage to appliance and improper opera-tion of appliance. Contact ACV-TriangleTube at 856-228-8881 or www.triangle-tube.com for list of distributors nearest you.

WARNING

37 1

/2” [

953

mm

]24 3/4” [628 mm]

14 3/4” [377 mm]

12 1/4” [310 mm]

21 1/4” [540 mm]

16” [405 mm]

1/2 ” NPSC Boiler Drain

1/2” NPT Gas Connection

3/4” NPSC Pressure Relief Valve

3” Combustion Air Inlet

3” Vent Outlet

19” [479 mm]

11 3/4” [300 mm]

7 1/2” [190 mm]

1” NPT Boiler Return

1” NPT Boiler Supply

Water Heater Specifications

19

Front View PRESTIGE Excellence 110

11 3/4” [300 mm]

2 3/4” [70mm]

16 3/8” [416 mm]

7 3/4” [200 mm]

15 1/4” [390 mm]

1/2” NPT Gas Connection

1” NPT Boiler Supply1” NPT Boiler Return

1/2” NPSC Boiler Drain

3” Vent Outlet3” Combustion AIr Inlet

3/4” NPSC Pressure Relief Valve

21 1/4” [540 mm]

Water Heater Specifications

20

Side View PRESTIGE Excellence 110

3/4” NPT DHW Inlet

3/4” NPSC Aux. Connection (Rear)1/2” NPSC Air Vent Connection

3/4” NPT DHW Outlet11.1/4" [286 mm]

7 1/2" [190 mm]

3 1/2" [87 mm]

8 1/2"

[216

mm]4 3

/8"

[110 m

m]

Water Heater Specifications

21

Top View PRESTIGE Excellence 110

Water Heater Specifications

22

Performance

Notes:

Additional quality water heating equipment available from: ACV-Triangle Tube

TTP Brazed Plate Heat Exchangers

- For domestic water, snow melting, radiant floor,refrigeration

- Plates made of stainless steel, with a 99.9 % copperand brazed, ensuring a high resistance to corrosion

- Self cleaning and self descaling- Computerized sizing available from ACV- Triangle

Tube- Available in capacities from 25,000 BTU/hr to

5,000,000 BTU/hr- UL Listed

- Construction of high quality corrosion resistantstainless steel (AISI 316)

- Specially designed built-in flow restrictor to assuremaximum heat exchange

- Compact and light weight- Available in 8 sizes that can accommodate any size

pool or spa

Maxi-flo Pool and Spa Heat Exchangers

Triangle Tube - 1 Triangle Lane - Blackwood, NJ 08012 (856) 228 8881 Fax (856) 228 3584www.triangletube.com / [email protected].