prisma plus the tested switchboard, complying with standard iec 60 439-1
TRANSCRIPT
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 2
Contents
The functions of an electrical switchboard
The IEC 60439-1standard
Prisma Plus : a structured switchboard based on functional units
Forms: partitioning
Forms : separations within an assembly
The minimum requirements to guarantee the safety of a LV switchboard
The tests of standard IEC 60439-1
7 type tests performed by the manufacturer
3 routine tests performed by the panelbuilder
Switchboard builders and manufacturer, together for the safety challenge IEC 60439-1
Prisma Plus and the IEC 60439-1 standard : an international influence
The low voltage electrical switchboard
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 3
The low voltage switchboard
A vital link for electrical distribution
and to provide a continual balance between: the needs of safety and availability and the constraints of reliability and maintenability of the installation.
To satisfy the increasing needs of safety of people and equipment and availability of electrical power : its realization is not improvised…
Definitions
Safety
Maintenability
Reliability
Availability
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 5
The functions of an electrical switchboard To group and protect against external influences the protection and control devices and all their
electrical and mechanical connections.
To inform the end-user on the state of his installation
To protect the switchboard user against the risk of accidents (direct and indirect contact).
To evolve with the activity.
Definitions Cubicles up to 3200 AWall-mount and floor standing enclosures up to 630 A
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 7
The IEC 60439-1 standard
The IEC 60439-1 standard gives general rules for switchboards construction to meet with safety and availability needs required by the application
guarantees the minimum level of safety of people and equipment concerns the low-voltage switchgear and controlgear assemblies
for the power distribution and control. states :
- the service conditions (temperature...)
- the construction requirements (IP, IK, forms,...)
- the tests requirements
So conformity to the standard is, for the end user, an insurance on switchboard realization quality.
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 8
Prisma Plus :a structured switchboard based on functional units
This modular design brings much clearness to the switchboard : incoming unit current distribution units feeder units distribution units connection units communication units
Definitions Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 10
Forms: partitioning
Contents
In most installations, Prisma Plus cubicles do not require partitioning, Schneider Electric offering options and features that go well beyond the recommendations of the standard :
front plates requiring a tool to be removed doors providing access to live parts are keylocked systematic installation of terminal shields on Compact NS circuit
breakers and Interpact INS and INV switch-disconnectors upstream and downstream terminals on the incoming device are
covered
The protection of people and equipment is ensured on origin
However, Prisma Plus offers different levels of partitioning to create separations inside the cubicles and thus create Form 2,3 and 4, as defined by the standard.
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 11
Forms : separations within an assembly
Form 1 Form 2a Form 3a Form 4a
Form 2b Form 3b Form 4b Definitions
Prisma Plus
Prisma PlusPrisma Plus Prisma PlusContents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 13
The minimum requirements to guarantee the reliability of a LV switchboard
First of all, it must comply with standards :
Structural standards for incorporated switchgear : IEC 60947-1 : general provisions IEC 60947-2/3 : circuit-breakers/switches IEC 60269-1 : low voltage fuses.
Switchboard construction standard : IEC 60439-1 : low voltage switchgear assemblies.
Installation standards : IEC 60364 : buildings electrical installation specific standards and rules to each country.
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 14
The tests of standard IEC 60439-1
7 type tests : n°1 - temperature rise limits n°2 - dielectric properties n°3 - short-circuit withstand n°4 - protective circuit
effectiveness n°5 - clearances and creepage
distances n°6 - mechanical operation n°7 - degree of protection
3 routine tests : n°8 - overall inspection :
cabling, electrical operation n°9 - insulation/dielectric
test n°10 - protection measures .
They guarantee that the switchboard complies with standard and confirm its characteristics:
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 15
7 type tests performed by the manufacturer The aim of these tests is to confirm the switchboard
characteristics.
The 7 type tests are carried out on most difficult and unfavourable system Prisma Plus configurations. The assembled and cabled switchboards are made up of their usual components, connection system…, equipped with Merlin Gerin and Telemecanique switchgear and assemblied and installed according to inductrial standards
The tests are conducted either in approved laboratories (Asefa, Kema, Lcie,…), or in Schneider Electric ones
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 16
Test n°1(8-2-1) :Temperature rise limits
Guarantees the safety and reliability of the switchboard, by avoiding problems such as :
connection damages reduction in insulation performances risk of burn for maintenance operators electronic components damages faulty operation of the devices :
inopportune release
Results
Conditions
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 19
Test n°2 (8-2-2) : dielectric properties
Guarantees the switchboard safety and reliability , to avoid problems such as :
electrical arc generation insulation performance decreasing connection damages
Results
Conditions
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 22
Test n°3 (8-2-3) : short-circuit withstand
This test simulates an incident which could occur on site
Withstanding the short-circuit currents is : to avoid danger (rupture and projections of components, arc
generation and propagation outside the switchboard,...) it also means the installation can be quickly put back into operation
after the incident
Results
Conditions
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 25
Test n°4 (8-2-4) : effectiveness of the protective circuit
The effectiveness of the protective circuit is verified by two tests : resistance measurement of the connection between the exposed
conductive parts and the protective circuits short-circuit withstand performed between the protective conductor
and the nearest phase conductor.
Results
Conditions
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 28
Test n°5 (8-2-5) : clearance and creepage distances
Results
Conditions
Clearance control : shortest distance between two conductive parts.
Creepage distance control : shortest distance along the surface of an insulating material between two conductive parts.
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 31
Test n°6 (8-2-6) : mechanical operation
Results
Conditions
Endurance of material, guaranteeing the longevity of the various mechanisms.
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 34
Test n°7 (8-2-7) : degree of protection
Results
Conditions
The tests carried out define the capacity of an equipped switchboard to : protect persons against contact with live parts protect equipment against penetration of solid objects and liquids protect equipment against external influences such as impacts
(shocks).
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 37
The IP degrees of protection : (IEC 60529/EN 60529)
1st digit: protection of persons protection against solids.
2nd digit : protection against liquids.
Additional letter (optional) : protection of persons against contact with live parts
A : protect againts access of the back of the hand B : protect against access of fingers Ø 12 mm C : protect against access of a tool diameter 2.5 mm D : protect against access of a tool diameter 0.1 mm
Definitions Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 39
IK code : 2 digits giving the level of shock energy, in Joules : IK 01 : 0,14 IK 02 : 0,2 IK 03 : 0,35 IK 04 : 0,5 IK 05 : 0,7 IK 06 : 1 IK 07 : 2 IK 08 : 5 IK 09 : 10 IK 10 : 20.
Degree of protection :IK (IEC 62262)
The IEC 62262 standard defines a IK code which gives the equipment capacity to resist to mechanical impacts , on all the enclosure surfaces.
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 40
3 routine tests performed by the panelbuilder The 3 routine tests, easily and rapidly performed, must be carried out by the
panelbuilder. : overall inspection according to the mounting instructions and technical
documents (right device ratings, tightening torques) insulation checking by a dielectric test checking of protective measures and of the electrical continuity of the
protective circuits.
They complete the 7 manufacturer type tests and guarantee professionnalism and responsability of panelbuilder.
Schneider Electric supplies a full range of tools for assistance: Quality inspection guide switchboard assembly and installation guide Prisma Plus System P and G assembly guides
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 41
Test n°8 (8-3-1) : cabling, electrical operation
Results
Conditions
Check of mechanical actuating elements, interlocks, ... effectiveness
Check of connections adequate contact, especially screwed and bolted connections.
Check of proper laying of conductors and cables and proper mounting of device
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 44
Test n°9 (8-3-4) : insulation resistance / (8-3-2) : dielectric test
Results
Conditions
No arc flash-over or insulator perforation must be observed between the live parts each other and between the live parts and the conductive structural parts.
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 47
Test n°10 (8-3-3) : protective measures
Results
Conditions
Checking of protective measures and of the electrical continuity of the protective circuits for metallic assemblies
Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 50
Panelbuilder and manufacturer, together to offer maximum safety and realibility Manufacturer :
products tested in real configurations detailed instructions for fautless construction.
Installer : it has to its disposal informations, by means of tools of switchboard assembly and
installation guide (catalogs, internet) confidence in products and swichboards systems, the result of many years of
experience
A shared success : this complementarity must fall under the duration to consolidate our
professionalism.
Customers advantages Contents
Prisma Plus Tested switchboard Conf. V2- 04/04 - En 52
Prisma Plus and IEC 60439-1 standard : an international influence IEC 60439-1 : the same standard for all the professionals of
switchboards
Prisma Plus complying with the IEC 60439-1 standard: an international dimension.
UL
IEC
IEC
IEC
IEC
IEC
Contents