SINGLE-PHASE TRANSFORMERS
These transformers are to be located on the distribution networks for pole installation or in
substation networks for floor installation. Immersed in insulating oil to be connected in medium
voltage networks Phase-Phase or Phase-Neutral (up to 34.5kV), with maximum BIL of 200KV and
power ratings available from 3KVA up to 500KVA.
If it is required by the customer, surge arresters could be
provided to protect equipment in medium and low voltage.
These units are manufactured in compliance with ANSI C-
57.12.00, IEC-76, NTC and RETIE standards.
TRANSFORMADORES MONOFASICOS 15 kV
KVA Approximate Oil
Volume (Lt)
Approximate Weight (Kg)
Dimensions (mm)
A B C
5 28 91 421 825 504
10 35 108 457 850 540
15 45 146 480 920 563
25 63 221 543 940 626
37,5 70 256 543 1010 626
50 92 331 640 935 723
75 99 448 640 1090 733
100 120 607 770 1190 810
167 160 680 1060 1170 950
B
A C
PAG 1
Environmental Friendly Products
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
NOTE: The above dimensions are approximate, at the time of purchasing the equipment please request an update on the dimensions, as these may have varied.
THREE-PHASE TRANSFORMERS
These transformers are to be located on the distribution
networks for pole installation or in substation networks for
floor installation. Immersed in insulating oil for use in
networks with delta or wye connections with supply voltage
of up to 46 KV, maximum BIL of 250KV and available for
power ratings ranging from 15KVA to 5000KVA.
NA: Not applicable (these transformers do not have wheels, instead they come equipped with pole mounting device).
SINGLE-PHASE TRANSFORMERS 15 kV
KVA Approximate
Oil Volume (Lt)
Approximate Weight (Kg)
Dimensions (mm)
A B C D
15 62 161.6 660 770 522 NA
30 116 284 860 790 562 NA
45 107 316.9 860 820 542 NA
75 182 485 1155 845 572 NA
112.5 166 545.1 1150 890 632 NA
150 216 677 49.3 36.8 36.5 23.2
225 322 884 52 40.4 37.5 25.6
300 462 1193.5 56.8 44.3 42 28.7
400 494 1382 56.8 48.6 44.5 28.3
500 619 1770 60.4 52.2 43.3 28.3
630 739 2150 66.3 55.3 47.4 28.7
750 855 2485 67 58.5 47.2 29.9
1000 1083 3070 73 60.9 49.2 31.9
PAG 2
Productos amigables con el medio ambiente
NOTE: The above dimensions are approximate, at the time of purchasing the equipment please request an update on the dimensions, as these may have varied.
C A
B
D
D
If required by the customer, surge arresters could be installed to protect equipment in medium or low voltage. These units are manufactured in compliance with ANSI C-57.12.00, IEC-76, NTC and RETIE standards.
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
2011 R1
PAG-2
THREE-PHASE PAD MOUNTED TRANSFORMERS
CONFIGURATIÓN:
LIMITER FUSE
BAY-O-NET FUSIBLE
TRANSFORMER
LIMITER FUSE
BAY-O-NET FUSE
TRANSFORMER
OUTPUT ELBOWNS OR ELBOW
ARRESTERS
AT BT
Tra
ns
form
ers
PAG 3
They are transformers for indoor or outdoor installation
of dead front, which have connecting elements, protection and incorporated maneuver. They are used in cases where for security, space or aesthetic need to be fed with dry shielded underground cable by means of lift and they are installed on a concrete slab base or pedestal named. They have elements of a substation to protect the equipment:
Failures in the secondary network and external overload by fuses bayonet type removable interchangeable.
Failures primary overvoltage surge through elbow type.
In addition, the transformer protects the primary network of high current faults in the windings by limiting fuses or backup link isolation.
Manufactured in accordance to: ANSI C-57.12.25, ANSI C-57.12.26, ANSI C-57.12.28, ANSI C-57.12.29, NTC 5074 and RETIE standards.
INPUT ELBOWNS
AT BT
INPUT ELBOWNS
4 - POSITION SWITCH ON-OFF
OUTPUT ELBOWNS OR
ELBOW ARRESTERS
2 - POSITION SWTCH ON-OFF
INPUT ELBOWNS SWITCH
LIMITER FUSE
BAY-O-NET FUSE
TRANSFORMER
AT BT
RADIAL MODIFIED PAD MOUNTED TRANSFORMER – SINGLE LINE DIAGRAM
RADIAL PAD MOUNTED TRANSFORMER – SINGLE LINE DIAGRAM
LOOP TYPE PAD MOUNTED TRANSFORMER – SINGLE LINE DIAGRAM
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
THREE-PHASE PAD MOUNTED TRANSFORMERS
THREE-PHASE PAD MOUNTED RADIAL TRANSFORMERS 15 - 25 kV
KVA Approximate Oil
Volume (Lt)
Approximate Weight (Kg)
Dimensions (mm)
A B C D E
30 253 552 1050 1310 970 470 350
45 296 637 1070 1340 1000 470 380
75 318 744 1100 1340 1000 470 380
112.5 405 919 1100 1340 1000 470 480
150 429 995 1145 1340 1195 470 480
225 560 1251 1270 1400 1290 470 540
300 682 1548 1320 1400 1395 470 610
400 694 1775 1390 1400 1340 470 590
500 798 2072 1440 1540 1415 470 600
630 989 2527 1530 1620 1480 470 630
750 1105 2867 1660 1640 1450 470 620
1000 1432 3590 1680 1790 1560 470 710
C
D E
A
B
PAG 4
NOTE: The above dimensions are approximate, at the time of purchasing the equipment please request an update on the dimensions, as these may have varied.
These units are available in powers ratings of up to 3000 KVA. Voltage supply ratings of up to 34.5 GRDY / 19.92 KV and 150 KV maximum BIL.
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
THREE PHASE LOOP TYPE PAD MOUNTED
THREE-PHASE PAD MOUNTED MESH TRANSFORMERS 15 - 25 kV
KVA Approximate Oil
Volume (Lt)
Approximate Weight (Kg)
Dimensions (mm)
A B C D E
30 253 552 1050 1310 970 470 350
45 296 637 1070 1340 1000 470 380
75 432 887 1300 1460 900 470 380
112.5 549 1082 1310 1460 1000 470 480
150 576 1165 1360 1460 1160 470 480
225 732 1446 1410 1540 1220 470 540
300 884 1760 1480 1540 1330 470 610
400 908 2030 1540 1540 1385 470 600
500 951 2250 1540 1540 1330 470 600
630 1121 2657 1660 1620 1410 470 630
750 1235 3010 1800 1640 1440 470 620
1000 1596 3770 1820 1790 1560 470 710
Tra
ns
form
ers
PAG 5
NOTE: The above dimensions are approximate, at the time of purchasing the equipment please request an update on the dimensions, as these may have varied.
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
SINGLE-PHASE PAD MOUNTED TRANSFORMER
These units are available in powers ranging from 15 KVA up to 500 KVA, and voltage rating up to GRDY 34.5 / 19.92 kV and up to 150 kV BIL.
SINGLE-PHASE PAD MOUNTED RADIAL TRANSFORMERS 15 - 25 kV
KVA Approximate Oil
Volume (Lt)
Approximate Weight (Kg)
Dimensions (mm)
A B C
25 162 375 946 915 863
37,5 187 430 946 915 920
50 214 441 986 915 945
75 252 629 986 935 1010
100 262 701 986 935 1031
167 387 935 1046 1155 1012
B
A
C
PAG 6
NOTE: The above
dimensions are approximate, at the time of purchasing the equipment please request an update on the dimensions, as these may have varied.
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
SELF-PROTECTED (SP CP CSP) TRANSFORMERS
PAG 7
These are Single-phase or three-phase transformers which have protection elements against overloads, external short circuits in the low voltage network and surges. These units also have oil immersed fuses in the high voltage side to insulate them from the electric grid in case of internal faults. Single-Phase transformers available in the following power ratings: • Power ranging from 5 kVA up to 167.5 kVA, with secondary voltage of 240/120 V. • Powers up to 333 KVA, with secondary voltage of 480/240. Three-Phase transformers are available in the following power ratings: • Powers ranging from 15 KVA up to 225 KVA, with secondary voltage of 220/127 V. • Powers ratings of up to 1000 kVA, with secondary voltage of 440/254 V. These transformers are manufactured in compliance with ANSI C57.12.00, IEC-76 and GTC148 standards.
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
SUBMERSIBLE TRANSFORMERS
PAG 8
These submersible transformers are available in capacities of up to 3000 KVA
for three-phase transformers and up to 500 KVA for single-phase transformers.
High voltage rating up to 34,5 GrdY/19.92 KV and 150 KV BIL.
These units are designed to operate in a chamber or under ground level vault
and subject to maximum possible flooding period of 24 hours under a water
column of 40 cm above the top of the transformer.
Theses transformers are equipped with substation elements in order to protect
the equipment:
Failures in the secondary network and external overload by means of
interchangeable bayonet type removable fuses.
Failures in the primary network by means of elbow arresters.
In addition, the transformer protects the primary network of high current faults
in the windings by means of current limiting fuses or backup isolation link.
These transformers can be supplied with one of the following configurations:
Radial configuration: End of medium voltage circuit, with load switch open-
closed.
Loop configuration (To continue the medium voltage circuit) with 4-position
switch.
These transformers are manufactured in compliance to: ANSI C-57.12.23,
ANSI C-57.12.24, NTC 4406 and RETIE standards.
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
DRY TYPE TRANSFORMERS
Low voltaje dry type transformers
Medium voltage dry type transformer
PAG 9
Single phase and three phase transformers with power ratings from 1KVA up to 500KVA, and voltages levels of up to 600 volts. These units are designed to operate indoors (enclosure with IP20 protection) or outdoor (IP23 protection cabinet). These units are cooled by natural circulation of air and have self-extinguishing high temperature insulation (class H-180°C) to reduce the risk of fire in case of external events, short circuit or overvoltage. Used in residential, commercial or industrial applications, with optimum efficiency, low loss and low noise level. These units are manufactured in compliance with NTC 3445 standard.
Air-cooled three-phase transformers, manufactured from 75KVA up to 630 KVA with standard voltage ratings of up to 15KV. Its active part is designed with copper or high-purity aluminum windings and stack core grain oriented silicon steel with low losses, allowing it to withstand the high temperature levels to which the transformer is exposed to when connected to a load. These units have self-extinguishing high temperature insulation (Class H-180 ° C) to reduce the risk of fire in case of external events, short circuit or overvoltage. These transformers are useful for raising or lowering voltage levels, in residential, commercial or industrial applications. Rymel´s dry-type transformers offer optimum efficiency, low losses level, and minimum noise levels.
Advantages and Applications:
Due to its lower weight (compared to an oil unit) it allows to be located inside buildings and/or elevated floors.
Its Self-extinguishing insulating material allows the dismissal of fire-proof rooms.
These units have a cheaper construction permit and their maintenance is easier compared to oil immersed transformers.
These transformers have no tank, given the fact that they are located in a substation cabinet.
Used in places where we want to minimize the environmental impact caused by insulating liquids.
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
2-WAY JUNCTION ENCLOUSURE 3-WAY JUNCTION ENCLOUSURE
4-WAY JUNCTION ENCLOUSURE 5-WAY JUNCTION ENCLOUSURE
JUNCTION ENCLOUSURES
Tra
ns
form
ers
PAG 10
It is dead-front switching equipment, immersed in oil with a group of high voltage elastomeric connectors and disconnectors whose function is to allow operability of different load circuits on medium voltage power systems.
It can be used for single-phase or three-phase applications, with 2, 3, 4, 5, 6 or 7 junction points. With current capacity of 200 and/or 600 A, voltage ratings of up to 34,5 GrdY/19,92 KV and 150 KV BIL. Conventional and submersible junction enclosures manufactured in accordance to ANSI C-57.12.25, ANSI C-57.12.26, ANSI C-57.12.28, ANSI C-57.12.29, NTC 5110 and RETIE standards.
OUTPUT INPUT
INPUT
DERIVATION
OUTPUT
INPUT
OUTPUT
DERIVATION
INPUT
OUTPUT
DERIVATION
DERIVATION
DERIVATION
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
Environmental Friendly Products
Descriptión
Objetive Electrical features
Rated Voltage Levels 15 - 27- 38 KV
Nominal Frequency 60 Hz
ESPECIFICATIONS
Maximum diameter 68 mm
High 55 mm
Diameter for driver input 21 mm
Colors Light Grey
PAG 11
WILDLIFE PROTECTOR COVER
For more information visit our website www.rymel.com.co and our telephone line (57) (4) 4440430 in Colombia.
It is a device for protecting live parts of the terminal insulators bushings in different equipment installed in the power distribution system and which may be exposed to potential contact by animals or people.
This wildlife protector cover is used in the insulators installed on distribution transformers, regulators, switches, load break switches, lighting arresters, and others to prevent birds, reptiles, rodents and other animals to cause short circuits or faults between phases or between phase and earth that could affect the quality of service and increase the costs of operation and maintenance. It is made of a material which is resistant to ultraviolet radiation, tracking, abrasion, shear, to carbonization, to cracking and deposition of feces of animals, it has high impact strength (not less than IZOD of 160.1 Joule / m), has a maximum water absorption capacity of 0.09% by weight and a minimum dielectric strength of 300V / mL. It aims to increase the insulation level of the structure and increase the leakage distance phase to earth.
Environmental Friendly Products