BT. 02.34 Q5/E
Process controllerwith PROFIBUS DPand Modbus Master/Slave 1/4 DIN - 96 x 96 mmgammadue® series Q5 lineSophisticatedmultifunctionprocess controllerwith high levelcommunicationsBy its three different kinds ofserial communications:• PROFIBUS DP Slave• Modbus Master• Modbus Slave,the gammadue® Q5 line caninterface, on different levels,with other devices, by exchanginginformations, after processingthem by mathematical package.The frequency input, added to the traditional inputs, two retransmission or control analogue outputsand four programs allow you touse it for the most diversifiedcontrol strategies.
ISO 9001 Certified
E
ULC US
LISTED
BT-Q5-ING 11-11-2003 17:29 Pagina 1
Tuning
Fuzzy-Tuning Two methods of initial tuningare available:- Auto-Tuning ”one shot“- Natural frequency ”one shot“The Fuzzy-Tuning automaticallyselects one of the two methodswhich assure the best resultfor each condition.
The Auto-Tuning method worksbest on the step responsebasis.When activated, if a deviationexists between the Setpointand process variable largerthan 5% of scale range, thecontroller modifies the outputvalue. Then, in a short time, itcalculates the PID parametersand the new algorithm isoperational immediately .The main advantages of thismethod are fast calculationand quick implementation.
The Natural frequency methodworks best when the processvariable is very near to theSetpoint. When activated, itcauses a process oscillationaround the Setpoint value.The main advantage of thismethod is a reduceddisturbance to the process.
Adaptive-TuningIt is self-teaching and waits forprocess change to recalculatethe new PID parameters.The new PID calculation does not influence the controloutput, avoiding anydisturbance.The PID optimisation is done only when necessary (e.g. Setpoint changes orprocess disturbances like loadchanges). No action by the operator isrequired.The operating mode ofAdaptive-Tuning is safe anduser friendly. It tests theprocess response after adisturbance, it memorises theintensity and frequency of thereaction, then the Adaptive-Tuning checks the newinformation with its statistical data base.The correct PID algorithm isthen ready to implement.This tuning is ideal for non-linear processes where the PIDparameters must be adapted to changing conditions.
SP
Start of autotuneoperation
PV variable
Control output
Setpoint change End of the tuningoperating and setting of
the new calculatedterms.
Disturbance
Newterms
PV variable
Control output
Tuning start
End of the tuningoperating and setting of
the new calculatedterms.
Configuration software
A software tool is available toimprove both the configurationand the parameterization. All the data can be stored to file. It is also possible to down-load the linearisationof the “custom” input by using the polynomial’scoefficients and to configure the PROFIBUS DP profile file.
Memory chip
The memory chip makespossible a fast and safe transfer of data related to the configuration and all parameters.With a simple operation, the information can be storedand copied to the memory chip.The procedure can beprotected by a password.
Integrity in data copy
Setpoint programmer
300
250
200
150
100
50
350
1° 2° 3° 4° 5° 9° 10° 11/12° 13° 14° End
300 50 70 80 110 170 190 210 230 250 time
t1 t2 t3 t4 t5 t9 t10 t11/t12 t13 t14
Segment Initial
Time t0
Programstart
SP0
°C Setpoint
SP1
SP2
SP3
SP4 SP9SP10
SP11
SP13SP12
Maximumallowed
deviation
band
SPF
SP14
Up to 4 profiles with 16segments can be programmed.Number of cycles as well asthe max. allowed deviation canbe configured.The time base can be selectedfrom seconds, minutes and hours. Run, Hold and Stopfunctions can be performed by means the front keypad,by external commands or by serial communications.
memory chip
Two methods of tuning are available:- one shot initial Fuzzy-Tuning- self-teaching continuous Adaptive-Tuning
2
BT-Q5-ING 11-11-2003 17:29 Pagina 3
Fast view
The Fast view is apassword protectedreview procedure of the 10 most usefulparameters. The combination of aluminous andcomprehensive displayand the ergonomickeypad allows theimmediate access tothe Fast view.
PROFIBUS DP SlaveIndustrial standard forperipheral devices connectionto a machine in a plant.
The protocol installed in thiscontroller, offers the followingadvantages against thestandard normallysupplied by other suppliers:• Communications baudrate
Up to 12 Mb/s with electricisolation
• The list of data transfer(profile file) is userconfigurable. It can be set by means the gammadue®
configuration software.
3
The mathematical package isable to process any information
there is in the controller by using a simple set of mathematical operations.For instance it can comparetwo values by selecting higheror lower, to do the sum or the ratio and so on.Together with Modbus Master,it becomes a very powerful information handler;
it can, for example, send to different controllers thesame Setpoint profile withdifferent values forevery controller.
Modbus serialcommunications allows a controller to exchangeinformations with otherdevices, gammadue® series or others with Modbus Slaveserial communications (PLC).For instance it is possible toread the acquired value from agammadue® C1 indicator withalarms and send this value as remote Setpoint to a gammadue® X3 controller; or the gammadue® Q5 controllercan send the Setpoint profile of the running program to manyX1 or Q1 controllers withoutSetpoint programmer function.An Q5 controller can realize a
simple network for the lowlevel data management. The Q5 can also reducethe work of the SCADA and grant the exchange of data in case of its failure.
Modbus Master Mathematical package
Self-configuring supervision software. Major features includemonitoring and control of the connected devices, the visualisationby means of instrument faceplates, trend and mimic pages, data archiving as well as report generation. A self-configuring tool automatically polls the connected devices and build up the application software, reducing the start-up costs.
AutoLink
BT-Q5-ING 11-11-2003 17:29 Pagina 4
High speed data acquisition and signal management
Use of differents actuators
Process with time variable characteristic
Alarm signalling and diagnostic
Interfacing with other devices
Temperature profile
Safe and reproducible configuration and parameter settings
Environmental protection
Noise immunity
Universal input signals, linear as well as non-linear
Reliability and safety
Technical support
Our solutionsYour needs
Sampling time: 100 msmeasure update time: 50 ms
Two analogue outputs, heat/cool (linear, water, oil), valve controloutput with potentiometer position feedback
Two initial and one continuous calculations of the right controlparameters
Absolute, band and deviation alarm, Latching/Blocking, loop breakalarm
Serial communications at 19,200 baud Modbus/Jbus Master andSlave, PROFIBUS DP at 12 Mbaud, two retransmission outputs,Remote Setpoint input, three digital inputs
4 program with 16 segments, 3 stored Setpoints
Memory chip for data transfer and storing, configuration andparameterisation software
IP65 front panel protection (indoor, dust and water protection)
Electromagnetic compatibility
Configurable input (TC, RTD, mA, Volt and ∆T, infrared sensor,“custom” linearisation, frequency input up to 20 kHZ)
CE compatibility, ASCON is ISO 9001 certified, 3 years warranty
Technical application assistance from ASCON sales and after sales service
4
gammadue®
the right solution to your needs
Main universal input
Control Alarms Retransmission
Resources
PV
AUX
IL1IL2IL3
OP1
OP2
OP3
OP4
OP5
OP6(option)
Q5
Setpoint Continuous tuning
Adaptive
Operating mode
Memory ChipData Copy/Data Store
(option)
2 OP5 OP1 OP2 OP3 OP4 OP6
3 OP1 OP2 OP3 OP4 OP5 OP6
4 OP1 OP5 OP2 OP3 OP4 OP6
5 OP5 OP2 OP1 OP3 OP4 OP6
1 OP1 OP2 OP3 OP4 OP5 OP6
6 OP5 OP6 OP1 OP2 OP3 OP4
Auxiliary input
Three digital inputs
PV/SP
Modbus RS485 MasterLink to otherinstruments(option)
Modbus RS485 SlaveParameterisationSupervision(option)
IL1, IL2 or IL3 connected functions
Fuzzy tuning with automatic selection
One shotAuto tuning
One shotNatural Frequency
(option)
Singolaction
Doubleaction
(option)
7 Valve OP1 OP2 OP3 OP4 OP5 OP6
BT-Q5-ING 11-11-2003 17:29 Pagina 5
Features(at 25°C T. env.amb.)
Description
Technical data
Totalconfigurability
Auxiliary inputs
Digital inputs3 logic
Operating modeand Outputs
Control mode
PV input (for signalranges see table 1)
From keypad or serial communication the user selects: - the type of input - thetype of Setpoint - the type of control algorithm - the type of output - the type andfunctionality of the alarms - control parameter values - access levels
A/D converter with resolution of 160.000 pointsCommon Update measurement time: 50 mscharacteristics Sampling time (max. update time of the output adjustable):
0.1…10.0 s. Configurable - Input shift: - 60…+ 60 digitInput filter with enable/disable: 0.1…999.9 seconds
Accuracy 0.25% ± 1 digits for temperature sensors Between 100 and0.1% ±1 digits (for mV and mA) 240V~error is minimal
Resistance Pt100Ω at 0°C 2 or 3 wires Max. wire Res.: 20 Ω max.thermometer (IEC 751) connection (3 wires) Sensitivity:(for ∆Τ: R1+R2 °C/°F Burnout (with any 0.1°C/10°C E. T.must be <320Ω) selectable combination) <0.1°C/10 Ω Wire Res.
L,J,T,K,S,R,B,N,E, Internal cold junction Line: 150Ω max.W3,W5 (IEC 584) compensation with NTC Input drift:
Thermocouple Rj >10MΩ Error 1°C/20°C <2µV/°C Env. Temp.°C/°F ± 0.5°C Burnout <5µV/10Ω Wire Res.selectable4-20mA, 0-20mA Burnout. EngineeringDC input (current) Rj >30Ω units, conf. decimal0-50mV, 0-300mV point, position with Input drift:Rj >10MΩ or without √ <0.1% / 20°C Env. Temp.DC input (voltage) 1-5, 0-5, 0-10V <5µV/10Ω Wire Res.Rj >10kΩ I. Sc.: -999…9,999
Frequency (option) Low level ≤2V F. Sc.: -999…9,9990-2.000 / 0-20.000Hz High level 4-24V (min. range of 100 digit)
Current0/4-20mA Bias in engineering units and ±rangeRemoteSetpoint Rj = 30Ω Ratio from -9.99…+99.99not isolated Voltage Local + Remote Setpointaccuracy 0.1% 1-5, 0-5, 0-10VRj = 300kΩ
Potentiometer from 100Ω to 10kΩ Feedback valve positionThe closure of the Auto/Man mode change, Local/Remote Setpoint mode change,external contact 3 Stored Setpoint activation, keyboard lock, measure hold,produces any slope inhibit and output forcingof the following Program Run/Hold and selection (if option installed)actions:
1 single or double action PID loop or On/Off with 1, 2, 3 or 4 alarms
Algorithm PID with overshoot control or On/Off, valve drive PIDalgorithm to control motorised positioners
Proport. band (P) 0.5…999.9%Integral time (I) 1…9,999 sDerivative time (D) 0.1…999.9 s
Error dead band 0.1…10.0 digit
enableddisabled
Overshoot control 0.01…1.00Manual reset 0…100%Cycle time (Time 0.2…100.0 s Single actionpoportional only) PID algorithm Min./Max 0…100% separately adjustableoutput limitsControl output 0.01…99.99%/srate limitSoft-start 1…100% output value time 1…9,999 sOutput safety -100…100%
enabled
valuedisabled
Control output -100…100%forcing valueControl output 0…5% Span in engineering units On/Off algorithmhysteresisDead band 0.0…5.0%Cool proportional 0.5…999.9%band (P)Cool integral 1…9,999 stime (I) Double actionCool derivative 0.1…9,999 s
enabledPID algorithm
time (D) disabled
(Heat/Cool)Cool cycle time (Time 0.2…100.0 sproportional only)Cool control 0…100%output high limitCool output 0.01…99.99/smax. rate
5
Input type Scale range-99.9…300.0 °C-99.9…572.0 °F-200…600 °C-328…1112 °F-50.0…50.0 °C-58.0…122.0 °F
0…600 °C32…1,112 °F0…600 °C
32…1,112 °F-200…400 °C-328…752 °F
0…1,200 °C32…2,192 °F0…1,600 °C
32…2,912 °F0…1,600 °C
32…2,912 °F0…1,800 °C
32…3,272 °F0…1,200 °C
32…2,192 °F0…600 °C
32…1,112 °F0…1,100 °C
32…2,012 °F0…2,000 °C
32…3,632 °F0…2,000 °C
32…3,632 °F
Configurableengineering units
mA, mV, V, bar, psi, Rh, ph
On request 0...2kHz or 0...20kHz
RTD Pt100 IEC751
RTD 2xPt100 IEC751 per ∆TTC L Fe-ConstDIN43710TC J Fe-CU45% NIIEC584TC T Cu-CuNiIEC584TC K Chromel-AlumelIEC584TC S Pt10% Rh PtIEC584TC R Pt13% Rh PtIEC584TC B Pt30% Rh Pt 6%IEC584TC N Nicrosil-NisilIEC584TC E Ni10% CR CuNiIEC584
TC NI-NiMo18%
TC D W3%Re 25%ReIEC584TC C W5%Re W26%ReIEC5840/4…20 mA0…50/300 mV0/1…5 V0…10 VCustom scaleFrequency (option)
Table 1: PV input
BT-Q5-ING 11-11-2003 17:29 Pagina 6
Features(at 25°C T. env.amb.)
Description
Technical data
OP1-OP2outputsOP3 outputOP4 output
Analogue /digitalOP5 and OP6(option) outputs
AL1- AL2 - AL3AL4 alarms
Setpoint
ProgrammableSetpoint(optional)
Tuning
Auto/Manselection
Serial comm.s(option)
Auxiliary supply
Operationalarm safety
Generalcharacteristics
Motor travel time 15…600 sMotor minimum step to 0.1…5.0% Valve drive PID algorithmFeedback potentiometer 100Ω…10kΩSPST relay N.O., 2A/250V~ for resistive loadTriac, 1A/250V~ for resistive loadSPDT relay N.O., 2A/250V~ for resistive loadSPST relay N.O., 2A/250V~ for resistive load
Galvanic isolation: Control 500V~ /1 min. Analogue: 0/1...5V, 0...10V, 500Ω / 20mA max.retransmission Short circuit 0/4…20mA, 750Ω /15V max.of PV/SP protected Digital: 0/24V- ±10% - 30mA max.
Resolution 12 bit for solid state relayAccuracy: 0.1%
Hysteresis 0…5% Span in engineering unitsActive high Action
Deviation threshold ±range
Active low type Band threshold 0…rangeAbsolute threshold whole range
Action Sensor break, heater break alarmSpecial Acknowledge (latching), activation inhibit (blocking)functions
OP3, OP4 connected to Timer or Program (if option installed)Local + 3 stored Up and down ramps 0.1…999.9 digit/min or digit/hRemote only (OFF=0)Local and Remote Low limit:Local with trim from low range to high limitRemote with trim High limit:
Programmable If option from low limit to high rangeinstalled Remote Setpoint not available with frequency input
4 programs, 16 segments (1 initial and 1 end)From 1 to 9999 cycles or continuous cycling (OFF)Time values in seconds, minutes and hoursStart, stop, hold, etc. activated from the keypad, digital input and serial lineFuzzy-Tuning type. The controller selects automatically Step responsethe best method according to the process conditions Natural frequency
Adaptive Tune self-learning, not intrusive, analysis of the process response toperturbations and continuous calculation of the PID parameters
Standard with bumpless function,by keypad, digital or serial communicationsRS 485 isolated, SLAVE Modbus/Jbus protocol, 1,200, 2,400, 4,800, 9,600, 19,200 bit/s3 wires.RS 485 isolated, MASTER Modbus/Jbus protocol, 1,200, 2,400, 4,800, 9,600, 19,200 bit/s3 wires.RS485 asynchronous / isolated, PROFIBUS DP protocol, from 9,600 bit/sat 12MB/s selectable, max. lenght 100 m (at 12 Mb/s).
+24– ± 20% 30mA max. - for external transmitter supply
Measure Detection of out of range, short circuit or sensor break withinput automatic activation of the safety strategies and alerts on displayControl Safety and forcing value separately adjustable: -100%…100%output
Parameters Parameter and configuration data are stored in a non volatile memory for an unlimited time
Access Password to access the configuration and parameters dataprotection Fast view
Power supply 100-240~ (-15% + 10%) 50/60Hz or Power
(fuse protected) 24~ (-15% + 25%) 50/60Hz and 24V– (continuous) consumption(-15% + 25%) 5W max.
Safety Compliance to EN61010-1 (IEC1010-1), installation class 2 (2,500V)pollution class 2, instrument class II
Electromagnetic Compliance to the CE standardscompatibilityUL and cUL File E176452ApprovalProtection IP65 front panelEN60529 (IEC529)Dimensions 1/4 DIN - 96 x 96, depth 110 mm, weight 500 g approx.
Electrical wirings
Control mode
6
Dimensions
96 mm3.78 in
110 mm4.33 in
10 mm max.0.39 in max.
10 mm max.0.39 in max.
96 mm3.78 in
Panel cut-out
92+
0.8
mm
3.62
+0.
031
in
113
mm
min
4.45
in
min
92+0.8 mm3.62+0.031 in
103 mm min4.05 in min
C
N
L1
2
3
4
5
6
7
8
9
10
11
12
19
20
23
24
25
26
27
28
29
30
31
32
33
34
35
36TC
NC
C
NO
OP3
NO
C
NO
OP1
OP2
OP4
DG
IN2(opion)
OP6(option)
24V—OUT
1
2
3
A
b
B
RTD
13
14
15
16
17
18
21
22 N/C
LOG
ICIN
PU
TP
rofib
us
VP
DP
DN
OP
5
RS
485
(mas
ter)
IN1
C RS
485
(Sla
ve)
POT
0%REM
NO
C
BT-Q5-ING 11-11-2003 17:29 Pagina 7
If not differently specified the controller will be supplied with standard versionModel: Q5 3100-0000
Power supply Outputs Serial/Mathematical packageOptions Setpoint programmableInstr. handbook Colour
Line Basic model Accessories
_• • • • • • •
A B C D E F G 0Q5
Ordering codes
Power supply100-240V~ (-15% +10%)24V~ (-25% +12%) or 24V– (-15% +25%)
OP1-OP2 outputsRelay-RelayTriac-Triac
Serial communications/Mathematical packageNot fittedMathematical package RS 485 Modbus/Jbus SLAVE + Mathematical packageRS 485 Modbus/Jbus SLAVE+MASTER + Mathematical packagePROFIBUS DP SLAVE + Mathematical packageRS 485 Modbus/Jbus SLAVE+PROFIBUS DP SLAVE + Mathematical package
OptionsNoneFrequency input (Remote Setpoint not available)Second analogue/digital output (OP6)Frequency input + second analogue output (OP6) (Remote Setpoint not available)
Setpoint programmerNot fittedFour “16 segments” programs
Instruction handbookItalian-English (std)French-EnglishGerman-EnglishSpanish-English
Front case colourDark (std)Beige
A350B15
C015678
D0146
E04
F0123
G01
7
Model:
BT-Q5-ING 11-11-2003 17:29 Pagina 8
ASCON spa
20021 Bollate(Milano) ItalyVia Falzarego, 9/11Tel. +39 02 333 371Fax +39 02 350 4243http://www.ascon.ite-mail [email protected]
ASCON FRANCE2 bis, Rue Paul Henri Spaak
ST. THIBAULT DES VIGNES
F-77462 LAGNY SUR
MARNE - Cedex
Tél. +33 (0) 1 64 30 62 62
Fax +33 (0) 1 64 30 84 98e-mail [email protected]
AGENCE SUD-EST
Tél. +33 (0) 4 74 27 82 81
Fax +33 (0) 4 74 27 81 71
WORLDWIDE NETWORK OFDIRECT SALES CENTRES,DISTRIBUTORS AND VARs
EuropeBelgium, Cyprus, Croatia, Czech Rep, Finland, France, Germany, Great Britain, Greece,Holland, Ireland, Norway, Poland,Portugal, Romania, Russia, Slovenia, Spain, Sweden, Switzerland, Turkey, Ukrain
AmericasArgentina, Brazil, Canada, Chile,Colombia, Ecuador, Peru, United States
Over the worldAustralia, China, Egypt, Hong Kong,India, Iran, Israel, Malaysia, New Zealand, Pakistan, Saudi Arabia,Singapore, Taiwan, Thailand,South Africa & South East Africa
BT-Q5-ING 11-11-2003 17:29 Pagina 2