process management system - siemens.de · • the pm-quality server communicates with the remote...
TRANSCRIPT
Unrestricted © Siemens AG 2019
siemens.com/process-managementUnrestricted © Siemens AG 2019
Process Management System Redundancy scenarios
Unrestricted © Siemens AG 2019
Redundancy scenarios
• PM-CONTROL (Option A: Stand-alone server)
• PM-CONTROL (Option B: Cold standby)
• PM-QUALITY (Option A: Stand-alone server)
• QUALITY (Option B: Data Center)
• PM-CONTROL + PM-QUALITY (Option A: Stand-alone server)
• PM-CONTROL + PM-QUALITY (Option B: Stand-alone PM-CONTROL + PM-
QUALITY Data Center)
Unrestricted © Siemens AG 2019
PM-CONTROL
Option A: Stand-alone PM-CONTROL serverUnrestricted © Siemens AG 2019
Unrestricted © Siemens AG 2019
PM-CONTROL redundancy option AStand-alone PM-CONTROL server
WinCC Competence Center Mannheim
WinCC RC/RT + Redundancy
PM-CONTROL Client (optional)
PM-AGENT
WinCC RT / Stand-alone SQL Server
PM-CONTROL Server
WinCC RT / Client
PM-CONTROL Client (optional)
WinCC RC/RT + Redundancy
PM-CONTROL Client (optional)
PM-AGENT
Unrestricted © Siemens AG 2019
• The PM-CONTROL server communicates with the remote WinCC servers via PM-AGENT. If one of the WinCC
servers isn’t available, the communication will switch to the second server.
• The relevant recipe data and/or jobs will be managed through the PM-CONTROL server on the separated computer.
The recipe data will be downloaded from the separated PC to the WinCC servers.
• A PM-AGENT license is required on both WinCC servers.
• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with
PM-CONTROL). Alternatively a local WinCC RT installation will also provide the necessary SQL Server installation.
PM-CONTROL redundancy option AStand-alone PM-CONTROL server
WinCC Competence Center Mannheim
Unrestricted © Siemens AG 2019
-Z*: -Z U02 = USB-Dongle; -Z S03 = License file
PM-CONTROL redundancy option AStand-alone PM-CONTROL server
WinCC Competence Center Mannheim
Required licenses
2x PM-AGENT 9AE7117-2SS01-1AA0-Z*
1x PM-CONTROL Type S Compact
OR
1x PM-CONTROL Type S Standard
OR
1x PM-CONTROL Type S Professional
9AE7110-2SS10-1AA0-Z*
9AE7110-2SS20-1AA0-Z*
9AE7110-2SS30-1AA0-Z*
Optional licenses
PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*
Unrestricted © Siemens AG 2019
PM-CONTROL
Option B: PM-CONTROL server + cold standbyUnrestricted © Siemens AG 2019
Unrestricted © Siemens AG 2019
PM-CONTROL redundancy option BPM-CONTROL server + cold standby
WinCC Competence Center Mannheim
WinCC RC/RT + Redundancy
PM-CONTROL Server
Copy Project
WinCC RT / Client
PM-CONTROL Client (optional)
WinCC RC/RT + Redundancy
PM-CONTROL Server
Copy Project
Unrestricted © Siemens AG 2019
• A PM-CONTROL server is located on both WinCC servers. Due to technical restrictions only one PM-CONTROL
server may be active at the same time, though. The relevant recipe data and/or jobs will be managed through the
currently active PM-CONTROL server. The recipe data will be downloaded to the local WinCC server.
If the active server is shut down for any reason, PM-CONTROL has to be started on the second server.
• The duplication of the database has to be performed in the background by using the WinCC Tool „Copy Project“
• All relevant functionality like the management of the startup of PM-CONTROL, the switch in case of a system outage
as well as the synchronization of the databases has to be performed either manually or by custom scripts. This
means there is no automatic synchronization between the two PM-CONTROL servers.
PM-CONTROL redundancy option BPM-CONTROL server + cold standby
WinCC Competence Center Mannheim
Unrestricted © Siemens AG 2019
-Z*: -Z U02 = USB-Dongle; -Z S03 = License file
PM-CONTROL redundancy option BPM-CONTROL server + cold standby
WinCC Competence Center Mannheim
Required licenses
2x PM-CONTROL Type S Compact
OR
2x PM-CONTROL Type S Standard
OR
2x PM-CONTROL Type S Professional
9AE7110-2SS10-1AA0-Z*
9AE7110-2SS20-1AA0-Z*
9AE7110-2SS30-1AA0-Z*
2x Copy Project 9AE7141-2SS01-1AA0
Optional licenses
PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*
Unrestricted © Siemens AG 2019
PM-QUALITY
Option A: Stand-alone PM-QUALITY serverUnrestricted © Siemens AG 2019
Unrestricted © Siemens AG 2019
PM-QUALITY redundancy option AStand-alone PM-QUALITY server
WinCC Competence Center Mannheim
WinCC RC/RT + Redundancy
PM-QUALITY Client (optional)
PM-AGENT
WinCC RT / Stand-alone SQL Server
PM-QUALITY Server
WinCC RT / Client
PM-QUALITY Client (optional)
WinCC RC/RT + Redundancy
PM-QUALITY Client (optional)
PM-AGENT
Unrestricted © Siemens AG 2019
• The PM-QUALITY server communicates with the remote WinCC servers via PM-AGENT. If one of the WinCC
servers isn’t available, the communication will switch to the second server.
• The PM-QUALITY database with the archived batch data is stored on the separated computer.
• A PM-AGENT license is required on both WinCC servers.
• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with
PM-QUALITY). Alternatively a local WinCC RT installation will also provide the necessary SQL Server installation.
PM-QUALITY redundancy option AStand-alone PM-QUALITY server
WinCC Competence Center Mannheim
Unrestricted © Siemens AG 2019
-Z*: -Z U02 = USB-Dongle; -Z S03 = License file
PM-QUALITY redundancy option AStand-alone PM-QUALITY server
WinCC Competence Center Mannheim
Required licenses
2x PM-AGENT 9AE7117-2SS01-1AA0-Z*
1x PM-QUALITY Type S Standard
OR
1x PM-QUALITY Type S Professional
9AE7111-2SS20-1AA0-Z*
9AE7111-2SS30-1AA0-Z*
Optional licenses
PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*
Unrestricted © Siemens AG 2019
PM-QUALITY
Option B: PM-QUALITY + Data CenterUnrestricted © Siemens AG 2019
Unrestricted © Siemens AG 2019
PM-QUALITY redundancy option B / 1PM-QUALITY + Data Center
WinCC Competence Center Mannheim
WinCC RC/RT + Redundancy
PM-QUALITY Server
PM-QUALITY Data Center
PM-QUALITY Client (optional)
WinCC RT / Client
PM-QUALITY Client (optional)
WinCC RC/RT + Redundancy
PM-QUALITY Server
Unrestricted © Siemens AG 2019
PM-QUALITY redundancy option B / 2PM-QUALITY + Data Center
WinCC Competence Center Mannheim
WinCC RC/RT + Redundancy
PM-QUALITY Server
PM-QUALITY Data Center
WinCC RT / Client
PM-QUALITY Client (optional)
WinCC RC/RT + Redundancy
PM-QUALITY Server
Unrestricted © Siemens AG 2019
• A PM-QUALITY server is located on both WinCC servers. Each PM-QUALITY server will communicate with the local
WinCC server and will record the batch data independently. After the end of the batch / product batch the batch data
of both servers will be merged into an common export database by the Data Center. Possible data gaps on one of
the servers will be filled with the data of the respective partner.
• The Data Center may be either installed on a seperate PC (Option B / 1) or on one of the WinCC servers (Option B /
2).
• The PM-QUALITY Data Center installation doesn‘t require an individual license. The necessary license (PM-
QUALITY Type S Professional + Data Center) has to be provided by the two PM-QUALITY servers.
PM-QUALITY redundancy option BPM-QUALITY + Data Center
WinCC Competence Center Mannheim
Unrestricted © Siemens AG 2019
-Z*: -Z U02 = USB-Dongle; -Z S03 = License file
PM-QUALITY redundancy option BPM-QUALITY + Data Center
WinCC Competence Center Mannheim
Required licenses
2x PM-QUALITY Type S Professional + Data Center 9AE7111-2SS30-1BA0-Z*
Optional licenses
PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*
Unrestricted © Siemens AG 2018
PM-CONTROL + PM-QUALITY
Option A: Stand-alone PM-CONTROL / PM-QUALITY serverUnrestricted © Siemens AG 2019
Unrestricted © Siemens AG 2019
PM-CONTROL / PM-QUALITY redundancy option AStand-alone PM-CONTROL / PM-QUALITY server
WinCC Competence Center Mannheim
WinCC RC/RT + Redundancy
PM-QUALITY Client (optional)
PM-CONTROL Client (optional)
PM-AGENT
WinCC RT / Stand-alone SQL Server
PM-CONTROL Server
PM-QUALITY Server
WinCC RT / Client
PM-CONTROL Client (optional)
PM-QUALITY Client (optional)
WinCC RC/RT + Redundancy
PM-QUALITY Client (optional)
PM-CONTROL Client (optional)
PM-AGENT
Unrestricted © Siemens AG 2019
• Both, the PM-QUALITY and the PM-CONTROL server are communicating with the remote WinCC servers via
PM-AGENT. If one of the WinCC servers isn’t available, the communication will switch to the second server.
• The PM-QUALITY database with the archived batch data is stored on the separated computer.
• The relevant recipe data and/or jobs will be managed through the PM-CONTROL server on the separated computer.
The recipe data will be downloaded from the separated PC to the WinCC servers.
• A PM-AGENT license is required on both WinCC servers.
• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with
PM-CONTROL / PM-QUALITY). Alternatively a local WinCC RT installation will also provide the necessary SQL
Server installation.
PM-CONTROL / PM-QUALITY redundancy option AStand-alone PM-CONTROL / PM-QUALITY server
WinCC Competence Center Mannheim
Unrestricted © Siemens AG 2019
-Z*: -Z U02 = USB-Dongle; -Z S03 = License file
PM-CONTROL / PM-QUALITY redundancy option AStand-alone PM-CONTROL / PM-QUALITY server
WinCC Competence Center Mannheim
Required licenses
2x PM-AGENT 9AE7117-2SS01-1AA0-Z*
1x PM-QUALITY Type S Standard
OR
1x PM-QUALITY Type S Professional
9AE7111-2SS20-1AA0-Z*
9AE7111-2SS30-1AA0-Z*
1x PM-CONTROL Type S Compact
OR
1x PM-CONTROL Type S Standard
OR
1x PM-CONTROL Type S Professional
9AE7110-2SS10-1AA0-Z*
9AE7110-2SS20-1AA0-Z*
9AE7110-2SS30-1AA0-Z*
Optional licenses
PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*
PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*
Unrestricted © Siemens AG 2019
PM-CONTROL + PM-QUALITY
Option B: PM-QUALITY Data Center + Stand-alone PM-CONTROL ServerUnrestricted © Siemens AG 2019
Unrestricted © Siemens AG 2019
PM-CONTROL / PM-QUALITY redundancy option BPM-QUALITY Data Center + Stand-alone PM-CONTROL Server
WinCC Competence Center Mannheim
WinCC RC/RT + Redundancy
PM-QUALITY Server Prof. + Data Center
PM-CONTROL Client (optional)
PM-AGENT
WinCC RT / Stand-alone SQL Server
PM-CONTROL Server
PM-QUALITY Data Center
PM-QUALITY Client (optional)
WinCC RT / Client
PM-CONTROL Client (optional)
PM-QUALITY Client (optional)
WinCC RC/RT + Redundancy
PM-QUALITY Server Prof. + Data Center
PM-CONTROL Client (optional)
PM-AGENT
Unrestricted © Siemens AG 2019
PM-CONTROL / PM-QUALITY redundancy option BPM-QUALITY Data Center + Stand-alone PM-CONTROL Server
WinCC Competence Center Mannheim
• A PM-QUALITY server is located on both WinCC servers. Each PM-QUALITY server will communicate with the local
WinCC server and will record the batch data independently. After the end of the batch / product batch the batch data
of both servers will be merged into an common export database by the Data Center. Possible data gaps on one of
the servers will be filled with the data of the respective partner.
• The PM-QUALITY Data Center installation doesn‘t require an individual license. The necessary license (PM-
QUALITY Type S Professional + Data Center) has to be provided by the two PM-QUALITY servers.
• The PM-CONTROL server is communicating with the remote WinCC servers via PM-AGENT. If one of the WinCC
servers isn’t available, the communication will switch to the second server.
• The relevant recipe data and/or jobs will be managed through the PM-CONTROL server on the separated computer.
The recipe data will be downloaded from the separated PC to the WinCC servers.
• A PM-AGENT license is required on both WinCC servers.
• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with
PM-CONTROL / PM-QUALITY). Alternatively a local WinCC RT installation will also provide the necessary SQL
Server installation.
Unrestricted © Siemens AG 2019
-Z*: -Z U02 = USB-Dongle; -Z S03 = License file
PM-CONTROL / PM-QUALITY redundancy option BPM-QUALITY Data Center + Stand-alone PM-CONTROL Server
WinCC Competence Center Mannheim
Required licenses
2x PM-AGENT 9AE7117-2SS01-1AA0-Z*
2x PM-QUALITY Type S Professional + Data Center 9AE7111-2SS30-1BA0-Z*
1x PM-CONTROL Type S Compact
OR
1x PM-CONTROL Type S Standard
OR
1x PM-CONTROL Type S Professional
9AE7110-2SS10-1AA0-Z*
9AE7110-2SS20-1AA0-Z*
9AE7110-2SS30-1AA0-Z*
Optional licenses
PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*
PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*