process management system - siemens.de · • the pm-quality server communicates with the remote...

27
siemens.com/process-management Unrestricted © Siemens AG 2019 Process Management System Redundancy scenarios

Upload: lytuong

Post on 26-Apr-2019

218 views

Category:

Documents


0 download

TRANSCRIPT

Unrestricted © Siemens AG 2019

siemens.com/process-managementUnrestricted © Siemens AG 2019

Process Management System Redundancy scenarios

Unrestricted © Siemens AG 2019

Redundancy scenarios

• PM-CONTROL (Option A: Stand-alone server)

• PM-CONTROL (Option B: Cold standby)

• PM-QUALITY (Option A: Stand-alone server)

• QUALITY (Option B: Data Center)

• PM-CONTROL + PM-QUALITY (Option A: Stand-alone server)

• PM-CONTROL + PM-QUALITY (Option B: Stand-alone PM-CONTROL + PM-

QUALITY Data Center)

Unrestricted © Siemens AG 2019

PM-CONTROL

Option A: Stand-alone PM-CONTROL serverUnrestricted © Siemens AG 2019

Unrestricted © Siemens AG 2019

PM-CONTROL redundancy option AStand-alone PM-CONTROL server

WinCC Competence Center Mannheim

WinCC RC/RT + Redundancy

PM-CONTROL Client (optional)

PM-AGENT

WinCC RT / Stand-alone SQL Server

PM-CONTROL Server

WinCC RT / Client

PM-CONTROL Client (optional)

WinCC RC/RT + Redundancy

PM-CONTROL Client (optional)

PM-AGENT

Unrestricted © Siemens AG 2019

• The PM-CONTROL server communicates with the remote WinCC servers via PM-AGENT. If one of the WinCC

servers isn’t available, the communication will switch to the second server.

• The relevant recipe data and/or jobs will be managed through the PM-CONTROL server on the separated computer.

The recipe data will be downloaded from the separated PC to the WinCC servers.

• A PM-AGENT license is required on both WinCC servers.

• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with

PM-CONTROL). Alternatively a local WinCC RT installation will also provide the necessary SQL Server installation.

PM-CONTROL redundancy option AStand-alone PM-CONTROL server

WinCC Competence Center Mannheim

Unrestricted © Siemens AG 2019

-Z*: -Z U02 = USB-Dongle; -Z S03 = License file

PM-CONTROL redundancy option AStand-alone PM-CONTROL server

WinCC Competence Center Mannheim

Required licenses

2x PM-AGENT 9AE7117-2SS01-1AA0-Z*

1x PM-CONTROL Type S Compact

OR

1x PM-CONTROL Type S Standard

OR

1x PM-CONTROL Type S Professional

9AE7110-2SS10-1AA0-Z*

9AE7110-2SS20-1AA0-Z*

9AE7110-2SS30-1AA0-Z*

Optional licenses

PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*

Unrestricted © Siemens AG 2019

PM-CONTROL

Option B: PM-CONTROL server + cold standbyUnrestricted © Siemens AG 2019

Unrestricted © Siemens AG 2019

PM-CONTROL redundancy option BPM-CONTROL server + cold standby

WinCC Competence Center Mannheim

WinCC RC/RT + Redundancy

PM-CONTROL Server

Copy Project

WinCC RT / Client

PM-CONTROL Client (optional)

WinCC RC/RT + Redundancy

PM-CONTROL Server

Copy Project

Unrestricted © Siemens AG 2019

• A PM-CONTROL server is located on both WinCC servers. Due to technical restrictions only one PM-CONTROL

server may be active at the same time, though. The relevant recipe data and/or jobs will be managed through the

currently active PM-CONTROL server. The recipe data will be downloaded to the local WinCC server.

If the active server is shut down for any reason, PM-CONTROL has to be started on the second server.

• The duplication of the database has to be performed in the background by using the WinCC Tool „Copy Project“

• All relevant functionality like the management of the startup of PM-CONTROL, the switch in case of a system outage

as well as the synchronization of the databases has to be performed either manually or by custom scripts. This

means there is no automatic synchronization between the two PM-CONTROL servers.

PM-CONTROL redundancy option BPM-CONTROL server + cold standby

WinCC Competence Center Mannheim

Unrestricted © Siemens AG 2019

-Z*: -Z U02 = USB-Dongle; -Z S03 = License file

PM-CONTROL redundancy option BPM-CONTROL server + cold standby

WinCC Competence Center Mannheim

Required licenses

2x PM-CONTROL Type S Compact

OR

2x PM-CONTROL Type S Standard

OR

2x PM-CONTROL Type S Professional

9AE7110-2SS10-1AA0-Z*

9AE7110-2SS20-1AA0-Z*

9AE7110-2SS30-1AA0-Z*

2x Copy Project 9AE7141-2SS01-1AA0

Optional licenses

PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*

Unrestricted © Siemens AG 2019

PM-QUALITY

Option A: Stand-alone PM-QUALITY serverUnrestricted © Siemens AG 2019

Unrestricted © Siemens AG 2019

PM-QUALITY redundancy option AStand-alone PM-QUALITY server

WinCC Competence Center Mannheim

WinCC RC/RT + Redundancy

PM-QUALITY Client (optional)

PM-AGENT

WinCC RT / Stand-alone SQL Server

PM-QUALITY Server

WinCC RT / Client

PM-QUALITY Client (optional)

WinCC RC/RT + Redundancy

PM-QUALITY Client (optional)

PM-AGENT

Unrestricted © Siemens AG 2019

• The PM-QUALITY server communicates with the remote WinCC servers via PM-AGENT. If one of the WinCC

servers isn’t available, the communication will switch to the second server.

• The PM-QUALITY database with the archived batch data is stored on the separated computer.

• A PM-AGENT license is required on both WinCC servers.

• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with

PM-QUALITY). Alternatively a local WinCC RT installation will also provide the necessary SQL Server installation.

PM-QUALITY redundancy option AStand-alone PM-QUALITY server

WinCC Competence Center Mannheim

Unrestricted © Siemens AG 2019

-Z*: -Z U02 = USB-Dongle; -Z S03 = License file

PM-QUALITY redundancy option AStand-alone PM-QUALITY server

WinCC Competence Center Mannheim

Required licenses

2x PM-AGENT 9AE7117-2SS01-1AA0-Z*

1x PM-QUALITY Type S Standard

OR

1x PM-QUALITY Type S Professional

9AE7111-2SS20-1AA0-Z*

9AE7111-2SS30-1AA0-Z*

Optional licenses

PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*

Unrestricted © Siemens AG 2019

PM-QUALITY

Option B: PM-QUALITY + Data CenterUnrestricted © Siemens AG 2019

Unrestricted © Siemens AG 2019

PM-QUALITY redundancy option B / 1PM-QUALITY + Data Center

WinCC Competence Center Mannheim

WinCC RC/RT + Redundancy

PM-QUALITY Server

PM-QUALITY Data Center

PM-QUALITY Client (optional)

WinCC RT / Client

PM-QUALITY Client (optional)

WinCC RC/RT + Redundancy

PM-QUALITY Server

Unrestricted © Siemens AG 2019

PM-QUALITY redundancy option B / 2PM-QUALITY + Data Center

WinCC Competence Center Mannheim

WinCC RC/RT + Redundancy

PM-QUALITY Server

PM-QUALITY Data Center

WinCC RT / Client

PM-QUALITY Client (optional)

WinCC RC/RT + Redundancy

PM-QUALITY Server

Unrestricted © Siemens AG 2019

• A PM-QUALITY server is located on both WinCC servers. Each PM-QUALITY server will communicate with the local

WinCC server and will record the batch data independently. After the end of the batch / product batch the batch data

of both servers will be merged into an common export database by the Data Center. Possible data gaps on one of

the servers will be filled with the data of the respective partner.

• The Data Center may be either installed on a seperate PC (Option B / 1) or on one of the WinCC servers (Option B /

2).

• The PM-QUALITY Data Center installation doesn‘t require an individual license. The necessary license (PM-

QUALITY Type S Professional + Data Center) has to be provided by the two PM-QUALITY servers.

PM-QUALITY redundancy option BPM-QUALITY + Data Center

WinCC Competence Center Mannheim

Unrestricted © Siemens AG 2019

-Z*: -Z U02 = USB-Dongle; -Z S03 = License file

PM-QUALITY redundancy option BPM-QUALITY + Data Center

WinCC Competence Center Mannheim

Required licenses

2x PM-QUALITY Type S Professional + Data Center 9AE7111-2SS30-1BA0-Z*

Optional licenses

PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*

Unrestricted © Siemens AG 2018

PM-CONTROL + PM-QUALITY

Option A: Stand-alone PM-CONTROL / PM-QUALITY serverUnrestricted © Siemens AG 2019

Unrestricted © Siemens AG 2019

PM-CONTROL / PM-QUALITY redundancy option AStand-alone PM-CONTROL / PM-QUALITY server

WinCC Competence Center Mannheim

WinCC RC/RT + Redundancy

PM-QUALITY Client (optional)

PM-CONTROL Client (optional)

PM-AGENT

WinCC RT / Stand-alone SQL Server

PM-CONTROL Server

PM-QUALITY Server

WinCC RT / Client

PM-CONTROL Client (optional)

PM-QUALITY Client (optional)

WinCC RC/RT + Redundancy

PM-QUALITY Client (optional)

PM-CONTROL Client (optional)

PM-AGENT

Unrestricted © Siemens AG 2019

• Both, the PM-QUALITY and the PM-CONTROL server are communicating with the remote WinCC servers via

PM-AGENT. If one of the WinCC servers isn’t available, the communication will switch to the second server.

• The PM-QUALITY database with the archived batch data is stored on the separated computer.

• The relevant recipe data and/or jobs will be managed through the PM-CONTROL server on the separated computer.

The recipe data will be downloaded from the separated PC to the WinCC servers.

• A PM-AGENT license is required on both WinCC servers.

• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with

PM-CONTROL / PM-QUALITY). Alternatively a local WinCC RT installation will also provide the necessary SQL

Server installation.

PM-CONTROL / PM-QUALITY redundancy option AStand-alone PM-CONTROL / PM-QUALITY server

WinCC Competence Center Mannheim

Unrestricted © Siemens AG 2019

-Z*: -Z U02 = USB-Dongle; -Z S03 = License file

PM-CONTROL / PM-QUALITY redundancy option AStand-alone PM-CONTROL / PM-QUALITY server

WinCC Competence Center Mannheim

Required licenses

2x PM-AGENT 9AE7117-2SS01-1AA0-Z*

1x PM-QUALITY Type S Standard

OR

1x PM-QUALITY Type S Professional

9AE7111-2SS20-1AA0-Z*

9AE7111-2SS30-1AA0-Z*

1x PM-CONTROL Type S Compact

OR

1x PM-CONTROL Type S Standard

OR

1x PM-CONTROL Type S Professional

9AE7110-2SS10-1AA0-Z*

9AE7110-2SS20-1AA0-Z*

9AE7110-2SS30-1AA0-Z*

Optional licenses

PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*

PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*

Unrestricted © Siemens AG 2019

PM-CONTROL + PM-QUALITY

Option B: PM-QUALITY Data Center + Stand-alone PM-CONTROL ServerUnrestricted © Siemens AG 2019

Unrestricted © Siemens AG 2019

PM-CONTROL / PM-QUALITY redundancy option BPM-QUALITY Data Center + Stand-alone PM-CONTROL Server

WinCC Competence Center Mannheim

WinCC RC/RT + Redundancy

PM-QUALITY Server Prof. + Data Center

PM-CONTROL Client (optional)

PM-AGENT

WinCC RT / Stand-alone SQL Server

PM-CONTROL Server

PM-QUALITY Data Center

PM-QUALITY Client (optional)

WinCC RT / Client

PM-CONTROL Client (optional)

PM-QUALITY Client (optional)

WinCC RC/RT + Redundancy

PM-QUALITY Server Prof. + Data Center

PM-CONTROL Client (optional)

PM-AGENT

Unrestricted © Siemens AG 2019

PM-CONTROL / PM-QUALITY redundancy option BPM-QUALITY Data Center + Stand-alone PM-CONTROL Server

WinCC Competence Center Mannheim

• A PM-QUALITY server is located on both WinCC servers. Each PM-QUALITY server will communicate with the local

WinCC server and will record the batch data independently. After the end of the batch / product batch the batch data

of both servers will be merged into an common export database by the Data Center. Possible data gaps on one of

the servers will be filled with the data of the respective partner.

• The PM-QUALITY Data Center installation doesn‘t require an individual license. The necessary license (PM-

QUALITY Type S Professional + Data Center) has to be provided by the two PM-QUALITY servers.

• The PM-CONTROL server is communicating with the remote WinCC servers via PM-AGENT. If one of the WinCC

servers isn’t available, the communication will switch to the second server.

• The relevant recipe data and/or jobs will be managed through the PM-CONTROL server on the separated computer.

The recipe data will be downloaded from the separated PC to the WinCC servers.

• A PM-AGENT license is required on both WinCC servers.

• A MSSQL Server Standard / Developer Edition installation is necessary on the separated PC (not included with

PM-CONTROL / PM-QUALITY). Alternatively a local WinCC RT installation will also provide the necessary SQL

Server installation.

Unrestricted © Siemens AG 2019

-Z*: -Z U02 = USB-Dongle; -Z S03 = License file

PM-CONTROL / PM-QUALITY redundancy option BPM-QUALITY Data Center + Stand-alone PM-CONTROL Server

WinCC Competence Center Mannheim

Required licenses

2x PM-AGENT 9AE7117-2SS01-1AA0-Z*

2x PM-QUALITY Type S Professional + Data Center 9AE7111-2SS30-1BA0-Z*

1x PM-CONTROL Type S Compact

OR

1x PM-CONTROL Type S Standard

OR

1x PM-CONTROL Type S Professional

9AE7110-2SS10-1AA0-Z*

9AE7110-2SS20-1AA0-Z*

9AE7110-2SS30-1AA0-Z*

Optional licenses

PM-QUALITY Type C 9AE7111-4SC01-1AA0-Z*

PM-CONTROL Type C 9AE7110-4SC03-1AA0-Z*