procom - user handbook - tucor, inctucor-inc.com/downloads/procom-manual.pdf · 3 central unit,...

47
1 PROCOM - USER HANDBOOK PROCOM - USER HANDBOOK PROCOM - USER HANDBOOK PROCOM - USER HANDBOOK PROCOM - USER HANDBOOK Rev.:1/08FEB01

Upload: others

Post on 21-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

1

PROCOM - USER HANDBOOKPROCOM - USER HANDBOOKPROCOM - USER HANDBOOKPROCOM - USER HANDBOOKPROCOM - USER HANDBOOK

Rev.:1/08FEB01

Page 2: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

2

Mains

Transformer

24 V AC

2 wires

Solenoid

Valve

Sensor

Solenoid

Valve

Line

Decoder

Sensor

Decoder

Line

Decoder

TWC-500

Rain Sensor

Serial Port

Optocoupler

LTB-500

Line Termination Box

Pump AlarmGround

Rod

Serial Port

PC

PROCOM System LayoutPROCOM System LayoutPROCOM System LayoutPROCOM System LayoutPROCOM System Layout

Page 3: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

3

Central Unit, connectionsCentral Unit, connectionsCentral Unit, connectionsCentral Unit, connectionsCentral Unit, connections

Aux. connector

Serial connector

ON/OFF switch

24VACfrom transformer

From PC

From LTB

Fuses 4 A/T

1 2 3 4 5 6

TWC-500

Sensor common

Pump Alarm

Rain Sensor

Line B

Line A

Cable 6xAWG18

Line Termination Box

LTB-500

Page 4: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

4

Installation ofInstallation ofInstallation ofInstallation ofInstallation ofsoftwaresoftwaresoftwaresoftwaresoftware

PC-program:Insert the CD with the software andfollow the instructions on the screen.If the Installation program does notstart automatically, use the com-mand <CD-drive>:Install.

Controller program:The software in the Controller isstored in memory which is suppliedfrom a backup battery. This meansthat a new version can be deliveredon a disk and easily “downloaded”from the PC. Software is normallypreinstalled.

If you need to install the Controllersoftware, select the COM Port fromthe System menu.

It is not possible to perform aIt is not possible to perform aIt is not possible to perform aIt is not possible to perform aIt is not possible to perform adownload via a modem/telephonedownload via a modem/telephonedownload via a modem/telephonedownload via a modem/telephonedownload via a modem/telephoneconnection!connection!connection!connection!connection!

When the COM-port is selected,Select “Download CU Software”.This will open a file window whereyou select the Controller Software file(procom.hex), click on <Open> andfollow the instructions on the screen.The progress can be monitored inthe messages on the screen. Thesteps are transfer of the data andstoring (“flashing 4 times”) of data inthe permanent memory. Theprocedure takes about 8 minutesand is finished when the message“Program is now running” appears.

Page 5: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

5

ParametersPasswordDelete all DataPrinter setupPrint PreviewPrint

Main PipeNew Pipe

Type of valvesLine Decoder

Pump Decoder

Sensor Inputs

Setup

Pipes

Valves

Pumps

Sensors

Installation Data

OpenDownload CU SoftwareSelect COM portExit

Irrigation SchedulesSectorsPump StatusSensor Status

Turn Decoder on/offStart/Stop IrrigationDisplay Man. started Decoders

Installation DataDate and TimePasswordTestWeather StationLanguage setup

StatusMonitor Irrigation, Screen

ContentsAbout PROCOM

Display/Modify SectorsDisplay all Decoders

Manual TestAutomatic TestET valuesET default valueGet Weather DataWeather Station setupConnection setup

System

Irrigation

Manual

Setup

View

Help

Main Menu

Menu TreeMenu TreeMenu TreeMenu TreeMenu Tree

The program has two main sections,the Installation Data and the Irriga-tion Part.

The Installation Data is a databasewhich contains all information aboutPumps, Pipes, Decoders andsensors. To write Schedules thenames/addresses of the decodersmust be in the data base anddetailed information about thehydraulic properties of the system isnecessary for the “Flow Optimizer” towork.

To enter the installation section,either select “Installation Data” fromthe Main Menu or click on the icon:

Note: Menus in italics are not yetavailable

Page 6: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

6

ParametersParametersParametersParametersParameters

Max. number active Solenoids.Max. number active Solenoids.Max. number active Solenoids.Max. number active Solenoids.Max. number active Solenoids.The Controller is rated for 40*simultanesouly active solenoids (28Ohms/2 W). If the resistance is lower,the maximum number must bereduced proportionally.

*2 sections with 20 each, moreabout this later.

Legal Characters. Do not change seeLine Decoders.

Power Off time.Power Off time.Power Off time.Power Off time.Power Off time.If a power failure occurs duringirrigation, the controller is able toresume the watering where it wasinterrupted. If the time is set to zero,irrigation will not be resumed. If thepower outage is less than the settime, watering will resume exactlywhere it stopped. If the outage ismore than the set time, the schedulewill resume with what is scheduledfor that time (there will be a “hole” inthe schedule).

ET is not yet implemented.ET is not yet implemented.ET is not yet implemented.ET is not yet implemented.ET is not yet implemented.

Measurement Units.Measurement Units.Measurement Units.Measurement Units.Measurement Units.The data are not converted whenother unit systems are selected. It istherefore important to select the unitsbefore entering the data.

(Installers)Password(Installers)Password(Installers)Password(Installers)Password(Installers)Password

To protect the Installation Data frombeing changed by unauthorizedpersons, it is recommended to usepassword protection. When pass-word is used the field changes fromgrey to colored. If you click on agreen password field, protection ison and the field changes to red.

To remove protection, click on thered field and enter the password asprompted.

Page 7: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

7

Remove passwordRemove passwordRemove passwordRemove passwordRemove password

Select password from the SetupMenu and enter the current pass-word. The two boxes for the newpassword must be left empty. Clickthe OK button and the password isremoved. Accordingly the fieldbecomes grey.

Main PipeMain PipeMain PipeMain PipeMain Pipe

The Main Pipe is equal to the pumpmanifold and no valves can beconnected to it. The capacity shall ofcourse be the same as the pumpcapacity.

The pipe model used by the FlowOrganizer is a tree structure andother layouts must therefore betransformed into such anapproximation.

New PipeNew PipeNew PipeNew PipeNew PipeTo add pipe sections the model,select “New Pipe” from the menuand enter the capacity of that pipe.Observe that the layout is completedwith a new pipe marked “Section 1”.You may drag Section 1to a positionthat suits you.

Section 1 can only be connected tothe Main Pipe but subsequentsections may be connected to othersections by use of the drop downmenu at the bottom of the table.

Page 8: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

8

Type of ValvesType of ValvesType of ValvesType of ValvesType of Valves

A Valve Type is determined by thefollowing:-CapacityCapacityCapacityCapacityCapacity (which is needed by theFlow Optimizer)-Precipitation rate Precipitation rate Precipitation rate Precipitation rate Precipitation rate (which is needefor ET control of irrigation)-Resistance -Resistance -Resistance -Resistance -Resistance (of solenoid which isneeded by the System Tests)-Electric code-Electric code-Electric code-Electric code-Electric code (which is necessaryto operate the valve)-Number of solenoids-Number of solenoids-Number of solenoids-Number of solenoids-Number of solenoids (which isnecessary not to overload thesystem)

If just one of these factors changes itis necessary to create a new ValveType. Up to 100 Valve Types may becreated.

Line DecodersLine DecodersLine DecodersLine DecodersLine Decoders

The table is the link between theNameNameNameNameName you want to use for thedecoder and the AddressAddressAddressAddressAddress on thedecoder label. For the names youcan use up to 8 characters. You mayuse any letter/digit combination, butif you want to use the Field AccessUnit (FA-100) your choice is limitedto the “Legal Characters” (see page6).

If a number is already used byanother Decoder, a warning will beshown. Duplicate numbers arepermitted, but should normally beavoided.

For each Line Decoder you mustalso list the following:-Valve Type-Valve Type-Valve Type-Valve Type-Valve Type-Decoder Type:-Decoder Type:-Decoder Type:-Decoder Type:-Decoder Type: 1=LD-100

2=LD-2004=LD-4006=LD-600

This information is needed for theTest Program to calculate correctlythe standby current.

-Pipe Section-Pipe Section-Pipe Section-Pipe Section-Pipe Section

The button with the “down arrow”takes you to the end of the list.

Page 9: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

9

Pump DecoderPump DecoderPump DecoderPump DecoderPump DecoderUp to 16 pumps may be defined,each with its own capacity and PumpDecoder. Line Decoders may beused to control pumps but they mustbe defined as Pump Decoders.

For each Pump number, the systemsuggests an AddressAddressAddressAddressAddress. The Pumpnumbers are created automaticallyand correspond to the switchpositions on the Pump Decoder:

P1: 284 P4: 292P2: 286 P5: 293P3: 287 P6: 295P7: 296 P8: 310

PriorityPriorityPriorityPriorityPriority can range from 0 to 6.Priority 1 is the highest, i.e. thispump is started first. More pumpswith the same priority take turns tostart first. Priority 0 corresponds tono Pump Decoder installed. A slave(booster) pump must be installedwith priority S.

On-delayOn-delayOn-delayOn-delayOn-delay is the time in seconds fromthe pump is turned on and till afollowing pump can be started.

Off-delayOff-delayOff-delayOff-delayOff-delay is the time in seconds fromthe end of demand and till the pumpis actually stopped.

A slave pump is a pump that must be started whenever valves on acertain pipe section are turned on. When the slave pump has beendefined in this table, open the window for that pipe section and enterthe pump number in the “Slave Pump” field. The capacity of a slavepump is not included in the total pump capacity.

Sensor InputsSensor InputsSensor InputsSensor InputsSensor Inputs

Rain SensorRain SensorRain SensorRain SensorRain SensorWhen the sensor is activated by rain,all Line Decoders and pumps areimmediately stopped and themessage RAIN is displayed in thestatus field. Decoders may be startedmanually. When the Sensor returnsto the passive mode, Irrigation willresume.

Alarm SensorAlarm SensorAlarm SensorAlarm SensorAlarm SensorInput may come from a pump, apressure gauge or similar. When thesensor is active, Line Decoders cannot be started neither by IrrigationSchedules nor manually. The statusdisplays ALARM

A Sensor that is not installed shall be set to NOT INSTALLED. To use asensor it shall be installed as either ON, CLOSED (Normally Open) or asON, OPEN (Normally Closed). A Rain Gauge which acts as an off-switch during rain and as a short-circuiter during dry periods, shall beinstalled as ON, OPEN. Sensors 1 and 2 may be disabled by changingtheir status to NOT USED in the Sensor Status menu. All sensors have aresponse time of about 1 minute from the physical activation till thestatus changes on the screen.

Page 10: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

10

Line Voltage & Short CircuitLine Voltage & Short CircuitLine Voltage & Short CircuitLine Voltage & Short CircuitLine Voltage & Short Circuit These two sensors are internal (inthe Line Control Module). Theymonitor the conditions on the Linesand their status can not be changed.

The Short Circuit Short Circuit Short Circuit Short Circuit Short Circuit sensor monitorsthe voltage on the line. If the voltagedrops below the set limit (default 25Volts), the line voltage is set to zeroand the message SHORT is dis-played in the status field. Every 10minutes the Line voltage will beapplied again for one minute tocheck if there is still a short. Sensor 4is by default ON,CLOSED.

Date and TimeDate and TimeDate and TimeDate and TimeDate and Time

Select from the Installation Datamenu “Date and Time”. Note thatMilitary Time is used. 6:13 PM musttherefore be entered as 18:13.

The Line Voltage SensorLine Voltage SensorLine Voltage SensorLine Voltage SensorLine Voltage Sensor monitors the voltage between the 2-wire andground. If a fault is detected, a relay automatically disconnects the Lineand the message ERROR is displalyed in the status field. This will causeall decoders and pumps to stop. After the fault is removed, the CentralUnit must be turned off and on again to restore operation. Sensor 3 isby default ON,OPEN.

Flow SensorFlow SensorFlow SensorFlow SensorFlow SensorFrom the Sensors menu select EditSensor Decoder. Now you have tokey in the informaiton needed to setup the flow sensor.

Page 11: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

11

Sensor DecoderSensor DecoderSensor DecoderSensor DecoderSensor Decoder

The address of the Sensor Decoderis printed ont he decoder label.

Calibration DataCalibration DataCalibration DataCalibration DataCalibration Data

This information is necessary for theController to convert themeasurement into GPM. In theexample 917 pulses counted over 10seconds correspond to 250 GPM.The actual numbers depends on theflow sensor and the pipe size.

Pulse/10 seconds are mostly usedwith impeller type flow meteres.

ms/pulse (milli-seconds betweenpulses us used with sensors thatgive a small number of pulses persecond.

mA (4-20 mA) is an industrial type ofsensor.

If you check this box allflow measurements willbe logged in the monitorfile.

High Flow alarmHigh Flow alarmHigh Flow alarmHigh Flow alarmHigh Flow alarm

If the flow exceeds 50 GPM for morethan 2 minutes, an alarm will betriggered. The controller reacts bystopping all decoders in the currentstep and calling the pager (phone)712 223 1221 which will display themessage 1111

Leakage alarmLeakage alarmLeakage alarmLeakage alarmLeakage alarm

If the flow exceeds 5 GPM for morethan 2 minutes the Controller willactivate the decoder MV and call thepager to display the message 0000.

The action can be “Activate” or“Deactivate” and the decoder canbe any decoder in the installation orall decoders.

If your controller is connected tomore than one Flow sensor you canset up the others in the same way bypressing “Next”.

Page 12: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

12

When you have defined all Flowsensors, press “Done” and thiswindow wil appear. Here you cansum the measurements from allsensors and set up the total flow totrigger alarms and log themeasurements to the montor file inthe sam e way as for the individualflows.

When you press “Finish”, the datasetup for the sensor decoders will bestored in the database on the PC.

Necessary to getflow measurementsin the Logviewer

Flow MonitoringFlow MonitoringFlow MonitoringFlow MonitoringFlow Monitoring

Measurements from the SensorDecoders are used in two differentways:

Alarm triggerAlarm triggerAlarm triggerAlarm triggerAlarm trigger, i.e. if a certain eventhappens, the controller will react in acertain way (refer to the previouspages).

Monitoring the systemMonitoring the systemMonitoring the systemMonitoring the systemMonitoring the system, i.e. thewater flow. The controller stores inmemory all events : Start a Decoder ,stop a Decoder, reading of a FlowSensor. This is useful if you haveseveral wataer sources an dyou wantto keep track of the flow rates reomeach water source. Themeasurements are sored in themonitro file and can be seen in theMonitor screen. If you use the“Extract and ViewExtract and ViewExtract and ViewExtract and ViewExtract and View” function the dataare presented with the “Show Data”funtion.

The flow measurementsmade by a specific FlowSensor is stored in themonitor file only if youcheck this box.

Page 13: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

13

Using the Flow summing will allowyou to monitor the sum of severalflow sensors (in this example 3sensors are installed but we onlywant to sum number 1 and 2).

The sum as defined here is stored inthe monitor file where it is used tocalculate the water consumption.Can be viewed in “Extract and view”using the “Show overview” function(Refer to page 32 Monitoring Data formore details.)

If you want to use the flowmeasurements to calculatethe water consumption, youmust check this box.

Transfer of DataTransfer of DataTransfer of DataTransfer of DataTransfer of Data

All changes of data are stored in thePC. For the controller to irrigateaccording to these data they must betransferred from the PC to thecontroller. There are 3 buttons likethis:

which may be used to initiate transferof data. When transfer is necessarythe 3 buttons change appearance asshown in the left picture. Whentransfer is complete, the buttonschange as shown in the right picture.

Page 14: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

14

ConnectConnectConnectConnectConnect

Transfer is not possible if the PC andthe Controller are not connected. Ifthe indicator on the toolbar of themain screen is “Off line” (red), clickon it and the Communication Statuswindow appears. In this window,click on the connect button toestablish the contact.

The Message Window will reportcurrent actions so that you canmonitor the progress. The datatransfer consists of the followingblocks:

-Sensor Decoders-General System Data-Installation DataIrrigation Schedules

The Status Field will show currentstatus.

If you are operating the Controllerremotely, you need to change theConnection setup to Modem andenter the Phone number of theremote installation.

When operating the system via atelephone line it is too costly to beconnected all the time. When youwant to disconnect, click on theDisconnect button in theConnumication Status window. Theindicator on the toolbar of the mainscreen wil change to Off line whendisconnected.

Modem connectionModem connectionModem connectionModem connectionModem connection

Page 15: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

15

Test of installationTest of installationTest of installationTest of installationTest of installationWhen the installation is finished it isrecommended to perform thefollowing (automatic) tests:- LD short- GF solenoids- GF sognal

Solenoid resistanceSolenoid resistanceSolenoid resistanceSolenoid resistanceSolenoid resistance

To enable the automatic measuringfacilities it is necessary to key valuesfor the soleonoids resistaces.Typically the resistance is 28 Ohms.If two such solenoids are parallelledthe resistance must be set to 14Ohms.

With the default value (0 Ohms) allWith the default value (0 Ohms) allWith the default value (0 Ohms) allWith the default value (0 Ohms) allWith the default value (0 Ohms) allvalves with that valve type isvalves with that valve type isvalves with that valve type isvalves with that valve type isvalves with that valve type isskipped in the automatic tests.skipped in the automatic tests.skipped in the automatic tests.skipped in the automatic tests.skipped in the automatic tests.

True monitoringTrue monitoringTrue monitoringTrue monitoringTrue monitoringValve types which are defined with aresistance from 1-50 Ohms arechecked for proper operation whenactivated in Irrigation Schedules. Ifthe solenoid does not respondcorrectly, the valve will be closed andan error message shown in themonitoring. Instead of the flow isshown the current when the valve isstarted.

In this example L6 and L7 has anerror. Current is 59 and 60 mA. Notethat the valves are stopped a fewseconds after they are started andnote also the message IS STOPPEDat the time where L6 is scheduled tostop.

Page 16: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

16

Automatic testingAutomatic testingAutomatic testingAutomatic testingAutomatic testing

This test will go through al the valvesin the order they are listed in thedatabase. Every time a valve doesnot respond properly, the name andmeasurement results are displayedin the window. In this exampledecoder L6 did not respond: The 3currents representing standby-inrush- and holding currents are allthe same. The number displayedafter the decoders is its address.Decoders L4 through L12 and MVare not tested because their valvetype resistance is set to zero.

Important!Important!Important!Important!Important!

Before you perform the “GF” andBefore you perform the “GF” andBefore you perform the “GF” andBefore you perform the “GF” andBefore you perform the “GF” andthe “LD thorough” test, you mustthe “LD thorough” test, you mustthe “LD thorough” test, you mustthe “LD thorough” test, you mustthe “LD thorough” test, you musthave done the “LD short” andhave done the “LD short” andhave done the “LD short” andhave done the “LD short” andhave done the “LD short” andcorrected any faults found in thatcorrected any faults found in thatcorrected any faults found in thatcorrected any faults found in thatcorrected any faults found in thattest. If you do not correct the faultstest. If you do not correct the faultstest. If you do not correct the faultstest. If you do not correct the faultstest. If you do not correct the faultsbefore proceeding the decodersbefore proceeding the decodersbefore proceeding the decodersbefore proceeding the decodersbefore proceeding the decoderswill fail in the other two tests aswill fail in the other two tests aswill fail in the other two tests aswill fail in the other two tests aswill fail in the other two tests aswell.well.well.well.well.

Page 17: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

17

GF SolenoidsGF SolenoidsGF SolenoidsGF SolenoidsGF Solenoids

The test offers a choice of 3 voltagelevels for the testing.Test level 1 (15Volts) will search for only severeleakages as compared to test level 3(35 Volts) which will search for verysmall leakages.

Unless there are many and severeleakages it is recommended to startat level3. If there are many faults thetest should be repeatet afterrepairing the faults because manyheavy faults may cover up for theminor leakages.

Reprogramming

After selection of the test voltage thetest will start with reprogramming ofall decoders followed by a period of5 minutes where the two linees areautomatically connected togetherand supplied wotih the line voltage(of the level selected), with respect toground.

Page 18: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

18

After the 5 min’s period the normalline voltage is applied again, and thetest “LD short” is run automatically.

During this rest all leaky positionaare displayed with measurementsresult on the screen . The threecurent values represent (as before)standby-, inrush- and holdingcurrents.

GF signalGF signalGF signalGF signalGF signal

In this case there is a leakage of 18mA on the lines. See Line Survey onpage 22.

Page 19: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

19

LD ThoroughLD ThoroughLD ThoroughLD ThoroughLD Thorough

This test checks the standby currentof each Line Decoder. Afterprogramming of all decoders, theLine Voltage is interrupted forapproximately one minute. Linevoltage is then reestablished and allDecoders are tested for correctresponse.

Any Decoder that foes not respondhas an abnormal comsumption andshould be replaced.

Page 20: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

20

Manual TestsManual TestsManual TestsManual TestsManual Tests

Line DecoderLine DecoderLine DecoderLine DecoderLine Decoder

A given number of currentmeasurements will be made eachtime a decoder is tested. The timeinterval will set the time betweeneach measure taken. The value ofthe time interval is user definable andcan be set from 5 ms to 100 ms. Thedefault value is 20 ms. In ourexample you may verify the standby,inrush and holding to 34, 482 and 56mA.

If you want to start with a specificdecoder, click on the button with thequestion mark and select the onefrom the drop down list. If you donot select a specific one, the testprogram will start with the first in theinstallation. When the readingsappear you may stop the valve andstart the next.

Page 21: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

21

The necessary instruments for servicing the irrigation system is a digitalvoltmeter and a clampmeter. If the voltmeter is used only to checkvoltages on the system, a resolution of 1 V is sufficient.

The clampmeter can be either a probe connected to a voltmeter or aseparate instrument. In the first case the voltmeter must have aresolution of 1 mV (AC). Observe that although the resolution is 1 mVthe accuracy is typically +/- 3 mV. The probe must have a resolution of 1mA. For the probe a conversion of 1 mA to 1 mV would be normal. As aseparate instrument, it is difficult to find one with a measuring rangedown to 1 mA. Most of these are designed for power applications andminumum ranges of 1 A are the usual. Normally clampmeters registeronly AC current but it is possible to get meters that register DC currentsas well, but those are more expensive.

A problem common to both the voltmeter and the clampmeter is thefrequency of the AC in the system. AC meters are normally designed forfrequencies from 50 Hz to 1000 Hz (mains frequency is 60 Hz). Thefrequency of the Flowmaster system is 1 Hz, but more about this inconnection with the individual measurements.

Digital Voltmeter

Clampmeter

Short FindingShort FindingShort FindingShort FindingShort Finding

Select “Electrical Measurement”From the manual Test Menu. Whenyou press “Run Test” the AC Linevoltage will change form 1 cycle/secto 50 cycles/sec which can bemeeasured with a clampmeter.

Start with measuring the currents onthe Lines at the LTB-500. If morethatn one Line has shorts, check oneat a time by disconnecting theothers. In cas eof a loop, disconnectone end. Follow current through theLine until it disappears indicating thatyou have passed the shorteningpoint. A precise “as built” diagramsaves time.

Page 22: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

22

Line SurveyLine SurveyLine SurveyLine SurveyLine SurveyThis screen gives an overview ofvoltages and currents in the system.Values are updated every second,but not all at the same time. Thismeans that when values are varyingwith time, the readings shown on thescreen does not correspond.

This part contains Line current. Thelimit is the current where the voltageis reguylated down to preventoverload. The expected current iscalculated on basis of the nubmer ofLine Decoders in the installation database. The difference between singleand multiple Decoders is of courseconsidered.

The voltage is the Line voltagemeasured on the output of thecontroller. When the voltage dropsbelow the high threshold, the linepower is shut off. The low theshold isused when the Field Access unitcommunicates. The Line 1 and Line2 fields alternates red/green tosimulate the AC but are notsynchronized with the actual LineVoltage.

This box shows values of the GroundVoltage system for corrosionprotedtion. Voltage “@ the case” isthe Ground Voltage referenced to thenegative line. When this voltagereaches the threshold, Line Voltageis shut off. The current is the leakagecurrent. Internal voltage is thereference for the Ground Voltageregulator.

Page 23: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

23

Irrigation SchedulesIrrigation SchedulesIrrigation SchedulesIrrigation SchedulesIrrigation Schedules

Select from the Irrigation Menu tobring up the window which is the“base” when writing schedules.

Schedule NameSchedule NameSchedule NameSchedule NameSchedule NameClick on the Name field to make itactive and write the name you wantfor your schedule.

Week DaysWeek DaysWeek DaysWeek DaysWeek DaysClick on the days field to bring up atable with the 2 weeks which are theprogramming period. To know whichweek is the current, open the View/Status window. In the Date and Timefield there is a number in parentesisafter the date. That number is theday number in a 14 day cycle. In theexample the current day is Wednes-day of the second week. When youclose the window, the marked daysare shown in the days field.

Start TimesStart TimesStart TimesStart TimesStart Timesclick on the “Start Times” field toopen the table and key in the desiredstart time. You may enter up to 12start times for each Schedule.

Note that Military Time is used. 20:00therefore equals 8:00 PM.

Page 24: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

24

Line DecoderLine DecoderLine DecoderLine DecoderLine DecoderFrom the drop down list under“Types” you may choose betweenDecoder or Sector, in this case selectDecoder.

Read about SectorsSectorsSectorsSectorsSectors on page 24.

Select the Decoder from the dropdown list under Name. Names thathave already been included in theschedule are removed from the list.

MinutesMinutesMinutesMinutesMinutesClick on the “Min” field and enter thedesired run time (in minutes) for thevalve.

MethodsMethodsMethodsMethodsMethodsIn the “Method” field selectSequential.

See page 26 for explanation of“Sequential”,“Priority” and“Automatic”.

Page 25: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

25

Dry Run (Simulation)Dry Run (Simulation)Dry Run (Simulation)Dry Run (Simulation)Dry Run (Simulation)

When a new schedule is created or aschedule is changed, the duration inthe field “Sim Time” is marked with astar. Click on the field to (re)calculatethe run time. This will bring up theDry Run table shown below.

In the table all times are shownrelative to the start time (00:00).Notice that there is a delay of oneminute from the schedule is startedand till the first decoder starts. Alsovalves start/stop at the full minuteonly. The first minute is used bytheFlow Optimizer to calculate howthe valves must be started. If youclick on the leftmost button, markedgraph, you will get the pump loadcurve (See the next page.)

Delete DecoderDelete DecoderDelete DecoderDelete DecoderDelete DecoderIf you want to delete a Decoder froma schedule, click on the grey “borderfield” left to the Decoder. The line isnow marked with a black arrow. Thepress the delete button.

To complete the deletion, click theYes button in the Warning window.

Page 26: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

26

The graph shows how the flow variesduring the schedule. The headingshows total flow and total time. Whenthe sursor is moved in the graph, thecoordinates are shown in the field inthe bottom of the window.

Irrigation MethodsIrrigation MethodsIrrigation MethodsIrrigation MethodsIrrigation Methods

The Irrigation method is by defaultsequential when you create anIrrigation schedule, but you willprobably prefer to use automatic orpriority because they lead to shorterwatering times.

Sequential MethodSequential MethodSequential MethodSequential MethodSequential MethodThe valves are activated one at atime, in order as listed in the Demoprogram and beginning at the top ofthe list. The graph on top showssequential method for our TESTschedule. Note that the total durationis 2:06. The Flow Optimizer is notused and even if you make themistake to place a valve that requiresmore water than the pipe’s capacity,the schedule will run.

Priority MethodPriority MethodPriority MethodPriority MethodPriority MethodAgain the valves are activated inorder as listed, but this time as manyas the flow data allows for. Note thatthe total duration is 0:47. If there aremistakes in the flow data (too largevalve on too small pipe) the schedulewill not run! This method is of coursemore efficient than the sequential butstill has the advantage that the orderin which the valves are started is wellknown.

Page 27: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

27

Automatic MethodAutomatic MethodAutomatic MethodAutomatic MethodAutomatic MethodThe Flow Optimizer calculates theoptimum number and order in whichto activate the valves, trying to utilizefully, as much of the time as possi-ble, the maximum water capacity ofthe system. Note that the totalduration is now 0:32. The onlyproblem is that the valves seems tocome on at random, which make ithard to figure out which will come onnext.

Start IrrigationStart IrrigationStart IrrigationStart IrrigationStart Irrigation

Schedule statusSchedule statusSchedule statusSchedule statusSchedule statusSelect the status field to get the dropdown menu and select “Active” tochange the schedule status frompassive to active. Only active sched-ules will run when Irrigation is turnedON.

When you set schedules to “Pas-sive”, they are stored for later useand will not be executed whenIrrigation is ON.

Irrigation ONIrrigation ONIrrigation ONIrrigation ONIrrigation ONEven schedules with status “Active”will not run until the Irrigation isturned ON.

Select “Status” from the View-menuand click on the “ON” button. Thefield with Irrigation Status will nowchange to “Irr On”.

Irrigation OFFIrrigation OFFIrrigation OFFIrrigation OFFIrrigation OFFIrrigation may be turned off in twoways. By clicking on the “Off”-buttonthe system is reset to Irrigation Offimmediately and execution of allschedules are stopped. By clickingon the “Off when idle”-button,system is changed to Irrigation Offbut the current schedule will becompleted as programmed.

Page 28: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

28

Schedule overlapSchedule overlapSchedule overlapSchedule overlapSchedule overlap

TWC-500 can only run one scheduleat a time. If you have overlappingschedules only the one alreadyrunning when the second comes tostart, will be executed, the secondwill be rejected.

To test that click the “Dry Run, All”button.

The table shows clearly whichSchedules are overlapping andwhich one is rejected.

Te resolve the conflict, change starttime for one or more schedules.

In the graph the schedules that runare blue and the rejected are markedwith red.

Updating windowUpdating windowUpdating windowUpdating windowUpdating window

Some fields, f. inst. the Sim. Time,are not updated automatically. Press<F5> to get the window completelyupdated. This will also rearrange theschedules so that active schedulesare moved to the top of the list (andin alphabetical order).

Page 29: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

29

Water BudgetWater BudgetWater BudgetWater BudgetWater BudgetWater budget allows you to adjustthe watering time from 0-300 %. aWater Budget of 100 % means thatthe irrigation will be carried out asinitially programmed. In this TESTschedule you will 3 get times theminutes that you keyed in with thedecoders. The 100 % should corre-spond to normal watering time. Indry periods, setting WB to 150 %would give you 50 % more water.

Time WindowTime WindowTime WindowTime WindowTime Window

Time Window prevents schedulesfrom watering within a certain timeframe called the Window. Thismeans that a running schedule willbe terminated when the TimeWindow starts. Manual operation ofschedules and decoders are stillpossible. Note that the IrrigationStatus field changes to “Closed”when within the window (andIrrigation is ON).

Manual Start/StopManual Start/StopManual Start/StopManual Start/StopManual Start/Stop

Decoder StartDecoder StartDecoder StartDecoder StartDecoder StartSelect from the “Manual” menuDecoder Start/Stop. In the controlwindow select the desired Decoderfrom the list. The list is sorted inalphabetical order. Enter the durationand click on the Start button.

Decoder StopDecoder StopDecoder StopDecoder StopDecoder StopSelect from the list the desiredDecoder and click on the Stopbutton.

Stop All DecodersStop All DecodersStop All DecodersStop All DecodersStop All DecodersClick on the Stop All button. This willalso stop all decoders that areactivated by a schedule.

Page 30: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

30

Schedule Start/StopSchedule Start/StopSchedule Start/StopSchedule Start/StopSchedule Start/StopSelect the schedule and click on theStart or the Stop button.

Display Man. startedDisplay Man. startedDisplay Man. startedDisplay Man. startedDisplay Man. startedDecodersDecodersDecodersDecodersDecoders

Page 31: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

31

MonitoringMonitoringMonitoringMonitoringMonitoring

This window lists all events in orderof time. Use the scroll slider to moveup and down in the list. All eventsare recorded to a file on the PC’sharddsik

When the PROCOM Central unit is“Off line” (not in contact with yourPC), it still records events to memoryin the TWC-500. The recordings aretransmitted to the PC next time theyare “On line”. The TWC-500 canstore at least 2.500 lines.

The monitor window shows thename of the unit, action, date & timeand the flow total.

Print MonitoringPrint MonitoringPrint MonitoringPrint MonitoringPrint MonitoringIf you click on the “copy” button thecontent of the monitor log is copiedto the Windows clipboard. Fromthere it can be pasted to thewordprocessor of your choice, andthen printed.

Page 32: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

32

To work with the monitoring data youmust use the function Extract andview monitor log.

The data can not be extractedThe data can not be extractedThe data can not be extractedThe data can not be extractedThe data can not be extractedunless you are connected with theunless you are connected with theunless you are connected with theunless you are connected with theunless you are connected with thecontroller.controller.controller.controller.controller.

When you select this menu point, theprogram “Logviewer” which is anExcel macro will be started. If yoursecurity system prompts you that theprogram contains macros that mightcontain virus, you must say yes tostart these.

For this to run properly you needFor this to run properly you needFor this to run properly you needFor this to run properly you needFor this to run properly you needExcell 7 or later and Windows 98Excell 7 or later and Windows 98Excell 7 or later and Windows 98Excell 7 or later and Windows 98Excell 7 or later and Windows 98or later.or later.or later.or later.or later.

If you are connected to the controllerthe TWC program will look for thespreadsheet program Excel. If it isinstalled on your PC, the program“Logviewer” which is an Excel macrowill be started. (If your securitysystem prompts you that theprogram contains macros that mightcontain virus, you must say yes tostart these.) The monitoring data willautomatically be imported into Excel.Activity bars will keep you informedof the progress in the import andconversion of the data.

LogviewerLogviewerLogviewerLogviewerLogviewer

Page 33: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

33

When the data treatment is finished,click on the Overview button on theFront Page to get the report osshown here. The report will showstart times and gallonage for theSchedules and eventual alarms.

If you want to check the deails of themonitoring, select from the “Excel”menu “data.xls”

This will open a window that listswhich valves were operatingtogether, the times and thecorresponding flows.

Notice that each Schedule has itsown sheet with a separate tag in thedata window.

Any of the monitoring sheets may beprinted from Excel in the usual way.

When you want to close the“Logviewer”, select “logviewer97-2000.xls and click the exit button. Allthe data sheets will automatically bestored when you exit this way.

Page 34: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

34

SectorSectorSectorSectorSectorSectors are groups of Decoders thatshould be treated in the same way. Itis a tool to expedite data input whenyou set up an Irrigation schedule.

In this example a sector (BEDS) iscreated with 4 Decoders that willnormally run together and for thesame time.

Though a Decoder is included in asector it may still be included inschedules as an individual.

Select Display/Modify Sector. In theSector Edit window select the firstfield (with Total) and wirte the sectorname.

Now click on the Decoders field inthe “BEDS” line. This will open anew window, “Decoders display”

Click on the first field (Total) andwrite the name of the first Decoder.To add another Decoder, press<Enter> until the next field becomesselected and write the next name.

If you key in a non existing name,this message will occur.

Page 35: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

35

When you are finished with yoursector, close the window.

Delete Sector memberIf you want to remove a member of asector, click on the grey border left tothe The line is now marked with ablack arrow. Decoder and press theDelete button.

You must click on the Yes button inthe warning window to complete thedeletion.

Page 36: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

36

Pump StatusPump StatusPump StatusPump StatusPump StatusThe pump status has three modes:

-Not installed-Active-Passive

The picture shows that only Pumps 1and 2 (with Pump Decoders) havebeen installed. Their status are now“Active”. This means that these twopumps will be used during irrigation.“Passive” means that a pump isinstalled, but is temporarily out ofoperation (for repair or mainte-nance). The system will correct forreduced pump capaicty duringirrigation. If you change the status ofa pump it will affect the time neededto carry out irrigation. It is thererforeadvisable to make a Dry Run.

Note that the status of pumps canonly be changed while the system isin Irrigation off mode.

Sensor StatusSensor StatusSensor StatusSensor StatusSensor StatusThe sensors status has three modes:

-Not installed-Used-Not used

If, for example, you want to preventyour Rain sensor from stopping theirrigation, it is not necessary todisconnnect it. Just change thestatus to “Not used”.

The table also shows when a sensorwas ON last time and when it wentOFF again. If a sensor is on whenyou select this function, no OFF timewill appear.

Page 37: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

37

User passwordUser passwordUser passwordUser passwordUser passwordThe User password is set up inexactly the same way as the Install-ers Passwork, see page 6-7.

Once the User Password is activated,the system asks for it beforechanges can be made in the follow-ing:

-Irrigation Start/Stop-Start/Stop of valves-Password-Date and Time-Sectors-Pump and Sensor status-Modify Irrigation Schedule-Time Window

Page 38: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

38

This page is intentionally blank.

Page 39: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

39

PROCOM Main PartsPROCOM Main PartsPROCOM Main PartsPROCOM Main PartsPROCOM Main Parts

M C M 3M C M 3M C M 3M C M 3M C M 3

PSM3PSM3PSM3PSM3PSM3LCM3LCM3LCM3LCM3LCM3

Page 40: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

40

LTB-500LTB-500LTB-500LTB-500LTB-500Line Terminatin BoxLine Terminatin BoxLine Terminatin BoxLine Terminatin BoxLine Terminatin Box

LTB-500/CBLTB-500/CBLTB-500/CBLTB-500/CBLTB-500/CBCircuit Board for LTB-500Circuit Board for LTB-500Circuit Board for LTB-500Circuit Board for LTB-500Circuit Board for LTB-500

System ComponentsSystem ComponentsSystem ComponentsSystem ComponentsSystem Components

Page 41: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

41

Line DecodersLine DecodersLine DecodersLine DecodersLine Decoders

LD-100 LD-200 LD-400 LD-600LD-100 LD-200 LD-400 LD-600LD-100 LD-200 LD-400 LD-600LD-100 LD-200 LD-400 LD-600LD-100 LD-200 LD-400 LD-600

SP-100SP-100SP-100SP-100SP-100Surge ProtectionSurge ProtectionSurge ProtectionSurge ProtectionSurge Protection

Page 42: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

42

PD-100PD-100PD-100PD-100PD-100Pump DecoderPump DecoderPump DecoderPump DecoderPump Decoder

SD-100SD-100SD-100SD-100SD-100Sensor DecoderSensor DecoderSensor DecoderSensor DecoderSensor Decoder

Page 43: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

43

MOP-1MOP-1MOP-1MOP-1MOP-1 MOP-1MOP-1MOP-1MOP-1MOP-1Modem cablesModem cablesModem cablesModem cablesModem cables

OC-100OC-100OC-100OC-100OC-100Optical IsolatorOptical IsolatorOptical IsolatorOptical IsolatorOptical Isolator

Page 44: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

44

FAB-100FAB-100FAB-100FAB-100FAB-100Field Access Unit connection boxField Access Unit connection boxField Access Unit connection boxField Access Unit connection boxField Access Unit connection box

FA-100FA-100FA-100FA-100FA-100Field Access UnitField Access UnitField Access UnitField Access UnitField Access Unit

Page 45: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

45

PROCOM SpecificationsPROCOM SpecificationsPROCOM SpecificationsPROCOM SpecificationsPROCOM Specifications

Hardware specifications:

System capacity 50, 100, 200, 300, 400, 500 decodersValves operating simultaneously 40Electrical input 24 VAC from security transformer, 50-60 Hz, 100 VAElectrical output 33 V square waveSignal cable 2-wire double insulatedMain processor NEC type V40, 16 bit microprocessorStorage components:

Main system program 128 kB EPROM +´256 kB FLASH-ROMInstallation Data 64 kB S-RAMWorking memory 512 kB RAM

Battery Backup Clock/calendar and Installation DataEnvironment Office: 41 F to 86 F

20 to 80 % humidity

Software specifications:

Irrigation Schedules 30Start times Each schedule: 12 times per dayTiming 0-999 minutes, in one minute stepsProgramming cycle 14 daysOperation methods Sequencial, Priority, AutomaticSectors 150Dry Run Simulation on screenMonitoring Monitoring on screen and with Logviewer to print/reportsManual operation Full manual operation of Decoders/SchedulesMain Pipe sections 100Valve types 100Pump control Full automatic control of 6 Main Pumps + 9 Booster pumps

Special Pump Decoder availableSensors Direct wired sensors: Rain Sensor

Aux. SensorLine monitoring: Line current

Leakage currentSensor decoder: 10 Sensor Decoders for flow

monitoring with high-flow andleakage alrams

Field Control Operation of Field Access Unit FA-100 supportedLanguages supported Currently english only, other languages available on request.Measurement units Gallons , inches, m3, liters, mm

Page 46: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

46

IndexIndexIndexIndexIndex

AAAAA

Automatic Method 27Automatic testing 16

CCCCC

Central Unit, connections 3Connect 14

DDDDD

Date and Time 10Decoder Start 29Decoder Stop 29Delete Decoder 25Delete Sector member 35Dry Run 25

FFFFF

Flow Monitoring 12Flow Sensor 10

GGGGG

GF signal 18GF Solenoids 17

IIIII

Installation of software 4Installers Password 6Irrigation Methods 26Irrigation OFF 27Irrigation ON 27Irrigation Schedules 23

LLLLL

LD Thorough 19Line Decoder 20, 24Line Decoders 8Line Survey 22Line Voltage 10Logviewer 32

MMMMM

Main Pipe 7Man. started Decoders 30Manual Start/Stop 29Manual Tests 20Menu Tree 5Methods 24Minutes 24Modem connection 14

Monitoring 31

NNNNN

New Pipe 7

PPPPP

Parameters 6Print Monitoring 31Priority Method 26Pump Decoder 9Pump Status 36

RRRRR

Remove password 7

SSSSS

Schedule Name 23Schedule overlap 28Schedule Start/Stop 30Sector 34Sensor Inputs 9Sensor Status 36Sequential Method 26Short Circuit 10Short Finding 21Simulation 25Solenoid resistance 15Start Irrigation 27Start Times 23Stop All Decoders 29System Layout 2

TTTTT

Test of installation 15Time Window 29Transfer of Data 13True monitoring 15TWC-500 Main Parts 39TWC-500 Specifications 45Type of Valves 8

UUUUU

Updating window 28User password 37

WWWWW

Water Budget 29Week Days 23

Page 47: PROCOM - USER HANDBOOK - Tucor, Inctucor-inc.com/downloads/Procom-Manual.pdf · 3 Central Unit, connections Aux. connector Serial connector ON/OFF switch 24VAC from transformer From

47