product catalogue australia 201 - ampac · 4 fire control panels 5 specifications power supply...

54
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS Product Catalogue Australia 2019

Upload: others

Post on 28-Jul-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS

Product Catalogue Australia 2019

Page 2: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

ContentsFire Control PanelsZoneSense DH4 Conventional 4ZoneSense PLUS Conventional 6ZoneSense PLUS AR Conventional 8LoopSense Intelligent 10FireFinder PLUS Intelligent 12FireFinder Intelligent 14Add Ons 16

Alarm SystemsStandalone Occupant Warning Panel 28Occupant Warning System Add-Ons 30EV3000 Emergency Control Panel 32EV3000 Emergency Control Panel - Add Ons 34

Graphics PackageSmart GraphicsHD 38

Detection & MCP’sConventionalSeries 65 Detection 40Heat Detection 42Manual Call Points 45Sampling Duct Units 46Beam Detection 47

AddressableXP95 Detection 48Discovery Detection 50Manual Call Points 53Duct Sampling Unit 54

Specialist DetectionFlame Detection 55Hazardous Area Detection 58Marine Detection 64Xpander Wireless Detection 66Aspirating Smoke Detection -Wagner Titanus Family 70High Sensitivity Detection System 72Aspirating Smoke Detection - FastSense 73

Audio Visual & InterfacesXP95 Interfaces 76Conventional Audio Visual 80Remote Indicators 83Bells 84Warning Signs 85Addressable Audio & Visual 89Hazardous Area - Intrinsically Safe 92Hazardous Area- Flameproof Equipment 93

Cable2 Core TPS Cable 94

AncillariesElectro-Magnetic Door Holders 97Power Supplies 101Batteries 103Test Equipment 103Ancillary Equipment 105Contact Page 107

www.ampac.net www.ampac.net

Page 3: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

4 5Fire Control Panels

Specifications

Power SupplyMains Supply voltage 204 – 264 VAC @ 47 – 63HzNom. Operating voltage 27 VDCPower Supply Current 1.6 A (max)Quiescent Current 20 mA (without Door Holder)Operating Temperature -5° to +55° C (no icing)Relative Humidity 25% - 75% (non condensing)

Zone Detection CircuitNo of Zones Four (4) x 2-wire systemZone Monitoring Open and Short circuitZone Quiescent Current 4mA, 10uF EOLNo of Detectors/Circuits 40 (max)End Of Line (EOL) 10uF EOLMax Cable Length 3km (Based on cable resistive and capacitive values of 50Ω and 1uF respectively)Outputs Available Alarm Outputs (monitored) Open Collector, 250mA (2 O/P’s available) 10KΩ EOLDoor Holder outputs (monitored) Open Collector, 250mA (2 O/P’s available) 10KΩ EOLFire Output Relay (voltage free) NO, C, NC Contact rating: 1A @ 30VDCFault Output Relay (voltage free) NO, C, NC Contact rating: 1A @ 30VDCAuxiliary DC Output 150mA @ 24VDC

Miscellaneous FeaturesClass Change Input Non-Latching, switched -veAlert Input Non-Latching, switched -veBattery Monitoring 4 Way DIP switch array (factory set to “OFF”)

MechanicalPacked H 310mm x W 500mm x D 110mmMaterial ABS Cabinet Metal Cabinet ABS/Blend High Impact 1.2mm Mild Steel Finish ABS Light Grey Metal Oyster Matt Ripple H 300 x W 360 x D 100 H 300 x W 360 x D 100Weight Packed excluding batteries 3kg 5.2kg

ZoneSense DH4 ABS (BX1) excl Batteries 2250-4200 ZoneSense DH4 METAL (BX10) excl Batteries 2250-4250 Metal BX10 Surround ENC3016-A

Item Numbers

Product Overview

The ZoneSense DH4 Control Panel is a simple and low cost 4 zone panel. It is an ideal fire panel for any small residential ap-plications (not requiring brigade monitoring) or can also be used as a door holder control panel. Each of the 4 zones can be connected up to 40 x high quality commercial grade conventional fire detectors to deliver a high quality detection & alarm system. It is possible to use the ZoneSense panel in ‘Mains only’ option mode which eliminates the need to connect back up batteries. Both ABS and Metal versions are available.

• Dual Door Holder Outputs • Mains Only Mode • Low Quiescent Current • Walk Test Facility • Alert Input • Up to 40 Conventional detectors per Zone • Available in ABS (BX1) and Metal (BX10) cabinet versions

ZoneSense DH4 Conventional

www.ampac.net www.ampac.net

Page 4: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

6 7Fire Control Panels

Specifications

Power SupplyMains Supply voltage 204 – 264 VAC @ 47 – 63HzNom. Operating voltage 27 VDCPower Supply Current 2 A (max)Quiescent Current 40.5 mA (min)

Zone Detection CircuitNo of Zones Four (4) or Eight (8) x 2-wire systemZone Monitoring Open and Short circuitZone Quiescent Current 4mA, 10uF EOLNo of Detectors/Circuits 40 (max)End Of Line Value (EOL) 3K3Ω (default), 4K7Ω, 6K8Ω, 10KΩ and 10uFMax Cable Length 3km (Based on cable resistive and capacitive values of 50Ω and 1uF respectively)

OutputsComms Output RS485 (4 and 8 zone only)EXT Bell Output (monitored) 1A (max) 10KΩ EOLWarning Sys Output (monitored) 1A (max) 10KΩ EOLACF Output (monitored) 1A (max) 10KΩ EOLASE Output (monitored) 1A (max) 10KΩ EOLReset/Buzzer Output Open Collector, 40mA 15sec pulseFire Alarm Output Relay (voltage free) NO, C, NC. Contact rating: 1A @ 30VDCFault Output Relay (voltage free) NO, C, NC. Contact rating: 1A @ 30VDCAuxiliary DC Output (monitored) 500mA @ 24VDC10KΩ EOL

EnvironmentalOperating Temperature -5° to +55° C (no icing)Relative Humidity 25% - 75% (non condensing)

Mechanical Material ABS Cabinet Metal Cabinet ABS/Blend High Impact 1.2mm Mild SteelFinish ABS Light Grey Metal Oyster Matt RippleWeight packed ex Batteries 3kg 8.5kgDimensions (mm) ABS 300 H x 360 W x 100 D Metal 500 H x 405 W x 145 DAncillary 250 H x 405 W x 145 D

ZoneSense PLUS 4 Zone SPX1 Inc Batteries 2553-0410ZoneSense PLUS SP1x OWS25W Inc Batteries 2553-0410-1100ZoneSense PLUS 4 Zone SP1x OWS50W Inc Batteries 2553-0410-1200ZoneSense PLUS 8 Zone SP1X Inc Batteries 2553-0810ZonesSense PLUS 8 Zone SP1X OWS25W Inc Batteries 2553-0810-1100ZoneSense PLUS 8 Zone SP1X OAWS50W Inc Batteries 2553-0810-1200

Ancillary Cabinet 4210-0040

Item Numbers

Product Overview

The Ampac ZoneSense PLUS Fire Alarm Control Panel is a versatile four or eight zone conventional panel. The user friendly navigation system provides simple operation during an emergency while also enabling complex cause and effect program-ming to be undertaken.

A range of modular panel add-on kits allows the panel to be professionally tailored to the requirements of each installation. This means small conventional panels can now be used in a wider range of applications.

ZoneSense PLUS offers you complete control. The panel can be easily upgraded and programmed on site. ZoneSense PLUS is approved to AS4428 and is available in ABS (BX1) or metal cabinets (BX20) with either four (4) or eight (8) zone conventional detection circuits

• Complies with AS4428.1 • Available in 4 Zone or 8 Zone Panels • Up to 40 Conventional detectors per zone • RS485 port supports a range of Add-on modules • vailable in ABS (BX1) and Metal (BX20) cabinet versions

ZoneSense PLUS Conventional

www.ampac.net www.ampac.net

Page 5: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

8 9Fire Control Panels

Item Numbers

ZoneSense PLUS 4 Zone SP1X Agent Release Inc Batteries 2553-0410-0100ZoneSense PLUS 8 Zone SP1X Agent Release Inc Batteries 2553-0810-0100

Product Overview

The ZoneSense PLUS AR (Agent Release) Panel is a dedicated panel for agent release systems. Housed in a metal cabinet, the ZoneSense PLUS AR is available in either four (4) or eight (8) zones. Based on a ZoneSense PLUS Fire Alarm Control Panel (FACP), the AR version is fitted with an Agent Release Panel Add-on (control card and termination board) and a dual action yel-low manual call point as standard. The Agent Release panel add-on option is factory set.

• Dedicated Agent Release system - purpose built with a host of ancillary products to suit • Comprehensive system status – the AR panel includes a number of system status indicators that facilitates ease of

operation and maintenance • Local Control Station with control and indication – mimics full status of the Agent Release panel. An outdoor version of

this product is available • User interface and operation based around Industry Fire Emergency procedures – ensures that the system installed is

intuitive and easy to use • Dual action Manual Call Point – the yellow MCP is a break glass type and requires a dual action to be activated i.e. lift the

protective transparent cover and break the glass • Agent Release Panel is compliant with AS4214

Specifications

Power SupplyMains Supply voltage 204 – 264 VAC @ 47 – 63HzNom. Operating voltage 27 VDC Power Supply Current 2 A (max)Quiescent Current 40.5 mA (min)

Zone DetectionNo of Zones 4 or 8, 2 Wire Zone Monitoring Open and Short circuitZone Quiescent Current 4mA, 10uF EOLNo. of Detectors per Zone 40 max Zone End Of Line Value 3K3Ω (default), 4K7Ω, 6K8Ω 10KΩ and 10uF

OutputsEXT Bell Output 500mA (max) 10KΩ EOL monitored Warning Sys Output 500mA (max) 10KΩ EOL monitored ACF Output 500mA (max) 10KΩ EOL monitoredASE Output 500mA (max) 10KΩ EOL monitoredFire Alarm Output Relay NO, C, NC Contact: 1A @ 30VDC Fault Output Relay NO, C, NC Contact rating: 1A @ 30VDC Auxiliary DC Output 500mA @ 24VDC 10KΩ EOL monitoredReset/Buzzer Output Open Collector, 40mA 15sec pulse

EnvironmentalComms Output RS485Operating Temperature -5° to +55° C Relative Humidity 25% - 75% non condensing

Dedicated Agent Release Inputs and Outputs Pressure Switch Input Monitored InputLow Pressure Switch Input Monitored Input Interlock Input Monitored InputGas Fired Output Volt Free Changeover 1A@24VDCSystem Inoperative Output Volt Free Changeover 1A@24VDC Stage 1 Relay Output Volt Free Changeover 1A@24VDCStage 1 Monitored Output 1Amp 10KΩ EOL (Voltage reversal)Stage 2 Relay Output Volt Free Changeover 1A@24VDCStage 2Monitored Output 1Amp 10KΩ EOL (Voltage reversal)Release Initial Agent Output Monitored current limited 2A max Release Reserve Agent Output Monitored current limited 2A max

MechanicalMaterial 1.2mm Mild Steel Finish RippleCabinet Dimensions (mm) 500(H) x 405(W) x 150(D) Ancillary Cabinet Dimensions (mm) 250(H) x 405(W) x 145(D)Weight packed ex Batteries Metal 8.5kg

ZoneSense PLUS AR Conventional

www.ampac.net www.ampac.net

Page 6: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

10 11Fire Control Panels

Specifications

Power Supply (General) SP1X P8XDimensions 00H x 405W x 150Dmm 845H x 515W x 175DmmWeight 9kg 15kgPower Supply 3 Amp PSU version 5 Amp PSU versionMaximum Battery Capacity 26Ah 40.0AhInput Voltage 204 - 264VACOutput Voltage 27.5VDC +/- 0.1VDC Battery Discharged Cut Off Voltage 21VDC 21VDCMaterial 1.2 mm steelFinish Surf Mist Ripple

LoopQuiescent Current(1 Loop Panel) 115mAQuiescent Current (2 Loop Panel) 135mALoop Capacity 500mA maxMax No of Detectors/Devices per Loop 126Cabling Requirements 2 core 1.5 to 2.5 mm2Fault supervision O/C, S/C, overcurrent

Outputs/InputsOutputs (SupervisedProgrammale) 4 x 24VDC @ 500mA maxRelay outputs (Programmable) 3 x Voltage free 24VDC @ 1AOpen Collector Output (Programmable) 2 x 30mAAuxiliary VDC(Programmable) 2 x 24VDC @ 500mAInputs (Programmable) 4 x O/C, S/C, 10K EOL

Communications PortInternal to LoopSense RS485External to LoopSense RS485Printer port RS232 or ParallelPC Interfacing RS232 or USB 2.0

EnvironmentalOperating temperature -5°C to +55°C (no icing)Relative humidity 25% to 75% (non condensing)IP rating IP30

Product Overview

LoopSense is an Intelligent Analogue Addressable Fire Alarm Control Panel. Available in one or two loops, the LoopSense comes packed with options and features that facilitate flexibility, ease of installation and commissioning.

• Complies to AS7240-2:2004, AS7240-4:2004, and AS4428-3:2010 -ActivFire listed • Clear back-lit 240 x 64 graphic LCD • 500mA loop current • Advanced balanced loop design for noise rejection • Auto learn facility • Supports extensive range of Add Ons, including the SmartTerminal Repeater • User friendly Loopmaster programming software tool • Laptop connection using USB2.0 or RS232 serial port • Available in ABS (BX1) and Metal (BX10) cabinet versions

LoopSense 1 Loop 3A SP1X 8251-0210LoopSense 1 loop 6A SP8X 8251-0210LoopSense 2 Loop 3A SP1X 8251-0113LoopSense 2 Loop 6A SP8X 8251-0213LoopSense 1 Loop 3A SP1X OWS25 8251-0110-1100LoopSense 2 Loop 3A SP1X OWS25 8251-0210-1100LoopSense 1 Loop 3A SP1X OWS50 8251-0110-1200LoopSense 1 Loop 6A SP8X OWS50 8251-0213-1200LoopSense 2 Loop 6A SP8X OWS50 8251-0213-1200

LoopSense Intelligent

Item Numbers

www.ampac.net www.ampac.net

Page 7: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

12 13Fire Control Panels

SpecificationsPower Supply (Gereral) Cabinet SP1X Cabinet SP8X/SP16XPower Supply 5A PSU version 5A PSU / 22A PSU Version Input Voltage 195 - 264VAC 195 - 264VACProtection 2 Amp 3AG 2 Amp 3AG (5A PSU)/ 5 Amp 3AG (18A PSU) Output Current 5.6 Amps 22 AmpCharger Current 1.25A 1.25A / 3AMaximum Battery Capacity: 26Ahr 40AhrCharger Output Voltage: 27.5 +/- 0.1VDCBattery Type: 2 x 12V Sealed Lead AcidDischarge Cut-off voltage: 21VDC

LoopPanel Quiescent Current1 Loop 220mAAdditional Loops (even) +40mA for each Loop Additional Loops (odd) +75mA for each LoopLoop Capacity 500mA max per LoopMax No of Devices per Loop 126Cabling Requirements 2 core 1.5 to 2.5mm² Fault supervision O/C, S/C, Over current Inputs/OutputsOutputs (Programmable) 4 x 24VDC @ 1 Max, 10K EOL Relay outputs (Programmable) 5 x Voltage Free - 24VDC@1AmpAuxiliary Power Outputs 2 x 24VDC @ 500mA Inputs (Programmable) 4 x O/C, S/C, 10K EOL

CommunicationComms External to FACP RS485Comms Printer port RS232 or ParallelComms PC Interface RS232 or USB 2.0

Environmental Temperature -5ºC to + 40ºC Humidity 25% to 95% (non-condensing)

MechanicalMaterial 1.2mm Mild SteelColour/Finish Surf Mist RippleDimensions (mm)SP1M 500H x 405W x 150DSP1X 500H x 405W x 150DSP8X 845H x 518.5W x 173D SP16X 1200H x 625X x 240D IP Rating IP30 (Indoor Use Only)

Item Numbers

Product Overview

FireFinder Plus is an Intelligent Analogue Addressable Fire Alarm Control Panel that is available in 1 to 8 loop panel options. The FireFinder Plus is suitable for medium to large sized fire detection systems and is compatible with Apollo XP95, Discovery and Series 90 detectors. Powerful and flexible programming is achieved via AMPAC’s configuration tool ConfigManager Plus which includes many dedicated pre-engineered programming functions. Simple system programming is easily achieved via the front panel. FireFinder Plus is configurable as a peer to peer network up to 100 panels/nodes with a maximum of 150 Loops.

• Fully approved to AS2740-2 , AS720-4 and AS4428.3:2010 • Fully Expandable 1 to 8 Loop Fire Alarm Control Panel • Large Graphic (240 x 64 pixel) Display • 500mA Loop Current • 4 Programmable Monitored Inputs • 4 Programmable Monitored Outputs • 5 Programmable Relays • 2 Auxiliary Power Outputs • Programmable via front panel • Networkable • Supports High Level Graphics Interface • Supports a Range of Panel Add-ons

FireFinder PLUS Intelligent

(Addressable) FireFinder PLUS 1 Loop 5A SP1X 8651-0110 FireFinder PLUS 1 Loop 5A Agent SP1 8651-0110-0100FireFinder PLUS 1 Loop OWS25 5A SP1 8651-0110-1100FireFinder PLUS 1 Loop OWS50 5A SP1 8651-0110-1200FireFinder PLUS 1 Loop 5A SP8X 8651-0113FireFinder PLUS 1 Loop Agent 5A SP8 8651-0113-0100FIREFINDER+ 1 Loop AGENT 5A SP8 8651-0113-0700FIREFINDER+ 1 Loop OWS50 5A SP8 8651-0113-1200

(Conventional) FireFinder PLUS 8 Zone 5A SP1X 8653-0810FireFinder PLUS 8 Zone OWS25 5A SP1 8653-0810-1100FireFinder PLUS 8 Zone OWS50 5A SP1 8653-0810-1200

www.ampac.net www.ampac.net

Page 8: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

14 15Fire Control Panels

Product Overview

FireFinder is a state of the art multi microprocessor controlled Intelligent Fire Alarm Control Panel. Modular in design, the FireFinder provides flexibility and versatility that can be configured to operate with both intelligent analogue addressable and conventional devices in the one system.

Available in single loop or multiple loop configurations, the FireFinder supports the leading Apollo XP95 and Discovery detec-tor protocols. The Ampac ConfigManager software tools provide a powerful combination with the FireFinder to configure the system operational and functional characteristics of an installation. Enhanced networking capabilities offer the user extended applications with FireFinder incorporating a Master/ Slave Fire control panel arrangement, true Peer to Peer systems, data gathering panels and SmartGraphics a PC based application for the supervision, monitoring and control oflarger fire management systems.

• Complies with AS4428.1 and AS1603.4 • Clear back-lit 40 character 8 line LCD display • Programming options via the front panel or laptop computer • Remote system interrogation and diagnostics • Extensive Alarm Management resources • Self Auto Learn capabilities • Day Night sensitivity settings • Versatile multi processor architecture • Event log and printer options • SPOT – Single Person Operation Test • Flexible modular expansion and panel Add Ons • Optional 32, 64, 96 & 128 zone indicators • SmartTerminal repeater options

(Conventional) FireFinder SP1X 16 Zone AS4428 8550-1150FireFinder SP1X 16 Zone ASE 8550-1250FireFinder SP1X 16Zone OWS25 8550-1450-1100FireFinder SP1X 16Zone OWS50 8550-1530-1200FireFinder SP1X 16Zone 8550-1151

(Addressable) FireFinder SP1X 1Loop AS4428 8550-1100FireFinder SP1X 1Loop ASE 8550-1200FireFinder SP1X 1Loop OWS50 8550-1440-1200

Specifications

Power SupplyFinish Arch White RippleMaterial 1.2mm steelInput Voltage 85 to 264Vac (47-63Hz)Output Voltage 27Vdc Output Current 2A, 5.6A or 18ABattery Type 2 x 12V SLA batteries

LoopQuiescent Current 240mA (min 1 Loop no load)Devices per Loop 126 Loop Current 250mADevices per Zone 40Conventional Zone EOL 3K3Cable (Loop and Conventional Circut) 2 core 1.5 to 2.5mm²

Outputs/InputsOutputsBell 1 2 Amp Fused Bell 2 2 Amp Fused Plant Monitored 1 Amp Fused, 10K EOLPlant Un-Monitored 1 Amp voltage free contactWarn Sys Monitored 1 Amp Fused, 10K EOL Warn Sys Un-Monitored 1 Amp voltage free contactFault Monitored 1 Amp Fused, 10K EOLFault Un-Monitored 1 Amp voltage free contact Isolate 1 Amp voltage free contactAlarm 1 Amp voltage free contact Valve Monitor 1 Amp voltage free contactBatt Fail (normally energised) 1 Amp voltage free contact Battery Output ProtectedAux Power Output 1 1 Amp FusedAux Power Output 1 EV40 use 3 Amp Fused Aux Power Output 2 1 Amp FusedDBA/MCP Monitored 10K EOL

Environmental Temperature 5ºC to + 55ºC Humidity 25% to 75% (non-condensing)IP Rating IP51

Item Numbers

FireFinder Intelligent

www.ampac.net www.ampac.net

Page 9: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

16 17Fire Control Panels

SmartTerminal Repeater *FF+ *LS *FF

The SmartTerminal has been designed to display the status of and provide limited controls for the FireFinder Plus and LoopSense Fire Alarm Control Panels (FACP) in m

Operating VoltageInternal (24Vdc) 18 – 27 V DCExternal (240Vac) 204 - 264VACQuiescent Current 12.5mA (backlight off, buzzer off)Maximum Current 43.8mA (backlight on, buzzer on)Temperature -5ºC to + 55ºCHumidity 25% to 75% (non-condensing)Cabling Requirements 2 core 1.5 to 2.5mm²External Power Supply 1.8A plus 400mA Battery Charging(4350-0005 only)Battery Size 3.2AHr(4350-0005 only)Material ABSDimensions BX05 195 (H) x 325 (W) x 50 (D) BX1 300 (H) x 360 (W) x 100 (D)

FireFinder FF SmartTerminal (BX1 enclosure) 4350-0001FF SmartTerminal inc PSU (BX1 enclosure) 4350-0002 FF SmartTerminal (BX05 slimline enclosure) 4350-0003

FireFinder Plus and LoopSense FF+/LS SmartTerminal (BX1 enclosure) 4350-0004FF+/LS SmartTerminal inc PSU (BX1 enclosure) 4350-0005FF+/LS SmartTerminal (BX05 slimline enclosure) 4350-0006Wall Mount Surround 4210-0046

FireFinderTerminal Repeater

Network Interface Card 2 Wire 4210-0006

2 Wire Network Interface Board *FF+

• Supports Redundant Network, with Isolated Network In and Out Ports • Up to 99 Network Nodes • 115200 Baud Rate • Distance Between Nodes 1.2km • Uses Industry Standard RS485 • Diagnostic LEDs

Voltage 27 VDCQuiescent Current 41 mAProtocol RS485Max distance (between NICs) 1.2kmCable requirements 2 Core Screened Fire ResistantOperating temperature -5°C to +40°C Relative humidity 0 to 95% (non condensing)

High Level Interafce - Factory Fitted 159-0268 High Level Interface - Add-On Kit 4310-0080

High Level Interface Expander or Port Expander Board *FF+ *LS *FF

• Building Management • Paging system • Nurse Call Systems • SmartGraphics • MODBUS

Voltage 24 VDCQuiescent current 2.4 mAMax current 80 mARelay contact rating 1 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 130 grams

Loop Module Expansion Kit *FF+

• Expands the capacity of the FireFinder to accommodate a further four loops, 64 conventional zones, four I/O modules or any combination of the above • Requires a main controller board

Voltage 24 VDCQuiescent current 5 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 110 grams

FireFinder Plus Loop Expansion Board 8610-0003

Analogue Loop Upgrade Kit *FF+

• This kit adds an intelligent analogue loop to the FireFinder PLUS Control Panel • For an odd numbered loop upgrade the kit consists of an I/O CPU module, cable

and termination card • An even numbered loop upgrade consists of an I/O CPU module and cable

Voltage 24 VDCQuiescent current 40 mALoop current 500 mA max.Operating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 200 grams

FireFinder Plus Slave CPU Board 8610-0001FireFinder Plus Term Board 8610-0002

LoopSense/FireFinder PlusTerminal Repeater

(*FF+ - FireFinder PLUS compatable, *FF - FireFinder compatable, *LS - LoopSense compatable, *ZSP- ZoneSense PLUS compatable)Add Ons

www.ampac.net www.ampac.net

Page 10: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

18 19Fire Control Panels

Relay Board 4310-0050Relay Board (Remote) 4310-0055

8 Way Relay Board *FF+ *LS *ZSP

• Provides volt free change over contacts • 8 relay outputs per board • Remote version available – DIN Mount chassis • Remote version communication via RS485 serial link

Voltage 24 VDCQuiescent current 2.4 mAMax current 80 mARelay contact rating 3 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 130 grams

8 Zone Conventional Board 4310-0082

8 Zone Conventional Board *FF+ *LS

• Supports up to eight conventional zones • Selectable end of line device 3K3, 4K7, 6K8, 10K or 10µF capacitor • Supports head removal requirement on each zone • Supports up to 40 conventional devices per zone circuit (ORBIS/Series 65) • Programmable latching and non-latching (self-resetting) input on each zone

circuit

Voltage 24 VDCQuiescent current 15mA (including capacitive EOL current) plus device currentAlarm current 43mA (one circuit in alarm)Operating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Size 72.5 x 155mmWeight 120 grams

16 way Input Board *FF+ *LS *ZS

• Provides inputs for sprinkler pumps, tanks, valves, shutdowns, etc • 16 inputs per board • Inputs map to relays or indicators • Programmed via the LoopMaster

Voltage 24 VDCQuiescent current 2.6 mAMax current 45 mAOutput rating 0.5 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing) Weight 120 grams

Input Board 4310-0040

Fire Fan Module *FF+ *LS *FF *ZSP

• Four (4) Controls per Module • Status indication for Run / Fault / Stop • Controls for On / Auto / Off • Audible and visual feedback of button press • Built in Plant Trip Reset • Supports 3, 4 and 5 Wire Connections • Available in Hard Wired or loop driven versions

Operating Voltage 27VDCDimensionsController Card Fits standard Panel Cut-OutTermination Board 155mm x 72mmContact Rating 1 @ 24VDCApproval AS1668

Hard Wired (Includes controls and termination board) 4310-0021Loop Driven (Controls only) 4310-0071

32 Zone Indicator Card *FF+ *LS

• Provides 32 Zone LED’s capable of indicating zone Fire, Disabled, Fault and Dependency B. • Suitable for use with the FireFinder range of FACP’s • Suitable for use with LoopSense FACP • Customisable zone identification label • Fully programmable via LoopMaster

Voltage 27 VDCQuiescent current 3.6 mAMax current 8mAOutput rating 0.5 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams

32 Zone Indicator Card 4310-0086

8-way Sounder Board *FF+ *LS *ZSP

• Provides 8 monitored switched 24 VDC outputs per board • Max 1 per FireFinder PLUS

Voltage 24 VDCQuiescent current 5.6 mAMax current 26 mAOutput rating (ea) 500 mA at 24 VDCEOL Monitoring Value 10k ΩOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams

Sounder Board 4310-0060

Add Ons

www.ampac.net www.ampac.net

Page 11: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

20 21Fire Control Panels

Add Ons

Zone Disable & Indicator Module 4310-0087

Zone Disable and Indicator Module *FF+ *LS *FF

• Provides 8 Programmable Zone Disable Switches • Provides 8 Status LEDs • Customisable Switch Identification Label

Voltage 27VDCQuiescent current 3.6 mAMax current 8 mACommunication RS485Operating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams

Switch/Indicator Card 4310-0030

8 Switch/Indicator Module *FF+ *LS *ZSP

• 8 x Push Button On / Off switches • Controls and Monitors solenoid test switches, manual shutdowns and etc • Programmable via the ZoneSense PLUS front panel • Programmable via ConfigManager for the FireFinder range of panels • Programmable via LoopMaster for the LoopSense range of panels

Voltage 24 VDCQuiescent current 3.6 mAMax current 8 mAOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 100 grams

Fire Brigade Board 4310-0070

Fire Brigade Board *LS ZSP

• Provides common outputs for connection to fire brigade signalling equipment • 5 outputs – Alarm, Fault, Isolate, Battery Fail and 2nd Alarm

Voltage 24 VDCQuiescent current 9 mAMax current 52 mAOutput rating 1 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 110 grams

Agent Release Module 4310-0011

Agent Release Module *FF+ *LS *FF *ZSP

• Compliance with AS4214 • Controls & Monitors Agent release system • Outputs for warning signs & activation devices • Inputs for signals from pressure switches & valves • Serial connection to Agent release (LCS) Local control Station • Programmed via the FACP front panel • Location or title descriptor label

Pressure Switch Input Monitored InputLow Pressure Switch Input Monitored InputInterlock Input Monitored InputGas Fired Output Volt Free Changeover 1A@24VDCSystem Inoperative Output Volt Free Changeover 1A@24VDCStage 1 Output MonitoredStage 2 Output MonitoredRelease Initial Agent Output Monitored current limited 2A maxRelease Reserve Agent Output Monitored current limited 2A max System Capacity FireFinder 8 Maximum LoopSense 8 Maximum ZoneSense Plus 1 Maximum

Network Interface Card (NIC)- 2 Wire Network *FF

• The NIC gives the FireFinder network capabilities via the RS422 communications port • Provides an additional RS232 communications port when connected to Controller

Interface Card (CIC) • High level interface for Building Management or ModBus protocol for

SmartGraphics and PLCs • The NIC can be isolated from other network devices • Loop In/Loop Out for easy installation

Voltage 24 VDCQuiescent Current 65 mAAvailable Ports RS422 – network RS232 – serial commsMax distance (between NICs) 1.2kmCable requirements RS485 – 1 pair twisted/screened RS232 – 1 pair twisted/screenedOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 225 grams

SP1X 159-0258SP8X 159-0259SP16X/Rack 159-0260Add-On Kit 4310-0079

Agent Release- Local Control Station *FF+ *LS *FF *ZSP

• Remote Agent release LCS • Complies with AS4214 • For use only with Agent release Module 4310-0011 • Double Action manual Agent release facility • Toggle between initial & reserve agent • Can install up to 8 x LCSs per panel

Local Control Station 4310-0019

www.ampac.net www.ampac.net

Page 12: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

22 23Fire Control Panels

4 Plus 4 Bell Monitor *FF

• The 4 Plus 4 Bell Monitor has screw terminals for 4 voltage free contacts and 4 switched 24V DC sounder outputs • The outputs are programmable and monitored for open or short circuit • The board connects directly to the main controller board

RS422 RS232 Voltage 24 VDCQuiescent Current 65 mAAvailable Ports Network Serial commsMax distance (between NICs) 1.2kmCable requirements 2 pair twisted/screened 1 pair twisted/screenedOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 225 grams

4 Plus 4 Bell Monitor Board 159-0069

8-Way 5A Relay *FF

• Each upgrade panel add-on offers 8 voltage free relay outputs. Each output is rated at 5 amps, 24 VDC • Each relay has a single normally open/close volt-free contact extended to a wire-

protected screw terminal • The standard 8-way relay upgrade requires spare capacity available on a 128/128

I/O and 16/16 I/O module

Voltage 24 VDCQuiescent current 5 mA (Serial Relay Board)Operating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 190 grams

SPX 8-Way 5A O/P Relay 159-0013Rack 8-Way 5A O/P Relay 159-0015

8 Way Bell Monitor Board *FF

• The 8-Way Bell Monitor has 8 switched 24V DC sounder outputs • The outputs are programmable and monitored for open or short circuit • The board connects directly to the main controller board

Voltage 24 VDCQuiescent current 20 mAMax sounder output current 1 Amp eachMax output current 4 Amps per boardOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 250 grams

8 Way Bell Monitor Board 159-0071

16 Way Conventional Zone Card *FF

• Adds 16 conventional Alarm Zone Circuits • Kit consists of an I/O CPU module, cable and 16 zone termination card • Supports up to 40 conventional detectors (Series 60, Series 65 or Orbis) per zone • Fixed 3K3 End-Of-Line device

Voltage 24 VDCQuiescent current 145 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 185 grams

SP8X/SP16X 16 Way Conventional Zone Card 159-0005Rack 16 Way Conventional Zone Card 159-0006

Module Expansion Kit for Modules (5-8) *FF

• Expands the capacity of the FireFinder to accommodate a further four loops, 64 conventional zones, four I/O modules or any combination of the above

• Requires a main controller board

Voltage 24 VDCQuiescent current 5 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 110 grams

SP8X Loop Module Expansion Kit 159-0012SP16x/Rack Loop Module Expansion Kit 159-0022

8 Way Serial Relay Output Board *FF

• Each serial relay output board offers 8 voltage free relay outputs, each rated at 5 amps, 24 VDC • Each relay has a single normally open/close volt-free contact extended to a wire-

protected screw terminal • The serial 8-way relay is driven directly from the main controller board

Voltage 24 VDCQuiescent current 5 mARelay output current 5 Amps at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 190 grams

Rack 8 Way Serial Relay Output Board 159-0072SPX8 8 Way Serial Relay Output Board 159-0079

Add Ons

www.ampac.net www.ampac.net

Page 13: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

24 25Fire Control Panels

Panel Mounted LED Indicators *FF

• Provide flexibility to include additional LED indicators to the FireFinder SP1X and SP8X • Available in three versions: • – 32 zone alarm only indication (red) • – 16 zone alarm/fault indication (red/amber) • – 32 zone general indication (amber) • Serial connection to the FireFinder panel • Simple clip installation • Indicators remain illuminated until reset by the panel • Indicators are tested by the FireFinder panel’s lamp test control

Voltage 27 VDCQuiescent current 30 mAMax current 40 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams

FireFinder SP1X 32 Zone Alarm Only Indication (Red) 159-0106FireFinder SP8X 32 Zone Alarm Only Indication (Red) 159-0089FireFinder SP1X 16 Zone Alarm/Fault Indication (Red/Amber) 159-0107FireFinder SP8X 16 Zone Alarm/Fault Indication (Red/Amber) 159-0108FireFinder SP1X 32 Zone General Indication (Amber) 159-0123FireFinder SP8X 32 Zone General Indication (Amber) 159-0124

Modem *FF

• The modem allows a remote access to FireFinder • Configuration and application software can be uploaded or downloaded via the

modem • Wireless Modem requires available signal from appropriate network • All modems are AUSTEL approved • Great tool to provide remote support

Voltage 27 VDCData transfer rate 9600 baud maxComms to FACP RS 232Operating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight SP & Rack: 1kg Wireless: 5kg

SPX Modem 159-0033Rack Modem 159-0065Wireless Modem 159-0068

Remote Mounted LED Indicators *FF

• The remote LED indicator boards provide facilities to mimic the FireFinder zone LEDs and switches • Connects to the RS485 communications bus via the controller interface card • Allows the custom design of geographic site layout mimics • Each termination board connects up to 32 zone LEDs – 31 boards maximum –

total 992 zone indications

Voltage 27 VDCQuiescent current 8 mA maxMax current 100 mACommunication mode RS485Baud rate 19200 maxCommunication cable 1 x pair twisted and screenedNo. of boards 31 maxNo. of zones 992 zones maxBuzzer external max current 20 mAOn board status indication Power on – green Normal – green Fault – yellowCommon inputs Reset Lamp test Buzzer mute Bell isolate Manual evacuateOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)

FireFinder LED Mimic Driver 32 Way 159-0145Mimic Output Termination Board 159-0152FireFinder 16 Zone LED Display Board 159-0218

Add Ons16 Opto Inputs *FF

• The Opto Input panel add-on provides 16 programmable electrically isolated inputs to the FACP • The input from a third party source should be a volt-free contact • This upgrade requires spare capacity available on a 128/128 I/O and 16/16 I/O

Interconnect Module

Voltage 24 VDCQuiescent current 5 mAOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 185 grams

SP 16 Opto Input 159-0010Rack 16 Opto Input 159-0011

www.ampac.net www.ampac.net

Page 14: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

26 27Fire Control Panels

Panel Printer *FF+ *LS *FF

• The dot matrix printer provides hardcopy activity report • Alarms, faults, isolates and system logs may be printed • 3 colour status LED • Self test mode • Easy maintenance for replaceable ribbon cassette and paper roll

Voltage 5 VDCQuiescent current 1A @ 5 VDCCharacter size 5 x 7 dotsOperating temperature -5°C to +55°C (no icing)Relative humidity 25 to 95% (non condensing)Weight 380 grams

Printer C/W Mounting plate (Suit Australian White SP1 cabinet) 159-0084Printer C/W Mounting plate (Suit Australian) 159-0110Paper Rolls (10) MIS1981Ribbon MIS1982

Analogue Loop Upgrade Kit *FF

• This kit adds an intelligent analogue loop to the FireFinder Control Panel • For an odd numbered loop upgrade the kit consists of an I/O CPU module, cable

and termination card • An even numbered loop upgrade consists of an I/O CPU module and cable

Voltage 24 VDCQuiescent current 40 mALoop current 250 mA max.Operating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 200 grams

1 Loop Upgrade Kit- even numbered loop SP1X 159-00011 Loop Upgrade Kit and Processor- odd numbered loop SP1X 159-0003Even No. Loop SP16X/Rack 159-0002Even No. Loop SP8 159-0046Odd No. Loop SP16X/Rack 159-0004

Add OnsFibre Optic Network Interface *FF

• 4 versions available to suit your cabling scheme on site • Redundant loop integrity (same as copper) • A network interface card is still required at each FACP node • Maximum distance using ‘Multimode’ (between nodes) up to 5km; using Single

Mode 50km

Supply Voltage 24 VDCQuiescent Current 80 mA @ 24 VDCOptical Connector ST standardPorts Available RS422/RS485Size (mm) 104D x 104W x 25HWeight 280gOperating Temperature -20°C to +75°CHumidity 0 to 95% relative, non-condensing

FireFinder Fibre Optic Multimode 2 Core 159-0251FireFinder Fibre Optic Multimode 1 Core 159-0252FireFinder Fibre Optic Single Mode 2 Core 159-0253FireFinder Fibre Optic Single Mode 1 Core 159-0254

www.ampac.net www.ampac.net

Page 15: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

28 29Alarm Systems

Product Overview

The Ampac EvacU is a fully self-contained Occupant Warning System. Systems are available from 25W up to 200W and incorporate Ampac’s new range of Class “D” 25N & 50N Amplifiers, Control & Indicating modules and Line splitters.

Up to eight Emergency zones and eight seperate Paging Zones can be configured using the dedicated EvacUwiz programming tool.

• Highly Efficient Class D Amplifier Technology • Alert and Evacuation Signals to AS1670.1 • Speaker Line Fault Monitoring and Protection • Monitored Strobe Output • Dedicated Emergency Microphone Input • Secondary BGM and PA Analogue Audio Input • False Alarm, System Test and Lock Down Messages • Custom Messages • Up to 8 Emergency Zones • 8 Zone Remote Paging console

Standalone Occupant Warning Panel

Specifications

Power Supply (General)Power Supply 3, 5 or 10Amps @ 24VBattery Size Max 17 Ahr(Battery box may be required) (depends on No. of Amplifiers fitted)Cabinet Dimension (mm) 500(H) x 405(W) x 150(D)

AmplifiersAmplifiers (Audio) Current Quiescent / Alarm25W (Max 4) 20 mA / 1.19 A each50W (Max 4) 20 mA / 2.39 A eachAmplifiers (Visual)Strobe Output 1A Max per AmplifierStrobes Xenon Max 8 setsStrobes LED Max 40 setsAmplifiers Audio O/P 100VacEmergency Zones Up to 8 maxFront Controls (Max 1) 10.5 mA Quiescent

Item Numbers

EvacU 25W 3A 6050-0010-1100 EvacU 50W 3A 6050-0010-1200 EvacU 100W (2 x 50W) 5A 6050-0010-1400 EvacU 150W (3 x 50W) 10A 6050-0010-1500EvacU 200W (4 x 50W) 10A 6050-0010-0800Handheld Microphone 6010-0010 OWSDual XENON 208-0011Dual LED Beacon Shallow Base 4107-1005Dual LED Beacon Deep Base 4107-1006

Zone Indicator Module 6010-0012 OWS

8 Zone Indicator Module

• An optional Zone Indicator module is available when more than one emergency zone is programmed and the user requires individual Zone Alarm, Alert, Evacuation and Fault indications • The Zone Module also provides the ability to select and broadcast live speech to

individual emergency zones

Quiescent Current 10.5 mA

4 Way Line Splitter 6010-0013 OWS

4 Way Line Splitter

• A four way Line splitter provides the ability to have a single emergency zone split into 4 separate monitored branches • When a remote paging console is connected each split can be assigned to separate

paging zones • Up to two splitters can be connected to a single amplifier with a maximum of four

splitters per system

Quiescent Current 10.5mA100V Line outs 4 (Max 100W each to a max of 250W total)Monitoring EOL 10K – 47K Ω

8 Zone Paging Console 6010-0014 OWS

8 Zone Paging Console

• The Remote Paging Console allows up to 8 individual paging zones to be pro-grammed when a combination of more than one amplifier and/or Line Splitters are included in the system

• Additionally the RPC includes a back ground music input which can be programmed to each zone via the Remote Paging Console

Quiescent Current 5.5 mANumber of Zones 8BGM Input Source 3.5mm Audio JackCable CAT5 RJ45 connectionCable Distance 100m

www.ampac.net www.ampac.net

Page 16: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

30 31Alarm Systems

Product Overview

The Ampac Single Zone Occupant Warning System is available with a 25 Watt and 50 Watt audio output with an optional front panel control. The alert and evacuation signals are compliant to AS1670.1 including voice messages as standard. The speaker circuit is protected and monitored for shorts and interruptions. Up to three spur lines (branches) are supported. A monitored strobe output is provided as standard which i supports both xenon and led strobes.

Each audio source (alert / evacuation signals, emergency paging and secondary analogue audio input) has a dedicated volume control. Three programmable relays are provides, which default to fault, volume control override and test mode.The optional front panel control has an integrated emergency microphone (and can optionally support a hand held microphone) The Single Zone Occupant Warning System is suitable for use in Ampac’s FireFinder, LoopSense and ZoneSense Plus Fire Alarm Control Panels.

• Available in 25Watt and 50Watt versions • Alert and Evacuation Signals to AS1670.1 • Speaker Line Monitoring and Protection • Monitored strobe output • Volume Control • Dedicated emergency microphone input • Secondary analogue audio input • Programmable evacuation strategies • False Alarm, System test and Lock Down Messages • Three programmable output relays

Occupant Warning System Add-Ons

OWS 50W Amplifier 6010-0001OWS 25W Amplifier 6010-0002OWS Indicator & Controls 6010-0003

25 W& 50W OWS 25watt 50watt

Max. Curret (full audio load, no strobe load) 1.19Amps 2.39AmpsSupply Voltage 27VCD (nominal) Quiescent Current (no audio load, no strobe load) 20mampsStrobe Output (Xenon) 8 sets (208-0011) Strobe Ouput (LED) 40 sets (4107-1005/6)Audio Output Voltage 100VACTemperature -20° to +70° C Humidity 0-95% non-condensingAlert / Evac Changeover time (secs) Alert only, Evac only, 60, 90, 120, 180, 300 or under manual controlSpeaker EOL Nominal 47KΩ 5% 1/3 WattTHD 0.12% 0.89%Signal to Noise Ratio 80.5dB 82.1dBAlert Signal To AS1670.1 including voiceEvacuate Signal To AS1670.1 including voiceAmplifier (L x W x H) 100 x 77 x 35mm

OWS 120W Amplifier 6010-0004OWS Indicator & Controls 6010-0003

120W OWS

Supply Voltage 27VDC (nominal)Max Audio Load 120WattQuiescent Current (no audio load, no strobe load) 240mAmpsMax. Current (full audio load, no strobe load) 8AmpsStrobe Output (Xenon) 8 sets (208-0011)Strobe Output (LED) 40 sets (4107-1005/6)Audio output voltage 100VACTemperature -20°C to 70°CHumidity 0-95% non-condensingAlert / Evac Changeover time (secs) Alert only, Evac only, 60, 90, 120, 180, 300 or under manual controlSpeaker EOL Nominal 47kΩ 5% 1/3 WattTHD <0.6%Signal to Noise Ratio 91dBAmplifier Dimension(L x W x H) 170mm x 210mm x 85mm

250W OWS

Supply Voltage 27VDC (nominal)Max Audio Load 250WattQuiescent Current (no audio load, no strobe load) 380mAmpsMax. Current (full audio load, no strobe load) 17Strobe Output (Xenon) 8 sets (208-0011)Strobe Output (LED) 40 sets (4107-1005/6)Audio output voltage 100VACTemperature -20°C to 70°CHumidity 0-95% non-condensingAlert / Evac Changeover time (secs) Alert only, Evac only, 60, 90, 120, 180, 300 or under manual controlSpeaker EOL Nominal 47kΩ 5% 1/3 WattTHD <0.6%Signal to Noise Ratio 91dBAmplifier Dimension(L x W x H) 300mm x 240mm x 95mm

OWS 250W Amplifier 6010-0005OWS Indicator & Controls 6010-0003

500w OWS

Supply Voltage 240VAC/27VDC (nominal)Max Audio Load 500WattQuiescent Current (no audio load, no strobe load) 500mAmpsMax. Current (full audio load, no strobe load) 35AmpsStrobe Output (Xenon) 8 sets (208-0011)Strobe Output (LED) 40 sets (4107-1005/6)Audio output voltage 100VACTemperature -20°C to 70°CHumidity 0-95% non-condensingAlert / Evac Changeover time (secs) Alert only, Evac only, 60, 90, 120, 180, 300 or under manual controlSpeaker EOL Nominal 47kΩ 5% 1/3 WattTHD <0.5%Signal to Noise Ratio 90dBAmplifier Dimension(L x W x H) 83mm x 380mm x 88mm

OWS 500W Amplifier 6010-0006OWS Indicator & Controls 6010-0003

www.ampac.net www.ampac.net

Page 17: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

32 33Alarm Systems

Specifications

MechanicalMaterial 1.6mm Mild SteelFinish Powder Coated Arch WhiteDimensions 10U 700H x 625W x 240D mm (SECP only) 12U 900H x 650W x 290D mm 16U 1200H x 700W x 375D mm 29U 1800H x 700W x 375D mmApprovals SSL – AS2220.1Signals Compliant with AS1670.4:2004

ElectricalPower Supply 7.5, 13, 19.5 or 26 A mps @ 24 VDCCommunication RS485 @ 9600 bpsEWS Zones 144 maxEIS Zones 288 maxPaging Console 8 max (recommended)ECP’s 12 max (recommended)Visual Warning Option 1 EV3000 Visual Outputs Maximum of 8 pairs per visual circuit (for Xenon 208-0011). Not T3 compliantOption 2 EV3000 Visual Outputs Maximum of 40 pairs per visual circuit (for LED 208-0063). T3 compliant Note: The LED visual pairs require the Ampac 4210-0031 Visual Driver Kit

fitted

Item Numbers

EV3000 12U 1 AMP RACK + FIRST 105-0001EV3000 16U 1 AMP RACK + FIRST 105-0002 EV3000 29U 1 AMP RACK + FIRST 105-0003EV3000 29U DBL CABINET 1 AMP 105-0007EV3000 10U SECP C/W FIRST 8 105-0004EV3000 12U SECP C/W FIRST 8 105-0005EV3000 16U SECP C/W FIRST 8 105-0006EV3000 29U SECP C/W FIRST 8 105-0009

Product Overview

The Ampac EV3000 Occupant Warning and Intercom System is designed for the purpose of enabling the orderly evacuation of occupants, from a building or structure, in the event of an emergency.

The system comprises of two (2) sub-systems. The first being the Occupant Warning System (OWS) and the other the Occupant Intercom System (OIS). While the Warning and Intercom System have separate controls, they coexist in a Apanel that is logically presented and aesthetically pleasing.

The Occupant Warning System makes use of speakers strategically placed around the site, to broadcast ALERT, and/or EVACUATION signals or public address announcements. The OWS may be automatically initiated or manually operated. When not used in an emergency situation, the EV3000 can broadcast background music and/or general paging announcements.

The Occupant Intercom System (OIS) consists of front panel control at the Emergency Control Panel (ECP) and Warden Intercom Phones (WIP) that are strategically placed throughout the building. Communication is only possible between the WIP and ECP.

For larger sites, multiple control panels may be networked. ABS (BX1) and Metal (BX10) cabinet versions.

• Network System • Modular System Design. • Discrete Front Panel Controls. • 40, 120, 240 & 480 Watts Amplifiers to suit your need. • Visual Output for Hearing Impaired or Noisy Environments. • Common or Individual Fire Alarm Inputs. • Common or Zoned Background Music Inputs. • Monitoring of Speaker Circuits. • Monitoring of Visual Warning Indicators. • Automatic Volume Control incorporating Ambient Noise Sensing Microphone. • Stand-by Signal Generators. • Digital Paging Console

EV3000 Emergency Control Panel

www.ampac.net www.ampac.net

Page 18: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

34 35Alarm Systems

40 Watt Power Amplifier

• A modular power amplifier that is rated at 40 watts • Multi-channel audio input supports Alert tone, Evacuation tone, Public Address, and

background music • Continuous monitoring of amplifier and 100 volt speaker circuit • Overload protection with Automatic • Easily plugs into an Ampac EV3000 amplifier frame • Can fit up to 8 amplifiers per frame

Voltage 24 VDCQuiescent current 58mAMax current 3400mAMax output power 40 WattsOutput voltage 100 VAC RMSFreq. Response 150Hz to 12kHz (±1dB)Distortion Max 1% at full load (typical 0.5%)Sensitivity +5dB <200Kohm balanced) (1.4VRMS)Overload 100 VRMS + 10%Weight 675 grams

120 Watt Power Amplifier

• A modular power amplifier that is rated at 120 watts • Multi-channel audio input supports Alert tone, Evacuation tone, Public Address, and

background music • Continuous monitoring of amplifier and 100 volt speaker circuit • Overload protection with Automatic • Easily plugs into an Ampac EV3000 amplifier frame • Can fit up to 4 amplifiers per frame

Voltage 24 VDCQuiescent current 175mAMax current 8100mAMax output power 120 WattsOutput voltage 100 VAC RMSFreq. Response 210Hz to 14.5kHz (±1dB)Distortion < 0.2% at full loadSignal to Noise 77 dBOverload 100 VRMS + 10%Weight 1160 grams

40 Watt Power Amplifier 154-0075

120 Watt Power Amplifier 154-0077

EV3000 Emergency Control Panel - Add Ons240 Watt Power Amplifier

• 24v DC supply • Mother board address strapping (120 address positions) • Continuous fault monitoring • Volume override output • Test tone input • Data selectable 4 channel input (balanced) • Tone generator synchronisation input • Indication (power on - green, power shutdown - yellow, amp or line fault - red,

overload - red) • Minimum cable size 2.5mm²

Voltage 24 VDCQuiescent current 350mAMax current 16200mAMax output power 240 WattsOutput voltage 100 VAC RMSFreq. Response 210Hz to 14.5kHz (±1dB)Distortion < 0.2% at full loadSignal to Noise 77 dBOverload 100 VRMS + 10%Weight 2320 grams

240 Watt Power Amplifier 154-0001

480 Watt Power Amplifier

• 24v DC supply • Mother board address strapping (120 address positions) • Continuous fault monitoring • Volume override output • Test tone input • Data selectable 4 channel input (balanced) • Tone generator • Indication (power on - green, power shutdown - yellow, amp or line fault - red, over-

load - red) • Minimum cable size 4mm²

Voltage 24 VDCQuiescent current 700mAMax current 32400mAMax output power 480 WattsOutput voltage 100 VAC RMSFreq. Response 210Hz to 14.5kHz (±1dB)Distortion < 0.2% at full loadSignal to Noise 77 dBOverload 100 VRMS + 10%Weight 4640 grams

480 Watt Power Amplifier 154-0002

www.ampac.net www.ampac.net

Page 19: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

36 37Alarm Systems

Warden Intercom Phone- 2 Wire (S0004)

• 2 Wire WIP/EAID wiring • High quality WIP audio • Complies with AS4428.4 • Suitable for models manufactured after July 2010

Operating Voltage 27 VDC (line driven)Line Voltage On hook - 25 VDC max Off hook - 14 VDC maxCurrent draw On hook - 5 mA max Off hook - 35 mA maxLine Impedance 360 ohm balancedLine Level 0 dB (± 3dB)Cabling 2 wire - 2.5mm² max.Dimensions 215H x 85W x 62D mmWeight 380 grams

Warden Intercom Phone – 2 Wire (S0004) 219-0015WIP Enclosure Metal Surface Mounted 291-0054

Warden Intercom Phone - 3 Wire

• The WIP is installed remote to the ECP • Provides intercommunication between users at the WIP and Emergency Control Panel • This feature is only available when the Emergency Warning Intercom facility has been

incorporated in the control panel • Made of high impact red ABS plastic • Compatible with most EV3000 systems manufactured before July 2010

Operating Voltage 27 VDC (line driven)Line Voltage On hook - 25 VDC max Off hook - 14 VDC maxCurrent draw On hook - 5 mA max Off hook - 35 mA maxLine Impedance 360 ohm balancedLine Level 0 dB (± 3dB)Cabling 3 wire - 2.5mm² max.Dimensions 215H x 85W x 62D mmWeight 380 grams

Warden Intercom Phone – 3 Wire 219-0007WIP Enclosure Metal Surface Mounted 291-0054

Emergency Alarm Intiating Device (EAID)

• Connects to S004 WIP • 2 wires for WIP & EAID • Compatible with 219-0015

Emergency Alarm Initiating Device (EAID) 213-0068

EV3000 Emergency Control Panel - Add OnsRemote Paging Console

• Provides a point to initiate a non-emergency voice announcement via the EV3000 • Provides a pre-announcement tone • Easy keypad operation to broadcast voice announcements to selected zones, or group

of zones • Connects to EV3000 via RS485 • Derives power from the EV3000 panel

Size 80H x 300W x 220D mmSupply voltage 12 VDCCurrent 400 mACommunication RS 485Weight 1160 grams

Remote Paging Console 154-0005

Fibre Optic Network Interface for EV3000

The fibre modem network interface kit offers the user a method of interconnecting two (2) or more EV3000 Emergency Warning and Intercom System (EWIS) using fibre optic cable as an alternative to copper. The modems convert hardwired data and audio, to a common fibre optic

compatible output.

The fibre optic modems are full duplex and have 4-channels to carry both data and two (2) audio signals. Two (2) channels are required – emergency public address and warden intercom audio signals.

Fibre Optic Network Interface for EV3000 154-0074EV3000 2 Core Single Mode Fibre Network Interface 154-0271EV300 Single Core Multi Mode Fibre Network Interface 154-0272 EV300 Single Core Singe Mode Fibre Network Interface 154-0273

www.ampac.net www.ampac.net

Page 20: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

38 39Graphics Package

SmartGraphics HD License Kit 4100-0002SmartGraphics HD PC System Complete 4100-0003SmartGraphics HD Touch PC System Complete 4100-0004USB-RS232 Converter Kit 4100-0006USB-RS485/422 Converter Kit 4100-0007SmartGraphics 19” Rack PC with Touch Screen 4100-0009

Item Numbers

Product Overview

AMPAC’s SmartGraphicsHD System unleashes the full power of FireFinder (fire detection) and the EV3000 (alarm and intercom) by creating a robust and versatile hub for controlling your fire detection, alarm and intercom systems with one fully integrated package. Flexible and intuitive in its design, SmartGraphicsHD puts the command of your systems at your fingertips.

• Interfaces to the FireFinder fire detection panel and the EV3000 emergency warning and intercom system • Clearly shows on the building floor plan the start and spread of the fire and the status of the emergency warning • and intercom system • Has capabilities of e-mailing maps to emergency service organisations and key stakeholders • Supports the latest 1920x1080 HD computer technology • Able to operate over existing IT infrastructure • Can be expanded to incorporate multi-site facilities into one central monitoring package • Historic data log on the activity of the fire detection system and alarm system • Three level password protection • Detailed Egress Pathways • Building Information (like hazardous materials) and mustering point displayed on maps

Smart GraphicsHD

Disable and Control

Access Map

Main Screen

History Page

Fire Status Indication

www.ampac.net www.ampac.net

Page 21: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

40 41Detection & MCP’s

Product Overview

Series 65 incorporates well-proven sensing technologies together with advances in materials and electronics. Developed from the highly successful Series 60 range of detectors, Series 65 includes a chip (integrated circuit) based on that used in XP95 analogue addressable detectors. The range consists of ionisation, integrating ionisation and optical smoke detectors, four grades of heat detector and a range of bases.

• Wide operating voltage • Advanced electronic technology • Flashing LED option • Magnetic test switch option • Can be used on security systems • Electrically and mechanically compatible with Series 60 • Proven detection performance

Optical Ionisation Integrating Ion Heat

Operating voltage 9 to 33 V dc

Quiescent current 50μA at 24 V dc

Alarm current 52mA at 24 V dc

Operating temp (no icing) -20°C to +60°C -20°C to +90°C

Relative humidity 0 to 95% (non condensing)

Diameter 100mm

Height 50mm

Weight inc base 150 grams 15 grams 153 grams 131 grams

IP Rating IP23D (EN60529)

Approvals AS240-7 AS240-5

Series 65 Detection

Series 65 Ionisation Smoke Detector

The Series 65 Ionisation Smoke Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.

• Responds well to fast-burning, flaming fires • Designed to operate in a variety of environments

Series 65 Ionisation Smoke Detector 4106-1002

Series 65 Integrating Ionisation Smoke Detector

Ionisation Detectors use a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. Circuitry in the Ionisation Smoke Detector protects against transient levels of smoke above the normal threshold for up to 20 seconds.

• Responds well to fast-burning, flaming fires • Designed to operate in environments where transient levels of smoke may be

expected

Series 65 Integrating Ionisation Smoke Detector 4106-1003

Series 65 Optical Smoke Detector

The Series 65 Optical Smoke Detector incorporates a pulsing LED located within the housing of the detector. The external detector moulding is identical to that of the ionisation detector but has an indicator LED which is clear in quiescent state but produces red light in alarm.

• Responds well to slow-burning, smouldering fires • Well suited for bedrooms and escape routes • Unaffected by wind or atmospheric pressure

Series 65 Optical Smoke Detector 4106-1001

Series 65 Heat Detector

The Series 65 Heat Detector monitors temperature by using a dual thermistor network which provides a voltage output proportional to the external air temperature. There are four classes of heat detectors in the Series 65 range designed to suit a wide variety of operating conditions.

• Can be used for applications where smoke detectors are unsuitable • Ideal in environments that are dirty or smoky under normal conditions

Series 65 A1R Standard Rate-of-Rise – MAT 50°C, MSRT 65°C 4106-1004Series 65 BR Standard Rate-of-Rise – MAT 65°C, MSRT 85°C 4106-1005Series 65 CR Standard Rate-of-Rise – MAT 80°C, MSRT 100°C 4106-1006 Series 65 CS Standard Static – MAT 80°C, MSRT 100°C 4106-1007

Series 65 Standard Base

The Series 65 Standard Base has been designed to enable detectors to be fitted without the need for force – particularly useful when fitting to suspended ceilings. All Series 65 bases have a one way fit and can be locked into place by a grub screw using a 1.5mm hexagonal screwdriver.

• Detector locking mechanism • One way fit • Easy to wire • Contains an earth connector • Contains no electrical parts

Series 65 Standard Base 4106-1008

www.ampac.net www.ampac.net

Page 22: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

42 43Detection & MCP’s

Type E Heat Detector Dual Thread 223-0002 Type E Heat Detector Single Thread 223-0003

Type E Detector Type E Detector

The Type E Heat Detector is a thermal sensitive switch. It is a fixed temperature device with a factory pre-set temperature in the range 60 °C to 240 °C. The detectorcomprises a pair of normally open electrical contacts mounted within a stainless steel Probe

• Resetting Type Heat Detector • Rate Compensation & Fast Response • Wide Temperature Range • Gold Plated Electrical Contacts • Corrosion & Shock Resistant

Contacts Normally open, close on temp set-pointOperating Current 0.25 A maxApplied Voltage DC at 0.25A 32 V maxOperating Temp Set-point +60°C to +240°CAmbient Temp Range -40°C to +180°CIP rating IP67Weight 140 gramsSensitivity & Accuracy +/- 5% or degreesApprovals AS1603-1 (CSIRO)

Thermal Type B Sealed Cool Room Detector (Hoc)

The conventional Type B Cool Room Heat Detector is a 60°C fixed temperature waterproof detector. The detector uses a bi-metallic strip to sense temperature change,therefore consuming minimal standby current and providing high reliability.

• Waterproof Design – rated to IP67 • No Mounting Base Required • Low Current Consumption • CSIRO Approved to AS1603.1

Operating Voltage 15 to 30 V dc (Nominal 24 V dc)Max Alarm Current 50 mA at 24 V dcRemote LED Current 4mA at 5VDimensions 98 mm Dia x 45 mm HOperating temperature -10°C to +40°CColour IvoryIP rating IP67Weight 80 gramsApprovals AS1603-1

Type B Cool Room Heat Detector 202-0023

Heat Detection

Product Overview

Orbis is a range of conventional detectors which has been developed with sophisticated technology previously only found in intelligent detectors. Orbis is a range with modern styling and incorporates a mounting base wihich saves installation time.

• Automatic drift compensation with DirtAlert® warning • Patented FasTest® which reduces the time taken to test detectors • SensAlert® uses a flashing LED to indicate that the sensor is not operating correctly • StartUpTM for fast commissioning • Attractive and compact design • Electrically compatible with Series 60 and Series 65 • Wide voltage and operating temperature ranges • Algorithms for transient rejection • Flashing LED option • 360° visibility of LEDs • Insect resistant

Optical Multisensor Heat

Operating voltage 8.5 to 33 V dc

Quiescent current 95μA at 24 V dc

Alarm current 40mA at 24 V dc

Operating temp -40°C to +70°C (no icing)

Relative humidity 0 to 98% (non condensing)

Diameter 97mm

Height inc base 46mm 57mm 51mm

Weight inc base 135 grams 140 grams 130 grams

IP Rating IP23D (EN60529)

Approvals AS7240-7 AS7240-5

Orbis Detection

www.ampac.net www.ampac.net

Page 23: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

44 45Detection & MCP’s

Orbis Multisensor Detector 4106-1052

Multisensor Smoke Detector

The Orbis Multisensor Detector benefits from the same false alarm reduction technology as the optical detector. It is a thermally enhanced smoke detector and so will not give an alarm from heat alone.

• Responds well to slow-burning, smouldering fires • Performs well in black and white smoke • Extra confirmation of smoke before alarm signal is given • Reduced incidence of false alarms • Sensing chamber keeps out dust and other airborne contaminants • Operates over a broad range of voltages at extremes of temperature

Heat Detector

The Orbis Heat Detector monitors temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature. There are seven classes of heat detectors in the Orbis range designed to suit a wide variety of operating conditions.

• Can be used for applications where smoke detectors are unsuitable • Ideal in environments that are dirty or smoky under normal conditions • Reduced incidence of false alarms • Increased reliability of detection

Orbis A1R (50°C) Heat Detector Rate of Rise 4106-1053Orbis A2S (50°C) Heat Detector (Type B) Static 4106-1054Orbis BR (65°C) Heat Detector (Type A) Rate of Rise 4106-1055Orbis BS (65°C) Heat Detector Static 4106-1056Orbis CR (80°C) Heat Detector (Type C) Rate of Rise 4106-1057Orbis CS (80°C) Heat Detector (Type D) Static 4106-1058

Orbis Optical Smoke Detector 4106-1051

Optical Smoke Detector

The Orbis Optical Smoke Detector works using the well established light scatter principle, however, the sensing technology is radically different in design from previous optical detectors and significantly reduces false alarms.

• Responds well to slow-burning, smouldering fires • Performs well in black and white smoke • Extra confirmation of smoke before alarm signal is given • Reduced incidence of false alarms • Sensing chamber keeps out dust and other airborne contaminants • Operates over a broad range of voltages at extremes of temperature

Orbis TimeSaver Relay Base

To support the Orbis detectors a range of bases are available. Each base has two slots for fixing screws at a spacing of 51mm to 69mm. The detectors fit into the base one way only and require minimal force in a clockwise rotation. The TimeSaver Relay base incorporates a single pole voltage-free changeover contact for switching external equipment. The relay is energised when the detector changes to alarm state and deactivates when the detector is reset. The relay is capable of switching up to 30V at 1A. The Orbis Adaptor base enables the detector to be fitted to a Series 60/65 base.

Orbis LX Base 201-0545Orbis TimeSaver Relay Base 201-0543Orbis Adaptor Base 201-0544

Manual Call Point – ACP-04

• Double terminal, wire protected connectors for independent input and output connections when looping to other devices • Protective film prevents glass from splintering when broken

Current Rating 3A @ 12/24 VDC 1.5A @ 48 VDCSize 88mm H x 88mm W x 59mm D (surface) 88mm H x 88mm W x 27mm D (flush)Switch Type Single pole microCable termination 6 x 2.5mm2 screwIn-Line Resistor 470Ω (N/O operation only)Material High impact ABSOperating Temperature -5°C to +70°CHumidity 0 – 95% non-condensingIP rating IP 24D (indoor use)Weight 153 grams

Manual Call Point – ACP-04 Red 213-0060Manual Call Point – ACP-04 Yellow 213-0061Manual Call Point – ACP-04 White 213-0062Manual Call Point – ACP-04 Green 213-0063Manual Call Point – ACP-04 Protective Cover 213-0057Manual Call Point – ACP-04 Glass 213-0058

Manual Call Point – Conventional Weatherproof

The Weatherproof Manual Call Point has been designed for use outdoors and in places where moisture may be present. The Manual Call Point provides a simple single pole changeover contact for use with older fire systems or in other applications requiring switching at up to mains voltage.

Contact rating 3A at 24 VDCSize 87mm H x 87mm W x 57mm DSwitch type Single PoleMaterial High Impact ABSTemperature range -25°C to +70°CIP rating IP65Weight 220g

IP65 MCP Reset n/c n/o con 213-0045

Manual Call Point - Conventional Waterproof

The Conventional Waterproof Manual Call Point has been designed to work on conventional systems. The Manual Call Point has an easilt resettalbe element rather than a break glass.

Supply Voltage 9-33VDCOperatin Temperature -30o to 70o

Humidity 0-95%(No condensation or icing)IP Rating 67Alarm Resistance 470-680 OhmsCurrent (Alarm LED On) 80mA

Conventional Waterproof MCP 4105-1002

Manual Call PointsOrbis Detection

www.ampac.net www.ampac.net

Page 24: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

46 47Detection & MCP’s

Sampling Duct Units

Orbis Duct Sampling Unit inc Detector Base 214-0052Duct Probe 300mm to 750mm 214-0060Duct Probe 750mm to 1500mm 214-0061Duct Probe 1500mm to 3000mm 214-0062

Product Overview

The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 me-ters per second. The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back into the air duct.

Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than 560mm, three other lengths of sampling pipe are available.

• Both sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier • The cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to

appear at the fire alarm control panel • Easily accessible wire clamping terminals ensure secure and fast termination • Clear cover hence the alarm LED on the detector is visible at all times • Integral smoke test port • Sampling pipes available in 4 lengths • Operates in air speeds of 0.5 m/s to 20 m/s • Volt free contacts

Item Numbers

Product Overview

The FIRERAY 5000 motorised reflective, auto aligning infrared optical beam smoke detector can be installed with up to two detector heads per system, thus saving on installation time and costs. In addition, each system controller houses two pairs of fire and fault relays, one per detector. This innovative system has been designed from the ground up to include pioneering technology that fully addresses the needs of the installer and user, both now and in the future.

• Allows for 2 Detectors per System Controller • Each Detector configurable from 8m to 100m • Separate Fire and Fault relays per Detector • Integral LASER alignment • Auto-Align Fast Automatic Beam Alignment • Building Movement and Contamination Compensation • Low Level System Controller • Logs the 50 most recent events per detector • Programmable Sensitivity and Fire Thresholds • 20mm Cable Gland Knockouts on System Controller • 2-wire interface from System Controller to Detector

Operating distance (separation) 8-100 metres

Cable length – system controller to detector 100 metres

Operating voltage (to system controller) 14VDC to 36VDC

Operating current with 1 detector 5 to 6 mA

Operating current with 2 detectors 7.5 to 8.5 mA

Operating temperature -10°C to +55°C (no icing)

Relative humidity 93% (non condensing)

IP rating IP54

Reflective Beam System 4109-1003Reflective Prism 220-0007Detector & Reflective Prism 220-0009Long Range Reflective Prism 220-0010Universal Bracket for Detector 220-0011Prism Plate (1) 220-0012Prism Plate (4) 220-0013Ceiling Pendant Mounting 220-0014Detector Protective Cage 220-0015

Beam Detection

Item Numbers

www.ampac.net www.ampac.net

Page 25: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

48 49Detection & MCP’s

Optical Ionisation Heat High Heat Multisensor

Operating voltage 17 to 28 V dc

Quiescent current at 24 V dc 340μA 280μA 250μA 500μA

Alarm current at 24 V dc 4mA 2mA 2mA 3.5mA

Operating temp (no icing) -20°C to +60°C -20°C to +70°C -20°C to +70°C -20°C to +120°C -20°C to +60°C

Relative humidity 0 to 95% (non condensing)

Diameter 100mm

Height 50mm 58mm

Weight inc base 157 grams 161 grams 161 grams 150 grams 160 grams

IP Rating IP23D (EN60529)

Approvals AS7240-5 -

Product Overview

The XP95 range of intelligent fire detectors is advanced in design, improved in performance and has unique features that benefit the installer and end user. The range features smoke detectors (ionisation and optical), standard and high temperature heat detectors and a multisensor. Beam detectors, flame detectors, manual call points, audio visual signalling devices, inter-face units and isolators complete the range. XP95 has a ‘central intelligence’ system where all the decisions are made by the control panel.

• Alarm Flag for fast alarm reporting • Alarm Address for fast location of alarm • XPERT card addressing • Electronics-free base • Easy installation • Elegant design • Insect Resistant

XP95 Detection®

XP95 Ionisation Smoke Detector

The XP95 Ionisation Smoke Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.

• Responds well to fast-burning, flaming fires • Designed to operate in a variety of environments • Minimal effects from temperature, humidity, atmospheric pressure • Well protected against electromagnetic interference over a wide frequency range

XP95 Ionisation Smoke Detector 4106-2002 XP95 Ionisation (Black) 4106-2011

XP95 Optical Smoke Detector

The XP95 Optical Smoke Detector works using the light scatter principle and is ideal for applications where slow-burning or smouldering fires are likely.

• Responds well to slow-burning, smouldering fires • Well suited for bedrooms and escape routes • Unaffected by wind or atmospheric pressure

XP95 Optical Smoke Detector 4106-2001XP95 Optical (Black) Smoke 4106-2010

XP95 Heat Detector

The XP95 Heat Detector monitors temperature by using a single thermistor network which provides a count output proportional to the external air temperature. The XP95 range features two Heat Detectors, standard and high temperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C. The high temperature detector, classified as a CS device, will report an alarm at 90°C.

• Ideal in environments that are dirty or smoky under normal conditions • Well suited for warehouses, loading bays and car parks • Unaffected by wind or atmospheric pressure

XP95 Heat Detector Standard – A2S 4106-2003 XP95 Heat A2S (Black) Detector 4106-2013

XP95 Multisensor Detector

The XP95 Multisensor Detector contains an optical smoke sensor and a thermistor temperature sensor whose outputs are combined to give the final analogue value.

• Sensitive to a wide range of fires • Well suited for environments such as hotel bedrooms • Unaffected by wind or atmospheric pressure

XP95 Multisensor Detector 4106-2004

www.ampac.net www.ampac.net

Page 26: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

50 51Detection & MCP’s

Product Overview

Discovery is a range of high-specification, intelligent fire detectors developed to meet the requirements of sophisticated systems while providing engineers with an additional dimension in fire protection capability. Discovery has a ‘distributed intelligence system’ where decisions are made in the detector head as well as at the control panel. Drift compensation is also incorporated into the detector, allowing it to adapt to dirty or dusty environments reducing false alarms.

• Rejection of transient signals • Flashing LED option • Five response modes for ease of optimisation to changing environments • Drift compensation to ensure constant sensitivity • Four bytes of non-volatile memory for user data • Alarm flag for fast alarm reporting • Conventional alarm facility during control panel processor fault • 360° visibility in alarm • Compatible with XP95 systems • Insect resistant

Optical Optical/Heat Multisensor

Ionisation CO/Heat Multisensor

Carbon Monoxide

Operating voltage 17 to 28 V dc

Quiescent current 24 V dc 300μA 400μA 300μA 400μA 300μA

Alarm current 24 V dc 3.5mA

Operating temp (no icing) -40°C to +70°C -30°C to +70°C -20°C to +55°C

Relative humidity 0 to 95% (non condensing)

Diameter 100mm

Height inc base 50mm 58mm 50mm 60mm 50mm

Weight inc base 160 grams

IP Rating IP44 (EN60529)

Approvals AS7240-7 AS7240-5 AS7240-7 - -

Discovery Detection

Discovery Ionisation Smoke Detector

The Discovery Ionisation Smoke Detector uses a low activity radioactive foil to irradiate the air in the smoke chamber causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.

• Responds well to fast-burning, flaming fires • Designed to operate in a variety of environments • Remote test feature

Discovery Ionisation Smoke Detector 4106-2006

Discovery Optical Smoke Detector

The Discovery Optical Smoke Detector works using the light scatter principle and is ideal for applications where slow-burning or smouldering fires are likely.

• Responds well to slow-burning, smouldering fires • Well suited for bedrooms and escape routes • Unaffected by wind or atmospheric pressure • Remote test feature

Discovery Optical Smoke Detector 4106-2005

Discovery Heat Detector

The Discovery Heat Detector, distinguishable by the low airflow resistant case, uses a single thermistor to sense the air temperature around the detector.

• Ideal in environments that are dirty or smokey under normal conditions • Well suited for warehouses, loading bays and car parks • Unaffected by wind or atmospheric pressure • Remote test feature

Discovery Heat Detector 4106-2007

Discovery Multisensor Detector

The Discovery Multisensor Detector comprises optical smoke and thermistor temperature sensors whose respective outputs can be split to deliver specific smoke or thermal actions respectively. This capability can aid early Alarm warning routines and other advanced detection techniques.

Discovery Multisensor Detector 4106-2008Discovery Multisensor (Black) 4106-2012

Discovery CO/Heat Multisensor Detector

The Discovery CO/Heat Multisensor Detector is good at detecting deepseated smouldering fires which give off a lot of CO as well as flaming fires. They are ideal for use in hotel bedrooms where steam may be present, dusty environments or even where simulated smoke may be present.

• Enhanced detection capability • Early response to hot fires • Ideal for smouldering fires • Less susceptible to false alarms caused by steam than smoke alarms • Five response modes

Discovery CO/Heat Multisensor Detector 4106-2009

www.ampac.net www.ampac.net

Page 27: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

52 53Detection & MCP’s

Discovery Carbon Monoxide Detector

The Discovery Carbon Monoxide (CO) Detector is good at detecting deep-seated fires. Please note that CO detectors do not detect smoke particles or heat and are not universal replacements for smoke detectors.

• Enhanced detection capability • Early response to hot fires • Ideal for smouldering fires • Less susceptible to false alarms caused by steam than smoke alarms • Five response modes

Discovery Carbon Monoxide Detector 201-0102

XP95/Discovery Isolating Base

The new style Isolating Base senses and detects short-circuit faults on XP95 loops and spurs.

• Up to 20 devices may be installed between isolating bases • High brightness LED

XP95/Discovery Isolating Base 201-0125

XP95/Discovery Intelligent Low Power Relay Base

The Low Power Relay Base incorporates a low power relay to control field equipment such as automatic door closers.

• Gives a set of voltage free contacts controlled by the remote output of a detector • Draws negligible current • Capable of switching up to 30V at 1A

XP95/Discovery Low Power Relay 201-0014

XP95/Discovery Intelligent Detector Base

All detectors in the XP95 range fit the Intelligent Detector Base. It is a low insertion force base with stainless steel contacts for the detector terminals.

• XPERT addressing • One way fit of detector • Locking feature to prevent unauthorised removal

XP95/Discovery Detector Base 201-0004XP95/Discovery Detector Base (Black) 201-0093

Discovery Detection

Waterproof Manual Call Point (New)

The Waterproof Addressable Manual Call Point has a highly visible alarm indicator which can be seen from up to 10 metres away. When activated, the manual call point interrupts the polling cycle for a fast response and has a combined LED indicator and front reset mechanism allowing for a quick and simple reset.

Voltage 17-28 VDCQuiescent current 100μAAlarm current 4mASize (surface mount) 110H x 110W x 74D mmOperating temperature -30°C to +70°C Relative humidity 0-95% RHIP rating IP67Weight 180 grams

Waterproof Manual Call Point 4105-2002 Transparent Cover 4105-2003Pack of 10 Reset Keys 4105-2004

Manual Call Points

Inetlligent Manual Call Point with Isolator 4105-2005Transparent Cover 4105-2003Pack of 10 Reset Keys 4105-2004

Intelligent Manual Call Point (New)

The Intelligent Manual Call Point has a highly visible alarm indicator which can be seen from up to 10 metres away. When activated, the manual call point interrupts the polling cycle for a fast response. A combined LED indicator and front reset mechanism allows for a quick and simple reset.

Voltage 17-28 VDCQuiescent current 100μAAlarm current 4mADimensions (surface mount) 87H x 87W x 54D mmOperating temperature -40°C to +70°C Humidity 0-95% RHIP rating 45Weight 180 grams

Addressable XP95 Manual Call Point

The XP95 Manual Call Point has been designed to operate on a loop of intelligent addressable fire detection devices. The address of each call point is set at the commissioning stage by means of a seven segment DIL switch. The device features plug and play terminal connections and a resettable element.

Voltage 17-28 VDCQuiescent current 100μA at 24VDCAlarm current 4mAAddress method 7 segment DIL switchSize (surface mount) 93mm H x 89mm W x 59.5mm DOperating temperature -20°C to +60°C (no icing)Relative humidity 0-95% (non condensing)IP rating IP24D (indoor use)Weight 160 grams

XP95 Manual Call Point (Surface) 213-0050XP95 Manual Call Point Protective Cover 213-0064Intelligent Waterproof Manual Call Point 213-0066

www.ampac.net www.ampac.net

Page 28: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

54 55Detection & MCP’s

Duct Sampling Unit inc XP95 Detector Base 214-0051 Duct Probe 300mm to 750mm 214-0060 Duct Probe 750mm to 1500mm 214-0061 Duct Probe 1500mm to 3000mm 214-0062

Product Overview

The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 me-ters per second. The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back into the air duct.

Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than 560mm, three other lengths of sampling pipe are available.

• Both sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier • The cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to

appear at the fire alarm control panel • Easily accessible wire clamping terminals ensure secure and fast termination • Clear cover hence the alarm LED on the detector is visible at all times • Integral smoke test port • Sampling pipes available in 4 lengths • Operates in air speeds of 0.5 m/s to 20 m/s • Volt free contacts

Duct Sampling Unit

Item Numbers

Product Overview

Flame detectors are effective in protecting areas where flaming fires may be expected. There is a choice of detection tech-niques - Ultra Violet and Infra-red, or a combination of both. UV Flame Detectors are generally used in engine rooms, factories and warehouse applications. Infra-red Flame Detectors are able to tolerate dirtier environments which may block UV radiation and are generally used in applications such as waste handling, colour printing and paper manufacturing.

• Detects a wide range of open fires • Insensitive to wind • Transient voltage protection • Three types of detector • Lockable security fitting • White finish

UV Base IR2 Base IR3 Base IR2 Flame IR3 Flame

Operating voltage 17-28 V DC

Quiescent current at 24 V dc 2.3mA 2.8mA 2.2mA 2.2mA 2.2mA

Field of view 90° cone 90° cone 90° cone 90° 90°

Operating temp (no icing) -40°C to +55°C -10°C to +55°C

Relative humidity 0 to 95% (non condensing)

Dimensions 100D x 48H mm 142W x 108H x 82D mm

Weight 210g 1 kg 2 kg

IP Rating IP66 IP65

Flame Detection

www.ampac.net www.ampac.net

Page 29: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

56 57Detection & MCP’s

Intelligent Base Mounted UV Flame Detector

The Intelligent Base Mounted UV Flame Detector is designed to protect internal areas where open fires may be expected. The detector has a single UV sensor with a narrow spectral response in order to discriminate between flames and most spurious sources of radiation.

• Responds to stationary flames with no flicker • Sensitive to UV radiation emitted by flames during combustion • Compact flame detector which can fit into Discovery or XP95 bases • Loop-powered • Increased reliability of detection

XP95 Base Mounted UV Flame Detector 201-0130

Intelligent Base Mounted UV IR² Flame Detector

The Intelligent Base Mounted UV IR² Flame Detector is designed to protect areas where open flaming fires may be expected. The detector has a UV and dual IR sensors responding to different wavelengths in order to discriminate between flames and spurious sources of radiation.

• Responds to stationary flames with no flicker • Sensitive to UV and low-frequency flickering IR radiation emitted by flames during

combustion • Compact flame detector which can fit into Discovery or XP95 bases • Loop-powered • False alarms due to electrical discharges from lightning or arc welding and flickering

sunlight are minimised

XP95 Base Mounted UV IR² Flame Detector 201-0131

Intelligent Base Mounted IR³ Flame Detector

The Intelligent Base Mounted IR³ Flame Detector is designed to protect areas where open flaming fires may be expected. The detector has three IR sensors that respond to different IR wavelengths in order to discriminate between flames and spurious sources of radiation.

• Responds to stationary flames with no flicker. • Sensitive to low-frequency flickering IR radiation emitted by flames during

combustion. • Compact flame detector which can fit into Discovery or XP95 bases. • Loop-powered. • False alarms due to factors such as flickering sunlight are avoided by a combination

of filters and signal processing techniques.

XP95 Flameproof IR³ Flame Detector 201-0132

Flame Detection

XP95 Triple IR3 Flame 201-0188

Intelligent Triple IR Flame Detector

The Intelligent Triple IR Flame Detector (IR³) is designed to protect areas where open flaming fires may be expected. It is sensitive to low frequency, flickering infra-red radiation emitted by flames during combustion.

Flame Detector Bracket

The Flame Detector Bracket is an optional accessory for the Intelligent Flame Detectors. It is a stainless steel mounting bracket adjustable in two axis. Not suitable for Base Mounted Flame Detectors.

Flame Detector Bracket 201-0189

Base Mounted Flame Detector Bracket

The Flame Detector Bracket is an optional accessory for the Intelligent Flame Detectors. It is a stainless steel mounting bracket adjustable in two axis.

Bracket for Base Mounted Flame Detectors 201-0186

Flame Detector Weather Shield

The Flame Detector Weather Shield protects the device from inclement conditions.

S/Steel Weather Shield for Standard Flame Detector 201-0190

Intelligent Dual IR Flame Detector

The Intelligent Dual Infra-Red (IR²) Flame Detector is designed for use in areas where flaming fires may be expected. The detector has two sensors which respond to different IR wavelengths to discriminate between flames and spurious sources of radiation. Applications include aircraft hangars, coal handling and paper manufacturing plants and woodworking environments.

XP95 Dual IR2 Flame Detector 201-0169

www.ampac.net www.ampac.net

Page 30: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

58 59Detection & MCP’s

Hazardous Area Detection

Product Overview

Ampac offers a range of Intrinsically Safe detectors in both conventional and addressable. Orbis IS ia a range with modern styling and is electronically compatible with Apollo Series 60 intrinsically safe conventional detectors. XP95 Intrinsically Safe range is a development of the well established intelligent XP95 range from Apollo specifically for use in hazardous areas and are set by means of the patented XPERT card.

Optical Ionisation Heat

Operating voltage 14 to 22 V dc

Quiescent current 24 V dc 340μA 300μA 300μA

Operating temp range 20°C to +60°C (no icing)

Relative humidity 0 to 95% (non condensing)

Dimensions inc base 100Dia x 50H mm

Weight inc base 157 grams 161 grams 161 grams

IP Rating IP23D (EN60529)

Category II IG Ex ia IIC T5 -20°C≤Ta≤45°C (T4≤60°C) Ga

Certificate IECEx BAS 12.0091X, BAS02ATEX 1289

TM

®

Orbis I.S. Heat Detector

The Orbis IS Heat Detector monitors temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature. There are seven classes of heat detectors in the Orbis IS range designed to suit a wide variety of operating conditions.

• Can be used for applications where smoke detectors are unsuitable • Ideal in environments that are dirty or smoky under normal conditions • Reduced incidences of false alarms • Increased reliability of detection

Orbis I.S. A1R Heat Detector- Rate of Rise 201-0134Orbis I.S. A1S Heat Detector- Static 201-0135Orbis I.S. A2S Heat Detector- Static 201-0601Orbis I.S. BR Heat Detector- Rate of Rise 201-0600Orbis I.S. BS Heat Detector- Static 201-0607Orbis I.S. CR Heat Detector- Rate of Rise 201-0602Orbis I.S. CS Heat Detector- Static 201-0603

Orbis I.S. Optical Smoke Detector

The Orbis I.S. Optical Smoke Detector works using the light scatter principle, and is ideal for applications where slow burning or smouldering fires are likely.

• Reduces false alarms • Recommended for early warning of fire in most areas • Improved sensitivity to black smoke • Compensation for slow changes in sensitivity • Algorithms for reliability of alarm

Orbis I.S. Optical Smoke Detector 201-0604

Orbis I.S. Multisensor Detector

The Orbis I.S. Multisensor Detector benefits from the same false alarm reduction technology as the optical detector. It is a thermally enhanced smoke detector and so will not give an alarm from heat alone.

• Reduces false alarms • Sensitive to fast burning, flaming fires • Improved sensitivity to black smoke • Compensation for slow changes in sensitivity • Algorithms for reliability of alarm

Orbis I.S. Multisensor Detector 201-0605

Orbis I.S. TimeSaver Base

The Orbis IS TimeSaver Base is a completely new design that provides installers with an open working area with fixing holes shaped to allow a simple mounting procedure.

• Grouped terminals to make wiring easy • Two fixing centres • LED alignment mark • Detector locking mechanism

Orbis I.S. TimeSaver Base 201-0606

www.ampac.net www.ampac.net

Page 31: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

60 61Detection & MCP’s

XP95 I.S. Ionisation Smoke Detector

The XP95 I.S. Ionisation Smoke Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.

• Detects super heating and flaming combustibles • Dual chamber technology • Wind resistant smoke inlets. • Transient voltage protection • Fine gauze insect protection • Lockable security fitting • Must be connected to a suitable safety barrier and protocol translator

XP95 I.S. Ionisation Smoke Detector 201-0103

XP95 I.S. Optical Smoke Detector

The XP95 I.S. Optical Smoke Detector works using the light scatter principle and is ideal for applications where slow-burning or smouldering fires are likely.

• Detects a wide range of fires • Insensitive to wind • Transient voltage protection • Fine gauze insect protection • Simple construction allows detection chamber to be cleaned • Lockable security fitting • Must be connected to a suitable safety barrier and protocol translator

XP95 I.S. Optical Smoke Detector 201-0104

XP95 I.S. Heat Detector

The XP95 I.S. Heat Detector operates by measuring heat levels with a single thermistor network which gives a count output proportional to the external air temperature.

• Rate of rise and fixed temperature alarm point • Single thermistor technology • Transient voltage protection • Resettable operation • Lockable security fitting • Must be connected to a suitable safety barrier and protocol translator

XP95 I.S. Heat Detector 201-0105

XP95 I.S. Mounting Base 201-0106

XP95 I.S. Mounting Base

The XP95 I.S. Mounting Base has been designed to accept only IS products. This ensures that standard detectors cannot inadvertently be fitted into an intrinsically safe system. XPERT cards are supplied with all bases.

• Wide cable entry • Contains no electronic parts • ‘One way only’ fit • Low insertion force • Large terminations • Lockable security fitting • White finish. • Must be connected to a suitable safety barrier and protocol translator

Orbis I.S. Galvanic Barrier Singel Channel 201-1061Orbis I.S. Galvanic Barrier Dual Channel 201-0198

Conventional Galvanic Barrier

The Conventional Galvanic Barrier is installed in the safe area and ensures system integrity

Conventional Intrinsically Safe Call Points

The range of conventional manual call points include break glass, push button and tool reset versions which are approved for Zone 0, 1, 2, 21 and 22 requiring intrinsically safe equipment for the control of fire and gas alarm systems

Supply Voltage 24V DC (28 max)Dimensions 98mm H x 95mm W x 76mm DMaterial Marine grade copper free LM6 AluminiumIP Rating IP66Approvals ATEX, IECEx, Inmetro, GOST-R

IS Break Glass Call Point, Red 4105-3007IS Push Button Call Point, Red 4105-3008IS Tool Reset Call Point, Red 4105-3009I.S. Break Glass Call Point 4105-3010I.S. Push Button Call Point 4105-3011I.S. Tool Reset Call Point 4105-3012

Conventional Indoor I.S. MCP Red (470 ohm)

The conventional IS manuall call point has been designed to aperate on contenctional instrinsically safe fire detection systems. designed specifically for use in atmospheres which explosivemixures are or may be present.

Supply Voltage 30V DCDimensions 93mm H x 89mm W x 59.5mm DMaterial ABS

Conventional Indoor I.S. MCP Red (470 ohm) 4105-3014

Hazardous Area Detection

www.ampac.net www.ampac.net

Page 32: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

62 63Detection & MCP’s

XP95 Intrinsically Safe Manual Call Point 201-0107

IP65 I.S. Manual Call Points

The XP95 IS Manual Call Point is based on the standard weatherproof model. It features an ‘interrupt’ facility to provide fast response to an alarm.

Voltage 14 to 22 VDCQuiescent current 300uAAlarm current 2mA (alarm LED On)Size 124mm H x 124mm W x 60mm DOperating temperature –20°C to +40°C (T5)–20°C to +60°C (T4)Humidity 0 to 95%IP rating IP67Weight 400 gramsClassification E Ex ia IIc T5Approvals EN54-11

XP95 I.S. Protocol Translator and Galvanic Barrier

The Protocol Translator and Galvanic Barrier are installed in the safe area ensuring integrity of communication between control equipment and field devices and safety within the limits of BASEEFA approvals

• Enables IS detectors to be connected to a standard loop driver • Loop powered • DIN-Rail mounting • Maximum of 20 XP95 IS devices per channel • Translators must be connected to detectors via a suitable safety barrier

XP95 Protocol Translator Single Channel 201-0108XP95 Protocol Translator Dual Channel 201-0155XP95 I.S. Galvanic Barrier 201-0109

DIN-Rail Interface Enclosures

DIN-Rail Interface Enclosures are available and can be used for housing intrinsically safe (IS) barriers or DIN-Rail mounted interfaces. A multi-purpose label that features a section for use with IS systems is supplied. For non-IS systems, the part referring to IS can simply be removed.

XP95 IS DIN Rail Interface Enclosure (4 units) 201-0142I.S. DIN Rail Interface (10 Units) 201-0153

Intelligent Flameproof Triple IR Flame Detector

The Intelligent Triple IR Flame Detector (IR³) is designed to protect areas where open flaming fires may be expected. It is sensitive to low frequency, flickering infra-red radiation emitted by flames during combustion.

• Loop-powered • Sensitive to flickering IR radiation • Detects through films of oil, dust, water and ice • Responds to flickering flames, including those invisible to the naked eye • False alarms due to lighting or flickering sunlight are minimised • Compatible with Discovery and XP95 protocols

XP95 Flameproof IR³ Flame Detector 201-0187

Intelligent Flameproof Dual IR Flame Detector

The Intelligent Dual Infra-Red (IR²) Flame Detector is designed for use in areas where flaming fires may be expected. The detector has two sensors which respond to different IR wavelengths to discriminate between flames and spurious sources of radiation. Applications include aircraft hangars, coal handling and paper manufacturing plants and woodworking environments.

• Sensitive to flickering IR radiation • Detects through films of oil, dust, water and ice • Responds to flickering flames, including those invisible to the naked eye • Compatible with Discovery and XP95 protocols • Remote optical self-test function • 90° field of view • Up to 40m coverage

XP95 Flameproof IR² Flame Detector 201-0191

Conventional BEx Flameproof Call Points

The range of conventional manual call points include break glass, push button and tool reset versions which are approved for Zone 1, 2, 21 and 22 hazardous areas for the control of fire and gas alarm systems.

Supply Voltage 24V DC (28 max)Dimensions 98mm H x 95mm W x 76mm DMaterial Marine grade copper free LM6 AluminiumColour Red (RAL3000)Operating Temperature Ta = -40°C to +50°CIP Rating IP66Weight 800gApprovals ATEX, IECEx, GOST-R

BEx Break Glass Call Point, Red, 470R Fire, 3K3 EOL 4105-3001BEx Push Button Call Point, Red, 470R Fire, 3K3 EOL 4105-3002BEx Tool Reset Call Point, Red ,470R Fire, 3K3 EOL 4105-3003BEx Break Glass Call Point, Red, 470R Fire 4105-3004BEx Push Button Call Point, Red, 470R Fire 4105-3005BEx Tool Reset Call Point, Red, 470R Fire 4105-3006BEx Push Button Call Point, Yellow, 470R Fire, 3K3 EOL 4105-3013

Hazardous Area Detection

www.ampac.net www.ampac.net

Page 33: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

64 65Audio Visual & Interafaces64 65Detection & MCP’s

Orbis Marine Optical Smoke Detector 201-0654

Orbis Marine Optical Smoke Detector

The Orbis Marine Optical Smoke Detector works on the well established light scatter principle. However, the sensing technology is radically different in design from previous optical detectors and significantly reduces false alarms.

Orbis Marine Multisensor Detector

The Orbis Marine Multisensor Detector benefits from the same false alarm reduction technology as the optical detector. It is a thermally enhanced smoke detector and so will not give an alarm from heat alone.

Orbis Marine Multisensor Detector 201-0655

Orbis Marine Heat Detector

The Orbis Marine Heat Detector uses a single thermistor to sense the air temperature around the detector. There are six classes of heat detectors in the Orbis Marine range designed to suit a wide variety of operating conditions.

Orbis Marine A1R Heat Detector- Rate of Rise 201-0162Orbis Marine A2S Heat Detector- Static 201-0651Orbis Marine BR Heat Detector- Rate of Rise 201-0650Orbis Marine BS Heat Detector- Static 201-0657Orbis Marine CR Heat Detector- Rate of Rise 201-0652Orbis Marine CS Heat Detector- Static 201-0653

Orbis Marine TimeSaver Base

The Orbis Marine TimeSaver Base is a completely new design that provides installers with an open working area with fixing holes shaped to allow a simple mounting procedure.

Orbis Marine TimeSaver Base 201-0656

Marine DetectionTM

www.ampac.netwww.ampac.net

Page 34: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

66 67Detection & MCP’s

XPander Optical Smoke Detector and Mounting Base

The Xpander Optical Smoke Detector works on the light scatter principle and is ideal for applications where slow-burning or smouldering fires are likely.

Voltage 3VDCSize inc base 100mm D x 75mm HOperating temperature -10°C to +50°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP23DWeight inc base 500 grams

XPander Optical Smoke Detector and Mounting Base 4106-5303

XPander Heat Detector and Mounting Base

There are two heat detectors in the Xpander range designed to suit a wide variety of operating conditions. A static heat detector (CS) which responds only when a fixed temperature has been reached and a rate-of-rise detector (A1R) which has a fixed upper limit, but in addition, measures the rate of increase in temperature

Voltage (regulated from radio base) 3VDCSize inc base 105mm D x 80mm HOperating temperature -10°C to +50°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP23DWeight inc base 400 grams

XPander A1R Heat Detector and Mounting Base 4106-5301XPander CS Heat Detector and Mounting Base 4106-5302

Xpander Combined Sounder & Detector

The Xpander Combined Sounder and Detector is wireless and designed to proved one point notification and detection.

• Wireless • Avaliable with a choice of Xpander detectors • Bi-directional (monitored) radio platform • A choice of 4 Tones including Temporal T3

XPander Sounder Heat A1R Combined Detector & Base 4111-1301XPander Sounder Heat CS Combined Detector & Base 4111-1302XPander Sounder Optical Combined Detector & Base 4111-1303

Xpander Combined Sounder Visual Indicator and Detector

The Xpander Combined Sounder Visual Indicator and Detector is wireless and designed to privide a one point notification and detection.

• Wireless • Avaliable with a choice of Xpander detectors • Bi-directional (monitored) radio platform • A choice of 4 tone including Temporal T3

XPander Sndr VI Red Heat A1R Combined Detector & Base 4111-1401XPander Sndr VI Red Heat CS Combined Detector & Base 4111-1402XPander Sndr VI Red Optical Combined Detector & Base 4111-1403XPander Sndr VI Clear Heat A1R Combined Detector & Base 4111-1501XPander Sndr VI Clear Heat CS Combined Detector & Base 4111-1502XPander Sndr VI Clear Optical Combined Detector & Base 4111-1503

Product Overview

Traditionally, fire detection systems in industrial and commercial applications have used hard wired installations. These systems are generally installed at the time of construction or refurbishment, making the laying of cables not a great issue. However, certain applications do not lend themselves to this approach, such as occupied buildings, heritage sites, architectur-ally sensitive buildings and annexes. This is where wireless systems provide the ideal solution.

Xpander is a system in which individual detectors, call points and alarm devices communicate with the XP95 loop by radio signals.

• Easy to install. • XPERT card addressing. • Self-monitoring. • Proven technology. • 915MHz radio channels. • Up to 31 devices per interface. • Up to 5 interfaces per loop (max devices per loop 126 inc interface) • All detectors within the Xpander range are supplied complete with mounting bases.

Xpander Wireless Detection

www.ampac.net www.ampac.net

Page 35: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

68 69Detection & MCP’s

Site Survey Kit

The Xpander Survey Tool is used at the site survey stage to ascertain if a site is suitable for an Xpander installation. A site survey must be carried out before Xpander can be installed.

• Indicates the suitability of proposed device location. • Tests for radio signal strength.

XPander Site Survey Kit 4112-1001Power Supply for Site Survey Kit (4112-1001) 4112-1002

Xpander Input/Output Unit

The Xpander Input/Output Unit is a radio based interface and offers two monitored input circuts and two relay outputs. It can be used for controlling fire doors, fire dampers, smoke vents and other fire engineering applications.

Supply Voltage 3VDC +Relay Rating 2A at 30VDCMaterial ABS grey plasticDimensions 120mm W x 240mmH x 60mm DOperating Temperature -10°C to +55°CHumidity 0% to 95% relative humidity (no condensation)IP rating 65

XPander Input/Output Unit 4110-2002XPander Dual Input/Output Unit 4110-2003

Xpander Wireless DetectionXPander Sounder Red and Red Mounting Base

The Xpander Sounder and Sounder Base is wireless and designed to be used with Xpander detectors and manual call points.

Voltage 3VDCAlarm tones (selectable) includes Temporal T3IP rating IP21CSound output 100dB(A)

XPander Sounder Red and Red Mounting Base 4107-8301XPander Sounder White and White Mounting Base 4107-8302

Xpander Manual Call Point

The Xpander Manual Call Point is compliant with AS7240-11 and is powered by two independent packs of three AA alkaline batteries with a typical five year life.

Voltage Regulated 3V from radio circuitingSize inc base 105mm D x 80mm HOperating temperature -10°C to +50°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP23DWeight inc base 500 grams

XPander Manual Call Point 4105-5001Transparent Hinged Cover for Manual Call Point 213-0064

XPander Sounder Beacon

The Xpander Sounder Beacon and Sounder Base is wireless and designed to be used with Xpander detectors and manual call points.

Voltage 3VDCAlarm tones (selectable) includes Temporal T3IP rating IP21CSound output 100dB(A)

XPander Sounder Beacon Red and Red Mounting Base 4107-8303XPander Sounder Beacon Amber and White Mounting Base 4107-8304XPander Sounder Beacon Clear and White Mounting Base 4107-8305

Xpander Diversity Loop Interface Unit

The Xpander Diversity Loop Interface Unit is connected to the detection loop and provides bi-directional communications from the LoopSense and FireFinder control panels to the wireless devices.

Voltage 24VDC + voltage pulsesOperating Current 15mAMechanical Isolation Isolator included as standardMaterial ABSDimension 270mmW x 205mmH x 85mmDOperating temperature -10°C to +55°CHumidity 0% to 95% relative humidity (no condensation)

XPander Diversity Interface Module with Isolator 4110-2001

Xpander Hub & Cluster

The Xpander Hub and Cluster System comprises of Radio Hub capable of receiving information from a maximum of 31 Radio Cluster Communicators (RCCs). The RCCs are each capable of receiving information from up to 31 wireless detection and alarm devices from the Xpander range.

Operating Temperature -10°C to 50°C (ambient)Humidity Up to 95% non-condensingOperating Voltage 17 to 28V DCPower Requirements Radio Hub 40mA at 24V DCRCC Mains Powered 220-240VAC, 50HzBattery Backup: Radio Hub N/ARCC 1 x 6V 4AhBattery Standby Time: Radio Hub N/ARCC 72 HoursMaterial: ABS - IP54Dimensions and Weight of Interface 270mm width x 205mm height x 85mm depth, 950 grams

Xpander Radio Hub 4110-2004Xpander Radio Communications Cluster 4110-2005

www.ampac.net www.ampac.net

Page 36: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

70 71Detection & MCP’s

Specifications

Power SupplyDetector Unit : PRO·SENS ®PRO·SENS® 2Number of Sensor Modules Fitted : 1 2Max. Number of Sampling Holes : 32 64Max. Total Pipe Length Capable : 300m* 560m*Weight: 1460g 1560gCurrent – Start Up Maximum: 300mA 320mACurrent - Quiescent (at 24 VDC) 200mA 220mACurrent - Alarm (at 24 VDC) 210mA 240mAOperating Voltage: 24 VDC (14 - 30 VDC)Tapered Pipe Connectors: 1 x 25mm 2 x 25mmDetector Dimensions (W x H x D) : 200 x 292 x 113mmHousing Colour: RAL 9018, Papyrus WhiteCabinet Type, Rating : ABS Plastics IP20 (Optional IP52)Temperature-Standard Version: -20 °C to + 60 °CTemperature-DeepFreeze Version: -40 °C to + 60 °CHumidity (Permanent) 10-95% Rel. Non-CondensingCable Entries: 5 x M20, 2 x M25Sensor Head Sensitivities: 0.5%, 0.1% and 0.015%Interface Types XP95 Addressable Loop, Conventional Circuit , RelaysAlarms 4 Adjustable Threshold Levels: - Alert, PreAlarm, Alarm & Alarm2Fault Signals Air Flow Low, Air Flow High, Processor/Hardware Fail, Ventilator Fail Air StabilisingAlarm & Fault Relay (CLI Version) 1A, 30 VDC max.Front Panel Control & Indications: Collective Fault - Yellow Operation – Green APID & CLI Versions: Reset & Isolate Controls Detector Isolation – Yellow X 2Noise level Standard & Freezer - 45 dB(A), Silent Version - 23dB(A)Remote BarGraph Display: Panel Mounted Display Module*The maximum permissible length is pipe branch shape dependant.

ProSens Base Unit-APID 7010-1000 ProSens Base Unit-CLI 7010-1010ProSens Base Unit- OEM 7010-1020 ProSens- 40 Base Unit- APID 7010-1100ProSens-40 Base Unit- CLI 7010-1110 ProSens-40 Base Unit- OEM 7010-1120ProSens Detector 0.5% AD-10-5130ProSens Detector 0.1% AD-10-5100ProSens Detector 0.015% AD-10-5115ProSens -40 Detector 0.5% AD-10-5200ProSens -40 Detector 0.1% AD-10-5190ProSens -40 Detector 0.015% AD-10-5195Wagner Filter Box LF-AD AD-10-1960Wagner Filter Element LF-AD-E AD-10-0330Wagner Filter Box LF-AD-1 AD-10-1963Wagner Filter Element LF-AD-ES AD-10-0335Wagner Filter Box LF-AD-2 AD-10-1966Wagner Filter Element LF-AD-E2 M AD-10-0332*Wagner Filter Pipe SF-400 Short AD-10-2010*Wagner Filter Element SF-400 AD-10-1930*Wagner Filter Pipe SF-650 Long AD-10-2000*Wagner Filter Element SF-650 AD-10-1920Bar Graph Display - Titanus (panel kit) 159-0280Bar Graph Display - Titanus (add on kit) 4310-0088Remote Bar Graph Display cw Enclosure 4310-0089*Allows full flow right up until 100% Capacity. Special order only.

Item Numbers

Aspirating Smoke Detection -Wagner Titanus Family

Product Overview

TITANUS PRO•SENS® is a universal air sampling device suitable for a broad range of applications. The high degree of modular-ity of the device makes it possible to achieve a cost-effective solution – customised to suit the specific needs of the customer. An additional price advantage comes with the optional equipping of the device with a second detector module.

The base TITANUS PRO•SENS® unit with 2 detector heads fitted (TITANUS PRO•SENS® 2) can be used for separate zone detec-tion of a room and its equipment, or configured as a double knock tripping system. Each detector is completely separate, with no switching or leak between detection zonesRobust & Efficient High Pressure Light Source (HPLS) Detection Technology

• LOGIC·SENS Fire Pattern Recognition Technology • Freezer Version Operates in -40Deg to +60DegC with No Heater Boxes Required • A Powerful & Efficient Aspirator Allowing up to 560m of Pipework • A BlowFree System for Programmed or Automated On-Demand Pipe Clearing • Modular Plug In Detector Heads for a Customised & Cost Effective Solution & Maintenance • Dual Detector Ability Allows Separate Monitoring & Reporting of Room & Equipment with One Unit • Time Saving Installation & Commissioning Via Plug & Play Setup • Large Capacity 3-Stage Filters with Selectable 1-15 Micron Ratings • A Large Range of Fittings, Pipework and Sampling Points • XP95 Interfacing to FireFinderTM and LoopSenseTM Fire Control Panels • FIP Bar Graph Display Module Available & SmartGraphicsHD Display Integration • Cost Effective Solutions for Every Application Type

www.ampac.net www.ampac.net

Page 37: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

72 73Detection & MCP’s

Product Overview

FastSense is an aspirating system that adopts laser technology making it extremely sensitive, thus providing the earliest warning to the slightest traces of smoke. FastSense is available in 3 models: FastSense 25, FastSense 100, FastSense PLUS. The FastSense 25 accommodates sampling pipe up to 25 metres in length while the FastSense 100 and FastSense PLUS has total sampling pipe capacity of 100 metres and 200 metres respectively.

• Advanced Laser Technology • ClassiFire Artificial Intelligence software • Patented ‘Wastegate’ system • In-built bar-graph and smoke level display; and programming • (Available only with the FastSense PLUS) • Apollo Protocol Interface Card Interface (APIC) provides portal for indication and

control of FastSense detectors at Ampac’s FireFinder Fire Alarm Control Panel

FASTSENSE Models 25 100 PLUSVoltage 27 VDC 27 VDC 27 VDCQuiescent current 250mA 400mA 400mA

Dimensions (mm)Height 215 220 372Width 140 300 427Depth 85 90 95

Relay Outputs (All normally open 1 Amp)Fire 1 Optional Optional FittedFire 2 Optional Optional FittedPre-Alarm Optional Optional FittedAuxiliary Optional Optional FittedFault Optional Optional Fitted

No. of Pipe Inlets 1 2 4Max. Pipe Length 25m 100m 200mSensitivity RangeMinimum 25% 25% 25%Maximum 0.03% 0.03% 0.03%Data Bus 1.2km 1.2km 1.2kmIP Rating IP50 IP50 IP50Operating temperature -10°C to +60°CHumidity 0 to 90% non-condensingWeight 1.7kg 3.8kg 5.2kgApprovals AS1603.8

Aspirating Smoke Detection - FastSense

FastSense 25 detector & docking station 230-0001FastSense 100 detector & docking station 230-0002FastSense PLUS detector 230-0011FastSense PLUS detector + command module 230-0012FastSense Range Apollo XP95 Interface (APIC) 230-0041FastSense 25/100 Dust Filter 230-0147FastSense Plus Dust Filter 230-0148

Item Numbers

High Sensitivity Detection System

The HIgh Sensitivity detectors are complemented by a range of light grey fittings intended to ensure that the system will suit most applications.

• Pipes, printed with red markings, have ‘bell’ ends for easy fit to the next pipe, thus saving time and material (less need for coupling for pipe joins). • T-piece is available with friction or lock fitting. • The friction fit sampling points are aesthetically designed and have an easy fit ‘finger twist’ lock nut. • Resilient snap-on conduit saddle clips and collars, are a boon for installers. • Sampling kits are available with either friction or locking TPiece and also includes a one (1) metre sampling tube and

sampling point • Sampling pipe plug available for extending sampling point whilst being unobtrusive.

Pipe (4M Length) 230-0061Pipe Coupling Std DX 40025 230-0062Pipe Coupling IP65 DX 43025 FitAncilliaries 230-0063Large 90o Bend - Standard 230-0067End Cap 25mm DX52125 230-0068Pipe Clip Saddle GW50603 230-0072Pipe Clip Mounting Rail GW50609 230-0074Label Sampling Pipe Roll 230-0121Sampling Point Kit 10mm - Friction Fit 230-0081Sampling Point Kit 10mm - Locking 230-0082Tube - 10mm (100 metre roll) natural 230-0112Wagner Reducer Film 2.0mmGrey Standard-Grey 01-10-9390Wagner Reducer Marking Tape 01-10-9330

High Sensitivity Detection System

Item Numbers

www.ampac.net www.ampac.net

Page 38: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

74 75Audio Visual & Interafaces

Input / Output Input Zone Input 3 Input / Output 3 Input

Operating voltage 17 to 28 V dc

Quiescent current at 24 V dc 1.25mA 1.25mA 7.5mA 1.31mA 1.25mA

Max loop current at 24 V dc 2mA 1.51mA 3.6mA 1.59mA 1.54mA

Output rating 1A at 30V ac/dc N/A 1A at 30V dc 1A at 30V ac/dc N/A

Operating temp -20°C to +70°C (no icing)

Relative humidity 0 to 95% (non condensing)

Dimensions - DIN 110W x 75H x 25D mm 144W x 75H x 25D mm

Dimensions - Enclosed 150W x 200H x 52D mm 150W x 200H x 52D mm

IP Rating IP44

Product Overview

Ampac offer an extensive range of addressable Interface devices which have a new uniform sleek design for ease of instal-lation and commissioning. Designed for the monitoring and controlling of many types of essential plant equipment, the Interface devices enable fire protection solutions to be engineered simply and effectively without the need for specialist enclosures.

The range includes both single and 3 channel input output devices together with a zone input device that may be mounted in bespoke enclosures, direct surface wall mounted or DIN rail mounted.

Ampac Interfaces Single Input/Output Device

The Ampac Single Input Output Device is designed to interface to a variety of plant control equipment such as door contacts, sprinkler flow switches and fire fan control systems.

• Loop Powered • Monitored Input • Change Over Relay Output • Compatible with XP95 & Discovery Protocol • Built In Short Circuit Isolator • Low Power Consumption • Diagnostic LED Indications • Surface Mount Enclosure • DIN Rail Mount Option

Single Input Output Device DIN Mount 4210-0050Single Input Output Device Enclosed 4210-0051Single Input Device DIN Mount 4210-0052Single Input Device Enclosed 4210-0053

Three Input Output Device

The Ampac Three Input Output Device is designed to interface to a variety of plant control equipment such as door contacts, sprinkler flow switches, gas valves and fire fan control systems.

• 3 x Independent Monitored Inputs • 3 x Change Over Relay Outputs • Loop Powered inc Short Circuit Isolator • Compatible with XP95 & Discovery Protocol • Low Power Consumption • Diagnostic LED Indications • Surface and DIN Mount Enclosures

Three Input Output Device DIN Mount 4210-0054Three Input Output Device Enclosed 4210-0055Three Input Device DIN Mount 4210-0056Three Input Device Enclosed 4210-0057

Zone Input Device

The Zone Input Device is designed to allow up to 40 conventional detectors to be interfaced to the Ampac range of Apollo analogue addressable control panels.

• Conventional Monitored Input • Selectable EOL Monitoring Device • Loop Powered • Compatible with XP95 & Discovery Protocol • Built In Short Circuit Isolator • Low Power Consumption • Diagnostic LED Indications • Surface Mount Enclosure • DIN Rail Mount Option

Zone Input Device DIN Mount 4210-0058Zone Input Device Enclosed 4210-0059

www.ampac.net www.ampac.net

Page 39: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

76 77Audio Visual & Interafaces

Input / Output

Zone Monitor

Sounder Unit

Switch Monitor (inc Plus)

Mains Input / Output

3 Input / Output

Mini Switch Monitor

Operating voltage

17 to 28 V dc

Quiescent current at 24 V dc

1.25mA 4mA + detectors

1.95mA 1.25mA 1.25mA 3mA 200 μA

Max loop current at 24 V dc

3.5mA 11mA 3.6mA 4.2mA 3.5mA 7.5mA 3.4mA

Output rating 1A at 30V dc N/A 1A at 30V dc 1mA (opto) 5A at 250V ac 1A at 30V dc N/A

Operating temp -20°C to +70°C (no icing)

Relative humidity 0 to 95% (non condensing)

Dimensions 150W x 90H x 48D mm - -

Weight 240 grams 621 grams 30 grams

IP Rating IP54 IP54 -

Product Overview

There are a variety of XP95 interfaces available to suit a number of individual applications. Standard interfaces are fitted with bi-directional short circuit isolators so that they are unaffected by a single short circuit on either loop input or output. The ex-ception to this is the Main Input/Output Unit which is not isolated. DIN-Rail interfaces feature enclosures that clip to standard 35mm DIN rails or are screwed to the base of a larger enclosure. They enable fire system designers to create multi-purpose interfaces for individual sites.

XP95 Interfaces Input/Output Unit with Isolator

The Input/Output unit with Isolator provides a voltage free, single, pole, change-over relay output, a single, monitored switch input and an unmonitored, non-polarised opto-coupled input.

• It can report fault, switch open and switch closed levels • Three visible LEDs • Loop powered • Voltage free • Capable of switching up to 1A at 30V • Built-in short circuit isolator

Input Unit with Isolator 201-0151Output Unit with Isolator 201-0152

Zone Monitor with Isolator

The Zone Monitor with Isolator powers and controls the operation of a zone of up to 20 Apollo Series 65 or Orbis fire detectors from a Discovery or XP95 Loop.

• Loop powered • Visible LED • Built-in short circuit isolator

Discovery/XP95 Zone Monitor with Isolator 201-0126

Sounder Control Unit with Isolator

The XP95 Sounder Control Unit with Isolator is used to control the operation of a zone of conventional sounders and report their status to the control panel.

• Allows sounders to be operated continuously or be pulsed or be pulsed, 1 second on 1 second off • May be synchronized when in pulsed operation

Sounder Control Unit with Isolator 201-0127

Three Channel Input/Output Unit with Isolator

The Three Channel Input/Output unit with Isolator provides three voltage free, single pole, change-over relay outputs, and three monitored switch inputs.

• Supervises one or more normally-open switches on each of the three inputs • Loop powered • Capable of switching up to 30V at 1A on each of the three outputs • Built-in short circuit isolator

Three Channel Input/Output Unit with Isolator 201-0175

www.ampac.net www.ampac.net

Page 40: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

78 79Audio Visual & Interafaces

Mains Switching Input/Output Unit

The XP95 Loop Powered Mains Switching Input/ Output Unit provides a voltage free, single pole charge- over relay output and a monitored switch input.

• Supervises one or more normally-open switches connected to a single pair of cables • Three visible LEDs • Capable of switching 250 vac at up to 5 amps

Mains Switching Input/Output Unit 201-0180

Mini Switch Monitor with Isolator

The Mini Switch Monitor is an interface within an entirely new housing. This allows the unit to be fitted onto a standard 35mm DIN-Rail (using a twist-click motion) or mounted within an enclosure, for example a Manual Call Point. It is designed to monitor the state of one or more single pole, volt-free contacts connected on a single pair of cables and to report the status to the FireFinder or LoopSense addressable control equipment.

• Designed for use where space is limited • Built in short circuit isolator • Interrupt/non interrupt in one unit • ‘Pre-alarm’ status available • Three coloured LEDs giving clear status indication

XP95 Mini Switch Monitor with Isolator 201-0184

Apartment Module

The Apartment Module (AM) is a loop powered addressable device that helps reduce the costly consequences of an unwanted alarm

Operating Voltage 21 to 28 VDC (loop powered)Quiescent Current 4.9mA with 6k2Ω EOL 1.9mA with 10μF EOLAlarm Current 4.2mA + Zone alarm current of 14.5mAZone Circuit 10 detectors (max) with 6k2Ω EOL (detector current < 1.2mA) 20 detectors (max) with 10μF EOL (detector current < 2.4mA) Zone EOL 6k2Ω, 10μFSpeaker Circuit 100Volt line, 6 W max, 47k EOLAddress Setting 1 to 126Dimension Single gang PDL plateMaterial High impact ABS (white)Weight 45 grams

Apartment Module 226-0003

XP95 InterfacesAlarm Acknowledgement Facility

The Alarm Acknowledgment Facility (AAF) is a loop powered addressable device that helps reduce the costly consequence of an unwanted alarm.

Operating Voltage 21 to 28 VDC (loop powered)Quiescent Current 900µAA at 24VDCAdditional Operational Currents Ext “Hush” enabled +100µA Poll LED “ON” steady +2mA Alarm LED “ON” steady & buzzer sounding– Ia = <8mA Temperature -20°C to 70°CHumidity (Non Condensing) 0 to 95% Address Setting 1 to 126 Alarm Current <8mA at 24VDCDimension Single gang Clipsal plateWeight 45 gramsCompliance AS7240.2 and AS4428.1 amendment 1

Alarm Acknowledgement Facility AS7240 226-0002Alarm Acknowledgement Facility Horizontal AS7240 226-0004

www.ampac.net www.ampac.net

Page 41: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

80 81Audio Visual & Interafaces

Vantage LED Beacons

Designed as a general purpose LED beacon for fire, security and industrial applications, the Vantage Beacon incorporates the latest in energy efficient LED technology to provide maximum all-round visibility in an aesthetically pleasing body with minimum power requirements.

Operating Voltage 20 - 35V DCSupply Current 9mAFlash Rate T3 Temporal (red & clear) 1Hz (amber)Operating Temp. -20°C +70°CHumidity 0 to 95% Non-condensingMaterial ABS fire retardant plasticDimensionsShallow Base 94mm Ø x 60mm HDeep Base 94mm Ø x 77mm HIP rating IP43 (shallow), IP65 (deep)Weight 145g (shallow), 165g (deep)

Red LED Beacon White Shallow Body 4107-1001 Amber LED Beacon White Shallow Body 4107-1002 Red LED Beacon White Deep Body 4107-1003 Amber LED Beacon White Deep Body 4107-1004 Red LED Beacon Red Deep Body 4107-1009 Amber LED Beacon Red Deep Body 4107-1010 Clear Lens Red LED Beacon White Shallow Body 4107-1011

Vector Sounder

The Vector sounder has been designed for general purpose conventional fire detection applications and incorporates AS1670.4 compliant signal tones. The Vector sounder can be installed as a sounder base for Ampac conventional detectors or a surface mount sounder when used in conjunction with the optional lid

Operating voltage 8 to 35 VDCSupply current Evac 15mA @ 24VDCSupply current Alert 8 mA @ 24VDCSignal output AS1670.4Max. Output level 91 dBA @ 1 metre with detectorEvac 93 dBA @ 1 metre with lidVolume control -30dBAIP rating IP42Temperature range -20 to + 70°CConstruction ABSDimension (mm) 106Ø x 35h (Sounder & lid only)

Vector Sounder 205-0077Vector Sounder Lid 205-0017

Vantage Sounder

The Vantage spatial sounder has been designed for general purpose, fire and security applications and incorporates AS1670.4 compliant signal tones.

Operating voltage 21 - 28VDCVolume setting Low Med HighCurrent @ 24VDC 9mA 18mA 36mASound output @ 1m (Tone 1) 86dBA 101dBA 106dBANumber of tones 32IP Rating (shallow) IP43IP Rating (deep) IP65Operating temperature -20°C to +70°C (no icing)Humidity 0 to 95% (non condensing)Dimensions (mm) 94Ø x 85H(shallow), 94Ø x 102H (deep)Weight 200g (shallow), 220g (deep) Approvals EN54-3, AI 2002, A2 2006

Vantage Sounder Red with Shallow Base 205-0062 Vantage Sounder White with Shallow Base 205-0063 Deep Base Only Red 205-0064Deep Base Only White 205-0065

Conventional Audio Visual

Vantage Combi

The Vantage Combi is a combined low profile electronic reflex horn sounder incorporating a high output LED cluster strobe array. The Vantage Combi has been designed for general purpose, fire and security applications and incorporates AS1670.4 compliant signals.

Voltage 18 to 35 VDCVolume setting Low, Med & HighCurrent (mA @ 27VDC ) 11 - 48mASound Output (dB @ 1m) 85 - 100dBSignal AS1670.4Flash rate 1 per secSize (shallow) 93mm Dia x 90mm HSize (deep) 93mm Dia x 107mm HTemperature range -20°C to +70°CHumidity 0 to 95%IP Rating (shallow base) IP43IP Rating (deep base) IP65Weight 223g & 253Approvals AS1670.4

Deep Base Only Red 205-0064Deep Base Only White 205-0065Vantage Combi Red with Shallow Base 205-0066 Vantage Combi White with Shallow Base 205-0067Amber Sounder Beacon White Deep Body (VTB-32 Tone) 4107-5001

www.ampac.net www.ampac.net

Page 42: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

82 83Audio Visual & Interafaces

Fire Alarm Remote Indicator - Round

Ampac offer a range of remote indicators which are designed for fire detection systems requiring local indication of an individual or group of detection devices located in concealed areas. Applications include floor and ceiling voids spaces, roof spaces, lift shafts and escalator machine rooms.

Voltage 24 VDCCurrent at 24v 1.5mASize 74mm Dia x 16mm HWeight 26 grams

Remote Indicator – Fire Alarm in Concealed Space 209-0004Remote Indicator – Fire Alarm in Roof Space 209-0005Remote Indicator – Fire Alarm in Room 209-0006Remote Indicator – Fire Alarm in Duct 209-0007Remote Indicator – Fire Alarm in Cupboard 209-0008Remote Indicator – Fire Alarm Under Floor 209-0009Remote Indicator – Fire Alarm in Return Air 209-0010Remote Indicator – Fire Alarm in Exhaust Duct 209-0011Remote Indicator – Fire Alarm in Supply Air Duct 209-0012Remote Indicator – Fire Alarm in Ceiling 209-0013Remote Indicator – Fire Alarm Above 209-0014Remote Indicator – Fire Alarm 209-0020Remote Indicator – Detector Activated 209-0023

Remote Indicators

Indicator / Buzzer & Indicator / Buzzer with Mute

• Alarm activation indicator and buzzer • 10mm red flashing LED • Buzzer (with mute facility) • Modern styling

Indicator / BuzzerVoltage 24 VDCCurrent at 24v 27mALED flash rate 45 per minuteBuzzer 3.8kHz @ 114dBASize 70H x 110W x 10D mmWeight 64gIndicator / Buzzer with MuteVoltage 24 VDCCurrent at 24v 43mALED flash rate 45 per minuteBuzzer 3.8kHz @ 114dBASize 70H x 110W x 10D mmWeight 89g

Flashing Indicator / Buzzer 209-0017Flashing Indicator / Buzzer with Mute Switch 209-0016

Beacon / Strobe Sign Plate

The beacon / strobe sign plate mounts directly behind the single Beacon or Sounder/Beacon and is generally located outside the main entrance to the building to attract the attention of approaching fire fighters.

Fixing Directly behind the Sonos Model Strobe / Beacons Material Painted metal 1mmSize 120mm W X 160mm H

Vantage Sounder / Beacon FIRE Legend Plate 4210-0048ASL-86 Strobe FIRE Legend Plate 4210-0049

Vantage Dual LED Beacon

The Vantage Dual LED Beacons are designed for use with the EV3000 Emergency Warning and Intercommunication Systems. Incorporating the latest in LED technology, the Vantage beacon offers maximum all-round visibility in an aesthetically pleasing body with minimum power requirements. The low current features of the product allow installers to use a larger number of visual devices on the EV3000 which negates the need for additional output circuits and power supplies.

Operating Voltage 18 - 35V DCSupply Current 9mAFlash Rate T3 Temporal (red), 1Hz (amber)Operating Temp. -20°C +70°CHumidity 0 to 95% Non-condensingMaterial ABS fire retardant plasticDimensionsFlush 188mm L x 94mm W x 62mm HSurface 188mm L x 94mm W x 80mm HIP rating IP43 (shallow), P65 (deep)Weight 215g (shallow), 235g (deep)

Dual LED Beacon Shallow Base 4107-1005 Dual LED Beacon Deep Base 4107-1006

Xenon Strobes

AMPAC offer the flexibility of individual red and amber strobes or a combined red/amber strobe unit, complete with mounting box and terminals.

Voltage 24 VDCCurrent 140mARating 10 WattsSize inc base 100Dia x 88H mmFlash rate 75 per minuteOperating temperature -20°C to + 60°CIP rating IP65Weight – strobe 182 gramsWeight – combined unit 719 grams

24V Strobe Light Red ASL86 208-000724V Strobe light Amber ASL86 208-000824V Strobe Light Combined Red/Amber 208-0011

Conventional Audio Visual

www.ampac.net www.ampac.net

Page 43: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

84 85Audio Visual & Interafaces

Product Overview

The Ampac range of Warning Signs offer state of the art LED technology for a variety of applications in a highly aesthetic design. The slimline enclosure can easily be adapted to surface or semi-flush mounting while a range of standard fascia plates has been developed to suite Agent Release applications. A weatherproof version is also available along with custom legend fascia plates.

A maximum of 6 Warning Signs can be connected to the output of each Agent Release module located within the ZoneSense, FireFinder or LoopSense fire control panels.

• Low Power Consumption • High Efficiency LED Indications • Aesthetically Pleasing • Two or Three Wire Connectivity • Single or Dual Level Operation • Continuous or Flashing LED Operation • Synchronisation between Signs • Integral Buzzer with Mute Facility • External Sounder Output • Surface or Semi-Flush Fixing • Waterproof Version

Warning Sign (no fascia plate) 4210-0110 Warning Sign IP65 (no fascia plate) 4210-0120 ‘Fire Alarm - Do Not Enter’ (fascia plate only) 4210-0131 ‘Fire Alarm - Evacuate Area’ (fascia plate only) 4210-0132 ‘Do Not Enter - Gas Discharged’ (fascia plate only) 4210-0133 ‘Fire Door Closing’ (fascia plate only) 4210-0134 ‘Extinguishing System Inoperative’ (fascia plate only) 4210-0135 Custom Legend (specify text) 4210-0136Wall / Ceiling Mount Surround - Smart Term/Warning Sign 4210-0046Dual Ceiling Mount Surround for Warning Sign 4210-0047

Warning Signs

4210-0110 4210-0120

Operating Voltage 17 Vdc to 29 Vdc

Power Consumption Level 1 active – 50mA at 24 Vdc Level 1 & 2 active – 100mA at 24 Vdc

Operating Temperature -20°C to +55°C

Humidity 0% to 95% non condensing

IP rating 4210-0110 – IP30 4210-0120 – IP65

Material ABS Enclosure / Acrylic Fascia

Dimension (mm) 4210-0110 – 195H x 325W x 50D 4210-0120 – 212H x 338W x 67D

Item Numbers

Bell Back Box

Surface mounting of bell box designed for use with the 150mm and 200mm Bell.

Material Cast AluminiumFinish RedDepth 40 mmWeight 270 grams

Bell Back Box 206-0006

Fire Alarm Bell 200mm

The Fire Alarm Bell incorporates a solenoid actuation mechanism and is designed for fire alarm applications. Its low current consumption, ease of installation incorporating diode polarity suppression and traditionally recognisable bell sound, makes it an ideal choice for fire alarm installations.

Voltage 19-27 VDCOperating current 100mASize (without back box) 200mm Dia x 70mm DSound Level 85 dB @ 3mOperating temperature -20°C to +70°C (no icing)Weight 1.25kg

Bell 200mm 24v dc Red 206-0011

Fire Alarm Bell 150mm

The Fire Alarm Bell is a motorised, maintenance free bell designed for fire alarm applications. Its low current consumption, ease of installation incorporating diode polarity suppression and universal recognisable bell sound, makes it an ideal choice for fire alarm installations.

Voltage 12V DC or 24V DCOperating current 55mA or 25mASize (without back box) 150mm Dia x 56mm DSound level 92 dB @ 1mOperating temperature -10°C to +55°C (no icing)Weight 764 grams

AFB-63 Bell 150mm Red 24VDC 206-0012AFB-63 Bell 150mm Red 12VDC 206-0011

Bells

www.ampac.net www.ampac.net

Page 44: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

86 87Audio Visual & Interafaces

Surface Speaker - 100mm

The Surface Mount 100mm Speaker is an excellent choice for use in plant rooms, warehouses, shopping centres and malls. The custom designed speaker and transformer assembly has been engineered to meet Australian Fire Evacuation Standards

Driver 100mm (4”) dual conePower taps 0.33, 0.66, 1.25, 2.5, 5WSPL 1W @ 1m 90dB @ 1kHz (+/- 2dB)Frequency response 100Hz-15kHzConnection 4 way terminal block + 22uF bipolar capacitor

Surface Speaker – 100mm 218-0022

EasyFit Ceiling Speakers

The EasyFit range of Ceiling Speakers are lightweight, quick and easy to install, and are finished in unobtrusive white with an attractive metal grille. The EasyFit Ceiling Speaker offers a wide frequency range along with good sound dispersion ensuring quality music reproduction and excellent speech intelligibility.

Ceiling Speaker, Easyfit 5w 4” - EVAC 218-0041 Ceiling Speaker, Easyfit 5w 5” - Brilliant White 218-0042 Ceiling Speaker, Easyfit 5w 5” White 218-0043 Ceiling Speaker, Easyfit 10w 6.5” 218-0044 Ceiling Speaker, Easyfit 15w 8” White 218-0045 Ceiling Speaker, Easyfit 30w 8” White 218-0046

4 Inch 5 Watt 6 Inch 10 Watt 8 Inch 15 Watt 8 Inch 30 Watt

Driver 4” 6.5” 8” 8”

Maximum/rated power 8W/5W 15W/10W 22W/15W 45W/30W

Power taps 5, 2.5, 1.25, 0.66, 0.33W 10, 5, 2.5, 1.25W 15, 10, 5, 2.5, 1.25W 30, 15, 7.5, 3.75W

Frequency Range 100Hz - 15kHz 60Hz - 20kHz 50Hz - 17kHz 50Hz - 17kHz

Axial sensitivity 1W/1m/1kHz 94dB SPL 91dB SPL 93dB SP 93dB SPL

Opening Angle( -6dB) 144° / 93° at 1kHz / 4kHz 170° at 1kHz 165° at 1kHz 100° at 1kHz

Ceiling cutout diameter 140mm 195mm 238mm 238mm

Overall dimensions 170mm x 110mm 220mm x 115mm 273mm x 103mm 273mm x 115mm

Safety acc to EN 60065 acc to EN 60065 acc to EN 60065 acc to EN 6006

Ceiling Speaker – 100mm Recessed

The 100mm speaker is ideal for use in a wide range of applications including Emergency Warning Systems (EWS), Background Music and Public Address (PA) paging within shopping centres, offices and hotels.

Rated Power 5 wattsLine Voltage 100 VoltFrequency R esponse 100 Hz to 20 kHzSPL 96 dB (1 watt @ 0.5m)Speaker Tap (watt) 0.33, 0.66, 1.25, 2.5, 5Cut-out size 85 mm DiameterDimensions 100 x 105 HmmWeight 800 grams

Ceiling Speaker – 100mm Recessed 218-0008Low Profile Grill 218-0003

One-Shot Ceiling Speaker

The 100mm and 200mm One Shot ceiling speakers are ideal for use in a wide range of applications including Emergency Warning Systems (EWS), Background Music and Public Address (PA) paging within shopping centres, offices and hotels. The One Shot speaker units install in seconds. They simply snap fit to any 10-13mm thickness ceiling by means of the 3 integral pressure clips.

Rated Power 5 wattsLine Voltage 100 VoltFrequency R esponse 100 Hz to 15 kHzSPL 98 dB (1 watt @ 0.5m)Speaker Tap (watt) 0.33, 0.66, 1.25, 2.5, 5Cut-out size 140 mm DiameterDimensions 155 x 110 HmmWeight 850 grams

Ceiling Speaker – 100mm One-Shot (White) 218-0026Ceiling Speaker – 100mm One-Shot (Black) 218-0031Ceiling Speaker – 200mm One-Shot (White) 218-0032 One Shot Combo Speakers (Box Qty 32) 4113-1001 One Shot Combo Grills (Box Qty 32) 4113-1002

Ceiling Speaker - 200mm Recessed

The 200mm speaker is ideal for use in a wide range of applications including Emergency Warning Systems (EWS), Background Music and Public Address (PA) paging within shopping centres, offices and hotels.

Rated Power 5 wattsLine Voltage 100 VoltFrequency R esponse 100 Hz to 20 kHzSPL 96 dB (1 watt @ 0.5m)Speaker Tap (watt) 0.33, 0.66, 1.25, 2.5, 5Cut-out size 190 mm DiameterDimensions 200 x 75 HmmWeight 1 kg

Ceiling Speaker – 200mm Recessed 218-0009Low Profile Grill 218-0021

Speakers

www.ampac.net www.ampac.net

Page 45: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

88 89Audio Visual & Interafaces

Integrated Sounder Base

The Integrated Sounder Base comprises a base sounder with integral mounting base and is for use with Discovery or XP95 ranges. It is designed for indoor use.

Voltage (polarity sensitive) 17-28 VDCQuiescent current 1.2mAMax current (sounder operated) 5mAMax sounder output 92dB(A)Operating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP21DSize 115Dia x 38H mmWeight 140 grams

Integrated Base Sounder 201-0110White Cap 201-0114

Addressable Beacon Base

The Beacon Base is a loop-powered beacon combined with a standard Intelligent Mounting Base. It is used to signal a fire alarm in enclosed areas. The Beacon Base can be used either with a detector fitted or with a cap for operation as a stand-alone alarm device.

Voltage (polarity sensitive) 17-28 VDCQuiescent current 300μA at 24V DCMax current (sounder operated) 3.1mA at 24V DCMax sounder output 92dB(A)Operating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP21DSize 115mm Dia x 31mmHWeight 109 grams

Beacon Base 201-0120White Cap 201-0114

Addressable Audio & Visual

Horn Speaker - 10 Watt / 20 Watt

The High Efficiency Ampac 10 and 20 watt horn loudspeaker is specifically designed for distributed Public Address (PA) and Emergency Warning Systems (EWS) with frequency response characteristics ensuring clear speech reproduction during announcements.

10 Watt 20 WattRated input 100V 100VPower handling 10W 20WPower taps 10, 7.5, 5, 2.5, 20, 15. 10, 1.25 7.5, 5WSPL at Rated Power (10W @ 1m) 119 dB 124 dBSPL at Rated Power (1W @ 1m) 108 dB 110 dBFrequency Range (-10dB) 300Hz - 13kHz 9kHzDispersion Angle(-6dB) 140°@1kHz 90°@1kHzWeight 1.3KG 2.1KG

Horn Speaker Bosch Easy Fit 10W IP66 Grey 218-0047Horn Speaker Bosch Easy Fit 20W IP66 Grey 218-0048

Horn Speaker - 10 Watt

The Ampac 10 Watt/ 20 Watt Horn Speaker is specifically designed for distributed Public Address (PA) and Emergency Warning Systems (EWS) with frequency response characteristics ensuring clear speech reproduction during announcements.

Rated Power 10 wattsLine Voltage 100 VoltFrequency R esponse 250 Hz to 13 kHzSPL 105 dB (1 watt @ 1m)Speaker Tap (watt) 1.25, 2.5, 5, 7.5, 10Dispersion angle 110°Material UV stabilised plasticIP Rating IP65Dimensions 150 Dia x 190 DmmWeight 1.4 kg

Horn Speaker – 10 Watt 218-0028Horn Speaker – 20 Watt 218-0007Horn Speaker Bracket Wurli-Gig 218-0040

Speakers

www.ampac.net www.ampac.net

Page 46: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

90 91Audio Visual & Interafaces

Loop-Powered Beacon

The Loop-Powered Beacon is a local-area beacon designed for indoor use. The beacon has been developed as a supplement to sounders for use in situations where there is a risk that sounders will not be heard.

Voltage (polarity sensitive) 17-28 VDCQuiescent current 150µAMax current (beacon operated) 3mAFlash rate 1HzOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP23DSize 115Dia x 38H mmWeight 140 grams

Loop-Powered Beacon (Red) 201-0118Loop-Powered Beacon (Amber) Standard Flash 201-0156Loop-Powered Beacon (Clear Lens/Red Flash) Standard Flash 201-0157

Intelligent Open-Area Beacon

The Intelligent Open-Area Beacon has been developed for use in situations where there is a risk that sounders will not be heard. It is weatherproof and can be used outside.

Voltage (polarity sensitive) 17-28 VDCQuiescent current 333µAMax current (beacon operated) 3.1mAFlash rate 1HzOperating temperature -10°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP65Size 104Dia x 97.5H mmWeight 205 grams

Intelligent Open Area Beacon (Red) Sonos 208-0100Intelligent Open Area Beacon (Clear) Sonos 208-0101

Intelligent Open-Area Sounder / Sounder Beacon

The Intelligent Open-Area Sounder /Sounder Beacon has been designed for use in open areas and can be connected to any Discovery or XP95 system.

Sounder Sounder/BeaconVoltage (polarity sensitive) 17-28 VDCQuiescent current 333µAMax current 5mA 8mA(sounder/beacon operated)Max sounder output - 1HzOperating temperature -10°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP65Size 104Dia x 97.5H mmWeight 225 grams 260 grams

Intelligent Open Area Sounder (Red) Sonos 205-0100Intelligent Open Area Sounder (White) Sonos 205-0101 Intelligent Open Area Sounder Beacon (Red) Sonos 205-0102Intelligent Open Area Sounder Beacon (Clear) Sonos 205-0103

Addressable Audio & VisualSounder Beacon Base

The Sounder Beacon Base is a loop-powered sounder and beacon combined with a standard Intelligent Mounting Base. It is used to signal a fire alarm in enclosed areas. The Sounder Beacon Base can be used either with a detector fitted or with a cap for operation as a stand-alone alarm device.

Voltage (polarity sensitive) 17-28 VDCQuiescent current + Beacon 300µAMax current (sounder operated) 8mAMax current (beacon only) 3.1 mAMax sounder output 91dB(A)Operating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP21DSize 115Dia x 38H mmWeight 160 grams

Sounder Beacon Base 201-0116Beacon Base 201-0120White Cap 201-0114

www.ampac.net www.ampac.net

Page 47: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

92 93Audio Visual & Interafaces

I.S. Sounder Red Body 205-0114I.S. Beacon Red Body, Red Lens 208-0201I.S. Beacon Red Body, Amber Lens 208-0202I.S. Beacon Red Body, Clear Lens 208-0203 I.S. Sounder Beacon Red Body, Red Lens 205-0111 I.S. Sounder Beacon Red Body, Amber Lens 205-0115I.S. Sounder Beacon Red Body, Clear Lens 205-0116Sounder/Beacon Solenoid Driver Single Channel 205-0112Sounder/Beacon Solenoid Driver Dual Channel 205-0117Sounder Circuit Zener Barrier 205-0118

Product Overview

The Intrinsically Safe range of products includes the compact I.S. Sounder, I.S. Beacon and I.S. Sounder / Beacon. The range is suitable for all intrinsically safe signalling applications including fire, security and process control. Approvals include ATEX and IECEx and GOST-R for Zone 0 applications and FM approval for Class I Division 1 and Class I Zone 0 applications. The I.S. Beacon optimises the effectiveness of its six high output LEDs via a prismatic lens design.

The I.S. combined Sounder and Beacon requires only one Zener barrier or galvanic isolator to run both sounder and beacon or alternatively the unit can be operated as individual signals. Power to the I.S. range should be via a certified zener barrier or galvanic isolator whose output parameter is no greater than, Uo=28v dc, Io=93mA,and Po=660mw. The beacon is internally input overload and reverse polarity protected and is end of line monitoring resistor certified.

• Input Overload and Reverse Current Protection • End of Line Resistor Certified • ATEX and IECEx approval • 2 x M20 clearance gland knockouts • Auto Synchronised Sound Output (exc. Beacon)

Sounder Beacon Sounder/Beacon

Voltage Range 16-28Vdc via Zener barrier or galvanic isolator

Nominal Current Consumption 25mA at 24V DC 25mA at 24V DC 30mA at 24V DC

Energy - double flash at 2Hz and 1Hz

Flash Rate - 23cd 23cd

Sound Output (nominal) at 1m +/- 3dB – Tone 2 100dB(A) 100dB(A)

Number of Tones 49 49

Temperature range -40 to +60°C

Protection rating IP65

Boxed weight Red

Body Colours Red, Amber, Clear

Item Numbers

Hazardous Area - Intrinsically Safe

BEx Flameproof Sounder Red Body 205-0113BEx Flameproof Beacon Red Body, Red Lens 208-0200BEx Flameproof Sounder Beacon Red Body, Red Lens 205-0110

Product Overview

The flameproof range of products is ideal for hazardous areas, specifically Zone 1 and 2 applications. The use of flameproof technology ensures that engineers installing into hazardous areas need not fit an intrinsically safe barrier and the associ-ated wiring requirements. Sound level outputs are up to 117dB(A) at 1 metre with a choice of 32 alarm tones and 3 remotely selectable stages.

Housings are manufactured from corrosion proof, marine grade copper free LM6 aluminium which is phosphated and powder coated. All models have two M20 cable entries, large termination areas and an ingress protection of IP66/67. Two entry points for cabling are present for IN and OUT wiring, thus eliminating the requirement for additional flameproof junction boxes.

• ATEX and IECEx approval • Rapid installation with no barrier requirements • Suitable for Zone 1 & 2 flameproof applications • Large termination area • Ratchet adjustable stainless steel ‘U’ bracket • Synchronisation on multi-sounder systems • Sounders have 32 synchronised tones available

Beacon Sounder Sounder/Beacon

Voltage Range 20-28V DC 20-28V DC 20-28V DC

Nominal Current Consumption 300mA 265mA 565mA

Energy 5 joules (5Ws) - 5 joules (5Ws)

Flash Rate 1Hz (60 fpm) - 1Hz (60 fpm)

Sound Output (nominal) at 1m +/- 3dB – Tone 2 - 110dB(A) 110dB(A)

Number of Tones - 32 32

Temperature range -50 to +70°C -50 to +70°C -50 to +70°C

Protection rating P66/67 IP66/67 I P66/67

Boxed weight 2.45Kg 3.2Kg 4.8Kg

Body Colours Red

Item Numbers

Hazardous Area- Flameproof Equipment

www.ampac.net www.ampac.net

Page 48: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

94 95Cable

Product Overview

AMPAC Safety’s CableSAFE cables are manufactured and approved for use in Fire Detection and Emergency Warning Systems. CableSAFE cables are available with coloured sheath stripes on Red Sheath to differentiate between detector and ancillary circuits. A twisted version is available for use in addressable loop cabling when reduced line noise is essential.

• Red Sheath for Fire Alarm Application as specified for Fire Alarm use • White, blue or yellow stripe on red sheath for fire related systems • StripEasy Sheath • Metre markings • Available in flat and twisted • AS/CAS008 compliant • 200m and 500m rolls available

Approved to: AS/NZS5000.2 Cable ConstructionAS/CAS008 ACMA Compliance N31145AS/NZS1125 ConductorsAS/NZS3808 Insulation & Sheath

Applications

Fire Systems

• Addressable Loop • Addressable Interfaces • Conventional Zones • Sounders & Bells • Door Holders • Remote Indicators • Agent Release • Warning Signs

2 Core TPS Cable

Warning Systems

• Ceiling Speakers • Horn Speakers • Visual Warning Devices

2 Core TPS Cable

TPS Flat 2c 0.75mm‚ - 200M 9000-4201-0200TPS Flat 2c 0.75mm‚ - 500M 9000-4201-0500TPS Flat 2c 0.75mm‚ White Stripe - 200M 9000-4202-0200TPS Flat 2c 0.75mm‚ White Stripe -500M 9000-4202-0500TPS Flat 2c 0.75mm Yelllow Stripe - 200M 9000-4203-0200TPS Flat 2c 0.75mm Yelow Stripe - 500M 9000-4203-0500TPS Flat 2c 0.75mm Blue Stripe - 200M 9000-4204-0200TPS Flat 2c 0.75mm Blue Stripe - 500M 9000-4204-0500TPS Flat 2c 1.0mm‚ White Stripe - 200M 9000-4205-0200TPS Flat 2c 1.0mm‚ White Stripe - 500M 9000-4205-0500TPS Flat 2c 1.5mm‚ - 200M 9000-4206-0200TPS Flat 2c 1.5mm‚ - 500M 9000-4206-0500TPS Flat 2c 1.5mm‚ White Stripe -200M 9000-4207-0200TPS Flat 2c 1.5mm‚ White Stripe - 500M 9000-4207-0500

TPS Twisted 2c 1.5mm‚ - 200M 9000-5203-0200TPS Twisted 2c 1.5mm‚ - 500M 9000-5203-0500TPS Twisted Screen 2c 1.5mm‚ -200M 9000-6203-0200TPS Twisted Screen 2c 1.5mm‚ - 500M 9000-6203-0500

2 Core TPS Cable Halogen Free

TPS Flat Hal Free 2c 1.5mm- 500M 9000-7203-0500TPS Twisted Hal Free 2c 1.5mm - 200M 9000-8203-0500

Item Number Cross Section mm2

ConductorStrands/ Dia

CoreConfiguration

Stripe Colour Overall Sizemm

Std DrumLength

Std DrumLength

9000-4201-0200 0.75 7 / 0.37 Flat - 6.2 x 4.0 200M 50

9000-4201-0500 0.75 7 / 0.37 Flat - 6.2 x 4.0 500M 50

9000-4202-0200 0.75 7 / 0.37 Flat White 6.2 x 4.0 200M 50

9000-4202-0500 0.75 7 / 0.37 Flat White 6.2 x 4.0 500M 50

9000-4203-0200 0.75 7 / 0.37 Flat Yellow 6.2 x 4.0 200M 50

9000-4203-0500 0.75 7 / 0.37 Flat Yellow 6.2 x 4.0 500M 50

9000-4204-0200 0.75 7 / 0.37 Flat Blue 6.2 x 4.0 200M 50

9000-4204-0500 0.75 7 / 0.37 Flat Blue 6.2 x 4.0 500M 50

9000-4205-0200 1.0 7 / 0.43 Flat White 7.1 x 4.2 200M 54

9000-4205-0500 1.0 7 / 0.43 Flat White 7.1 x 4.2 500M 54

9000-4206-0200 1.5 7 / 0.505 Flat - 8.0 x 5.0 200M 75

9000-4206-0500 1.5 7 / 0.505 Flat - 8.0 x 5.0 500M 75

9000-4207-0200 1.5 7 / 0.505 Flat White 8.0 x 5.0 200M 75

9000-4207-0500 1.5 7 / 0.505 Flat White 8.0 x 5.0 500M 75

9000-5203-0200 1.5 7 / 0.505 Twisted - 7.5 x 6.5 200M 80

9000-5203-0500 1.5 7 / 0.505 Twisted - 7.5 x 6.5 500M 80

9000-6203-0200 1.5 7 / 0.505 Screened - 7.6 200M 93

9000-6203-0500 1.5 7 / 0.505 Screened - 7.6 500M 93

Specifications

Item Numbers

www.ampac.net www.ampac.net

Page 49: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

96 97Ancillaries

Product Overview

Ampac offers a wide range of Ancillary devices for use in conjunction with its range of intelligent and conventional detectors and control panels. A versatile and functional range offering a huge choice for any application.

Products incude:

• Electro magnetic door retainters • MultiAmp PSU • Key Holders • Wall Boxes • Document cabinets • Sealed Rechargable Lead-Acid Batteries

Ancillaries

Surface Mount Door Holder

The Surface Mount Door Holders combine good looks, high performance and economy in a low profile package. Designed to allow doors to be held open under normal conditions and released during a fire alarm condition, the Surface Mount Door Holders are simple to install and commission and are suited to a wide range of applications including:

4101- 1001/3/4 1002/5Operating Voltage 24V dc 230V acCurrent 50mA 12mADimensions (mm)ABS 87 W x 95 H x 46 DSteel 86 W x 86 H x 62 DManual Release YesOperating Temp. -10° to +50°CIP rating IP51Finish White Fire Resistant ABSApprovals EN1155

Surface Mount 200N 24V ABS Case Door Holder 4101-1001Surface Mount 200N 230V ABS Case Door Holder 4101-1002Surface Mount 500N 24V ABS Case Door Holder 4101-1003Surface Mount 200N 24V Steel Case Door Holder 4101-1004Surface Mount 200N 230V Steel Case Door Holder 4101-1005Adjustable Keeper Plate 4101-6004

Electro Magnetic Door Retainer

The AMPAC Door Retainer enables doors to be held open under normal conditions and released during a fire alarm condition. They are simple to install and commission and are suited to a wide range of applications including Hospitals, Schools, Manufacturing Plants and Office Buildings.

Operating Voltage 15 to 29 VDCOperating Current 55mA @ 24 VDCHolding Force 50kgHousing White High Temperature ABSOperating Temperature -10° to +55° CDimension (mm) 100h x 100w x 50dIP rating IP 51Weight 750 gApproval C-Tick

Ampac Door Holder 24VDC 50KG 212-0012

Electro-Magnetic Door Holders

www.ampac.net www.ampac.net

Page 50: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

98 99Ancillaries

Electro-Magnetic Door Holders

* For product specifications, please refer to the Product Data Sheet.

Flush or Surface Mount- Metal Case

The Flush Mount Door Holder is built around a robust fascia plate for flush mounting on a back box. The Surface Mount unit is supplied with a back box incorporating 20mm knockouts. Designed to allow doors to be held open under normal conditions and released during a fire alarm condition, the Door Holders are simple to install and commission and are suited to a wide range of applications including:

4101- 3001/1004 3005/1005 Operating Voltage 24V dc 230V acCurrent 50mA 12mADimensions (mm)Flush Mount 86 W x 86 H x 43 DSurface Mount 86 W x 86 H x 62 DManual Release YesOperating Temp -10° to +50°CIP rating IP51Finish Nickel Coated Painted WhiteApprovals EN1155

Flush Mount 200N 24Vdc Door Holder 4101-3001Flush Mount 200N 230Vac Door Holder 4101-3005

Floor Mount Door Holder

The Floor Mount Door Holder features rugged cast aluminium housing, a holding electromagnet with integral anti-residual ejection pin and a manual release switch.

4101- 2001/3 4 1002/4 Operating Voltage 24V dc Current 45mA 90mADimensions (mm) 110 W x 95 H x 96 DManual Release YesOperating Temp. -10° to +50°CIP rating P51Finish Aluminium White Housing Zinc Plated MagnetApproval EN1155

Floor Mount 200N 24V Cast Aluminium Door Holder 4101-2001Floor Mount 500N 24V Cast Aluminium Door Holder 4101-2002Floor Mount 200N 24V Vandal Proof Door Holder 4101-2003Floor Mount 500N 24V Vandal Proof Door Holder 4101-2004

Decorative Flush or Surface Mount

Decorative Door Holders are particularly suitable for installation in prestigious projects such as Hotels, Offices, Historical Buildings and Museums. Built around a robust fascia plate for flush mounting and supplied with a back box, the Door Holders are available in Bright Chrome, Lacquered Brass or Stainless Steel finish with matching Decorative Keeper Plate.

4101- 3002/03/04 3006/07/08Operating Voltage 24V dc 230V ac Current 50mA 12mADimensions (mm) Flush Mount 86 W x 86 H x 24 DSurface Mount 86 W x 86 H x 62 DManual Release YesOperating Temp. -10° to +50°CIP rating IP51Approval EN115

Chrome Flush Mount 24V Door Holder 4101-3002Brass Flush Mount 24V Door Holder 4101-3003Stainless Steel Flush Mount 24V Door Holder 4101-3004Chrome Flush Mount 230V Door Holder 4101-3006Brass Flush Mount 230V Door Holder 4101-3007Stainless Steel Flush Mount 230V Door Holder 4101-3008Chrome Surface Mount Kit 4101-6005Brass Surface Mount Kit 4101-6006 Stainless Steel Surface Mount Kit 4101-6007 Brass Keeper Plate 4101-6008Stainless Steel Keeper Plate 4101-6009Bright Chrome Keeper Plate 4101-6010

Universal Door Holder

The Universal Door Holder is designed for floor, ceiling or wall mount applications and enables doors to be held open under normal conditions and released during a fire alarm condition. The Universal Door Holder is simple to install and commission and is suited to a wide range of applications including:

4101- 4001 / 02 4003 / 04Operating Voltage 24V dc Current 43mA 76mAStand Length (mm)Floor Mount H1 183 / 282Steel 250 / 350Manual Release YesOperating Temp -10° to +50°CIP rating IP51Finish Nickel Coated Painted WhiteApproval EN1155

Universal Mount 500N Short Stand 24V Door Holder 4101-4001 Universal Mount 500N Long Stand 24V Door Holder 4101-4002Universal Mount 1000N Short Stand 24V Door Holder 4101-4003Universal Mount 1000N Long Stand 24V Door Holder 4101-4004

www.ampac.net www.ampac.net

Page 51: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

100 101Ancillaries

Weatherproof IP65

The Weatherproof Door Holder is ideal for most applications in all types of buildings while its high level of ingress protection means it is particularly suited to use outdoors and in marine type applications.

4101-5001 4101-5002Operating Voltage 24V dc 230V ac Current 300mA 45mADimensions (mm) Assembly Ø 102 x 45Keeper Plate Ø 89 x 42Magnet Weight 2.0kgManual Release NoOperating Temp. -10° to +50°CIP rating IP65Finish Zinc Plated Steel

IP65 Protected 1200N 24Vdc 4101-5001IP65 Protected 1200N 230Vac 4101-5002

Floor Mount Bracket

A floor mounting bracket is available for the Surface Mount Door Holders. With this the Door Holder can be mounted in any convenient position on the floor to suit the door. It is supplied in a white finish with mounting instructions and is compatible with standard conduit back boxes.

Floor Mounting Bracket 4101-6001

Low Profile Keeper Plate

The non-adjustable, slim style keeper plate is for use with 200N Door Holders. It is an alternative to the standard adjustable keeper design where the gap between the door and the magnet needs to be kept to a minimum.

Low Profile Keeper Plate 200N 4101-6003

Chain Keeper Plate

The Chain Keeper enables a wall mounted electromagnetic door holder to be used even when the door will not open fully to meet the magnet. It is a very flexible solution to awkward mounting. A one metre length of chain is supplied as standard.

Keeper Plate and Mounting with 1M Chain 4101-6002

Electro-Magnetic Door Holders

Remote Door Release

Remotely releases fire doors held open by electro magnetic door holder.

Remote Door Release Plate Vertical Screen 268-0003Remote Door Release Plate Horizontal Screen 268-0010

MultiAmp-DH 250MA Flush Mount 4510-1100MultiAmp-DH 250MA Surface Mount 4510-1101

MultiAmp-DH

Remotely releases fire doors held open by electro magnetic door holder.

Material High Impact ABSFinish WhiteDimension (Recessed) 91mm H X 149mm W x 40mm D(Surface) 91mm H X 149mm W x 53mm DWeight 400g packedMains Supply Voltage 230 VAC +/- 10% @ 47-63HzDoor Holder Output Voltage 24 VDC @ 250mAOperating Temperature -5° to +45° CRelative Humidity 25% to 95%

Power Supplies

Document Cabinets

AMPAC offers ABS and metal document cabinets designed to complement the range of AMPAC’s fire control panels. The cabinets can hold in excess of 100 A4 sheets of fire and security information relevant to the premises.

Dimensions ABS – 300mm H x 360mm W x 100mm D Metal – 295mm H x 356mm W x 92mm DIP Rating IP30Weight ABS – 1kg Metal – 3kg

Document Cabinet ABS 4210-0010 Document Cabinet Metal Cool Grey 4210-0020 Document Cabinet Metal White 4210-0021

www.ampac.net www.ampac.net

Page 52: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

102 103Ancillaries

Power Supplies

2 Amp PSU - Space for 2 x 12Ahr Batts 4510-81022 Amp PSU - Space for 2 x 38Ahr Batts 4510-82025 Amp PSU - Space for 2 x 38Ahr Batts 4510-820510 Amp PSU - Space for 2 x 38Ahr Batts 4510-82105 Amp PSU - Space for 2 x 65Ahr Batts 4510-830510 Amp PSU - Space for 2 x 65Ahr Batts 4510-8310

Product Overview

The MultiAmp PSU range of power supplies has been specifically designed for Fire System Installations and features intelligent battery charging and monitoring with remote fault signalling. Available in 2A, 5A or 10A versions, the MultiAmp PSU range of switch mode power supplies has been specifically designed for use with compliant fire detection and alarm systems.

The units include intelligent battery charging using efficient EcoCharge technology, possess mains & battery monitoring with independent voltage free relay outputs. The units also feature battery deep discharge protection in the event of a prolonged mains failure. The inclusion of LED indicators provides quick diagnostics of the status of the power supply, while a variety of enclosures offer the installer a choice of standby battery backup options.

• 27.6V dc output • Energy efficient operation • Cost effective switch mode technology • Intelligent battery charging and monitoring technology with Deep discharge protection • Mains AC transient protection • Remote fault signalling • Space for addressable loop interface module

Output (mains on) 27.6Vdc

Load Output 2.0, 5.0 & 10.0 Amps

Mains Supply 110V ac to 230V ac @ 50Hz

Environment -10°C to 40°C @ 75%RH

Dimensions (mm)

12Ahr Enclosure 330W x 280H x 121D

38Ahr Enclosure 425W x 400H x 216D

65Ahr Enclosure 425W x 680H x 216D

IP rating IP30

Material 1.6mm Mild Steel

Finish Power coated - Surf Mist

Approval Complies with AS7240.4

Item Numbers

Sealed Rechargeable Lead-Acid Batteries

Ampac sells a comprehensive battery range for all applications requiring a reliable rechargeable power source. The wide range of sizes coupled with good cycling ability make them perfect for critical systems such as fire alarm and emergency warning systems. Designed using VRLA technology, negating the need to add water, these batteries can be applied in many critical systems requiring reliable reserve power. Available as 12V or for very large systems 2 volt cells (x12).

Extra large 12 Volt (consideration of battery cabinet space required)

12V 1.3AH SLA Battery 210-0008 12V 3.2AH SLA Battery 210-0006 12V 7AH SLA Battery 210-0016 12V 12AH SLA Battery 210-0010 12V 18AH SLA Battery 210-0003 12V 26AH SLA Battery 210-0012 12V 40AH SLA Battery 210-0013 12V 65AH SLA Battery 210-0015 12V 75AH SLA Battery 210-000412V 100AH SLA Battery 210-000212V 160AH SLA Battery 210-002212V 150AH SLA Battery 210-001712V 230AH SLA Battery 210-0011

2V 250AH SLA Battery 210-00182V 300AH SLA Battery 210-00192V 500AH SLA Battery 210-0020

Batteries

Detector Test Equipment

• Access poles are used with interchangeable heads that fit onto the end of the pole. • The equipment is suitable for use on a wide range of detectors. • Poles are telescopic, nonconductive, toughened fibreglass. • Light weight and simple to use

Telescopic Pole 2.5M To 4 mtrs 204-0001Single Extension Pole - 1.13M 204-0002Universal Detector Removal Tool 204-0003 Smoke Detector Test Dispenser 204-0004 Heat Detector Tester 240V AC 204-0005Heat Detector Tester - cordless (head only) 204-0017Smoke Detector Test Set - 8.2 metre 204-0009Smoke & Mains Heat Tester Set - 6 metre 204-0010Smoke & Cordless Heat Tester Set - 4.5 metre 204-0018Battery Baton for Cordless Heat Tester 204-0021Smoke Detector Test Gas 250ml Aerosol Test Gas 204-0014Can Smoke 150ML (Handheld) 204-0015Carbon Monoxide Smoke Can Detector Tester (Test Pole) 204-0020

Test Equipment

www.ampac.net www.ampac.net

Page 53: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

104 105Ancillaries

Key Holder – D2

• Provides a visible place to locate a key used for emergency access • Red finish • Instructions on glass • Break glass operation similar to a manual call point • Suitable for indoor use

Size 100mm Dia x 32mm DFinish RedWeight 130 grams

Break Glass Key Holder D2 215-0003D2 Key Box Holder Spare Glass KP-308 215-0004

Test Equipment

Discovery Programmer

The Discovery Programmer is a portable test and configuration tool for Discovery smoke and heat detectors

Discovery Programmer 53832-030 EUR

Flame Sensor Test Unit and Case

The Flame Sensor Test Kit is a tool which is designed to test flame detectors without the need of real flames.

Flame Sensor Test Unit and Case 29600-226

Smoke Pen

The Smoke Pen kit has been designed to provide a smooth, thin, non-volatile smoke stream and is ideal for testing High Sensitivity Smoke Detectors promoted by Ampac. The Smoke Pen incorporates a purpose designed dispenser which safely retains the smoke stick for easy use during serving and commissioning of aspirating systems. Each kit comes complete with five (5) smoke sticks offering over 4 hours of smoke stop/re-start usage)

Smoke Pen 204-0030

Wall Boxes

• Used for flush mounting devices such as manual call points and sounders • Suitable for MCP models ACP-01 & FP2 • Suitable for ‘Vara’ sounder

Size Metal 72mm H x 72mm W x 47mm DPlastic 72mm H x 72mm W x 35mm DWeight Metal 153 gramsPlastic 47 grams

Wall Box Metal 25mm Deep for MCPs 268-0002 Wall Box Plastic 35mm Deep for MCPs 268-0009

Ancillary Equipment

Detector Base – Mounting Block

• The mounting block is recommended for use when detectors are installed on uneven surfaces • The mounting block ensures the correct fit with the base and the detector, improves

reliability and ensures that the mounting tags on the base are not overtightened • Used with Base Mounted Flame Detector

Mounting Block For S65 / XP95 Base 201-0192

Void Fire Detector Holder

The Void Fire Detector Holder allows the installation of a fire detector within a sealed ceiling space at variable heights. The holder enables easy inspection and maintenance of the fire detector located within the ceiling void space from below ceiling level.

Three models are available to suit various ceiling void heights from 0.6 metres to 3 metres.

• Adjustable mounting tubes • Aesthetically pleasing • Fixing brackets included • Removable ceiling plate

Void Detector Holder 1 Metre 4112-2001Void Detector Holder 2 Metre 4112-2002Void Detector Holder 3 Metre 4112-2003

Wilco Detector Bracket

The Willco Detector Bracket has been designed to allow installation of fire detectors within a concealed ceiling space at variable heights. The bracket assembly enables easy inspection and maintenance of the fire detector from below ceiling level. Installation is quick and easy using the existing designated false ceiling hanger along with readily available 20mm electrical conduit (not supplied).

• Adjustable mounting heights • 3 x Height adjustment brackets included • Manufactured from Galvanised Steel

Wilco Detector Bracket 4112-2008

www.ampac.net www.ampac.net

Page 54: Product Catalogue Australia 201 - Ampac · 4 Fire Control Panels 5 Specifications Power Supply Mains Supply voltage 204 – 264 VAC @ 47 – 63Hz Nom. Operating voltage 27 VDC Power

106 107Ancillaries

Ancillary EquipmentDeckhead Mounting Boxes

The Deckhead Mounting Box gives extra protection to devices to be fitted in areas where there is the possibility of moisture or condensation ingressing through the rear of the base. The new version is suitable for a wider range of detector bases as well as Apollo’s AV bases.

• Protects against water ingress. • Improved performance. • Available in polycarbonate or metal.

Deckhead Mounting Box 201-0193Metal Deckhead Mounting Box with PG16 Access Ports 201-0195Metal Deckhead Mounting Box with M20 Access Ports 201-0194Deckhead Adaptor 27249-005(for use with 29600-196 - converts cable glands from PG16 to M20)

Head Office - Perth

Ampac Pty Ltd7 Ledgar Road, Balcatta, Western Australia, 6021 Telephone: +61 8 9201 6100Fax: +61 8 9201 6101Email: [email protected]: www.ampac.net

Australia

New South Wales & Australian Capital Territory

Unit B, 28–32 Egerton Street, Silverwater, NSW 2128T: +61 2 8866 6200F: +61 2 9648 4932E: [email protected]

Northern Territory

21 Raphael Road, Winnellie, NT 0820T: +61 8 8911 1260F: +61 8 8911 1261E: [email protected]

Queensland

160 Blomfield Street, Salisbury, QLD 4107T: +61 7 3462 5700F: +61 7 3208 9355E: [email protected]

South Australia

10 Commercial Street, Marleston SA 5033T: +61 8 8246 3800F: +61 8 8246 3801E: [email protected]

Victoria & Tasmania

345 Darebin Road, Thornbury, VIC 3071T: +61 3 8459 3300F: +61 3 8459 3301E: [email protected]

As part of Ampac’s commitment to continuous improvement, specifications may change without notice. Version 6/11/19