/ Written by CA Subject to modification Product specification 1/22 Product Data Sheet Type : 1 to 4 poles Reference : MUxxxA Family : 01.03.08 Summary : 1 General Characteristics ......................................................................................................................... 2 2 Dimensional characteristics.................................................................................................................. 4 2.1 Dimensions ............................................................................................................................................... 4 2.2 4 2.3 Weight & packaging ................................................................................................................................. 4 3 Marking .................................................................................................................................................... 4 4 Installation............................................................................................................................................... 5 5 Options .................................................................................................................................................... 6 5.1 Accessories : ............................................................................................................................................ 6 6 Standards ................................................................................................................................................ 6 7 Power loss : ............................................................................................................................................ 7 8 Operation in DC current......................................................................................................................... 7 9 References .............................................................................................................................................. 8 10 Tripping curve of MCB :......................................................................................................................... 9 11 Energy let-through (I²t) : under 230V and 400V................................................................................... 9 12 Current limitation : under 230V and 400V ............................................................................................ 9 13 Discrimination......................................................................................................................................... 9 14 Cascading ............................................................................................................................................... 9 15 Circuit breaker protection of different loads ....................................................................................... 9 Appendix 1 : Temperature correction factor table ......................................................................................10 Appendix 2 : C Curve at 30 °C .......................................................................................................................11 Appendix 3 : Energy let through at 400 V ....................................................................................................12 Appendix 4 : Current limitation at 400 V ......................................................................................................13 Appendix 5 : Discrimination table.................................................................................................................14 Appendix 6 : Cascading table .......................................................................................................................19

Upload: others

Post on 20-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 1/22

Product Data Sheet Type : 1 to 4 poles Reference : MUxxxA Family : 01.03.08 Summary :

1 General Characteristics .........................................................................................................................2 2 Dimensional characteristics..................................................................................................................4 2.1 Dimensions...............................................................................................................................................4 2.2 4 2.3 Weight & packaging .................................................................................................................................4 3 Marking....................................................................................................................................................4 4 Installation...............................................................................................................................................5 5 Options ....................................................................................................................................................6 5.1 Accessories : ............................................................................................................................................6 6 Standards................................................................................................................................................6 7 Power loss : ............................................................................................................................................7 8 Operation in DC current.........................................................................................................................7 9 References ..............................................................................................................................................8 10 Tripping curve of MCB :.........................................................................................................................9 11 Energy let-through (I²t) : under 230V and 400V...................................................................................9 12 Current limitation : under 230V and 400V............................................................................................9 13 Discrimination.........................................................................................................................................9 14 Cascading ...............................................................................................................................................9 15 Circuit breaker protection of different loads .......................................................................................9 Appendix 1 : Temperature correction factor table ......................................................................................10 Appendix 2 : C Curve at 30 °C .......................................................................................................................11 Appendix 3 : Energy let through at 400 V ....................................................................................................12 Appendix 4 : Current limitation at 400 V ......................................................................................................13 Appendix 5 : Discrimination table.................................................................................................................14 Appendix 6 : Cascading table .......................................................................................................................19

Page 2: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 2/22

1 General Characteristics

Protection against overloads and short circuits, switch control and isolation. In commercial and industrial electrical distribution systems. Curve : C (see Appendix 1) Pôles : 1P, 2P, 3P, 4P Current rating : 6 to 63 A Voltage rating : 230V to 240V / 400V to 415V and +10% Breaking capacity (Icn) 60898 : Breaking capacity (Ics) 60898 : 100% of Icn Breaking capacity (Icu) 60947-2 : Breaking capacity (Ics) 60947-2 : 75% of Icu Frequency : 50 – 60 Hz

If the frequency is different, it’s necessary to multiplied the magnetic value by coefficient K. But the thermal value is unchanged.

Number of poles Voltage (V) Breaking capacity (A)

1P 230 to 240 6 000 230 to 240 10 000 2P, 3P, 4P 400 to 415 6 000

Number of poles Voltage (V) Breaking capacity (kA)

230 to 240 10kA 1P 400 to 415 3kA (1) 230 to 240 20kA 2P, 3P, 4P 400 to 415 10kA

(1) Breaking capacity on 1 pole for IT system

F (Hz) 16 2/3 Hz – 60 Hz 100 Hz 200 Hz 400 Hz K 1 1,1 1,2 1,5

Rating insulation voltage (Ui) : 500 V according to EN60898-1 Rated impulse voltage (Uimp) : 4 kV Electrical endurance : 10 000 cycles (O-C) up 25A to In according to EN60898 4 000 cycles (O-C) up 63A to In according to EN60898 Mechanical endurance : 20 000 cycle without load IP rating : IP2x of terminals IP40 of enclosure

Page 3: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 3/22

Temperature : Calibration temperature : 30°C according to IEC / EN 60898 Working temperature : - 25°C to + 60 °C Storage temperature : - 25°C to + 80 °C Temperature derating : MCBs are designed and calibrated to carry their rated current and to operate

within their designated thermal time/current zone at 30 °C. Testing is carried out with the breaker mounted singly in a vertical plane in a controlled environment. Therefore if the circuit breaker is required to operate in conditions which differ from the reference conditions, certain factors have to be applied to the standard data. For instance if the circuit breaker is required to operate at higher ambient temperature than 30 °C it will require progressively less current to trip within the designated time/current zone.

Temperature Correction factor : You will find in Appendix 1 the correction values considering the ambient temperature

Grouping factor : Rated current reduced by factor K

Consideration should also be given to the proximity heating effect of the breakers themselves when fully loaded and mounted together in groups. There is a certain amount of watts loss from each breaker depending on the trip rating which may well elevate the ambient air temperature of the breaker above the ambient air temperature of the enclosure

No. of units n K (grouping factor)

n = 1 1 2 ≤ n < 4 0,95 4 ≤ n < 6 0,9 6 ≤ n 0,85

Note :If the design current of a circuit (lb) is less than 0,85 times the nominal setting of the circuit breaker (In) grouping can be ignored.

Pollute degree : 3 Dielectric strength : 2,5kV according to EN 60898 Case material : Thermoplastic (Polyamide) Compliance with IEC 695-2-1 Glow-wire test : 960°C for case according to IEC 60695-2-1 650°C for toggle according to IEC 60695-2-1 Tropicalisation : All climates, treatment 2 (relative humidity = 95% at 55°C)

Page 4: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 4/22

2 Dimensional characteristics

2.1 Dimensions

2.2

2.3 Weight & packaging

Poles Lg (Nb. Modules)*

1P 1 2P 2 3P 3 4P 4

* Width of 1 Mod 17,6 ±0,1

No. of pole 1P 2P 3P 4P Weight (g) 118 237 354 475 Number of products per box x12 x6 x4 x3

3 Marking

On the shoulder : On the face : On the side (right & left) :

3 25061 4531 0

20

Barre code & EAN13

Page 5: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 5/22

4 Installation

Mounting : Din rail EN 50.022-35 Supply : Feed either top or bottom Connection capacity : Rigid conductor : 25 mm² Flexible conductor : 16 mm² On a bottom, there is a bi-connect terminal Tightening torque : 2,5 Nm nominal with Screw head pozidrive size 2 and slot 6 mm 3,15 Nm maximal with Screw head pozidrive size 2 and slot 6 mm Type of cable : Copper Sealable : The locking kit (MZN 175) allows locking MCB in the “OFF” and “ON” position. The locking kit is sealable. The MCB can be lock in the “OFF” and “ON” position with max.∅ 1,5mm

leading wire Flag indicator : No flag

Installation altitude : 2 000 meters max Working position : Product performances not affected if installed vertically, horizontally or flat Din clip type : Metal Din clip with 2 positions Auxiliaries : Yes

Page 6: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 6/22

5 Options

5.1 Auxiliaries :

Earth leakage add-on blocks : please see the catalogue Auxiliary contacts : MZ 201 Auxiliary contact + alarm indication : MZ 202 Shunt trip : MZ 203 Under voltage release : MZ 205 (48 VAC)

MZ 206 (230 VAC) Remote control : MZ 900

5.2 Accessories :

Locking kit : MZN 175 Locking wire : MZN 176 Fork Busbar : KDN xxx Connectors : KF xxx

6 Standards

Complies with : EN 60898 and IEC 60898 Approval laboratory Logo Countries

Kema

Netherland

Page 7: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 7/22

7 Power loss :

The power loss of MCB's is closely controlled by the standards and is calculated on the basic of the voltage drop across the main terminals measured at rated current. The table below gives the watts loss per pole at rated current.

MCB rated current (A) 6A 10A 16A 20A 25A 32A 40A 50A 63A

Watts loss per pole (W) 1.4 1.9 3 2.8 3.2 3.8 4.5 5.1 6.4

Resistance R (mΩ) 113 39 13 13.3 11.7 7 5.1 3.7 2.8

Inductance L (µH) 4.2 7.2 2.4 3.1 2.7 1.54 1.5 1.21 1.29

Reactance Lω (mΩ) 1.32 2.26 0.75 0.97 0.85 0.48 0.47 0.38 0.41

Impedance Z (mΩ) 113 39.1 13 13.3 11.7 7.02 5.12 3.72 2.83

8 Operation in DC current

Because of their quick make and break design and excellent arc quenching capabilities Hager circuit breakers are suitable for DC applications. The following parameters must be considered : Max voltage per pole : 60V (15kA) Network voltage : determined by the number of poles connected in series. Short circuit current : determined the breaking capacity in relation to the network voltage and the

number of poles connected in series.

Breaking capacity (kA) L/R= 15 ms No. of poles

in series ≤ 60 V ≤ 125 V ≤ 250 V 1 15 - - 2 20 15 - 3 25 20 - 4 35 25 15

Tripping characteristics : the thermal trip remains unchanged.

the magnetic trip will become less sensitive requiring derating by √2 the AC value.

C Curve Magnetic trip 50 Hz DC

Irm1 5 In 5 In Irm2 10 In 15 In

Page 8: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 8/22

9 References

Com. Réf. Num. Réf. EAN code Designation

MU106A 451700 3250614517006 MCB 1P 6kA C-6A 1M MU110A 451701 3250614517013 MCB 1P 6kA C-10A 1M MU116A 451703 3250614517037 MCB 1P 6kA C-16A 1M MU120A 451704 3250614517044 MCB 1P 6kA C-20A 1M MU125A 451705 3250614517051 MCB 1P 6kA C-25A 1M MU132A 451706 3250614517068 MCB 1P 6kA C-32A 1M MU140A 451707 3250614517075 MCB 1P 6kA C-40A 1M MU150A 451708 3250614517082 MCB 1P 6kA C-50A 1M MU163A 451709 3250614517099 MCB 1P 6kA C-63A 1M MU206A 451710 3250614517105 MCB 2P 6kA C-6A 2M MU210A 451711 3250614517112 MCB 2P 6kA C-10A 2M MU216A 451713 3250614517136 MCB 2P 6kA C-16A 2M MU220A 451714 3250614517143 MCB 2P 6kA C-20A 2M MU225A 451715 3250614517150 MCB 2P 6kA C-25A 2M MU232A 451716 3250614517167 MCB 2P 6kA C-32A 2M MU240A 451717 3250614517174 MCB 2P 6kA C-40A 2M MU250A 451718 3250614517181 MCB 2P 6kA C-50A 2M MU263A 451719 3250614517198 MCB 2P 6kA C-63A 2M MU306A 451730 3250614517303 MCB 3P 6kA C-6A 3M MU310A 451731 3250614517310 MCB 3P 6kA C-10A 3M MU316A 451733 3250614517334 MCB 3P 6kA C-16A 3M MU320A 451734 3250614517341 MCB 3P 6kA C-20A 3M MU325A 451735 3250614517358 MCB 3P 6kA C-25A 3M MU332A 451736 3250614517365 MCB 3P 6kA C-32A 3M MU340A 451737 3250614517372 MCB 3P 6kA C-40A 3M MU350A 451738 3250614517389 MCB 3P 6kA C-50A 3M MU363A 451739 3250614517396 MCB 3P 6kA C-63A 3M MU406A 451811 3250614518119 MCB 4P 6kA C-6A 4M MU410A 451812 3250614518126 MCB 4P 6kA C-10A 4M MU416A 451814 3250614518140 MCB 4P 6kA C-16A 4M MU420A 451815 3250614518157 MCB 4P 6kA C-20A 4M MU425A 451816 3250614518164 MCB 4P 6kA C-25A 4M MU432A 451817 3250614518171 MCB 4P 6kA C-32A 4M MU440A 451818 3250614518188 MCB 4P 6kA C-40A 4M MU450A 451819 3250614518195 MCB 4P 6kA C-50A 4M MU463A 451820 3250614518201 MCB 4P 6kA C-63A 4M

Page 9: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 9/22

10 Tripping curve of MCB :

The curve in Appendix 2 gives the time of tripping in relation to the prospective current.

11 Energy let-through (I²t) : under 230V and 400V

The energy let-through of a circuit breaker is expressed in ampere squared seconds and referred as to as I²t. The curve in Appendix 3 and 3’ gives the maximum values of I²t as a function of the prospective current.

12 Current limitation : under 230V and 400V

The energy limiting characteristics of circuit breakers reduce the damage that might otherwise be caused by short-circuits. The curves in Appendix 4 and 4’ show energy limiting characteristics of our circuit breakers.

13 Discrimination

Prospective fault levels to which selectivity is achieved are in Appendix 5.

14 Cascading

Cascading or back-up protection as it is sometimes referred to, is the coordination of two or more protective devices to disconnect a fault and allows designers and installers to use a device with a breaking capacity lower than the prospective fault current. See Appendix 6

15 Circuit breaker protection of different loads

The different tables give recommended circuit breaker ratings for use in circuits with different load type. See Appendix 7, 7’, 7’’

Page 10: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 10/22

Appendix 1 : Temperature correction factor table

Miniature circuit breaker Standard EN 60898 Curve B, C and D

In (A) -25°C -20°C -15°C -10°C -5°C 0°C 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C6 8.64 8.4 8.16 7.92 7.68 7.44 7.2 6.96 6.72 6.48 6.24 6 5.76 5.52 5.28 5.04 4.8 4.5610 14.4 14 13.6 13.2 12.8 12.4 12 11.6 11.2 10.8 10.4 10 9.6 9.2 8.8 8.4 8 7.6 15 21.6 21 20.4 19.8 19.2 18.6 18 17.4 16.8 16.2 15.6 15 14.4 13.8 13.2 12.6 12 11.416 23.0 22.4 21.8 21.1 20.5 19.8 19.2 18.6 17.9 17.3 16.6 16 15.4 14.7 14.1 13.4 12.8 12.220 28.8 28 27.2 26.4 25.6 24.8 24 23.2 22.4 21.6 20.8 20 19.2 18.4 17.6 16.8 16 15.225 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 32 46.1 44.8 43.5 42.2 41.0 39.7 38.4 37.1 35.8 34.6 33.3 32 30.7 29.4 28.2 26.9 25.6 24.340 57.6 56 54.4 52.8 51.2 49.6 48 46.4 44.8 43.2 41.6 40 38.4 36.8 35.2 33.6 32 30.450 72 70 68 66 64 62 60 58 56 54 52 50 48 46 44 42 40 38 63 90.7 88.2 85.7 83.2 80.6 78.1 75.6 73.1 70.6 68.0 65.5 63 60.5 58.0 55.4 52.9 50.4 47.9

Page 11: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 11/22

Appendix 2 : C Curve at 30 °C

Miniature circuit breaker Standard EN 60898

MCB CURVE C TIME-CURRENT CHARACTERISTICCalibration temperature: 30 °C

0.01

0.1

1

10

100

1000

10000

1 10Current in multiple of rated current

Tim

e in

sec

onds

A2

CD

G1

C

100

Page 12: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 12/22

Appendix 3 : Energy let through at 400 V

Miniature circuit breaker Standard EN 60898 Curve C

DISJONCTEUR 1 MODULE ACCESSORIABLENorme EN 60898 Courbe C / Contraintes thermiques à 400 V

0.0001

0.001

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100 1000 10000 100000Intensité présumée (A)

Con

train

te th

erm

ique

(kA

²s)

63 A

50 A

40 A

32 A

25 A

20 A

16 A

13 A

10 A

6 A

4 A

3 A

2 A

1 A

0.5 A

0.5 A

1 A, 2 A

3 A, 4 A

6 A 10 A 13 A, 16 A 20 A, 25 A

32 A, 40 A 50 A, 63 A

6 000

Page 13: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 13/22

Appendix 4 : Current limitation at 400 V

Miniature circuit breaker Standard EN 60898 Curve C

DISJONCTEUR 1 MODULE ACCESSORIABLENorne EN 60898 Courbes C / Intensités crêtes à 400 V

100

1000

10000

100 1000 10000 100000Intensité présumée (A)

Inte

nsité

crê

te (A

)

0.5 A

1 A, 2 A

3 A, 4 A

6 A

10 A 13 A, 16 A

20 A, 25 A 32 A, 40 A

50 A, 63 A

6 000

Page 14: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 14/22

Appendix 5 : Discrimination table

SELECTIVITY CHART 240/415 V AC ACCORDING TO IEC 60947-2 Upstream : Hager MCCB Downstream : all MCB (1 & 1,5 module / pole) and RCBO ranges

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs

Page 15: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 15/22

Upstream : all MCB (1 & 1,5 module / pole) and RCBO ranges Downstream : all MCB (1 & 1,5 module / pole) and RCBO ranges

The rated short-circuit breaking capacity of the upstream device should be at least the same as the downstream device

Page 16: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 16/22

Upstream : Fuse category gG (SOCOMEC) Downstream : MCB (1 module / pole) in Océan 2 & V1 ranges

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs

Page 17: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 17/22

Upstream : Fuse category DIAZED gL/gl 500V (SIEMENS) Downstream : MCB (1 module / pole) in Océan 2 & V1 ranges

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs

Page 18: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 18/22

Upstream : Fuses category NH00 500V gL/gI (SIEMENS) Downstream : MCB (1 module / pole) in Océan 2 & V1 ranges

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs

Page 19: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 19/22

Appendix 6 : Cascading table

Upstream : MCB (1 module / pole) and RCBO ranges Downstream : MCB (1 module / pole) and RCBO ranges

Page 20: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 20/22

Upstream : Hager MCCB Downstream : MCB (1 module / pole) and RCBO ranges

Page 21: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n

/ Written by CA Subject to modification Product specification 21/22

Upstream : Fuse category gG (SOCOMEC) Downstream : MCB (1 module / pole) and RCBO ranges

Page 22: Product Data Sheetpararrayos-sipa.com.ar/wp-content/uploads/2018/07/... · ambient air temperature of the breaker above the ambient air temperature of the enclosure No. of units n