product description data ee - fire protection technologies · 2016. 11. 28. · data ee 1 product...
TRANSCRIPT
Unit 1/251 Ferntree Gully Road, Mt Waverley, Victoria, 3149 Australia - P.O. Box 75, Mt Waverley, Victoria, 3149 - Phone: 1300 742 296 Email: [email protected] Web: www.fire-protection.com.au
DATA SH
EET
1
Product DescriptionThe new Revised AFP Motorised Blast Vent utilises all of the tried and tested features of the SHX UN series of low to high pressure relief vents with the ability to motor the blades open for either ventilation or for multi room cascade venting applications along with offering full pressure relief when in the closed position.
SHX UN MOTORISED BLAST VENT
FORM
NO
. 35-PRV-0075 ISSUE N
O. A D
ATE. 08/05/2015
Design has been blast tested using Propane/oxygen and Acetylene/Oxygen ignition mix. 60Kpa +
1 . Blades can be motored open for ventilation or cascade venting2. Motors spring return when required. e.g.fire alarm signal3. Due to ‘one way’ linkage the blades can open independently from the motor drive to give full and instant pressure relief when needed.4. 4hr fire rated.6. New design allows the body of the vent to be installed in the wall cavity for extra security and ease of installation.7. Conforms to BRE SHX blast test certification 20088. Has been blast tested for blade opening in 13ms9. Stocked item so normal supply within 5 working days
Unit 1/251 Ferntree Gully Road, Mt Waverley, Victoria, 3149 Australia - P.O. Box 75, Mt Waverley, Victoria, 3149 - Phone: 1300 742 296 Email: [email protected] Web: www.fire-protection.com.au
DATA SH
EET
2
Vent Size A B C D E Hole Cutout Width
Hole Cutout Height FVA m2
SHX UN 1000M 1120 1040 1028 1054 1043 1055 1045 0.85SHX UN 700M 820 740 728 754 743 755 745 0.416SHX UN 500M 620 540 528 554 543 555 545 0.212SHX UN 300M 420 340 328 354 343 355 345 0.076
SPECIFICATIONS - UNIT DIMENSIONS
EUROPEAN APPROVALSBS EN 1363-1 Fire RatingNo 232889 BRE UK- 2 Hour Integrity
No Chilt/IF 10004- 4 Hour Integrity
No Chilt/IF 10030- 30 Min Insulation
BS EN 13501 - 2 CertificationNo Chilt/CF 10030- E60 / E130
No Chilt/CF 10004- EW120
PERFORMANCE CERTIFICATIONNo 122084 BRE UK
FORM
NO
. 35-PRV-0075 ISSUE N
O. A D
ATE. 08/05/2015
US APPROVALSUL555 & ASTM E 119-08a- 2 hour IntegrityTest Report by Guardian Laboratories USA