PRODUCT GUIDE

LFII Residential Sprinklers

Sprinkler System Components

CPVC Pipe & Fittings

2 3

•   Developed specifically for residential occupancies

•   The most complete system on the market today from a single manufacturer

•   Features BlazeMaster® CPVC pipe and fittings, making installation quick, easy, flexible, and affordable

•   Exclusive ten-year limited warranty lets you install with confidence

•  Product line meets all NFPA standards

•   Components are all UL listed for residential installations

Table of Contents

Series LFII Sprinklers .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 4-8

Series LFII Dry Sprinklers .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 9

Series LFII NFPA 13 Optimized Sprinklers .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..10-13

System Components .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..14-15

CPVC Pipe and Fittings .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..16-17

Rapid Response™ Residential Fire Sprinkler Systems

2 3

•   Developed specifically for residential occupancies

•   The most complete system on the market today from a single manufacturer

•   Features BlazeMaster® CPVC pipe and fittings, making installation quick, easy, flexible, and affordable

•   Exclusive ten-year limited warranty lets you install with confidence

•  Product line meets all NFPA standards

•   Components are all UL listed for residential installations

Table of Contents

Series LFII Sprinklers .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 4-8

Series LFII Dry Sprinklers .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 9

Series LFII NFPA 13 Optimized Sprinklers .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..10-13

System Components .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..14-15

CPVC Pipe and Fittings .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..16-17

Rapid Response™ Residential Fire Sprinkler Systems

4 5

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

Series LFII Sprinklers

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

13 GPM (49,2 LPM)7.0 psi (0,48 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) below ceiling 6” – 12” (150 mm – 300 mm) below ceiling

155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

12 GPM (45,4 LPM) 8.2 psi (0,57 bar)

12 GPM (45,4 LPM) 8.2 psi (0,57 bar)

13 GPM (49,2 LPM) 9.6 psi (0,48 bar)

13 GPM (49,2 LPM) 9.6 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

16 GPM (60,6 LPM)14.5 psi (1,00 bar)

17 GPM (64, 3 LPM) 16.4 psi (1,13 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

16 GPM (60,6 LPM)14.5 psi (1,00 bar)

16 GPM (60,6 LPM)14.5 psi (1,00 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

21 GPM (79,5 LPM) 25.0 psi (1,72 bar)

21 GPM (79,5 LPM) 25.0 psi (1,72 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

23 GPM (87,1 LPM) 30.0 psi (2,07 bar)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

26 GPM (98,4 LPM) 38.3 psi (2,64 bar)

26 GPM (98,4 LPM) 38.3 psi (2,64 bar)

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.2 (60,5)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP410

LFII (TY2234) Pendent, Recessed Pendent and Domed Concealed LFII (TY1334) Horizontal and Recessed Horizontal Sidewall

• Fast response

•Approved for special applications with beamed ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.9 (70,6)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass, Custom

Tech Data TFP400 (TFP450 Domed Concealed)

We can match any Sherwin Williams color for Flat Plate and Domed Concealed sprinklers you install. See the cover plate chart on page 7 for standard colors and finishes.

• Fast response

•Used in wet pipe residential sprinkler systems for one-and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

K Factor K=3.0 (43,2)

Thread Size 1/2” (15 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP402

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

8 GPM (30,3 LPM) 7.1 psi (0,49 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

11 GPM (41,6 LPM) 13.4 psi (0,92 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

13 GPM (49,2 LPM)18.8 psi (1,29 bar)

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) below ceiling 6” – 12” (150 mm – 300 mm) top of deflector to ceiling

155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

16 GPM (60,6 LPM)13.2 psi (0,91 bar)

16 GPM (60,6 LPM)13.2 psi (0,91 bar)

17 GPM (64,3 LPM) 14.9 psi (1,03 bar)

17 GPM (64,3 LPM) 14.9 psi (1,03 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

20 GPM (75.7 LPM) 20.7 psi (1,43 bar)

20 GPM (75.7 LPM) 20.7 psi (1,43 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

18 x 20 (5,5 x 6,1)

18 (5,5)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.4 (63,4)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP412

LFII (TY1234) Pendent and Recessed Pendent LFII (TY2334) Horizontal and Recessed Horizontal Sidewall

4 5

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

Series LFII Sprinklers

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

13 GPM (49,2 LPM)7.0 psi (0,48 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) below ceiling 6” – 12” (150 mm – 300 mm) below ceiling

155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

12 GPM (45,4 LPM) 8.2 psi (0,57 bar)

12 GPM (45,4 LPM) 8.2 psi (0,57 bar)

13 GPM (49,2 LPM) 9.6 psi (0,48 bar)

13 GPM (49,2 LPM) 9.6 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

16 GPM (60,6 LPM)14.5 psi (1,00 bar)

17 GPM (64, 3 LPM) 16.4 psi (1,13 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

16 GPM (60,6 LPM)14.5 psi (1,00 bar)

16 GPM (60,6 LPM)14.5 psi (1,00 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

21 GPM (79,5 LPM) 25.0 psi (1,72 bar)

21 GPM (79,5 LPM) 25.0 psi (1,72 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

23 GPM (87,1 LPM) 30.0 psi (2,07 bar)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

26 GPM (98,4 LPM) 38.3 psi (2,64 bar)

26 GPM (98,4 LPM) 38.3 psi (2,64 bar)

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.2 (60,5)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP410

LFII (TY2234) Pendent, Recessed Pendent and Domed Concealed LFII (TY1334) Horizontal and Recessed Horizontal Sidewall

• Fast response

•Approved for special applications with beamed ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.9 (70,6)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass, Custom

Tech Data TFP400 (TFP450 Domed Concealed)

We can match any Sherwin Williams color for Flat Plate and Domed Concealed sprinklers you install. See the cover plate chart on page 7 for standard colors and finishes.

• Fast response

•Used in wet pipe residential sprinkler systems for one-and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

K Factor K=3.0 (43,2)

Thread Size 1/2” (15 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP402

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

8 GPM (30,3 LPM) 7.1 psi (0,49 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

11 GPM (41,6 LPM) 13.4 psi (0,92 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

13 GPM (49,2 LPM)18.8 psi (1,29 bar)

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) below ceiling 6” – 12” (150 mm – 300 mm) top of deflector to ceiling

155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

16 GPM (60,6 LPM)13.2 psi (0,91 bar)

16 GPM (60,6 LPM)13.2 psi (0,91 bar)

17 GPM (64,3 LPM) 14.9 psi (1,03 bar)

17 GPM (64,3 LPM) 14.9 psi (1,03 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

20 GPM (75.7 LPM) 20.7 psi (1,43 bar)

20 GPM (75.7 LPM) 20.7 psi (1,43 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

23 GPM (87,1 LPM) 27.3 psi (1,88 bar)

18 x 20 (5,5 x 6,1)

18 (5,5)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

26 GPM (98,4 LPM) 34.9 psi (2,41 bar)

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.4 (63,4)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP412

LFII (TY1234) Pendent and Recessed Pendent LFII (TY2334) Horizontal and Recessed Horizontal Sidewall

6 7

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

Series LFII Sprinklers

K Factor K= 4.9 (70,6)

Thread Size 1/2” (15 mm)

Finish White, Chrome, Brass, Custom

Tech Data TFP442

• Fast response

•Solder type

•Can be used for horizontal and sloped ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

•Cover plate conceals sprinkler components above ceiling

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

160°F/71°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

13 GPM (49,2 LPM)7.0 psi (0,48 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

LFII (TY3596) Flat Plate Concealed Pendent Flat Plate Concealed Cover Plate Colors & Finishes

Flat Plate Concealed Cover Plate Tool

Before Making A Final Color SelectionThe purpose of this color chart is to provide a basic representation of Rapid Response Flat Plate Concealed Cover Plate finish colors. This color chart shall not be used for final color selection, as color differences may occur in print and on monitors when compared to the actual product. Actual color selection should be made from a sample supplied by Tyco Fire Protection Products. Samples shall be prepared using same color applications, tools and techniques to assure consistency and accuracy. Please contact your Tyco Fire Protection Products representative for more information.

•Specially designed for installing and removing TYCO LFII and RFII Flat plate concealed cover plates

•Contains foam insert to prevent scratching of cover plate finish

•Attaches to painter’s pole, or a length of 1” CPVC pipe

• No need for ladder or scaffold to install cover plates

Custom Colors Available

Beige (RAL 1001)

Brushed Brass

Light Ivory (RAL 1015)

Brushed Chrome

Jet Black (RAL 9005)

Grey White (RAL 9002)

Terra Brown (RAL 8028)

Signal White (RAL 9003)

6 7

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

Series LFII Sprinklers

K Factor K= 4.9 (70,6)

Thread Size 1/2” (15 mm)

Finish White, Chrome, Brass, Custom

Tech Data TFP442

• Fast response

•Solder type

•Can be used for horizontal and sloped ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

•Cover plate conceals sprinkler components above ceiling

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

160°F/71°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

13 GPM (49,2 LPM)7.0 psi (0,48 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

LFII (TY3596) Flat Plate Concealed Pendent Flat Plate Concealed Cover Plate Colors & Finishes

Flat Plate Concealed Cover Plate Tool

Before Making A Final Color SelectionThe purpose of this color chart is to provide a basic representation of Rapid Response Flat Plate Concealed Cover Plate finish colors. This color chart shall not be used for final color selection, as color differences may occur in print and on monitors when compared to the actual product. Actual color selection should be made from a sample supplied by Tyco Fire Protection Products. Samples shall be prepared using same color applications, tools and techniques to assure consistency and accuracy. Please contact your Tyco Fire Protection Products representative for more information.

•Specially designed for installing and removing TYCO LFII and RFII Flat plate concealed cover plates

•Contains foam insert to prevent scratching of cover plate finish

•Attaches to painter’s pole, or a length of 1” CPVC pipe

• No need for ladder or scaffold to install cover plates

Custom Colors Available

Beige (RAL 1001)

Brushed Brass

Light Ivory (RAL 1015)

Brushed Chrome

Jet Black (RAL 9005)

Grey White (RAL 9002)

Terra Brown (RAL 8028)

Signal White (RAL 9003)

8 9

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

Series LFII Sprinklers

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

162°F/72°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

22 GPM (83.3 LPM) 27.4 psi (1,89 bar)

• Fast response

•Solder type

•Approved for special applications with beamed ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.2 (60,5)

Thread Size 1/2” (15 mm)

Finish White, Chrome, Brass, Black

Tech Data TFP420

LFII (TY2284) Flush Pendent

LFII (TY2384) Flush Horizontal Sidewall

LFII (TY2235)  Residential Dry Sprinkler, Recessed Pendent

MAXIMUM COVERAGE AREA

MAXIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m)

DRY PIPE WET PIPE

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

14 GPM (52,9 LPM) 8.2 psi (0,57 bar)

14 GPM (52,9 LPM) 8.2 psi (0,57 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

15 GPM (56,8 LPM) 9.4 psi (0,65 bar)

15 GPM (56,8 LPM) 9.4 psi (0,65 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

18 GPM (68,1 LPM) 13.5 psi (0,93 bar)

18 GPM (68,1 LPM) 13.5 psi (0,93 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

21 GPM (79,5 LPM) 18.3 psi (1,30 bar)

21 GPM (79,5 LPM) 18.4 psi (1,30 bar)

K Factor K=4.9 (70,6)

Thread Size 1” NPT (25 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP460

• Fast response

• For residential occupancies per NFPA 13D, 13R and residential portions of any occupancy per NFPA 13

•UL listed for use in wet pipe, dry pipe and pre action systems

K Factor K= 4.2 (60,5)

Thread Size 1/2” (15 mm)

Finish White, Chrome, Brass, Custom

Tech Data TFP425

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE Top of Deflector to Ceiling 4” to 6” (100 mm – 150 mm)

162°F/72°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

20 GPM (75,7 LPM) 22.7 psi (1,57 bar)

• Fast response

•Solder type

•Approved for special applications with beamed ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

LFII (TY2335) Residential Dry Sprinkler, Horizontal Sidewall

MAXIMUM COVERAGE AREA

MAXIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) Top of Deflector to Ceiling 6” – 12” (150 mm – 300 mm) Top of Deflector to Ceiling

DRY PIPE WET PIPE DRY PIPE WET PIPE

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

15 GPM (56,8 LPM) 11.6 psi (0,80 bar)

15 GPM (56,8 LPM) 11.6 psi (0,80 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

16 GPM (60,6 LPM) 13.2 psi (0,91 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

16 GPM (60,6 LPM) 13.2 psi (0,91 bar)

15 GPM (56,8 LPM) 11.6 psi (0,80 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

17 GPM (64,3 LPM)14.9 psi (1,03 bar)

17 GPM (64,3 LPM)14.9 psi (1,03 bar)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

16 x 18 (4,9 x 5,5)

16 (4,9) N/A 19 GPM (71,9 LPM)

18.6 psi (1,28 bar) N/A 20 GPM (75,7 LPM) 20.7 psi (1,43 bar)

16 x 20 (4,9 x 6,1)

16 (4,9) N/A 25 GPM (94,6 LPM)

32.3 psi (2,23 bar) N/A 25 GPM (94,6 LPM) 32.3 psi (2,23 bar)

K Factor K=4.4 (63,4)

Thread Size 1” NPT (25 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP461

• Fast response

• For residential occupancies per NFPA 13D, 13R and residential portions of any occupancy per NFPA 13

•UL listed for use in wet pipe, dry pipe and pre action systems

8 9

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

Series LFII Sprinklers

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceiling (Max. 2” rise for 12” run)

162°F/72°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

22 GPM (83.3 LPM) 27.4 psi (1,89 bar)

• Fast response

•Solder type

•Approved for special applications with beamed ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=4.2 (60,5)

Thread Size 1/2” (15 mm)

Finish White, Chrome, Brass, Black

Tech Data TFP420

LFII (TY2284) Flush Pendent

LFII (TY2384) Flush Horizontal Sidewall

LFII (TY2235)  Residential Dry Sprinkler, Recessed Pendent

MAXIMUM COVERAGE AREA

MAXIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m)

DRY PIPE WET PIPE

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

14 GPM (52,9 LPM) 8.2 psi (0,57 bar)

14 GPM (52,9 LPM) 8.2 psi (0,57 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

15 GPM (56,8 LPM) 9.4 psi (0,65 bar)

15 GPM (56,8 LPM) 9.4 psi (0,65 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

18 GPM (68,1 LPM) 13.5 psi (0,93 bar)

18 GPM (68,1 LPM) 13.5 psi (0,93 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

21 GPM (79,5 LPM) 18.3 psi (1,30 bar)

21 GPM (79,5 LPM) 18.4 psi (1,30 bar)

K Factor K=4.9 (70,6)

Thread Size 1” NPT (25 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP460

• Fast response

• For residential occupancies per NFPA 13D, 13R and residential portions of any occupancy per NFPA 13

•UL listed for use in wet pipe, dry pipe and pre action systems

K Factor K= 4.2 (60,5)

Thread Size 1/2” (15 mm)

Finish White, Chrome, Brass, Custom

Tech Data TFP425

MAXIMUM COVERAGE AREA

ft x ft (m x m)

MAXIMUM SPACING

ft (m)

MINIMUM FLOW & RESIDUAL PRESSURE Top of Deflector to Ceiling 4” to 6” (100 mm – 150 mm)

162°F/72°C

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

20 GPM (75,7 LPM) 22.7 psi (1,57 bar)

• Fast response

•Solder type

•Approved for special applications with beamed ceilings

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

LFII (TY2335) Residential Dry Sprinkler, Horizontal Sidewall

MAXIMUM COVERAGE AREA

MAXIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) Top of Deflector to Ceiling 6” – 12” (150 mm – 300 mm) Top of Deflector to Ceiling

DRY PIPE WET PIPE DRY PIPE WET PIPE

12 x 12 (3,7 x 3,7)

12 (3,7)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

13 GPM (49,2 LPM) 8.7 psi (0,60 bar)

15 GPM (56,8 LPM) 11.6 psi (0,80 bar)

15 GPM (56,8 LPM) 11.6 psi (0,80 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

16 GPM (60,6 LPM) 13.2 psi (0,91 bar)

14 GPM (53,0 LPM) 10.1 psi (0,70 bar)

16 GPM (60,6 LPM) 13.2 psi (0,91 bar)

15 GPM (56,8 LPM) 11.6 psi (0,80 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

17 GPM (64,3 LPM)14.9 psi (1,03 bar)

17 GPM (64,3 LPM)14.9 psi (1,03 bar)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

19 GPM (71,9 LPM) 18.6 psi (1,28 bar)

16 x 18 (4,9 x 5,5)

16 (4,9) N/A 19 GPM (71,9 LPM)

18.6 psi (1,28 bar) N/A 20 GPM (75,7 LPM) 20.7 psi (1,43 bar)

16 x 20 (4,9 x 6,1)

16 (4,9) N/A 25 GPM (94,6 LPM)

32.3 psi (2,23 bar) N/A 25 GPM (94,6 LPM) 32.3 psi (2,23 bar)

K Factor K=4.4 (63,4)

Thread Size 1” NPT (25 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP461

• Fast response

• For residential occupancies per NFPA 13D, 13R and residential portions of any occupancy per NFPA 13

•UL listed for use in wet pipe, dry pipe and pre action systems

10 11

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

NFPA 13 Optimized SprinklersThe large orifice 6.9 K, 5.6 K and 5.8 K sprinklers are primarily intended for residential use where there is a 0.1 gpm/sq. ft. density NFPA 13 design requirement, and are generally used for installations in excess of four stories. They are optimized for residential applications where this higher water-flow demand is required, and can meet those requirements with less pressure and smaller pipe sizes.

LFII (TY4234)  Pendent, Recessed Pendent and Domed Concealed LFII (TY3934)  5..8K Pendent, Recessed Pendent 

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupan-cies up to and includ-ing four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=6.9 (99,4)

Thread Size 3/4” (19.05 mm)

Escutcheon Style 30

Bulb Type 3 mm

Finish White, Chrome, Brass, Custom

Tech Data TFP408

MAXIMUM COVERAGE AREA

MAXIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m) Pendent and Recessed Pendent Concealed Pendent

155°F/68°C or 175°F/79°C 155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

21 GPM (79,5 LPM) 9.3 psi (0,64 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

22 GPM (87,1 LPM) 10.2 psi (2,07 bar)

24 GPM (90,8 LPM) 12.1 psi (1,15 bar)

K Factor K=5.8 (83,5)

Thread Size 1/2” (19.05 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish Natural Brass, Pure or Signal White, Jet Black, Chrome Plated

Tech Data TFP401

MAXIMUM COVERAGE AREA

MINIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE Pendent and Recessed Pendent

ft x ft (m x m) ft (m) 155°F/68°C / 175°F (79°C)

12 x 12 (3,7 x 3,7)

12 (3,7)

16 GPM (60,6 LPM) 7.6 psi (0,52 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

16 GPM (60,6 LPM) 7.6 psi (0,52 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

16 GPM (60,6 LPM) 7.6 psi (0,52 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

18 GPM (68,1 LPM) 9.6 psi (0,66 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

20 GPM (75,7 LPM) 11.9 psi (0,82 bar)

•UL and C-UL Listed

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

10 11

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

NFPA 13 Optimized SprinklersThe large orifice 6.9 K, 5.6 K and 5.8 K sprinklers are primarily intended for residential use where there is a 0.1 gpm/sq. ft. density NFPA 13 design requirement, and are generally used for installations in excess of four stories. They are optimized for residential applications where this higher water-flow demand is required, and can meet those requirements with less pressure and smaller pipe sizes.

LFII (TY4234)  Pendent, Recessed Pendent and Domed Concealed LFII (TY3934)  5..8K Pendent, Recessed Pendent 

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupan-cies up to and includ-ing four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=6.9 (99,4)

Thread Size 3/4” (19.05 mm)

Escutcheon Style 30

Bulb Type 3 mm

Finish White, Chrome, Brass, Custom

Tech Data TFP408

MAXIMUM COVERAGE AREA

MAXIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m) Pendent and Recessed Pendent Concealed Pendent

155°F/68°C or 175°F/79°C 155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

19 GPM (71,9 LPM) 7.6 psi (0,52 bar)

21 GPM (79,5 LPM) 9.3 psi (0,64 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

22 GPM (87,1 LPM) 10.2 psi (2,07 bar)

24 GPM (90,8 LPM) 12.1 psi (1,15 bar)

K Factor K=5.8 (83,5)

Thread Size 1/2” (19.05 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish Natural Brass, Pure or Signal White, Jet Black, Chrome Plated

Tech Data TFP401

MAXIMUM COVERAGE AREA

MINIMUM SPACING

MINIMUM FLOW & RESIDUAL PRESSURE Pendent and Recessed Pendent

ft x ft (m x m) ft (m) 155°F/68°C / 175°F (79°C)

12 x 12 (3,7 x 3,7)

12 (3,7)

16 GPM (60,6 LPM) 7.6 psi (0,52 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

16 GPM (60,6 LPM) 7.6 psi (0,52 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

16 GPM (60,6 LPM) 7.6 psi (0,52 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

18 GPM (68,1 LPM) 9.6 psi (0,66 bar)

20 x 20 (6,1 x 6,1)

20 (6,1)

20 GPM (75,7 LPM) 11.9 psi (0,82 bar)

•UL and C-UL Listed

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

12 13

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

NFPA 13 Optimized SprinklersThe large orifice 6.9 K, 5.6 K and 5.8 K sprinklers are primarily intended for residential use where there is a 0.1 gpm/sq. ft. density NFPA 13 design requirement, and are generally used for installations in excess of four stories. They are optimized for residential applications where this higher water-flow demand is required, and can meet those requirements with less pressure and smaller pipe sizes.

LFII (TY3334) Horizontal and Recessed Horizontal Sidewall

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) Top of Deflector to Ceiling 6” – 12” (152 mm – 305 mm) Top of Deflector to Ceiling

155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C

Recessed of Non-Recessed

12 x 12 (3,7 x 3,7)

12 (3,7)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

16 x 14 (4,9 x 4,9)

16 (4,9)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

16 x 16 (4,9 x 4,9 )

16 (4,9)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

24 GPM (90,8 LPM) 17.1 psi (1,18 bar)

24 GPM (90,8 LPM) 17.1 psi (1,18 bar)

16 x 20 (4,9 x 6,7)

16 (4,9)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

Non-Recessed

16 x 22 (4,9 x 6,7)

16 (4,9)

38 GPM (143,8 LPM) 42.9 psi (2,96 bar)

38 GPM (143,8 LPM) 42.9 psi (2,96 bar)

40 GPM (151,4 LPM) 47.6 psi (2,96 bar)

40 GPM (151,4 LPM) 47.6 psi (2,96 bar)

K Factor K=5.8 (80,6)

Thread Size 1/2” (15 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP417

LFII (TY4334) Horizontal and Recessed Horizontal Sidewall

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

• Fast response

•Used in wet pipe resi-dential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=5.6 (80,6)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass, Custom

Tech Data TFP415

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m) 4” to 6” (102 mm—152 mm) 6” to 12” (152 mm—305 mm)

155°F/68°C or 175°F/79°C 155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

17 GPM (64,3 LPM) 9.2 psi (0,63 bar)

20 GPM (75,7 LPM) 12.8 psi (0,88 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

19 GPM (71,9 LPM) 11.5 psi (0,79 bar)

22 GPM (83,3 LPM) 15.4 psi (1,06 bar)

16 x 14 (4,9 x 4,3)

16 (4,9)

20 GPM (75,7 LPM) 12.8 psi (0,88 bar)

24 GPM (90,8 LPM) 18.4 psi (1,27 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

24 GPM (90,8 LPM) 18.4 psi (1,27 bar)

28 GPM (106,0 LPM) 25.0 psi (1,72 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

26 GPM (98,4 LPM) 21.6 psi (1,49 bar)

31 GPM (117,3 LPM) 30.6 psi (2,11 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

29 GPM (109,8 LPM) 26.8 psi (1,85 bar)

37 GPM (140,0 LPM) 43.7 psi (3,01 bar)

12 13

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

NFPA 13 Optimized SprinklersThe large orifice 6.9 K, 5.6 K and 5.8 K sprinklers are primarily intended for residential use where there is a 0.1 gpm/sq. ft. density NFPA 13 design requirement, and are generally used for installations in excess of four stories. They are optimized for residential applications where this higher water-flow demand is required, and can meet those requirements with less pressure and smaller pipe sizes.

LFII (TY3334) Horizontal and Recessed Horizontal Sidewall

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

ft x ft (m x m) ft (m) 4” – 6” (100 mm – 150 mm) Top of Deflector to Ceiling 6” – 12” (152 mm – 305 mm) Top of Deflector to Ceiling

155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C

Recessed of Non-Recessed

12 x 12 (3,7 x 3,7)

12 (3,7)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

19 GPM (71,9 LPM) 10.7 psi (0,74 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

16 x 14 (4,9 x 4,9)

16 (4,9)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

16 x 16 (4,9 x 4,9 )

16 (4,9)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

21 GPM (79,5 LPM) 13.1 psi (0,90 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

23 GPM (79,5 LPM) 15.7 psi (1,08 bar)

24 GPM (90,8 LPM) 17.1 psi (1,18 bar)

24 GPM (90,8 LPM) 17.1 psi (1,18 bar)

16 x 20 (4,9 x 6,7)

16 (4,9)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

18 x 18 (5,5 x 5,5)

18 (5,5)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

29 GPM (109,8 LPM) 25.0 psi (1,72 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

30 GPM (113,6 LPM) 26.8 psi (1,85 bar)

Non-Recessed

16 x 22 (4,9 x 6,7)

16 (4,9)

38 GPM (143,8 LPM) 42.9 psi (2,96 bar)

38 GPM (143,8 LPM) 42.9 psi (2,96 bar)

40 GPM (151,4 LPM) 47.6 psi (2,96 bar)

40 GPM (151,4 LPM) 47.6 psi (2,96 bar)

K Factor K=5.8 (80,6)

Thread Size 1/2” (15 mm)

Bulb Type 3 mm

Finish White, Chrome, Brass

Tech Data TFP417

LFII (TY4334) Horizontal and Recessed Horizontal Sidewall

• Fast response

•Used in wet pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

• Fast response

•Used in wet pipe resi-dential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA 13D

•Used in wet pipe residential occupancies up to and including four stories in height per NFPA 13R

•Used in wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

K Factor K=5.6 (80,6)

Thread Size 1/2” (15 mm)

Escutcheon Style 20

Bulb Type 3 mm

Finish White, Chrome, Brass, Custom

Tech Data TFP415

MAXIMUM COVERAGE AREA

MAXIMUM SPACING MINIMUM FLOW & RESIDUAL PRESSURE

For Horizontal Ceilings (Max. 2” rise for 12” run)

ft x ft (m x m) ft (m) 4” to 6” (102 mm—152 mm) 6” to 12” (152 mm—305 mm)

155°F/68°C or 175°F/79°C 155°F/68°C or 175°F/79°C

12 x 12 (3,7 x 3,7)

12 (3,7)

17 GPM (64,3 LPM) 9.2 psi (0,63 bar)

20 GPM (75,7 LPM) 12.8 psi (0,88 bar)

14 x 14 (4,3 x 4,3)

14 (4,3)

19 GPM (71,9 LPM) 11.5 psi (0,79 bar)

22 GPM (83,3 LPM) 15.4 psi (1,06 bar)

16 x 14 (4,9 x 4,3)

16 (4,9)

20 GPM (75,7 LPM) 12.8 psi (0,88 bar)

24 GPM (90,8 LPM) 18.4 psi (1,27 bar)

16 x 16 (4,9 x 4,9)

16 (4,9)

24 GPM (90,8 LPM) 18.4 psi (1,27 bar)

28 GPM (106,0 LPM) 25.0 psi (1,72 bar)

16 x 18 (4,9 x 5,5)

16 (4,9)

26 GPM (98,4 LPM) 21.6 psi (1,49 bar)

31 GPM (117,3 LPM) 30.6 psi (2,11 bar)

16 x 20 (4,9 x 6,1)

16 (4,9)

29 GPM (109,8 LPM) 26.8 psi (1,85 bar)

37 GPM (140,0 LPM) 43.7 psi (3,01 bar)

14 15

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

System Components

Model VS-SP  WaterFlow Detector • Used with wet pipe sprinkler systems in

residential dwellings and mobile homes• Actuation of the switch can initiate an alarm

indicating that the sprinkler system is operating• Sustained flow of 8 gallons per minute will deflect

the vane and actuate a single-pole, double-throw snap action switch

• Can be wired to a local bell and/or protection panel for outside notification to an alarm company or fire department

Hangers for BlazeMaster®  CPVC ProductsTyco offers a full line of pipe hangers designed especially for use with BlazeMaster® CPVC Products.

• Designed for ease of installation• Hangers have rounded edges to prevent

damage to pipe and fittings• Meets the requirements specified in NFPA 13,

NFPA 13R and NFPA 13D

CPVC Installation Equipment• Retrofit Tools • Cutting and Deburring Tools• BlazeMaster Caulk & Walk® Firestop• One-step CPVC Cement and Daubers• •Hangers&Fasteners

Electric Alarm Bell• Ideally suited for residential applications • Unobtrusive to the homeowner, yet absolutely

dependable in a fire event• When used with a flow switch, if water flow

occurs in a sprinkler system protecting residential occupancies, an audible alarm sounds to alert the occupants and neighbors of trouble

Sprinkler Head Cabinet• Spare sprinkler head cabinets are available.

All cabinets have ample room for sprinkler wrench storage.

Riser Manifold• Available in 1” - 2”• Available in either threaded or grooved configurations• Meets NFPA 13, 13R and 13D requirements

Resi-Riser• Compact, pre-assembled, ready to install sprinkler riser• Brass construction for use in potable water supply• Available in 1” - 2” (25 mm - 50 mm) sizes• Integral test and drain assembly, flow switch with

retard mechanism, 300 psi gauge, and check valve• Compact size allows for easy installation between

2” x 4” studs in wall• Molded mounting points allow for fast and easy

left or right-hand installation• Available with or without pressure relief valve

feature and flow switch retard mechanism

“Powerball” Butterfly Valves• Ideal for use in residential sprinkler systems

as main control valves• An alternative to bulky OS&Y valves• Mandated visual indicator showing that the

valve is open or closed• Available from 1” through 2-1/2”

Residential Domestic  Shut-off Valve 1” and 2”• Used in piping systems that supply water to

both domestic service and the fire sprinkler system designed per NFPA 13D or 13R in one/two- family dwellings and mobile homes

• In the set position, water is available on demand to the domestic system, and the valve acts as a check valve for the fire protection system

• When a sprinkler operates, the supply to the domestic system is automatically shut off, maximizing the available water supply for fire protection

• Eliminates the need for expensive pumps, pressurized tanks, or electrically operated domestic shutoff valves

14 15

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

System Components

Model VS-SP  WaterFlow Detector • Used with wet pipe sprinkler systems in

residential dwellings and mobile homes• Actuation of the switch can initiate an alarm

indicating that the sprinkler system is operating• Sustained flow of 8 gallons per minute will deflect

the vane and actuate a single-pole, double-throw snap action switch

• Can be wired to a local bell and/or protection panel for outside notification to an alarm company or fire department

Hangers for BlazeMaster®  CPVC ProductsTyco offers a full line of pipe hangers designed especially for use with BlazeMaster® CPVC Products.

• Designed for ease of installation• Hangers have rounded edges to prevent

damage to pipe and fittings• Meets the requirements specified in NFPA 13,

NFPA 13R and NFPA 13D

CPVC Installation Equipment• Retrofit Tools • Cutting and Deburring Tools• BlazeMaster Caulk & Walk® Firestop• One-step CPVC Cement and Daubers• •Hangers&Fasteners

Electric Alarm Bell• Ideally suited for residential applications • Unobtrusive to the homeowner, yet absolutely

dependable in a fire event• When used with a flow switch, if water flow

occurs in a sprinkler system protecting residential occupancies, an audible alarm sounds to alert the occupants and neighbors of trouble

Sprinkler Head Cabinet• Spare sprinkler head cabinets are available.

All cabinets have ample room for sprinkler wrench storage.

Riser Manifold• Available in 1” - 2”• Available in either threaded or grooved configurations• Meets NFPA 13, 13R and 13D requirements

Resi-Riser• Compact, pre-assembled, ready to install sprinkler riser• Brass construction for use in potable water supply• Available in 1” - 2” (25 mm - 50 mm) sizes• Integral test and drain assembly, flow switch with

retard mechanism, 300 psi gauge, and check valve• Compact size allows for easy installation between

2” x 4” studs in wall• Molded mounting points allow for fast and easy

left or right-hand installation• Available with or without pressure relief valve

feature and flow switch retard mechanism

“Powerball” Butterfly Valves• Ideal for use in residential sprinkler systems

as main control valves• An alternative to bulky OS&Y valves• Mandated visual indicator showing that the

valve is open or closed• Available from 1” through 2-1/2”

Residential Domestic  Shut-off Valve 1” and 2”• Used in piping systems that supply water to

both domestic service and the fire sprinkler system designed per NFPA 13D or 13R in one/two- family dwellings and mobile homes

• In the set position, water is available on demand to the domestic system, and the valve acts as a check valve for the fire protection system

• When a sprinkler operates, the supply to the domestic system is automatically shut off, maximizing the available water supply for fire protection

• Eliminates the need for expensive pumps, pressurized tanks, or electrically operated domestic shutoff valves

16 17

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

CPVC Pipe & Fittings

Install With ConfidenceTyco BlazeMaster® CPVC Piping Systems are UL and cUL listed, FM approved, and exceed ASTM standards. Benefits over traditional piping systems include:

• Resistant to rust, scale and foreign contaminant buildup

• Superior flow characteristics for increased hydraulic capabilities (C-Factor=150)

• Easily transported, handled and modified on site

• Can be easily connected to copper and steel piping

• Resist sweating and condensation

• Immune to Microbiologically Influenced Corrosion (MIC)

Fire Performance• CPVC has an LOI (Limited Oxygen Index) that is

better than wood, PVC, PB or other common building materials. It will not support combustion; therefore, it cannot be the source of a fire or cause a fire to spread.

• Does not contribute to flashover

• Low smoke generation

• Toxicity is extremely low when compared with common building and finishing materials; equal to wood and less than wool or cotton (University of Pittsburgh protocol)

The Rapid Response Residential Fire Sprinkler System features CPVC Pipe and Fittings manufactured with Lubrizol’s BlazeMaster® compound – listed by Underwriters Laboratories, Inc. for use in:

• Light hazard occupancies as defined in the Standard for Installation of Fire Sprinkler Systems, NFPA 13

• Residential occupancies as defined in the Standard for Installation of Fire Sprinkler Systems in Residential Occupancies up to Four Stories in Height, NFPA 13R

• Residential occupancies as defined in the Standard for Fire Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, NFPA 13D

• Air plenums, as defined by the Installation of Air Conditioning and Ventilating Systems, NFPA 90A and model mechanical codes

• Underground water pressure service, NFPA 24

• Unfinished basements

(Note: for complete listing and approval information, please refer to the installation instructions and technical manual No. 19-1.0.)

FEMALE SPRINKLER HEAD ADAPTER

(WEST)

SPIGOT SPRINKLER HEAD ADAPTER

(SLIP X FIPT)

FEMALE SPRINKLER HEAD ADAPTER

(EAST)

CPVC MALE ADAPTER

CPVC BACK-TO-BACK SPRINKLER

HEAD ADAPTER

CPVC SPRINKLER HEAD 90° ELBOW

BACK-TO-BACK CROSS SPRINKLER

HEAD ADAPTER

CPVC TO COPPER-FEMALE ADAPTER (SLIP X FEMALE)

CPVC GROOVED COUPLING ADAPTER

(GROOVE X SLIP)

CPVC PIPE (3/4” — 3”)

CPVC CROSS

CPVC ELBOW 90°

CPVC ELBOW 45° CPVC REDUCING TEE

CPVC COUPLING

CPVC REDUCING COUPLING

CPVC BUSHING

CPVC CAP

CPVC TEE

16 17

Always refer to the technical data sheet for complete description and all listing criteria, design parameters, installation instructions, care and maintenance guidelines and our limited warranty.

CPVC Pipe & Fittings

Install With ConfidenceTyco BlazeMaster® CPVC Piping Systems are UL and cUL listed, FM approved, and exceed ASTM standards. Benefits over traditional piping systems include:

• Resistant to rust, scale and foreign contaminant buildup

• Superior flow characteristics for increased hydraulic capabilities (C-Factor=150)

• Easily transported, handled and modified on site

• Can be easily connected to copper and steel piping

• Resist sweating and condensation

• Immune to Microbiologically Influenced Corrosion (MIC)

Fire Performance• CPVC has an LOI (Limited Oxygen Index) that is

better than wood, PVC, PB or other common building materials. It will not support combustion; therefore, it cannot be the source of a fire or cause a fire to spread.

• Does not contribute to flashover

• Low smoke generation

• Toxicity is extremely low when compared with common building and finishing materials; equal to wood and less than wool or cotton (University of Pittsburgh protocol)

The Rapid Response Residential Fire Sprinkler System features CPVC Pipe and Fittings manufactured with Lubrizol’s BlazeMaster® compound – listed by Underwriters Laboratories, Inc. for use in:

• Light hazard occupancies as defined in the Standard for Installation of Fire Sprinkler Systems, NFPA 13

• Residential occupancies as defined in the Standard for Installation of Fire Sprinkler Systems in Residential Occupancies up to Four Stories in Height, NFPA 13R

• Residential occupancies as defined in the Standard for Fire Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, NFPA 13D

• Air plenums, as defined by the Installation of Air Conditioning and Ventilating Systems, NFPA 90A and model mechanical codes

• Underground water pressure service, NFPA 24

• Unfinished basements

(Note: for complete listing and approval information, please refer to the installation instructions and technical manual No. 19-1.0.)

FEMALE SPRINKLER HEAD ADAPTER

(WEST)

SPIGOT SPRINKLER HEAD ADAPTER

(SLIP X FIPT)

FEMALE SPRINKLER HEAD ADAPTER

(EAST)

CPVC MALE ADAPTER

CPVC BACK-TO-BACK SPRINKLER

HEAD ADAPTER

CPVC SPRINKLER HEAD 90° ELBOW

BACK-TO-BACK CROSS SPRINKLER

HEAD ADAPTER

CPVC TO COPPER-FEMALE ADAPTER (SLIP X FEMALE)

CPVC GROOVED COUPLING ADAPTER

(GROOVE X SLIP)

CPVC PIPE (3/4” — 3”)

CPVC CROSS

CPVC ELBOW 90°

CPVC ELBOW 45° CPVC REDUCING TEE

CPVC COUPLING

CPVC REDUCING COUPLING

CPVC BUSHING

CPVC CAP

CPVC TEE

1918

 :Q  When a fire occurs, will every sprinkler in the  house activate?

 :A  No, all fire sprinklers in a sprinkler system do not activate at once.. When a fire sprinkler activates, the sprinkler closest to the fire goes off.. In 90% of cases, one sprinkler is enough to suppress the fire..

 :Q  Can smoke trigger the sprinkler system?

 :A  No, burning toast, cigars and other smoke sources will not trigger a fire sprinkler.. Fire sprinklers are only activated by extremely high temperatures, and only a truly threatening fire can generate enough heat to activate one..

 :Q  Isn’t there a lot of water damage when a  sprinkler system activates?

 :A  No.. A residential fire sprinkler uses only 38-95 liters of water per minute, and operates early in a fire.. A hose used by firefighters flows about 10 times that amount – around 473-946 liters per minute, which has the potential to cause much greater damage..

 :Q  Can a fire sprinkler go off accidentally?

 :A  The chances a  fire sprinkler will accidentally discharge due to a manufacturing defect are about 1 in 16 million.. Overall, fire sprinkler accidents are less likely and less severe than accidents involving home plumbing systems..

 :Q  Won’t fire sprinklers look out of place in my  beautiful new home?

 :A  Not at all.. RAPID RESPONSE sprinklers come in a wide range of colors and styles, ensuring they blend aesthetically with any home décor.. Plus, they’re small and unobtrusive..

 :Q  How much can I expect to spend on a RAPID RESPONSE sprinkler system?

 :A  Installing a fire sprinkler costs about the same as a flooring upgrade, and can save you up to 15% on your homeowner’s insurance premium..

 :Q  Does a home fire sprinkler system require  a lot of maintenance?

 :A  No, after installation, nothing more than a simple once a year system testing is recommended.. 

A Typical RAPID RESPONSE Residential Fire Sprinkler System

Frequently Asked Questions

J

IH

G

F

E

D

C

B

A

A: Main Water Control Valve

B:  Water Meter

C: “T” Connection  to Water Main

D: Backflow Valve

E:  Water Supply to  Sprinkler System

 F: Control Valve for   Plumbing System

 G: Flow Switch (Optional)

 H:  Water Supply to  Plumbing System

  I:  Test and Drain Assembly

 J: Pressure Gauge

Your system may contain different components than the one pictured.

The water meter (B) may also be located outside.

1918

 :Q  When a fire occurs, will every sprinkler in the  house activate?

 :A  No, all fire sprinklers in a sprinkler system do not activate at once.. When a fire sprinkler activates, the sprinkler closest to the fire goes off.. In 90% of cases, one sprinkler is enough to suppress the fire..

 :Q  Can smoke trigger the sprinkler system?

 :A  No, burning toast, cigars and other smoke sources will not trigger a fire sprinkler.. Fire sprinklers are only activated by extremely high temperatures, and only a truly threatening fire can generate enough heat to activate one..

 :Q  Isn’t there a lot of water damage when a  sprinkler system activates?

 :A  No.. A residential fire sprinkler uses only 38-95 liters of water per minute, and operates early in a fire.. A hose used by firefighters flows about 10 times that amount – around 473-946 liters per minute, which has the potential to cause much greater damage..

 :Q  Can a fire sprinkler go off accidentally?

 :A  The chances a  fire sprinkler will accidentally discharge due to a manufacturing defect are about 1 in 16 million.. Overall, fire sprinkler accidents are less likely and less severe than accidents involving home plumbing systems..

 :Q  Won’t fire sprinklers look out of place in my  beautiful new home?

 :A  Not at all.. RAPID RESPONSE sprinklers come in a wide range of colors and styles, ensuring they blend aesthetically with any home décor.. Plus, they’re small and unobtrusive..

 :Q  How much can I expect to spend on a RAPID RESPONSE sprinkler system?

 :A  Installing a fire sprinkler costs about the same as a flooring upgrade, and can save you up to 15% on your homeowner’s insurance premium..

 :Q  Does a home fire sprinkler system require  a lot of maintenance?

 :A  No, after installation, nothing more than a simple once a year system testing is recommended.. 

A Typical RAPID RESPONSE Residential Fire Sprinkler System

Frequently Asked Questions

J

IH

G

F

E

D

C

B

A

A: Main Water Control Valve

B:  Water Meter

C: “T” Connection  to Water Main

D: Backflow Valve

E:  Water Supply to  Sprinkler System

 F: Control Valve for   Plumbing System

 G: Flow Switch (Optional)

 H:  Water Supply to  Plumbing System

  I:  Test and Drain Assembly

 J: Pressure Gauge

Your system may contain different components than the one pictured.

The water meter (B) may also be located outside.

www.tyco-rapidresponse.com

Copyright © 2014-2015  Tyco Fire Products LP.. All rights reserved..All trademarks and registered trademarks are the property of their respective owners.. 

WORLDWIDE HEADQUARTERSTyco Fire Protection Products, 1400 Pennbrook Parkway, Lansdale, PA 19446,

Tel: +1 215-362-0700,

www.tyco-fire.com

UNITED KINGDOMTyco Fire Protection Products Tyco Park, Grimshaw Lane Manchester M40 2WL

Tel: +44 (0)161 259 4000

[email protected]

EUROPE, MIDDLE EAST & AFRICA Tyco Fire Protection Products Kopersteden 1, P.O. Box 198, 7500 AD Enschede, The Netherlands,

Tel. +31 (0)53-428-4444

www.tfppemea.com

ASIA PACIFICTyco Fire Protection Products, 2 Serangoon North Avenue 5, #07-01, Singapore 554911

Tel. +65-6577-4360,

www.tyco-fire.com