High precision air conditioners are ideal for applications where high sensible cooling and close control of temperature and humidity are required. s-MEXT takes advantage of more than 50 years experience of the RC brand within the IT Cooling market, coupled with Mitsubishi Electric renowned quality standards. The split cooling package consists of the indoor s-MEXT high precision air conditioner connected to a Mr Slim Power Inverter outdoor unit. The result is a full inverter split system, designed according to the best quality standards and dedicated to the most reliable IT environments. Key Features High Efficiency - full Mitsubishi Electric inverter technology and EC plug fans Small footprint Pipe runs up to 100m Trusted Mr Slim Power Inverter technology Available in Upflow [over] and Downflow [under] variants s-MEXT DX Close Control Units IT Cooling Product Information IT COOLING

Upload: others

Post on 12-Nov-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Product Information IT Cooling Close Control Units s-MEXT DX

High precision air conditioners are ideal for applications where high sensiblecooling and close control of temperature and humidity are required.

s-MEXT takes advantage of more than 50 years experience of the RC brand within the IT Cooling market, coupledwith Mitsubishi Electric renowned quality standards. The split cooling package consists of the indoor s-MEXT highprecision air conditioner connected to a Mr Slim Power Inverter outdoor unit. The result is a full inverter split system,designed according to the best quality standards and dedicated to the most reliable IT environments.

Key Features

High Efficiency - full Mitsubishi Electric inverter technology and EC plug fans

Small footprint

Pipe runs up to 100m

Trusted Mr Slim Power Inverter technology

Available in Upflow [over] and Downflow [under] variants

s-MEXT DX

Close Control UnitsIT Cooling

Product Information

IT  COOLING

Page 2: Product Information IT Cooling Close Control Units s-MEXT DX

COOLING CAPACITY (kW)

SHR *1

SYSTEM EER

EC SUPPLY FAN (no.)

AIRFLOW (m³/h)

NOMINAL EXTERNAL STATIC PRESSURE (Pa)

MAX EXTERNAL STATIC PRESSURE (Pa)

POWER INPUT (kW) *2

ABSORBED CURRENT (A)

STARTING CURRENT (A)

PLATE CURRENT (A)

ELECTRICAL PANEL

SOUND LEVEL [ISO 3744] (dB(A)) *3

AIR FILTERS (no.)

REFRIGERANT CIRCUITS (no.)

POWER SUPPLY (V / Ph / Hz)

DIMENSIONS (mm)

NET WEIGHT (kg)

CONNECTIONS

Total

Sensible

Nominal (27°C - 47% RH)

Power Input (kW)

Pressure Level

Power Level

Extended filtering surface (m²)

Efficiency [ISO EN 16890] (COARSE)

Width

Depth

Height

Upflow

Downflow

Refrigerant pipes diameter - Gas (Ø Inch)

Refrigerant pipes diameter - Liquid (Ø Inch)

Condensate (Ømm) *4

Power Supply wiring Cable (no. x mm²) *5

6.79

6.28

0.92

3.92

1

2,000

20

200

0.21

0.93

0.5

2.3

0.14

53

69

1

0.68

60%

1

230 / 1 / 50

600

500

1,980

103

103

5/8"

3/8"

19

3G1.5

s-MEXT DX

006 S F1

CRAC UNITS (Computer Room Air Conditioning)

10.1

9

0.89

3.98

1

2,500

20

25

0.37

1.64

0.5

2.3

0.14

57

73

1

0.68

60%

1

230 / 1 / 50

600

500

1,980

115

115

5/8"

3/8"

19

3G1.5

s-MEXT DX

009 S F1

11.9

10.3

0.87

2.97

1

2,800

20

45

0.52

3.23

0.5

3.15

0.14

61

77

1

0.68

60%

1

230 / 1 / 50

600

500

1,980

115

115

5/8"

3/8"

19

3G1.5

s-MEXT DX

013 S F1

22.5

19.5

0.87

2.87

2

5,000

20

25

0.74

3.28

0.5

4.6

0.14

60

76

2

1.05

60%

1

230 / 1 / 50

1,000

500

1,980

185

185

1"

1/2"

19

3G1.5

s-MEXT DX

022 S F2

38.8

34

0.88

3.15

1

8,800

20

125

1.43

2.2

0.5

4.2

0.14

63

79

4

1.76

60%

2

400 / 3 / 50+N

1,000

890

1,980

297

297

1"

3/8"

19

4G1.5

s-MEXT DX

038 D F3

42.4

37.5

0.88

2.59

1

10,000

20

25

2.1

3.22

0.5

4.2

0.14

67

83

4

1.76

60%

2

400 / 3 / 50+N

1,000

890

1,980

297

297

1"

1/2"

19

4G1.5

s-MEXT DX

044 D F3

Notes. The cooling capacity does not consider the supply fan motor thermal load.

*1 SHR = Sensible cooling capacity / Total cooling capacity. *2 Corresponding to the nominal ESP=20Pa. *3 Sound pressure level on air return at 1m. *4 Rubber pipe – referred to internal diameter. *5 Minimum section.

*6 For 75 to 100m please concult the service handbook. *7 Optional air protection guide is required for tempertures below -5°C. These units contain <HFC R410A [GWP100 2088]> fluorinated greenhouse gas.

s-MEXT DX

Close Control UnitsIT Cooling

Product Information

015 015

UNITED KINGDOM Mitsubishi Electric Europe Living Environment Systems Division

Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England General Enquiries Telephone: 01707 282880 Fax: 01707 278881

IRELAND Mitsubishi Electric Europe Westgate Business Park, Ballymount, Dublin 24, Ireland

Telephone: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531)

Telephone: 01707 282880email: [email protected]

web: les.mitsubishielectric.co.uk

Note: The fuse rating is for guidance only. Please refer to the relevant databook for detailed specification. It is the responsibility of a qualified electrician/electrical engineer to select the correct cable size and fuse rating based on current regulationand site specific conditions. Mitsubishi Electric’s air conditioning equipment and heat pump systems contain a fluorinated greenhouse gas, R410A (GWP:2088), R32 (GWP:675), R407C (GWP:1774) or R134a (GWP:1430). *These GWPvalues are based on Regulation (EU) No 517/2014 from IPCC 4th edition. In case of Regulation (EU) No.626/2011 from IPCC 3rd edition, these are as follows. R410A (GWP:1975), R32 (GWP: 550), R407C (GWP:1650) or R134a (GWP:1300).

Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2019. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation intechnical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations,drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request.Third-party product and brand names may be trademarks or registered trademarks of their respective owners.

Effective as of January 2019

SOUND  PRESSURE  LEVEL (dB(A))

WEIGHT (kg)

DIMENSIONS (mm)

ELECTRICAL  SUPPLY

PHASE

OUTDOOR POWER  INPUT (kW)

STARTING  CURRENT (A)

MAX RUNNING CURRENT (A)

FUSE RATING (BS88) - HRC (A)

MAINS CABLE

MAX PIPE LENGTH (m)

MAX HEIGHT DIFFERENCE (m)

CHARGE REFRIGERANT (kg)

MAX ADDITIONAL REFRIGERANT (kg) *6

GUARANTEED OPERATING RANGE (°C)

Cooling

Width x Depth x Height

Cooling (nominal)

Cooling

No. CORES

R410A - 30m

R410A

Max Temp

Min Temp *7

47

70

950 x 330 + 30 x 943

220-240v, 50Hz

Single

1.53

5

19

25

3

40

30

3.5

1.2

46

-15

PUHZ-ZRP60VHA2OUTDOOR UNITS

49

116

1050 x 330 + 40 x 1338

220-240v, 50Hz

Single

2.17

12

26.5

32

3

75

30

5

2.4

46

-15

PUHZ-ZRP100VKA3

50

125

1050 x 330 + 40 x 1338

380-415v, 50Hz

Three

3.49

4

9.45

16

5

75

30

5

2.4

46

-15

PUHZ-ZRP125YKA3

59

135

1050 x 330+40 x 1338

380-415v, 50Hz

Three

7.11

5

21

32

5

100

30

7.7

4.80 (75m)

46

-15

PUHZ-ZRP250YKA3

59

135

1050 x 330+40 x 1338

380-415v, 50Hz

Three

5.44

5

19

32

5

100

30

7.1

3.60 (75m)

46

-15

2 x PUHZ-ZRP200YKA3

59

135

1050 x 330+40 x 1338

380-415v, 50Hz

Three

7.11

5

21

32

5

100

30

7.7

4.80 (75m)

46

-15

2 x PUHZ-ZRP250YKA3