Level measurement Radar VEGAPULS 61 VEGAPULS 62 VEGAPULS 63 VEGAPULS 65 VEGAPULS 66 Product Information

Upload: others

Post on 26-Jun-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Level measurementRadar

VEGAPULS 61VEGAPULS 62VEGAPULS 63VEGAPULS 65VEGAPULS 66

Product Information

Page 2: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Contents

2 Radar – Level measurement

Contents

1 Application, function, configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Type overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Electrical connection

4.1 General requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134.2 Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134.3 Connection cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134.4 Cable screening and grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134.5 Wiring plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

5 Operation5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155.2 Adjustment with the indicating and adjustment module PLICSCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . 155.3 Adjustment with PACTware™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155.4 Adjustment with other adjustment programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

6 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 Product code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

31486-EN-070307

Page 3: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

1 Application, function, configuration

Extremely short microwave pulses with low emitted power aretransmitted by the antenna system to the measured product, re-flected by the product surface and received by the antenna sys-tem. Radar waves travel at the speed of light. The time fromemission to reception of the signals is proportional to the levelin thevessel.Aspecial timestretchingprocedureensures reliableand precise measurement of the extremely short transmissionperiods.The latest microprocessor technology and the proven softwareECHOFOX select the level echo from among a large number offalse echoes and measure it precisely.By simply entering the vessel dimensions, the sensor can bemade to indicate a level-proportional signal. The product levelmust not be varied during adjustment.

Unaffected by temperature and pressureThe propagation of microwaves is practically unaffected by theambient temperature and pressure. Hence these radar sensorsare ideal for use under extremely difficult process conditions.Pressures from vacuum up to 160 bar (2320 psi) and temper-atures from -40 … +400 °C (-40 … +752 °F) are no problem forradar measurement.

Unaffected by product propertiesFluctuations in product composition or even complete productchanges do not influence the measuring result. A fresh adjust-ment is not necessary.

Frequency ranges for all applicationsVEGA radar sensors are available in two different frequencyranges and can thus be implemented in a wide variety of appli-cations.K-band instrumentswork in a frequency range over 20GHz. Thisenables theuse of very small antennasand respectively compactprocess fittings. Due to strong signal focussing, the measuringsystem achieves very high accuracy.C-band instrumentsare characterisedby low frequenciesaround6 GHz. Thus, in most cases, buildup and dirt on the anntennasystemor foamon the product surfacedo not affect themeasure-ment.

Functional safety (SIL)VEGAPULS 61, 62, 63, 65 and 66 radar sensors can be used forapplications thatmeet the special requirements of safety technol-ogy. In single channel architecture this is possible up to SIL2, indouble channel, diversitary redundant architecture up to SIL3.

Instrument selectionVEGAPULS series 60 radar sensors are optimised for each re-spectiveapplicationarea.Theyoperate in twodifferent frequencyranges (C or K band technology) and are available with differentantennas. These factors determine the instrument-specific beam

angles, measuring ranges and measuring characteristics. Theselection of the most suitable radar sensor depends on the re-spective application. The type overview on the following pagesprovides a good initial survey. For a detailed selection you canuse the "Finder" and "Configurator" on ourwebsite or contact oneof our agencies.

1.1 Application examplesAcid tank

Fig. 1: Level measurement in an acid tank with VEGAPULS 61

A non-contactmeasuringprinciple is particularly suitable for levelmeasurement in acid tanks.VEGAPULS 61 is characterised by a small process fitting and aPVDF encapsulated antenna. The sensor is insensitive to tem-perature fluctuations and gas phases.

Application, function, configuration

Radar – Level measurement 3

3148

6-EN-

0703

07

Page 4: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Bitumen tank

Fig. 2: Level measurement in a bitumen tank with VEGAPULS 62

Bitumen accrues during the crude oil distillation and is stored attemperatures around 200 °C (392 °F).The non-contact radarmeasuring principle is particularly suitablefor level measurement under high temperatures and in outgasingproducts. Due to its temperature adapter, the VEGAPULS 62radar sensor is suitable for temperatures up to 200 °C (392 °F).

Sugar evaporator

Fig. 3: Level measurement in a sugar evaporator with VEGAPULS 63

The VEGAPULS 63 radar sensor is particularly suitable for levelmeasurement in sugar evaporators. The PTFE encapsulatedhorn antenna protects against contamination and gumming upby the juice. The instrument is overpressure and vacuum resist-ant, even against pressure or vacuum shocks.

Storage tank for hazardouswaste

Fig. 4: Level measurement in a storage tank with VEGAPULS 65

The VEGAPULS 65 radar sensor is the ideal measuring systemfor level measurement of lacquers, colours and dilutions. Unaf-fected by process conditions such as outgasing andmovementsof the agitator, the radar measurement delivers exact measuringresult.

Storage tower

Fig. 5: Level measurement in a storage tower with VEGAPULS 65

Paper suspension is stored in large storage towers. The VEGA-PULS 66 radar sensor with a DN 250 flange and large horn an-tenna is well suited for level measurement in the upper part of thetowers.Thesensordelivers reliablemeasuredvalues,unaffectedby process conditions such as temperature, steam and high pulpdensities.

Application, function, configuration

4 Radar – Level measurement

31486-EN-070307

Page 5: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Ammonia vessel

Fig. 6: Level measurement in an ammonia vessel with VEGAPULS 66

The optimumsolution for level measurement in an ammonia ves-sel, is the VEGAPULS 66 radar sensor in standpipe version.It operates with low frequencies so that its microwave are onlyslightly damped. The strandpipe improves the reflective proper-ties. The signal coupling in the standpipe is completely diffusion-tight through the ceramic antenna system.

Information:Continuative documentation:l Operating instructions manual "VEGAPULS 61"l Operating instructions manual "VEGAPULS 62"l Operating instructions manual "VEGAPULS 63"l Operating instructions manual "VEGAPULS 65"l Operating instructions manual "VEGAPULS 66"l Supplementary instructions manual "Functional

safety VEGAPULS series 60 - 4… 20mA/HART"

Application, function, configuration

Radar – Level measurement 5

3148

6-EN-

0703

07

Page 6: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

2 Type overview

VEGAPULS 61 VEGAPULS 62 VEGAPULS 63

Applications: corrosive liquids in small vesselsunder easy process conditions

virtually all products in storage tanksand process vessels under the mostdifficult process conditions, hightemperatures and pressures

very corrosive liquids in storage tanksand process vessels, particularly underhygienic process conditions

Measuring range: depending on the antenna up to 10m(32.808 ft)or up to 20m (65.616 ft)

up to 30m (98.425 ft) up to 20m (65.617 ft)

Antenna,material: completely PVDF encapsulated Horn antenna or with mounted½"standpipe, 316L

completely PTFE, PFA or PVDFencapsulated

Process fitting,material: Thread G1½ A, PVDF, PP or flangePP

Thread G1½ A or flange, 316L,Hastelloy

Flange or hygienic fitting 316L

Process temperature: -40… +80 °C (-40… +176 °F) -40… +200 °C (-40… +392 °F) -40… +150 °C (-40… +302 °F)Process pressure: -1 … 3 bar/-100… 300 kPa

(-14.5… 43.5 psi)-1 … 40 bar/-100… 4000 kPa(-14.5… 580 psi)

-1 … 16 bar/-100… 1600 kPa(-14.5… 232 psi)

Measuring accuracy: ±5mm ±3mm ±3mmFrequency range: K-band K-band K-bandSignal output: 4… 20mA/HART in two-wire, four-

wire, Profibus PA, FoundationFieldbus technology

4… 20mA/HART in two-wire, four-wire, Profibus PA, FoundationFieldbus technology

4… 20mA/HART in two-wire, four-wire,Profibus PA, Foundation Fieldbustechnology

Adjustment/Indication: PLICSCOM PLICSCOM PLICSCOMRemote adjustment/indication:

VEGADIS 61 VEGADIS 61 VEGADIS 61

Functional safety: up to SIL3 up to SIL3 up to SIL3

Type overview

6 Radar – Level measurement

31486-EN-070307

Page 7: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 65 VEGAPULS 66

Applications: corrosive liquids, vessels with small process fitting undereasy process conditions

liquids and solids, large storage tanks as well as processvessels under difficult or extreme process conditions,highest temperatures and pressures

Measuring range: up to 30m (98.425 ft) up to 35m (114.829 ft)Antenna,material: completely PVDF- or PTFE encapsulated, PFA plated Horn antenna or with mounted 2" standpipe, 316LProcess fitting,material: G1½ A or flange, PVDF, 316L Flange 316L, HastelloyProcess temperature: -40… +150 °C (-40… +302 °F) -40… +400 °C (-40… +752 °F)Process pressure: -1 … 16 bar/-100… 1600 kPa (-14.5… 232 psi) -1 … 160 bar/-100… 16000 kPa (-14.5 … 2320 psi)Measuring accuracy: ±10mm ±10mmFrequency range: C-band C-bandSignal output: 4… 20mA/HART in two-wire, four-wire, Profibus PA,

Foundation Fieldbus technology4… 20mA/HART in two-wire, four-wire, Profibus PA,Foundation Fieldbus technology

Adjustment/Indication: PLICSCOM PLICSCOMRemote adjustment/indication:

VEGADIS 61 VEGADIS 61

Functional safety: up to SIL3 up to SIL3

Type overview

Radar – Level measurement 7

3148

6-EN-

0703

07

Page 8: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Indicating and adjustmentmodule

PLICSCOM

Housing

Plastic Stainless steel Aluminium Aluminium (doublechamber)

Electronics

4 … 20 mA/HART 4 … 20 mA/HARTfour-wire

Profibus PA Foundation Field-bus

Process fitting

Thread Flange Sanitary

Sensors

Horn antenna Encapsulated an-tenna

Rod antenna

Approvals

SIL FM CSA

Type overview

8 Radar – Level measurement

31486-EN-070307

Page 9: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

3 Mounting instructions

Installation positionSelect an installation position you can easily reach for mountingand connecting as well as later retrofitting of an indicating andadjustmentmodule. The housing can be rotated by 330° withoutthe use of any tools.You canalso install the indicating andadjust-ment module in four different positions (each displaced by 90°).Measuring rangeFor the flange versions, the lower flange side is the referenceplane for the measuring range, for threaded versions, the sealsurface of the thread.

1 32

100%

0%

4

Fig. 7: Measuring range (operating range),max.measuring distance and referenceplane1 full2 empty (max.measuring distance)3 Measuring range4 Reference plane

PressureThe process fitting must be sealed if there is gauge or low pres-sure in the vessel. Before use, check if the seal material is resist-ant against the measured product. The max. permissible pres-sure is stated in chapter "Technical data" or on the type label ofthe sensor.Horn and parabolic antennaThe illustrations in the mounting instructions show a VEGAPULSwith horn antenna. The mounting instructions also apply to theversion with parabolic antenna.Installation positionMount VEGAPULS in a distance of at least 200 mm from thevessel wall. An ideal installation location is at half vessel radius.If the sensor is mounted in the center of round or arched vesseltops,multiple echoes can be cause which can be gated out by arespective adjustment.If this distancecannotbemaintained, a false echo storageshouldbe carried out during setup. This applies particularly if buildup onthe vessel wall is expected. In such case,we recommendrepeat-ing the false echo storage later on with existing buildup.

1 2

> 200 mm

Fig. 8: Mounting on round vessel tops VEGAPULS 61, 62, 631 Reference plane2 Vessel center or symmetry axis

12

> 500 mm

Fig. 9: Mounting on round vessel tops VEGAPULS 65, 661 Reference plane2 Vessel center or symmetry axis

In vessels with conical bottom it can be advantageous to mountthe sensor in the center of the vessel, as measurement is thenpossible down to the lowest point of the vessel bottom.

Fig. 10: Vessel with conical bottom

SocketSocket pieces should be dimensionedsuch that the antennaendprotrudes at least 10mm (0.4 in) out of the socket.

Mounting instructions

Radar – Level measurement 9

3148

6-EN-

0703

07

Page 10: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

ca. 1

0 m

m

Fig. 11: Recommended socket mounting

If the reflectivepropertiesof themediumare good, youcanmountVEGAPULS on sockets higher than the antenna length. You willfind recommended values for socket heights in the following illus-tration. The socket end should be smooth and burr-free, if possi-ble also rounded.

d

hm

ax. d

1½"50 mm/2"80 mm/3"100 mm/4"150 mm/6"

200 mm250 mm300 mm500 mm800 mm

h max.

Fig. 12: Deviating socket dimensions

Inflowing mediumDo notmount the instruments in or above the filling stream.Makesure that you detect the product surface and not the inflowingproduct.

Fig. 13: Inflowing medium

Sensor orientationIn liquids, direct the sensor as perpendicular as possible to theproduct surface to achieve optimummeasurement results.

Fig. 14: Orientation in liquids

Vessel installationsThe radar sensor should be installed at a location where no in-stallations cross the radar signals.Vessel installations such as, for example, ladders, limit switches,heatingspirals, struts,etc. cancause falseechoes thatget super-imposed on the useful echo. Make sure when planning yourmeasuring site that the radar sensor has a "clear view" to themeasured product.If there are existing vessel installations, a false echo storageshould be carried out during setup.If large vessel installationssuch as struts or supports cause falseechoes, these can be attenuated through supplementary meas-ures. Small, inclined sheet metal baffles above the installationsscatter the radar signals andprevent direct interfering reflections.

Fig. 15: Cover smooth profiles with deflectors

AgitatorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motion. This ensures that theinterferingreflections from theagitatorsare savedwith thebladesin different positions.

Fig. 16: Agitators

Foam generationThrough the action of filling, stirring and other processes in thevessel, dense foams which considerably damp the emitted sig-nals may form on the product surface.

Mounting instructions

10 Radar – Level measurement

31486-EN-070307

Page 11: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

If foams lead to measurement errors, you should use the biggestpossible radar antennas or low frequency radar sensors, e.g.VEGAPULS 65, 66 (C-band).VEGAFLEX sensors with guided microwaves are not influencedby foamgeneration and are particularly suitable for such applica-tions.Standpipe antennaBy the use of a standpipe antenna, influence of turbulences andvessel installations such as e.g. caused by heating spirals oragitators is excluded.The standpipe antenna is also suitable for vessels with foamgeneration or for measurement of products with low dielectricvalues (DK > 1.6).Standpipe antennas must extend alls the way down to the re-quested min. level, as measurement is only possible within thetube. If a goodmixingof theproduct is important, youshouldusearadar sensor with perforated surge pipe.Adhesive productsMeasurement in a standpipe is not recommended for very adhe-sive products.TurbulencesIf turbulences or heavy product movements are caused in thevessel, longstandpipeantennasshouldbe fastened to the vesselwall.Inflowing mediumDo not mount the instruments in or above the filling stream.

Fig. 17: Inflowing liquid

Measurement in the standpipe (surge or bypass tube)By using a standpipe, the influence of vessel installations andturbulence can be excluded. Under these prerequisites, themeasurement of products with low dielectric values (from DKvalue 1.6) is possible.

Note:Measurement in a standpipe is not recommended forvery adhesive products.

Surge or bypass tubes must extend all the way down to the re-quested min. level, as measurement is only possible within thetube.

Makesureyouprovide thenecessaryupperventhole in theSurgepipe. The hole must be aligned so that it and the polarisationmarking on the sensor are in the same plane (see illustration:"Pipe antenna system in a tank").

max.

min.

2

1

Fig.18: Pipeantennasystemina tank.Theventhole in thesurgepipemustbe inoneplane with the polarisationmarking on the sensor.1 Marking of the polarisation direction2 Vent holde max. ø 5mm (0.2 in)

If possible, theantennadiameterof thesensorshouldcorrespondto the inner diameter of the tube.WithVEGAPULS this is approx.40 mm (1.575 in). The sensor can be used with tube diametersbetween 40… 80mm (1.575… 3.15 in).Asanalternativeto thesurgepipe in thevessel,apipesystemcanbe mounted outside of the vessel as a Bypass tube. For setup,select the function "Bypass tube".Align the sensor in suchaway that thepolarisationmarkingon theprocess fitting is in the same plane as the tube holes or the tubeconnection openings (see illustration: "VEGAPULS in a bypasstube").

100%

0%

1

> 30

0 m

m

Fig. 19: VEGAPULS in a bypass tube. The polarisation marking on the processfitting must be in one plane to the tube holes or the tube connection openings.1 Marking of the polarisation direction

When the sensor is mounted on a bypass tube, the distance fromVEGAPULS to the upper tube connection should be approx.300mm (11.8 in) or more. In case of extremely rough tube innerwalls, you should use an inserted tube (tube in tube) or a radarsensor with tube antenna.

Mounting instructions

Radar – Level measurement 11

3148

6-EN-

0703

07

Page 12: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Information:WithVEGAPULS in flangeversion, the polarisation levelis always in the center between two flange holes.

Flow measurementThe short examples should just give introductory information forthe flowmeasurement. Planning information is available from theflume manufacturers and in special literature.Note the following facts for the Measuring wall with rectangularflume:l Installation of the sensor on the headwater sidel Installation in the center of the flume and vertical to the liquid

surfacel Distance to the overfall orificel Distance orifice opening above groundl Min. distance of the orifice opening to bottom waterl Min. distance of the sensor to max. storage level

3 ... 4 hmax

≥ 50 mm90°

2 3

1

h max

d min

≥ 2

mm

x h m

ax

90°

4

Fig. 20: Flowmeasurementwith rectangular flume: d =min. distance of the sensor;hmax. = max. filling of the rectangular flume1 Overfall orifice (side view)2 Headwater3 Bottom water4 Overfall orifice (view from bottom water)

Note the following facts for the Khafagi-Venturi flume:l Installation of the sensor at the inlet sidel Installation in the center of the flume and vertical to the liquid

surfacel Distance to the Venturi flumel Min. distance of the sensor to max. storage level

2

3 ... 4 x hmax

90°

hmax

d

1 B

Fig. 21: Flow measurement with Khafagi-Venturi flume: d = Min. distance of thesensor; hmax. =max. filling of the flume; B = biggest throat of the flume1 Position sensor2 Venturi flume

Gauge measurementThe illustration shows an example for a gauge measurement.In general, the following points must be observed:l Installation of the sensor in a protected areal Installation vertical to the liquid surface

Fig. 22: Gauge measurement

Mounting instructions

12 Radar – Level measurement

31486-EN-070307

Page 13: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

4 Electrical connection

4.1 General requirementsThe supply voltage range can differ depending on the instrumentversion. You can find exact specifications in chapter "Technicaldata".Take note of country-specific installation standards (e.g. theVDEregulations in Germany) as well as prevailing safety regulationsand accident prevention rules.

In hazardous areas you should take note of the appro-priate regulations, conformity and type approval certifi-cates of the sensors and power supply units.

4.2 Voltage supply4… 20mA/HART two-wireThe VEGA power supply units VEGATRENN 149AEx, VEGAS-TAB 690, VEGADIS 371 as well as VEGAMET signal condition-ing instruments are suitable for power supply.When one of theseinstruments is used, a reliable separation of the supply circuitsfrom the mains circuits according to DIN VDE 0106 part 101 isensured for VEGAPULS.4… 20mA/HART four-wirePower supply and current output are carried on two separateconnection cables.The standard version can be operated with an earth-connectedcurrent output, the Exd version must be operated with a floatingoutput.The instrument is designed in protection class I. To maintain thisprotection class, it is absolutely necessary that the ground con-ductor be connected to the internal ground conductor terminal.Profibus PAPower is supplied by a Profibus DP/PA segment coupler or aVEGALOG 571 EP input card.

Fig. 23: Integrationof instruments in aProfibusPA system via segment couplerDP/PA or data recording systems with Profibus PA input card

Foundation FieldbusPower supply via the H1 Fieldbus cable.

4.3 Connection cableGeneralThe sensors are connected with standard cable without screen.Anoutercablediameterof5…9mmensures theseal effectof thecable entry.4… 20mA/HART four-wireFor power supply, an approved installation cable with PE con-ductor is necessary.4… 20mA/HART two-wire and four-wireIf electromagnetic interference is expected which is above thetest values of EN 61326 for industrial areas, screened cableshould be used. In HART multidrop mode the use of screenedcable is generally recommended.Profibus PA, Foundation FieldbusThe installation must be carried out according to the appropriatebus specification. VEGAPULS is connected respectively withscreened cable according to the bus specification. Power supplyand digital bus signal are transmitted via the same two-wire con-nection cable.Make sure that the bus is terminated via appropri-ate terminating resistors.VEGAPULS are optionally available with usual plug connectors(see "Technical data").

In Ex applications, the corresponding installation regu-lations must be noted for the connection cable.

4.4 Cable screening and groundingIf screened cable is necessary, the cable screen must be con-nected on both ends to ground potential. If potential equalisationcurrents are expected, the connection on the evaluation sidemust be made via a ceramic capacitor (e.g. 1 nF, 1500 V).Profibus PA, Foundation FieldbusIn systems with potential separation, the cable screen is con-nected directly to ground potential on the power supply unit, inthe connection box and directly on the sensor.In systems without potential equalisation, connect the cablescreen directly to ground potential only at the power supply unitand at the sensor - do not connect to ground potential in theconnection box or T-distributor.

Electrical connection

Radar – Level measurement 13

3148

6-EN-

0703

07

Page 14: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

4.5 Wiring planSingle chamber housing

I2C

Display

1

1 2 5 6 7 8

Fig. 24: ConnectionHART two-wire, Profibus PA, Foundation Fieldbus1 Power supply and signal output

Double chamber housing - two-wire

I2C

1

1 2

Fig. 25: ConnectionHART two-wire, Profibus PA, Foundation Fieldbus1 Power supply and signal output

Double chamber housing - 4… 20mA/HART four-wire

4 ... 20 mA

PE

/ L/ N

L1 N GND

1 2

1 2 3 4

4...20mA IS

Fig. 26: Connection 4… 20mA/HART four-wire1 Voltage supply2 Signal output

Electrical connection

14 Radar – Level measurement

31486-EN-070307

Page 15: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

5 Operation

5.1 OverviewVEGAPULS can be adjusted with the following adjustment me-dia:l with indicating and adjustment modulel anadjustmentsoftwareaccording toFDT/DTM standard,e.g.

PACTware™ and PC

and, depending on the signal output, also with:l a HART handheld (4… 20mA/HART)l the adjustment program AMS (4 … 20 mA/HART and Foun-

dation Fieldbus)l the adjustment program PDM (Profibus PA)l a configuration tool (Foundation Fieldbus)

The entered parameters are generally saved in VEGAPULS, op-tionally also in PLICSCOM or in the adjustment program.

5.2 Adjustment with the indicating and adjust-ment module PLICSCOM

Setup and indicationPLICSCOM is a pluggable indication and adjustment module forplics® sensors. It can be placed in four different positions on theinstrument (each displaced by 90°). Indication and adjustmentare made via four keys and a clear, graphic-capable dot matrixindication. The adjustment menu with language selection isclearly structured and enables easy setup. After setup,PLICSCOMservesas indicating instrument: throughthescrewedcover with glass insert, measured values can be read directly inthe requested unit and presentation style.The integratedbackground lightingof thedisplaycanbeswitchedvia the adjustment menu.1)

PLICSCOM adjustment

1.1

2

3

1

Fig. 27: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysKey functions

l [OK] key:- move to the menu overview

- confirm selected menu- edit parameter- save value

l [->] key to select:- menu change- list entry- Select editing position

l [+] key:- Change value of a parameter

l [ESC] key:- interrupt input- jump to the next higher menu

5.3 Adjustment with PACTware™PACTware™/DTMIndependent of the signal output 4… 20mA/HART, Profibus PAor Foundation Fieldbus, the VEGAPULS sensors can be oper-ated directly on the instrument via PACTware™. An instrumentdriver for the respective VEGAPULS is necessary for the adjust-ment with PACTware™. All currently available VEGA DTMs arecomposed as DTMCollection with the current PACTware™ ver-sion on a CD. They are available for a protective fee from ourrespective VEGA agency. In addition, this DTM Collection incl.PACTware™ canbe downloadedfree-of-charge in the basic ver-sion via the Internet.To use the entire range of functions of a DTM, incl. project doc-umentation, a DTM licence is required for that particular instru-ment family. This licence can be bought from the VEGA agencyserving you.Connecting the PC directly to the sensor

~

=

Power supply

VEGACONNECT 3

PACTware /TM

>PA<

2

3 1

Fig. 28: Connection directly to the sensor1 RS232 connection2 VEGAPULS3 I²C adapter cable for VEGACONNECT 3ToadjustwithPACTware™,aVEGACONNECT3with I²Cadapt-er cable (art. no. 2.27323) as well as a power supply unit is nec-essary in addition to the PC and the suitable VEGA-DTM.

Operation

Radar – Level measurement 15

1) For instruments with national approvals such as e.g. according to FM and CSA only available at a later date.3148

6-EN-

0703

07

Page 16: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Connecting the PC to the signal cable (4… 20mA/HART)

2

3

1

4~

=

Power supply

VEGACONNECT 3

PACTware /TM

Fig. 29: Connecting the PC to the signal cable1 RS232 connection2 VEGAPULS3 HART adapter cable for VEGACONNECT 34 HART resistance 250 OhmTo adjust with PACTware™, a VEGACONNECT 3 with HARTadapter cable (art. no. 2.25397) as well as a power supply unitand aHART resistor with approx. 250Ohm is required in additionto the PC and the suitable VEGA DTM.

Note:With power supply units with integrated HART resist-ance (internal resistance approx. 250 Ohm), an addi-tional external resistance is not necessary. This applies,e.g. to the VEGA instruments VEGATRENN 149A, VE-GADIS 371, VEGAMET 381. Also standard Ex separa-tors aremost of the timeequippedwith a sufficientlyhighcurrent limitation resistor. In such cases, VEGA-CONNECT 3 can be connected in parallel to the4… 20mA cable.

Connecting the PC to the signal cable (4 … 20 mA/HARTfour-wire)

2

3

1

4

5

Power supply

VEGACONNECT 3

PACTware /TM

Fig. 30: Connecting the PC to the signal cable1 RS232 connection2 VEGAPULS3 HART adapter cable for VEGACONNECT 34 HART resistance 250 Ohm5 4… 20mA processingTo adjust with PACTware™, a VEGACONNECT 3 with HARTadaptercable (art. no.2.25397) andaHART resistorwith approx.250Ohm is required in addition to the PC and the suitableVEGADTM.

5.4 Adjustment with other adjustment pro-grams

PDMFor VEGA PA sensors, device descriptions are also available asEDD for the adjustment program PDM. The device descriptionsare already implemented in the current versions ofPDM. For old-er versions of PDM they are available as a free-of-charge down-load from the Internet.AMSFor VEGA FF sensors, device descriptions are also available asDD for the adjustment program AMS™. The device descriptionsare already implemented in the current version of AMS™. Forolder versions of AMS™, a free-of-charge download is availablevia Internet.

Operation

16 Radar – Level measurement

31486-EN-070307

Page 17: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

6 Technical data

General data316L corresponds to 1.4404 or 1.4435Common dataMaterials, non-wetted parts- Housing Plastic PBT (Polyester), Alu die-casting powder-coated, 316L- Seal ring between housing and housing cover NBR (stainless steel housing), silicone (Alu/plastic housing)- Inspection window in housing cover for PLICSCOM Polycarbonate (UL-746-C listed)- Ground terminal 316Ti/316LVEGAPULS 61Materials, wetted parts- Process fitting - thread, flange PVDF, 316L, PPWeight 0.7… 3.4 kg (1.5… 7.5 lbs),depending on the process fitting and housingVEGAPULS 62Materials, wetted parts- Process fitting 316L, Hastelloy C22, Hastelloy C22 plated, Monell Alloy- Seal - process fitting 316L Klingersil C-4400- Antenna 316L, Hastelloy C22,Monell Alloy- Antenna cone PTFE (TFM 1600 PTFE), PP- seal, antenna system FKM (Viton), Kalrez 2035, 6230 (FDA), 6375- Standpipe 316L, Hastelloy C22Weight with horn antenna- Process fitting - thread 2… 2.8 kg (4.4… 6.2 lbs), depending on thread size and housing- Process fitting - flange 4.2 … 15.4 kg (9.3 … 34 lbs), depending on flange size and housingWeight with parabolic antenna- Process fitting - thread 2.8 … 3.6 kg (6.2 … 13.7 lbs), depending on thread size and housing- Process fitting - flange 5… 16.2 kg (11… 35.7 lbs), depending on the flange size and housingStandpipe length up to 5.85 mVEGAPULS 63Materials, wetted parts- Process fitting 316L- Antenna PTFE (TFM 1600)Weight- Tri-Clamp, bolting 3.5 … 6.0 kg (7.7 … 13.2 lbs), depending on size and housing- Flanges 4.2 … 15.4 kg (9.3 … 34 lbs), depending on flange size and housingVEGAPULS 65Materials, wetted parts- Process fitting - thread PVDF, 316L- Seal - thread PVDF FKM (Viton)- Process fitting - flange Flange plating PTFE- Antenna for sockets 50mm (1.969 in) PVDF and PTFE- Antenna for sockets 100mm (3.937 in) and 250mm (9.843 in) PTFEWeight- Process fitting - thread 2… 2.8 kg (4.4… 6.2 lbs), depending on thread size and housing- Process fitting - flange 4.2 … 15.4 kg (9.3 … 34 lbs), depending on flange size and housingVEGAPULS 66Materials, wetted parts- Process fitting 316L, Hastelloy C22 plated- Antenna 316L, Hastelloy C22- Antenna cone PTFE (TFM 1600), ceramic (99.9 % AL2O3)- seal, antenna system FKM (Viton), Kalrez 6375, FEP FKM (Viton) coated, EPDM (FDA-ap-

proved), graphite- Standpipe 316L, Hastelloy C22Weight 6.3… 136 kg (13.9… 300 lbs), depending on flange size, pressure stage

and housingStandpipe length up to 5.85 m

Technical data

Radar – Level measurement 17

3148

6-EN-

0703

07

Page 18: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Output variable4… 20mA/HARTOutput signal 4… 20mA/HARTResolution 1.6 µAFailure message Current output unchanged 20.5 mA, 22 mA, <3.6 mA (adjustable)Current limitation 22mALoad- 4… 20mA/HART two-wire instrument see load diagram under Power supply- 4… 20mA/HART four-wire instrument max. 500 Ohm2)

Integration time (63% of the input variable) 0… 999 s, adjustableFulfilled NAMUR recommendations NE 43Profibus PAOutput signal digital output signal, format according to IEEE-754Sensor address 126 (default setting)Current value 10mA, ±0.5 mAIntegration time (63% of the input variable) 0… 999 s, adjustableFoundation FieldbusOutput- Signal digital output signal, Foundation Fieldbus protocol- Physical layer according to IEC 61158-2Channel Numbers- Channel 1 Primary Value- Channel 2 Secondary Value 1- Channel 3 Secondary Value 2Transmission rate 31.25 Kbit/sCurrent value 10mA, ±0.5 mAIntegration time (63% of the input variable) 0… 999 s, adjustable

Input variableCommon dataParameter distance between process fitting and product surface

VEGAPULS 61Min. distance from antenna end 50mm (2 in)3)

Recommendedmeasuring rangePVDFencapsulatedantennasystem

up to 10m (32.808 ft)

Recommended measuring range plastic horn antenna up to 20m (65.617 ft)VEGAPULS 62Min. distance from antenna end 50mm (1.969 in)Recommended measuring range depending on the diameter of the antenna horn- ø 40 mm (1.6 in) up to 10m (32.808 ft)- ø 48 mm (1.89 in) up to 15m (49.213 ft)- ø 75 mm (2.953 in), ø 95mm (3.74 in), parabolic antenna up to 30m (98.425 ft)Max.measuring range- Horn or parabolic antenna bis 35m (114.8 ft)- Standpipe version according to standpipe lengthVEGAPULS 63min. distance from flange 50mm (2 in)

Technical data

18 Radar – Level measurement

2) With inductive load ohmic share min. 25 Ohm/mH.3) In products with low dielectric value up to 50 cm (19.7 in).

31486-EN-070307

Page 19: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Recommended measuring range depending on the process fitting- Tri-Clamp 2" up to 10m (32.808 ft)- Tri-Clamp 3", 4" up to 20m (65.617 ft)- Bolting DN 50 up to 10m (32.808 ft)- Bolting DN 80 up to 20m (65.617 ft)- flange DN 50, ANSI 2" up to 10m (32.808 ft)- Flange DN 80… DN 150, ANSI 3" … 6" up to 20m (65.617 ft)VEGAPULS 65Min. distance from antenna tip 100mm (4 in)Measuring range up to 30m (98.425 ft)VEGAPULS 66Min. distance from antenna edge 100mm (4 in)Recommended measuring range 30m (98.4 ft)Max.measuring range- Horn antenna 35m (114.8 ft)- Standpipe version according to standpipe length

Accuracy (similar to DIN EN 60770-1)Reference conditions according to DIN EN 61298-1- Temperature +18… +30 °C (+64 … +86 °F)- Relative humidity 45… 75%- Air pressure 860… 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)

Deviation in characteristics and characteristics4)

Common dataAverage temperature coefficient of the zero signal (tempera-ture error)

0.06 %/10 K

Resolution, general max. 1 mmFrequency K-bandAdjustment time5) >1 s (dependent on the parameter adjustment)Received average emitted power reaching an object directly in front of the antenna- Distance 1 m 108 nW per cm² (108x10-9 W/cm²)- Distance 5 m 4.3 nW per cm² (4.3x10-9 W/cm²)VEGAPULS 61Beam angle- encapsulated antenna system at -3 dB 22°- Plastic horn antenna at -3 dB 10°Accuracy see diagram

0,5 m 10 m

10 mm

5 mm

- 5 mm

- 10 mm

Fig. 31: Accuracy VEGAPULSwith encapsulated antenna system

Technical data

Radar – Level measurement 19

4) Relating to the nominal range, incl. hysteresis and repeatability, determined according to the limit point method.5) Time to output the correct level (with max. 10 % deviation) after a sudden level change.3148

6-EN-

0703

07

Page 20: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

0,5 m 20 m

10 mm

5 mm

-5 mm

-10 mm

Fig. 32: Accuracy VEGAPULSwith plastic horn antenna

VEGAPULS 62Beam angle with horn antenna, depending on the antenna diameter- ø 40 mm (1.6 in) 22°- ø 48 mm (1.9 in) 18°- ø 75 mm (3 in) 10°- ø 95 mm (3.7 in) 8°Beam angle with parabolic antenna- ø 245mm (9.7 in) 4°Accuracy see diagram

0,5 m 30 m

10 mm

3 mm

-3 mm

-10 mm

Fig. 33: Accuracy VEGAPULS 62 with horn antenna

2,0 m 30 m

40 mm

3 mm

-3 mm

-40 mm

Fig. 34: Accuracy VEGAPULS 62 with parabolic antenna

Accuracy VEGAPULS 62 with standpipe antenna see diagram

Technical data

20 Radar – Level measurement

31486-EN-070307

Page 21: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

0,5 m 5,85 m

10 mm

3 mm

-3 mm

-10 mm

Fig. 35: Accuracy VEGAPULS 62 with standpipe antenna

VEGAPULS 63Beam angle- Tri-Clamp 2" 18°- Tri-Clamp 3", 4" 10°- Bolting DN 50 18°- Bolting DN 80 18°- flange DN 50, ANSI 2" 18°- Flange DN 80… DN 150, ANSI 3" … 6" 10°Accuracy see diagram

0,5 m 20 m

10 mm

3 mm

-3 mm

-10 mm

Fig. 36: Accuracy VEGAPULS 63

VEGAPULS 65Beam angle 24°Accuracy see diagram

1,0 m 30 m

20 mm

10 mm

-10 mm

-20 mm

Fig. 37: Accuracy VEGAPULS 65

Technical data

Radar – Level measurement 21

3148

6-EN-

0703

07

Page 22: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 66Beam angle, depending on antenna system at -3 dB- without horn antenna 38°- ø 75 mm (3 in) 38°- ø 96 mm (3.8 in) 30°- ø 145mm (5.7 in) 20°- ø 195mm (7.6 in) 17°- ø 240mm (9.4 in) 14°Accuracy with horn antenna see diagram

1,0 m 35 m

20 mm

10 mm

-10 mm

-20 mm

Fig. 38: Accuracy VEGAPULS 66 with horn antenna

Accuracy with standpipe antenna see diagram

0,5 m 5,85 m

20 mm

5 mm

-5 mm

-20 mm

Fig. 39: Accuracy VEGAPULS 66 with standpipe antenna

Ambient conditionsAmbient, storage and transport temperature- Standard version -40… +80 °C (-40… +176 °F)- Version IP 66/IP 68 1 bar with connection cable PE -20… +60 °C (-4 … +140 °F)

Process conditionsCommon dataVibration resistance mechanical vibrations with 4 g and 5 … 100 Hz6)

VEGAPULS 61Vessel pressure -1 … 3 bar/-100… 300 kPa (-14.5 … 43.5 psi)Process temperature (measured on the process fitting) -40… +80 °C (-40… +176 °F)

Technical data

22 Radar – Level measurement

6) Tested according to the regulations of German Lloyd, GL directive 2

31486-EN-070307

Page 23: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 62Process temperature (measured on the process fitting), depending on the seal of the antenna system- FKM (Viton) -40… +130 °C (-40… +266 °F)- FKM (Viton) with temperature adapter -40… +200 °C (-40… +392 °F)- Kalrez 2035, 6230 (FDA) -15… +130 °C (+5 … +266 °F)- Kalrez 2035, 6230 (FDA) with temperature adapter -15… +200 °C (+5 … +392 °F)- Kalrez 6375 -20… +130 °C (-4… +266 °F)- Kalrez 6375 with temperature adapter -20… +200 °C (-4… +392 °F)Vessel pressure horn antenna -1 … 40 bar/-100… 4000 kPa (-14.5… 580 psi)Vessel pressure parabolic antenna -1 … 6 bar/-100… 6000 kPa (-14.5 … 870 psi)VEGAPULS 63Vessel pressure with process fittings up to 2", DN 50 -1 … 16 bar/-100… 1600 kPa (-14.5… 232 psi)Vessel pressure with process fittings from 3", DN 80 -0,8… 16 bar/-80… 1600 kPa (-11.6… 232 psi)Process temperature (measured on the process fitting)- TFM-PTFE, PFA -40… +150 °C (-40… +302 °F)- TFM-PTFE, FKM (Viton) -25… +130 °C (-13… +266 °F)- TFM-PTFE, EPDM -40… +130 °C (-40… +266 °F)VEGAPULS 65Vessel pressure- Threaded part PVDF -1 … 3 bar/-100… 300 kPa (-14.5 … 43.5 psi)- Screwed part and flange 316L -1 … 16 bar/-100… 1600 kPa (-14.5… 232 psi)Process temperature (measured on the process fitting)- for sockets 50mm (2 in) and sockets 100mm (4 in) and

250mm (10 in) with PVDF screwed part-40… +130 °C (-40… +266 °F)

- other versions -40… +150 °C (-40… +302 °F)VEGAPULS 66Process temperature (measured on the process fitting depending on process seal- FKM (Viton) -40… +80 °C (-40… +176 °F)- FKM (Viton) with temperature adapter -40… +150 °C (-40… +302 °F)- Kalrez 6375 -20… +150 °C (-4… +302 °F)- graphite (antenna cone ceramic) -60… +250 °C (-76… +482 °F)- graphite (antenna cone ceramic) with temperature adapter -60… +400 °C (-76… +752 °F)Vessel pressure of the antenna cone (note nominal pressure stage of the flange!)- PTFE -1 … 40 bar/-100… 4000 kPa (-14.5… 580 psi) with PN 40- Ceramic -1 … 160 bar/-100… 16000 kPa (-14.5 … 2321 psi) with PN 160

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug7)

- Single chamber housing l 1x closing cap½ NPT, 1x blind plug½ NPTor:l 1x plug (depending on version), 1x blind stopper½ NPT

- Double chamber housing l 1x closing cap½ NPT, 1x blind stopper½ NPT, plugM12x1 for VE-GADIS 61 (optional)

or:l 1x plug (depending on version), 1x blind stopper½NPT; plugM12x1

for VEGADIS 61 (optional)Spring-loaded terminals for wire cross-section up to 2.5mm²

Indicating and adjustmentmodulePower supply and data transmission through sensor via gold-plated sliding contacts (I²C bus)Indication LC display in Dot matrixAdjustment elements 4 keys

Technical data

Radar – Level measurement 23

7) Depending on the version M12x1, according to DIN 43650, Harting, Amphenol-Tuchel, 7/8" FF; note plug protection.3148

6-EN-

0703

07

Page 24: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Protection- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Polyester foil

Supply voltage - 4… 20mA/HARTStandard versionSupply voltage- Non-Ex instrument 14… 36 V DC- EEx ia instrument 14… 30 V DC- EExd ia instrument 20… 36 V DCSupply voltage with lighted indicating and adjustment module8)

- Non-Ex instrument 20… 36 V DC- EEx ia instrument 20… 30 V DC- EExd ia instrument 20… 36 V DCPermissible residual ripple- <100 Hz Uss <1 V- 100 Hz … 10 kHz Uss <10mVLoad see diagram

1000

750

500

250

14 1816 20 22 24 26 28 30 32 34 36

Ω

V

4

1 2

3

Fig. 40: Voltage diagram1 HART load2 Voltage limit EEx ia instrument3 Voltage limit non-Ex instrument4 Supply voltage

Voltage supply - 4… 20mA/HART four wire instrumentSupply voltage- Non-Ex and Exd instrument 20… 72 V DC, 20… 253 V AC, 50/60 Hz (with and without lighting of the

indicating and adjustment module)Power consumption max. 4 VA,max. 2.1 W

Power supply - Profibus PASupply voltage- Non-Ex instrument 9… 32 V DC- EEx ia instrument 9… 24 V DCSupply voltage with lighted indicating and adjustment module9)

- Non-Ex instrument 12… 36 V DC- EEx ia instrument 12… 30 V DC

Technical data

24 Radar – Level measurement

8) For instruments with national approvals such as e.g. according to FM and CSA only available at a later date.9) For instruments with national approvals such as e.g. according to FM and CSA only available at a later date.

31486-EN-070307

Page 25: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Power supply by/max. number of sensors- DP/PA segment coupler max. 32 (max. 10 with Ex)- VEGALOG 571 EP card max. 15 (max. 10 with Ex)

Power supply - Foundation FieldbusSupply voltage- Non-Ex instrument 9… 32 V DC- EEx ia instrument 9… 24 V DCSupply voltage with lighted indicating and adjustment module10)

- Non-Ex instrument 12… 32 V DC- EEx ia instrument 12… 24 V DCPower supply by/max. number of sensors- H1 power supply max. 32 (max. 10 with Ex)

Electrical protective measuresProtection- Plastic housing IP 66/IP 67- Double chamber Alu-housing, four-wire instruments IP 66/IP 67- Alu and stainless steel housing, two-wire instruments IP 66/IP 68 (0.2 bar)11)Overvoltage category IIIProtection class- two-wire, Profibus PA, Foundation Fieldbus II- four-wire I

Approvals12)13)14)

FM FM CI.I, Div 2 (NI)+CI.II, III, Div 1 (DIP); FM CI.I-III, Div 1 (IS); FM CI.I-III,Div1 (IS)+Cl.I-III, Div1 Gr.C-G(XP)

CSA CSA CI.I, Div2 (NI)+CI.II, III, Div1 (DIP); CSA CI.I-III, Div 1 (IS)

CE conformityEMC (89/336/EWG) Emission EN 61326: 1997 (class A), susceptibility EN 61326: 1997/A1:

1998R & TTE directive I-ETS 300-440 Expert opinion No. 0043052-02/SEE, Notified Body No.

0499LVD (73/23/EWG) EN 61010-1: 2001

Functional safety (SIL)You can find detailled information in the SafetyManual ofVEGAPULS or under www.vega.com.Functional safety according to IEC 61508-4- Single channel architecture (1oo1D) up to SIL2- double channel diversitary redundant architecture (1oo2D) up to SIL3

FCC conformity (only for USA/Canada)Conformity to part 15 of the FCC regulations

Environmental instructionsVEGA environment management system15) certified according to DIN EN ISO 14001

Technical data

Radar – Level measurement 25

10) For instruments with national approvals such as e.g. according to FM and CSA only available at a later date.11) Prerequisite for maintaining the protection is a suitable cable.12) Depending on the instrument type.13) Deviating data in Ex applications: see separate safety instructions.14) You can find detailed information under www.vega.com.15) You can find detailed information under www.vega.com.3148

6-EN-

0703

07

Page 26: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

7 Dimensions

Housing in protection IP 66/IP67 and IP 66/IP 68; 0.2 bar

112m

m (4

13/ 3

2")

117m

m (4

39/ 6

4")

116m

m (4

9 /16

")

120m

m (4

23/ 3

2")

~ 69mm(2 23/32") ø 77mm

(3 1/32")

~ 69mm(2 23/32") ~ 116mm (4 9/16")

~ 87mm (3 27/64")ø 77mm(3 1/32") ø 84mm (3 5/16")

ø 84mm(3 5/16")

M20x1,5M20x1,5/½ NPT

M20x1,5/½ NPT

M20x1,5/½ NPT

M20x1,5/½ NPT

M16x1,5

1 2 3 4

Fig. 41: Housing versions in protection IP 66/IP 67 and IP 66/IP 68, 0.2 bar (withintegrated PLICSCOM the housing is 9mm/0.35 in higher)1 Plastic housing2 Stainless steel housing3 Aluminium double chamber housing4 Aluminium housing

Housing in protection IP 66/IP 68, 1 bar

117m

m (

4 39

/ 64"

)

116m

m (

4 9 /

16")

120m

m (

4 23

/ 32"

)

~ 103mm(4 1/16") ~ 150mm (5 29/32")

~ 105mm (4 9/64")

ø 77mm(3 1/32") ø 84mm (3 5/16")

ø 84mm(3 5/16")

M20x1,5M20x1,5 M20x1,5

M20x1,5/½ NPT

M16x1,5

1 2 3

Fig. 42: Housing versions in protection IP 66/IP 68, 1 bar (with integratedPLICSCOM the housing is 9mm/0.35 in higher)1 Stainless steel housing2 Aluminium double chamber housing3 Aluminium housing

VEGAPULS 61 - encapsulated antenna system in threadedversion

43m

m(1

11 /

16")

20m

m (

25/ 3

2")

78m

m (

3 5 /

64")

ø 39mm(1 17/32")

50mm(1 31/32")

G1½A / 1½ NPT

Fig.43: VEGAPULS -encapsulatedantennasystem in threadedversionG1½Aand1½ NPT

VEGAPULS 61 - encapsulated antenna system with hy-gienic fitting

1 2

312

1mm

(4 49

/ 64"

)

ø 39mm(1 17/32")

50mm(1 31/32")

ø64mm (2 33/64")ø91mm (3 37/64")

121m

m(4

49/ 6

4")

ø 39mm(1 17/32")

50mm(1 31/32")

ø78mm (3 5/64")ø95mm (3 47/64")

121m

m(4

49/ 6

4")

ø 39mm(1 17/32")

50mm(1 31/32")

ø 68mm(2 43/64")ø 84mm(3 5/16")

Fig. 44: VEGAPULS - encapsulated antenna system in threaded version with hy-gienic fitting1 Tri-Clamp 2" and 3"2 Bolting according to DIN 11851 DN 50 and DN 803 TuchenhagenVariventDN 32

Technical data

26 Radar – Level measurement

31486-EN-070307

Page 27: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 61 - plastic horn antenna with mounting strap

15 m

m(1

9 /32

")98

mm

(3 55

/ 64"

)

2,5 mm(1/8")

125 mm(4 59/64")

170

mm

/(6

11/ 1

6") /

300

mm

(11

3 /4"

)

19 m

m(3

/ 4")

8,5

mm

(21 /

64")

75 mm(2 61/64")107 mm(4 7/32")115 mm(4 17/32")

9 mm(23/64")

85 m

m(3

11/ 3

2")

12 m

m(1

5 /32

")9

mm

(23 /

64")

12 mm(15/32")

PP

PBT-GF30

1.4301

Fig. 45: VEGAPULS - plastic horn antenna with mounting strap

VEGAPULS 61 - plastic horn antenna with compressionflange

ø 21mm(53/64")

ø 107mm (4 7/32")

ø 115mm(4 17/32")

ø 156mm(6 9/64")

ø 200mm(7 7/8")

ø 75mm(2 61/64")

10,5

mm

(13 /

32")

19m

m(3

/ 4")

126m

m

(4 61

/ 64"

)

Fig. 46: VEGAPULS -plastic hornantennawith compressionflangeDN 80/3"/JIS80

VEGAPULS 62 - horn antenna in threaded version

mm

inch

38m

m (

1 1 /

2")

22m

m (

55/ 6

4")

22m

m (

55/ 6

4")

118m

m (

4 41

/ 64"

)

46mm(1 13/16")

3 15/16" ø1 37/64"ø1 57/64"ø2 61/64"ø3 47/64"

4 23/32"8 1/2"

16 59/64"

xy

100 ø40

120 ø48

216 ø75

430 ø95

1½"

2"

3"

4"

xy

1½"

2"

3"

4"

x

y

G1½A / 1½ NPT

x

y

21

Fig. 47: VEGAPULS 62 - horn antenna in threaded version1 Standard2 with temperature adapter

VEGAPULS 62 - horn antenna in threaded version withpurging air connection

mm

inch3 15/16"4 23/32"8 1/2"

16 59/64"

ø1 37/64"ø1 57/64"ø2 61/64"ø3 47/64"

xy100 ø40120 ø48216 ø75430 ø95

1½"2"3"4"

xy1½"2"3"4"

38m

m (1

1 /2"

)

22m

m (5

5 /64

")

22m

m (5

5 /64

")

118m

m (4

41/ 6

4")46mm(1 13/16")

x

yx

y

G1½A/1½ NPT

3

4

49mm(1 59/64")

40mm(1 37/64")

37m

m(1

29/ 6

4")

1 2

G1/

8

max. 7mm(9/32")

“X”

“X” M2:1

Fig. 48: VEGAPULS62 - horn antenna in threaded version with purging air connec-tion1 Standard2 with temperature adapter3 Rinsing air connectionG⅛ A for mounting of a suitable adapter4 Reflux valve - attached (with non-Ex option, with Ex in the scope of delivery)

Dimensions

Radar – Level measurement 27

3148

6-EN-

0703

07

Page 28: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 62 - horn antenna in threaded version with an-tenna extension

mm

inch

38m

m (1

1 /2"

)

22m

m (5

5 /64

")

22m

m (5

5 /64

")

118m

m (4

41/ 6

4")

7 7/8" ø1 37/64"ø1 57/64"ø2 61/64"ø3 47/64"

8 21/32"12 7/16"20 55/64"

46mm(1 13/16")

x

y

G1½A / 1½ NPT

xy > 200 ø40> 220 ø48> 316 ø75> 530 ø95

1½"2"3"4"

xy1½"2"3"4"

x

y

21

Fig. 49: VEGAPULS62 - horn antenna in threaded version with purging air connec-tion and antenna extension16)

1 Standard2 with temperature adapter

VEGAPULS 62 - horn antenna in flange version

60m

m(2

23/ 6

4")

140m

m (5

33/ 6

4")

4xø3/4"4xø3/4"

8xø55/64"

8xø3/4"8xø7/8"

4xø45/64"8xø45/64"8xø45/64"

4 3/4"

4 59/64"6 19/64" 2 61/64"

3 47/64"3 47/64"

16 59/64"16 59/64"

1 57/64" 4 23/32"

8 1/2"

1 37/64"1 57/64" 4 23/32"

3 15/16"

2 61/64"3 47/64"3 47/64"

16 59/64"16 59/64"

8 1/2"

7 3/32"9 29/64"

25/32"

25/32"55/64"

15/16"

3/4"

15/16"

15/16"6 1/2"

4xø45/64"4 21/64"45/64"5 29/32"

7 7/8"8 21/32"11 7/32"

7 1/2"7 1/2"9 1/2"

6"6"

9"11" 1"

Dmm b k d x

DN 50 PN 40 165 20 125 4xø18DN 80 PN 40 200 24 160 8xø18DN 100 PN 16 220 20 180 8xø18DN 150 PN 16 285 22 240 8xø222" 150 lb 152,4 19,1 120,7 4xø19,13" 150 lb 190,5 23,9 152,4 4xø19,14" 150 lb 228,6 23,9 190,5 8xø19,16" 150 lb 279,4 25,4 241,3 8xø22,4

y

48 12075 21695 43095 43048 120

x y

75 21695 43095 430

Dinch b k d

DN 50 PN 40DN 40 PN 40 150 18 110 4xø18 40 100 DN 40PN 40

DN 80 PN 40DN 100 PN 16DN 150 PN 162" 150 lb3" 150 lb4" 150 lb6" 150 lb

Dkx

d

by

21

Fig. 50: VEGAPULS 62 - horn antenna in flange version1 Standard2 with temperature adapter

VEGAPULS 62 - parabolic antenna in threaded version

38m

m (1

1 /2"

)

22m

m (5

5 /64

")

22m

m (5

5 /64

")

118m

m (4

41/ 6

4")

138m

m(5

7 /16

")

ø 244mm (9 39/64")

46mm(1 13/16")

G1½A / 1½ NPT

21

Fig. 51: VEGAPULS 62 - parabolic antenna in threaded version1 Standard2 with temperature adapter

VEGAPULS 62 - Standpipe version with thread

ø 21,3mm(27/32")

ø 21,3mm(27/32")

ø 39,5mm(1 9/16")

ø 39,5mm(1 9/16")

224m

m (8

13/ 1

6")

16m

m (5

/ 8")

32m

m (1

17/ 6

4")

32m

m (1

17/ 6

4")

ø 3,

5mm

(9/ 6

4")

20m

m (2

5 /32

")

22m

m (5

5 /64

")22

4mm

(8 13

/ 16"

)LL

32mm(1 17/64")

G¾A¾ NPT

46mm(1 13/16")

G1½A1½ NPT

Fig. 52: VEGAPULS 62 - Standpipe version with thread17)

Dimensions

28 Radar – Level measurement

16) Depending on the product properties, an antenna extension causes a reduction of the sensitivity in the narrow range. Depending on the length, asuitable support of the antenna extensions must be provided.

17) The plant operator must provide a suitable support for the standpipe depending on the length and the process conditions.

31486-EN-070307

Page 29: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 63 - flange version

100m

m (

3 15

/ 16"

)

163m

m (

6 27

/ 64"

)

4mm

(5 /

32")

4mm

(5 /

32")

ø 44mm (1 47/64")

ø 75mm (2 61/64")

4xø3/4"

4xø3/4"

8xø55/64"

8xø3/4"

8xø7/8"

4xø45/64"

8xø45/64"

8xø45/64"

4 3/4"

4 59/64"

6 19/64" 5 7/16"

6 7/32"

8 11/32"

35/64"

35/64"

35/64"

3 5/8" 5/16"

4 1/64" 5/16"

5"

6 3/16"

8 1/2"

35/64"

35/64"

35/64"

7 3/32"

9 29/64"

25/32"

25/32"

55/64"

15/16"

3/4"

15/16"

15/16"

6 1/2"

7 7/8"

8 21/32"

11 7/32"

7 1/2"

7 1/2"

9 1/2"

6"

6"

9"

11" 1"

Dmm b k d xDN 50 PN 40 165 20 125 4xø18DN 80 PN 40 200 24 160 8xø18DN 100 PN 16 220 20 180 8xø18DN 150 PN 16 285 22 240 8xø222" 150 lb 152,4 19,1 120,7 4xø19,13" 150 lb 190,5 23,9 152,4 4xø19,14" 150 lb 228,6 23,9 190,5 8xø19,16" 150 lb 279,4 25,4 241,3 8xø22,4

y 102 8138 14158 14212 1491,9 8

x y

127 14157,2 14215,9 14

Dinch b k dDN 50 PN 40DN 80 PN 40DN 100 PN 16DN 150 PN 162" 150 lb3" 150 lb4" 150 lb6" 150 lb

d

d

k

D

x

k

D

x

b

y

y

b

21

Fig. 53: VEGAPULS 63 - flange version1 Flange version - flange size DN 502 Flange version - flange size from DN 80

VEGAPULS 63 - hygienic fitting 1

1 2

3 4

60m

m(2

23/ 6

4")

46m

m(1

13/ 1

6")

ø 90mm(3 35/64")

ø 66mm(2 19/32")

85m

m(3

11/ 3

2")

20m

m(2

5 /32

")

ø 78mm(3 5/64")

60m

m(2

23/ 6

4")

46m

m(1

13/ 1

6")

ø 50mm(1 31/32")ø 90mm(3 35/64")

100m

m (3

15/ 1

6")

Fig. 54: VEGAPULS 63 - hygienic fitting1 NeumoBiocontrol2 TuchenhagenVariventDN 253 Hygienic fitting LA4 Hygienic fitting LB

VEGAPULS 63 - hygienic fitting 2

1 2

3 4

8mm

(5/ 1

6")

ø 92mm(3 5/8")

ø 124mm(4 7/8")

100m

m(3

15/ 1

6")

163m

m(6

27/ 6

4")

14m

m(3

5 /64

")

8mm

(5/ 1

6")

ø 94mm(3 45/64")

ø 133mm(5 15/64")

100m

m(3

15/ 1

6")

163m

m(6

27/ 6

4")

14m

m(3

5 /64

")

Fig. 55: VEGAPULS - hygienic fitting 31 BoltingDIN 11851, DN 50, 2" and 3"2 BoltingDIN 11851, DN 80, 4"3 BoltingDIN 11864-2, DN 504 BoltingDIN 11864-2, DN 80

Dimensions

Radar – Level measurement 29

3148

6-EN-

0703

07

Page 30: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 65 - threaded version

41m

m(1

39/ 6

4")

ø 40mm(1 37/64")ø 33mm(1 19/64")

ø 33mm(1 19/64")

22m

m (5

5 /64

")

22m

m (5

5 /64

")

82m

m (3

15/ 6

4")

415m

m (1

6 11

/ 32"

)

120m

m (4

23/ 3

2")

270m

m (1

0 5 /

8")

565m

m (2

2 1 /

4")

70m

m(2

3 /4"

)

352m

m (1

3 55

/ 64"

)

50mm(1 31/32")

50mm (1 31/32")46mm (1 13/16")G1½A / 1½ NPT

PVDF:1.4435:

G1½A / 1½ NPT

21

Fig. 56: VEGAPULS 65 - threaded version1 For socket heights up to 50mm (2 in)2 For socket heights up to 100mm (4 in) or up to 250mm (10 in)

VEGAPULS 65 - flange version

d

ø 33mm(1 19/64")

395m

m (

15 3

5 /64

")

120m

m (

4 23

/ 32"

)

270m

m (

10 5

/ 8")

545m

m (

21 2

9 /64

")94

mm

(3

45/ 6

4")

2mm

(5 /

64")

4xø3/4"

4xø3/4"

8xø55/64"

8xø3/4"

8xø7/8"

4xø45/64"

8xø45/64"

8xø45/64"

4 3/4"

4 59/64"

6 19/64"

7 3/32"

9 29/64"

25/32"

25/32"

55/64"

15/16"

3/4"

15/16"

15/16"

6 1/2"

7 7/8"

8 21/32"

11 7/32"

7 1/2"

7 1/2"

9 1/2"

6"

6"

9"

11" 1"

b

k

D

Dmm b k dDN 50 PN 40 165 20 125 4xø18DN 80 PN 40 200 24 160 8xø18DN 100 PN 16 220 20 180 8xø18DN 150 PN 16 285 22 240 8xø222" 150 lb 152,4 19,1 120,7 4xø19,13" 150 lb 190,5 23,9 152,4 4xø19,14" 150 lb 228,6 23,9 190,5 8xø19,16" 150 lb 279,4 25,4 241,3 8xø22,4

Dinch b k dDN 50 PN 40DN 80 PN 40DN 100 PN 16DN 150 PN 162" 150 lb3" 150 lb4" 150 lb6" 150 lb

Fig. 57: VEGAPULS65 - flangeversion for socket heightup to100mm (4 in)or up to250mm (10 in)

VEGAPULS 66 - standard versionD b k x yd

DN 50 PN 40 165 20 125 4xø18 - -DN 80 PN 40 200 24 160 8xø18 75 75DN 100 PN 16 220 20 180 8xø18 96 110DN 150 PN 16 285 22 240 8xø22 146 205DN 200 PN 16 340 24 295 12xø22 190 300DN 250 PN 16 405 26 355 12xø26 240 3802" 150 lb 152,4 19,1 120,7 4xø19,1 - -3" 150 lb 190,5 23,9 152,4 4xø19,1 75 754" 150 lb 228,6 23,9 190,5 8xø19,1 96 1106" 150 lb 279,4 25,4 241,3 8xø22,4 146 2058" 150 lb 342,9 28,4 298,5 8xø22,4 190 30010" 150 lb 406,4 30,2 362 12xø25,4 240 380

60m

m(2

23/ 6

4")

8xø55/64"

8xø3/4"8xø3/4"

4xø45/64"8xø45/64"8xø45/64"

4 59/64"6 19/64" 2 61/64"

3 25/32"5 3/4"

4 9/64"7 9/32"

2 43/64"

2 61/64"3 25/32"5 3/4"

4 9/64"7 9/32"

2 43/64"

7 3/32"9 29/64"

25/32"

25/32"55/64"

3/4"

15/16"6 1/2"7 7/8"

8 21/32"11 7/32"

4 3/4"6"

4xø55/64"11 39/64"13 25/64" 7 31/64" 10 35/64"15/16"4xø11/32"13 31/32"15 15/16" 1 1/32" 9 29/64" 14 11/64"

9 29/64" 14 11/64"

6"

8xø3/4"

12xø1"

15/16"15/16"

7 1/2"7 1/2"

14 1/4"1 3/16"

9"

16"7 31/64" 10 35/64"8xø7/8"13 1/2"

8xø7/8"9 1/2"1 1/8" 11 3/4"

11" 1"

x y - -

- -

Dinch

mm

b k dDN 50 PN 40DN 80 PN 40DN 100 PN 16DN 150 PN 16DN 200PN 16DN 250 PN 162" 150 lb3" 150 lb4" 150 lb6" 150 lb8" 150 lb10" 150 lb

d

kD

x

yb

Fig. 58: VEGAPULS 66 - standard version

VEGAPULS 66 - standard version with purging air connec-tion

D b k x ydDN 50 PN 40 165 20 125 4xø18 - -DN 80 PN 40 200 24 160 8xø18 75 68DN 100 PN 16 220 20 180 8xø18 96 105DN 150 PN 16 285 22 240 8xø22 146 185DN 200 PN 16 340 24 295 12xø22 190 268DN 250 PN 16 405 26 355 12xø26 240 3602" 150 lb 152,4 19,1 120,7 4xø19,1 - -3" 150 lb 190,5 23,9 152,4 4xø19,1 75 684" 150 lb 228,6 23,9 190,5 8xø19,1 96 1056" 150 lb 279,4 25,4 241,3 8xø22,4 146 1858" 150 lb 342,9 28,4 298,5 8xø22,4 190 26810" 150 lb 406,4 30,2 362 12xø25,4 240 360

136m

m (5

23/ 6

4")

8xø55/64"

8xø3/4"8xø3/4"

4xø45/64"8xø45/64"8xø45/64"

4 59/64"6 19/64" 2 61/64"

3 25/32"5 3/4"

4 9/64"7 9/32"

2 43/64"

2 61/64"3 25/32"5 3/4"

4 9/64"7 9/32"

2 43/64"

7 3/32"9 29/64"

25/32"

25/32"55/64"

3/4"

15/16"6 1/2"7 7/8"

8 21/32"11 7/32"

4 3/4"6"

4xø55/64"11 39/64"13 25/64" 7 31/64" 10 35/64"15/16"4xø11/32"13 31/32"15 15/16" 1 1/32" 9 29/64" 14 11/64"

9 29/64" 14 11/64"

6"

8xø3/4"

12xø1"

15/16"15/16"

7 1/2"7 1/2"

14 1/4"1 3/16"

9"

16"7 31/64" 10 35/64"8xø7/8"13 1/2"

8xø7/8"9 1/2"1 1/8" 11 3/4"

11" 1"

12

x y - -

- -

Dinch

mm

b k dDN 50 PN 40DN 80 PN 40DN 100 PN 16DN 150 PN 16DN 200PN 16DN 250 PN 162" 150 lb3" 150 lb4" 150 lb6" 150 lb8" 150 lb10" 150 lb

d

kD

x

yb

Fig. 59: VEGAPULS 66 - standard version with purging air connection1 Rinsing air connectionG¼ A for mounting of an own adapter2 Reflux valve - attached (with non-Ex option, with Ex in the scope of delivery)

Dimensions

30 Radar – Level measurement

31486-EN-070307

Page 31: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 66 - high temperature version

200m

m (

7 7 /

8")

337m

m (

13 1

7 /64

")

21

Fig. 60: VEGAPULS 66 - high temperature version1 For process temperatures up to 250 °C (482 °F)2 For process temperatures up to 400 °C (752 °F)

VEGAPULS 66 - standpipe version

7 7/8"

1 1/32"

1 3/16"1 1/8"

8 21/32"11 7/32"13 25/64"15 15/16"

7 1/2"

13 1/2"

6 19/64"7 3/32"

11 3/4"14 1/4"

7 1/2"9 1/2"

9 29/64"11 39/64"13 31/32"

6"9"

11"

16"

1"

15/16"25/32"55/64"15/16"

15/16"15/16"

inchmm D b k dDN 80 PN 16/40 200 24 160 8xø18DN 100 PN 16 220 20 180 8xø18DN 150 PN 16 285 22 240 8xø22DN 200 PN 16 340 24 295 12xø22DN 250 PN 16 405 26 355 12xø263" 150 lb 190,5 23,9 152,4 4xø19,14" 150 lb 228,6 23,9 190,5 8xø19,16" 150 lb 279,4 25,4 241,3 8xø22,48" 150 lb 342,9 28,4 298,5 8xø22,410" 150 lb 406,4 30,2 362 12xø25,4

D b k dDN 80 PN 16/40 8xø45/64"

8xø45/64"8xø55/64"

12xø55/64"12xø11/32"

4xø3/4"8xø3/4"8xø7/8"8xø7/8"

DN 100 PN 16DN 150 PN 16DN 200 PN 16DN 250 PN 163" 150 lb4" 150 lb6" 150 lb8" 150 lb10" 150 lb 12xø1"

kD

b

L

d

ø 52mm(2 3/64")

ø 8mm(5/16")

ø 56mm(2 13/64")

47m

m(1

27/ 3

2")

60m

m(2

23/ 6

4")

180m

m(7

3 /32

")

317m

m(1

2 31

/ 64"

)

2 31

Fig. 61: VEGAPULS 66 - standpipe version18)

1 Standard version2 For process temperatures up to 250 °C (482 °F)3 For process temperatures up to 400 °C (752 °F)

Dimensions

Radar – Level measurement 31

18) The plant operator must provide a suitable support for the standpipe depending on the length and the process conditions.3148

6-EN-

0703

07

Page 32: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

8 Product code

VEGAPULS 61ApprovalUX FM Cl.I, Div2 (NI)+Cl.II, III, Div1 (DIP) UF FM Cl.I-III,DIV1(IS)UG FM Cl.I-III, Div 1(IS)+Cl.I-III,Div 1 Gr.C-G(XP) KX CSA Cl.I,Div2 (NI)+ Cl. II,III Div1 (DIP)KF CSA Cl. I-III, Div 1 (IS)KG CSA Cl.I-III,Div1(IS)+ Cl.I-III,Div1,Gr.C-G(XP)

Version / Material / Process temperatureA with encapsulated horn antenna / PVDF / -40...80°C

Process connection / MaterialNP Thread 1½NPT PN3 / PVDF CA Tri-Clamp 2" PN3 / 316L CB Tri-Clamp 3" PN3 / 316L

ElectronicsH Two-wire 4...20mA/HART® V Four wire 4...20mA/HART® 1)

P Profibus PAF Foundation Fieldbus

Housing / ProtectionK Plastic / IP66/IP67A Aluminium / IP66/IP68 (0.2 bar)D Aluminium double chamber / IP66/IP67 V Stainless steel 316L / IP66/IP68 (0.2bar)

Cable entry / Plug connectionN ½NPT / without

Indicating/adjustment module (PLICSCOM)X withoutA top mountedB side mounted

PS61.

1) Only in conjunction with Housing / Protection "D"

VEGAPULS 62ApprovalUX FM Cl.I, Div2 (NI)+Cl.II, III, Div1 (DIP) UF FM Cl.I-III,DIV1(IS) UG FM Cl.I-III, Div 1(IS)+Cl.I-III,Div 1 Gr.C-G(XP)KX CSA Cl.I,Div2 (NI)+ Cl. II,III Div1 (DIP) KF CSA Cl. I-III, Div 1 (IS) KG CSA Cl.I-III,Div1(IS)+ Cl.I-III,Div1,Gr.C-G(XP)

Version / MaterialB with horn antenna ø40 mm / 316LC with horn antenna ø48 mm / 316LD with horn antenna ø75 mm / 316LE with horn antenna ø95 mm / 316LK with parabolic antenna ø245mm / 316LF with ½"-standpipe / 316L 1)

Process connection / MaterialND Thread 1½NPT PN40 / 316L AC Flange 1½"150lb RF,ANSI B16.5/316L AE Flange 2" 150lb RF, ANSI B16.5 / 316L AI Flange 3" 150lb RF, ANSI B16.5 / 316L

AK Flange 4" 150lb RF, ANSI B16.5 / 316LAM Flange 6" 150lb RF, ANSI B16.5 / 316LAN Flange 8"150lb RF,ANSI B16.5/316LAP Flange 10"150lb RF,ANSI B16.5/316L

Seal / Process temperature2 FKM (Viton) / -40...130°C 3 Kalrez 6375 / - 20...130ºC4 FKM (Viton) / -40...200°C5 Kalrez 6375 / -20...200°C

ElectronicsH Two-wire 4...20mA/HART® V Four wire 4...20mA/HART® 2)

P Profibus PAF Foundation Fieldbus

Housing / ProtectionK Plastic / IP66/IP67A Aluminium / IP66/IP68 (0.2 bar)D Aluminium double chamber / IP66/IP67 V Stainless steel 316L / IP66/IP68 (0.2bar)

Cable entry / Plug connectionN ½NPT / without

Indicating/adjustment module (PLICSCOM)X withoutA top mountedB side mounted

Additional equipmentX without1 Antenna extension single section 316L K Purging connec.

PS62.

1) Only in conjunction with Seal / Process temperature "4" or "5"2) Only in conjunction with Housing / Protection "D"

Product code

32 Radar – Level measurement

31486-EN-070307

Page 33: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 63ApprovalUX FM Cl.I, Div2 (NI)+Cl.II, III, Div1 (DIP) UF FM Cl.I-III,DIV1(IS)UG FM Cl.I-III, Div 1(IS)+Cl.I-III,Div 1 Gr.C-G(XP)KX CSA Cl.I,Div2 (NI)+ Cl. II,III Div1 (DIP) KF CSA Cl. I-III, Div 1 (IS) KG CSA Cl.I-III,Div1(IS)+ Cl.I-III,Div1,Gr.C-G(XP)

Version / Material / Process temperatureP with encapsulated horn antenna / TFM-PTFE / -40...150°CB with encapsulated horn antenna / PVDF / 0...150°CF with encapsulated horn antenna / PFA / -40...150°CK encaps.horn ant. for Clamp/TFM-PTFE/-40°C...150°C

Process connection / MaterialCA Tri-Clamp 2" / 316L CD Tri-Clamp 2½" / 316L CB Tri-Clamp 3" / 316L CE Tri-Clamp 3½" / 316LCC Tri-Clamp 4" / 316L AE Flange 2" 150lb RF, ANSI B16.5 / 316LAI Flange 3" 150lb RF, ANSI B16.5 / 316L

AK Flange 4" 150lb RF, ANSI B16.5 / 316LAM Flange 6" 150lb RF, ANSI B16.5 / 316L

ElectronicsH Two-wire 4...20mA/HART® V Four wire 4...20mA/HART® 1)

P Profibus PAF Foundation Fieldbus

Housing / ProtectionK Plastic / IP66/IP67 A Aluminium / IP66/IP68 (0.2 bar)D Aluminium double chamber / IP66/IP67V Stainless steel 316L / IP66/IP68 (0.2bar)

Cable entry / Plug connectionN ½NPT / without

Indicating/adjustment module (PLICSCOM)X withoutA top mounted B side mounted

PS63.

1) Only in conjunction with Housing / Protection "D"

VEGAPULS 65ApprovalUX FM Cl.I, Div2 (NI)+Cl.II, III, Div1 (DIP) UF FM Cl.I-III,DIV1(IS)UG FM Cl.I-III, Div 1(IS)+Cl.I-III,Div 1 Gr.C-G(XP) KX CSA Cl.I,Div2 (NI)+ Cl. II,III Div1 (DIP)KF CSA Cl. I-III, Div 1 (IS)KG CSA Cl.I-III,Div1(IS)+ Cl.I-III,Div1,Gr.C-G(XP)

Version / Material / Process temperatureK Rod antenna for socket 50mm / PVDF a. PTFE /-40...130°C 1)

L Rod antenna for socket 100mm / PTFE / -40...130/150°C 2)

M Rod antenna for socket 250mm / PTFE / -40...130/150°C 2)

Process connection / MaterialND Thread 1½NPT PN16 / 316LNP Thread 1½NPT PN3 / PVDFAE Flange 2" 150lb RF, ANSI B16.5 / 316LAI Flange 3" 150lb RF, ANSI B16.5 / 316L

AK Flange 4" 150lb RF, ANSI B16.5 / 316LAM Flange 6" 150lb RF, ANSI B16.5 / 316L

ElectronicsH Two-wire 4...20mA/HART®V Four wire 4...20mA/HART® 3)

P Profibus PA F Foundation Fieldbus

Housing / ProtectionK Plastic / IP66/IP67A Aluminium / IP66/IP68 (0.2 bar)D Aluminium double chamber / IP66/IP67 V Stainless steel 316L / IP66/IP68 (0.2bar)

Cable entry / Plug connectionN ½NPT / without

Indicating/adjustment module (PLICSCOM)X withoutA top mounted B side mounted

PS65.

1) Only for Process connection / Material "GP" or "NP"2) With Process connection / Material "GP" or "NP" process temperature only -40...130°C 3) Only in conjunction with Housing / Protection "D"

Product code

Radar – Level measurement 33

3148

6-EN-

0703

07

Page 34: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

VEGAPULS 66ApprovalUX FM Cl.I, Div2 (NI)+Cl.II, III, Div1 (DIP) UF FM Cl.I-III,DIV1(IS) UG FM Cl.I-III, Div 1(IS)+Cl.I-III,Div 1 Gr.C-G(XP)KX CSA Cl.I,Div2 (NI)+ Cl. II,III Div1 (DIP)KF CSA Cl. I-III, Div 1 (IS) KG CSA Cl.I-III,Div1(IS)+ Cl.I-III,Div1,Gr.C-G(XP)

Version / MaterialA without horn antenna for standpipeD with horn antenna ø75 mm / 316L 1)

N with horn antenna ø 75 mm/2.4602 alloy C22E with horn antenna ø96 mm / 316L 1)

O with horn antenna ø 96 mm/2.4602 alloy C22H with horn antenna ø145 mm/316L Q with horn antenna ø 145 mm/2.4602 alloy C22I with horn antenna ø195 mm / 316L

J with horn antenna ø 240 mm / 316LF with standpipe ø50 mm / 316L

Process connection / MaterialAE Flange 2" 150lb RF, ANSI B16.5 / 316L BE Flange 2"150lb RF,ANSI B16.5/316L,C22 coat.AI Flange 3" 150lb RF, ANSI B16.5 / 316LBI Flange 3"150lb RF,ANSI B16.5/316L,C22 coat.

AK Flange 4" 150lb RF, ANSI B16.5 / 316L BK Flange 4"150lb RF,ANSI B16.5/316L,C22 coat. AM Flange 6" 150lb RF, ANSI B16.5 / 316L BM Flange 6"150lb RF,ANSI B16.5/316L,C22 coat. AN Flange 8" 150lb RF, ANSI B16.5 / 316L AP Flange 10" 150lb RF, ANSI B16.5 / 316L

Seal / Process temperature2 FKM (Viton) / -40...150°C 3 Kalrez 6375 / -20...150°C G Graphite and ceramic / -60...250°C H Graphite and ceramic /-60...400°C

ElectronicsH Two-wire 4...20mA/HART® V Four wire 4...20mA/HART® 2)

P Profibus PAF Foundation Fieldbus

Housing / ProtectionK Plastic / IP66/IP67A Aluminium / IP66/IP68 (0.2 bar)D Aluminium double chamber / IP66/IP67 V Stainless steel 316L / IP66/IP68 (0.2bar)

Cable entry / Plug connectionN ½NPT / without

Indicating/adjustment module (PLICSCOM)X withoutA top mounted B side mounted

Additional equipmentX without1 Antenna extension single sectionK Cooling air connection

PS66.

1) Only for measurement in Standpipes / Bypass tubes2) Only in conjunction with Housing / Protection "D"

34 Radar – Level measurement

31486-EN-070307

Page 35: Product Information VEGAPULS 61 / VEGAPULS 62 / …literature.puertoricosupplier.com › 017 › FT16506.pdfVEGAPULS 61 is characterisedby a small process fitting and a ... The VEGAPULS

Radar – Level measurement 35

3148

6-EN-

0703