1truflo®
CE Rohs
Product Selection
General DataSPECIFICATION DESCRIPTION
Fluid Water or Chemical Liquid - Viscosity Range : .5-20 centistokes
Accuracy > ± 1.0% of F.S. @ 25°C - Repeatability ± .5% of Full Scale
10 m/s max - (32.8 ft/sec max)
Min Flow 0.3 m/s min. - (.98 ft/sec min)
Operating press. 125 psi
Turndown 10 : 1
Response time Real Time
Material of Construction Paddle: Tefzel Body: PVC/PP/ 316 Shaft: Ceramic Seals: EPDM/FPM
Operating temperature
Electronics -25°C to +50°C
PVC < 60°C - PP< 80°C - 316 SST< 120°C
Protection Class
Approval
IP-65 NEMA 4X
CE Rohs
( 1 ) SERIES
TKM = Paddle Wheel Flow Meter with TransmitterTKP = Paddle Wheel Flow Meter & Flow TotalizerTKS = Paddle Wheel Flow Meter Relay OutputTKW = Paddle Wheel Flow Sensor - No Display
( 2 ) PIPE SIZE
15 = ( 1/2”) / 20 = (3/4”)25 = ( 1”) / 40 = (1 1/2”)50 = ( 2”) 80=(3”) / 100=(4”)
( 3 ) COMMUNICATION OR TRANSMITTER
Non = Without communicationRS = TKP series with RS-485 or MODBUS selectableA = TKM & TKW series with Transmitter (4 - 20mA) + PulseV = TKM & TKW series with Transmitter (0 - 5V) + PulseP = TKW series pulse output only
( 4 ) BODY MATERIAL
PVC = PVC PP = PPST = 316 SST
( 5 ) CONNECTION METHOD
STD = Wire Lead (3m)
TKMEXAMPLE:
25 A PVC
truflo® FLOW METER INSTRUCTION MANUAL
2 Flow Meter Instruction Manual
Programming TKP/TKM Series
Running Status
Setting of Lock Out
Unit of Flow Meter
Flow Volume
Span of Transmitter (TKM Series Only)
Transmitter (TKM Series Only)
Range of Transmitter (TKM Series Only)
0
Lck
Ut
K
tr
SPn
O S t
0
10
0
Preset
100
1.000
0.000
FUNCTION OF DISPLAY DISPLAY DESCRIPTION
Press SET
Press SET
Press SET
Press SET
Press SET
Press SET Hold (3 sec)
1] Lck = 10 (Unlocked)
Power On Flow Meter Display Will Show 0
: * (Change to Another Number to Lock Unit)
1] Range: 0-3 2] Unit of Flow & Total 3] Ut = 0 : Liter Ut = 1 : Gallon Ut =2 : Kiloliter (KL)
1] Range : 0.1-9.999 (K -Factor Factory Preset) ( Value of Flow rate = Input pulses x 1 / k (LPM))
1] Range : 0.1-9.999 (100 Standard) (4-20 mA or 0 - 5V) (Depending on Unit Ordered))
1] Range : 0.000 -9.999 (Standard value : 1.000 - Factory Preset)
1] Range : 0.000-9.999- 1.999mA-(0 is Standard)
Press SET + F (3 sec)
Standard pipe size
Pipe Size (O.D.) ANSI (ID)(mm)
DIN (ID)(mm)
Flow rate (LPM)
0.3m/s min. 10m/s max.
1/2” 21.34 20 3.5 120.0
3/4” 26.67 25 5.0 170.0
1” 33.40 32 9.0 300.0
11/2” 48.26 50 25.0 850.0
2” 60.32 63 40.0 1350.0
(
3truflo®
How to set the limit of meter (TKP / TKM Series)
Flow Meter 0
0
TL
TL
TL
FR
FR
FR
0.0
0.0
2000
100.0
FUNCTION OF METER DISPLAY DESCRIPTION
Press
Press
Press
Setting of Flow Rate
Setting of Flow Total
1 ] Set Value of Flow Rate Output
Display reads 0
2 ] CV SV ----> Flow rate output ON CV SV ----> Flow rate output OFF
1] Set Value of Flow Total Output2] SV : Preset value of Flow Total CV SV ----> Flow Rate output ON
* Please press the SET or key to change value and set the limit of Flow Rate or Flow Total * To reset the �ow totalizer to Zero : Please press [SET] & Down Arrow Key for 3 Sec * CV=Current Value (Flow) * SV=Selected Value (Programmed Value) * FR=Flow Rate* TL=Total Flow (Totalizer)
Preset Value of Flow Rate
4 Flow Meter Instruction Manual
Programming Control Function ( TKP / TKM Series)
Running Status
OP2 Output Control
OP2 Output Reset Time
LPM ( OP1 ) Output Status
OP1 Power on Delay Time
Communication Code
BPS
Controller No.
Hysteresis of LPM Output
0
Con
t1
ALT
Hys
t 2
r S
b P S
I d
0.0
n
0.50
0
1.0
10
0
9600
1
FUNCTION OF DISPLAY DISPLAY DESCRIPTION
Press SET (3 sec)
(Hold 3 sec)
Press SET
Press SET
Press SET
Press SET
Press SET
Press SET
Press SET
Press SET (3 sec)
1] Range : E.n.r.c output control for Flow total
Power On Flow Meter Display Will Show 0
2] Con = n : Op 2 manual r eset ; Con = r : Op2 auto reset using timer Con = r o c : Op 2 auto reset when total volume value=SV Con = E : Op 2 = Pulse output of Unit volume Standard = One litre/pulse
1] Range: 0 - 999.99 sec ; Reset time of Flow total 2] Only for Op if Con = n or E ----> No timer control ----> t1 will not be an option
1] Range: 0.1-999.99
1] Range: 0-9999
1] Range: 0 - 32] RS = 0 : BCD ; RS = 1 : RTU-HEX RS = 2 : ASCII-BCD ; RS = 3 : MODBUS-HEX
1] Range: 96 or 1922] 96 = 9600 bps
192 = 19200 bps
1] Range: 1-99
Use to name controller - ID
Only available on RS Communication Models
Only available on RS Communication Models
1] Range: 0 - 12] CoS = 0 : LPM > SV ----> Op 1 ON
LPM < SV - HYS ----> Op 1 OFF CoS = 0 : LPM > SV ----> Op 1 ON
LPM > SV + HYS ----> Op 1 OFF
Mode of NPN Output
ALT NO. DESCRIPTION
ALt = 0 [ PV ] [ SV ] ----> ON: [ PV ] < [ SV - HyS ] ----> OFF
ALt = 1 [ PV ] [ SV ] ----> ON: [ PV ] > [ SV + HyS ] ----> OFF
ALt = 2 [ SV + HyS ] [ PV] [ SV- HyS ] ----> ON: [ PV ] > [ SV + HyS ] or [ PV ] < [ SV - HyS ] ----> OFF
ALt = 3 [ SV + HyS ] [ PV] [ SV- HyS ] ----> OFF: [ PV ] > [ SV + HyS ] or [ PV ] < [ SV - HyS ] ----> ON
PV= Current Value=Flow Rate SV= Selected Value - Programmed Value
5truflo®
Programming TKS Series
Programming Alarm Set Point TKS Series
Running Status
Flow Meter
Setting of Lock
Set Relay
Setting of K Value
Relay Hysteresis
Setting of Alarm Status
Power on Delay Time
0
0
Lk.10
123.4
0
*
d.99.9
C.0
t.00
FUNCTION OF DISPLAY
FUNCTION OF DISPLAY
DISPLAY
DISPLAY
DESCRIPTION
DESCRIPTION
Press SET + F (3 sec)
Press SET
Press SET
Press SET
Press SET
Press SET
Press SET
Press SET
1] Lk = 10 (unlocked status) - Standard
1] Range : 0.1-999.92] C.0 : PV > SV ----> Relay ON C.1 : PV < SV ----> Relay ON
1] Range: 0.1-999.9 *(Depends on Meter Size-Factory Programmed)w meter = Input pulses x 1 / k (LPM)
1] Range: 0.1-99.9 2] C.0 : PV SV - d ----> Relay OFF C.1 : PV SV + d ----> Relay OFF
1] Range: 0-99 sec 2] Delay time of power on alarm output
1] Range: C.0 - C.12] C.0 : PV > SV ----> Relay ON C.1 : PV > SV ----> Relay ON
* In the setting status, the display will Flash
Mode of AlarmALT NO. DESCRIPTION
ALt = 0 [ PV ] [ SV ] ----> Relay ON: [ PV ] < [ SV - d] ----> Relay OFF 1 AMP
ALt = 1 [ PV ] [ SV ] ----> Relay ON: [ PV ] > [ SV + d] ----> Relay OFF 1 AMP
ALt = 2 [ SV + d ] [ PV] [ SV- d ] ----> Relay ON: [ PV ] > [ SV + d ] or [ PV ] < [ SV - d ] ----> Relay OFF 1 AMP
ALt = 3 [ SV + d ] [ PV] [ SV- d ] ----> Relay OFF: [ PV ] > [ SV + d ] or [ PV ] < [ SV - d ] ----> Relay ON 1 AMP
]
PV= Current Value - Flow SV= Selected Value - Programmed Value
6 Flow Meter Instruction Manual
General Features
Range of transmitter (TKW Series)
enter
2 ] [tr] : Range of transmitter [0.0 ~ T r] ----> [4-20 mA] or [0 - 5V]
3 ] [SPn] : Span of transmitter Range [0.000 - 9.999] : Standard value: [1.000]
- 9.999] : Standard value: [0.000]
Reset [Con= r] ----> Auto reset, [Con= C] ----> Auto reset, [Con= E] ----> Pulse output of Unit volume
6 ] [Cos] : Flow rate meter [LPM] output status selecting [OP1], [Cos] = [SV] OP1 ON- SV - HYS OP1 OFF [Cos] = 1 [SV] OP1 ON - SV + HYS OP1 OFF
* Unit of Flow rate meter LPM : USGPM* Unit of Flow total meter FTM : Liter / Gallon / KL
1/2”
0 - 30 LPM
3/4”
0 - 60 LPM
1”
0 - 90 LPM
11/2”
0 - 200 LPM
2”
0 - 330 LPM
* Please press the SET or key to set the limit of LPM or FTM
7] How to reset the �ow total meter: Please press [SET] Down Arrow Key for 3 sec
]
]
]
7truflo®
Wiring Diagram
TKW P
TKP
TKS
TKM
TKM
Brown Black12 - 24 VDC Paddle Pulse Output
5Khz Square Wave Pulse OutputBlue 0V
Brown 12 - 24 VDC Black + (0-5V or 4-20mA)
Blue 0V White - (0-5V or 4-20mA)
Grey Paddle Pulse Output Shielded Shielded wire
Brown 10 - Yellow + (4-20mA) or 0-5V)
Blue Grey 4 - 20 or 0 - 5 v
Black Flow Total Output NPN Pulse Flow Total Output NPN Pulse White Flow Rate Output NPN Pulse Flow Rate Output NPN Pulse
Brown 10 - 30 VDC (+) 30 VDC (+)Yellow ( + ) RS-485 (OPT)
Blue 0V (-) 0V (-)Grey ( - ) RS-485 1 (OPT)
Black White
Brown 10 - 30 VDC (+) White COM
Blue 0V (-) Grey NO
Black NPN Pulse Output
+ V
0V 0V
+ V
VA
+ +
o r
Lo a d
0V
RS-485
+
+ V1
4
2
5
6
3
Lo a d
Lo a d
* Black wire is changeable for FTM limit output or Unit volume Pulse output.
* Black wire is changeable for FTM limit output or Unit volume Pulse output.
* Black wire is a Unit volume Pulse output
0 V
+ V
Lo a d
Lo a d
1
4
5
6
3
2
o rA
+V
+
1
4 Lo ad
2
3
+ V
NO
COM
0V
5
LOAD RESISTANCE:
Current output ( 4 - 20mA ) : 120 Ω max.Voltage output ( 0 - 5V ) : 10K Ω min.
Output Circuit
Output Circuit
Output Circuit
Output Circuit
Output Circuit
BrownBrown
Blue
Black
Shielded
Grey
Black
White
Blue
Shielded
Brown
Brown
Black
Grey
White
Blue
Grey
Black
White
Yellow
Blue
BrownGreen Ground
Grey
Black
White
Yellow
Blue
Load
-
OPT
8 Flow Meter Instruction Manual
Standard pipe size
Installation positions
Pipe Size
H L D
TKWTKM / TKP All Models
Pulse Output Linear output
1/2” 78 86 95 140 41
3/4” 80 88 97 150 53
1” 83.3 91.3 100.3 160 60
11/2” 101.6 109.6 118.6 185 83
2” 115.4 123.4 132.4 196.8 110
Pipe Size (O.D.) ANSI (ID)(mm)
DIN (ID)(mm)
Flow rate (LPM) / USGPM
0.3m/s min. 10m/s max.
1/2” 21.34 20 3.5/41.6 120.0/488
3/4” 26.67 25 5.0/60.6 170.0 /2108
1” 33.40 32 9.0/110 300.0 /3668
11/2” 48.26 50 25.0/310 850.0 /10553
2” 60.32 63 40.0/496 1350.0 /16760
* measurement in mm
t
CORRECT10x 10x
10x 10x
3x 3x
3x 3x
CORRECTCORRECT
CORRECTINCORRECT
INCORRECT
INCORRECT
INCORRECT
Dimensions
NOTICE OF INSTALLATION1] Please make sure the pipe is �lled with the �uid under normal operation.2] KT series can be installed in a horizontal or vertical direction. 3] Please ensure enough length of straight pipe to avoid turbulence that can e�ect readings. Min 10x pipe DIA upstream 3x pipe DIA downstream.4] Filtering device in the upstream to avoid the paddle wheel from the damage by the solids or �bers - max 10% particle size - not to exceed .5mm cross section or length.5] Please do not �ush the pipe after the measuring unit being installed, if done, it may crack the ceramic shaft.
Speci�cation may be modi�ed without notice in advance.