These Technical Specifications define the range of the manufactured sizes and models, the main dimensions and thescope of use of the FDMA-PM fire dampers (hereinafter referred to only as the "fire dampers"). They are binding forproduction, designing, ordering, delivery, storage, assembly, operation, maintenance and operability inspections.

1. Description......................................................................................................................... 3

2. Design................................................................................................................................ 4

3. Communication and control devices.................................................................................... 15

4. Dimensions, weights and effective area.............................................................................. 18

5. Placement and Assembly.................................................................................................... 20

6. Statement of installations.................................................................................................... 22

7. Thin shaft wall..……………................................................................................................. 55

8. Installation frames..……………........................................................................................... 58

9. Suspension system………….........................................................................................…. 64

10. Pressure loss................................................................................................................... 68

11. Coefficient of local pressure loss....................................................................................... 69

12. Noise data......................................................................................................................... 69

13. Material............................................................................................................................. 71

14. Inspection, testing............................................................................................................. 72

15. Logistic terms.................................................................................................................... 72

16. Assembly.......................................................................................................................... 72

17. Entry into service and revisions......................................................................................... 73

18. Spare parts....................................................................................................................... 74

19. Restore function of actuating mechanism after fuses initiation........................................... 74

75

20. Ordering key..................................................................................................................... 75

21. Data label...........................................................................................….......……........…. 76

Page 3: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

3

Damper characteristics• CE certified acc. to EN 15650• Tested in accordance with EN 1366-2• Classified acc. to EN 13501-3+A1• Fire resistance EIS 120, EIS 90• External Casing leakage class C, Internal leakage class 2 acc. to EN 1751• Cycling test in class C 10000 acc. to EN 15650

• Corrosion resistant acc. to EN 15650 • ES Certificate of conformity No. 1391-CPR-2016/0158 • Declaration of Performance No. PM/FDMA-PM/01/20/1 • Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b

Fire dampers are shutters in ducts of air-conditioning devices that prevent spreading the fire andcombustion products from one fire segment to the other one by means of closing the duct in the pointsof fire separating constructions.The damper blade automatically closes the air duct using a shutting spring or an actuating mechanismof back spring. The shutting spring is activated by pressing the start button or by the impulse from thethermal fuse. The back spring of the actuating mechanism is started when the thermoelectric startingmechanism BAT is activated, when the reset button on BAT is pressed or when the power supply tothe actuating mechanism is stopped.After closing the blade, the damper is sealed with a silicon packing against smoke penetration. Thedamper can be delivered with a seal without silicone at the customer's wish. At the same time, thedamper blade is embedded in a material which enlarges its volume due to increasing temperature andhermetically seals the air duct.The dampers have one inspection hole, as the shutting device and the inspection hole can be set tothe most advantageous position with respect to operation and handling of the control device by turningthe damper a little in case of the spiro model of the dampers.

Working conditionsRight damper function is secured under the following conditions:

a) Maximum air circulation speed: 12 m/s Maximum pressure difference: 1200 Pa b) The air circulation in the whole damper section must be secured as steady on whole

surface. Operation of the dampers does not depend on the direction of air circulation. The dampers can

be located in an arbitrary position.Dampers are suitable for systems without abrasive, chemical and adhesive particles.

Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3. Temperature in the place of installation is permitted to range from -30°C to +50°C.

Page 4: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

4

Design with mechanical control

Design with mechanical control with a thermal protective fuse which actuates the shutting device,after the nominal start temperature 72°C has been reached. Automatic initiation of the shuttingdevice is not activated if the temperature does not exceed 70°C. In case that other starttemperatures are required, thermal fuses with nominal start temperature +104°C or +147°C canbe supplied (this requirement must be specified in the order).

Design .01 with mechanical control can be complemented with a terminal switches signaling ofthe damper blade position "CLOSED" and "OPEN". Limit switches are connected via dampercasing, cables are connected directly to limit switches.

Limit switch“CLOSED”

Limit switch“CLOSED”

Limit switch“OPEN”

Design .01 with mechanical control can be complemented with a limit switch signalling of thedamper blade position "CLOSED". Cable is connected directly to limit switch.

Page 5: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

5

1(COM) - black wire2(NC) - gray wire4(NO) - blue wire

This limit switch is possible to connect in following two versions:a) if the arm is moving … connect wire 1+2b) if the arm is moving … connect wire 1+4

AC 230V / 5AIP 67

-25°C … +120°C

1 Damper2 Mounting plate3 Sealing cover4 Seal plates5 Mounting plate cover6 Thermal fuse7 Mechanics8 Actuator9 Temperature sensor10 Sensor sticker

Page 6: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

6

Design with actuating mechanism

The dampers are equipped with Belimo actuating mechanisms with back spring and thermoelectricactuating device, of range BF (hereinafter referred to only as the "actuating mechanism"). After beingconnected to power supply AC/DC 24V or AC 230V, respectively, the actuating mechanism movesthe damper blade to "OPEN" operation position and at the same time pre-stretches its back spring.While the actuating mechanism is under voltage, the damper blade is in the "OPEN" position and theback spring is pre-stretched. The time needed for full opening of the damper blade from "CLOSED"position to "OPEN" position is 120 seconds at the maximum. if the power supply to the actuatingmechanism is cut off (due to loss of power supply or by pressing the reset button on the BATthermoelectric starting mechanism), the back spring will move the damper blade to "CLOSED" failureposition. The time of moving the blade from "OPEN" position to "CLOSED" position takes 20seconds at the maximum. If the power supply is restored (the blade can be in any position), theactuating mechanism starts to move the damper blade to "OPEN" position again.

A thermoelectrical starting mechanism BAT, which contains two thermal fuses Tf1 and Tf2, is a partof the actuating mechanism. These fuses are activated when temperature +72°C has beenexceeded (the fuse Tf1 when the temperature around the damper and the fuses Tf2 when thetemperature inside the air-conditioning piping has been exceeded). After the thermal fuse Tf1 or Tf2has been activated, the power supply is permanently and irreversibly cut off and the actuatingmechanism, by means of the pre-stretched spring, displaces the damper blade into the breakdownposition "CLOSED".

Signalisation of damper blade position "OPEN" and "CLOSE" is provided by two limit switches.

1 2 S3S1 S2 S5S4 S6

N L1

~- +

<5° <80°

BATTf Tf LED

BATActuatingmechanism

Page 7: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

7

Design .41 or .51 with actuating mechanism can be complemented with smoke detector ORS 142K. The voltage can be AC 230 V or 24 V DC. Design with voltage AC 230 V is equpped withCommunication and supply device BKN 230-24-MOD and with actuating mechanism BF 24-TN.

The smoke detector is activated when smoke spreads in air duct system. Deactivation of smokedetector is provided by interruption of supply voltage for min. 2s.

Signalisation of damper blade position "OPEN" a "CLOSE" is provided by two limit switches..

Operating voltage 18 … 28 V DC

Residual ripple ≤ 200 mV

Power Consumption Socket(without actuating mechanism) max. 22 mA

Degree of protection IP 42

Ambient temperature -20°C … +75°C

Aditional temperature senzor +70°C

Connection - net - motor - communication and supply device BKN

Cabel 1m, connected to terminals 1, 2 and 4Actuator connected on the terminals 2 and 5

Cabel 1m, connected to terminals 1, 2, 4 and 5

Nominal voltage AC 24 V 50/60 HzDC 24 V

AC 230 V 50/60 Hz

Power consumption - motoring - holding

7 W2 W

8 W3 W

Dimensioning 10 VA (Imax 8,3 A @ 5 ms) 12,5 VA (Imax 500 mA @ 5 ms)Protection class III IIDegree of protection IP 54Running time - motor - spring return

120 sec~ 16 sec

Ambient Temperature - normal duty - safety duty - non-operating temperature

-30°C … +50°CThe safe position will be attained up to max. 75°C

-40°C … +50°CConnecting - motor - auxiliary switch

cable 1 m, 2 x 0,75 mm²cable 1 m, 6 x 0,75 mm²

(BF 24-T-ST) with plug-in connectors

Thermal trips Tf1: duct outside temperature Duct +72°CTf2/Tf3: duct intside temperature Duct +72°C

Page 8: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

8

2

3

4

5

6

1relaycontact

relaycontact

RS-Bus communication

1234567

12 S2S1 S3 S5S4 S6

2

3

4

5

6

1

BATTf Tf LED

12 S2S1 S3 S5S4 S6

24 V DC

2

3

4

5

6

1

BATTf Tf LED

Page 9: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

9

Design with the communication and supply device BKN 230-24 and the actuating mechanismBF 24-TN-ST. It simplifies electrical wiring and interconnection of fire flap valves. It facilitates onsite check and enables central control and checks of fire damper by means of a simple 2--conductor wiring.

BKN 230-24 functions as a decentralized network device for supplying the actuating mechanismBF 24-TN-ST with a spring back drive on one hand and on the other hand it transmits the signalinforming about the flap valve position OPERATION and FAILURE through 2-conductor wiring tothe central. Control command SWITCHED ON - SWITCHED OFF from the central through BKN230-24 goes through the same wiring to the actuating mechanism.

To simplify the connection, the actuating mechanism BF 24-TN-ST is equipped with connecting plugs that are inserted directly to BKN 230-24. BKN 230-24 is supplied with aconductor and an EURO plug to be connected to the 230V mains. 2- conductor wiring isconnected to BKN 230-24 by means of terminals 6 and 7. If the drive is supposed to be controlledwithout any signal from the central, it can be switched on by means of a bridge between theterminals 3 and 4. A green LED pilot light on BKN 230-24 is on when voltage is present in thedrive (AC 24V).

If the button on BAT is switched on or if the power supply (e.g. by a signal from ELECTRICALFIRE SIGNALISATION ) is disconnected, the damper position will be "FAILURE".

BAT

BKN

Actuatingmechanism

Nominal voltage AC 230 V 50/60Hz

Power consumption 3,5 W (operating position)

Dimensioning 11 VA (including actuating mechanism with spring return)

Protection Class II

Degree of protection IP 40

Ambient temperatureNon-operating temperature

-20°C … +50°C-40°C … +80°C

Connection - net - motor - terminal board

cable 0,9 m with EURO plug type 266-pole connector, 3-pole connectorscrew terminals for cable 2x1,5 mm²

Page 10: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

10

Design .61 with communication and supply device can be complemented with smoke detector ORS 142 K. For supply and comunnication is used BKN 230-24-C-MP, which together with theBF 24-TN-ST enables central control and checks of fire damper by means of a simple 2-conductorwiring and it also allows connection to the system via MP-BUS communication. More informationin the Belimo catalog.

Nominal voltage AC 230 V 50/60Hz

Power consumption 3,5 W (operating position)

Dimensioning 10 VA (including actuating mechanism with spring return)

Protection Class II

Degree of protection IP 40

Ambient temperatureNon-operating temperature

-20°C … +50°C-40°C … +80°C

Connection - net - motor - terminal board

cable 0,9 m with EURO plug type 266-pole connector, 3-pole connectorscrew terminals for cable 2x1,5 mm²

External smoke detector, +24 V, max. 50 mAExternal smoke detector, control inputConnection of more BKN devices as slavesGNDMP-BUSab

1234567

BAT

1234567 b

a

1)1)

2)

BAT

1) Bridge has been installed by the manufacturer. If needed, it can beremoved ad replaced with a thermoelectric starting mechanism. Ifterminals 1 and 2 are not interconnected, safety function is initiated.

2) Bridge can be used only for starting and without BKS24… !

Two conductor wiring to BKS24

Page 11: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

11

Design .60 with communication and supply device can be complemented with smoke detectorORS 142 K. For supply and comunnication is used BKN 230-24-MOD, which is used together withthe BF 24-TN-ST for communication with control systems using the Modbus RTU or BACnet MS/ TP protocol. The wiring of the line is to be carried out in accordance with applicable RS485regulations. Parameterization of the communication is done using DIL switches. The BKN230-24-MOD can be installed separately, without a connection to a master control system, inwhich case the connection bridge between the terminals 1 and 4 must be installed. For moreinformation, see the Belimo catalog.

Nominal voltage AC 230 V 50/60Hz

Power consumption 3 W (operating position)

Dimensioning 14 VA (including actuating mechanism with spring return)

Protection Class II

Degree of protection IP 40

Ambient temperatureNon-operating temperature

-20°C … +50°C-40°C … +80°C

Connection - net - motor - terminal board

cable 0,9 m with EURO plug type 266-pole connector, 3-pole connectorscrew terminals for cable 2x1,5 mm²

1234567

1 2 S2S1 S3 S5S4 S6

2

3

4

5

6

1

BATTf Tf LED

Page 12: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

12

Design with the communication and supply device BKN 230-24MP and actuating mechanism BF24TL-TN-ST for connection to MP-Bus. BKN 230-24MP supplies to intelligent actuatingmechanisms of fire dampers BF 24TL-TN-ST decentrally needed power supply. In this way canbe realize long MP-Bus communications (up to 800 m). Up to 8 Bus nodes can be parallelconnected and controlled by Master device (DDC with interface).More information in Belimo catalogue.

Design with the communication and supply device BKN 230-24LON and actuating mechanismsof fire dampers BF 24TL-TN-ST for cooperation with control units based on technologyLonWorks. BKN 230-24LON complements actuating mechanism for integrated safety functionand converts digital protocol MP from actuating mechanism to LonTalk and back.More information in Belimo catalogue.

1234567

2

3

4

5

6

1

1 2 S2S1 S3 S5S4 S6

BATTf Tf LED

External smoke detector, +24 V, max. 50 mAExternal smoke detector, control inputGNDBKN Direct Control, override control inputGNDD+D-

1234567

BAT

Page 13: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

13

BAT

BKN

Actuatingmechanism

Nominal voltage AC 24 V 50/60HzDC 24 V

Power consumption - motoring - holding

7 W2 W

Dimensioning 10 VA (Imax 8,3 A @ 5 ms)

Protection class III

Degree of protection IP 54

Running time - motor - spring return

120 sec~ 16 sec

Ambient temperatureNon-operating temperature

-30°C … +50°C-40°C … +50°C

Connection Connector for BKN 230-24LON and BKN 230-24MPcable 1 m, 4 x 0,75 mm² halogen-free

Nominal voltage AC 230 V 50/60Hz

Power consumption 11 W (including actuator mechanism)

Dimensioning 13 VA (including actuator mechanism)

Protection Class II

Degree of protection IP 40

Ambient temperatureNon-operating temperature

-30°C … +50°C-40°C … +80°C

Connection - net - motor (BF…-Top) - net MP - starting mechanism (variable) - Top-Line PC-Tool (via ZIP-RS232)

cable 1m, with EURO plug4-pole connector

screw terminal 2-polescrew terminal 2-pole

3-pole connector

Page 14: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

14

Nominal voltage AC 230 V 50/60Hz

Power consumption 14 W (including actuating mechanism)

Dimensioning 16 VA (including actuating mechanism)

Protection Class II

Degree of protection IP 40

Ambient temperatureNon-operating temperature

-30°C … +50°C-40°C … +80°C

Connection - net - actuator (BF…-Top) - net LonWorks - starting mechanism (optional) - Top-Line PC-Tool (via ZIP-RS232)

cable 1m, with Euro plug4-pole connector

screw terminal 2-polescrew terminal 2-pole

3-pole connector

PC Tool1 7

Ya24VGNDMP1) 2)

24V

AC230 V

GND

MP

net MP-Busadditional external conntact,eg. fire smoke detector

PC Toolba1) 2)

Test

AC230 V

GND

MP

net LON WORKSadditional external conntact,eg. fire smoke detector

Page 15: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

15

BKS 24-1B communication and control device is used for control and checks of fire dampers withBF 24-TN-ST actuating mechanism in conjunction with the BKN 230-24 supply andcommunication device. BKS 24-1B receives information about the situation of the fire damperthrough the BKN 230-24 supply and communication device and issues controlling commands.The device is intended for building in into the distribution board. Light diodes on the front side ofthe device signalise the operating situations of the damper and breakdowns of the whole system.Potentialless auxiliary contacts enable connection to the master control system (signaling of thedamper position, failure reports, release of the ventilators etc.).

While a flashing green LED pilot light signalises damper blade motion towards the given position,the same pilot light reports reaching the required position when shining constantly. If the flapblade, with respect to the given time, does not reach the required position, then a red LED pilotlight starts to flash and at the same time, the failure contact is active. Once the damper bladereaches the given position, this contact is deactivated. The LED pilot light keeps flashing unlessthe failure is unblocked by means of the RESET button. Except for reporting failures, other threeauxiliary contacts are available. Contacts showing operating and failure position of the damperare active when the damper is in the given position. Function check can be done by pressing andholding the button "RESET/TEST" for longer time. While holding the button, the damper blademoves in the direction of the failure position. Fault function is indicated by the LED pilot light.BKS 24-1B can be connected by means of ZSO-11 11 pole connector for DIN 35 mm panel.

4

78

210

1

5

9

an insulationtransformer

~

damper positionbreakdown

Notice: Relay contacts are drawn without power

11ba2-conductor wiring

to BKN230-24

Control

on /off

ResetTest

External butonoptional

be interchanged

6

3

AC24V

damper positionoperation

ResetTest

open

closed

alarm

failure

Connection through

conection can

not available, starting with switching AC 24 on or pressing

«Reset/Test» button possible cause: • short circuit or interruption of 2-conductor wiring

or damper failure (at BKN..) • Power supply AC 230V missing • defective thermoelectrical starting • smoke detector activated • exceeded operation time

• Fault in system signalled, system check should be doneDamper (drive) turning into of breakdown position

Damper (drive) in

Damper (drive) turning into of operating position

Damper (drive) in

light diodes contacts Description

Cause/Coursestateopen closed alarmclosed

flashing

6 3

6 3

6 76 4

6 4

6 3

6 3

6 7

switched

closed closed

closed closed

closed closed

closed

closed

closed

closed

closed

closed

closed

closed

open open open

open

open

open

flashing

flashing

• damper blocked

Page 16: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

16

Nominal voltage AC 24 V 50/60Hz

Power consumption 2,5 W (operating position)

Dimensioning 5 VA

Protection Class III

Degree of protection IP 30

Ambient temperature 0 … +50°C

Connection 11-pole connector ZSO-11, it is not part of BKS24-1B,ZSO-11 is 11-pole screw terminal 11 x 1,5 mm²

BKS 24-9A communication and control device is used for group control and checks of 1 to 9 firedampers with the actuating mechanism BF 24-TN-ST in connection with the supply andcommunication device BKN 230-24. Signalisation of the damper position is individual; thedamper can be controlled and tested only as a group. BKS 24-9A is intended for use in thedistribution board and displays the operation situations and failure reports of the connected firedampers. It is possible to signalise functions such as the damper position and failure reports or totransmit them further to the system by means of integrated auxiliary switches. BKS 24-9Areceives signals from BKN 230-24 through the two-conductor wiring and issues controlcommands. Proper damper operation is indicated by two light LED diodes:

Control ON = position OPERATION Control OFF = position FAILURE

If the fire damper do not reach the given position in time tolerable for displacing, the appropriatelight diode FAILURE starts to flash and K1 contact is opened (current failure). In case that thefaulty damper finally reaches its given position, K1 is closed and the failure report light shines (thefailure is saved in memory). K2 - the auxiliary contact - is used for signaling of the flap position tothe master device. Function of this auxiliary contact can be programmed through the terminal14 according to the Tab. 3.2.1.

current failure 15 16

no failure 15 16

K2 contact is on if all theflaps are open 14 11

17 18K2 contact is on if the flapNo. 1 is open 14 12

K2 contact is on if all theflaps are closed 14 open

Function check can be done in the position OPERATION by means of pushing the TEST button.While the button is pushed, the flap blade is turning into the position FAILURE. Fault function isindicated by a report "FAILURE". Assembly and connection BKS 24 - 9A can be made by DIN35 mm panel. It is connected by two 9-pole plug-in connectors.

Page 17: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

17

Nominal voltage AC 24 V 50/60Hz

Power consumption 3,5 W

Dimensioning 5,5 VA

Protection Class III

Degree of protection IP 30

Ambient temperature 0 … +50°C

Connection terminal 2 x 1,5 mm²

Page 18: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

18

475

115

37550 50

13020110

125

ØD

Position:1 Damper casing2 Mechanics3 Damper blade4 Inspection hole covering5 Sensor sticker6 Hole for camera

475

115

375 5050

13020

ØD

Position:1 Damper casing2 Actuating mechanism3 Damper blade4 Inspection hole covering5 BAT thermoelectrical starting mechanism6 Hole for camera

Dimensions

Page 19: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

19

Weights and effective area

84,5 326,5 53,0 56,0 0,5727 BF M4

134,5 376,5 70,9 73,9 0,7147 BF M4

134,5 376,5 56,0 59,0 0,5727 BF M4

184,5 426,5 74,0 77,0 0,7147 BF M4

Blades overlaps

Act. mechanism side "g"Tab. 4.2.1

Side without act. mechanism "h"Act. mechanism side "e"

Tab. 4.2.2Side without act. mechanism "f"

efgh

For the design .60 (with BKN supply and communication device) add to weight of the damper with an actuating mechanism (from the Tab. 4.2.1. and 4.2.2.) the weight of BKN (0.5 kg).

Page 20: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

20

The fire dampers are suitable for installation in arbitrary position in vertical and horizontal passagesof fire separating structures. The damper assembly procedures must be done so that all load transferfrom the fire separating constructions to the damper body is absolutely excluded. The back-to-backair-conditioning piping must be suspended or supported so that all load transfer from the back-to-back piping to the damper flanges is absolutely excluded. The gap between the installed damper andthe building structure must be perfectly filled with approved material all over its volume.To provide the necessary space for access to the control device, all other items must be situated atleast 350 mm from the control parts of the damper. At least one inspection hole must be accessible.The damper must be installed so that the damper blade (in closed position) is situated in the fireseparating structure - marked by the label BUILD-IN EDGE on the damper body. If such solution isnot possible, the piping between the fire separating structure and the damper blade must beprotected according to the certified installation method, see Section 6.During the installation and plastering process, the control mechanism must be protected (covered)against damage and pollution. The damper body should not be deformed during bricking in. Oncethe damper is built in, the damper blade should not grind on the damper body during opening orclosing.The distance between the fire damper and the structure (wall, ceiling) must be 75 mm at theminimum. If two or more dampers are to be installed in one fire separating structure, the distance

Built in edge

375

260

5050

"Wall edge sticker" indicates the recommended edge of installation of fire damper into the fire partition structure (wall).The damper must be installed so that the entire damper blade - in the closed position - is located inside the fire separating structure

(wall) and at the same time the control mechanism and inspection openings are freely accessible.

Page 21: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

21

The fire damper can be integrated into a solid wall construction made e.g. of normal concrete/ masonry, porous concrete with minimum thickness 100 mm or into solid ceiling construction made

e.g. of normal concrete with minimum thickness 110 mm or porous concrete with minimumthickness 125 mm.

The fire damper can be integrated into a gypsum wall construction with fire classification EI 120or EI 90.

Examples of fire damper installing

Page 22: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

22

100 Mortar or gypsum EIS 120EIS 90 23

100 Battery - mortar or gypsum EIS 90 24100 Installation next to wall - mortar or gypsum and mineral wool EIS 90 25100 Installation next to wall - mortar or gypsum EIS 90 26

100 Installation next to wall - installation frame R3, R4, R5 and mineralwool EIS 90 26

100 Stuffing box with fire protection mastic and cement lime plate EIS 90 27100 Installation frame R1, R2, R3, R4, R5 EIS 90 28100 Weichschott EIS 90 29100 Battery - installation frame R1 EIS 90 30100 Mineral wool - mortar or gypsum EIS 45 31100 Mineral wool - stuffing box and fire protection mastic EIS 45 31

100 Mineral wool, stuffing box, fire protection mastic and cement limeplate EIS 90 32

100 Insulating with cement lime plates - installation frame R6 EIS 90 33

100 Mortar or gypsum EIS 120EIS 90 34

100 Battery - mortar or gypsum EIS 90 35100 Installation next to wall - mortar or gypsum and mineral wool EIS 90 36100 Installation next to wall - mortar or gypsum EIS 90 37

100 Installation next to wall - installation frame R1, R2, R5 and mineralwool EIS 90 37, 38

100 Stuffing box with fire protection mastic and cement lime plate EIS 90 39100 Installation frame R1, R2, R3, R4, R5 EIS 90 40100 Weichschott EIS 90 41100 Battery - installation frame R1 EIS 90 42100 Flexible ceiling - Installation frame R7 EIS 90 43100 Mineral wool - mortar or gypsum EIS 45 44100 Mineral wool - stuffing box and fire protection mastic EIS 45 44

100 Mineral wool, stuffing box, fire protection mastic and cement limeplate EIS 90 45

110 - Concrete125 - Aerated

concrete

Mortar or gypsum EIS 120EIS 90 46

Battery - mortar or gypsum EIS 90 47Stuffing box with fire protection mastic and cement lime plate EIS 90 48Installation frame R1, R2, R3, R4, R5 EIS 90 49Weichschott EIS 90 50Battery - installation frame R2 EIS 90 51Mineral wool - mortar or gypsum EIS 90 52Concrete EIS 90 53Concrete with installation frame R5 EIS 90 53Insulating with cement lime plates - installation frame R6 EIS 90 54

100 Mortar or gypsum EIS 90 56100 Installation frame R1 EIS 90 57

Page 23: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

23

Position:1 Fire damper2 Solid wall construction3 Mortar or gypsum4 Duct

≥ 100

≥ 40

Page 24: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

24

≥ 100

≥ 40

≥ 10

≥ 40

≥ 100

Position:1 Fire damper2 Solid wall construction3 Mortar or gypsum

≥ 10

● Installation opening for each damper has minimal dimensionsD+80 mm (D+160 mm for dampers with flanges)

● Gap between damper and construction is filled by mortar or gypsum● Distance between dampers 70 mm● Flange to flange connection - Up to four dampers can be installed

Page 25: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

25

Position:1 Fire damper2 Mortar or gypsum3 Stuffing box (mineral stone wool min. density 140 kg/m³)

D-20 D-20

≥ D

+100

D-2

0

≥ 100

(≥ 100)+50

≥ 10

≥ 10

● Gap between damper and construction is filledby mortar or gypsum and mineral wool

● Wool is fixed to damper body and constructionby fire protection mastic.

● Mineral wool thickness = construction thickness+ 20 mm or 50 mm

● Installation is valid for ceiling construction

Page 26: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

26

≥ D

+100

≥ 100

≥ 10

≥ 10

Position:1 Fire damper2 Fire damper with installation frame R3, R4, R53 Mortar or gypsum4 Stuffing box (mineral stone wool min. density 140 kg/m³)5 Holder

● Wool is fixed to installation frame andconstruction by fire protection mastic.

● Installation is valid for ceiling construction

Fitting with threaded rodsFitting with steel bracket

≥ 100

≥ 50

≥ 50

≥ 10D+111+5

It is possible to usecorresponding numberof holes and screws

Page 27: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

27

Screws has to be fixed in wall/ceiling construction.(If it is needed use steel bracket).

≤ 300

≤ 300

Screw(min. 4x50)

≥ 25

≥ 25

Position:1 Fire damper2 Solid wall construction3 Stuffing box (mineral stone wool min. density 140 kg/m³)4 Fire protection mastic min. thickness 1 mm5 Cement lime plate min. thickness 15 mm min. density 870 kg/m³6 Duct

Used materials - example:*3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/504 Promastop - P, K, Hilti CFS-CT5 Promatect - H

≥ 40

≥ 100

≥ 50

* Fire resistant insulation and fire resistant board canbe replaced by another approved fire sealing sys-tem for damper installation with equivalent materialproperties.

Page 28: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

28

Position:1 Fire damper2 Installation frame3 Solid wall construction

≥ 100 ≥ 100

≥ 100

Page 29: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

29

Position:1 Fire damper2 Solid wall construction3 Fire resistant board4 Fire stop coating thickness 1 mm5 Duct

Used materials - example:*3 Hilti CFS-CT B 1S 140/504 Hilti CFS-CT

≥ 100

D+60 to 800max. 2050

D+60 to 800max. 1650

* Fire resistant insulation and fire resistant board canbe replaced by another approved fire sealing sys-tem for damper installation with equivalent materialproperties.

Page 30: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

30

Position:1 Fire damper with installation

frame R12 Solid wall construction3 Mineral stone wool min.

density 140 kg/m³

20

≥ 100

20

≥ 100

It is possible to usecorresponding numberof holes and screws

● Gap between frame and damper body and frame andconstruction must be filled by glue (PROMAT K84).

● Distance between dampers 160 mm

● Flange to flange connection - Up to four dampers canbe installed

Page 31: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

31

Position:1 Fire damper2 Solid wall construction3 Mortar or gypsum4 Stone wool with wired mat on

one side, density 66 kg/m³5 Duct

Used materials - example:**4 Isover Ultimate Protect Wired MAT 4.0, th. 100 mm ALU1

≥ 40*

≥ 100

* Around the perimeter

Position:1 Fire damper2 Solid wall construction3 Mineral stone wool min.

density 150 kg/m³4 Fire protection mastic min.

thickness 1 mm5 Stone wool with wired mat on

one side, density 66 kg/m³6 Duct

Used materials - example:**3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/504 Promastop - P, K, Hilti CFS-CT5 Isover Ultimate Protect Wired MAT 4.0, th. 100 mm ALU1

≥ 40*

≥ 100

≥ 50*

* Around the perimeter

** The materials for stuffing box, fire protection mastic, lining and insulation materials canbe replaced by another approved fire sealing system with equivalent properties.

The maximum distance of the fire damper from the structure is not limited and according to EN 15882-2, the required number of suspensions acc. to EN 1366-1:2014 must be used.

** The materials for stuffing box, fire protection mastic, lining and insulation materials canbe replaced by another approved fire sealing system with equivalent properties.

The maximum distance of the fire damper from the structure is not limited and according to EN 15882-2, the required number of suspensions acc. to EN 1366-1:2014 must be used.

Page 32: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

32

≤ 300

≤ 300

Screw(min. 4x50)

≥ 25

≥ 25

Screws has to be fixed in wall/ceiling construction.(If it is needed use steel bracket).

Used materials - example:*3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/504 Promastop - P, K, Hilti CFS-CT5 Promatect - H6 Rockwool Wired Mat 105 th. 3x60 mm7 Rockwool Wired Mat 105 th. 60 mm

Position:1 Fire damper2 Solid wall construction3 Stuffing box (mineral stone wool min. density 140 kg/m³)4 Fire protection mastic min. thickness 1 mm5 Cement lime plate min. thickness 15 mm

(min. density 870 kg/m³)6 Stone wool with one side stitched wire fencing (min.

density 105 kg/m³), thickness 180 mm (e.g. 3x60 mm)7 Stone wool with one side stitched wire fencing (min.

density 105 kg/m³), thickness 60 mm8 Duct

≥ 40

≥ 50

≥ 100

240

180

≥ 400≥ 100 variable**

* Stuffing box, fire protection mastic, cement lime plate andinsulation materials can be replaced by another approved firesealing system for damper installation with equivalent materialproperties.

** Depends on the distance of the flap from the construction, whenthe maximum distance from the construct is not limited andaccording to EN 15882-2 must use the required number ofhinges according to EN 13366-1:2014.

Page 33: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

33

≥ 100

≥ 50

Position:1 Fire damper2 Installation frame R63 Solid wall construction4 Cement lime plate5 Duct

Page 34: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

34

≥ 40

≥ 100

Position:1 Fire damper2 Gypsum plate3 Mineral wool (type depending on the type of construction)4 Mortar or gypsum5 Duct

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Page 35: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

35

≥ 40

≥ 100

≥ 40

≥ 100

Position:1 Fire damper2 Gypsum plate3 Mineral wool

(type depending on the type of construction)4 Mortar or gypsum

≥ 10

≥ 10

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

● The installation opening for each fire damper has a minimum size ofa x b = (D + 97+3 mm) + 20 mm x (D + 97+3 mm)

or a x b = (D + 97+3 mm) x (D + 97+3 mm) + 20 mm● Gap between damper and construction is filled by mortar or gypsum● Distance between dampers 70 mm● Flange to flange connection - Up to four dampers can be installed

Page 36: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

36

Position:1 Fire damper2 Mortar or gypsum3 Stuffing box (mineral stone wool min. density 140 kg/m³)

D-20 D-20

≥ D

+100

D-2

0

≥ 10

≥ 10

≥ 100

(≥ 100)+50

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

● Gap between damper and construction is filled bymortar or gypsum and mineral wool

● Wool is fixed to damper body and construction byfire protection mastic.

● Mineral wool thickness = construction thickness+ 20 mm or 50 mm

● Installation is valid for ceiling construction

Page 37: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

37

≥ D

+100

Dimensions Number X1

Number Y

NumberZ1

900 < D ≤ 1000 12 24 6

≥ 10

≥ 10

1020

10

10

10

10

10

10

D+151+5

D+1

51+5

2xD

+313

+8

D+141+5

10

Position:1 Fire damper2 Fire damper with installation frame R1, R23 Mortar or gypsum4 Stuffing box (mineral stone wool min. density 140 kg/m³)5 Holder6 Holder L

≥ 100

≥ 100

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

It is possible to usecorresponding numberof holes and screws

It is possible to usecorresponding numberof holes and screws

● Gap between frame and damper body and frame andconstruction must be filled by glue (PROMAT K84).

● Wool is fixed to installation frame and construction byfire protection mastic.

● Installation is valid for ceiling construction

Page 38: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

38

Fitting with threaded rods

≥ 10 ≥ 20

≥ 10

≥ 10

≥ 20

Position:1 Fire damper with installation frame R52 Stuffing box (mineral stone wool min. density 140 kg/m³)3 Fitting with threaded rods or steel bracket

≥ 100

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Page 39: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

39

≤ 300

≤ 300

Screw(min. 4x50)

≥ 25

≥ 25

Position:1 Fire damper2 Gypsum plate3 Mineral wool (type depending on the type of construction)4 Stuffing box (mineral stone wool min. density 140 kg/m³)5 Fire protection mastic min. thickness 1 mm6 Cement lime plate min. thickness 15 mm

(min. density 870 kg/m³)7 Duct

Used materials - example:*3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/504 Promastop - P, K, Hilti CFS-CT5 Promatect - H

≥ 40

≥ 50

≥ 100Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Screws has to be fixed in wall/ceiling construction.(If it is needed use steel bracket).

* Fire resistant insulation and fire resistant board canbe replaced by another approved fire sealing sys-tem for damper installation with equivalent materialproperties.

Page 40: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

40

≥ 100

≥ 100 ≥ 100

Position:1 Fire damper2 Installation frame3 Gypsum plate4 Mineral wool (type depending on the type of construction)

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Page 41: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

41

Position:1 Fire damper2 Gypsum plate3 Mineral wool (type depending on the type of construction)4 Fire resistant board5 Fire stop coating thickness 1 mm6 Duct

Used materials - example:*3 Hilti CFS-CT B 1S 140/504 Hilti CFS-CT

≥ 100

D+60 to 800max. 2050

D+60 to 800max. 1650

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

* Fire resistant insulation and fire resistant board canbe replaced by another approved fire sealing sys-tem for damper installation with equivalent materialproperties.

Page 42: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

42

≥ 100

Position:1 Fire damper with installation

frame R12 Gypsum plate3 Mineral wool (type depending

on the type of construction)4 Stuffing box (mineral stone

wool min. density 140 kg/m³)

20

≥ 100

20

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

It is possible to usecorresponding numberof holes and screws

● Gap between frame and damper body and frame andconstruction must be filled by glue (PROMAT K84).

● Distance between dampers 160 mm

● Flange to flange connection - Up to four dampers canbe installed

Page 43: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

43

Position:1 Fire damper2 Installation frame R73 Solid ceiling construction4 Wall with possibility of ceiling movement

* min. 110 - Concrete/ min. 125 - Aerated concrete

* *

Page 44: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

44

Position:1 Fire damper2 Gypsum plate3 Mineral wool (type depending

on the type of construction)4 Mortar or gypsum5 Stone wool with wired mat on

one side, density 66 kg/m³6 Duct

Used materials - example:**5 Isover Ultimate Protect Wired MAT 4.0, th. 100 mm ALU1

≥ 40*

≥ 100

* Around the perimeter

Used materials - example:**4 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/505 Promastop - P, K, Hilti CFS-CT6 Isover Ultimate Protect Wired MAT 4.0, th. 100 mm ALU1

≥ 40*

≥ 100

≥ 50*

* Around the perimeter

Position:1 Fire damper2 Gypsum plate3 Mineral wool (type depending on the type

of construction)4 Mineral stone wool min.

density 150 kg/m³5 Fire protection mastic min. thickness 1 mm6 Stone wool with wired mat on one side,

density 66 kg/m³7 Duct

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

** The materials for stuffing box, fire protection mastic, lining and insulation materials canbe replaced by another approved fire sealing system with equivalent properties.

The maximum distance of the fire damper from the structure is not limited and according to EN 15882-2, the required number of suspensions acc. to EN 1366-1:2014 must be used.

** The materials for stuffing box, fire protection mastic, lining and insulation materials canbe replaced by another approved fire sealing system with equivalent properties.

The maximum distance of the fire damper from the structure is not limited and according to EN 15882-2, the required number of suspensions acc. to EN 1366-1:2014 must be used.

Page 45: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

45

≤ 300

≤ 300

Screw(min. 4x50)

≥ 25

≥ 25

Used materials - example:*3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/504 Promapyr. Rockwool Steprock HD. Hilti CFS-CT C 1S 140/505 Promastop - P, K, Hilti CFS-CT6 Promatect - H7 Rockwool Wired Mat 105 th. 3x60 mm8 Rockwool Wired Mat 105 th. 60 mm

Position:1 Fire damper2 Gypsum plate3 Mineral wool (type depending on the type of construction)4 Stuffing box (mineral stone wool min. density 140 kg/m³)5 Fire protection mastic min. thickness 1 mm6 Cement lime plate min. thickness 15 mm

(min. density 870 kg/m³)7 Stone wool with one side stitched wire fencing (min.

density 105 kg/m³), thickness 180 mm (e.g. 3x60 mm)8 Stone wool with one side stitched wire fencing (min.

density 105 kg/m³), thickness 60 mm9 Duct

≥ 100

180

240

≥ 100 variable** ≥ 400

≥ 40

≥ 50

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Screws has to be fixed in wall/ceiling construction.(If it is needed use steel bracket).

* Stuffing box, fire protection mastic, cement lime plate andinsulation materials can be replaced by another approved firesealing system for damper installation with equivalent materialproperties.

** Depends on the distance of the flap from the construction, whenthe maximum distance from the construct is not limited andaccording to EN 15882-2 must use the required number ofhinges according to EN 13366-1:2014.

Page 46: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

46

Position:1 Fire damper2 Solid ceiling construction3 Mortar or gypsum4 Duct

* min. 110 - Concrete/ min. 125 - Aerated concrete

≥ 40

Page 47: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

47

≥ 40

*

≥ 40

*

* min. 110 - Concrete/ min. 125 - Aerated concrete

Position:1 Fire damper2 Solid ceiling construction3 Mortar or gypsum

≥ 10

≥ 10

● Installation opening for each damper has minimal dimensionsD+80 mm (D+160 mm for dampers with flanges)

● Gap between damper and construction is filled by mortar or gypsum● Distance between dampers 70 mm● Flange to flange connection - Up to four dampers can be installed

Page 48: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

48

≤ 300

≤ 300

Screw(min. 4x50)

≥ 25

≥ 25

Used materials - example:**3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/504 Promastop - P, K, Hilti CFS-CT5 Promatect - H

* min. 110 - Concrete/ min. 125 - Aerated concrete

Position:1 Fire damper2 Solid ceiling construction3 Stuffing box (mineral stone wool min. den-

sity 140 kg/m³)4 Fire protection mastic min. thickness 1 mm5 Cement lime plate min. thickness 15 mm

min. density 870 kg/m³6 Duct

≥ 40≥ 50

Screws has to be fixed in wall/ceiling construction.(If it is needed use steel bracket).

** Fire resistant insulation and fire resistant board can bereplaced by another approved fire sealing system fordamper installation with equivalent material properties.

Page 49: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

49

*

* *

* min. 110 - Concrete/ min. 125 - Aerated concretePosition:1 Fire damper2 Installation frame3 Solid ceiling construction

Page 50: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

50

** Fire resistant insulation and fire resistant board can bereplaced by another approved fire sealing system fordamper installation with equivalent material properties.

Position:1 Fire damper2 Solid ceiling construction3 Fire resistant board4 Fire stop coating thickness 1 mm5 Duct

* min. 110 - Concrete/ min. 125 - Aerated concrete

Used materials - example:**3 Hilti CFS-CT B 1S 140/504 Hilti CFS-CT

*

D+60 to 800max. 1650

D+60 to 800max. 2050

Page 51: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

51

20

* min. 110 - Concrete/ min. 125 - Aerated concrete

Position:1 Fire damper with installa-

tion frame R22 Solid ceiling construction3 Mineral stone wool min.

density 140 kg/m³

20

*

*

● Gap between frame and damper body and frame andconstruction must be filled by glue (PROMAT K84).

● Distance between dampers 160 mm

● Flange to flange connection - Up to four dampers can be installed

It is possible to usecorresponding numberof holes and screws

Page 52: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

52

Used materials - example:**

4 Rockwool Wired Mat 105 th. 3x60 mm5 Rockwool Wired Mat 105 th. 60 mm

Position:1 Fire damper2 Solid ceiling construction3 Mortar or gypsum4 Stone wool with one side stitched wire fencing (min.

density 105 kg/m³), thickness 180 mm (e.g. 3x60 mm)5 Stone wool with one side stitched wire fencing (min.

density 105 kg/m³), thickness 60 mm6 Duct

* min. 110 - Concrete/ min. 125 - Aerated concrete

≥ 40

180240

≥ 100

*

variable***

≥ 400

** Stuffing box, fire protection mastic, cement lime plate and insulation materials can bereplaced by another approved fire sealing system for damper installation with equivalentmaterial properties.

*** Depends on the distance of the flap from the construction, when the maximum distancefrom the construct is not limited and according to EN 15882-2 must use the requirednumber of hinges according to EN 13366-1:2014.

Page 53: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

53

Position:1 Fire damper2 Solid ceiling construction3 Concrete B204 Rebar5 Duct

Position:1 Fire damper2 Solid ceiling construction3 Installation frame R54 Concrete B205 Rebar6 Duct

** Around the perimeter* min. 110 - Concrete/ min. 125 - Aerated concrete

≤ 100

≤ 100

≤ 100

≤ 100

30**

≥ 100**≥ 50**

*

≤ 750

≤ 750

30**

≥ 100**≥ 50**

*

** Around the perimeter* min. 110 - Concrete/ min. 125 - Aerated concrete

Page 54: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

54

Position:1 Fire damper2 Installation frame R63 Solid ceiling construction4 Cement lime plate5 Duct

≥ 50

*

* min. 110 - Concrete/ min. 125 - Aerated concrete

Page 55: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

55

Shaft wall is a vertical, non-bearing partition construction meeting the double-sided fire requirements. Theshaft wall can be mounted only from one side. No mineral insulation is used in the construction.

First of all, the shaft wall structure must be laid out. Apart from other vertical constructions, the perimetersections must be fitted with connection sealing made from A1 or A2 fire reaction materials (for instancefloor strips Orsil N/PP). The perimeter sections must be anchored using steel plugs Ø 6 mm (for exampleDN6 or ZHOP) with 500 mm span.

Sheathing is carried out using two layers of Glasroc F boards Ridurit with 20 mm thickness, the boards areoriented horizontally. First sheathing layer is fixed with TN 212 screws in spacing 200mm to the supportstructure. The boards are mounted to tight butt joints without need of cementing. The second sheathinglayer is screwed to the first sheathing layer using screws Rodurit in square net 250 mm. Reset of joints ofthe first and second layer of Ridurit sheathing is set to 600 mm vertically and 300 mm horizontally.

Vertical intermediate R-CW sections are fixed in 1000 mm layout spacing between R-UW sections andvertical perimeter R-CW sections.

Maximum width of the shaft wall is 2 metres in this case (board length). Steel squares made from steelgalvanized plate metal 40/20/1 mm are used as perimeter sections, they are anchored to bearing wall usingØ 6 mm steel plugs (for example DN6 or ZHOP) with 500 mm spacing.

Rigips solution is shown here as an example. Alternatively it is possible to apply thesolution from Knauf or Promat. In such a case follow the instructions of the producer.

250

max. 2000

200

1000

250

200

250

250

Page 56: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

56

Position:1 Fire damper2 Mortar or gypsum3 Fire resistant board4 Profile 50 UW or 50 CW5 Screw6 Additional fire resistant board

Used materials - example:*3 Glasroc F Ridurit th. 20 mm4 R-CW5 Screw Ridurit6 Glasroc F Ridurit th. 20 mm

* It is alternatively possible to use Knauf or Promat solution.

≥ 100

≤ 25050

≤ 250

50

≥ 50

50 20

20

110

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Page 57: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

57

≥ 100

≤ 250

50

20

20

80

Position:1 Fire damper2 Installation frame R13 Holder (including in installa-

tion frame R1 packing)4 Fire resistant board5 Screw6 Additional fire resistant board7 Fire resistant foam tape

Used materials - example:*4 Glasroc F Ridurit th. 20 mm5 Screw Ridurit6 Glasroc F Ridurit th. 20 mm7 Promaseal XT

≤ 25050

It is possible to usecorresponding numberof holes and screws

* It is alternatively possible to use Knauf or Promat solution.

Gap between frame and thin shaft wall construction must be filled by glue (PROMAT K84). Dampers has to be suspended in an appropriate manner see chapter 9

Page 58: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

58

R1 Cementlime √ ≥100 √ ≥150 √ ≥100 - - - -

R2 Cementlime √ ≥150 √ ≥150 √ ≥100 - - - -

R3 Cementlime √ ≥100 √ ≥150 √ ≥100 - - - -

R4 Cementlime √ ≥150 √ ≥150 √ ≥100 - - - -

R5 Cementlime - - - - - - Solid ceiling

construction *) ≥150 √ ≥100

R6 Cementlime - - - - - - √ ≥100/

≥150 - -

R7 Cementlime - - - - √ **) ≥100 - - - -

Page 59: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

59

Installation frames R1, R2 are suitable for:● Solid wall construction● Gypsum wall construction● Solid ceiling construction

On the inside and outside is installation frame equipped by intumescent sealing. It enlarges its capacityand air proofs the gap between damper body and installation frame and between installation frame andwall construction.

● Gypsum wall construction has to be installed according manufacture requirements.

● Installation frame: cement lime plates● Fasteners: galvanized plate

● a x b = (D + 141+3mm) x (D + 141+3mm)

≥ 100

*

Gap between frame end damper body and frame and solid (gypsum)wall construction must be filled by glue (PROMAT K84).

Dampers has to be suspended in an appropriate manner see chapter 9.

* min. 110 - Concrete/ min. 125 - Aerated concrete

Position:1 Fire damper with installation frame R1 or R22 Holder

≥ 100

It is possible to usecorresponding numberof holes and screws

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Page 60: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

60

Installation frame R3, R4 are suitable for:● Solid wall construction● Gypsum wall construction● Solid ceiling construction

On the inside and outside is installation frame equipped by intumescent sealing. It enlarges its capacityand air proofs the gap between damper body and installation frame and between installation frame andwall construction.

● Gypsum wall construction has to be installed according manufacture requirements.

● Installation frame: cement lime plates● Fasteners: galvanized plate

● d = (D + 111+3mm)

≥ 100

*

* min. 110 - Concrete/ min. 125 - Aerated concrete

Position:1 Fire damper with installation frame R3 or R42 Holder

≥ 100

Gap between frame end damper body and frame and solid (gypsum)wall construction must be filled by glue (PROMAT K84).

Dampers has to be suspended in an appropriate manner see chapter 9.

It is possible to usecorresponding numberof holes and screws

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Page 61: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

61

Installation frame R5 is suitable for:● Instalaci on solid wall/ceiling construction● Installation on gypsum wall construction● Instalaci outside solid ceiling constructions with concreteOn the inside is installation frame equipped by intumescent sealing. It enlarges its capacity and airproofs the gap between installation frame and damper body.

● Gypsum wall construction has to be installed according manufacture requirements.

● Installation frame: cement lime plates and galvanized plate● Fasteners: galvanized plate

● d = (D + 10+3mm)● d = (D + 100+3mm) installation with concrete

30

≥ 100**

≥ 100

≥ 100

* min. 110 - Concrete/ min. 125 - Aerated concrete

*

≤ 100

≤ 100

* ** Around the perimeter

Position:1 Fire damper with installation frame R52 Fitting with threaded rods or steel bracket3 Concrete B204 Rebar

≤ 750

Installation opening has tobe reinforced by profile(UW, CW). Profil is fixed byscrews ≥3,5 mm with corre-sponding length. Distancebetween screws ≤200 mm.

Page 62: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

62

Installation frame R6 is suitable for:● Installation outside solid wall/ceiling construction with cement lime platesOn the inside is installation frame equipped by intumescent sealing. It enlarges its capacity and airproofs the gap between installation frame and damper body.

● Installation frame: cement lime plates● Fasteners: galvanized plate

● d = (D +100+3mm)

80

≤ 300

≤ 300

20

40

20

≥ 100

≤ 300

≤ 300

≤ 300

20

20

≤ 300

40

40Screw(min. 4x80)

Screw(min. 4x80)

≤ 300

20

20

≤ 300

Screw(min. 4x80)

Screw(min. 4x80)

80

≤ 300

≤ 30020

20

*

Screws has to be fixed in wall/ceiling construction.(If it is needed use steel bracket).

All parts are glued with glue PromatK84 and secured by screws.

Dampers has to be suspended in anappropriate manner see chapter 9

Position:1 Fire damper with installation frame R62 Cement lime plates min. thickness 40 mm

(min. density 450 kg/m³)3 Cement lime prisms min. thickness 40 mm

(min. density 450 kg/m³)

* min. 110 - Concrete/ min. 125 - Aerated concrete

≤ 300

40

40

≤ 300

Screw(min. 4x80)

40

Screw(min. 4x80)

Page 63: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

63

2

XD+60

D+1

41+x

+y

D+141

D+60

D+1

41+x

D+141

Y

X = Ceiling movement (max. 40 mm)Y = Distance of movement (max. 80 mm)

Position:1 Fire damper with installation frame R72 Cement lime filling min. density 450 kg/m³3 Ceiling movement: construction th. 100 mm4 Threaded rod5 Nut6 Washer Ø 35 mm

Ceiling sag

X

Ceiling sag

210

Fitting with threaded rods or steel bracket.

● For ceiling movement ≥10 mm

Installation frame R7 is suitable for gypsum wall construction with ceiling movement possibility. Distanceof movement “x”.On the inside and outside is installation frame equipped by intumescent sealing. It enlarges its capacityand air proofs the gap between damper body and installation frame and between installation frame andwall construction.

Damper position:● Directly on the ceiling● In distance from ceiling max. 80 mm

● Installation frame: cement lime plates● Fasteners: galvanized plate

Page 64: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

64

Mounting to the ceiling wall

Position:1 Threaded rod M8 – M202 Nut3 Washer4 Coupling Nut5 Anchor6 Hinge plate - min. thickness 10 mm

2xØ9

120

80

50

²

M8 366 22 44M10 58 35 70M12 84,3 52 104M14 115 70 140M16 157 96 192M18 192 117 234M20 245 150 300

4xØ9

M20

100

150

M8 to M16

Page 65: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

65

Fire dampers can be suspended by using threaded rods and a mounting profiles. Load thesuspension system depend on weight of the fire damper.

Damper assembly procedures must be done so as all load transfer from the fire separatingconstructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping must be hung or supported so as all load transfer from the back-to-back piping to the damper isabsolutely excluded.

Threaded rods longer than 1,5 m require fire-resistant insulation.

Threaded rod fixing to the ceiling construction - see fig. 75

Fire dampers can be suspended by using threaded rods and a mounting profiles. Load thesuspension system depend on weight of the fire damper.

Damper can be suspended from the ceiling construction or supported above the ceiling construc-tion. Damper assembly procedures must be done so as all load transfer from the fire separatingconstructions to the damper body is absolutely excluded. Back-to-back air-conditioning pipingmust be hung or supported so as all load transfer from the back-to-back piping to the damper isabsolutely excluded.

Threaded rods longer than 1,5 m require fire-resistant insulation.

Position:1 Fire damper2 Damping pad3 Extension piece4 Threaded rod5 Suspension ring

Examples of using materials:

Page 66: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

66

Damper must be firmly connected with extension piece by screws or rivets.

Position:1 Fire damper2 Damping pad3 Extension piece4 Threaded rod5 Mounting rail6 Nut7 Washer8 Screw connection9 Mounting profile10 Bolt11 Screw or rivet

Examples of using materials:

Page 67: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

67

Duct between fire damper and fire separating construction can be suspended by using threadedrods and suspension rings. Load the suspension system depend on weight of the fire damper andduct system.

Max. length between two suspension systems is 1500 mm.

Damper assembly procedures must be done so as all load transfer from the fire separatingconstructions to the damper body is absolutely excluded. Back-to-back air-conditioning pipingmust be hung or supported so as all load transfer from the back-to-back piping to the damper isabsolutely excluded.

Threaded rod fixing to the ceiling construction.

The insulation boards are fastened to the duct by weld pins. Distance between weld pins,distance between weld pins and flanges is dependent on the materials. For more information seedocumentation of insulation manufacturer.

Position:1 Fire damper2 Duct3 Insulation4 Threaded rod5 Suspension ring6 Weld pin

Page 68: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

68

p =w2

Pressure loss calculation

p [Pa] presure loss

w [m.s ] air flow speed in nominal damper section

[kg.m ] air density

[-] coefficient of local pressure loss for the nominal damper section(see Tab. 11.1.1.)

Determination of pressure loss by using diagram = 1,2 kg.m

Page 69: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

69

Level of acoustic output corrected with filter A.

Coefficient of local pressure loss (-)

LWA = LW1 + 10 log(S) + KA

LWA [dB(A)] level of acoustic output corrected with filter A.

LW1 [dB] level of acoustic output LW1 related to the 1 m² section (see Tab. 12.3.1.)

S [m²] duct cross section

KA [dB] correction to the weight filter A (see Tab. 12.3.2.)

Level of acoustic output in octave ranges.

LWoct = LW1 + 10 log(S) + Lrel

LWoct [dB] spectrum of acoustic output in octave range

LW1 [dB] level of acoustic output LW1 related to the 1 m² section (see Tab. 12.3.1.)

S [m²] duct cross section

Lrel [dB] relative level expressing the shape of the spectrum (see Tab. 12.3.3.)

0,090 0,083

Page 70: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

70

9 11,5 14,7 16,9 20,1 22,3 24,1 27,2 29,4 31,2 32,6 33,8

16,7 22,1 25,3 27,5 30,7 32,9 34,6 37,8 40 41,7 43,2 44,4

24,2 29,6 32,8 35 38,1 40,4 42,1 45,3 47,5 49,2 50,7 51,9

30,0 35,4 38,6 40,8 44 46,2 47,9 51,1 53,3 55,1 56,5 57,7

34,8 40,2 43,3 45,6 48,7 51 52,7 55,8 58,1 59,8 61,2 62,4

38,8 44,2 47,3 49,6 52,7 55 56,7 59,9 62,1 63,8 65,2 66,4

42,3 47,7 50,8 53,1 56,2 58,4 60,2 63,3 65,6 67,3 68,7 69,9

45,4 50,7 53,9 56,1 59,3 61,5 63,3 66,4 68,6 70,4 71,8 73

48,1 53,5 56,6 58,9 62 64,3 66 69,1 71,4 73,1 74,5 75,7

50,6 56 59,1 61,4 64,5 66,7 68,5 71,6 73,9 75,6 77 78,2

52,8 58,2 61,4 63,6 66,8 69 70,7 73,9 76,1 77,9 79,3 80,5

-15,0 -11,8 -9,8 -8,4 -7,3 -6,4 -5,7 -5,0 -4,5 -4,0 -3,6

-4,5 -6,9 -10,9 -16,7 -24,1 -33,2 -43,9 -56,4

-3,9 -5,3 -8,4 -13,1 -19,5 -27,6 -37,4 -48,9

-3,9 -4,5 -6,9 -10,9 -16,7 -24,1 -33,2 -43,9

-4,0 -4,1 -5,9 -9,4 -14,6 -21,5 -30 -40,3

-4,2 -3,9 -5,3 -8,4 -13,1 -19,5 -27,6 -37,4

-4,5 -3,9 -4,9 -7,5 -11,9 -17,9 -25,7 -35,1

-4,9 -3,9 -4,5 -6,9 -10,9 -16,7 -24,1 -33,2

-5,2 -3,9 -4,3 -6,4 -10,1 -15,6 -22,7 -31,5

-5,5 -4 -4,1 -5,9 -9,4 -14,6 -21,5 -30

-5,9 -4,1 -4 -5,6 -8,9 -13,8 -20,4 -28,8

-6,2 -4,3 -3,9 -5,3 -8,4 -13,1 -19,5 -27,6

Table of acoustics values

Page 71: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

71

Damper bodies are supplied in the design made of galvanized plate without any other surfacefinishing.Damper blades are made of fire resistant asbestos free boards made of mineral fibres.

Control devices of dampers has cover from mechanically resistant and standing plastic and restof the parts is galvanised without further surface treatment.

Springs are galvanized.Thermal protective fuses are made of sheet brass, thickness = 0.5 mm.

Fasteners is galvanized. Fasteners is galvanized.

According to the customer's requirements, damper can be made of stainless material.

Specifications for stainless-steel models – classification of stainless steel:

● Class A2 – Food-grade stainless steel (AISI 304 – ČSN 17240)● Class A4 – Chemistry-grade stainless steel (AISI 316, 316L – ČSN 17346, 17349)

The respective stainless steel is the material for all components present or accessing the damperinterior; components outside the damper body are typically from galvanised sheet metal(fasteners for mounting the servo drive or mechanics, mechanics components except Item 4),frame components.

The following components, including the fasteners, are made from stainless steel at all times:

1) Damper body and all components permanently attached2) Leaf holders, including pins, metal parts of leaf3) Control components inside the damper (leaf angle selector, pin with lever)4) Mechanical components entering the interior of damper body (lower sheet of mechanics,

lock holder “1”, lock lever “2”, lock spring, 8 dia. stopper pin, mechanics pin)5) Inspection hole cover including the clip and fasteners (if they are parts of the cover)6) Bearing for torque transfer from the lever with pin on the angle selector at the leaf (made

from AISI 440C)

The leaf of the damper is made from a single piece of homogeneous material Promatect-MST,thickness 40 mm.

Plastic, rubber and silicon components, sealants, foaming bands, glass-ceramic seals, housings,brass bearings of the leaf, servo drives, and end switches are identical for all material variants ofthe dampers.

The thermal link is identical for all material variants of the dampers. Upon specification bycustomer, the thermal link may be made from A4 stainless steel. The solder is standard,corresponding to the initialisation temperature.

The temperature-dependent initiator of the servo drive (sensor) is modified for stainless-steelvariants of the dampers; the standard galvanised screws are replaced with stainless-steel M4screws of corresponding class the counterpart has stainless-steel riveting M4 nuts.

Some fasteners and components are available in one class of stainless steel; the type will beused in all stainless-steel variants.

The leaf in the variants for chemical environments (Class A4) is always treated with a coating ofchemically resistant Promat SR.

Any other requirements for the design shall be considered atypical and shall be addressed on anindividual basis.

Page 72: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

72

The appliance is constructed and preset by the manufacturer, its operation is dependent onproper installation and adjustment.

Dampers are transported by box freight vehicles without direct weather impact, there must notoccur any sharp shocks and ambient temperature must not exceed +40°C. Dampers must beprotected against mechanic damages when transported and manipulated. During transportation,the damper blade must be in the "CLOSED" position.

Dampers are stored indoor in environment without any aggressive vapours, gases or dust. Indoortemperature must be in the range from -30°C to +40°C and maximum relative humidity 95 %(avoid condensation on the damper body). Dampers must be protected against mechanicdamages when transported and manipulated.

All effective safety standards and directives must be observed during fire damper assembly.

The damper body should not be deformed in the course of bricking in. Once the damper is builtin, its blade should not grind on the damper body during opening or closing.

To ensure reliable fire damper function it is necessary to avoid blocking the closing mechanismand contact surfaces with collected dust, fibre and sticky materials and solvents.

Page 73: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

73

Before entering the dampers into operation after their assembly and by sequential checks, thefollowing checks must be carried out. Visual inspection of proper damper integration , insidedamper area, damper blade, contact surfaces and silicon sealing. Check of thermal protectivefuse and closing mechanism. Check the closing function of the damper blade. This can be doneby removing of thermal fuse from damper body.

Before entering the dampers with actuating mechanism into operation after their assembly andby sequential checks. Check of blade displacement into the breakdown position "CLOSED" canbe done after cutting off the actuating mechanism supply (e.g. by pressing the RESET button atthe thermoelectrical starting mechanism BAT or cutting off the supply from ELECTRICAL FIRESIGNALISATION). Check of blade displacement back into the "OPEN" position can be done afterrestoration of power supply (e.g. by releasing the RESET button or restoration of supply fromELECTRICAL FIRE SIGNALISATION). Without power supply, the damper can be operatedmanually and fixed in any required position. Release of the locking mechanism can be achievedmanually or automatically by applying the supply voltage. It is recommended to provide periodicalchecks, maintenance and service actions on Fire Equipment by Authorized persons. The author-ized persons can be trained by Producer, or by authorized Distributor. All effective safetystandards and directives must be observed during fire damper assembly.

For regular or exceptional inspection of interior of fire damper, micro-camera device can be used.On each fire damper is ispection hole. In the case of inspection by camera, take out the blackrubber cap, insert the camera inside the damper, check interior and at the end of inspection, putthe rubber cap back tightly to cover the empty hole.

Before entering the dampers with manual control (design .01, .11, .80) into operation after theirassembly and by sequential checks and following checks must be carried out.

Adjustment of damper blade in position "CLOSED" shall be made following:

• Damper is in „OPEN“ position.• By pressing control button mechanism, you close damper in "CLOSED" position.• Check damper blade adjustment in "CLOSED" position.• Closing must be strong and control lever must be in "CLOSED" position.• If closing is not sufficiently strong and damper control lever is not in "CLOSED" position, you

must contact manufacturer and order new mechanism.• Mechanism dimension is marked M1 to M4, according to internal forces of spring.

Adjustment of damper blade in position "OPEN" shall be made following:

• Rotate control lever by 90°.• Lever get fasten automatically in “OPEN” position.• Check damper blade adjustment in "OPEN" position.

• To check the function and the status of the fuse is possible to remove whole mechanism fromthe body of fire damper - mechanism is attached to the dampers body with four screws M6.

• Removing the thermal fuse from the fuse holder of initiation device, check its correctfunctionality.

• There must be a release lever, which releases initiation lever of control and mechanism willdisplace to "CLOSED" position.

• If not, you need to contact the manufacturer and order new mechanism.• Mechanism dimension is marked M1 to M4, according to internal forces of spring.

Page 74: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

74

Manual operation Without power supply, the damper can be operated manually and fixed in any required position.

Release of the locking mechanism can be achieved manually or automatically by applying thesupply voltage.

It is recommended to provide periodical checks, maintenance and service actions on FireEquipment by Authorized persons schooled by Producer.

All effective safety standards and directives must be observed during fire damper assembly.

Before entering the dampers with actuating mechanism into operation after their assembly andby sequential checks and following checks must be carried out.

Check of blade displacement into the breakdown position "CLOSED" can be done after cuttingoff the actuating mechanism supply (e.g. by pressing the RESET button at the thermoelectricalstarting mechanism BAT or cutting off the supply from ELECTRICAL FIRE SIGNALISATION).Check of blade displacement back into the "OPEN" position can be done after restoration ofpower supply (e.g. By releasing the RESET button or restoration of supply from ELECTRICALFIRE SIGNALISATION).

Dampers could be displaced into position “CLOSED” only in case that ventilator, or Air HandlingUnit is switched off. The goal is the securing of proper closing and safe function of Fire Damperin case of Fire.

Spare parts are supplied only on basis of an order.

Control for square damper and round damper is identical.

If fuse Tf1 is initiated (duct outside temperature) than is necessary to change thermoelectricalstarting mechanism BAT72B-S. Whereas is initiation temperature higher than actuator mecha-nism operating temperature +50°C, recommended actuating mechanism manufacturer makecomplete revision or change actuating mechanism and thermoelectrical starting mechanism.

If fuses Tf2/Tf3 are initiated (duct inside temperature) than is possible change only part ZBAT72or ZBAT95 (according initiating temperature).

Page 75: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

75

Technical specifications

Design according Tab. 20.1.1.

Nominal size

P - with round duct flangeSL - spiro damper with rubber sealing

type

Manual and thermal .01Manual and thermal (ZONE 1, 2) .02Manual and thermal with a terminal switch („CLOSED“) .11Manual and thermal with a terminal switch („CLOSED“) (ZONE 1, 2) .12With actuating mechanism BF 230-TN .40With actuating mechanism BF 24-TN, with smoke detector ORS 142 K and with supply deviceBKN 230-24-MOD (voltage AC 230 V) .41

With actuating mechanism ExMax-15-BF (AC 230 V, AC/DC 24 V) with thermoelectrical startingmechanism (ZONE 1,2) .42

With actuating mechanism BF 24-TN .50With actuating mechanism BF 24-TN, with smoke detector ORS 142 K (voltage AC/DC 24 V) .51With communication and supply device BKN 230-24 and with actuating mechanism BF 24-TN-ST .60With communication and supply device BKN 230-24-C-MP, with actuating mechanism BF 24-TN-ST and with smoke detector ORS 142 K .61

With communication and supply device BKN 230-24MP and with actuating mechanism BF 24TL-TN-ST (Top-Line) for connection to MP-Bus .62

With communication and supply device BKN 230-24-MOD, with actuating mechanism BF 24-TN-ST and with smoke detector ORS 142 K .63

With communication and supply device BKN 230-24LON and with actuating mechanism BF 24TL-TN-ST (Top-Line) for connection to LonWorks .64

Manual and thermal with two terminal switches („OPEN“, „CLOSED“) .80Manual and thermal with two terminal switches („OPEN“, „CLOSED“) (ZONE 1,2) .81

Page 76: production, designing, ordering, delivery, storage, assembly, … · 2020-06-29 · mechanism BAT is activated, when the reset button on BAT is pressed or when the power supply to

76

Data label is placed on the damper body.

The producer reserves the right for innovations of the product. For actual product information seewww.mandik.com

MANDÍK, a.s.Dobříšská 55026724 HostomiceCzech RepublicTel.: +420 311 706 706E-Mail: [email protected]

WEIGHT (kg):

Dobříšská 550, 267 24 Hostomice, Czech RepublicMANDÍK, a.s.

ACTUATING SYSTEM:

YEAR/SER.NO.:

DIMENSION:

1391EN 15650:2010 TPM 145/20

R

FIRE PROTEC. CLASS:

MANUAL

Cert. No.: 1391-CPR-2016/0158, DoP: PM/FDMA-PM/01/20/1