Page 1: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

PRODUCTSCOMMERCIAL BUILDING WIRE & CABLE

Page 2: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Table of content

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Generated 8/2/18 www.nexans.us Page 2 / 87

About Nexans 3

Commercial Building Wire & Cable 4

Armored 5

ENERGEX® AC-HCF - Green Striped Armor 6

ENERGEX® AC 9

ENERGEX® MC 120 Aluminum Armored PVC Jacketed 12

ENERGEX® MC 120 Aluminum Armored Unjacketed 16

ENERGEX® MC 120 Steel Armored 20

ENERGEX® MC 277 Aluminum Armored 24

ENERGEX® MC Aluminum Feeder Cable 28

ENERGEX® MC Ground Plus 33

ENERGEX® MC Mega Neutral 37

ENERGEX® MC Multi Conductor 42

Direct Buried 47

ENERGEX® 8000 RHH/RHW-2/USE-2 Aluminum 48

ENERGEX® RHH/RHW-2/USE-2 Copper 52

Conduit Wire & Cable 56

ENERGEX® 8000 Aluminum XHHW-2 57

ENERGEX® INSTAGLIDE® THHN / THWN-2 / MTW 61

ENERGEX® INSTAGLIDE® XHHW-2 Copper 65

Components, Specialty & Bare Copper 69

ENERGEX® PV/RHH/RHW-2/USE-2 70

Soft Bare Copper USA* 85

Page 3: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

About Nexans

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Generated 8/2/18 www.nexans.us Page 3 / 87

Nexans brings energy to life through an extensive range of cables and cabling solutions that deliver increasedperformance for our customers worldwide. Nexans’ teams are committed to a partnership approach that supportscustomers in four main business areas: Power transmission and distribution (submarine and land), Energy resources(Oil & Gas, Mining and Renewables), Transportation (Road, Rail, Air, Sea) and Building (Commercial, Residential andData Centers). Nexans’ strategy is founded on continuous innovation in products, solutions and services, employeedevelopment, customer training and the introduction of safe, low-environmental-impact industrial processes.In 2013, Nexans became the first cable player to create a Foundation to introduce sustained initiatives for access toenergy for disadvantaged communities worldwide.We have an industrial presence in 40 countries and commercial activities worldwide, employing close to 26,000 peopleand generating sales in 2015 of 6.2 billion euros.Nexans is listed on Euronext Paris, compartment A.

Page 4: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Generated 8/2/18 www.nexans.us Page 4 / 87

Nexans wide assortment of safe, reliable and environmentally friendly commercialbuilding cables assure ease of installation and provide for the safety and efficiencyof low and high-rise offices, retail establishments and public buildings such asschools, hospitals and libraries.

Choose the cable type required:

Page 5: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ArmoredContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Generated 8/2/18 www.nexans.us Page 5 / 87

Cables with interlocked metal tape armor or continuous metal sheath are suitablefor applications where cable might be exposed to mechanical damage.The Nexansarray of armored cables encompasses superior designs with rugged jackets fordirect buried applications while our jacketed and unjacketed cables aremanufactured for extreme conditions to withstand the dangers of physical andenvironmental damage that could be a factor when employed in exposed runs.

Page 6: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® AC­HCF ­ Green StripedArmor

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 6 / 87

STANDARDS

National UL 4; UL 83

Green Striped Aluminum Armored AC Cable for Health Care Facility, UL Type AC THH,600 V, 90°C dry rated - Copper Conductors - RoHS compliant

DESCRIPTIONENERGEX® AC-HCF cables may be used for branch, feeder and service fordistribution in commercial, industrial, and multi-residential construction. They may beused in patient areas of hospitals, out-patient centers and medical and dental offices.They are not permitted where hazardous anesthetizing is performed. They may also beused in applications which require AC cable with a redundant ground in accordancewith NEC Article 250.118(8). They are suitable for installations in accordance with NECArticle 320. These cables may be installed exposed, concealed or in cable tray andmay be run in spaces used for environmental air in accordance with NEC Article300.22(C) ONLY.

Nexans AC HCF cable is RoHS compliant.

Construction

Conductor:

Solid conductors are soft bare annealed copper to ASTM B3. Stranded conductors aresoft bare annealed copper to ASTM B3 and ASTM B8.

Insulation:PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1flame test.

Bond Wire:Longitudinal aluminum bond wire in continuous contact with armor.

Ground Wire:Green PVC/Nylon Type THHN insulation, sized in accordance with NEC and UL.

Assembly:Conductors are individually paper wrapped and cabled with a marker tape/coreprotection tape combination which assembles the core in an essentially roundconfiguration.

Armor:Interlocking aluminum tape armor applied directly over the core. Armor has anintermittent green stripe to identify HCF cable.

Marker Tape Print:ALUMINUM ARMORED CABLE NOT FOR USE ON DC CIRCUITS / CAUTION NOTTO BE USED WITH SET SCREW CONNECTOR / FOR CT USE LEAD FREE (MFGDATE)

Specifications

Meets UL 4: Armored Cable•Meets UL 83: Thermoplastic-Insulated Wires and Cables•Meets UL 1581: Reference Standard for Electrical Wires, Cables, and Flexible Cords•Designated Type AC per NEC Article 320•Meets UL 2556: Wire and Cable Test Methods•Meets NEC Articles: 250.94, 250.118(8), 300.22(C), 320, 517.13 and 645•

Page 7: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® AC­HCF ­ Green StripedArmor

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 7 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

ENERGEX® AC­HCF ­ GREEN STRIPED ARMOR

PartNumber

Number ofConductors

ConductorSizeAWG

GroundSizeAWG

CircuitConductorColor Code

Nominal Diameterover Armor

Approximate NetCable Weight

Ampacity(Amps)

inches mm lb/kft kg/km 60ºC75ºC90ºC

250 ft coil1000 ft reel

671560 672170 2 12 (1) 12 (1) white/black 0.49 12.4 133 198 20 20 20

672188 672196 3 12 (1) 12 (1) white/black/red 0.52 13.2 157 234 20 20 20

673426 673434 4 12 (1) 12 (1) white/black/red/blue 0.55 13.9 187 278 20¹ 20¹ 20¹

673715 2 10 (1) 10 (1) white/black 0.50 12.8 181 269 30 30 30

3 10 (1) 10 (1) white/black/red 0.54 13.6 226 336 30 30 30

673756 4 10 (1) 10 (1) white/black/red/blue 0.59 14.9 279 415 30¹ 30¹ 30¹

2 12 (19) 12 (19) white/black 0.49 12.4 133 198 20 20 20

3 12 (19) 12 (19) white/black/red 0.52 13.2 157 234 20 20 20

Bend Radius: 7 × overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in araceway or direct buried at 30°C ambient temperature.60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 AWG through 1 AWG.75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C - Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC Table 310.15(B) (16).• NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temprature and number of conductors havebeen applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).¹ Where the 4th (white) conductor is the neutral of a balanced 3 phase system.

SELLING INFORMATION

Product Features

Page 8: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® AC­HCF ­ Green StripedArmor

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 8 / 87

Cables are UL listed as Type AC, 600 V •UL listed insulated conductors •UL listed for use in cable trays per NEC Article 320.10(2) •Temperature rating of 90ºC dry •Excellent mechanical and physical properties •Lightweight aluminum armor with intermittent green stripe to identify HCF cable •Standard Nexans ENERGEX® AC-HCF is RoHS compliant•

Options

The following constructions can be provided on special orders:

Special conductor counts•

Page 9: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® ACContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 9 / 87

STANDARDS

National UL 4; UL 83

Aluminum Armored AC Cable UL Type ACTHH, 600 V, 90°C dry rated - CopperConductors - RoHS compliant

DESCRIPTIONApplications

ENERGEX® AC cables may be used for branch, feeder and service for distribution incommercial, industrial, and multi-residential construction. They are suitable forinstallations in accordance to NEC Article 320. These cables may be installedexposed, concealed or in cable tray and may be run in spaces used for environmentalair in accordance with NEC Article 300.22(C) ONLY.

Nexans ACTHH cable is RoHS compliant.

Construction

Conductor:

Solid conductors are soft bare annealed copper to ASTM B3. Stranded conductors aresoft bare annealed copper to ASTM B3 and ASTM B8.

Insulation:

PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1flame test.

Bond Wire:

Longitudinal aluminum bond wire in continuous contact with armor.

Assembly:

Conductors are individually paper wrapped and cabled with a marker tape/coreprotection tape combination which assembles the core in an essentially roundconfiguration.

Armor:

Interlocking aluminum tape armor applied directly over the core.

Marker Tape Print:

ALUMINUM ARMORED CABLE NOT FOR USE ON DC CIRCUITS / CAUTION NOTTO BE USED WITH SET SCREW CONNECTOR / FOR CT USE LEAD FREE (MFGDATE)

Specifications:

Meets UL 4: Armored Cable•Meets UL 83: Thermoplastic-Insulated Wires and Cables•Meets UL 1581: Reference Standard for Electrical Wires, Cables, and Flexible Cords

Meets UL 2556: Wire and Cable Test Methods•Designated Type AC per NEC Article 320•

Page 10: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® ACContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 10 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

ENERGEX® AC

Numberof

Conductors

ConductorSizeAWG

CircuitConductorColor Code

Nominal Diameterover Armor

Approximate NetCable Weight Ampacity (Amps)

inches mm lb/kft kg/km 60ºC 75ºC 90ºC2 14 (1) white/black 0.48 12.1 89 132 15 15 15

3 14 (1) white/black/red 0.50 12.6 109 162 15 15 15

2 12 (1) white/black 0.50 12.8 109 162 20 20 20

3 12 (1) white/black/red 0.52 13.3 137 204 20 20 20

4 12 (1) white/black/red/blue 0.56 14.2 168 250 20¹ 20¹ 20¹

2 10 (1) white/black 0.56 14.3 146 217 30 30 30

3 10 (1) white/black/red 0.59 15.0 190 283 30 30 30

4 10 (1) white/black/red/blue 0.64 16.1 236 351 30¹ 30¹ 30¹

3 8 (19) white/black/red 0.64 16.1 246 366 40 50 55

3 6 (19) white/black/red 0.74 18.7 357 531 55 65 75

Bend Radius: 7 x overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in araceway or direct buried at 30°C ambient temperature.60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 AWG through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC Table 310.15(B) (16).• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temprature and number of conductors havebeen applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).¹ Where the 4th (white) conductor is the neutral of a balanced 3 phase system.

SELLING INFORMATION

Product Features

Page 11: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® ACContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 11 / 87

Cables are UL listed as Type ACTHH, 600 V•UL listed insulated conductors•UL listed for use in cable trays per NEC Article 320.10(2)•Temperature rating of 90ºC dry•Excellent mechanical and physical properties•Lightweight aluminum armor•Standard Nexans ENERGEX® AC is RoHS compliant•

Options

The following constructions can be provided on special orders:

Special conductor counts•

Page 12: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored PVC Jacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 12 / 87

STANDARDS

National UL 1569; UL 83; UL 44

Aluminum Armored Jacketed MC Cable UL Type MC, 600 V, 90°C DRY - RoHSCompliant Copper Conductors

DESCRIPTION

Applications

ENERGEX® MC 120 cables may be used for branch, feeder and service for distributionin commercial, industrial, and multi-residential construction in accordance withNEC Article 330. They are suitable for installation In motion picture studios, theaters,and places of assembly (100 people or more) per NEC Articles 230.43, 300.22(C),330, 396, 518, 520, 530 and 645. These cables may be installed in approvedraceways and as open runs of cable on a messenger. They may be installed exposed,concealed or in cable tray and may be run in spaces used for environmental air inaccordance with NEC Article 300.22(C) ONLY.

Nexans MC 120 cable is RoHS compliant.

Construction

Conductor:Solid soft bare annealed copper per ASTM B3. Stranded soft bare annealed copperper ASTM B3 and ASTM B8 Class C compressed stranded for sizes 8 AWG to 2 AWG.

Insulation:Colored PVC/Nylon type THHN in accordance with UL 83, flame retardant, meeting ULVW-1 flame test for sizes 14 AWG to 1 AWG. Colored cross-linked polyethylene typeXHHW-2 per UL 44 for sizes 1/0 AWG and larger.

Ground Wire:Green PVC/Nylon Type THHN insulation for phase conductor sizes from 14 AWG to 1AWG, sized in accordance with NEC and UL, (green cross-linked polyethylene TypeXHHW-2 for phase conductors sized 1/0 AWG and larger).

Assembly:Conductors are cabled with grounding wires. A marker tape/core protection tapecombination assembles the core in an essentially round configuration.

Armor:Interlocking aluminum tape armor applied directly over the core.

Jacket:

Black PVC jacket.

Marker Tape Print:

NEXANS TYPE MC 600 VOLT FOR CT USE (SIZE) THHN (UL) E-47409 LEAD FREE(MFG DATE)

Page 13: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored PVC Jacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 13 / 87

Specifications

Meets UL 44: Thermoset Insulated Wires and Cables (1/0 AWG and larger)•Meets UL 83: Thermoplastic Insulated Wires and Cables (14 AWG to 1 AWG)•Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or threehour fire rated assemblies (for cables up to 2 AWG)

Meets UL 1569: Metal Clad Cables•Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords•Meets UL 2556: Wire and Cable Test Methods•Designated Type MC per NEC Article 330•

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 14: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored PVC Jacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 14 / 87

ENERGEX® MC 120 ALUMINUM ARMORED JACKETEDNumbe

rof

Con­ductors

ConductorSizeAWG

GroundSizeAWG

Circuit ConductorColor Code

Nominal Diameter

over Armor

Nominal Diameter

over Jacket

ApproximateNet

Cable WeightAmpacity(Amps)

inches mm inches mm lb/kft kg/km 60ºC 75ºC 90ºC

2 14 (1) 14 (1) white/black 0.45 11.3 0.55 14.0 147 219 15 15 15

3 14 (1) 14 (1) white/black/red 0.47 12.0 0.58 14.7 166 247 15 15 15

2 12 (1) 12 (1) white/black 0.48 12.3 0.59 14.9 183 272 20 20 20

3 12 (1) 12 (1) white/black/red 0.51 13.1 0.62 15.7 210 313 20 20 20

4 12 (1) 12 (1) white/black/red/blue 0.55 14.0 0.66 16.6 238 354 20¹ 20¹ 20¹

2 10 (1) 10 (1) white/black 0.55 14.0 0.66 16.6 239 356 30 30 30

3 10 (1) 10 (1) white/black/red 0.57 14.9 0.69 17.6 283 421 30 30 30

4 10 (1) 10 (1) white/black/red/blue 0.64 16.3 0.75 19.0 319 475 30¹ 30¹ 30¹

2 8 (19) 10 (1) white/black 0.66 16.7 0.76 19.3 309 460 40 50 55

3 8 (19) 10 (1) white/black/red 0.71 18.1 0.82 20.8 380 566 40 50 55

4 8 (19) 10 (1) white/black/red/blue 0.78 19.7 0.88 22.4 451 671 40¹ 50¹ 55¹

2 6 (19) 8 (19) white/black 0.74 18.9 0.85 21.5 410 610 55 65 75

3 6 (19) 8 (19) white/black/red 0.81 20.6 0.92 23.3 515 766 55 65 75

4 6 (19) 8 (19) white/black/red/blue 0.89 22.0 0.99 25.2 612 911 55¹ 65¹ 75¹

3 4 (19) 8 (19) white/black/red 0.94 23.9 1.05 26.6 714 1063 70 85 95

4 4 (19) 8 (19) white/black/red/blue 1.06 26.8 1.16 29.5 945 1406 70¹ 85¹ 95¹

3 2 (19) 6 (19) white/black/red 1.09 25.9 1.20 30.4 1086 1616 95 115 130

4 2 (19) 6 (19) white/black/red/blue 1.20 30.5 1.31 33.2 1345 2002 95¹ 115¹ 130¹

Bend Radius: 7 x overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) forconductors in a raceway or direct buried at 30°C ambiant temperatures.60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 AWG through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.15(B)(16).• NEC Article 240.4(D) requires that overcurrent protection not exceed15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductorsafter any correction factors for ambient temperature and number of conductors have been applied.Exceptions to this may be covered in NEC Article 240.4(E) through (G).

¹Where the Ampacity assuming 4th (white) conductor is the neutral of a balanced 3 phase system.

Page 15: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored PVC Jacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 15 / 87

SELLING INFORMATION

Product Features

Cables are UL listed as Type MC, 600 V•UL listed insulated conductors•Fire Wall Penetration rated depending on type of installation and fire-stop system used•UL listed for use in cable trays per NEC Article 330.10(A)(6)•UL listed for use in cable trays per NEC Article 501.10(B)(1), Class II, Div.2 per NEC Article 502.10(B)(1) and ClassIII, Div. 1 & 2 per NEC Article 503.10(A) and with approved termination fittings.

Temperature rating of 90ºC dry•Excellent mechanical & physical properties•Lightweight aluminum armor•Nexans ENERGEX® MC 120 is RoHS compliant•

Options

The following constructions can be provided on special orders:

Special conductor counts•XHHW-2 insulation on sizes 14 AWG to 1 AWG•Conductor sizes larger than 1/0 AWG•

Page 16: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored Unjacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 16 / 87

Aluminum Armored, Unjacketed MC Cable, UL Type MC, 600 V, 90°C dry rated -RoHS Compliant Copper Conductors

DESCRIPTION

Applications

ENERGEX® MC 120 cables may be used for branch, feeder and service fordistribution in commercial, industrial, and multi-residential construction in accordancewith NEC Article 330. They are suitable for installation in motion picture studios,theaters, and places of assembly (100 people or more) per NEC Articles 230.43,300.22(C), 330, 396, 518, 520, 530 and 645.These cables may be installed inapproved raceways and as open runs of cable on a messenger.They may be installedexposed, concealed or in cable tray and may be run in spaces used for environmentalair in accordance with NEC Article 300.22(C) ONLY.

Nexans MC 120 cable is RoHS compliant.

Construction

Conductor:Solid soft bare annealed copper per ASTM B3. Stranded soft bare annealed copperper ASTM B3 and ASTM B8 Class C compressed stranded for sizes 12 AWG to 2AWG. Stranded soft bare annealed copper per ASTM B3 and ASTM B8 Class B Unilaycompressed stranded for sizes 1 AWG and larger.

Insulation:Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant, meetingUL VW-1 flame test.

Ground Wire:Green PVC/Nylon Type THHN insulation bare copper, sized in accordance with NECand UL.

Assembly:Conductors are cabled with grounding wires. A marker tape/core protection tapecombination assembles the core in an essentially round configuration.

Armor:Interlocking aluminum tape armor applied directly over the core.

Marker Tape Print:

NEXANS-C TYPE MC 600V FOR CT USE (SIZE) THHN (UL) E-47409

Specifications

Meets UL 83: Thermoplastic Insulated Wires and Cables•Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or threehour fire rated assemblies (for cables up to 2 AWG)

Meets UL 1569: Metal Clad Cables•Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords•Meets UL 2556: Wire and Cable Test Methods•Designated Type MC per NEC Article 330•

STANDARDS

National UL 1479; UL 1569;UL 83

Page 17: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored Unjacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 17 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 18: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored Unjacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 18 / 87

ENERGEX® MC 120 ALUMINUM ARMORED UNJACKETED

Part NumberNumber of

Conductors

ConductorSizeAWG

GroundSizeAWG

Circuit ConductorColor Code

Nominal Diameter

over ArmorApproximate Net

Cable WeightAmpacity(Amps)

250 ft coil1000 ft reel inches mm lb/kft kg/km 60°C75°C90°C618777 642876 2 14 (1) 14 (1) white/black 0.45 11.3 87 129 15 15 15

618785 642884 3 14 (1) 14 (1) white/black/red 0.47 12.0 106 158 15 15 15

670050 670051 4 14 (1) 14 (1) white/black/red/blue 0.51 12.8 123 183 15¹ 15¹ 15¹

618793 635045 2 12 (1) 12 (1) white/black 0.48 12.3 118 176 20 20 20

618801 635052 3 12 (1) 12 (1) white/black/red 0.51 13.1 145 216 20 20 20

618819 635060 4 12 (1) 12 (1) white/black/red/blue 0.55 14.0 173 257 20¹ 20¹ 20¹

618827 636977 2 10 (1) 10 (1) white/black 0.55 14.0 164 244 30 30 30

618835 636985 3 10 (1) 10 (1) white/black/red 0.59 14.9 207 308 30 30 30

618843 640177 4 10 (1) 10 (1) white/black/red/blue 0.64 16.3 244 363 30¹ 30¹ 30¹

642892 642900 2 12 (19) 12 (19) white/black 0.48 12.3 118 176 20 20 20

644997 645002 3 12 (19) 12 (19) white/black/red 0.51 13.1 145 216 20 20 20

645010 645028 4 12 (19) 12 (19)white/black/red/blue 0.55 14.0 173 257 20¹ 20¹ 20¹

672972 672980 2 10 (19) 10 (19) white/black 0.55 14.0 164 244 30 30 30

672576 672584 3 10 (19) 10 (19) white/black/red 0.58 14.9 207 308 30 30 30

670017 672634 4 10 (19) 10 (19)white/black/red/blue 0.64 16.3 244 363 30¹ 30¹ 30¹

200 ft reel500 ft reel670085 670190 2 8 (19) 8 (19) white/black 0.66 16.7 229 341 40 50 55

670086 642918 3 8 (19) 8 (19) white/black/red 0.71 18.1 300 446 40 50 55

--- 670208 4 8 (19) 10 (19)white/black/red/blue 0.78 19.7 371 552 40¹ 50¹ 55¹

125 ft reel500 ft reel670088 670182 2 6 (19) 8 (19) white/black 0.74 18.9 330 491 55 65 75

670089 643445 3 6 (19) 8 (19) white/black/red 0.81 20.6 435 647 55 65 75

--- 670174 4 6 (19) 8 (19) white/black/red/blue 0.89 22.5 541 805 55¹ 65¹ 75¹

--- 670539 3 4 (19) 8 (19) white/black/red 0.94 23.9 624 929 70 85 95

--- --- 4 4 (19) 8 (19) white/black/red/blue 1.06 26.8 855 1272 70¹ 85¹ 95¹

--- 673848 3 3 (19) 6 (19) white/black/red 1.02 25.8 795 1183 85 100 110

--- 670237 4 3 (19) 6 (19) white/black/red/blue 1.13 28.7 1049 1561 85¹ 100¹110¹

--- 670521 3 2 (19) 6 (19) white/black/red 1.09 27.7 966 1438 95 115 130

--- 673871 4 2 (19) 6 (19) white/black/red/blue 1.20 30.5 1245 1853 95¹ 115¹130¹

--- --- 3 1 (19) 6 (19) white/black/red 1.20 30.6 1427 2124 110 130 150

--- --- 3 1/0 (19) 6 (19) white/black/red 1.27 32.3 1585 2359 125 150 170

Bend Radius: 7 x overall diameter

*60°C – When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 AWG through 1 AWG.75°C – When terminated to equipment for circuits rated 100 amperes or less or marked for conductor larger than 1 AWG.90°C – Wet or dry locations. For ampacity derating purposes.

Notes:• Where stated, “nominal” and “approximate” value are provided for information purposes only and are subject to standardmanufacturing tolerances.• Ampacities are in accordance with NEC Articles 310.15 and 334.80, which are based on NEC Table 310.15(B)(16) forconductors in a raceway or direct buried at 30°C ambient temperature. Ampacities for cables having more than threeconductors have been derated per NEC Table 310.15(B)(3)(a).• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings seeNEC Table 310.15(B)(16).• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG,and 30 amperes for 10 AWG copper conductors after any correcting factors for ambient temperature and number of conductors have beenapplied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).

¹Where the 4th conductor is the neutral of a balanced 3 phase system.

Page 19: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 AluminumArmored Unjacketed

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 19 / 87

SELLING INFORMATION

Product Features

Cables are UL listed as Type MC, 600 V•UL listed insulated conductors•Fire Wall Penetration rated depending on type of installation and fire-stop system used•UL listed for use in cable trays per NEC Article 330.10(A)(6) or NEC Article 330.10(6)•For use in Class 1, Div. 2 per NEC Article 501.10(B)(1), Class II, Div.2 per NEC Article 502.10(B)(1) and Class III, Div.1 & 2 per NEC Article 503.10 with approved termination fittings.

Temperature rating of 90ºC dry•Suitable for direct burial•Excellent mechanical & physical properties•Lightweight aluminum armor•Nexans ENERGEX® MC 120 is RoHS compliant•

Options

The following constructions can be provided on special orders:

Special conductor counts•XHHW-2 insulation•

Page 20: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 Steel ArmoredContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 20 / 87

STANDARDS

National UL 1479; UL 1569;UL 83

Steel Armored MC Cable, UL Type MC, 600 V, 90°C dry rated - RoHS Compliant,Copper Conductors

DESCRIPTION

ApplicationsENERGEX® MC 120 cables may be used for branch, feeder and service for distributionin commercial, industrial, and multi-residential construction. They are suitable forinstallation in motion picture studios, theaters, and places of assembly (100 people ormore) per NEC Articles 230.43, 300.22(C), 330, 396, 518, 520, 530 and 645. Thesecables may be installed in approved raceways and as open runs of cable on amessenger. They may be installed exposed, concealed or in cable tray and may berun in spaces used for environmental air in accordance with NEC Article 300.22(C)ONLY.

Nexans MC 120 cable is RoHS compliant.

ConstructionConductor:Solid soft bare annealed copper per ASTM B3. Stranded soft bare annealed copperper ASTM B3 and ASTM B8 Class C compressed stranded for sizes 12 AWG to 6AWG.

Insulation:PVC/Nylon Type THHN in accordance with UL 83, flame retardant meeting UL VW-1flame test.

Ground Wire:Green PVC/Nylon Type THHN insulation sized in accordance with NEC and UL.

Assembly:Conductors are cabled with grounding wires. A marker tape/core protection tapecombination assembles the core in an essentially round configuration.

Armor:Interlocking galvanized steel tape armor applied directly over the core.

Marker Tape Print

NEXANS-C TYPE MC 600V FOR CT USE (SIZE) THHN (UL) E-47409

SpecificationsMeets UL 83: Thermoplastic Insulated Wires and Cables•Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or threehour fire rated assemblies (for cables up to 2 AWG)

Meets UL 1569: Metal Clad Cables•Meets UL 1581: Reference Standard for Electrical Wires, Cables, and Flexible Cords•Meets UL 2256: Wire and Cable Test Methods•Designated Type MC per NEC Article 330•

Page 21: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 Steel ArmoredContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 21 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 22: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 Steel ArmoredContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 22 / 87

ENERGEX® MC 120 STEEL ARMORED CABLE

Partnumber

Numberof

Con­ductors

ConductorSizeAWG

GroundSizeAWG Circuit Conductor

Color Code

Nominal Diameter

over Armor

ApproximateNet

Cable Weight

Ampacity(Amps)

inches mm lb/kft kg/km 60ºC 75ºC 90ºC

250 ftcoil

1000 ftreel

670033 670040 2 14 (1) 14 (1) white/black 0.44 11.2 144 214 15 15 15

670035 - 3 14 (1) 14 (1) white/black/red 0.47 11.9 167 249 15 15 15

670036 670043 4 14 (1) 14 (1) white/black/red/blue 0.50 12.7 189 281 15¹ 15¹ 15¹

670011 670044 2 12 (1) 12 (1) white/black 0.48 12.1 179 266 20 20 20

670012 670045 3 12 (1) 12 (1) white/black/red 0.51 12.9 213 317 20 20 20

670013 670046 4 12 (1) 12 (1) white/black/red/blue 0.54 13.8 247 368 20¹ 20¹ 20¹

670014 670047 2 10 (1) 10 (1) white/black 0.54 13.8 238 354 30 30 30

670015 670048 3 10 (1) 10 (1) white/black/red 0.58 14.8 287 427 30 30 30

670016 670049 4 10 (1) 10 (1) white/black/red/blue 0.63 16.0 333 496 30¹ 30¹ 30¹

- - 2 12 (19) 12 (19) white/black 0.48 12.3 215 320 20 20 20

- - 3 12 (19) 12 (19) white/black/red 0.51 13.1 252 375 20 20 20

- - 4 12 (19) 12 (19) white/black/red/blue 0.55 14.0 290 432 20¹ 20¹ 20¹

- - 2 10 (19) 10 (19) white/black 0.55 14.0 164 244 30 30 30

- - 3 10 (19) 10 (19) white/black/red 0.59 14.9 207 308 30 30 30

- - 4 10 (19) 10 (19) white/black/red/blue 0.64 16.3 244 363 30¹ 30¹ 30¹

- - 3 8 (19) 10 (19) white/black/red 0.71 18.1 300 446 40 50 55

- - 3 6 (19) 8 (19) white/black/red 0.81 20.6 435 647 55 65 75

Bend Radius: 7 x overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) forconductors in a raceway at 30°C ambient temperatures.60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes14 AWG through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductors largerthan size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.15(B)(16).• NEC Article 240.4(D) requires that overcurrent protection not exceed15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductorsafter any correction factors for ambient temperature and number of conductors have been applied.Exceptions to this may be covered in NEC Article 240.4(E) through (G).

¹Where the 4th (white) conductor is the neutral of a balanced 3 phase system.

Page 23: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 120 Steel ArmoredContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 23 / 87

SELLING INFORMATION

Product FeaturesCables are UL listed as Type MC, 600 V•UL listed insulated conductors•Fire Wall Penetration rated depending on type of installation and fire-stop system used•UL listed for use in cable trays per NEC Article 330.10(A)(6)•For use in Class I, Div. 2 per NEC Article 501.10(B)(1), Class II, Div.2 per NEC Article 502.10(B)(1) and Class III, Div.1 & 2 per NEC Article 503.10 with approved termination fittings.

Temperature rating of 90ºC dry •Excellent mechanical & physical properties•Nexans ENERGEX® MC 120 is RoHS compliant•

OptionsThe following constructions can be provided on special orders:

Special conductor counts•XHHW-2 insulation•

Page 24: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 277 AluminumArmored

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 24 / 87

STANDARDS

National UL 1479; UL 1569;UL 83

Aluminum Armored MC Cable 277 Volts and Special Color Codes UL Type MC, 600 V,90ºC dry rated - RoHS Compliant Copper Conductors

DESCRIPTIONENERGEX® MC 277 cables may be used for branch, feeder and service fordistribution in commercial, industrial, and multi-residential construction in accordancewith NEC Article 330. They are suitable for installation in motion picture studios,theaters, and places of assembly (100 people or more) per NEC Articles 230.43,300.22(C), 330, 396, 518, 520, 530 and 645. These cables may be installed inapproved raceways and as open runs of cable on a messenger. They may be installedexposed, concealed or in cable tray and may be run in spaces used for environmentalair in accordance with NEC Article 300.22(C) ONLY.

Nexans MC 277 cable is RoHS compliant.

Construction

Conductor:

Solid soft bare annealed copper per ASTM B3. Stranded soft bare annealed copperper ASTM B3 and ASTM B8 Class C compressed stranded for sizes 12 AWG to 6AWG.

Insulation:Colored PVC/Nylon Type THHN in accordance with UL 83, flame retardant,meeting UL VW-1 flame test.

Ground Wire:Green PVC/Nylon Type THHN insulation sized in accordance with NECand UL.

Assembly:Conductors are cabled with grounding wires. A marker tape / coreprotection tape combination assembles the core in an essentially round configuration.

Armor:Interlocking aluminum tape armor applied directly over the core.

Marker Tape Print:NEXANS-C TYPE MC 600V FOR CT USE (SIZE) THHN (UL) E-47409

Specifications

Meets UL 83: Thermoplastic-Insulated Wire and Cables•Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two orthree hour fire rated assemblies (for cables up to 2 AWG)

Meets UL 1569: Metal Clad cables•Meets UL 1581: Reference Standard for Electrical Wires, Cables, and Flexible Cords•Meets UL 2556: Wire and Cable Test Methods•Designated Type MC per NEC Article 330•

Page 25: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 277 AluminumArmored

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 25 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 26: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 277 AluminumArmored

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 26 / 87

ENERGEX® MC 277 ALUMINUM ARMORED MC CABLE

PartNumber

Numberof

Con­ductors

ConductorSizeAWG

GroundSizeAWG

Circuit ConductorColor Code

Nominal Diameter

over Armor

ApproximateNet

Cable WeightAmpacity*

(Amps)

inches mm lb/kft kg/km 60°C 75°C 90°C250 ftcoil

1000 ftreel

654269 652537 2 12 (1) 12 (1) brown/gray 0.48 12.3 118 176 20 20 20

654251 671917 2 12 (1) 12 (1) orange/gray 0.48 12.3 118 176 20 20 20

654244 671925 2 12 (1) 12 (1) yellow/gray 0.48 12.3 118 176 20 20 20

--- --- 2 12 (1) 12 (1) purple/gray 0.48 12.3 118 176 20 20 20

--- --- 2 12 (1) 12 (1) brown/yellow 0.48 12.3 118 176 20 20 20

652263 670570 2 12 (1) 12 (1) red/white 0.48 12.3 118 176 20 20 20

652271 670554 2 12 (1) 12 (1) blue/white 0.48 12.3 118 176 20 20 20

669762 669770 3 12 (1) 12 (1) brown/orange/gray 0.51 13.1 145 216 20 20 20

--- --- 3 12 (1) 12 (1) brown/purple/gray 0.51 13.1 145 216 20 20 20

--- --- 3 12 (1) 12 (1) purple/yellow/gray 0.51 13.1 145 216 20 20 20

--- --- 3 12 (1) 12 (1) brown/yellow/gray 0.51 13.1 145 216 20 20 20

--- --- 3 12 (1) 12 (1) red/blue/white 0.51 13.1 145 216 20 20 20

--- --- 3 12 (1) 12 (1) black/blue/white 0.51 13.1 145 216 20 20 20

671891 669812 4 12 (1) 12 (1) brown/orange/yellow/gray 0.55 14.0 173 257 20¹ 20¹ 20¹

--- --- 4 12 (1) 12 (1) brown/purple/yellow/gray 0.55 14.0 173 257 20¹ 20¹ 20¹

--- 672923 2 10 (1) 10 (1) brown/gray 0.55 14.0 164 244 30 30 30

--- 672949 3 10 (1) 10 (1) brown/orange/gray 0.59 14.9 207 308 30 30 30

672592 672600 4 10 (1) 10 (1) brown/orange/yellow/gray 0.64 16.3 244 363 30¹ 30¹ 30¹

--- --- 2 12 (19) 12 (19) brown/gray 0.48 12.3 118 176 20 20 20

--- --- 3 12 (19) 12 (19) brown/orange/gray 0.51 13.1 145 216 20 20 20

--- --- 4 12 (19) 12 (19) brown/orange/yellow/gray 0.55 14.0 173 257 20¹ 20¹ 20¹

--- --- 2 10 (19) 10 (19) brown/gray 0.55 14.0 164 244 30 30 30

--- --- 3 10 (19) 10 (19) brown/orange/gray 0.59 14.9 207 308 30 30 30

--- --- 4 10 (19) 10 (19) brown/orange/yellow/gray 0.64 16.3 244 363 30¹ 30¹ 30¹

500 ftreel

1000 ftreel

642918 ---- 3 8 (19) 10 (19) brown/orange/gray 0.71 18.1 300 446 40 50 55

643445 --- 3 6 (19) 8 (19) brown/orange/gray 0.81 20.6 435 647 55 65 75

Bend Radius: 7 x overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) forconductors in a raceway at 30°C ambient temperatures.60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductorsizes 14 AWG through 1 AWG.75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductorslarger than size 1 AWG.90°C - Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductor temperatureratings see NEC Table 310.15(B)(16).• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correctionfactors for ambient temperature and number of conductors have been applied.Exceptions to this may be covered in NEC Article 240.4(E) through (G). .

¹Where the 4th (gray) conductor is the neutral of a balanced 3 phase system.

Page 27: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC 277 AluminumArmored

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 27 / 87

SELLING INFORMATIONProduct features

* Cables are UL listed as Type MC, 600 V* UL listed insulated conductors* Fire Wall Penetration rated depending on type of installation and fire-stop system used* UL listed for use in cable trays per NEC Article 330.10(A)(6)* For use in Class I, Div. 2 per NEC Article 501.10(B)(1), Class II, Div. 2 per NEC Article 502.10(B)(1)(6) and Class III,Div. 1 & 2 per NEC Article 503.10 with approved termination fittings.* Temperature rating of 90°C dry* Excellent mechanical & physical properties* Lightweight aluminum armor

* Nexans ENERGEX® MC 277 is RoHS compliant

Options

The following constructions can be provided on special orders:

* Special conductor counts* XHHW-2 insulation

Page 28: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Aluminum FeederCable

ContactIndustrial CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 28 / 87

STANDARDS

National UL 1569; UL 44

Aluminum Interlock Armored Power Feeder Cable, UL Type MC, 600 V, 90°C dry rated- Unjacketed, 3 or 4 aluminum conductors - XLPE insulated, with bare aluminumground wire - LEAD FREE

DESCRIPTIONApplications

Unjacketed aluminum conductor MC cable is suitable and allowed by the NEC for usein the following applications:

Power lighting, control and signal circuits and as branch circuits and power feedersin industrial, commercial, institutional and residential installations up to 600 volts.

Fished or embedded in plaster and concrete except in damp or wet locations.•Aerial cable when fixed to a messenger support cable.•Concealed or exposed applications.•Cable trays and other raceways.•Class I and II, Division 2 as well as Class III, Division 1 and 2 hazardous locations.•Under raised floors of information technology rooms.•Environmental air-handling spaces per NEC Article 300.22 (C).•Places of Assembly per NEC Article 518.4 and theaters per NEC Article 520.5.•

Construction

Conductor:Compact stranded AA-8000 series aluminum conductor material (ACM) per ASTMB801 Class B or ASTM B836 (Single Input Wire).Insulation:Colored crosslinked polyethylene (XLPE) type XHHW-2 per UL 44.

Ground Wire:Bare compact stranded AA-8000 series aluminum alloy (ACM).

Assembly:Insulated conductors are cabled with a bare ground wire, interstices are filled withsuitable non-hygroscopic fillers, as required. A binder tape of synthetic materialassembles the core in an essentially round configuration.

Armor:Interlocking aluminum tape armor applied over the assembled core.

Conductor Identification:3/C black, red, white4/C black, red, blue, white

Specifications

Meets UL 44, XHHW-2 600 V conductors•Meets UL 1569 requirements for Type MC, Metal Clad cables•Designated Type MC per NEC Article 330•

Page 29: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Aluminum FeederCable

ContactIndustrial CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 29 / 87

CHARACTERISTICSConstruction characteristics

Conductor material AluminumElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

ENERGEX® MC ALUMINUM FEEDER CABLE3 Conductors with Bare Ground

PartNumber

(Color CodedConductors)

ConductorSize

InsulationThickness

GroundWire Size

Nominal Diameterover Armor

Approximate NetCable Weight Ampacity (Amps)

AWG/kcmil mils mm AWG inches mm lb/kft kg/km 60ºC 75ºC 90ºC

603520 6 45 1.14 6 0.776 19.71 210 312 40 50 55

603521 4 45 1.14 6 0.876 22.26 285 424 55 65 75

603523* 2 45 1.14 6 1.008 25.60 396 589 75 90 100

603524 1 55 1.40 4 1.124 28.54 503 748 85 100 115

603525* 1/0 55 1.40 4 1.198 30.43 586 872 100 120 135

603526* 2/0 55 1.40 4 1.285 32.63 687 1022 115 135 150

603527* 3/0 55 1.40 4 1.388 35.24 814 1211 130 155 175

603528* 4/0 55 1.40 2 1.499 38.07 992 1476 150 180 205

603529* 250 65 1.65 2 1.781 45.23 1172 1744 170 205 230

603531* 350 65 1.65 2 1.859 47.21 1521 2264 210 250 280

603542 400 65 1.65 1 1.951 49.55 1709 2544 225 270 305

603532* 500 65 1.65 1 2.248 57.11 2249 3346 260 310 350

603562* 750 80 2.03 1/0 2.680 68.07 3213 4781 320 385 435

*Denotes stock item. Other constructions available upon request.

Page 30: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Aluminum FeederCable

ContactIndustrial CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 30 / 87

3 CONDUCTORS WITH BARE GROUND CONNECTORSCablePart

NumberConductor Size Crouse­Hinds /

Eaton Bridgeport Appleton

(Color CodedConductors) AWG or kcmil ACB Series DC2 DCX2 AC­90

603520 6 ACB50 682-DC2 AC-95

603521 4 ACB75 683-DC2 AC-95

603523 2 ACB100 683-DC2 683-DCX2 AC-95

603524 1 ACB100 684-DC2 684-DCX2 AC-96

603525 1/0 ACB100 684-DC2 684-DCX2 AC-96

603526 2/0 ACB125 685-DC2 685-DCX2 AC-96

603527 3/0 ACB125 685-DC2 685-DCX2 AC-97

603528 4/0 ACB125 685-DC2 685-DCX2 AC-97

603529 250 ACB150 686-DC2 686-DCX2 AC-98

603531 350 ACB150 686-DC2 AC-99

603542 400 ACB200 686-DC2 AC-99

603532 500 ACB200 687-DC2 687-DCX2 AC-985

603562 750 ACB250 688-DC2 688-DCX2 AC-250-D

Page 31: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Aluminum FeederCable

ContactIndustrial CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 31 / 87

ENERGEX® MC ALUMINUM FEEDER CABLE4 Conductors with Bare Ground

PartNumber

(Color CodedConductors)

ConductorSize

InsulationThickness

GroundWire Size

Nominal Diameterover Armor

ApproximateNet Cable Weight Ampacity (Amps)

AWG/kcmil inches mm AWG inches mm lb/kft kg/km 60ºC 75ºC 90ºC

603533 6 0.045 1.14 6 0.85 21.6 269 400 40 50 55

603534 4 0.045 1.14 6 0.99 25.1 384 571 55 65 75

603535* 2 0.045 1.14 6 1.11 28.2 499 742 75 90 100

603536 1 0.055 1.40 4 1.24 31.6 655 974 85 100 115

603537* 1/0 0.055 1.40 4 1.33 33.7 767 1142 100 120 135

603538* 2/0 0.055 1.40 4 1.42 36.0 903 1343 115 135 150

603539 3/0 0.055 1.40 4 1.54 39.1 1077 1603 130 155 175

603540* 4/0 0.055 1.40 2 1.66 42.2 1313 1954 150 180 205

603541 250 0.065 1.65 2 1.81 46.1 1496 2227 170 205 230

603874* 250 0.065 1.65 1 1.83 46.6 1518 2259 170 205 230

603580 350 0.065 1.65 2 2.18 55.2 2152 3202 210 250 280

603876* 350 0.065 1.65 1/0 2.19 55.6 2195 3266 210 250 280

603543 400 0.065 1.65 1 2.29 58.1 2415 3593 225 270 305

603581 500 0.065 1.65 1 2.47 62.9 2881 4288 260 310 350

603878 500 0.065 1.65 2/0 2.47 62.8 2919 4344 260 310 350

603757* 500 0.065 1.65 250 2.53 64.3 3048 4536 260 310 350

603574* 750 0.080 2.03 3/0 2.94 74.8 4199 6249 320 385 435

Bending Radius:Fixed position: 7 x cable overall diameterDuring pulling: 12 x cable overall diameter

60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 6 AWG through 1 AWG.75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C - For ampacity derating purposes.

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in araceway or direct buried at 30°C ambient temperature and 90°C rated conductors. Ampacities for fourconductor cables apply where the 4th conductor is the neutral of a balanced 3 phase system.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.15(B)(16).• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).

* Denotes stock item. Other constructions available upon request.

Page 32: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Aluminum FeederCable

ContactIndustrial CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 32 / 87

4 CONDUCTORS WITH BARE GROUND CONNECTORSCablePart

NumberConductor Size Crouse­Hinds /

Eaton Bridgeport Appleton

(Color CodedConductors) AWG or kcmil ACB Series DC2 DCX2 AC­90

603533 6 ACB75 682-DC2 AC-95

603534 4 ACB75 683-DC2 683-DCX2 AC-95

603535 2 ACB100 684-DC2 684-DCX2 AC-96

603536 1 ACB100 684-DC2 684-DCX2 AC-96

603537 1/0 ACB125 685-DC2 685-DCX2 AC-97

603538 2/0 ACB125 685-DC2 685-DCX2 AC-97

603539 3/0 ACB125 686-DCX2 AC-98

603540 4/0 ACB150 686-DCX2 AC-98

603541 250 ACB150 686-DC2 686-DCX2 AC-98

603874 250 ACB150 686-DC2 686-DCX2 AC-98

603580 350 ACB200 687-DC2 687-DCX2 AC-985

603876 350 ACB200 687-DC2 687-DCX2 AC-985

603543 400 ACB200 687-DC2 687-DCX2 AC-985

603581 500 ACB250 688-DC2 688-DCX2 AC-250-D

603878 500 ACB250 688-DC2 688-DCX2 AC-250-D

603757 500 ACB250 688-DC2 688-DCX2 AC-250-D

603574 750 ACB250 689-DC2 689-DCX2 AC-250-D

SELLING INFORMATIONProduct Features

• Cables are UL listed as Type MC, rated 600 V• UL listed XHHW-2 insulated conductors• Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEEE 1202 and CSA FT4• Fire wall penetration rated depending on type of installation and fire-stop system used• Cables exhibit a -25°C cold bend rating with suitable precautions• Temperature rating of 90°Cdry• 130°C emergency rating and 250°C short circuit rating• Excellent mechanical and physical properties• RoHS Compliant• Suitable for use in cabletray• Can be installed in hazardous locations as permitted by the NEC

Page 33: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Ground PlusContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 33 / 87

STANDARDS

National UL 1479; UL 1569;UL 83

Aluminum Armored Isolated Ground MC Cable UL Type MC, 600 V, 90°C dry rated -RoHS Compliant Copper Conductors

DESCRIPTIONApplications

ENERGEX® MC Ground Plus cables are for use in applications where isolated,dedicated or redundant ground is required. They may be used for branch, feeder andservice for distribution in commercial, industrial and multi-residential construction. They are also suitable for installation in motion picture studios, theaters, and places ofassembly (100 people or more) per NEC Articles 230.43, 300.22(C), 330, 396, 518,520, 530 and 645. These cables may be installed in approved raceways and as openruns of cable on a messenger. They may be installed exposed, concealed or in cabletray and may be run in spaces used for environmental air in accordance with NECArticle 300.22(C) ONLY.

Nexans MC Ground Plus cable is RoHS compliant.

Construction

Conductor:Solid soft bare annealed copper per ASTM B3. Stranded soft bare annealed copperper ASTM B3 and ASTM B8 Class C compressed stranded for sizes 8 AWG and 6AWG.

Insulation:PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1flame test.

Ground Wires:Sized in accordance with NEC and UL, one with green THHN insulation, one withgreen THHN insulation with a yellow stripe.

Assembly:Conductors are cabled with grounding wires. A marker tape/core protection tapecombination assembles the core in an essentially round configuration.

Armor:Interlocking aluminum tape armor applied directly over the core.

Marker Tape Print:

NEXANS-C TYPE MC 600V FOR CT USE (SIZE) THHN (UL) E-47409

Specifications

Meets UL 83: Thermoplastic Insulated Wires and Cables•Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or threehour fire rated assemblies (for cables up to 2 AWG)

Meets UL 1569: Metal Clad Cables•Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords•Meets UL 2556: Wire and Cable Test Methods•Designated Type MC per NEC Article 330•

Page 34: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Ground PlusContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 34 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 35: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Ground PlusContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 35 / 87

ENERGEX® MC GROUND PLUS

PartNumber

Numberof

Con-ductors

ConductorSizeAWG

GroundSizeAWG

CircuitConductorColor Code

NominalDiameter

over Jacket

ApproximateNet

Cable Weight

Ampacity(Amps)

inches mm lb/kft kg/km 60ºC 75ºC 90ºC

250 ft coil 1000 ft reel

- - 2 14 (1) 2 x 14 (1) white/black 0.48 12.1 106 158 15 15 15

- - 3 14 (1) 2 x 14 (1) white/black/red 0.49 12.3 123 183 15 15 15

- - 4 14 (1) 2 x 14 (1) white/black/red/blue 0.53 13.3 140 208 15¹ 15¹ 15¹

671818 671826 2 12 (1) 2 x 12 (1) white/black 0.51 13.1 145 216 20 20 20

- - 3 12 (1) 2 x 12 (1) white/black/red 0.55 14.0 173 257 20 20 20

- - 4 12 (1) 2 x 12 (1) white/black/red/blue 0.58 14.8 201 299 20¹ 20¹ 20¹

- - 2 10 (1) 2 x 10 (1) white/black 0.58 14.0 207 308 30 30 30

- - 3 10 (1) 2 x 10 (1) white/black/red 0.62 15.8 244 363 30 30 30

- - 4 10 (1) 2 x 10 (1) white/black/red/blue 0.68 17.2 281 418 30¹ 30¹ 30¹

- - 2 8(19) 2 x 10 (1) white/black 0.66 16.8 300 446 40 50 55

- - 3 8(19) 2 x 10 (1) white/black/red 0.75 19.1 371 552 40 50 55

- - 4 8(19) 2 x 10 (1) white/black/red/blue 0.83 21.0 442 658 40¹ 50¹ 55¹

- - 2 6(19) 2 x 8(19) white/black 0.82 20.9 435 647 55 65 75

- - 3 6(19) 2 x 8(19) white/black/red 0.90 22.9 541 805 55 65 75

- - 4 6(19) 2 x 8(19) white/black/red/blue 0.98 24.8 647 963 55¹ 65¹ 75¹

Bend Radius: 7 x overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature.60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 AWG through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings seeNEC Table 310.15(B) (16).• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temprature andnumber of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).

¹ Where the 4th (white) conductor is the neutral of a balanced 3 phase system.

Page 36: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Ground PlusContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 36 / 87

SELLING INFORMATION

Product FeaturesCables are UL listed as Type MC, 600 V•UL listed insulated conductors•Fire Wall Penetration rated depending on type of installation and fire-stop system used•UL listed for use in cable trays per NEC Article 330.10(A)(6)•For use in Class 1, Div. 2 per NEC Article 501.10(B)(1), Class II, Div.2 per NEC Article 502.10(B)(1) and Class III, Div.1 & 2 per NEC Article 503.10 with approved termination fittings.

Temperature rating of 90ºC dry•Excellent mechanical and physical properties•Lightweight aluminum armor•Nexans ENERGEX® MC Ground Plus is RoHS compliant•

OptionsThe following constructions can be provided on special orders:

Special conductor counts•XHHW insulation•

Page 37: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Mega NeutralContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 37 / 87

STANDARDS

National UL 1479; UL 1569;UL 83

Aluminum Armored MC Cable, UL Type MC, 600 V, 90°C dry rated - RoHS CompliantCopper Conductors

DESCRIPTION

Applications

ENERGEX® MC Mega Neutral cables are for use in applications where increasedneutral capacity is required due to non-linear switching loads which can cause additiveharmonic currents to be present on the neutral conductors. They may be used forbranch, feeder and service for distribution in commercial, industrial, and multi-residential construction. It is also suitable for installation in motion picture studios,theaters, and places of assembly (100 people or more) per NEC Articles 230.43,300.22(C), 330, 396, 518, 520, 530 and 645. These cables may be installed inapproved raceways and as open runs of cable on a messenger. They may be installedexposed, concealed or in cable tray and may be run in spaces used for environmentalair in accordance with NEC Article 300.22(C) ONLY.

Nexans MC Mega Neutral Cable is RoHS compliant.

Construction

Conductor:Solid soft bare annealed copper per ASTM B3. Stranded soft bare annealed copperper ASTM B3 and ASTM B8 Class C compressed stranded for sizes 8 AWG and 6AWG.

Insulation:PVC/Nylon Type THHN in accordance to UL 83, flame resistant, meeting UL VW-1flame test.

Neutral Conductor: Softcopper, with white THHN insulation and colored stripe where indicated. Cable haseither one neutral per phase conductor or one over-sized neutral per two phaseconductors.

Ground Wire(s):Sized in accordance with NEC and UL, one with green THHN insulation, one withgreen THHN insulation with a yellow stripe (in cables with two grounds).

Assembly:Conductors are cabled with neutrals and grounding wires. A marker tape/coreprotection tape combination assembles the core in an essentially round configuration.

Armor:Interlocking aluminum tape armor applied directly over the core.

Marker Tape Print:

NEXANS TYPE MC 600V FOR CT USE 12/4C - 10/2C THHN (UL) E-47409

Page 38: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Mega NeutralContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 38 / 87

Specifications

Meets UL 83: Thermoplastic-Insulated Wires and Cables•Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or threehour fire rated assemblies (for cables up to 2 AWG)

Meets UL 1569: Metal Clad Cables•Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords•Meets UL 2556: Wire and Cable Test Methods•Designated Type MC per NEC Article 330•

Page 39: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Mega NeutralContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 39 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 40: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Mega NeutralContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 40 / 87

ENERGEX® MC MEGA NEUTRALNeutral Per Leg (NPL)

PartNumber

Number ofPower

Conductors

ConductorSizeAWG

NeutralSizeAWG

GroundSizeAWG

Circuit ConductorColor Code

White NeutralStripe Color

NominalDiameter

over Armor

ApproximateNet

Cable Weight

Ampacity(Amps)

250 ftcoil

1000 ftreel inchesmmlb/kft kg/km60ºC75ºC90ºC

671628671602 2 12 (1) 2x12 (1) 2x12 (1) black/red black/red 0.52 13.1 120 179 20 20 20

671636671586 3 12 (1) 3x12 (1) 2x12 (1) black/red/blue black/red/blue 0.53 13.4 163 243 20 20 20

- - 4 12 (1) 3x12 (1) 2x12 (1)black/red/pink/tan none/pink/tan 0.55 13.9 191 284 20¹ 20¹ 20¹

- - 2 10 (1) 2x10 (1)2x10 (1) black/red black/red 0.60 15.3 226 336 30 30 30

675413675405 3 10 (1) 3x10 (1)2x10 (1) black/red/blue black/red/blue 0.66 16.6 300 446 30 30 30

Oversize Neutral Conductor (ONC)

PartNumber

Number ofPower

Conductors

ConductorSizeAWG

NeutralSizeAWG

GroundSizeAWG

Circuit ConductorColor Code

White NeutralStripe Color

NominalDiameter

over Armor

ApproximateNet

Cable Weight

Ampacity(Amps)

250 ftcoil

1000 ftreel inchesmmlb/kft kg/km60ºC75ºC90ºC

- 672097 1 12 (1) 10 (1) 12 (1) black no stripe 0.52 13.1 120 179 20 20 20

- 671644 2 12 (1) 10 (1) 12 (1) black/red no stripe 0.53 13.4 163 243 20 20 20

- 671578 3 12 (1) 10 (1) 12 (1) black/red/blue no stripe 0.55 13.9 191 284 20 20 20

- 671651 3 12 (1) 8 (19) 12 (1) black/red/blue no stripe 0.60 15.3 226 336 20 20 20

- 672212 4 12 (1) 2x10 (1)2x12 (1)black/red/blue/pink none/pink 0.66 16.6 300 446 20¹ 20¹ 20¹

- 670588 2 10 (1) 8 (19) 10 (1) black/red no stripe 0.60 15.1 215 320 30 30 30

- 670596 3 10 (1) 6 (19) 10 (1) black/red/blue no stripe 0.58 14.6 320 476 30 30 30

- 674911 4 10 (1) 2x8 (19)2x10 (1)black/red/blue/pink none/pink 0.79 20.1 400 595 30¹ 30¹ 30¹

Bend Radius: 7 x overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperatures.60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 AWG through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings seeNEC Table 310.15(B)(16).• NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG, and 30 amperesfor 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied.Exceptions to this may be covered in NEC Article 240.4(E) through (G).

¹Where the 4th (white) conductor is the neutral of a balanced 3 phase system.

Page 41: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Mega NeutralContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 41 / 87

SELLING INFORMATION

Product Features

Cables are UL listed as Type MC, 600 V•UL listed insulated conductors•Fire Wall Penetration rated depending on type of installation and fire-stop system used•UL listed for use in cable trays per NEC Article 330.10(A)(6)•For use in Class 1, Div. 2 per NEC Article 501.10(B)(1), Class II, Div.2 per NEC Article 502.10(B)(1) and Class III, Div.1 & 2 per NEC Article 503.10(A) and (B) with approved termination fittings.

Temperature rating of 90ºC dry•Excellent mechanical and physical properties•Lightweight aluminum armor•Nexans ENERGEX® MC Mega Neutral is RoHs compliant•

Options

The following constructions can be provided on special orders:

Special conductor counts•XHHW-2 insulation

Page 42: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Multi ConductorContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 42 / 87

STANDARDS

National UL 1479; UL 1569;UL 83

Aluminum Armored MC Cable UL Type MC, 600 V, 90°C dry rated - RoHS CompliantCopper Conductors

DESCRIPTION

Applications

ENERGEX® MC Multi Conductor cables are designed for applications that require sixor more conductors. They may be used for branch, feeder and service for distributionin commercial, industrial, and multi-residential construction. They are suitable forinstallation in motion picture studios, theaters, and places of assembly (100 people ormore) per NEC Articles 230.43, 300.22(C), 330, 396, 518, 520, 530 and 645. Thesecables may be installed in approved raceways and as open runs of cable on amessenger. They may be installed exposed, concealed or in cable tray and may be runin spaces used for environmental air in accordance with NEC Article 300.22(C) only.

Nexans MC Multi Conductor Cables are RoHS compliant.

Construction

Conductor:Solid soft bare annealed copper per ASTM B3.

Insulation:PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1flame test.

Ground Wire:Green PVC/Nylon Type THHN insulation, sized in accordance with NEC and UL.

Assembly:Conductors are cabled with grounding wires. A marker tape/core protection tapecombination assembles the core in an essentially round configuration.

Armor:Interlocking aluminum tape armor applied directly over the core.

Marker Tape Print:

NEXANS-C TYPE MC 600V FOR CT USE (SIZE) THHN (UL) E-47409

Color Code:

(tan is stripe color)

6 conductor: black, red, white, black/tan, red/tan, white/tan

8 conductor: black, red, white, blue, black/tan, red/tan, white/tan, blue/tan

Page 43: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Multi ConductorContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 43 / 87

Specifications

Meets UL 83: Thermoplastic Insulated Wires and Cables•Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or threehour fire rated assemblies (for cables up to 2 AWG)

Meets UL 1569: Metal Clad Cables•Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords•Meets UL 2556: Wire and Cable Test Methods•Designated Type MC per NEC Article 330•

Page 44: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Multi ConductorContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 44 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 45: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Multi ConductorContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 45 / 87

ENERGEX® MC MULTI CONDUCTORPart

Number

1000 ftreels

Numberof

Conductors

ConductorSizeAWG

GroundSizeAWG

Nominal Diameterover Armor

Approximate NetCable Weight

Ampacity(Amps)

inches mm lb/kft kg/km 60ºC 75ºC 90ºC

671669 6 12 (1) 12 (1) 0.57 14.5 225 335 16 20 20

671677 8 12 (1) 12 (1) 0.65 16.4 290 432 14 18 20

- 10 12 (1) 12 (1) 0.70 17.8 320 476 10 13 15

- 12 12 (1) 12 (1) 0.75 19.1 350 521 10 13 15

- 14 12 (1) 12 (1) 0.80 20.3 410 610 10 13 15

- 16 12 (1) 12 (1) 0.83 21.0 465 692 10 13 15

- 18 12 (1) 12 (1) 0.84 21.2 475 707 10 13 15

- 20 12 (1) 12 (1) 0.87 22.1 565 841 10 13 15

- 24 12 (1) 12 (1) 0.95 24.1 650 967 9 11 14

673707 6 10 (1) 10 (1) 0.68 17.2 340 506 24 28 30

673699 8 10 (1) 10 (1) 0.76 19.3 390 580 21 25 28

- 10 10 (1) 10 (1) 0.83 21.0 470 699 15 18 20

- 12 10 (1) 10 (1) 0.88 22.4 560 833 15 18 20

- 14 10 (1) 10 (1) 0.94 23.9 635 945 15 18 20

- 16 10 (1) 10 (1) 0.98 24.9 730 1086 15 18 20

- 18 10 (1) 10 (1) 0.99 25.2 805 1198 15 18 20

- 20 10 (1) 10 (1) 1.03 26.0 915 1362 15 18 20

- 24 10 (1) 10 (1) 1.13 28.7 1130 1682 14 16 18

Bend Radius: 7 x overall diameter

Notes:• Dimensions and weights shown are nominal values, subject to standard industry tolerances.• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors ina raceway or direct buried at 30°C ambient temperature.60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 AWG through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC Table 310.15(B) (16).• NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number ofconductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).

SELLING INFORMATION

Product Features

Page 46: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® MC Multi ConductorContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V4.0 Generated 8/2/18 www.nexans.us Page 46 / 87

Cables are UL listed as Type MC, 600 V•UL listed insulated conductors•Fire Wall Penetration rated depending on type of installation and fire-stop system used•UL listed for use in cable trays per NEC Article 330.10(A)(6)•For use in Class 1, Div. 2 per NEC Article 501.10(B)(6), Class II, Div.2 per NEC Article 502.10(B)(1) and Class III, Div.1 & 2 per NEC Article 503.10 with approved termination fittings.

Temperature rating of 90ºC dry•Excellent mechanical and physical properties•Lightweight aluminum armor•Nexans ENERGEX® MC Multi Conductor is RoHS compliant•

Options

The following constructions can be provided on special orders:

Special conductor counts•XHHW insulation•

Page 47: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Direct BuriedContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Generated 8/2/18 www.nexans.us Page 47 / 87

Armored and unarmored cable are available for direct burial in the earth withappropriate protection as required by the local inspection authority. All are designedfor ease of installation and superior performance.

Page 48: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 RHH/RHW­2/USE­2Aluminum

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 48 / 87

STANDARDS

National ICEA S-95-658;UL 854; UL 44

XLPE Insulated Cable, ACM Aluminum Conductors, 600 Volts, 90ºC Dry or Wet -RoHS compliant

DESCRIPTION

ApplicationNexans ENERGEX® 8000 RHH/RHW-2/USE-2 is an AA-8000 series aluminum (ACM)conductor with cross-linked polyethylene insulation. The cable may be installed inraceways and conduits or directly buried. They are 90ºC, 600 volts per NEC Articles310 and 338.

Type USE-2 conductors are suitable as service entrance conductors which can beinstalled directly buried in accordance with the NEC.

When used as type RHH, the cables are suitable for installation in dry locations.

As type RHW-2 and USE-2, cables are suitable for installation in both wet and drylocations.

Nexans RHH/RHW-2/USE-2 conductors are RoHS compliant.

Construction

Conductor:Compact stranded AA-8000 series aluminum conductor material (ACM) per ASTMB801 or ASTM B836 (Single Input Wire).

Insulation:Heat, sunlight, moisture and abrasion resistant cross-lined polyethylene (XLPE)insulation per UL 854 and UL 44. Black only.

Specifications

Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables•Meets UL 854: (USE-2) Service Entrance Cables•Federal Specification A-A-59544•ICEA 5-95-658: Power Cables Rated 2000 Volts or Less for the Distribution ofElectrical Energy

National Electrical Code - NFPA 70•Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated CT use.•

Surface Print Legend (example)

NEXANS-C 1/0 AWG COMPACT AA-8000-AL USE-2 OR RHH OR RHW-2 600V FORCT USE SUN RES(UL) ROHS (MFG. DATE)

Page 49: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 RHH/RHW­2/USE­2Aluminum

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 49 / 87

CHARACTERISTICSConstruction characteristics

Conductor material AluminumElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 50: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 RHH/RHW­2/USE­2Aluminum

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 50 / 87

ENERGEX® 8000 RHH/RHW­2/USE­2 ALUMINUM

Conductor Size Nominal Insulation Thickness Nominal Diameter Approximate Net Cable WeightAmpacity*

(Amps)

AWG/kcmil mils mm inches mm lb/kft kg/km 60 ºC 75 ºC 90 ºC

6 (7) 60 1.52 0.29 7.4 47 70 40 50 55

4 (7) 60 1.52 0.33 8.4 66 98 55 65 75

2 (7) 60 1.52 0.39 9.9 96 143 75 90 100

1 (18) 80 2.03 0.46 11.7 127 189 85 100 115

1/0 (18) 80 2.03 0.50 12.7 152 226 100 120 135

2/0 (18) 80 2.03 0.54 13.7 182 271 115 135 150

3/0 (18) 80 2.03 0.59 15.0 222 330 130 155 175

4/0 (18) 80 2.03 0.64 16.3 271 403 150 180 205

250 (35) 95 2.41 0.71 18.0 328 488 170 205 230

300 (35) 95 2.41 0.76 19.3 385 573 195 230 260

350 (35) 95 2.41 0.81 20.6 435 647 210 250 280

400 (35) 95 2.41 0.85 21.6 494 735 225 270 305

500 (35) 95 2.41 0.93 23.6 600 893 260 310 350

600 (58) 110 2.79 1.07 27.2 721 1073 285 340 385

700 (58) 110 2.79 1.11 28.2 828 1232 315 375 425

750 (58) 110 2.79 1.13 28.7 899 1338 320 385 435

1000 (58) 110 2.79 1.28 32.5 1141 1698 375 445 500

*60ºC ­ When terminated to equipment for circuits rated 100 amperes or less or marked forconductor sizes 12 through 1 AWG.75ºC ­ When terminated to equipment for circuits rated over 100 amperes or marked forconductors larger than 1 AWG.90ºC ­ RHH dry locations. RHW­2 and USE­2 wet or dry locations. For ampacityderating purposes.

Notes:

• Where stated, "nominal" and "approximate" values are provided for information purposesonly and are subject to standard manufacturing tolerances.• Ampacities are in accordance with NEC Article 310.15, which are basedon NEC Table 310.15(B)(16) for conductors in a raceway ordirect buried at 30°C ambient temperature.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.15(B)(16).• NEC Article 240.4(D) requires that over current protection not exceed15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum conductors after any correctionfactors for ambient temperature and number of conductors have been applied. Exceptions to thismay be covered in NEC Article 240.4(E) through (G).

SELLING INFORMATION

Product FeaturesCables are UL listed as Type USE-2•Temperature rating of 90ºC dry and wet•

Page 51: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 RHH/RHW­2/USE­2Aluminum

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 4.0 Generated 8/2/18 www.nexans.us Page 51 / 87

Suitable for direct burial•Sunlight resistant•RoHS compliant•Bare conductors are heat treated after stranding for maximum flexibility•

Page 52: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® RHH/RHW­2/USE­2 CopperContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V2.0 Generated 8/2/18 www.nexans.us Page 52 / 87

STANDARDS

National ICEA S-95-658;UL 854; UL 44

XLPE Insulated Cable 600 Volts, 90ºC Dry or Wet - LEAD FREE NEC ART 310 and338 Copper Conductors

DESCRIPTION

ApplicationNexans ENERGEX® RHH/RHW-2/USE-2 conductors may be installed in racewaysand conduits or directly buried. They are 90ºC, 600 volts per NEC Articles 310 and338.

Type USE-2 conductors are suitable as service entrance conductors which can beinstalled directly buried in accordance with the NEC.

When used as type RHH, the cables are suitable for installation in dry locations.

As type RHW-2 and USE-2, cables are suitable for installation in both wet and drylocations.

Nexans RHH/RHW-2/USE-2 conductors are LEAD FREE and RoHS compliant.

ConstructionConductor:Stranded annealed soft bare copper conductors per ASTM B8 and B787

Insulation:Heat, sunlight, moisture and abrasion resistant cross-lined polyethylene (XLPE)insulation per UL 854 and UL 44. Black only.

SpecificationsMeets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables•Meets UL 854 (USE-2) Service Entrance Cables•Federal Specification A-A-59544•ICEA 5-95-658•National Electrical Code - NFPA 70•Conductors 1/0 AWG and larger are rated CT use•

Surface Print Legend (example)

NEXANS 1/0 AWG (53.5 mm2) (UL) E64801 F RHW-2 OR USE-2 600V FOR CT USESR MADE IN CANADA LEAD FREE (MFG DATE).

Page 53: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® RHH/RHW­2/USE­2 CopperContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V2.0 Generated 8/2/18 www.nexans.us Page 53 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 54: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® RHH/RHW­2/USE­2 CopperContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V2.0 Generated 8/2/18 www.nexans.us Page 54 / 87

ENERGEX® 8000 RHH/RHW­2/USE­2 COPPER ­ 600 V

ConductorSize

AWG/kcmil

Insulation Thickness Nominal Diameter Approximate NetCable Weight

Ampacity*(amps)

mils mm inches mm lb/kft kg/km 60ºC 75ºC 90ºC14 (1) 45 1.14 0.16 4.0 21 31 15 15 15

12 (1) 45 1.14 0.17 4.4 30 44 20 20 20

10 (1) 45 1.14 0.19 4.9 44 65 30 30 30

14 (7) 45 1.14 0.16 4.1 21 31 15 15 15

12 (7) 45 1.14 0.18 4.7 30 44 20 20 20

10 (7) 45 1.14 0.21 5.2 44 65 30 30 30

8 (7) 60 1.52 0.27 6.8 70 105 40 50 55

6 (7) 60 1.52 0.31 7.8 104 156 55 65 75

4 (7) 60 1.52 0.35 8.9 157 234 70 85 95

2 (19) 60 1.52 0.41 10.4 240 357 95 115 130

1 (19) 80 2.03 0.49 12.4 309 460 110 130 150

1/0 (19) 80 2.03 0.53 13.4 379 564 125 150 170

2/0 (19) 80 2.03 0.57 14.5 474 706 145 175 195

3/0 (19) 80 2.03 0.61 15.4 583 869 165 200 225

4/0 (19) 80 2.03 0.68 17.2 755 1124 195 230 260

250 (37) 95 2.41 0.74 18.7 867 1291 215 255 290

300 (37) 95 2.41 0.81 20.5 1029 1531 240 285 320

350 (37) 95 2.41 0.86 21.8 1192 1773 260 310 350

400 (37) 95 2.41 0.90 22.9 1352 2012 280 335 380

500 (37) 95 2.41 0.99 25.1 1686 2509 320 380 430

600 (61) 110 2.79 1.09 26.4 2012 2995 355 420 475

700 (61) 110 2.79 1.16 29.5 2332 3470 385 460 520

750 (61) 110 2.79 1.20 30.4 2492 3710 400 475 535

1000 (61) 110 2.79 1.35 34.2 3288 4895 455 545 615

Page 55: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® RHH/RHW­2/USE­2 CopperContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V2.0 Generated 8/2/18 www.nexans.us Page 55 / 87

*60ºC ­ When terminated to equipment for circuits rated 100 amperes or less or marked forconductor sizes 14 through 1 AWG.75ºC ­ When terminated to equipment for circuits rated over 100 amperes or marked forconductors larger than 1 AWG.90ºC ­ RHH dry locations. RHW­2 and USE­2 wet or dry locations. For ampacityderating purposes.

Notes:

• Where stated, "nominal" and "approximate" values are provided for information purposesonly and are subject to standard manufacturing tolerances.• Ampacities are in accordance with NEC Article 310.15, which are basedon NEC Table 310.15(B)(16) for conductors in a raceway ordirect buried at 30°C ambient temperature.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.15(B)(16).• NEC Article 240.4(D) required that over current protection not exceed15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copperconductors after any correction factors for ambient temperature and number of conductorshave been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).

SELLING INFORMATION

Product FeaturesCables are UL listed as Type USE-2•Temperature rating of 90ºC dry and wet•Suitable for direct burial•Sunlight resistant•LEAD FREE and RoHS compliant.•

Page 56: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Conduit Wire & CableContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Generated 8/2/18 www.nexans.us Page 56 / 87

Unarmoured Nexans wire and cable is generally installed in conduit or undergroundduct in dry, damp and wet locations depending on the product construction. All aredesigned for ease of installation and superior performance.

Page 57: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 Aluminum XHHW­2ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V5.0 Generated 8/2/18 www.nexans.us Page 57 / 87

STANDARDS

National ICEA S-95-658; UL 44

XLPE Insulated Cable, ACM Aluminum Conductors, 600 Volts, 90ºC Dry or Wet -RoHS Compliant

DESCRIPTION

ApplicationNexans ENERGEX® 8000 XHHW-2 is an AA-8000 series aluminum (ACM) conductorwith cross-linked polyethylene insulation. The cable is rated at 600 volts and 90ºC foruse in wet and dry locations. XHHW-2 can be used in conduit and other raceways forservices, feeders and other applications recognized by the NEC. Sizes 12 AWG to4/0 AWG are approved as SIS.

Nexans XHHW-2 is RoHS compliant.

ConstructionConductor:Compact stranded AA-8000 series aluminum alloy (ACM) per ASTM B801 or B836.

Insulation:Black, sunlight resistant, cross-linked polyethylene (XLPE) meeting the requirementsfor XHHW-2 per UL 44.

SpecificationsNexans ENERGEX® 8000 Type XHHW-2 meets or exceeds all applicable ASTMspecifications

UL 44: Thermoset - Insulated Wires and Cables•NEC Article 310.104•Federal Specification A-A-59544 and the requirements of the NEC•Meets or exceeds the requirements of NEMA WC 70 / ICEA S-99-658: PowerCables Rated 2000 Volts or Less for the Distribution of Electrical Energy

Sunlight resistant in black 8 AWG and larger•Sizes 12 AWG to 4/0 AWG rated SIS•Voltage rating - 600 Volts•Meets IEEE 1202•

Surface Print Legend (example)NEXANS-C 1/0 AWG COMPACT AA-8000-AL XHHW-2 600V SR ROHS (UL)(MFG. DATE)

Page 58: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 Aluminum XHHW­2ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V5.0 Generated 8/2/18 www.nexans.us Page 58 / 87

CHARACTERISTICSConstruction characteristics

Conductor material AluminumElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 59: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 Aluminum XHHW­2ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V5.0 Generated 8/2/18 www.nexans.us Page 59 / 87

ENERGEX® 8000 XHHW­2 ALUMINUM

ConductorSize

AWG/kcmil

Insulation Thickness Nominal Diameter Approximate NetCable Weight

Ampacity*(Amps)

mils mm inches mm lb/kft kg/km 60 ºC 75 ºC 90 ºC6 45 1.14 0.26 6.6 40 59 40 50 55

4 45 1.14 0.31 7.9 57 85 55 65 75

2 45 1.14 0.36 9.1 84 125 75 90 100

1 55 1.40 0.42 10.7 108 161 85 100 115

1/0 55 1.40 0.45 11.4 131 196 100 120 135

2/0 55 1.40 0.49 12.4 161 239 115 135 150

3/0 55 1.40 0.54 13.7 198 294 130 155 175

4/0 55 1.40 0.59 15.0 243 361 150 180 205

250 65 1.65 0.66 16.8 292 434 170 205 230

300 65 1.65 0.71 18.0 352 524 195 230 260

350 65 1.65 0.75 19.1 394 586 210 250 280

400 65 1.65 0.8 20.3 446 663 225 270 305

500 65 1.65 0.87 22.1 548 815 260 310 350

600 80 2.03 0.98 24.9 670 997 285 340 385

700 80 2.03 1.04 26.4 787 1171 315 375 425

750 80 2.03 1.08 27.4 822 1224 320 385 435

900 80 2.03 1.16 29.5 994 1478 355 425 480

*60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked forconductor sizes 12 AWG through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked forconductors larger than size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.

Notes:

• Where stated, "nominal" and "approximate" values are provided for information purposesonly and are subject to standard manufacturing tolerances.• Ampacity are in accordance with NEC Article 310.15, which are basedon NEC Table 310.15(B)(16) for aluminum conductors in a racewayor direct buried at 30°C ambient temperature.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.15(B)(16).• NEC Article 240.4(D) required that over current protection not exceed15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum conductors after anycorrection factors for ambient temperature and number of conductors have been applied.Exceptions to this may be covered in NEC Article 240.4(E) through (G).

Page 60: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® 8000 Aluminum XHHW­2ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V5.0 Generated 8/2/18 www.nexans.us Page 60 / 87

PACKAGE QUANTITIES AND PART NUMBERS

ConductorSize

AWG/kcmil

Package Quantity / Part Number

500 ft reel 1000 ft reel 5000 ft reel Long LengthCutting Reels

6 677096 677088 677427 680016

4 677153 677146 677435 680018

2 677112 677104 677211 680019

1 677864 677872 - 677898

1/0 660993 661009 - 661033

2/0 677179 677161 - 661777

3/0 - 680086 - 661322

4/0 677070 677062 - 661363

250 677591 677583 - 677906

300 - - - 680053

350 661041 661058 - 661082

400 - 680194 - 661348

500 677914 677922 - 677955

600 - - 661371 661355

750 - 680732 - 661330

900 - - - 662547

SELLING INFORMATIONProduct Features

· Cables are UL listed as Type XHHW-2

·Temperature rating of 90ºC dry and wet

·Sunlight Resistant, black 8 AWG and larger

·RoHS compliant

·Bare conductors are heat treated after stranding for maximum flexibility

· Sizes 12 AWG - 4/0 AWG rated SIS

Options

Rating for CT use available in conductor sizes 1/0 AWG and larger (4 AWG and larger in green).

Page 61: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® THHN /THWN­2 / MTW

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V6.0 Generated 8/2/18 www.nexans.us Page 61 / 87

STANDARDS

National CSA C22.2 N° 75;ICEA S-95-658; UL 1063; UL 83

PVC/Nylon Cable, Copper Conductors, 600 Volts, 90°C dry rated - LEAD FREE

DESCRIPTION

ApplicationNexans ENERGEX® INSTAGLIDE® THHN / THWN-2 / MTW is a general purposewiring product for use in power, lighting and control circuits. It can be used in conduit,ducts and trays for service feeders and branch circuits in industrial and commercialinstallations. When used in accordance with the NEC, THHN / THWN-2 is suitable foruse in wet and dry locations, at conductor temperatures not exceeding 90ºC or for usein oil or coolants at conductor temperatures not exceeding 75ºC. THHN / THWN-2 isgasoline and oil resistant II. When used as Machine Tool Wire (MTW) it is rated at90ºC in dry locations and 60ºC in wet locations or when exposed to oil or coolants.

Nexans ENERGEX® INSTAGLIDE® THHN / THWN-2/ MTW wire is RoHS compliant.

Nexans INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.

ConstructionConductor:Solid bare, annealed copper per ASTM B3. Stranded bare annealed copper per ASTMB3 and ASTM B8 Class C compressed for sizes 14 AWG to 2 AWG, and ASTM B8Class B unilay compressed for sizes 1 AWG and larger.

Insulation:Color coded polyvinyl chloride (PVC), heat, moisture and flame retardant compoundper UL 83 and UL 1063.

Covering:A tough abrasion resistant polyamide (Nylon) covering.

SpecificationsNexans ENERGEX® INSTAGLIDE® THHN / THWN-2 or MTW meets or exceeds allapplicable ASTM specifications

UL 83: Thermoplastic-Insulated Wires and Cables•UL 1063: Machine-Tool Wires and Cables (stranded cables only)•NEMA WC70 / ICEA S-95-658: Power Cables Rated 2000V or Less for theDistribution of Electrical Energy

Federal Specification A-A-59544 and requirements of the NEC•CSA C22.2 No. 75: Thermoplastic Insulated Wires and Cables•14 AWG through 750 kcmil are rated VW-1.•Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated CT use•Black sizes 1/0 AWG and larger are sunlight resistant•Rated 600 volts•Sizes 8 AWG and larger sequentially marked every 2 feet.•

Surface Print Legend (example)

NEXANS-C INSTAGLIDE 500 kcmil (253mm2) TYPE MTW OR THHN OR THWN-2GRII SR FOR CT USE VW-1 600V (UL) RoHS (MFG. DATE)

Page 62: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® THHN /THWN­2 / MTW

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V6.0 Generated 8/2/18 www.nexans.us Page 62 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 63: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® THHN /THWN­2 / MTW

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V6.0 Generated 8/2/18 www.nexans.us Page 63 / 87

ENERGEX® INSTAGLIDE® THHN / THWN­2 / MTW COPPER

ConductorSize

PVC InsulationThickness

NylonThickness

NominalDiameter

Approximate NetCable Weight

Ampacity*(Amps)

AWG/kcmil mils mils inches lbs/kft 60ºC 75ºC 90ºC14 (1) 15 4 0.11 15 15 15 15

12 (1) 15 4 0.12 23 20 20 20

10 (1) 20 4 0.15 37 30 30 30

14 (19) 15 4 0.11 16 15 15 15

12 (19) 15 4 0.13 24 20 20 20

10 (19) 20 4 0.17 39 30 30 30

8 (19) 30 5 0.22 63 40 50 55

6 (19) 30 5 0.26 98 55 65 75

4 (19) 40 6 0.33 157 70 85 95

3 (19) 40 6 0.36 193 85 100 110

2 (19) 40 6 0.39 240 95 115 130

1 (19) 50 7 0.43 300 110 130 150

1/0 (19) 50 7 0.47 376 125 150 170

2/0 (19) 50 7 0.51 467 145 175 195

3/0 (19) 50 7 0.56 581 165 200 225

4/0 (19) 50 7 0.61 724 195 230 260

250 (37) 60 8 0.68 855 215 255 290

300 (37) 60 8 0.73 1022 240 285 320

350 (37) 60 8 0.78 1191 260 310 350

400 (37) 60 8 0.82 1345 280 335 380

500 (37) 60 8 0.90 1668 320 380 430

600 (61) 70 9 0.98 1994 355 420 475

750 (61) 70 9 1.08 2465 400 475 535

*60ºC ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductorsizes 14 through 1 AWG. For MTW in wet locations or when exposed to oil or coolant.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductorslarger than size 1 AWG. THWN­2 when exposed to oil or coolant.90°C ­ THHN dry locations. THWN­2 wet or dry locations. For ampacity derating purposes.Available colors: Black, White, Red, Blue, Green, Yellow, Brown, Orange, Purple, Gray, Pink.

Notes:• Where stated, “nominal” and “approximate” values are provided for information purposes only andare subject to standard manufacturing tolerances.• Ampacities are in accordance with NEC Article 310.15, which are based onNEC Table 310.15(B)(16) for conductors in a raceway or directburied at 30°C ambient temperature.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.15(B)(16).• NEC Article 240.4(D) requires that overcurrent protection not exceed15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copperconductors after any correction factors for ambient temperature and number of conductorshave been applied. Exceptions to this may be covered in NECArticle 240.4(E) through (G).

Page 64: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® THHN /THWN­2 / MTW

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V6.0 Generated 8/2/18 www.nexans.us Page 64 / 87

SELLING INFORMATION

Product FeaturesNexans INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.•Sizes 8 AWG to 600 kcmil available in various colors from stock•Cables are UL listed as Type THHN / THWN-2/ MTW•Meets UL VW-1 flame test requirements•Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) are rated CT use•Black sizes 1/0 AWG and larger are sunlight resistant•Color coded polyvinyl chloride (PVC), heat, moisture and flame retardant insulation system•THWN-2 90ºC rated for dry and wet locations•Gasoline and Oil Resistant II•Small diameter for improved conduit fill•RoHS compliant•

Packaging14 AWG & 12 AWG: 4 x 500' spools (2000' per carton) or 2500' reel•10 AWG: 2 x 500' spools (1000' per carton) or 2500' reel•8 AWG - 350 kcmil: 500', 1000', 2500' or 5000' reel•400 kcmil - 500 kcmil: 500', 1000', or 2500' reel•600 kcmil - 750 kcmil: 500' reel•

* Only stranded cables are MTW listed per UL 1063.

Page 65: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® XHHW­2Copper

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V3.0 Generated 8/2/18 www.nexans.us Page 65 / 87

STANDARDS

National ICEA S-95-658; UL 44

XLPE Insulated Cable, Copper Conductors, 600 Volts, 90ºC Dry or Wet - LEAD FREE

DESCRIPTION

ApplicationNexans ENERGEX® INSTAGLIDE® XHHW-2 is a copper conductor, with cross-linkedpolyethylene insulation. The cable is rated at 600 volts and 90°C for use in wet anddry locations. XHHW-2 can be used in conduit and other raceways for services,feeders and other applications recognized by the NEC.

Sizes 14 AWG to 4/0 AWG are approved as Type SIS.

Sizes 1/0 AWG and larger (4 AWG and larger in green) in all colors are cable tray (CT)rated.

Nexans ENERGEX® INSTAGLIDE® XHHW-2 conductors are RoHS compliant.

Nexans INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.

ConstructionConductor:Annealed soft bare copper per ASTM B3, B787 and B8

Insulation:Cross-linked polyethylene (XLPE) insulation per UL 44

Surface Print Legend (example)NEXANS EXELENE 500 kcmil (253 mm2) XHHW-2 (UL) E64801 F 600V FOR CTUSE SR - MADE IN CANADA LEAD FREE (MFG. DATE)

SpecificationsNexans ENERGEX® Type XHHW-2 meets or exceeds all applicable ASTMspecifications.

UL 44: Thermoset-Insulated Wire and Cables•Federal Specification A-A-59544 and the requirements of the NEC.•NEMA WC70 / ICEA S-95-658: Power Cables Rated 2000 Volts or Less for theDistribution of Electrical Energy.

Conductor sizes 1/0 AWG and larger (4 AWG and larger in green) rated for CT use.•Sunlight resistant in black 8 AWG and larger.•14 AWG to 10 AWG are available in 10 distinct colors for identification purposes.•Sizes 14 AWG to 4/0 AWG rated SIS.•Nexans XHHW-2 is LEAD FREE.•Voltage rating - 600 Volts.•

Page 66: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® XHHW­2Copper

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V3.0 Generated 8/2/18 www.nexans.us Page 66 / 87

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 67: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® XHHW­2Copper

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V3.0 Generated 8/2/18 www.nexans.us Page 67 / 87

ENERGEX® INSTAGLIDE® XHHW­2 COPPER

ConductorSize

AWG/kcmil

Insulation Thickness NominalDiameter

Approximate NetCable Weight

Ampacity*(amps)

mils mm inches mm lb/kft kg/km 60ºC 75ºC 90ºC14 (7) 30 0.76 0.130 3.40 18 27 15 15 15

12 (7) 30 0.76 0.150 3.80 26 39 20 20 20

10 (7) 30 0.76 0.170 4.50 40 60 30 30 30

8 (7) 45 1.14 0.240 6.00 64 95 40 50 55

6 (7) 45 1.14 0.270 6.90 97 144 55 65 75

4 (7) 45 1.14 0.320 8.20 149 222 70 85 95

2 (7) 45 1.14 0.380 9.60 230 342 95 115 130

1 (19) 55 1.40 0.430 10.90 288 429 110 130 150

1/0 (19) 55 1.40 0.480 12.10 360 536 125 150 170

2/0 (19) 55 1.40 0.520 13.20 456 679 145 175 195

3/0 (19) 55 1.40 0.560 14.20 563 838 165 200 225

4/0 (19) 55 1.40 0.610 15.60 703 1046 195 230 260

250 (37) 65 1.65 0.680 17.10 837 1245 215 255 290

300 (37) 65 1.65 0.750 18.90 995 1481 240 285 320

350 (37) 65 1.65 0.800 20.20 1155 1719 260 310 350

400 (37) 65 1.65 0.840 21.40 1324 1970 280 335 380

500 (37) 65 1.65 0.930 23.50 1643 2445 320 380 430

600 (61) 80 2.03 1.040 26.30 1986 2955 355 420 475

700 (61) 80 2.03 1.100 27.90 2283 3397 385 460 520

750 (61) 80 2.03 1.140 28.80 2467 3671 400 475 535

1000 (61) 80 2.03 1.290 32.70 3230 4806 455 545 615

*60°C ­ When terminated to equipment for circuits rated 100 amperes or less or marked forconductor sizes 14 through 1 AWG.75°C ­ When terminated to equipment for circuits rated over 100 amperes or marked forconductors larger than size 1 AWG.90°C ­ Wet or dry locations. For ampacity derating purposes.

Notes:

• Where stated, "nominal" and "approximate" values are provided for information purposesonly and are subject to standard manufacturing tolerances.• Ampacity are in accordance with NEC Article 310.15, which are basedon NEC Table 310.16 or NEC Table 310.15(B)(16) for conductors in a raceway ordirect buried at 30°C ambient temperature.• For correction factors for different ambient temperatures and ampacities at different conductortemperature ratings see NEC Table 310.16 or NEC Table 310.15(B)(16).• NEC Article 240.4(D) required that over current protection not exceed15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copperconductors after any correction factors for ambient temperature and number of conductorshave been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).

Page 68: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® INSTAGLIDE® XHHW­2Copper

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V3.0 Generated 8/2/18 www.nexans.us Page 68 / 87

SELLING INFORMATION

Product FeaturesSizes 14 AWG to 10 AWG are available in 10 colors: Black, White, Red, Blue, Green, Yellow, Brown, Orange, Gray,Purple.

Size 8 AWG and larger in black only.•Meets IEEE 1202•Conforms to ICEA S-95-658•Sunlight Resistant 8 AWG and larger in black•Conductor sizes 1/0 AWG and larger (4 AWG and larger in green are rated for CT use•Sizes 14 AWG to 4/0 AWG rated SIS•Meets or exceeds all applicable industry standards•LEAD FREE•

Packaging14 AWG to 10 AWG 2 x 500’ spools (1000 feet) per carton; 2500’ reel•8 AWG to 600 kcmil long length•750 kcmil 500’ reel or long length•

Page 69: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Components, Specialty & Bare CopperContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Generated 8/2/18 www.nexans.us Page 69 / 87

Cables specially designed for unique installation requirements.

Page 70: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

ENERGEX® PV/RHH/RHW­2/USE­2ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 70 / 87

STANDARDS

National ICEA S-95-658;UL 854; UL 854 Subject 4703;UL 44

DESCRIPTIONNexans ENERGEX® PV solar cables offer exceptional performance, easy installationand long-term reliability for DC connections. They link photovoltaic panels on rooftopsor solar farms, and also connect them to the array box (if one exists), and to theinverter which transforms DC solar energy into usable AC electricity. These cableshave a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, andare certified as UL type PV.

Page 71: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableAluminum ­ 2 kV

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 71 / 87

STANDARDS

National ICEA S-95-658;UL 854; UL 854 Subject 4703;UL 44

Part Number: Solar Cable

DESCRIPTIONNexans ENERGEX® PV solar cables offer exceptional performance, easy installationand long-term reliability for DC connections. They link photovoltaic panels on rooftopsor solar farms, and also connect them to the array box (if one exists), and to theinverter which transforms DC solar energy into usable AC electricity. These cableshave a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, andare certified as UL type PV.

Application

Nexans ENERGEX® PV/RHH/RHW-2/USE-2 cables may be installed indoors oroutdoors, in raceways and conduits, or directly buried. They are 90ºC, 2 kV per NECArticles 310 and 338, and suitable for use in a photovoltaic system per NEC Article690.

Type PV cables are for use on the DC side of a photovoltaic system, suitable forinstallation in both wet and dry locations, and may be exposed to sunlight.

Type USE-2 cables are suitable as service entrance cables, which can be installeddirectly buried in accordance with the NEC.

When used as type RHH cables are suitable for installation in dry locations.

Type RHW-2 and USE-2 cables are suitable for installation in both wet and drylocations.

Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE.

Construction

Conductor: Compact stranded AA-8000 series aluminum conductor material (ACM)per ASTM B801 Class B or ASTM B836 (Single Input Wire).

Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene(XLPE) insulation in black or colors per UL 854 and UL 44

Specifications

Meets UL Subject 4703 (PV) Photovoltaic Wire•Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables•Meets UL 854 (USE-2) Service Entrance Cables•Federal Specification A-A-59544•National Electrical Code - NFPA 70•Conductors 1/0 AWG and larger are rated CT use•UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2)•

Surface Print Legend (example)

(mon/year) NEXANS [plant] 350 kcmil (177.3 mm2) CPT ACM ALUM (UL) USE-2 600VOR RHW-2 OR PV WIRE 2000V 90C WET OR DRY SR DIR BUR LEAD FREE

Page 72: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableAluminum ­ 2 kV

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 72 / 87

CHARACTERISTICSConstruction characteristics

Conductor material AluminumElectrical characteristics

Maximum operating voltage 2000 VUsage characteristics

Maximum operating temperature 90 °C

Page 73: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableAluminum ­ 2 kV

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 73 / 87

ENERGEX® PV/RHH/RHW­2/USE­2 ALUMINUM ­ 2 KV

ConductorSize

AWG/kcmil

Insulation Thickness Nominal Diameter Approximate NetCable Weight

Ampacity*(amps)

mils mm inches mm lb/kft kg/km 60ºC 75ºC 90ºC6 85 2.16 0.34 8.6 57 84 40 50 60

4 85 2.16 0.39 9.9 77 115 55 65 75

2 85 2.16 0.44 11.2 108 160 75 90 100

1 105 2.67 0.51 13.0 142 212 85 100 115

1/0 105 2.67 0.55 14.0 169 251 100 120 135

2/0 105 2.67 0.59 15.0 202 300 115 135 150

3/0 105 2.67 0.64 16.3 240 357 130 155 175

4/0 105 2.67 0.69 17.5 292 434 150 180 205

250 120 3.05 0.76 19.3 354 528 170 205 230

300 120 3.05 0.81 20.6 412 613 190 230 255

350 120 3.05 0.86 21.8 468 697 210 250 280

400 120 3.05 0.90 22.9 525 781 225 270 305

500 120 3.05 0.98 24.9 607 904 260 310 350

600 135 3.43 1.09 27.7 771 1147 285 340 385

750 135 3.43 1.18 30.0 935 1391 320 385 435

1000 135 3.43 1.33 33.8 1214 1806 375 445 500

60ºC ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductorsizes #6 through #1 AWG.75ºC ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductorslarger than #1 AWG.90ºC ­ RHH dry locations. PV and RHW­2 wet or dry locations. For ampacity derating purposes.For conductors installed in conduit on a roof top, use the derating factors specified byTable 310.15(B)(3)(c) in the NEC.

* Allowable ampacities shown are for general use as specified by the NEC, Section 310.15.

SELLING INFORMATIONProduct Features

Cables are UL listed as Type PV•Cables are UL listed as Type USE-2•Temperature rating of 90ºC dry and wet•Suitable for direct burial•Sunlight resistant in black and colors•Conductors 1/0 AWG and larger are rated CT use•LEAD FREE•

Options

Class C stranding available•

Page 74: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableAluminum ­ 600 V

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 74 / 87

STANDARDS

National ICEA S-95-658;UL 854; UL 854 Subject 4703;UL 44

Part Number: Solar Cable

DESCRIPTIONNexans ENERGEX® PV solar cables offer exceptional performance, easy installationand long-term reliability for DC connections. They link photovoltaic panels on rooftopsor solar farms, and also connect them to the array box (if one exists), and to theinverter which transforms DC solar energy into usable AC electricity. These cableshave a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, andare certified as UL type PV.

Application

Nexans ENERGEX® PV/RHH/RHW-2/USE-2 cables may be installed indoors oroutdoors, in raceways and conduits, or directly buried. They are 90ºC, 600 V per NECArticles 310 and 338, and suitable for use in a photovoltaic system per NEC Article690.

Type PV cables are for use on the DC side of a photovoltaic system, suitable forinstallation in both wet and dry locations, and may be exposed to sunlight.

Type USE-2 cables are suitable as service entrance cables, which can be installeddirectly buried in accordance with the NEC.

When used as type RHH cables are suitable for installation in dry locations.

Type RHW-2 and USE-2 cables are suitable for installation in both wet and drylocations.

Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE.

Construction

Conductor:Compact stranded AA-8000 series aluminum conductor material (ACM)per ASTM B801 Class B or ASTM B836 (Single Input Wire).

Insulation:Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene(XLPE) insulation in black or colors per UL 854 and UL 44

Specifications

Meets UL Subject 4703 (PV) Photovoltaic Wire•Meets UL 44: (RHH, RWH-2) Thermoset Insulated Wires and Cables•Meets UL 854 (USE-2) Service Entrance Cables•Federal Specification A-A-59544•National Electrical Code - NFPA 70•Conductors 1/0 AWG and larger are rated CT use•UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2)•

Surface Print Legend (example)

(mon/year) NEXANS [plant] 350 kcmil (177.3 mm2) CPT ACM ALUM (UL) RHW-2 ORUSE-2 OR PV WIRE 600V 90C WET OR DRY SR DIR BUR LEAD FREE

Page 75: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableAluminum ­ 600 V

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 75 / 87

CHARACTERISTICSConstruction characteristics

Conductor material AluminumElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 76: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableAluminum ­ 600 V

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 76 / 87

ENERGEX® PV/RHH/RHW­2/USE­2 ALUMINUM ­ 600 V

ConductorSize

AWG/kcmil

Insulation Thickness Nominal Diameter Approximate NetCable Weight

Ampacity*(amps)

mils mm inches mm lb/kft kg/km 60ºC 75ºC 90ºC6 75 1.91 0.32 8.2 52 77 40 50 60

4 75 1.91 0.37 9.3 72 107 55 65 75

2 75 1.91 0.42 10.7 102 151 75 90 100

1 95 2.41 0.49 12.5 135 201 85 100 115

1/0 95 2.41 0.53 13.4 161 240 100 120 135

2/0 95 2.41 0.57 14.5 193 288 115 135 150

3/0 95 2.41 0.62 15.6 231 344 130 155 175

4/0 95 2.41 0.67 17.0 282 420 150 180 205

250 110 2.79 0.74 18.9 344 512 170 205 230

300 110 2.79 0.79 20.2 401 596 190 230 255

350 110 2.79 0.84 21.3 456 679 210 250 280

400 110 2.79 0.88 22.4 512 762 225 270 305

500 110 2.79 0.96 24.4 621 925 260 310 350

600 125 3.18 1.07 27.1 755 1124 285 340 385

750 125 3.18 1.16 29.5 918 1367 320 385 435

1000 125 3.18 1.31 33.4 1195 1778 375 445 500

60ºC ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductorsizes #6 through #1 AWG.75ºC ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductorslarger than #1 AWG.90ºC ­ RHH dry locations. PV, RHW­2 and USE­2 wet or dry locations. For ampacity derating purposes.For conductors installed in conduit on a roof top, use the derating factors specified byTable 310.15(B)(3)(c) in the NEC.

* Allowable ampacities shown are for general use as specified by the NEC, Section 310.15.

SELLING INFORMATIONProduct Features

Cables are UL listed as Type PV•Cables are UL listed as Type USE-2•Temperature rating of 90ºC dry and wet•Suitable for direct burial•Sunlight resistant in black and colors•Conductors 1/0 and larger are rated CT use•LEAD FREE•

Options

Class C stranding available•

Page 77: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 2 kV

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 77 / 87

STANDARDS

National ICEA S-95-658;UL 854; UL 854 Subject 4703;UL 44

Part Number: Solar Cable

DESCRIPTIONNexans ENERGEX® PV solar cables offer exceptional performance, easy installationand long-term reliability for DC connections. They link photovoltaic panels on rooftopsor solar farms, and also connect them to the array box (if one exists), and to theinverter which transforms DC solar energy into usable AC electricity. These cableshave a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, andare certified as UL type PV.

Application

Nexans ENERGEX® PV/RHH/RHW-2/USE-2 cables may be installed indoors oroutdoors, in raceways and conduits, or directly buried. They are 90ºC, 2 kV per NECArticles 310 and 338, and suitable for use in a photovoltaic system per NEC Article690.

Type PV cables are for use on the DC side of a photovoltaic system, suitable forinstallation in both wet and dry locations, and may be exposed to sunlight.

Type USE-2 cables are suitable as service entrance cables, which can be installeddirectly buried in accordance with the NEC.

When used as type RHH, the cables are suitable for installation in dry locations.

Type RHW-2 and USE-2 cables are suitable for installation in both wet and drylocations.

Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE.

Construction

Conductor: Stranded annealed soft bare copper conductors per ASTM B8 and B787

Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene(XLPE) insulation in black or colors per UL 854 and UL 44

Specifications

Page 78: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 2 kV

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 78 / 87

Meets UL Subject 4703 (PV) Photovoltaic Wire•Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables•Meets UL 854 (USE-2) Service Entrance Cables•Federal Specification A-A-59544•National Electrical Code - NFPA 70•Conductors 1/0 AWG and larger are rated CT use•UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2•

Surface Print Legend (example)

(mon/year) NEXANS [plt] 350 kcmil (177.3 mm2) (UL) USE-2 600V OR RHW-2 OR PVWIRE 2000V 90C WET OR DRY SR DIR BUR LEAD FREE

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 2000 VUsage characteristics

Maximum operating temperature 90 °C

Page 79: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 2 kV

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 79 / 87

ENERGEX® PV/RHH/RHW­2/USE­2 COPPER ­ 2 KV

ConductorSize

AWG/kcmil

Insulation Thickness Nominal Diameter Approximate NetCable Weight

Ampacity*(amps)

mils mm inches mm lb/kft kg/km 60ºC 75ºC 90ºC8 (7) 85 2.16 0.31 7.9 80 119 40 50 55

6 (7) 85 2.16 0.35 8.8 115 171 55 65 75

4 (7) 85 2.16 0.40 10.0 169 251 70 85 95

2 (7) 85 2.16 0.46 11.5 253 377 95 115 130

1 (19) 105 2.67 0.53 13.3 323 481 110 130 150

1/0 (19) 105 2.67 0.57 14.3 398 592 125 150 170

2/0 (19) 105 2.67 0.61 15.4 489 728 145 175 195

3/0 (19) 105 2.67 0.66 16.6 605 900 165 200 225

4/0 (19) 105 2.67 0.71 18.0 750 1116 195 230 260

250 (37) 120 3.05 0.79 19.9 896 1333 215 255 290

300 (37) 120 3.05 0.84 21.6 1059 1576 240 285 320

350 (37) 120 3.05 0.88 22.4 1220 1816 260 310 350

400 (37) 120 3.05 0.93 23.5 1388 2066 280 335 380

500 (37) 120 3.05 1.10 25.6 1714 2551 320 380 430

600 (61) 135 3.43 1.12 28.2 2064 3072 355 420 475

700 (61) 135 3.43 1.21 29.9 2395 3564 385 460 520

750 (61) 135 3.43 1.24 30.7 2560 3810 400 475 535

1000 (61) 135 3.43 1.39 35.2 3367 5011 455 545 615

60ºC ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductorsizes 8 through 1 AWG.75ºC ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductorslarger than 1 AWG.90ºC ­ RHH dry locations. PV, RHW­2 and USE­2 wet or dry locations. For ampacity derating purposes.

* Allowable ampacities shown are for general use as specified by the NEC, Section 310.15. Forconductors installed in conduiton a roof top, use the derating factors specified by Table 310.15(B)(3)(c) in the NEC.

Note: Where stated, "nominal" and "approximate" values are provided for information purposes only andare subject to standard manufacturing tolerances.

SELLING INFORMATIONProduct Features

Cables are UL listed as Type PV•Cables are UL listed as Type USE-2•Temperature rating of 90ºC dry and wet•Suitable for direct burial•Sunlight resistant in black and colors•Coductors 1/0 AWG and larger are rated CT use•LEAD FREE•

Page 80: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 2 kV

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 80 / 87

Options

Class C stranding available•

Page 81: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 600 V

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 81 / 87

STANDARDS

National ICEA S-95-658;UL 854; UL 854 Subject 4703;UL 44

Part Number: Solar Cable

DESCRIPTIONNexans ENERGEX® PV solar cables offer exceptional performance, easy installationand long-term reliability for DC connections. They link photovoltaic panels on rooftopsor solar farms, and also connect them to the array box (if one exists), and to theinverter which transforms DC solar energy into usable AC electricity. These cableshave a wet and dry temperature rating of 90°C, are UV resistant, flame-retardant, andare certified as UL type PV.

Application

Nexans ENERGEX® PV/RHH/RHW-2/USE-2 cables may be installed indoors oroutdoors, in raceways and conduits, or directly buried. They are 90ºC, 600 V or 2 kVper NEC Articles 310 and 338, and suitable for use in a photovoltaic system per NECArticle 690.

Type PV cables are for use on the DC side of a photovoltaic system, suitable forinstallation in both wet and dry locations, and may be exposed to sunlight.

Type USE-2 cables are suitable as service entrance cables, which can be installeddirectly buried in accordance with the NEC.

Type RHH cables are suitable for installation in dry locations.

Type RHW-2 and USE-2 cables are suitable for installation in both wet and drylocations.

Nexans PV/RHH/RHW-2/USE-2 cables are LEAD FREE.

Construction

Conductor: Stranded annealed soft bare copper conductors per ASTM B8 and B787

Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene(XLPE) insulation in black or colors per UL 854 and UL 44

Specifications

Page 82: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 600 V

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 82 / 87

Meets UL Subject 4703 (PV) Photovoltaic Wire•Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables•Meets UL 854 (USE-2) Service Entrance Cables•Federal Specification A-A-59544•National Electrical Code - NFPA 70•Conductors 1/0 AWG and larger are rated CT use•UL File Numbers: E338981 (PV), E49786 (USE-2), E64801 (RHH, RHW-2)•

Surface Print Legend (example)

(mon/year) NEXANS [plant] 350 kcmil (177.3 mm2) (UL) RHW-2 OR USE-2 OR PVWIRE 600V 90C WET OR DRY SR DIR BUR LEAD FREE

CHARACTERISTICSConstruction characteristics

Conductor material CopperElectrical characteristics

Maximum operating voltage 600 VUsage characteristics

Maximum operating temperature 90 °C

Page 83: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 600 V

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 83 / 87

ENERGEX® PV/RHH/RHW­2/USE­2 COPPER ­ 600 V

ConductorSize

AWG/kcmil

Insulation Thickness Nominal Diameter Approximate NetCable Weight

Ampacity*(amps)

mils mm inches mm lb/kft kg/km 60ºC 75ºC 90ºC8 (7) 75 1.91 0.29 7.5 76 113 40 50 55

6 (7) 75 1.91 0.33 8.4 110 164 55 65 75

4 (7) 75 1.91 0.38 9.6 164 244 70 85 95

2 (7) 75 1.91 0.44 11.0 248 369 95 115 130

1 (19) 95 2.41 0.51 12.9 316 470 110 130 150

1/0 (19) 95 2.41 0.55 13.9 390 580 125 150 170

2/0 (19) 95 2.41 0.59 15.0 481 716 145 175 195

3/0 (19) 95 2.41 0.64 16.2 596 887 165 200 225

4/0 (19) 95 2.41 0.69 17.6 740 1101 195 230 260

250 (37) 110 2.79 0.77 19.5 884 1316 215 255 290

300 (37) 110 2.79 0.82 20.8 1048 1560 240 285 320

350 (37) 110 2.79 0.86 22.0 1207 1796 260 310 350

400 (37) 110 2.79 0.91 23.1 1375 2046 280 335 380

500 (37) 110 2.79 0.99 25.1 1700 2530 320 380 430

600 (61) 125 3.18 1.10 27.8 2048 3048 355 420 475

700 (61) 125 3.18 1.19 30.2 2378 3539 385 460 520

750 (61) 125 3.18 1.22 31.0 2542 3783 400 475 535

1000 (61) 125 3.18 1.37 34.8 3347 4981 455 545 615

*60ºC ­ When terminated to equipment for circuits rated 100 amperes or less or marked for conductorsizes 8 through 1 AWG.75ºC ­ When terminated to equipment for circuits rated over 100 amperes or marked for conductorslarger than 1 AWG.90ºC ­ RHH dry locations. PV, RHW­2 and USE­2 wet or dry locations. For ampacity derating purposes.

Allowable ampacities shown are for general use as specified by the NEC, Section 310.15.For conductors installed in conduit on a roof top, use the derating factors specified byTable 310.15(B)(3)(c) in the NEC.

Note: Where stated, "nominal" and "approximate" values are provided for information purposes only and are subjectto standard manufacturing tolerances.

SELLING INFORMATIONProduct Features

Cables are UL listed as Type PV•Cables are UL listed as Type USE-2•Temperature rating of 90ºC dry and wet•Suitable for direct burial•Sunlight resistant in black and colors•Conductors 1/0 AWG and larger are rated CT use•LEAD FREE•

Page 84: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Commercial Building Wire & CableCopper ­ 600 V

ContactLV Building Wire & Equipment CablesPhone: [email protected]

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version 2.0 Generated 8/2/18 www.nexans.us Page 84 / 87

Options

Class C stranding available•

Page 85: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Soft Bare Copper USA*

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V2.0 Generated 8/2/18 www.nexans.us Page 85 / 87

STANDARDS

National Factory standard

Bare Copper Conductors

DESCRIPTIONASTM B-3 Soft or Annealed Copper Wire. ASTM B-3 Specification details therequirements for solid wires and the individual wires in stranded conductors.

ASTM B-8 Concentric - Lay - Stranded Copper Conductors

Solid or stranded 100% conductivity copper conductors.

ApplicationUsed for bonding and grounding electrical circuits and systems.

CHARACTERISTICSConstruction characteristics

Conductor material Annealed copper

Page 86: PRODUCTS COMMERCIAL BUILDING WIRE & CABLE...AWG Ground Size AWG Circuit Conductor Color Code Nominal Diameter over Armor Approximate Net Cable Weight Ampacity (Amps) inches mm lb/kft

Soft Bare Copper USA*

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans isindicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Version V2.0 Generated 8/2/18 www.nexans.us Page 86 / 87

SOFT DRAWN BARE COPPER

SizeAWG or kcmil Nominal Diameter

ApproximateConductor Weight

Nominal D.C.Resistance

@ 25°Cmm in kg/km lbs/kft Ω/km Ω/kft

14 (1) 1.63 0.064 18.5 12.4 8.44 2.570

12 (1) 2.05 0.081 29.4 19.8 5.31 1.620

10 (1) 2.59 0.102 46.8 31.4 3.34 1.020

8 (7) 3.61 0.142 75.9 51.0 2.14 0.653

6 (7) 4.55 0.179 121.0 81.1 1.35 0.411

4 (7) 5.72 0.225 192.0 129.0 0.848 0.258

2 (7) 7.19 0.283 305.0 205.0 0.533 0.163

1 (19) 7.95 0.313 385.0 258.0 0.423 0.129

1/0 (19) 8.94 0.352 485.0 325.0 0.335 0.102

2/0 (19) 10.03 0.395 611.0 410.0 0.266 0.081

3/0 (19) 11.25 0.443 771.0 518.0 0.211 0.064

4/0 (19) 12.65 0.498 972.0 653.0 0.167 0.051

250 (37) 13.77 0.542 1149.0 772.0 0.142 0.043

300 (37) 15.09 0.594 1378.0 926.0 0.118 0.036

350 (37) 16.28 0.641 1609.0 1081.0 0.101 0.031

400 (37) 17.40 0.685 1838.0 1235.0 0.088 0.027

500 (37) 19.46 0.766 2298.0 1544.0 0.071 0.021

600 (61) 21.34 0.840 2758.0 1853.0 0.059 0.018

750 (61) 23.85 0.939 3447.0 2316.0 0.047 0.014

1000 (61) 28.37 1.117 4595.0 3088.0 0.035 0.011

* ASTM B-3 Specification details the requirements for solid wires and the individual wires in stranded conductors.