This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc. Copyright - Ramaker & Associates, Inc. - All Rights Reserved DRAWN BY: CHECKED BY: C I:\44200\44223\CAD\44223_10025533_AE201_210503_MAL02084_5G NR.dwg Printed by: amaurtua on May 11, 2021 - 5:17pm Cert i f i cat i on & Sea l : SHEET NUMBER PROJECT NUMBER ISSUE PHASE DATE ISSUED MARK DATE DESCRIPTION SCALE: NONE SHEET TITLE: PROJECT TITLE: PROJECT INFORMATION: 2021 44223 SOUTH END TREMONT FA# 10025533 SITE# MAL02084 567 TREMONT STREET BOSTON, MA 02118 SUFFOLK COUNTY FINAL 05/11/2021 85 RANGEWAY ROAD - BLDG 3, SUITE 102 NORTH BILLERICA, MA 01862 SMARTLINKLLC.COM 0 08/17/20 CDs ISSUED FOR REVIEW 1 09/11/20 CDs REVISED FOR REVIEW 2 10/06/20 FINAL CDs ISSUED 3 11/03/20 REVISED PER RFDS v6 4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP 5 05/11/21 REVISED PER COMMENTS Registered Civil Engineer Signature: Date: I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Massachusetts. 5/11/2021 T-1 TITLE SHEET RAG AJK SHEET INDEX SHEET NUMBER SHEET DESCRIPTION T-1 TITLE SHEET GN-1 GENERAL NOTES C-1 COMPOUND PLAN C-2 EQUIPMENT LAYOUT PLAN C-3 ALPHA & BETA SECTOR ANTENNA LAYOUT C-4 GAMMA SECTOR ANTENNA LAYOUT AND ANTENNA SCHEDULE A-1 CONSTRUCTION DETAILS A-2 RF PLUMBING DIAGRAM S-1 STRUCTURAL DETAILS S-1 STRUCTURAL DETAILS T1 RAYCAP / STEALTH DRAWINGS N1 RAYCAP / STEALTH DRAWINGS N2 RAYCAP / STEALTH DRAWINGS S1 RAYCAP / STEALTH DRAWINGS S2 RAYCAP / STEALTH DRAWINGS S3 RAYCAP / STEALTH DRAWINGS S4 RAYCAP / STEALTH DRAWINGS S5 RAYCAP / STEALTH DRAWINGS S6 RAYCAP / STEALTH DRAWINGS G-1 GROUNDING DETAILS G-2 GROUNDING DETAILS SITE LOCATION Know what's below. before you dig. Call R CODE COMPLIANCE: SITE NAME: SOUTH END TREMONT FA NUMBER: 10025533 SITE NUMBER: MAL02084 ADDRESS: 567 TREMONT STREET BOSTON, MA 02118 SCOPE: 5G NR UPGRADE - MRCTB039377 (2101A0P37B), 5C - MRCTB025514 (2101A0DAXQ), 4TXRX ANTENNA RETROFIT - MRCTB025632 PROJECT DESCRIPTION/ SCOPE OF WORK SITE INFORMATION: LATITUDE: 42.3438800° N LONGITUDE: 71.0725031° W JURISDICTION: SUFFOLK COUNTY APPLICANT/LESSEE: COMPANY: AT&T ADDRESS: 550 COCHITUATE ROAD FRAMINGHAM, MA 01701 PROPERTY OWNER: PROPERTY OWNER: BRIGS, LLC ADDRESS: 376 MASSACHUSETTS AVENUE ARLINGTON, MA 02474 ENGINEER: COMPANY: RAMAKER & ASSOCIATES, INC. ADDRESS: 855 COMMUNITY DRIVE CITY, STATE, ZIP: SAUK CITY, WI 53583 CONTACT: ANGELA KVALHEIM E-MAIL: [email protected] PROJECT INFORMATION: NORTH · INSTALL (3) NEW CCI TPA65R-BU4DA ANTENNAS, (1) PER SECTOR · REMOVE (3) EXISTING KATHREIN 742-264 ANTENNAS, (1) PER SECTOR · INSTALL (3) NEW 4449 B5/B12 RRU, (1) PER SECTOR · INSTALL (3) NEW 8843 B2/B66A, (1) PER SECTOR · REMOVE (3) EXISTING RRUS-11 B12, (1) PER SECTOR · REMOVE (3) EXISTING RRUS-11 B5, (1) PER SECTOR · REMOVE (3) EXISTING RRUS-12 B2 + RRUS A2 B25, (1) PER SECTOR · REMOVE (6) EXISTING DTMABP7819VG12A (TWIN 700/850 BYPASS) TMAs, (2) PER SECTOR · ADD 6630 + IDLe · ADD (1) PROPOSED PIPEMAST, (1) PER ALPHA SECTOR · ADD (1) PROPOSED PIPE TO PIPE MOUNT, (1) PER BETA SECTOR · ADD (6) Y CABLES FOR DUAL BAND RRU, (2) PER SECTOR PROPOSED PROJECT SCOPE BASED ON RFDS ID# 4078603, VERSION 2.0, LAST UPDATED 09/18/2020 & ID# 3232650, VERSION 6.0, LAST UPDATED 10/08/2020. AERIAL MAP: PROJECT NOTES: 1. SITE INFORMATION OBTAINED FROM THE FOLLOWING: A. PLAN ENTITLED "SOUTH END TREMONT" PREPARED BY DEWBERRY OF BOSTON, MA LAST REVISED 02/28/2018. B. LIMITED FIELD OBSERVATION BY RAMAKER & ASSOCIATES ON 05/07/2019. 2. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES, ORDINANCES, LAWS AND REGULATIONS OF ALL MUNICIPALITIES, UTILITY COMPANIES OR OTHER PUBLIC/GOVERNING AUTHORITIES. 3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND INSPECTIONS THAT MAY BE REQUIRED BY ANY FEDERAL, STATE, COUNTY OR MUNICIPAL AUTHORITIES. 4. THE CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER, IN WRITING, OF ANY CONFLICTS, ERRORS OR OMISSIONS PRIOR TO THE SUBMISSION OF BIDS OR PERFORMANCE OF WORK. 5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING SITE IMPROVEMENTS PRIOR TO COMMENCING CONSTRUCTION. THE CONTRACTOR SHALL REPAIR ANY DAMAGE AS A RESULT OF CONSTRUCTION OF THIS FACILITY AT THE CONTRACTOR'S EXPENSE TO THE SATISFACTION OF THE OWNER. 6. THE SCOPE OF WORK FOR THIS PROJECT SHALL INCLUDE PROVIDING ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED TO COMPLETE THIS PROJECT. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. 7. THE CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO SUBMITTING THE BID TO VERIFY THAT THE PROJECT CAN BE CONSTRUCTED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AND CONSTRUCTION DRAWINGS. 8. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THESE DRAWINGS MUST BE VERIFIED. THE CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER OF ANY DISCREPANCIES PRIOR TO ORDERING MATERIAL OR PROCEEDING WITH CONSTRUCTION. 9. SINCE THE CELL SITE MAY BE ACTIVE, ALL SAFETY PRECAUTIONS MUST BE TAKEN WHEN WORKING AROUND HIGH LEVELS OF ELECTROMAGNETIC RADIATION. EQUIPMENT SHOULD BE SHUTDOWN PRIOR TO PERFORMING ANY WORK THAT COULD EXPOSE THE WORKERS TO DANGER. PERSONAL RF EXPOSURE MONITORS ARE REQUIRED TO BE WORN TO ALERT OF ANY POTENTIALLY DANGEROUS EXPOSURE LEVELS. 10. THE PROPOSED FACILITY WILL CAUSE NO INCREASE IN STORM WATER RUNOFF, THEREFORE, NO DRAINAGE STRUCTURES ARE PROPOSED. 11. NO NOISE, SMOKE, DUST OR ODOR WILL RESULT FROM THIS FACILITY AS TO CAUSE A NUISANCE. 12. THE FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION (NO HANDICAP ACCESS IS REQUIRED). 13. THE FACILITY DOES NOT REQUIRE POTABLE WATER OR SANITARY SERVICE. 14. CONTRACTOR SHALL VERIFY ANTENNA ELEVATION AND AZIMUTHS WITH RF ENGINEERING PRIOR TO INSTALLATION. 15. THE TOWER, MOUNTS AND ANTENNAS SHALL BE DESIGNED TO MEET EIA/TIA-222-G AS PER IBC REQUIREMENTS. 16.ALL STRUCTURAL ELEMENTS SHALL BE HOT DIPPED GALVANIZED STEEL. 17. CONTRACTOR MUST FIELD LOCATE ALL EXISTING UNDERGROUND UTILITIES PRIOR TO ANY EXCAVATION. 18. CONSTRUCTION SHALL NOT COMMENCE UNTIL COMPLETION OF A PASSING STRUCTURAL ANALYSIS CERTIFIED BY A LICENSED PROFESSIONAL ENGINEER. 19. CONTRACTOR SHALL CONTACT STATE SPECIFIC ONE CALL SYSTEM THREE WORKING DAYS PRIOR TO ANY EARTH MOVING ACTIVITIES. ALL WORK SHALL BE PERFORMED AND MATERIALS INSTALLED IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THESE CODES. 1. 9TH EDITION OF THE MA STATE BUILDING CODE 2. 2015 INTERNATIONAL BUILDING CODE 3. 2015 INTERNATIONAL MECHANICAL CODE 4. ANSI/TIA-22-G STRUCTURAL STANDARD REAL ESTATE: COMPANY: SMARTLINK, LLC ADDRESS: 85 RANGEWAY ROAD BUILDING 3, SUITE 102 CITY, STATE, ZIP: NORTH BILLERICA, MA 01862 CONTACT: RYAN LYNCH E-MAIL: [email protected] CONSTRUCTION MANAGER: COMPANY: SMARTLINK, LLC ADDRESS: 85 RANGEWAY ROAD BUILDING 3, SUITE 102 CITY, STATE, ZIP: NORTH BILLERICA, MA 01862 CONTACT: RYAN LYNCH E-MAIL: [email protected] PENDING STRUCTURAL REDESIGN

Upload: others

Post on 24-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

T-1

TITLE SHEET

RAG

AJK

SHEET INDEXSHEET NUMBER SHEET DESCRIPTION

T-1 TITLE SHEETGN-1 GENERAL NOTES

C-1 COMPOUND PLANC-2 EQUIPMENT LAYOUT PLAN

C-3 ALPHA & BETA SECTOR ANTENNALAYOUT

C-4 GAMMA SECTOR ANTENNALAYOUT AND ANTENNA SCHEDULE

A-1 CONSTRUCTION DETAILSA-2 RF PLUMBING DIAGRAMS-1 STRUCTURAL DETAILSS-1 STRUCTURAL DETAILST1 RAYCAP / STEALTH DRAWINGSN1 RAYCAP / STEALTH DRAWINGSN2 RAYCAP / STEALTH DRAWINGSS1 RAYCAP / STEALTH DRAWINGSS2 RAYCAP / STEALTH DRAWINGSS3 RAYCAP / STEALTH DRAWINGSS4 RAYCAP / STEALTH DRAWINGSS5 RAYCAP / STEALTH DRAWINGSS6 RAYCAP / STEALTH DRAWINGSG-1 GROUNDING DETAILSG-2 GROUNDING DETAILS

SITELOCATION

Know what's below.before you dig.Call

R

CODE COMPLIANCE:

SITE NAME: SOUTH END TREMONTFA NUMBER: 10025533SITE NUMBER: MAL02084ADDRESS: 567 TREMONT STREET

BOSTON, MA 02118SCOPE: 5G NR UPGRADE - MRCTB039377 (2101A0P37B),

5C - MRCTB025514 (2101A0DAXQ),4TXRX ANTENNA RETROFIT - MRCTB025632

PROJECT DESCRIPTION/SCOPE OF WORKSITE INFORMATION:

LATITUDE: 42.3438800° NLONGITUDE: 71.0725031° WJURISDICTION: SUFFOLK COUNTY

APPLICANT/LESSEE:COMPANY: AT&TADDRESS: 550 COCHITUATE ROAD

FRAMINGHAM, MA 01701

PROPERTY OWNER:PROPERTY OWNER: BRIGS, LLCADDRESS: 376 MASSACHUSETTS AVENUE ARLINGTON, MA 02474

ENGINEER:COMPANY: RAMAKER & ASSOCIATES, INC.ADDRESS: 855 COMMUNITY DRIVECITY, STATE, ZIP: SAUK CITY, WI 53583CONTACT: ANGELA KVALHEIME-MAIL: [email protected]

PROJECT INFORMATION:

NORTH

· INSTALL (3) NEW CCI TPA65R-BU4DA ANTENNAS, (1) PERSECTOR

· REMOVE (3) EXISTING KATHREIN 742-264 ANTENNAS, (1)PER SECTOR

· INSTALL (3) NEW 4449 B5/B12 RRU, (1) PER SECTOR· INSTALL (3) NEW 8843 B2/B66A, (1) PER SECTOR· REMOVE (3) EXISTING RRUS-11 B12, (1) PER SECTOR· REMOVE (3) EXISTING RRUS-11 B5, (1) PER SECTOR· REMOVE (3) EXISTING RRUS-12 B2 + RRUS A2 B25, (1) PER

SECTOR· REMOVE (6) EXISTING DTMABP7819VG12A (TWIN 700/850

BYPASS) TMAs, (2) PER SECTOR· ADD 6630 + IDLe· ADD (1) PROPOSED PIPEMAST, (1) PER ALPHA SECTOR· ADD (1) PROPOSED PIPE TO PIPE MOUNT, (1) PER BETA

SECTOR· ADD (6) Y CABLES FOR DUAL BAND RRU, (2) PER SECTOR

PROPOSED PROJECT SCOPE BASED ON RFDSID# 4078603, VERSION 2.0, LAST UPDATED 09/18/2020 & ID#3232650, VERSION 6.0, LAST UPDATED 10/08/2020.

AERIAL MAP:

PROJECT NOTES:1. SITE INFORMATION OBTAINED FROM THE FOLLOWING:

A. PLAN ENTITLED "SOUTH END TREMONT" PREPARED BYDEWBERRY OF BOSTON, MA LAST REVISED 02/28/2018.

B. LIMITED FIELD OBSERVATION BY RAMAKER & ASSOCIATES ON 05/07/2019.

2. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLECODES, ORDINANCES, LAWS AND REGULATIONS OF ALLMUNICIPALITIES, UTILITY COMPANIES OR OTHERPUBLIC/GOVERNING AUTHORITIES.3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAININGALL PERMITS AND INSPECTIONS THAT MAY BE REQUIRED BYANY FEDERAL, STATE, COUNTY OR MUNICIPAL AUTHORITIES.4. THE CONTRACTOR SHALL NOTIFY THE CONSTRUCTIONMANAGER, IN WRITING, OF ANY CONFLICTS, ERRORS OROMISSIONS PRIOR TO THE SUBMISSION OF BIDS ORPERFORMANCE OF WORK.5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTINGALL EXISTING SITE IMPROVEMENTS PRIOR TO COMMENCINGCONSTRUCTION. THE CONTRACTOR SHALL REPAIR ANYDAMAGE AS A RESULT OF CONSTRUCTION OF THIS FACILITY ATTHE CONTRACTOR'S EXPENSE TO THE SATISFACTION OF THEOWNER.6. THE SCOPE OF WORK FOR THIS PROJECT SHALL INCLUDEPROVIDING ALL MATERIALS, EQUIPMENT AND LABOR REQUIREDTO COMPLETE THIS PROJECT. ALL EQUIPMENT SHALL BEINSTALLED IN ACCORDANCE WITH MANUFACTURER'SRECOMMENDATIONS.7. THE CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TOSUBMITTING THE BID TO VERIFY THAT THE PROJECT CAN BECONSTRUCTED IN ACCORDANCE WITH THE CONTRACTDOCUMENTS AND CONSTRUCTION DRAWINGS.8. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONSAND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALLDIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THESEDRAWINGS MUST BE VERIFIED. THE CONTRACTOR SHALLNOTIFY THE CONSTRUCTION MANAGER OF ANY DISCREPANCIESPRIOR TO ORDERING MATERIAL OR PROCEEDING WITHCONSTRUCTION.9. SINCE THE CELL SITE MAY BE ACTIVE, ALL SAFETYPRECAUTIONS MUST BE TAKEN WHEN WORKING AROUND HIGHLEVELS OF ELECTROMAGNETIC RADIATION. EQUIPMENTSHOULD BE SHUTDOWN PRIOR TO PERFORMING ANY WORKTHAT COULD EXPOSE THE WORKERS TO DANGER. PERSONALRF EXPOSURE MONITORS ARE REQUIRED TO BE WORN TOALERT OF ANY POTENTIALLY DANGEROUS EXPOSURE LEVELS.10. THE PROPOSED FACILITY WILL CAUSE NO INCREASE INSTORM WATER RUNOFF, THEREFORE, NO DRAINAGESTRUCTURES ARE PROPOSED.11. NO NOISE, SMOKE, DUST OR ODOR WILL RESULT FROM THISFACILITY AS TO CAUSE A NUISANCE.12. THE FACILITY IS UNMANNED AND NOT FOR HUMANHABITATION (NO HANDICAP ACCESS IS REQUIRED).13. THE FACILITY DOES NOT REQUIRE POTABLE WATER ORSANITARY SERVICE.14. CONTRACTOR SHALL VERIFY ANTENNA ELEVATION ANDAZIMUTHS WITH RF ENGINEERING PRIOR TO INSTALLATION.15. THE TOWER, MOUNTS AND ANTENNAS SHALL BE DESIGNEDTO MEET EIA/TIA-222-G AS PER IBC REQUIREMENTS.16.ALL STRUCTURAL ELEMENTS SHALL BE HOT DIPPEDGALVANIZED STEEL.17. CONTRACTOR MUST FIELD LOCATE ALL EXISTINGUNDERGROUND UTILITIES PRIOR TO ANY EXCAVATION.18. CONSTRUCTION SHALL NOT COMMENCE UNTIL COMPLETIONOF A PASSING STRUCTURAL ANALYSIS CERTIFIED BY ALICENSED PROFESSIONAL ENGINEER.19. CONTRACTOR SHALL CONTACT STATE SPECIFIC ONE CALLSYSTEM THREE WORKING DAYS PRIOR TO ANY EARTH MOVINGACTIVITIES.

ALL WORK SHALL BE PERFORMED AND MATERIALS INSTALLED IN ACCORDANCE WITH THECURRENT EDITIONS OF THE FOLLOWING CODES AS ADOPTED BY THE LOCAL GOVERNINGAUTHORITIES. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOTCONFORMING TO THESE CODES.

1. 9TH EDITION OF THE MA STATE BUILDING CODE2. 2015 INTERNATIONAL BUILDING CODE3. 2015 INTERNATIONAL MECHANICAL CODE4. ANSI/TIA-22-G STRUCTURAL STANDARD

REAL ESTATE:COMPANY: SMARTLINK, LLCADDRESS: 85 RANGEWAY ROAD

BUILDING 3, SUITE 102CITY, STATE, ZIP: NORTH BILLERICA, MA 01862CONTACT: RYAN LYNCHE-MAIL: [email protected]

CONSTRUCTION MANAGER:COMPANY: SMARTLINK, LLCADDRESS: 85 RANGEWAY ROAD

BUILDING 3, SUITE 102CITY, STATE, ZIP: NORTH BILLERICA, MA 01862CONTACT: RYAN LYNCHE-MAIL: [email protected]

PENDING STRUCTURAL REDESIGN

AutoCAD SHX Text
www.call811.com
Page 2: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

GENERAL NOTES:

1. THE SUBCONTRACTOR SHALL REVIEW AND INSPECT THE EXISTING FACILITY GROUNDING SYSTEM (ASDESIGNED AND INSTALLED) FOR STRICT COMPLIANCE WITH THE NEC (AS ADOPTED BY THE AHJ), THESITE-SPECIFIC (UL, LPI, OR NFPA) LIGHTING PROTECTION CODE, AND GENERAL COMPLIANCE WITHTELCORDIA AND TIA GROUNDING STANDARDS. THE SUBCONTRACTOR SHALL REPORT ANY VIOLATIONS ORADVERSE FINDINGS TO THE CONTRACTOR FOR RESOLUTION.

2. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION,AND AC POWER GES'S) SHALL BE BONDED TOGETHER, AT OR BELOW GRADE, BY TWO OR MORE COPPERBONDING CONDUCTORS IN ACCORDANCE WITH THE NEC.

3. THE SUBCONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTIAL RESISTANCE TO EARTH TESTING (PERIEEE 1100 AND FOR GROUND ELECTRODE SYSTEMS. THE SUBCONTRACTOR SHALL FURNISH AND INSTALLSUPPLEMENTAL GROUND ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5O HMS OR LESS.

4. THE SUBCONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUNDCONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM ORDAMAGE TO THE CONDUIT.

5. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTEDBONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH #6 AWG COPPER WIRE ULAPPROVED GROUNDING TYPE CONDUIT CLAMPS.

6. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR.STRANDED COPPER CONDUCTORS WITH GREEN INSULATION, SIZED IN ACCORDANCE WITH THE NEC, SHALLBE FURNISHED AND INSTALLED WITH THE POWER CIRCUITS TO BTS EQUIPMENT.

7. EACH BTS CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE EQUIPMENT GROUND RING WITHGREEN INSULATED SUPPLEMENTAL EQUIPMENT GROUND WIRES, 6 AWG STRANDED COPPER OR LARGERFOR INDOOR BTS; 2 AWG STRANDED COPPER FOR OUTDOOR BTS.

8. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED. BACK TO BACKCONNECTIONS ON OPPOSITE SIDES OF THE GROUND BUS ARE PERMITTED.

9. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING,SHALL BE #2 AWG SOLID TINNED COPPER UNLESS OTHERWISE INDICATED.

10. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDINGCONNECTIONS.

11. USE OF 90° BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45° BENDSCAN BE ADEQUATELY SUPPORTED. ALL BENDS SHALL BE MADE WITH 12" RADIUS OR LARGER.

12. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE.13. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR) SHALL BE FORMED USING HIGH PRESS CRIMPS

EXCEPT FOR GROUND BAR CONNECTION FROM MGB TO OUTSIDE EXTERIOR GROUND SHALL ALL BECADWELD CONNECTIONS.

14. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS.15. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED TO THE TOWER GROUND BAR.16. APPROVED ANTIOXIDANT COATINGS (I.E. CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL

COMPRESSION AND BOLTED GROUND CONNECTIONS.17. ALL EXTERIOR AND INTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT

MATERIAL.18. MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE

BONDED TO THE GROUND RING, IN ACCORDANCE WITH THE NEC.19. BOND ALL METALLIC OBJECTS WITHIN 6 FT OF MAIN GROUND WIRES WITH 1-#2 AWG TIN-PLATED COPPER

GROUND CONDUCTOR.20. GROUND CONDUCTORS USED IN THE FACILITY GROUND AND LIGHTNING PROTECTION SYSTEMS SHALL NOT

BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR, SUCH ASMETALLIC CONDUITS, METAL SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS. WHEN IT ISREQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS,NON-METALLIC MATERIAL SUCH AS PVC PLASTIC CONDUIT SHALL BE WHERE USE OF METAL CONDUIT ISUNAVOIDABLE (E.G. NON-METALLIC CONDUIT PROHIBITED BY LOCAL CODE) THE GROUND CONDUCTORSHALL BE BONDED TO EACH END OF THE METAL CONDUIT.

21. ALL NEW STRUCTURES WITH A FOUNDATION AND/OR FOOTING HAVING 20 FT. OR MORE OF 1/4" IN. ORGREATER ELECTRICALLY CONDUCTIVE REINFORCING STEEL MUST HAVE IT BONDED TO THE GROUND RINGUSING AN EXOTHERMIC WELD CONNECTION USING #2 AWG SOLID BARE TINNED COPPER GROUND WIRE,PER NEC 250.50.

22. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:CONTRACTOR - SMARTLINKSUBCONTRACTOR - GENERAL CONTRACTOR (CONSTRUCTION)OWNER - AT&T (NEW CINGULAR WIRELESS PCS, LLC)

23. ALL SITE WORK SHALL BE COMPLETED AS INDICATED ON THE DRAWINGS AND PROJECT SPECIFICATIONS.24. DRAWINGS PROVIDED HERE ARE NOT TO BE SCALED AND ARE INTENDED TO SHOW OUTLINE ONLY.25. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE

CODES, REGULATIONS, AND ORDINANCES. SUBCONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES ANDCOMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS, AND LAWFUL ORDERS OF ANY PUBLICAUTHORITY REGARDING THE PERFORMANCE OF THE WORK.

26. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANYSPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND APPLICABLE REGULATIONS.

27. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT,APPURTENANCES, AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THEDRAWINGS.

28. THE SUBCONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITHMANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.

29. IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE

SUBCONTRACTOR SHALL PROPOSE AN ALTERNATIVE INSTALLATION SPACE FOR APPROVAL BY THECONTRACTOR.

30. THE SUBCONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING ANDSTRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT SUBCONTRACTOR'S EXPENSE TO THESATISFACTION OF OWNER.

31. THE SUBCONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OFCONSTRUCTION.

32. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES WHERE ENCOUNTERED IN THEWORK, SHALL BE PROTECTED AT ALL TIMES, AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THEWORK, SHALL BE RELOCATED AS DIRECTED BY THE RESPONSIBLE ENGINEER. EXTREME CAUTION SHOULDBE USED BY THE SUBCONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES.SUBCONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE WORKING CREW. THIS WILL INCLUDE BUTNOT BE LIMITED TO A) FALL PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING &EXCAVATION.

33. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH INTERFERE WITH THEEXECUTION OF THE WORK, SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUEDAT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK, AS DIRECTED BY THERESPONSIBLE ENGINEER, AND SUBJECT TO THE APPROVAL OF THE OWNER AND/OR LOCAL UTILITIES.

34. THE AREAS OF THE OWNER'S PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER,EQUIPMENT OR DRIVEWAY SHALL BE GRADED TO A UNIFORM SLOPE AND STABILIZED TO PREVENT EROSION.

35. SUBCONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSIONCONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCALGUIDELINES FOR EROSION AND SEDIMENT CONTROL.

36. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS, SNOWOR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.

37. THE SUBGRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO FINISHEDSURFACE APPLICATION.

38. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE BTS EQUIPMENT ANDTOWER AREAS.

39. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER REFUSE SHALL BE REMOVED FROMTHE SITE AND DISPOSED OF LEGALLY.

40. THE SUBCONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICALSPECIFICATION FOR SITE SIGNAGE.

41. SUBCONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION.42. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING SUBCONTRACTOR SHALL VISIT THE CELL SITE TO

FAMILIARIZE WITH THE EXISTING CONDITIONS AND TO CONSTRUCTION DRAWINGS. ANY DISCREPANCYFOUND SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR.

43. SUBCONTRACTOR SHALL DETERMINE ACTUAL ROUTING OF CONDUIT, POWER AND T1 CABLES, GROUNDINGCABLES AS SHOWN ON THE POWER, GROUNDING AND TELCO PLAN DRAWING. SUBCONTRACTOR SHALLUTILIZE EXISTING TRAYS AND/OR SHALL ADD NEW TRAYS AS NECESSARY. SUBCONTRACTOR SHALLCONFIRM THE ACTUAL ROUTING WITH THE CONTRACTOR.

44. ALL CONCRETE REPAIR WORK SHALL BE DONE IN ACCORDANCE WITH AMERICAN CONCRETE INSTITUTE (ACI)301.

45. ANY NEW CONCRETE NEEDED FOR THE CONSTRUCTION SHALL BE AIR-ENTRAINED AND SHALL HAVE 4000 PSISTRENGTH AT 28 DAYS.

46. ALL STRUCTURAL STEEL WORK SHALL BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITHAISC SPECIFICATIONS. ALL STRUCTURAL STEEL SHALL BE ASTM A36 (FY = 36 KSI) UNLESS OTHERWISENOTED. PIPES SHALL BE ASTM A53 TYPE E (FY = 36 KSI). ALL STEEL EXPOSED TO WEATHER SHALL BE HOTDIPPED GALVANIZED. TOUCHUP ALL SCRATCHES AND OTHER MARKS IN THE FIELD AFTER STEEL IS ERECTEDUSING A COMPATIBLE ZINC RICH PAINT.

47. CONSTRUCTION SHALL COMPLY WITH SPECIFICATIONS AND "GENERAL CONSTRUCTION SERVICES FORCONSTRUCTION OF AT&T MOBILITY SITES."

48. SUBCONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO COMMENCING ANYWORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS MUST BE VERIFIED.SUBCONTRACTOR SHALL NOTIFY THE CONTRACTOR OF ANY DISCREPANCIES PRIOR TO ORDERINGMATERIAL OR PROCEEDING WITH CONSTRUCTION.

49. THE EXISTING CELL SITE IS IN FULL COMMERCIAL OPERATION, ANY CONSTRUCTION WORK BYSUBCONTRACTOR SHALL NOT DISRUPT THE EXISTING NORMAL OPERATION. ANY WORK ON EXISTINGEQUIPMENT MUST BE COORDINATED WITH CONTRACTOR. ALSO, WORK SHOULD BE SCHEDULED FOR ANAPPROPRIATE MAINTENANCE WINDOW USUALLY IN LOW TRAFFIC PERIODS AFTER MIDNIGHT.

50. SINCE THE CELL SITE IS ACTIVE, ALL SAFETY PRECAUTIONS MUST BE TAKEN WHEN WORKING AROUND HIGHLEVELS OF ELECTROMAGNETIC RADIATION. EQUIPMENT SHOULD BE SHUTDOWN PRIOR TO PERFORMINGANY WORK THAT COULD EXPOSE THE WORKERS TO DANGER. PERSONAL RF EXPOSURE MONITORS AREADVISED TO BE WORN ALERT OF DANGEROUS EXPOSURE LEVELS.

GN-1

NOTES

RAG

AJK

Page 3: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

EXISTING CABLE TRAY

EXISTING VENT PIPE

EXISTING HVAC

EXISTING DOG HOUSE

EXISTING CABLEENTRY PORT

EXISTING CABLE TRAY

EXISTING DUCT

EXISTING SKYLIGHT

EXISTINGPENTHOUSE

EXISTING UPPERROOF DECK

EXISTING EQUIPMENT ROOMLOCATED IN BASEMENT(SEE 1/C-2 FOR DETAIL)

TREMONT STREET

UNION PARK

MONTGOMERY STREET

CLARENDON STREET

AT&T GAMMA SECTOR(SEE 2/C-2 FOR DETAIL)

AT&T ALPHA & BETA SECTORS(SEE 2/C-2 FOR DETAILS)

EXISTING RRUS AND SURGEARRESTOR MOUNTED TOBALLAST FRAME

EXISTING RAILING

SCALE: 1" = 15'

COMPOUND PLAN1

NORTH

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

0 30'15'7.5'

11" x 17"22" x 34"

- 1" = 15'- 1" = 7.5'

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

C-1

COMPOUND PLAN

RAG

AJK

Page 4: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

GRADE@ ±0'-0" AGL

TOP OF LOWER ROOF@ ±68'-0" AGL

AT&T ANTENNASC/L @ ±83'-0" AGL

ALPHA & BETA SECTORS,SEE C-3 FOR DETAILS

GAMMA SECTOR,SEE C-3 FOR DETAILS

(6) EXISTING COAX, (3) EXISTING FIBERTRUNK, & (6) EXISTING DC POWERCABLES TO REMAIN.

ADD (6) Y CABLES FORDUAL BAND RRHs

AT&T ANTENNASTOP @ ±85'-0" AGL

EXISTING HIP ROOFTOP @ ±85'-6" AGL

EXISTING NOKIA CABINET EXISTING BOOSTER ADD 6630 TOEXISTING LTE RACK

EXISTING 3206 CABINET EXISTING POWER PLANT

EXISTING RXAIT RACK

EXISTING AC PANELON EXISTING TELCOBOARD

SCALE: 1" = 25'

ELEVATION VIEW2

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE:AS NOTED

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

C-2

EQUIPMENT LAYOUT ANDELEVATION VIEW

RAG

AJK

SCALE: 1" = 3.75'

EQUIPMENT LAYOUT1

NORTH

NOTE:A STRUCTURAL ASSESSMENT OF THE ANTENNAAND EQUIPMENT MOUNTING STRUCTURES HASBEEN COMPLETED BY RAMAKER, DATEDSEPTEMBER 11, 2020.SEE S-1 FOR STRUCTURAL DETAILS TO BECOMPLETED PRIOR TO ANTENNA AND EQUIPMENTINSTALLATION.

PENDING STRUCTURAL REDESIGN

Page 5: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

A1

EXISTING (1) QUINTEL QS465122ANTENNA TO BE RELOCATED

B2

EXISTING (1) QUINTEL QS465122ANTENNA TO REMAIN

EXISTING (1) RRUS-11B12 TO BE REMOVED

EXISTING (1) RRUS-32B30 TO REMAIN

EXISTING (1) RRUS-11B12 TO BE REMOVED

EXISTING (1) KATHREIN 742-264ANTENNA TO BE REMOVED

EXISTING (1) KATHREIN 742-264ANTENNA AND PIPE TO BE REMOVED

B1

EXISTING (1) RRUS-12B2 + RRUS A2 B25 TOBE REMOVED

EXISTING (1) RRUS-12 B2 + RRUSA2 B25 TO BE REMOVED

EXISTING (2) RRUS-11 B5TO BE REMOVED

EXISTING (1) DC/FIBERTO REMAIN

EXISTING (2) DTMABP7819VG12A(TWIN 700/850 BYPASS) TMAS TOBE REMOVED

EXISTING (2)DTMABP7819VG12A(TWIN 700/850 BYPASS)TMAS TO BE REMOVED

A2

EXISTING (1) DC/FIBERTO REMAIN

EXISTING (1) RRUS-32 B30TO REMAIN

B1

UMTS 850 / LTE

PCS / WCS

AZIMUTH = 150°

A1

LTE

700(

BC) /

850

/ LT

E AW

S

AZIM

UTH

= 30

°

4'-2"(3' MIN.)

ALPHA SECTORCENTERLINE = 83'

AZIMUTH = 30°

BETA SECTORCENTERLINE = 83'

AZIMUTH = 150°

PROPOSED (1) CCI TPA65R-BU4DAANTENNA TO BE MOUNTED ONPROPOSED PIPE MAST

UMTS

850

/ LT

E PC

S / W

CS

AZIM

UTH

= 30

°

EXISTING (1) QUINTEL QS465122ANTENNA TO REMAIN

EXISTING (1) RRUS-32B30 TO REMAIN

B2

EXISTING (1) QUINTEL QS465122ANTENNA TO BE RELOCATED ONEXISTING ANTENNA MOUNT

A2

EXISTING (1) DC/FIBERTO REMAIN

3'-0"

(3' MIN.)

PROPOSED (1) 8843B2/B66A TO BE MOUNTEDON EXISTING UNISTRUT EXISTING (1) DC/FIBER

TO REMAIN

EXISTING (1) RRUS-32 B30TO REMAIN

LTE 700(BC) / 850 / LTE AWS

AZIMUTH = 150°

PROPOSED (2) Y CABLESFOR DUAL RRHs

PROPOSED (2) Y CABLESFOR DUAL RRHs

PROPOSED (1) RRUS 4449B5/B12 TO BE MOUNTEDON EXISTING UNISTRUT

PROPOSED (1) CCI TPA65R-BU4DAANTENNA TO PROPOSED PIPE TOPIPE MOUNT

PROPOSED (1) 8843B2/B66A TO BE MOUNTEDON EXISTING UNISTRUT

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

C-3

ALPHA & BETA SECTORANTENNA LAYOUT

RAG

AJK

NORTH

NOTES:-3 FEET MINIMUM SEPARATION BETWEEN LTE ANTENNAS-6 FEET MINIMUM SEPARATION BETWEEN 700 BC & 700 DE ANTENNAS-8 INCH MINIMUM SEPARATION BETWEEN BACK OF PANEL ANTENNAAND EXISTING/PROPOSED EQUIPMENT

SCALE: NTS

EXISTING ANTENNA LAYOUT1

SCALE: NTS

PROPOSED ANTENNA LAYOUT2

PENDING STRUCTURAL REDESIGN

Page 6: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

C4

EXISTING (1) RRUS-11 B12 TO BEREMOVED

EXISTING (1) RRUS-11 B5 TO BE REMOVED

EXISTING (1) RRUS-32 B30 TO REMAIN

EXISTING (1) DC/FIBER TO REMAIN

C1 EXISTING (1) RRUS-12 B2 + RRUSA2 B25 TO BE REMOVED

EXISTING (1) KATHREIN 742-264ANTENNA TO BE REMOVED

EXISTING (1) QUINTEL QS465122ANTENNA TO BE RELOCATED

LTE 700(BC) / 850 / LTE AWSAZIMUTH = 270°

UMTS 850 / LTE PCS / WCSAZIMUTH = 270°

GAMMA SECTORCENTERLINE = 83'

AZIMUTH = 270°

PROPOSED RRUS-4449B5/B12 TO BE MOUNTED ONEXISTING UNISTRUT

EXISTING (1) RRUS-32 B30 TO REMAIN

EXISTING (1) DC/FIBER TO REMAIN

C1

C2

PROPOSED (1) 8843B2/B66A TO BE MOUNTEDON EXISTING UNISTRUT

PROPOSED (2) Y CABLESFOR DUAL BAND RRHs

EXISTING (1) QUINTEL QS465122ANTENNA TO BE RELOCATED

PROPOSED (1) CCI TPA65R-BU4DAANTENNA MOUNTED TO EXISTING PIPE

3'-0'' MIN

.

NORTHNOTES:-3 FEET MINIMUM SEPARATION BETWEEN LTE ANTENNAS-6 FEET MINIMUM SEPARATION BETWEEN 700 BC & 700 DE ANTENNAS-8 INCH MINIMUM SEPARATION BETWEEN BACK OF PANEL ANTENNAAND EXISTING/PROPOSED EQUIPMENT

SCALE: NTS

EXISTING ANTENNA LAYOUT1

SCALE: NTS

PROPOSED ANTENNA LAYOUT2

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

C-4

GAMMA SECTORANTENNA LAYOUT ANDANTENNA SCHEDULE

RAG

AJK

SCALE: NTS

ANTENNA SCHEDULE3

SECTOR EXISTINGANTENNA

PROPOSEDANTENNA TECHNOLOGY ANTENNA

STATUSHEIGHT

(IN.)WIDTH

(IN.)DEPTH

(IN.)WEIGHT

(LBS.)

ANTENNAAZIMUTH

(DEG.)

ANT. C/LELEV.(FT.)

REMOTE RADIO/TMACONFIGURATION

TRANSMISSION CABLERAYCAP

UNITQUANTITY TYPE STATUS

SEC

TOR

1

1KATHREIN CCI

LTE 700(BC) / 850 / LTE AWS PROPOSED 48.0 20.7 7.7 52.6 30 83 (1) 4449 B5/B12 12

FIBER TRUNKDC POWER EXISTING

(3) E

XIST

ING

DC

6-48

-60-

18-8

F SQ

UID

742-264 TPA65R-BU4DA

2- QUINTEL

UMTS 850 / LTE PCS / WCS EXISTING 52 12 10.8 75 30 83(1) 8843 B2/B66A(1) RRUS-32 B30 2 COAX EXISTING

- QS46512-2

3 - - - VACANT - - - - - - - - - -

4QUINTEL

- - VACANT - - - - - - - - - -QS46512-2

SEC

TOR

2

1KATHREIN CCI

LTE 700(BC) / 850 / LTE AWS PROPOSED 48.0 20.7 7.7 52.6 150 83 (1) 4449 B5/B12 12

FIBER TRUNKDC POWER EXISTING

742-264 TPA65R-BU4DA

2- QUINTEL

UMTS 850 / LTE PCS / WCS EXISTING 52 12 10.8 75 150 83(1) 8843 B2/B66A(1) RRUS-32 B30 2 COAX EXISTING

- QS46512-2

3 - - - VACANT - - - - - - - - - -

4QUINTEL

- - VACANT - - - - - - - - - -QS46512-2

SEC

TOR

3

1QUINTEL CCI

LTE 700(BC) / 850 / LTE AWS PROPOSED 48.0 20.7 7.7 52.6 150 83 (1) 4449 B5/B12 12

FIBER TRUNKDC POWER EXISTING

QS46512-2 TPA65R-BU4DA

2 - - - VACANT - - - - - - - - - -

3 - - - VACANT - - - - - - - - - -

4KATHREIN QUINTEL

UMTS 850 / LTE PCS / WCS EXISTING 52 12 10.8 75 150 83(1) 8843 B2/B66A(1) RRUS-32 B30 2 COAX EXISTING

742-264 QS46512-2

BASED ON: RF ENGINEERING DESIGN ENTITLED "NEW-ENGLAND_BOSTON_MAL02084_2020-5G-NR-RADIO_CELL-SITE-RF-MODIFICATIONS_MM093Q_2101A0P37B_10025533_54524_07-23-2020_FINAL-APPROVED_V2.00" LAST REVISED 09/18/2020.

BASED ON: RF ENGINEERING DESIGN ENTITLED "NEW-ENGLAND_BOSTON_MAL02084_2018-LTE-MULTI-CARRIER_LTE_MH705R_2101A0DB1B_10025533_54524_06-27-2019_FINAL-APPROVED_V6.00" LAST REVISED 10/08/2020.

Page 7: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

8" MIN

EXISTING ANTENNAMOUNTING PIPE (TYP)

PROPOSED ANTENNAMOUNTING BRACKET,TYP

PROPOSED ANTENNA

PROPOSED ANTENNAMOUNTING BRACKET

NOTES:-3 FEET MINIMUM SEPARATION BETWEEN LTE ANTENNAS

-8 INCH MINIMUM SEPARATION BETWEEN BACK OF PANELANTENNA AND EXISTING/PROPOSED EQUIPMENT

CCI TPA65R-BU4DA

DIMENSIONS (HxWxD):48.0"×20.7"×7.7"WEIGHT (LBS): 52.6"

48.0

"

7.7" 20.7"

ERICSSON B5/B12 4449

DIMENSIONS (HxWxD):18.0"x13.2"x9.4"WEIGHT (LBS): 75

9.4"

18.0

"

13.2" 9.4"

13.2"

18.0

"

11.3"

11.3

"

ERICSSON B2/B66A 8843

DIMENSIONS (HxWxD):18.0"x13.2"x11.3"WEIGHT (LBS): 70

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

A-1

CONSTRUCTION DETAILS

RAG

AJK

SCALE: NTS

ANTENNA MOUNTING DETAIL1 SCALE: NTS

ANTENNA DETAIL2 SCALE: NTS

RRUS 4449 B5 / B12 DETAIL3

SCALE: NTS

RRUS 8843 B2/B66A DETAIL4

Page 8: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

A-2

RF PLUMBING DIAGRAMS

RAG

AJK

SCALE: NTS

RF PLUMBING DIAGRAMS1

BASED ON: RF ENGINEERING DESIGN ENTITLED "NEW-ENGLAND_BOSTON_MAL02084_2018-LTE-MULTI-CARRIER_LTE_MH705R_2101A0DB1B_10025533_54524_06-27-2019_FINAL-APPROVED_V6.00" LAST REVISED 10/08/2020.

Page 9: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

S-1

STRUCTURAL DETAILS

RAG

AJK

SCALE: NTS

PROPOSED MOUNT DETAIL1

PENDING STRUCTURAL REDESIGN

Page 10: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

NOTE:

DO NOT INSTALL CABLEGROUND KIT AT A BEND ANDALWAYS DIRECT GROUNDWIRE DOWN TO CIGBE.

FROM ANTENNA

APPROVEDWEATHERPROOFING KIT,TYP.

APPROVED GROUNDCONNECTOR KIT, TYP.

ANTENNA CABLE TO CABLETRAY, TYP.

TINNED, SOLID COPPER BUSSBAR, HARGER TGBI14420MGROUND BAR OR EQUIVALENT

#6 AWG

#2 AWG BTCW

FROM ANTENNAFRAME, SUPPORTGROUND WIRE ASNEEDED

JUMPER REQUIREDONLY WHEN 11

4"AND LARGER, TYP.

APPROVEDWEATHERPROOFINGKIT, TYP.

TX/RX

TX

RX

#2 BTCW, TYP. TO BGR, MGB,OR BUILDING GROUND SYSTEM

NOTES:

1. ALL MOUNTING HARDWARE CAN BE USED ON 6", 12", 18",ETC. GROUND BARS.

2. ENTIRE ASSEMBLY AVAILABLE FROM NEWTON INSTRUMENTCO. CAT. NO. 2106060010 OR AS HARGER TGBI14420M.

LEGEND

1. TINNED COPPER GROUND BAR, 14" x 4" x 20", NEWTON CO., HARGER TGBI14420M,OR EQUIVALENT. HOLE CENTERS TO MATCH NEMA DOUBLE LUGCONFIGURATION.

2. INSULATORS. INSTRUMENT CO. CAT. NO. 3061-4 OR HARGER EQUIVALENT.

3. 58" LOCKWASHERS, NEWTON INSTRUMENT CO. CAT. NO. 3015-8 OR EQUIVALENT.

4. WALL MOUNTING BRACKET, NEWTON INSTRUMENT CO. CAT. NO. A-6056 ORHARGER EQUIVALENT.

5. 58" x 1" H.H.C.S. BOLTS, NEWTON INSTRUMENT CO. CAT. NO. 3012-1 OR HARGER

EQUIVALENT.

2

1

54

3

716"

1"

34"

2"

TYPE NCTHROUGH AND TAP CABLES TOGROUND ROD

TYPE GYTHROUGH CABLE TO SIDE OFGROUND ROD

TYPE TATEE OF HORIZONTAL RUN ANDTAP CABLES

TYPE PCPARALLEL TAP CABLES

TYPE GRCABLE TAP TO TOP OFGROUND ROD

TYPE WTHROUGH VERTICAL CABLE TOVERTICAL STEEL SURFACE ORTO THE SIDE OF EITHERHORIZONTAL OR VERTICALPIPE TYPE XB

CROSS OF HORIZONTALCABLES. LAPPED AND NOT CUT.

TYPE PT (PARALLEL HORIZ. COND.)PARALLEL THROUGH CONNECTIONOF HORIZONTAL CABLES

TYPE VS (VERT. STEEL SURFACE)CABLE TAP DOWN AT 45° TO VERTICALSTEEL SURFACE INCLUDING PIPE

TYPE HS (HORIZ. STEEL SURFACE)TO FLAT STEEL SURFACEOR HORIZONTAL PIPE

TYPE GT (THROUGH CABLE TO GROUND ROD)THROUGH CABLE TO TOP OF GROUND ROD

TYPE YA-2 (COPPER LUGS)TWO HOLE- LONG BARREL LENGTH

TYPE 2-YA-2 (BOND JUMPER)FIELD FABRICATED GREENSTRANDED INSULATED

TYPE VS (VERTICAL PIPE)CABLE TAP DOWN AT 45° TORANGE OF VERTICAL PIPES

TYPE LJ (FLAT BUSBAR)TAP OF HORIZONTAL CABLE TOEDGE OF HORIZONTAL

COLD SHRINKORAPPROVEDEQUAL

LABEL

1" MIN.

1/ 4" MIN.

BUTT CONDUCTOR INSULATIONUP AGAINST THE CONDUCTORBARREL

INSPECTION WINDOW REQUIREDFOR ALL INTERIOR TWO-HOLECONNECTORS

EXTERNAL TOOTHED

3/8" Ø x 1-1/2"

S/S NUT

S/S LOCK WASHERS/S FLAT WASHER

APPLY NO-OXS/S FLAT WASHER

S/S BOLT (1 OF 2)

TINNED COPPERGROUNDING BAR

GROUND BAR

COLD SHRINKORAPPROVEDEQUAL

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

G-1

GROUNDING DETAILS

RAG

AJK

SCALE: NTS

GROUND WIRE TO GROUND BAR DETAIL1 SCALE: NTS

TYPICAL GROUND BAR DETAIL2

SCALE: NTS

TYPICAL CADWELD TYPES DETAIL4

SCALE: NTS

TYPICAL GROUND BAR CONNECTION DETAIL3

Page 11: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

PROPOSED PANELANTENNA

PROPOSED RRH

PIPE MAST

FURNISH AND INSTALL 12"JUMPER AND RET CABLEBETWEEN RRH ANDANTENNA

GROUND PROPOSED ANTENNATO SECTOR GROUND BAR PERMANUFACTURERS'SPECIFICATIONS, TYP. AT EACHSECTOR.

EXISTING SECTORGROUND BAR, TYP.

PROPOSED PIPE, TYP.GROUND LEAD WITH LUGCONNECTION TO PROPOSEDSECTOR GROUND BAR.

ALPHASECTOR

ANTENNA

BETASECTOR

ANTENNA

GAMMASECTOR

ANTENNA

RRU

ANTENNAMAST RRU

ANTENNAMAST RRU

ANTENNAMAST

GROUNDBAR (CIGBE)

GROUNDBAR (CIGBE)

GROUNDBAR (CIGBE)

GROUNDBAR (CIGBE)

(MASTER)

SURGESUPRESSOR

#6 AWG (TYP.)#2 AWG THW OR TWSTRANDED GROUNDLEAD

#2 AWG (TYP.)

This

doc

umen

t c

onta

ins c

onfid

entia

l or

pro

prie

tary

inf

orma

tion

of R

amak

er &

Ass

ociat

es, I

nc.

Neith

er t

his d

ocum

ent

nor

the

info

rmat

ion

here

in is

to

be

repr

oduc

ed,

dist

ribut

ed,

used

or

disc

lose

d ei

ther

in w

hole

or

in p

art

exc

ept

as

auth

orize

d by

Ram

aker

and

Ass

ociat

es, I

nc.

Copy

right

- Ra

make

r & As

socia

tes, In

c. -

All Ri

ghts

Rese

rved

DRAW

N BY:

CHEC

KED B

Y:C

I:\44

200\

4422

3\C

AD\4

4223

_100

2553

3_AE

201_

2105

03_M

AL02

084_

5G N

R.d

wg

Prin

ted

by:

amau

rtua

on M

ay 1

1, 2

021

- 5:1

7pm

Certification & Seal:

SHEETNUMBER

PROJECTNUMBER

ISSUEPHASE

DATEISSUED

MARK DATE DESCRIPTION

SCALE: NONE

SHEET TITLE:

PROJECT TITLE:

PROJECT INFORMATION:

2021

44223

SOUTH END TREMONTFA# 10025533

SITE# MAL02084567 TREMONT STREETBOSTON, MA 02118SUFFOLK COUNTY

FINAL 05/11/2021

85 RANGEWAY ROAD - BLDG 3, SUITE 102NORTH BILLERICA, MA 01862

SMARTLINKLLC.COM

0 08/17/20 CDs ISSUED FOR REVIEW

1 09/11/20 CDs REVISED FOR REVIEW

2 10/06/20 FINAL CDs ISSUED

3 11/03/20 REVISED PER RFDS v6

4 05/03/21 REVISED PER ANTENNA 3M TRANSPARENT WRAP

5 05/11/21 REVISED PER COMMENTS

Registered Civil Engineer Signature: Date:

I hereby certify that this plan, specification, or report was preparedby me or under my direct supervision and that I am a duly Licensed

Professional Engineer under the laws of the State of Massachusetts.

5/11/2021

G-2

GROUNDING DETAILS

RAG

AJK

SCALE: NTS

ANTENNA & RRU GROUNDING DETAIL1 SCALE: NTS

SCHEMATIC DIAGRAM GROUNDING SYSTEM2

Page 12: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc.

DRAWN BY:C I:\44200\44223\Images\Photo Sim\44223_10025533_MAL02084_PhotoSim_210204.dwg Printed by: amaurtua on May 11, 2021 - 5:21pm2021Copyright - Ramaker & Associates, Inc. - All Rights Reserved

SHEET TITLE:

PROJECT NUMBER:

PROJECT TITLE:

PROJECT LOCATION:85 RANGEWAY ROAD - BLDG 3, SUITE 102

NORTH BILLERICA, MA 01862SMARTLINKLLC.COM

44223

SOUTH END TREMONT

567 TREMONT STREET BOSTON, MA 02118

AEM

PHOTO RENDERING/SIMULATION LOCATION MAP

NORTH

2 LOOKINGWEST

1LOOKINGNORTH

3 LOOKINGSOUTH

PROPOSED ANTENNALOCATIONS

TREMONT STREET

MONTGOMERY STREET

UNION PARK

CLARENDON STREET

Page 13: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc.

DRAWN BY:C I:\44200\44223\Images\Photo Sim\44223_10025533_MAL02084_PhotoSim_210204.dwg Printed by: amaurtua on May 11, 2021 - 5:21pm2021Copyright - Ramaker & Associates, Inc. - All Rights Reserved

SHEET TITLE:

PROJECT NUMBER:

PROJECT TITLE:

PROJECT LOCATION:85 RANGEWAY ROAD - BLDG 3, SUITE 102

NORTH BILLERICA, MA 01862SMARTLINKLLC.COM

44223

SOUTH END TREMONT

567 TREMONT STREET BOSTON, MA 02118

AEM

BEFORE PHOTO RENDERING/SIMULATION - LOOKING NORTH

NORTH

TOP OF PARAPET@ ±78'-0" AGLTOP OF BUILDING ROOF @ ±76'-0" AGL

UNION PARK TREMONT STREET

EXISTING ANTENNA& EQUIPMENTLOCATIONS BEYOND

TOP OF HIP ROOF @ ±85'-6" AGLTOP OF ANTENNA @ ±85'-3" AGL

Page 14: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc.

DRAWN BY:C I:\44200\44223\Images\Photo Sim\44223_10025533_MAL02084_PhotoSim_210204.dwg Printed by: amaurtua on May 11, 2021 - 5:21pm2021Copyright - Ramaker & Associates, Inc. - All Rights Reserved

SHEET TITLE:

PROJECT NUMBER:

PROJECT TITLE:

PROJECT LOCATION:85 RANGEWAY ROAD - BLDG 3, SUITE 102

NORTH BILLERICA, MA 01862SMARTLINKLLC.COM

44223

SOUTH END TREMONT

567 TREMONT STREET BOSTON, MA 02118

AEM

AFTER PHOTO RENDERING/SIMULATION - LOOKING NORTH

NORTH

UNION PARK TREMONT STREET

TOP OF PARAPET@ ±78'-0" AGLTOP OF BUILDING ROOF @ ±76'-0" AGL

PROPOSED ANTENNA& EQUIPMENTLOCATIONS BEYOND

TOP OF HIP ROOF @ ±85'-6" AGLTOP OF ANTENNA @ ±85'-0" AGL

Page 15: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc.

DRAWN BY:C I:\44200\44223\Images\Photo Sim\44223_10025533_MAL02084_PhotoSim_210204.dwg Printed by: amaurtua on May 11, 2021 - 5:21pm2021Copyright - Ramaker & Associates, Inc. - All Rights Reserved

SHEET TITLE:

PROJECT NUMBER:

PROJECT TITLE:

PROJECT LOCATION:85 RANGEWAY ROAD - BLDG 3, SUITE 102

NORTH BILLERICA, MA 01862SMARTLINKLLC.COM

44223

SOUTH END TREMONT

567 TREMONT STREET BOSTON, MA 02118

AEM

BEFORE PHOTO RENDERING/SIMULATION - LOOKING WEST

NORTH

TREMONT STREET CLARENDON STREET

EXISTING ANTENNA& EQUIPMENTLOCATIONS BEYOND

TOP OF HIP ROOF @ ±85'-6" AGLTOP OF ANTENNA @ ±85'-3" AGL

TOP OF PARAPET@ ±78'-0" AGLTOP OF BUILDING ROOF @ ±76'-0" AGL

TOP OF CHIMNEY VENTS @ ±83'-0" AGL

Page 16: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc.

DRAWN BY:C I:\44200\44223\Images\Photo Sim\44223_10025533_MAL02084_PhotoSim_210204.dwg Printed by: amaurtua on May 11, 2021 - 5:21pm2021Copyright - Ramaker & Associates, Inc. - All Rights Reserved

SHEET TITLE:

PROJECT NUMBER:

PROJECT TITLE:

PROJECT LOCATION:85 RANGEWAY ROAD - BLDG 3, SUITE 102

NORTH BILLERICA, MA 01862SMARTLINKLLC.COM

44223

SOUTH END TREMONT

567 TREMONT STREET BOSTON, MA 02118

AEM

AFTER PHOTO RENDERING/SIMULATION - LOOKING WEST

NORTH

TREMONT STREET CLARENDON STREET

TOP OF HIP ROOF @ ±85'-6" AGLTOP OF ANTENNA @ ±85'-3" AGL

TOP OF PARAPET@ ±78'-0" AGLTOP OF BUILDING ROOF @ ±76'-0" AGL

TOP OF PROPOSED ANTENNA@ ±85'-0" AGL

TOP OF CHIMNEY VENTS @ ±83'-0" AGL

EXISTING ANTENNA& EQUIPMENTLOCATIONS BEYOND

Page 17: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc.

DRAWN BY:C I:\44200\44223\Images\Photo Sim\44223_10025533_MAL02084_PhotoSim_210204.dwg Printed by: amaurtua on May 11, 2021 - 5:21pm2021Copyright - Ramaker & Associates, Inc. - All Rights Reserved

SHEET TITLE:

PROJECT NUMBER:

PROJECT TITLE:

PROJECT LOCATION:85 RANGEWAY ROAD - BLDG 3, SUITE 102

NORTH BILLERICA, MA 01862SMARTLINKLLC.COM

44223

SOUTH END TREMONT

567 TREMONT STREET BOSTON, MA 02118

AEM

BEFORE PHOTO RENDERING/SIMULATION - LOOKING SOUTH

NORTH

MONTGOMERY STREET

CLARENDON STREET

EXISTING ANTENNA &EQUIPMENT LOCATIONS

PROPOSED ANTENNA& EQUIPMENTLOCATION BEYOND

TOP OF ANTENNA @ ±85'-3" AGL

TOP OF PARAPET@ ±78'-0" AGL

TOP OF BUILDING ROOF @ ±76'-0" AGL

TOP OF CHIMNEY VENTS @ ±83'-0" AGL

Page 18: PROJECT NOTES: PENDING STRUCTURAL REDESIGN

This document contains confidential or proprietary information of Ramaker & Associates, Inc. Neither this document nor the information herein is to be reproduced, distributed, used or disclosed either in whole or in part except as authorized by Ramaker and Associates, Inc.

DRAWN BY:C I:\44200\44223\Images\Photo Sim\44223_10025533_MAL02084_PhotoSim_210204.dwg Printed by: amaurtua on May 11, 2021 - 5:21pm2021Copyright - Ramaker & Associates, Inc. - All Rights Reserved

SHEET TITLE:

PROJECT NUMBER:

PROJECT TITLE:

PROJECT LOCATION:85 RANGEWAY ROAD - BLDG 3, SUITE 102

NORTH BILLERICA, MA 01862SMARTLINKLLC.COM

44223

SOUTH END TREMONT

567 TREMONT STREET BOSTON, MA 02118

AEM

AFTER PHOTO RENDERING/SIMULATION - LOOKING SOUTH

NORTH

PROPOSED ANTENNA& EQUIPMENTLOCATION BEYOND

MONTGOMERY STREET

CLARENDON STREET

TOP OF ANTENNA @ ±85'-3" AGL

TOP OF PARAPET@ ±78'-0" AGL

TOP OF BUILDING ROOF @ ±76'-0" AGL

TOP OF PROPOSED ANTENNA@ ±85'-0" AGL

TOP OF CHIMNEY VENTS @ ±83'-0" AGL