proposing measures for instanta- neous power failure and ... · inputs 200vac power supply. connect...
TRANSCRIPT
[DG2CP1]
Features
• When an instantaneous power failure occurs, the main circuit’s power failure tolerance time is secured by supplying energy from the auxiliary capacitor. This enables normal stopping.
• Heat generated in the cabinet can be reduced by reducing the dissipation of regeneration heat.
• When an external regenerative resistor is also installed, the resistor capacity can be reduced. Thus, the cabinet can be downsized.
• The auxiliary capacitor unit can be easily added to an existing system. Just connect a 200VAC power supply and connect to the servo amplifier’s P/N terminals to use.
MR-J4(200V class, 1kW or less)
Securing power failure tolerance timeduring instantaneous power failure, and
Reducing the dissipation of regeneration heatby using regenerative energy charged in the capacitor
Power running
Con
vert
er
Servo motor
Acceleration
Con
vert
er
Capacitor
EnergySmall
Servo amplifier
Chargingenergy supply
Capacitor
Inve
rter
Auxiliary capacitor unit
Regeneration
Servo amplifier
Decelerationenergy charging
Con
vert
er
Servo motor
Deceleration
Con
vert
er
Capacitor
Capacitor
Inve
rter
Auxiliary capacitor unit
DG2CP1DG2CP1
Drive GoodsAuxiliary Capacitor Unit for Drive Amplifier
New Product Release No.4
Proposing Measures for Instanta-neous Power Failure and Heating Prevention for MR-J4 Servo System by using deceleration energy charging
Before and after Introduction of Unit
Operation atinstantaneous power failure
Operation when auxiliarycapacitor unit is connected
Motor speed3000 [r/min]
Bus voltage when axis stops200VDC
Bus voltage when axis stops200VDC
Initial bus voltage290VDC
Power failure tolerance time is secured
Axis stopPower failure occurs
Undervoltage alarm occurs
Power failure occurs
4600ms
Axis stop
730ms
Motor speed3000 [r/min]
Initial bus voltage290VDC
Instantaneous
power failure
measures
Note) The power failure tolerance time varies depending on the motor load at the time of power failure
Very Frequent Operation before and after Introduction of Unit
Power running Regeneration
Power running Regeneration
Servo amplifier
Capacitor
Regenerativeresistor
Servo motor
EnergyLarge
Acceleration
Servo motor
Acceleration
Capacitor
Energysmall
Servo amplifier
Servo amplifier Servo amplifier
Capacitor
Regenerativeresistor
Servo motor
Deceleration
Dissipation of deceleration energy heat(Heat dissipation area is required in cabinet)
Charging energy supply Deceleration energy charging
Capacitor
Auxiliary capacitor unit
Servo motor
Deceleration
Con
vert
er
Capacitor
Capacitor
Auxiliary capacitor unit
Heat reduction
Power running
Motor speed
AccelerationAcceleration DecelerationDeceleration
Motor energy Time
TimeRegenerationRegeneration
The regenerative energy is chargedin the capacitor and used for the
next power running (acceleration).
Very frequent operation using regenerative resistor
Very frequent operation using auxiliary capacitor unit
Con
vert
er
Inve
rter
Con
vert
er
Inve
rter
Con
vert
erC
onve
rter
Inve
rter
Con
vert
er
Inve
rter
Auxiliary Capacitor Unit for Drive Amplifier
Confirmation of Effect
<System Configuration (Example)>
Capacity selected for above operation
Servo amplifier: MR-J4-70_
Servo motor: HG-KR73
Load inertia ratio: 10 times
Operation frequency: 46 [SPM]
(1) Regenerative power: 38 [W] 0 [W] (No heat is generated by the regenerative resistor.)
(2) External regenerative option: MR-RB12 (100 [W]) An external regenerative option is not required.
(3) Energy-saving effect: An energy-saving effect of 7,500 [yen/year] can be achieved.
When calculated with the following conditions:
24 hr, 365 day operation, electricity rate: \15 yen/kWh
Effect of charging with capacitor unit: 74J/cycle, 1 cycle operation time: 1.334sec
MalfunctionRA1
OFF
Emergency stop switch
Auxiliary capacitor unit
MCCB
3-phase200VAC
ON
MC SK
MC
MC*6 CNP1
CNP2
CNP1
CNP2
CN1
CN1
EM2
SON
DICOM
ALM
DICOM
CN8
CN2*10
CNP3*10
Servo amplifierServo motor
TE1
L1
L1
U U
V
WM
V
W
L2
L3
N-
P3
P4
THM1
P+
P+
P+
Insulated
Forced stop 2
Main circuitpower supply*7
Servo ON
C
D
L11
L21
N-
N-
THM2
L2
L3
Encodercable*3
24VDC*11
24VDC*11
Encoder
Malfunction
Short-circuit connector(Packed with servo amplifier)
RA1
*4
*2
*5
*1
*1
*9
Motor
*8
Standard Connection Diagram
*1: Remove the short bar connected across P3 and P4 to connect. When using the power factor improving DC reactor, connect to the section *1 . The power factor improving DC reactor
and power factor improving AC reactor cannot be used simultaneously.
*2: Always connect across P+ and D (factory-wired). When using the regenerative option, refer to the Servo Amplifier Instruction Manual.
*3: For the encoder cable, use of the option cable is recommended. Refer to “Servo Motor Instruction Manual (Vol. 3)” for details on selecting cable.
*4: This diagram is for sink I/O interface. Refer to the Instruction Manual for details on the source I/O interface.
*5: Refer to “Servo Motor Instruction Manual (Vol. 3)” for details on connecting servo motor power wires.
*6: Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80ms or less.
Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration.
When dynamic brake deceleration is not required, delay the time to turn off the magnetic contactor.
*7: To prevent an unexpected restart of the servo amplifier, configure a circuit to turn off EM2 when the main circuit power supply is turned off.
*8: When not using the STO function, attach the short-circuit connector came with a servo amplifier.
*9: When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
*10: Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
*11: The illustration of the 24VDC power supply is divided between input signal and output signal for convenience. However, they can be configured by one.
Auxiliary Capacitor Unit for Drive Amplifier
Product Appearance, External Dimensions, and Name of Each Part
Auxiliary Capacitor Unit Specifications
(1) General specificationsItem Environment
Ambient
temperature
Ambient
humidity
Ambience
Altitude
Vibration resistance
Operation
Storage
Operation
Storage
0°C to 55°C (with no freezing)
-20°C to 65°C (with no freezing)
90%RH or less (with no condensation)
Indoors (no direct sunlight), free from corrosive
gas, flammable gas, oil mist, dust, and dirt
1000m or less above sea level
5.9m/s2, 10Hz to 55Hz (in each X, Y and Z direction)
(2) Performance specificationsItem Specifications
Connected servo amplifier
Main circuit
Control circuit power input
Protective function
Compliance to international standards
Structure (IP rating)
External dimensions (mm)
Mass (g)
Power/frequency
Permissible voltage fluctuation
Permissible frequency fluctuation
Voltage
MR-J4 series*1
3-phase 200 to 240VAC, 50Hz/60Hz*2
3-phase 170 to 264VAC*2
Within ±5%
1-phase 200VAC
Converter overheat detection
CE, UL/cUL
Natural cooling, release (IP20)
168(H)×45(W)×157.8(D)
250*1: Cannot be connected to MR-J4W2-B or MR-J4W3-B.
*2: A voltage of 220VAC or less is recommended to adequately store regenerative energy.
No. Name Symbol Function(1)
(2)
(3)
(4)
Main circuit power connector
Bus connection connector
Main circuit heating
detection connector
Charge lamp
CNP1
CNP2
TE1
CHARGE
Inputs 200VAC power supply.
Connect to the servo amplifier.
Changes to “OPEN” when main
circuit heating is detected.
Lights up when the main circuit is
charged. While this lamp is lit, do
not reconnect the cables.
Product Model
Item Model Description
Capacitor unit for storing regenerative energyDG2CP1Auxiliary capacitor unit for drive amplifier
157.8
154.5
156
168
(3)
(2)
(1)
(4)
45
1-13-5, Kudankita, Chiyoda-ku, Tokyo, 102-0073, Japan Phone +81-3-3288-1101 Fax +81-3-3288-1507
Before using this product, ensure the safety in case of failure.We shall not bear any responsibility for consequential damages caused by failure of the product.
MEI C118E·164 (1605) MEENew publication, effective May. 2016
Specifications subject to change without notice.
Unit: mm