PROTECTING AGAINST ARC FLASH HAZARDS
Presented by:Andrew J. Fitzpatrick, P.E.
COMMITMENT & INTEGRITY DRIVE RESULTS
Electricity
Simply stated electricity is the flow of electrons Electricity is governed by laws:
Ohms Law : V=IR Kirchoff’s Law: Total Voltage around a closed loop must be equal
to zero Electricity is predictable Electricity is a potential hazard
COMMITMENT & INTEGRITY DRIVE RESULTS
What is Electrical Safety?
OSHA 1910 Subpart S Addresses electrical safety requirements for safeguarding of
employees in the workplace NFPA 70E
The standard defining safe work practices to protect personnel from electrical hazards
2015 NFPA Report Last 20 years has seen a dramatic decrease of fatal electrical
injuries, non-fatal is not as consistent, recent trend is decreasing OSHA investigations found majority of injuries due to inappropriate
work on energized equipment
COMMITMENT & INTEGRITY DRIVE RESULTS
Electrical Safety – Engineers Perspective
Employer is responsible for providing PPE used to comply with OSHA requirements. All electrical systems greater than 50V NFPA 70E defines two methods of selecting PPE
Incident energy analysis (IEEE 1584 equations) Arc Flash PPE Categories
Accurate Data, data collection and understanding of electrical distribution systems paramount to accurate assessments
COMMITMENT & INTEGRITY DRIVE RESULTS
IEEE 1584 Empirical Method based on testing in certified test laboratories Voltages from 208V – 15kV (Lee Method available above
15kV) 50 or 60Hz systems Bolted Fault Current from 700A – 106,000A Different grounding types, ungrounded Different enclosure types and protective devices Use computer based software:
Easypower SKM ETAP
COMMITMENT & INTEGRITY DRIVE RESULTS
IEEE 1584 Con’t
Two (2) main components: Ia = arcing current (based on bolted fault current with adjustments) t = time (in seconds) arcing time
A reduction of Ia or t will decrease incident energy levels Arc Current
Modify service transformer characteristics (increased impedance, reduced size)
Add resistance
COMMITMENT & INTEGRITY DRIVE RESULTS
IEEE 1584 Con’t
Protection Scheme changes to reduce time Current limiting fuses (selected appropriately) Adjustable type circuit breakers (LSIG) Reduced Energy – Maintenance Mode Circuit Breakers Zone Interlocking Relays - Differential protection Relays – Optical Add protection devices to system (i.e. main ahead of main)
COMMITMENT & INTEGRITY DRIVE RESULTS
High Incident Energy Level Examples “Small” distribution systems (Pump Stations, Wells, etc)
Low utility fault current Protection devices not adjustable (MCCB Thermal-Magnetic,
fuses) Service sizes mismatched with utility transformers Utility Fuses
Large distribution systems (Treatment Plants) High utility fault current Device Coordination Emergency Power Scenarios
COMMITMENT & INTEGRITY DRIVE RESULTS
Preferred Method of Protection: De-energize
“It is now an industry standard to de-energize live parts, whenever possible, before an employee
works on or near them.”
COMMITMENT & INTEGRITY DRIVE RESULTS
If you Cannot De-energize…
“Employees are permitted to work on or near exposed live parts only if they are qualified and it can be demonstrated that de-energization introduces additional or increased hazards or is infeasible due to equipment design or operational limitations.”
COMMITMENT & INTEGRITY DRIVE RESULTS
What are “Exposed Live Parts”?
that could be inadvertently touched or approached
COMMITMENT & INTEGRITY DRIVE RESULTS
Electrically Safe Work Condition
Infeasible: not capable of being carried out or put in practice
Examples: Interruption of life support
equipment Deactivation of emergency
alarm systems Shutdown of hazardous
location ventilation equipment
▀ Inconvenient: not suited to your comfort, purpose or needs
▀ Examples:▀ Financial▀ In a hurry▀ “I know what I’m doing.”▀ Want to serve client
COMMITMENT & INTEGRITY DRIVE RESULTS
Hierarchy of Hazard ControlHow do we want to control the hazards?
Engineering Controls
Administrative Controls
PPELeast effective
Most effective
Change of operation; do it a different way; training
Move/add switches, meters, or phase loss monitors
Last resort
COMMITMENT & INTEGRITY DRIVE RESULTS
Qualified Person One who has skills and knowledge related to the
construction, installation, maintenance and operation of the electrical equipment and installations and has received safety training on the hazards involved.o Ability to distinguish exposed live parts from other parts of
electrical equipmento Ability to determine nominal voltage of exposed live partso Knowledge of clearance distanceso Familiar with proper use of special precautionary techniques,
PPE, and tools
Qualified vs. Unqualified
Can be “qualified” for certain tasks and not for others
COMMITMENT & INTEGRITY DRIVE RESULTS
What this training qualifies you to do
Work around or near live exposed parts: e.g., Accessing a live panel
Work on live exposed parts: Use a voltage meter (including verification of de-energized state)
COMMITMENT & INTEGRITY DRIVE RESULTS
Really? I have to be “qualified” to do LOTO?
COMMITMENT & INTEGRITY DRIVE RESULTS
Electrical Safety Training Includes:
Basics of electricity Basic requirements of NFPA 70E and NEC Recognizing common electrical hazards Distinguishing exposed live parts from other electrical equipment Determining nominal voltage of exposed live parts Clearance distances for working on/near exposed live parts Safe work practices and PPE Ability to determine the extent of the hazard How to release victims from contact with live circuits Methods of first aid Recognizing electrical tasks that you are not permitted to perform
COMMITMENT & INTEGRITY DRIVE RESULTS
Electrical Safety Program
Key Components: Training Energized Electrical Work Permit PPE Risk Assessment Job Briefing Safe Work Practices Electrical Contractors Evaluation/Performance Review
COMMITMENT & INTEGRITY DRIVE RESULTS
Energized Electrical Work Permit (EEWP) Required when working within
the restricted approach boundary Exceptions - permits not
required for: Testing, troubleshooting, and
voltage measuring (as long as safe work practices and PPE are used)
Thermography and visual inspections (as long as restricted approach boundary will not be crossed)
Be sure to know the boundaries before you start!
COMMITMENT & INTEGRITY DRIVE RESULTS
Safety Signs and Tags. Safety signs, safety symbols, or accident prevention tags shall be used where necessary to warn employees about electrical hazards that might endanger them.
Barricades. Barricades shall be used in conjunction with safety signs where it is necessary to prevent or limit employee access to work areas containing energized conductors or circuit parts.
Attendants. If signs and barricades do not provide sufficient warning and protection from electrical hazards, an attendant shall be stationed to warn and protect employees.
Alerting Techniques
COMMITMENT & INTEGRITY DRIVE RESULTS
Reading a Label
Depending on who did your study and when it was done, the labels may look a little different, but the information should be the same.
COMMITMENT & INTEGRITY DRIVE RESULTS
If an arc flash analysis hasn’t been done….
COMMITMENT & INTEGRITY DRIVE RESULTS
EEWP
COMMITMENT & INTEGRITY DRIVE RESULTS
Personal Protective Equipment (PPE) All of these are PPE: Insulated tools Meters and testing equipment Arc-rated (AR) clothing Rubber insulating equipment (gloves, matting, blankets,
sleeves..) Fall Protection Harnesses Day glow vests
COMMITMENT & INTEGRITY DRIVE RESULTS
Must comply with IEC 900 and ASTMF 1505-94 standards. Will have the 1000 volt
double triangle symbol on all rated/certified tools. Dielectrically tested with
10,000 volts, and rated for use on energized circuits up to 1000 volts.
Insulated Tools
COMMITMENT & INTEGRITY DRIVE RESULTS
Variety of Arc Flash PPE Shirts – Fire Retardant Pants – Fire Retardant Over clothing wear – Arc-rated
(Coveralls, or overcoat and over pants). Hardhat and face shield. Hoods – Arc-rated Hearing protection Rubber gloves. Leather protectors. Cotton glove liners. Glove bag. Rain gear – Arc-rated Winter wear (coats) – Arc-rated Dielectric boots. Safety shoes rated EH.
(Electrical Hazard- no metal fasteners) Harness – Arc-rated
COMMITMENT & INTEGRITY DRIVE RESULTS
Typical PPE Kit
Arc rated long-sleeve shirt & pants, or arc rated coverall.
Class OO, 11” high certified rubber gloves with leather protectors.
Hard hat. Safety glasses or goggles Head covering (hood). Arc rated face shield with arc rated
balaclava. Hearing Protection. Leather safety shoes.
PPE Category 2 arc rated clothing (min rating 8 cal/cm2)
COMMITMENT & INTEGRITY DRIVE RESULTS
When do you need to wear this?
This category of PPE will NOT protect you against all hazards for all tasks. It is appropriate for: Voltage testing/troubleshooting Removal of covers Verifying de-energizationProviding the equipment matches or exceeds the potential hazard.
PPE Category 2 arc flash apparel
COMMITMENT & INTEGRITY DRIVE RESULTS
PPE: Hand Protection Rubber gloves need to have
the class and voltage rating visible on the outer cuff.
Wear heavy-duty leather protectors when using rubber gloves, and remember leather gloves are not voltage rated, they are only to protect the rubber.
Glove liners need to be 100% cotton.
COMMITMENT & INTEGRITY DRIVE RESULTS
PPE: Hand Protection
Store gloves in a canvas glove bag to protect against damage and UV damage and store flat (do not fold).
Inspect gloves before every use for damage, which includes an inflation test.
Gloves need to be dielectrically tested by a certified lab before being put into service and then every 6 months.
COMMITMENT & INTEGRITY DRIVE RESULTS
Hazard Risk Analysis Evaluate hazards in each
step of the job and consider safety controls Same as JSA – Job Safety
Analysis
Required whenever an electrical hazard exists
COMMITMENT & INTEGRITY DRIVE RESULTS
Job Briefing Required for all electrical
work Must cover:
Hazards Work procedures Energy source controls PPE
Can be simple and verbal, or more detailed and written
COMMITMENT & INTEGRITY DRIVE RESULTS
When you hire Electrical Contractors…… Follow Established Contractor
Policy: Contractor Pre-qualification
Contractor Orientation, including notice of hazards
Performance Evaluation
Note: The meeting between owner and the electrical contractor must be documented. If imminent danger exists,
STOP WORK!!!
COMMITMENT & INTEGRITY DRIVE RESULTS
Evaluation/Performance ReviewThe owner is required to perform field audits to verify you are
following these electrical safety requirements.
So make sure you are following safe work practices and wearing your PPE when you’re supposed to.