Introduction
Why do we need protection systems
How do we protect – concepts of protection system design
Protection Schemes
Overcurrent
Distance
Differential
etc.
Udaya Annakkage Power System Protection
![Page 2: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/2.jpg)
. . . . . .
Abnormal conditions in power systems
Examples of abnormal conditions
Large currents
Large voltages, low voltages
Presence of negative and zero sequence currents
What is the problem with abnormal conditions ?
Damage to equipment and people
Interruption to power supply
Udaya Annakkage Power System Protection
![Page 3: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/3.jpg)
. . . . . .
Objectives
Prevent or at least minimize damage when abnormalconditions arise
Isolate only the directly affected part of the system
Udaya Annakkage Power System Protection
![Page 4: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/4.jpg)
. . . . . .
Design Criteria
Reliability
Speed
Selectivity (Discrimination)
Simlicity and Economy
Udaya Annakkage Power System Protection
![Page 5: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/5.jpg)
. . . . . .
Protection Zones
Each protection scheme is mainly responsible for clearingfaults within its zone
Some schemes provide backup protection to neighbouringzones
Some schemes do not provide backup protection (unitprotection schemes)
Zones are overlapped to avoid unprotected areas.
Udaya Annakkage Power System Protection
![Page 6: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/6.jpg)
. . . . . .
Functions of a protection system
Monitor the power system variables – Transducers
Detect abnormal conditions – Relay
Isolate the faulty section – Circuit Breakers
..
CB
.
Trip Signal
.
Transducer
.
Relay
.
CT
Udaya Annakkage Power System Protection
![Page 7: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/7.jpg)
. . . . . .
Transducers
Current Transformers (CT)
Electromagnetic type (most common)
Magneto–Optical type
Voltage Transformers (VT)
Capacitor divider type
Electromagnetic type
Udaya Annakkage Power System Protection
![Page 8: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/8.jpg)
. . . . . .
Burden on a CT
The load on a current transformer is called the burden
This can be expressed either as a VA load or as animpedance
.Example..
.
5 VA burden on a 1 A current transformer means:I = 1 AVI = 5 VATherefore, V=5 Vi.e. R = 5 ohm
What is the equivalent load in ohms of a 5 A burden on a 5VA CT?
Udaya Annakkage Power System Protection
![Page 9: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/9.jpg)
. . . . . .
Standard CT ratios:50:5, 100:5,150:5, 200:5, 250:5, 300:5, 400:5, 450:5,500:5, 600:5, 800:5, 900:5, 1000:5, 1200:5
Udaya Annakkage Power System Protection
![Page 10: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/10.jpg)
. . . . . .
Relays
Electromechanical: attracted armature, induction discunit, induction cup unit etc.
Static: logic units (AND,OR,NOT), time delay units,magnitude comparators, phase comparators, phase shiftunits, amplification units.
Numerical Relays: Sampling, A/D conversion, filtering,signal processing (computation of peak, average, rms,fundamental component, dc offset etc)
Udaya Annakkage Power System Protection
![Page 11: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/11.jpg)
. . . . . .
Circuit Breakers
Duties:...1 Carry full load current...2 Withstand normal voltages...3 Open and close the circuit on no load...4 Make and break normal operating currents...5 Make short circuit currents...6 Break short circuit currents
1–3 Isolators1–5 Switches1–6 Circuit BreakersTypes: Oil, Air, Air blast, Vacuum, SF6
Udaya Annakkage Power System Protection
![Page 12: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/12.jpg)
. . . . . .
Logical Design of Relays
...1 Magnitude Relays (example: overcurrent relays)
...2 Directional Relays (example: mho relays)
...3 Ratio Relays (example: distance relays)
...4 Differential Relays (example: generator or transformerinternal fault protection)
Udaya Annakkage Power System Protection
![Page 13: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/13.jpg)
. . . . . .
Overcurrent Relays
Instantaneousrelays
Inverse time relays
.
.
..Relay Current (A)
.Operatingtime(s)
Udaya Annakkage Power System Protection
![Page 14: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/14.jpg)
. . . . . .
Inverse time overcurrent relay
Relay operating time = time taken for relay operation. i.e.time delay between the occurrence of the abnormal conditionand sending a trip signal to the circuit breaker.
Electromechanical type relay
Operating time depends on:...1 Initial position of the moving contact...2 Speed of the disc (depends on mmf of the coil)
Two settings:...1 Pick-up current (plug setting, current setting)...2 Time setting (time dial setting, Time Multiplier Setting,TMS)
Udaya Annakkage Power System Protection
![Page 15: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/15.jpg)
. . . . . .
Example 1
..
Relay
.CT:400/5. If
The operatng time of the relay is given by:
t =0.14
I 0.02r − 1× TMS
where, Ir =IfIsis the ratio between the fault current If and the
current setting Is of the relay. If the current setting and TMShave been chosen to be 6A and 1.0 respectively, determine theoperating time of the relay for a fault current of 800A.
Udaya Annakkage Power System Protection
![Page 16: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/16.jpg)
. . . . . .
Example 2
The following information is given:
CT Ratio: 400/5
Current setting (pick up current) = 5.0 A
TMS = 0.2
t = 3×TMSlog(Ir )
Determine the operating time of the relay for a fault current of500A.
Udaya Annakkage Power System Protection
![Page 17: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/17.jpg)
. . . . . .
Example 3
The following information is given:
CT Ratio: 200/5
Current setting (pick up current) = 6.0 A
Fault current If is 1200A
t = 3×TMSlog(Ir )
Determine the TMS to get an operating time of 1.4 s for thisfault.
Udaya Annakkage Power System Protection
![Page 18: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/18.jpg)
. . . . . .
Example 4: Back up protection
..
A
.
B
.
R1
.CT:400/5.
R2
.CT:400/5
Current settings of R1 and R2 are at 6A and TMS of R2 is 0.1.R1 is required to provide back up protection to R2 for a faultcurrent of 1200A (a fault near bus A).Allow 0.3 seconds for backing up and determine the TMS ofR1.The fault current for a fault near bus B is 1800A. What is theoperating time of R1 for this fault.
Udaya Annakkage Power System Protection
![Page 19: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/19.jpg)
. . . . . .
Example 5: Overcurrent relay coordination
..
Bus 1
.
j5.0
.
j5.0
.
Grounded Y-Y
.
Bus 2
.B1
.j9.6
.
Bus 3
.B2
.j6.4
.
Bus 4
.B3
.j8.0
.
Bus 5
.B4
.j12.8
.Fault Currents:..
.
Bus # 1 2 3 4 5Max. Fault Current (A) 3187 659 431 301 203Min. Falut Current (A) 1380 473 329 238 165Max. Load Current (A)
Udaya Annakkage Power System Protection
![Page 20: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/20.jpg)
. . . . . .
Example 5: Settings for R4
.
.
Minimum fault current seen by Relay at B4 is 165A
Therefore choose a setting current of one third of 165A(165/3 = 55A)
Use a CT ratio of 50/5
relay current corresponding to 55A is:Ip = 55× 5/50 = 5.5A
Choose the nearest setting current, i.e. 5A.
Use a TMS of 0.5 (smallest available value is chosen tohave the fastest relay operation)
Udaya Annakkage Power System Protection
![Page 21: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/21.jpg)
. . . . . .
Example 5: Settings for R3.
.
R3 must provide primary protection to line 3–4 and backup protection for R4
Minimum fault current seen by R3 is 165A
Choose CT ratio of 50/5 and a setting current of 5A
The highest fault current seen by R4 is 301A.Corresponding relay current is 301× 5/50 = 30.1A
If /Ip = 30.1/5 = 6.
From the given relay characteristics (If /Ip = 6 and TMS= 0.5) operating time of R4 is 0.135s
For the same fault current the operating time of R3 mustbe 0.135 + 0.3 = 0.435 s
From the given relay characteristics, the required TMS is2.0
Udaya Annakkage Power System Protection
![Page 22: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/22.jpg)
. . . . . .
Example 5: Settings for R2.
.
R2 must provide primary protection to line 2–3 and backup protection for R3
Minimum fault current seen by R2 is 238A
Choose CT ratio of 100/5 (238/3 = 79.3) and a settingcurrent of 4A (79.3× 5/100)
The highest fault current seen by R3 is 431A.Corresponding relay current is 431× 5/50 = 43.1A
From the given relay characteristics (If /Ip = 8.6 and TMS= 2) operating time of R3 is 0.31s
For the same fault current the operating time of R2 mustbe 0.31 + 0.3 = 0.61 s
From the given relay characteristics, the required TMS is2.6 (If /Ip = 431× 5/100× 1/4 = 5.4)
Udaya Annakkage Power System Protection
![Page 23: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/23.jpg)
. . . . . .
TCCC – Time Current Characteristics Curves
..
R4
.
R3
.
R2
.
0.3s
.0.3s
.Fault Current (A)
.
Operatingtime(s)
Udaya Annakkage Power System Protection
![Page 24: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/24.jpg)
. . . . . .
Directional Relay
.. R.
T
.
I12
.
V
.
θmin
.
θmax
.
V
.
I12
.
−I12
θmin > θ > θmax TRIP
θmin < θ < θmax BLOCK
Udaya Annakkage Power System Protection
![Page 25: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/25.jpg)
. . . . . .
Ratio Relay: Impedance Characteristics
.. R.T
.
I
.
V
.
Real
.
Imag
.
Zr
|Z | < |Zr | TRIP
|Z | > |Zr | BLOCK
Udaya Annakkage Power System Protection
![Page 26: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/26.jpg)
. . . . . .
Ratio Relay: Mho Characteristics
..
Real
.
Imag
.
Zr
|Z − Zr | < |Zr | TRIP
|Z − Zr | > |Zr | BLOCK
|x + iy − xr − iyr | < |Zr |(x − xr )
2 + (y − yr )2 < |Zr |2
Udaya Annakkage Power System Protection
![Page 27: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/27.jpg)
. . . . . .
Ratio Relay: Offset Mho Characteristics
..
Real
.
Imag
.
Zr1
|Z − Zr1| < |Zr2| TRIP
|Z − Zr1| > |Zr2| BLOCK
|x + iy − xr1 − iyr1| < |Zr2|(x − xr1)
2 + (y − yr1)2 < |Zr2|2
Udaya Annakkage Power System Protection
![Page 28: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/28.jpg)
. . . . . .
Distance Protection
.
.
...
B1
.
B2
.
B3
.
R1:Zone 1
.
R1:Zone 2
.
R1:Zone 3
.
.
..
Impedance
.
Operatingtime(s)
.
R1:Zone 1
.
R1:Zone 2
.
R1:Zone 3
.
R2:Zone 1
.
R2:Zone 2
.
R3:Zone 1
.
R3:Zone 2
Udaya Annakkage Power System Protection
![Page 29: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/29.jpg)
. . . . . .
Example 6: Distance Protection (Impedance
Relays)
The impedance of a transmission line is 5 + j45 Ω. The CTratio is 400/5 and the VT ratio is 1000/1. A three phase faultoccurs at 60 % of the line. What is the impedance seen by therelay..
.
V
I= (5 + j45) ∗ 0.6 = 3 + j54
Vmeasured =V
1000
Imeasured =5
400I
Zmeasured =Vmeasured
Imeasured=
V
I× 1
1000× 400
5= 0.24 + j4.32Ω
Udaya Annakkage Power System Protection
![Page 30: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/30.jpg)
. . . . . .
Example 7
Determine the Zone 1 and Zone 2 settings for the relay inExample 6..Zone 1 setting..
.
Line Impedance seen by the relay = 0.4 + j 7.2 ΩZone 1 setting is 80 % of the line impedance =0.8×
√0.42 + 7.22 = 0.8× 7.21 = 5.77Ω
.Zone 2 setting..
.
Zone 2 setting is 120 % of the line impedance =1.2× 7.21 = 8.65Ω
Udaya Annakkage Power System Protection
![Page 31: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/31.jpg)
. . . . . .
Example 8
Determine the Zone 3 setting for the relay in Examples 6 and7 to provide back up protection to the next line having animpedance of 10 + j100 Ω..Zone 3 setting..
.
Impedance of the second line as seen by the relay =(10 + j100)× 400
1000×5= 0.8 + j8Ω
Zone 3 setting is 7.21 + 1.2×√0.82 + 82 = 9.65Ω
Udaya Annakkage Power System Protection
![Page 32: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/32.jpg)
. . . . . .
Differential Protection
The principle of discrimination is by comparison ofcurrents entering and leaving the protected zone.
Differential protection (also known as unit protection)schemes have absolute selectivity, fast operation and highsensitivity.
They provide protection only to a specied unit and do notprovide back up protection to other units of the system.
This is in contrast to all other schemes that operate onthe principle of time discrimination.
Udaya Annakkage Power System Protection
![Page 33: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/33.jpg)
. . . . . .
Differential Protection
..
External Fault
.
Internal Fault
Udaya Annakkage Power System Protection
![Page 34: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/34.jpg)
. . . . . .
Differential Protection: Spill Current
..
Non-ideal situation
CTs are not identical
Leads connecting the CTs to the relay are not identical
Therefore, the magnetizing currents are different.
Udaya Annakkage Power System Protection
![Page 35: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/35.jpg)
. . . . . .
Differential Protection: High Impedance Scheme
.
Stabilizing Resistance Rs is chosen to prevent relay operationfor external faults under worst case scenario where only oneCT is saturated.
Udaya Annakkage Power System Protection
![Page 36: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/36.jpg)
. . . . . .
Differential Protection: Low Impedance – Bias
.
|IR | > k |I1 + I2| TRIP
|IR | < k |I1 + I2| BLOCK
Udaya Annakkage Power System Protection
![Page 37: Protection 2014](https://reader038.vdocument.in/reader038/viewer/2022110219/577ccf061a28ab9e788eb05f/html5/thumbnails/37.jpg)
. . . . . .
State whether the following statements are True or
False and explain your answer
...1 Inverse time overurrent relays can be used for back upprotection
...2 Differential protection can provide primary protection to atransformer and back up protection to a nearby bus bar.
...3 Overlapping zones are used for providing back upprotection.
...4 Impedance relay characteristics are not suitable fordistance protection.
...5 An overcurrent relay is expected to operate undermaximum loading conditions.
...6 There will be no spill current in a differential protectionscheme if the CTs are identical.
Udaya Annakkage Power System Protection