Protection Basics
![Page 2: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/2.jpg)
Protection Review
• Fault types
• Electrical equipment damage
• Time versus current plot
• Protection requirements
• Protection system elements
![Page 3: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/3.jpg)
Power System Faults
• Short circuits
• Contacts with ground ♦ Isolated neutral systems
♦ High-impedance grounded systems
• Open phases
![Page 4: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/4.jpg)
Typical Short-Circuit-Type Distribution
Single-phase-to-ground 70 – 80%
Phase-to-phase-to-ground 10 – 17%
Phase-to-phase 8 – 10%
Three-phase 2 – 3%
![Page 5: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/5.jpg)
abc
Distribution Substation
Faults in Electrical Systems Produce Current Increments
I
I
Wire
![Page 6: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/6.jpg)
–te eiT(t) (T – T )e Tτ= +2dW I R
dt=
Temperature Rise From Current
t
T
Equilibrium
Ti
TeI
T
Constant Current
![Page 7: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/7.jpg)
Factors Influence Wire Heating
d
Current Magnitude Wire Material
Properties
Ambient Temperature
and Other Environmental
Factors
I
Wire Size
![Page 8: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/8.jpg)
t
T
td
Insulation Damage
Ti
Td
Te
Insulated Conductor (Cable) Thermal Damage
I
Insulation
![Page 9: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/9.jpg)
Insulated Conductor Thermal Damage
I
T
Damage Curve
I1Imd I
t
I2 I3
t1t2t3
t2t3 t
T
t1
Td
Ti
I = Imd
I = I1I = I2 > I1I = I3 > I2
![Page 10: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/10.jpg)
Damage Curve
RatingIn Imd I
t
Electrical Equipment Component Thermal Damage Curve
![Page 11: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/11.jpg)
Mechanical Damage
Mechanical forces (f1 and f2) produced by short-circuit currents cause instantaneous damage to busbars, insulators, supports,
transformers, and machines
i1 i2
f1 f2
f1 (t) =k i1 (t) i2 (t)
![Page 12: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/12.jpg)
Real-World Mechanical Damage
![Page 13: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/13.jpg)
Power System Protection Requirements
• Reliability ♦ Dependability
♦ Security
• Selectivity
![Page 14: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/14.jpg)
Power System Protection Requirements
• Speed ♦ System stability
♦ Equipment damage
♦ Power quality
• Sensitivity ♦ High-impedance faults
♦ Dispersed generation
![Page 15: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/15.jpg)
Protection Functions
• Fault detection
• Faulted element disconnection
• Fault indication
![Page 16: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/16.jpg)
Protective Devices
• Fuses
• Automatic reclosers
• Sectionalizers
• Circuit breakers
• Protective relays
![Page 17: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/17.jpg)
Relay Classification
• Protective
• Regulating
• Reclosing and synchronism check
• Monitoring
• Auxiliary
![Page 18: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/18.jpg)
IEEE C37.2 Device Numbers
51 Time-overcurrent relay
50 Instantaneous-overcurrent relay
67 Directional-overcurrent relay
21 Distance relay
87 Differential relay
52 Circuit breaker
![Page 19: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/19.jpg)
Protective Relaying System
52
Relay
DC Supply
Communications Channel
DC Supply
Circuit Breaker
Current Transformers
(CTs)
Voltage Transformers
(VTs)
![Page 20: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/20.jpg)
Protection System Elements
• Protective relays
• Circuit breakers
• CTs and VTs (instrument transformers)
• Communications channels
• DC supply system
• Control cables
![Page 21: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/21.jpg)
Protection System Elements
• Protective relays ♦ Monitor
♦ Detect
♦ Report
♦ Trigger
• Circuit breakers ♦ Interrupt
♦ Isolate from abnormal condition
![Page 22: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/22.jpg)
Instrument Transformers
• CTs ♦ Current scaling
♦ Isolation
• VTs ♦ Voltage scaling
♦ Isolation
![Page 23: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/23.jpg)
Overcurrent Relay Connections
52
50, 51 50, 51 50, 51 50N, 51N
3I0
Ia
IbIc
abc
Residual Current
![Page 24: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/24.jpg)
DC Tripping Circuit
DC Station Battery SI Relay
Contact
Relay
Circuit Breaker
52a
(+)
(–)
SI
52 TC
![Page 25: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/25.jpg)
Overcurrent Relay Setting
• 51 elements ♦ Pickup setting
♦ Time-dial setting
• 50 elements ♦ Pickup setting
♦ Time delay
![Page 26: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/26.jpg)
Review
• What is the function of power system protection?
• Name two protective devices
• For what purpose is IEEE device 52 is used?
• Why are seal-in and 52a contacts used in the dc control scheme?
• In a typical feeder OC protection scheme, what does the residual relay measure?
![Page 27: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/27.jpg)
Questions?
![Page 28: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/28.jpg)
Copyright © SEL 2013
Digital Relay Basics
SEL-751A Feeder Protection Relay
![Page 29: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/29.jpg)
Simple Protective Relay Auxiliary input
(ac or dc)
Settings
Output (dry contact)
Contact used to energize circuit breaker trip coil
Set relay thresholds and operation time
Current, voltage (I and V), or other quantities
Input
![Page 30: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/30.jpg)
Electromechanical Instantaneous Overcurrent Elements
![Page 31: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/31.jpg)
Magnetic Attraction Unit
Instantaneous Element
Force of contact: F = k • I2
Contacts
ArmatureHinge
Coil
Contacts
Coil
Iron coreAdjustable
stop
Contacts
Hinge
Restraining magnet
Operating magnet
![Page 32: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/32.jpg)
Pickup Current Setting
• Tap in relay current coil
• Adjust air gap
• Adjust spring
![Page 33: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/33.jpg)
Electromechanical Inverse-Time Overcurrent Elements
![Page 34: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/34.jpg)
-5 -6 -7 -8 -9 1.0
Anatomy of Induction Disc
Overcurrent Relays
Time Dial
Spring
Disc
Main Core
Permanent Magnet
Main Coil,NT Turns
Moving Contact
![Page 35: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/35.jpg)
Simplified View Shaded Pole Element
Main coil NT
turns
Permanent magnet
Taps
Spring
Disk
Axis Φ2Φ1
![Page 36: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/36.jpg)
Electromagnetic Induction Principle
Φ2 Φ1
F2 F1 iΦ1
iΦ1
iΦ2
iΦ2
Torque
![Page 37: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/37.jpg)
Summary of Induction 51 Element Setting
• Pickup current setting – taps in relay current coil
• Time-current curve setting – controls initial disc position (time dial setting)
![Page 38: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/38.jpg)
Microprocessor-Based Protection
![Page 39: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/39.jpg)
Digital Relay I/O Scheme
Computer-based relay (digital)
Computer communications
Analog inputs
Discrete inputs
Auxiliary inputs (ac or dc)
Dry contact outputs (trip and alarm)
“Live” outputs
![Page 40: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/40.jpg)
Digital Relay Architecture
Microprocessor
RAM ROM / PROM EEPROM
Discrete output
subsystem
Operation signalling
Analog input
subsystem
Discrete input
subsystem
}
Analog-to-digital (A/D)
conversion
Tripping
Outputs
Communications ports
![Page 41: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/41.jpg)
Digital Relay Algorithm
Read present sample k
Digital filtering
Phasor calculation
Protection methods
Relay logic
Modify if required
Trip orderNo trip
![Page 42: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/42.jpg)
Relay Operation Analog Inputs
![Page 43: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/43.jpg)
Signal Path for Microprocessor-Based Relays
Analog low-pass
filter
A/D conversion
Digital cosine
filter and phasor
Magnitude and
impedance
Current transformer
(CT)
Potential transformer
(PT)
![Page 44: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/44.jpg)
A/D Conversion
A/D
Analog signal Digital signal
00000001 00000101 00001001 00100100 10010000
: .
Input Output
![Page 45: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/45.jpg)
Nonfiltered signal (samples)
Filtered signal (samples)
Digital Filtering
Digital filtering
![Page 46: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/46.jpg)
Phasor samples: magnitude and angle
versus reference
| I |
θ Reference
Phasor Calculation
Filtered signal (samples)
Phasor calculation
![Page 47: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/47.jpg)
Sinusoid-to-Phasor Conversion
0 t
A 2 A
0
v(t)
θ
![Page 48: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/48.jpg)
Sinusoid to Phasors Current Channels Are Sampled
IA
t
IA
1559 –69
–1656 –2274 –1558
70 1656 2273
1 cycles8
![Page 49: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/49.jpg)
Sinusoid to Phasors
• Pick quadrature samples (1/4 cycle apart)
• Pick current sample (x sample)
• Pick previous sample 1/4-cycle old (y sample)
y sample (1/4-cycle old)
x sample (present)
IA
1559 –69
–1656 –2274 –1558
70 1656 2273
![Page 50: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/50.jpg)
Sinusoid to Phasors
2274
70
2275
X
Y
IA
t
Ia(t)
–88.2
22 yxMagnitude +=
22 )2274(–70Magnitude +=
=
xyarctanAngle
=
702274–arctanAngle
°∠= 2.88–2275IA
1 cycles8
![Page 51: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/51.jpg)
Relay Operation Relay Word Bits and Logic
![Page 52: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/52.jpg)
Relay Word Bits
• Instantaneous overcurrent
• Time overcurrent
• Voltage elements
• Inputs
• Internal relay logic: SELOGIC® variable (SV) and latches
• Outputs Assert to logical 1 when conditions are true,
deassert to logical 0 when conditions are false
![Page 53: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/53.jpg)
Instantaneous-Overcurrent Element
• 50P1P = instantaneous phase-overcurrent setting
• Ip = measured current of maximum phase
• 50P1P = 1 if Ip > 50PIP; 50P1P = 0 if Ip < 50P1P
When b (+) terminal is greater than a (–) terminal, c is logical 1
a b
c +
_
+
_50P1P
50P1P settingIp
Comparator
![Page 54: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/54.jpg)
SEL-751A Protection System Phase Time-Overcurrent Element
51P1T Phase Time-Overcurrent Element Curve Timing and Reset Timing
51P1P51P1C51P1TD51P1RS
51P1CT
51P1MR
Settings
Relay Word Bits51P1P
51P1T
51P1R
Controls the Torque Control Switch
Pickup
CurveTimeout
Reset
Torque Control Switch
Setting51P1P
IP(From Figure 4.1)
51P1TC
Reset TimingSetting
51P1RS=Electromechanical 1 Cycle
YN
51P1TCState
Torque Control Switch Position
Logical 1Logical 0
ClosedOpen
SELOGICSetting
PickupPickup TypeTime DialElectromechanical Reset? (Y / N)Constant Time AdderMinimum Response
SELOGICTorque Control
![Page 55: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/55.jpg)
SEL-751A Protection System ORED – Overcurrent Elements
• Relay Word bit ORED50T is asserted if 50PnT, 50NnT, 50GnT, or 50QnT Relay Word bits are asserted
• Relay Word bit ORED51T is asserted if 51AT, 51BT, 51CT, 51P1T, 51P2T, 51N1T, 51N2T, 51G1T, 51G2T, or 51QT Relay Word bits are asserted
![Page 56: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/56.jpg)
Standard Time-Current Characteristics IEEE C37.112-1996
![Page 57: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/57.jpg)
SEL-751A Voltage Calculation
Voltage Magnitude Calculation
(Minimum Phase Voltage Magnitude)
(Minimum Phase-to-Phase Voltage Magnitude)
(Maximum Phase-to-Phase Voltage Magnitude)
(Maximum Phase Voltage Magnitude)
VAB or VA
VBC or VB
VCA or VC
VA
VP min
VPP min
VPP max
VP max
VS
![Page 58: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/58.jpg)
SEL-751A Single- and Three-Phase Voltage Elements
VP min
VPP max
+
_
–+
–+
27P1P • Vnm
27P2P • Vnm
27P1D
27P1D
0
0
RelayWordBits
3P27
27P1
27P1T
27P2
27P2T
When DELTA_Y := WYE
![Page 59: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/59.jpg)
SEL-751A Relay Word Bit Tables 8 Relay Word Bits Per Numbered Row
Row Relay Word Bits
1 50A1P 50B1P 50C1P 50PAF ORED50T ORED51T 50NAF 52A
2 50P1P 50P2P 50P3P 50P4P 50Q1P 50Q2P 50Q3P 50Q4P
3 50P1T 50P2T 50P3T 50P4T 50Q1T 50Q2T 50Q3T 50Q4T
4 50N1P 50N2P 50N3P 50N4P 50G1P 50G2P 50G3P 50G4P
5 50N1T 50N2T 50N3T 50N4T 50G1T 50G2T 50G3T 50G4T
![Page 60: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/60.jpg)
Logic
![Page 61: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/61.jpg)
Boolean Logic
• Mathematics of logical variables (Relay Word bits)
• Operators: AND, OR, NOT, rising and falling edge, parentheses
• SELOGIC control equations Boolean operators ♦ Defined symbols
♦ Application rules
![Page 62: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/62.jpg)
SELOGIC Control Equations Operators
Operator Symbol Function
Parentheses ( ) Group terms
Negation - Changes sign of numerical value
NOT NOT Invert the logic
Rising edge R_TRIG Output asserts for one processing interval on inputs rising-edge transition
Falling edge F_TRIG Output asserts for one processing interval on inputs falling-edge transition
Multiply * Multiply numerical values
![Page 63: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/63.jpg)
SELOGIC Control Equations Operators
Operator Symbol Function
Divide / Divide numerical values
Add + Add numerical values
Subtract – Subtract numerical values
Comparison <,>,<=,>=,=, <> Compare numerical values
AND AND Multiply Boolean values
OR OR Add Boolean values
![Page 64: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/64.jpg)
SELOGIC Control Equation Examples
A
A
A
B
B
B C
C
C C = A OR B
C = A AND B
C = A AND NOT B
A B
A B
OR1
AND1
AND1 A B
![Page 65: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/65.jpg)
E = A AND B OR C OR NOT D
Equation implemented
Programmable Logic
Logic
ABCD
E
A
B
DC
E
(–)
(+)
![Page 66: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/66.jpg)
SELOGIC Control Equation Examples
TR = 50P1P AND 50G1
50P1P 50G1P
TR
TRIP
OUT101
OUT101 = TRIP
Normally open; closes when
OUT101 asserts
When the TR equation asserts, the TRIP Relay Word bit asserts
![Page 67: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/67.jpg)
Typical Logic Settings for Trip
![Page 68: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/68.jpg)
SELOGIC Control Equation Examples
CL = CC AND 3P59 AND 27S1
CL
CLOSE
OUT102
OUT102 = CLOSE
Normally open; closes when
OUT102 assertsWhen CL equation
asserts, CLOSE Relay Word bit
asserts
27S1
3P59
CC
![Page 69: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/69.jpg)
SELOGIC Example
OUT101 = (51P1T OR OUT101) AND NOT TRGTR
!TRGTR
OUT 101
51P1T OUT101OUT101 =
![Page 70: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/70.jpg)
Optoisolated Inputs
• Relay Word bits IN101 and IN102 monitor physical state inputs
• Debounce timer is built in and settable
65000 ms
65000 ms
IN101
IN102
de-energized
energized
logical 0
logical 1
IN101
IN10265000
ms
65000 ms
![Page 71: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/71.jpg)
Latching Control Logic
SET01 = CLOSE RST01 = TRIP 52A = LT01
SELOGIC Latch Equation
Relay Word Bit
LTnSETn
RSTnn = 1 – 32
![Page 72: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/72.jpg)
SV Timer
• Set as logic placeholder and timer
• Example settings ♦ SV05 = 50P1P
♦ SV05PU = 0.17 seconds
• Operation ♦ SV05 asserts when 50P1P asserts
♦ SV05T asserts 0.17 seconds after 50P1P asserts
SV05PU
SV05D0
SV05 SV05
SV05T
![Page 73: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/73.jpg)
Outputs
• When OUT101 equation is true (logical 1), OUT101 closes
• Example setting: OUT301 = SV05T
• Operation: OUT301 closes after 50P1P has been asserted for 0.17 seconds
OUT101
OUT102
OUT101
OUT102
logical 0
logical 1
de-energize
energize
OUT101(a)
OUT102(a)
Open
Closed
![Page 74: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/74.jpg)
Track Relay Word Bit State Change With Sequential Events Report (SER)
Example: 50P1 = 4 A; CTR = 120; Primary PU = 480 A
![Page 75: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/75.jpg)
Event Reporting
• Helpful in fault analysis
• Relay collects 15-cycle event report when ER = R_TRIG 50P1P
• HIS command text
![Page 76: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/76.jpg)
![Page 77: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/77.jpg)
![Page 78: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/78.jpg)
![Page 79: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/79.jpg)
Summary
• Microprocessor-based relays create phasors from sinusoid (waveform) input
• Relay Word bits control relay I/O
• Microprocessor-based relays offer many troubleshooting and fault analysis tools
• SELOGIC control equations provide programming flexibility to create virtual control circuits
![Page 80: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/80.jpg)
Questions?
![Page 81: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/81.jpg)
Copyright © SEL 2008
Protection Basics: Overcurrent Protection
![Page 82: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/82.jpg)
Fast Protection Minimizes
• Temperature rise
• Mechanical damage from magnetic forces
• Voltage sag
• Transient stability issues
• Shock and arc-flash hazards
![Page 83: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/83.jpg)
Understand Basic Protection Principles
• Overcurrent (50, 51, 50N, 51N)
• Directional overcurrent (67, 67N)
• Distance (21, 21N)
• Differential (87)
![Page 84: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/84.jpg)
Overcurrent Relays Protect Radial Lines
=+ +LOAD
Source Line LOAD
EIZ Z Z
=+FAULT
Source Line
EIZ m• Z
IFAULT >> ILOAD
Relay Load
Im
![Page 85: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/85.jpg)
Relay Operates When Current Magnitude Rises Above Threshold
125 Vdc
TC
Overcurrent Relay(+)
(–)
52a
I
Circuit Breaker Trip Coil and Auxiliary Contact
![Page 86: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/86.jpg)
Evolving Protective Relay Designs
• Electromechanical relays
• Electronic analog relays – solid state (transistors, integrated circuits)
• Microprocessor-based relays – digital or numeric
![Page 87: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/87.jpg)
How Do Instantaneous Relays Work?
ContactsCoil
Armature
Hinge
Contacts
CoilIron Core
Adjustable Stop
Contacts
Moving Cup or Cylinder
Magnetic Core
Electromagnet
Coil 2
Coil 1
![Page 88: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/88.jpg)
Plotting Electromechanical 50 Elements Time vs. Current Curve
Adjustable
t
IIpickup
toperate < 1.5 Cycles
![Page 89: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/89.jpg)
Digital Overcurrent Relay Block Diagram
Microprocessor
Analog Input Subsystem
Operation SignalingDiscrete
Input Subsystem
Discrete Output Subsystem
===
===
===
===
Tripping Outputs
Communications Ports
A / D
ROM / PROMRAM EEPROM
}
![Page 90: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/90.jpg)
Digital Relays Use Sampled Signals
∆t = Sample Interval
Present Sample
![Page 91: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/91.jpg)
Advantages of Digital 50 Elements
• No contact chatter with alternating currents
• Not affected by dc offset
• Reset-to-pickup ratio close to one
• Resistant to misoperation due to mechanical shock
![Page 92: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/92.jpg)
-5 -6 -7 -8 -9 1.0
Anatomy of Induction Disc
Overcurrent Relays
Time Dial
Spring
Disc
Main Core
Permanent Magnet
Main Coil,NT Turns
Moving Contact
![Page 93: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/93.jpg)
Operating torque > spring torque
Pickup condition
Pickup set by changing number of turns (TAP)
Induction Disc Operation Condition
pu s e s TI T K T K / N′= =
2e sK I T≥
2e pu sK I T≥
![Page 94: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/94.jpg)
Induction Disc Relay Dynamics
Acceleration Torque
Ta = Top – Tpm – Ts – Tf
θ
θF
MC
SC
![Page 95: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/95.jpg)
High Current Can Damage Equipment Thermal Damage Curve
t
IIRated Idamage
Damage Curve
Time vs. Current Plot
![Page 96: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/96.jpg)
• Displacement of moving contact is adjustable
• Time dial sets total movement required to close contact
Changing Induction Disc Operation Time
Adjustment of Time Curve t
IIpickup
Adjustable
Time Dial
Damage Curve
![Page 97: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/97.jpg)
Select Overcurrent Relay Curve
Curve shape not adjustable for
induction disc relays
100
1
0.1
0.011
10
10
Curve Comparison for TDS = 1
Multiples of Current Pickup
Tim
e (s
) Moderately Inverse
Inverse
Very Inverse
Extremely Inverse
![Page 98: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/98.jpg)
• IEEE C37.112-1996
• IEC 225-4
Time-Current Characteristics Become Standard
PAt TD• B
M 1 = + −
PAt TD•
M 1=
−
![Page 99: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/99.jpg)
U.S. inverse curve
Family of IEEE Inverse Characteristics
OP 25.95t TD• 0.18
M 1 = + −
A = 5.95, P = 2, B = 0.18 TD=
Time vs. Current Plot
Multiples of Current Pickup
101
Tim
e (s
)
102
100
10–1
10–2
101100 102
10
321
![Page 100: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/100.jpg)
• Pickup current (or tap)
• Time-dial setting (TD)
• Curve shape – inverse, very inverse, etc.
Increase Flexibility With Digital 51 Relays Settings
t
IIpickup
TD
Curve Shape
![Page 101: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/101.jpg)
Connecting Electromechanical Overcurrent Relays
52
50 / 51 50 / 51 50 / 51 50N / 51N
abc
Residual Current
Īa
ĪbĪc 3Ī0
![Page 102: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/102.jpg)
Residual current for balanced load or
three-phase faults
Residual current for ground fault
Digital Relays Calculate Residual Current
IC
IB
IA
A B C 0 GI I I 3I I+ + = =
3I0 = IG
A B C 0 GI I I 3I I 0+ + = = =
IC
IB
IA
![Page 103: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/103.jpg)
Using Zero-Sequence CT for Ground Fault Protection
Zero-sequence or core-balance CT 52
ABCCurrent Inputs
IA
IB
IC
IN
INCOM
INCOM
INCOM
INCOM
Photo courtesy of NEI Electric Power Engineering
![Page 104: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/104.jpg)
High Residual Current Due to CT Saturation
• Residual settings must be higher than elements operating from zero-sequence CTs
• Residual elements may not be appropriate for motors
• Zero-sequence CTs not subject to this problem
![Page 105: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/105.jpg)
15,000 HP Motor Trips on Start
50G
50N
49800/5
Numerical Relay
50/5IN
IG
![Page 106: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/106.jpg)
What Are Negative-Sequence Quantities?
• Unbalanced load
• Rolled phases
• Open phases
• Unbalanced faults
22 A B C3I I a I aI
where a 1 120= + +
= ∠ °
PositiveSequence
NegativeSequence
IC
IB
IA
IC
IA
IB
![Page 107: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/107.jpg)
Negative-Sequence Element Response
Three-Phase Faults
Relay
52
I2, IPhase
Fault
BI 1 120= ∠ − °AI 1 0= ∠ ° CI 1 120= ∠ °
2 A3I I= + +2Ba I CaI
1 120 •1 120∠ ° ∠ °1 240 •1 120∠ ° ∠ − °1 00
= ∠ °=
+ +
![Page 108: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/108.jpg)
Negative-Sequence Element Response Phase-to-Phase Faults
Relay
52
I2, IPhase
Fault
BI 1 0= ∠ °AI 0= CI 1 180= ∠ °
1 120 •1 180∠ ° ∠ °1 240 •1 0∠ ° ∠ °01.73 – 90
== ∠ °
+ +
2 A3I I= + +2Ba I CaI
![Page 109: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/109.jpg)
Maximum Load vs. Minimum Short Circuit
Relay
R
Phase Relay Maximum Reach
3-Phase Fault CurrentPhase-to-Phase Fault Current
I
d
IPUILOAD
![Page 110: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/110.jpg)
Sensitive Protection With Negative-Sequence Elements
Relay
R
Reach of Conventional Phase Relaysb-c fault, 3I2
b-c fault, phase current
I
d3I2 PU
ILOAD
Reach of Negative-Sequence
Element
![Page 111: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/111.jpg)
Coordinating Negative-Sequence Elements
52
F
R
51F, 51QF
Feeder Relay
IF IR51R
Phase 51, no 51Q
Line Recloser
FeederBus
![Page 112: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/112.jpg)
Traditional Phase Coordination Plus Negative Sequence
51F
310 2 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 70.1
0.2
0.30.40.50.7
1
2
3457
10
20
SECONDS
CURRENT (A)
51R51EP Equivalent Phase
Element With Low Pickup
IPU-EIR IF
![Page 113: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/113.jpg)
Set Negative-Sequence Element Pickup
Negative-sequence element is faster and more sensitive than phase overcurrent element for
phase-to-phase faults
51Q pickup (51EP pickup) 3 •=
![Page 114: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/114.jpg)
Protection Plus …
![Page 115: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/115.jpg)
Questions?
![Page 116: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/116.jpg)
Copyright © SEL 2013
Transformer Protection Basics
![Page 117: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/117.jpg)
Differential Protection Is Easy in Theory
Kirchhoff’s Current Law (KCL): n
kk 1
I 0=
=∑
I1
I2 I3
![Page 118: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/118.jpg)
Current In = Current Out
No Relay Operation if CTs Are Considered Ideal
Protected Equipment
50
CT CT
External Fault
IOP = 0
Balanced CT Ratio
![Page 119: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/119.jpg)
Operate Current Flows
Relay Operates
Protected Equipment
50
CT CT
Internal Fault
IOP > ISETTING
![Page 120: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/120.jpg)
Differential Scheme Objective
• Provide security during through faults
• Operate fast for internal faults
![Page 121: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/121.jpg)
I1
I2 I3
I1
I2 I3
Transformer Compensation
I1
I2 I3
Transformer Compensation
Transformer Energization
I1
I2 I3
Transformer Compensation
Transformer Energization
CT Saturation
What Makes Differential Protection Challenging?
![Page 122: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/122.jpg)
Examine CT Saturation Challenges
![Page 123: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/123.jpg)
Unequal CT Performance Problems
Protected Equipment
50
CT CT
External Fault
IOP ≠ 0
![Page 124: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/124.jpg)
Unequal CT Saturation
Current at LeftCurrent at Right
Differential Current
Sec
onda
ry A
mpe
res
Cycles
–200
–150
–100
–50
0
50
100
150
200
0 1 2 3 4 5 6
![Page 125: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/125.jpg)
Possible Scheme – Percentage Differential Protection Principle
Protected Equipment
CTR CTR
Relay (87)
OP S R
S RRT
I I II I
k • I k •2
= +
+=
Compares:
ISP
IS IR
IRP
![Page 126: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/126.jpg)
Differential Element
![Page 127: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/127.jpg)
Differential Characteristic Basics
Relay Operates When:
OP RT PUI k • I I≥ +
For ExternalFault WithSaturated CT
OperateRegion
RestraintRegion
IRT
IPU
IOP
IOP
![Page 128: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/128.jpg)
Percentage Differential Relays IOP Versus IRT
PowerTransformer
W1 W2
DifferentialRelay
CT1 CT2IW1 IW2
![Page 129: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/129.jpg)
Dual-Slope Characteristic IOP
IRT
Unrestrained Pickup
Minimum Pickup
Slope 1–2 Transition
(Multiples of Tap)
(Mul
tiple
s of
Tap
)
Slope 1
Slope 2Operate Region
Restraint Region
![Page 130: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/130.jpg)
How to Set Slope Characteristic Settings
• Load tap changer (10%)
• No-load tap changer (5%)
• Measuring relay error (< 5%)
• CT errors (1 to 10%)
• Transformer excitation (3 to 4%)
![Page 131: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/131.jpg)
SEL-387 / SEL-787 Logic
SEL-387 /SEL-787
HR / HB2nd and 4th
DIFFO87P
![Page 132: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/132.jpg)
IOP (IRT)2
1.51
0.50
1 2 3 4 5 6 7 8 9 100IRT
2.53
SEL-387 / SEL-787 Slope
![Page 133: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/133.jpg)
Examine Transformer Compensation Challenges
![Page 134: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/134.jpg)
Transformer Connection Compensation Phase Shift (Degrees) Connections
0 Yy0 Dd0 Dz0 30 lag Yd1 Dy1 Yz1 60 lag Dd2 Dz2
120 lag Dd4 Dz4 150 lag Yd5 Dy5 Yz5 180 lag Yy6 Dd6 Dz6 150 lead Yd7 Dy7 Yz7 120 lead Dd8 Dz8 60 lead Dd10 Dz10 30 lead Yd11 Dy11 Yz11
![Page 135: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/135.jpg)
( )( )a b 2 1I I N / N−
( )( )b c 2 1I I N / N−
( )( )c a 2 1I I N / N−
aI
bI
cI
N1 : N2
Traditional Compensation Method CTR1
( )( )c a 2 1 1I I N / N / CTR−
R3
R2
R1( )( )b c 2 1 1I I N / N / CTR−
( )( )a b 2 1 1I I N / N / CTR−
( )c a 2I I / CTR−
( )b c 2I I / CTR−
( )a b 2I I / CTR−
CTR2
![Page 136: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/136.jpg)
Compensation With Digital Relays
• Current magnitude and phase shift compensation
• Set relay according to transformer characteristics
• Consider all possible connections
![Page 137: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/137.jpg)
Tap Compensation
where:
C = 1 for wye-connected CTs
C = for delta-connected CTs 3
=LL
MVA •1000 • CTAP3 • KV • CTR
![Page 138: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/138.jpg)
Simpler and Better Connections
Winding 1 Winding 2A
H2
H1 aX2
X1
H1
H2H3
X1
X3
X2
IAW1IBW1ICW1
IAW2IBW2ICW2
BC
bcH3 X3
![Page 139: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/139.jpg)
DABY Transformer and CT Connection Compensation
H1
H2H3
1Tap1
Y
87
1Tap2
DAB
Y Y
X1
X3
X2
≡DABY Dy1
![Page 140: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/140.jpg)
Wye Connection Compensation
IAW11
Tap1
IBW11
Tap1
1Tap1
ICW1
Y
= IAW1I1W1CTap1
= ICW1I3W1CTap1
= IBW1I2W1CTap1
![Page 141: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/141.jpg)
DAB Connection Compensation
IAW21
Tap2
IBW21
Tap2
1Tap2
ICW2
DAB
( )−=
IAW2 IBW21I1W2C •Tap2 3
( )−=
ICW2 IAW21I3W2C •Tap2 3
( )−=
IBW2 ICW21I2W2C •Tap2 3
![Page 142: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/142.jpg)
Compensation Matrices
IAWnIAWnC
M1M2
M3
M4
M5M6M7
M8
M9
M10
M11M12
![Page 143: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/143.jpg)
SEL-387 Compensation Method
• [CTC(m)]: 3 x 3 matrix
• m = 0, 1,…12 ♦ m = 0: identity matrix (no changes)
♦ m ≠ 0: remove I0; compensate angles
♦ m = 12: remove I0; no angle compensation
[ ]IAWnC IAWnIBWnC CTC(m) • IBWnICWnC ICWn
=
![Page 144: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/144.jpg)
Differential Element Operate and Restraint Quantities
I2
I1IW1
IW2
IW1'
IW2'
1Tap1
1Tap2
Transformer / CT Connection Compensation
Transformer / CT Connection Compensation
1 2I I+ IOP(Multiples of Tap)
1 2I I2+ IRT
(Multiples of Tap)
+
![Page 145: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/145.jpg)
Examine Transformer Inrush Challenges
![Page 146: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/146.jpg)
0 1 2 3 4 5 6 7–50
0
50
100
150
200
250
300
Cycles
Prim
ary
Cur
rent
(A)
Phase C Inrush Current Obtained From Transformer Testing
![Page 147: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/147.jpg)
Inrush Current Has High Second Harmonic
1 2 3 4 5 6 70
50
100
Fundamental Frequency Magnitude2nd Harmonic Magnitude
Prim
ary
Cur
rent
(A)
Cycles
1 2 3 4 5 6 70
20
40
60
80
Cycles
Per
cent
age
of
Fund
amen
tal
2nd Harmonic Percentage
2nd Harmonic Block Threshold
![Page 148: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/148.jpg)
Internal Faults Versus Inrush Harmonic-Based Methods
• Harmonic blocking
• Harmonic restraint
![Page 149: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/149.jpg)
Inrush Conditions – Blocking
Operate Region
Restraint Region
Slope 2
Slope 1
IRT
Operate Point
IOP
![Page 150: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/150.jpg)
Inrush Conditions – Restraint
IOP
Operate Region
Operate Point
Slope 1
Slope 2Restraint Region
IRT
![Page 151: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/151.jpg)
Conclusions
• Apply differential element Slope 2 to compensate for CT saturation
• Set current compensation for phase and magnitude differences across transformers
• Use harmonic blocking and restraint to prevent differential element assertion during inrush
![Page 152: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/152.jpg)
Questions?
![Page 153: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/153.jpg)
Copyright © SEL 2013
Induction and Synchronous Motor Protection Recommendations
![Page 154: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/154.jpg)
Induction Motor Protection
• Phase overcurrent (50 / 51)
• Ground overcurrent (50G / 50N / 51G / 51N)
• Voltage (27 / 59)
• Current unbalance (46)
• Differential (87)
![Page 155: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/155.jpg)
Induction Motor Protection
• Phase sequence (47)
• Resistance temperature device (RTD) thermal (49R)
• Thermal overload (49)
• Load-loss / load-jam (37)
• Starts per hour, time between starts (66)
• Antibackspin
![Page 156: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/156.jpg)
Synchronous Motor Protection
• Induction motor protection elements
• Loss-of-excitation (40)
• Loss-of-synchronism (78)
• Field ground fault (64F)
![Page 157: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/157.jpg)
Phase Overcurrent Protection (50 / 51)
Ground Overcurrent Protection (50G / 50N / 51G / 51N)
![Page 158: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/158.jpg)
Phase Overcurrent Protection
• Phase overcurrent devices detect phase-to-phase and three-phase faults within motor windings and on feeder cables
• Failure to clear fault quickly causes ♦ Increased motor conductor or feeder
cable damage
♦ Stator iron damage
♦ Prolonged system voltage dips
![Page 159: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/159.jpg)
Settings Considerations
• Do not use relay phase fault protection with fused motor contactors
• Avoid tripping on motor inrush ♦ Symmetrical locked rotor current
♦ Subtransient component
♦ Asymmetrical (dc offset) component effectively removed from element by microprocessor-based relay
• Coordinate with upstream protection
![Page 160: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/160.jpg)
Optimum Two-Level Phase Overcurrent Protection
• Level 1 settings ♦ Phase overcurrent pickup at 1.2 to 1.5 • LRA
♦ Overcurrent delay at 6 to 10 cycles to ride through subtransient inrush
• Level 2 settings ♦ Phase overcurrent pickup at 1.65 to
2.0 • LRA
♦ Phase overcurrent delay at 0
![Page 161: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/161.jpg)
Ground Overcurrent Protection
• Ground overcurrent devices detect faults involving ground within motor windings and on feeder cables
• Failure to clear these faults quickly causes ♦ Increased motor conductor or feeder cable
damage
♦ Stator iron damage
♦ Prolonged system voltage dips
![Page 162: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/162.jpg)
Ground Fault Protection Depends on System Grounding Design
• Solidly grounded systems have high phase-to-ground fault currents
• Resistance-grounded systems limit phase-to-ground fault current
• Limiting current limits damage due to ground faults but requires increased relay sensitivity
![Page 163: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/163.jpg)
CT Connections
MPR
50 50G
Motor
3
Solidly / Low-Resistance Grounded Source
MPR
50 50N
Motor
3
Solidly / Low-Resistance Grounded Source
1
MPR
50
50N
Motor
3
Low- / High- Resistance Grounded
Source
1
(a) (b)
(c)
MPR = motor protection relay
![Page 164: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/164.jpg)
Solidly Grounded Systems
• Ground fault currents in solidly grounded systems can approach phase fault levels
• Ground fault protection for these systems is usually provided by residual protection, either calculated by relay or by external CT residual connection to IN input
![Page 165: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/165.jpg)
Settings Considerations
• Residual protection set to coordinate with upstream devices
• False residual current can occur because of CT saturation
• Level 1 residual overcurrent pickup set at 0.4 to 0.6 • FLA
• Level 1 residual overcurrent delay set at 0.2 s to ride through false residuals
![Page 166: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/166.jpg)
Low-Resistance Grounded Systems
• Ground fault currents limited to 100 to 1000 A
• Ground faults cleared in < 10 s ♦ Minimize fault arc damage
♦ Protect grounding resistors from thermal damage
• Ground fault protection for motors is usually instantaneous or definite-time
![Page 167: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/167.jpg)
Settings Considerations
• Residual elements ♦ Set Level 1 residual overcurrent pickup at
0.4 to 0.6 • FLA
♦ Set Level 1 residual overcurrent delay at 0.2 s to ride through false residuals upon starting
• Ground elements with core-balance CT ♦ Set Level 1 neutral overcurrent pickup at
5 to 20 A primary current
♦ Set Level 1 neutral overcurrent delay at 0.1 s
![Page 168: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/168.jpg)
High-Resistance Grounded Systems
• Typically found on low-voltage systems but sometimes used on medium-voltage systems
• Limit phase-to-ground fault currents to < 10 A
![Page 169: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/169.jpg)
High-Resistance Grounded Systems
• Single-phase-to-ground fault produces an alarm only – ground can then be located and cleared in controlled manner
• This system requires core-balance CT for sensitivity
![Page 170: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/170.jpg)
Settings Considerations
• Set Level 1 neutral overcurrent pickup at 25 to 50% of available ground fault current
• Set Level 1 neutral overcurrent delay at 2 to 5 s
• Program neutral overcurrent for alarm only
![Page 171: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/171.jpg)
Ground Overcurrent Settings Considerations
Source Grounding
Available Ground Fault
Current
CT Connections
Relay Function
Setting Considerations Delay
Solidly grounded
Can approach phase fault
levels
a 50G 40 to 60% • FLA 0.2 s
b 50N
Low-resistance grounded
100 to 1000 A
a 50G 40 to 60% • FLA 0.2 s
b 50N
c 50N 5 to 20 A (primary) 0.1 s
High-resistance grounded
< 10 A c 50N
25 to 50% of available
ground fault current
2 to 5 s
![Page 172: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/172.jpg)
Undervoltage Protection (27)
Overvoltage Protection (59)
![Page 173: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/173.jpg)
Undervoltage
• Running motors for prolonged periods at less than rated voltage can cause overheating
• Undervoltage tripping can clear a bus after complete loss of voltage – prevents simultaneous restart of connected motors when voltage returns
![Page 174: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/174.jpg)
Settings Considerations
• Motor standards require motors capable of continuous operation at 90% of motor-rated voltage per motor specification
• Undervoltage protection should not trip motors because of voltage dips caused by faults or motor starts
• Undervoltage protection is not usually set to trip motors during fast bus transfers
![Page 175: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/175.jpg)
Settings Considerations – Trip
• Set undervoltage trip pickup slightly under minimum rated operating voltage
• Set undervoltage trip delay longer than ♦ Maximum time required for fast bus transfers
♦ Maximum fault-clearing time for faults that would cause voltage to drop below pickup
♦ Starting time for any motor on bus if motor starts will cause bus voltage to drop below undervoltage trip pickup
![Page 176: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/176.jpg)
Settings Considerations – Alarm
• Set undervoltage alarm level at or slightly above motor minimum rated operating voltage
• Set undervoltage alarm delay longer than ♦ Maximum time required for normal bus
transfers
♦ Maximum fault-clearing time for faults that would cause voltage to drop below pickup
![Page 177: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/177.jpg)
Overvoltage
Running motors for prolonged periods at greater than rated voltage can cause loss of
insulation life or insulation failure
![Page 178: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/178.jpg)
Settings Considerations
• Motor standards require that motors be capable of continuous operation at 110% of rated voltage
• Overvoltage alarming is generally used in favor of overvoltage tripping
• If overvoltage tripping is applied, consider using a time delay
![Page 179: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/179.jpg)
Current Unbalance Protection (46)
![Page 180: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/180.jpg)
Current Unbalance
• Caused by ♦ Unbalanced voltages
♦ Single phasing
• Creates negative-sequence current flow in rotor ♦ Heating effect at full load is same as locked
rotor condition
♦ Rotor overheats
![Page 181: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/181.jpg)
Negative-Sequence Heating
• Negative-sequence current causes double-frequency flux in rotor
• Rotor current occupies one-sixth of cross-section area of bars, causing overheating at periphery
Rotor Bar Status
UnbalanceS′ = 2 – S
RunningS′ = S = 0.01
StartingS′ = S = 1
S = Slip S′ = Rotor Current Frequency
![Page 182: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/182.jpg)
Current Unbalance
• Biases thermal overload element
• Is detected by ♦ Thermal model under moderate conditions
♦ Current unbalance elements under severe conditions
![Page 183: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/183.jpg)
Settings Considerations
• Trip ♦ Set current unbalance trip pickup to 15%
♦ Set current unbalance trip delay to 5 s
• Alarm ♦ Set current unbalance alarm pickup to 10%
♦ Set current unbalance alarm delay to 10 s
![Page 184: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/184.jpg)
Differential Protection (87)
![Page 185: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/185.jpg)
Differential Protection
• Phase differential (large machines)
• Self-balancing (87M) differential (machines rated 1000 hp and up)
• Detection of phase faults and possibly phase-to-ground faults depending on system grounding
87
M52CT
![Page 186: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/186.jpg)
Phase Percentage Differential (87R)
O = operating coil R = restraining coil
R
RO
R
R
R
R
O
O
52
![Page 187: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/187.jpg)
Percentage Restraint (87) Differential Characteristic
IRT(Multiples of TAP)
(Mul
tiple
s of
TA
P)
Slope 1 to 2 Transition
Slope 2 60%
Slope 1 25%
IOP
Unrestrained Pickup
Minimum Pickup
Restrain
Operate
![Page 188: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/188.jpg)
Self-Balancing (87M) Differential Protection
Core-balance CT
Neutral-side CT with IA, IB, and IC connected
Neutral-side CT with IA, IB, and IC not connected
A
CB Motor
IA87 IC87IB87
A
CB Motor
IA87
IC87
IB87
IA
IB
IC
A
CB Motor
IA87
IC87
IB87
![Page 189: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/189.jpg)
Phase Sequence Protection (47)
![Page 190: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/190.jpg)
Phase Sequence
• Also referred to as phase reversal
• Operates on voltage or current
• Checks that phase rotation signals applied to relay match phase rotation setting
![Page 191: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/191.jpg)
RTD Thermal Protection (49R)
![Page 192: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/192.jpg)
RTD Thermal Element Detects Loss-of-Cooling Efficiency
• Cooling pump failure
• Inlet air reduction
• Detection using direct temperature measurement (RTDs)
![Page 193: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/193.jpg)
Thermal Overload Protection (49)
![Page 194: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/194.jpg)
Thermal Protection
• Running overload
• Starting / stalling
• Running unbalance
![Page 195: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/195.jpg)
Running Protection
• Load greater than service factor causes excessive I2R heating in stator windings
• Unbalance current causes excessive heating in rotor
![Page 196: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/196.jpg)
Thermal Model Protection
• Electromechanical relays using bimetal and solder-pot elements do not match motor time constants
• Microprocessor-based relays can match thermal properties identified by motor data and can monitor RTDs embedded in stator winding
![Page 197: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/197.jpg)
Integrated Motor Thermal Protection
• Provides locked rotor, overload, and unbalance protection
• Defines operating characteristics by motor characteristics
![Page 198: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/198.jpg)
Bimetallic Overload Element
• I2R heating opens contacts to trip motor
• Reset characteristic not related to motor
• This element has ♦ Uncertain response to unbalance
♦ Sensitivity to cabinet ambient temperature
![Page 199: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/199.jpg)
Motor First Order Thermal Model
Cth = equivalent thermal capacityRth = equivalent thermal resistanceθ = temperature rise with respect to ambient
Cth Rth θ
Motor
f (I1,I2)
![Page 200: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/200.jpg)
Motor Thermal Image or Thermal Model Relays
• Use single-state model
• Use double-state model ♦ Starting
♦ Running
Relay
![Page 201: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/201.jpg)
Single-State Thermal Model Relay Principle
Cth Rth θa • I2
+–
Tripθtrip
θ
Heating Cooling
Relay
![Page 202: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/202.jpg)
Two-State Thermal Model Protection Element
θ
Relay
Cth Rth θ
2 21 23 • (I I )+
2 21 2(I 5 • I )+
For I1 > ILIM
For I1 < ILIM
Running State
Start / Stall State
C′th R′th
![Page 203: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/203.jpg)
Thermal Model Relay Starting State
• If Cth is fixed, determine only one setting, θtrip
• Use locked rotor safe stall times
θ2 21 23 • (I I )+
Start / Stall State
+–θtrip
TripRelay
Cth
![Page 204: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/204.jpg)
Thermal Model Relay Running State
• Determine settings: Cth, Rth, θtrip
• Use motor damage curves to fit model
θ2 21 2(I 5 • I )+
Running State
+–θtrip
Trip
Cth Rth
Relay
![Page 205: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/205.jpg)
High-Inertia Starting
• High-inertia loads, such as induced draft fans, require long acceleration times
• Starting time may exceed locked rotor limit
10 100 1,000
100
10
1
0.1
0.01
1,000
Sec
onds
Amperes
M-S
tart
M
Motor Locked
Rotor Limit
![Page 206: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/206.jpg)
Traditional Solution: Speed Switch Proximity Probe and Rotating Disk
• Proximity probe is magnetic
• Rotating disc uses laser
• Safe stall time setting is increased to accommodate acceleration – supervised by detection of shaft rotation (25 to 35% of speed) within set time limit
![Page 207: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/207.jpg)
Rotor Design
![Page 208: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/208.jpg)
Rotor Resistance Variation
Skin Effect Deep Bar Effect
Skin effect
Deep bar effect
![Page 209: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/209.jpg)
Linear Approximation of Slip-Dependent Rotor Resistance and Reactance
XM
RN
XN
RM
01Slip
![Page 210: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/210.jpg)
Steinmetz Electrical Model
( )r1 SR S
S−
jXr(S) Rr(S)
Ir
jXmV
jXS RS
IS
![Page 211: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/211.jpg)
Slip-Dependent Rotor Resistance
• Motor heating is caused by watt loss in rotor and stator resistance
• Rotor resistance decreases from high locked rotor value to low value at rated speed (shown in Steinmetz model)
![Page 212: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/212.jpg)
Positive- and Negative-Sequence Rotor Resistances Are Linear
Functions of Slip
Where:
RM = resistance at locked rotor
RN = rotor resistance at rated speed
S = slip
( )( )( )
1 M N N
2 M N N
R R R S R
R R R 2 S R
= − + = − − +
![Page 213: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/213.jpg)
RM and RN Defined
• RM and RN are defined by ♦ Locked rotor current IL
♦ Locked rotor torque LRQ
♦ Synchronous speed ωsyn
♦ Rated speed ωrated
• In Steinmetz model, mechanical power PM is 2
M r1 SP • I R
S−
=
![Page 214: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/214.jpg)
Solving for Rotor Resistance
Torque is power divided by speed
Solving for rotor resistance Rr
− = = = = ω − −
22M M r
M rP P I R1 S 1Q I R
1 S S 1 S S
Mr 2
QR SI
=
![Page 215: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/215.jpg)
Substitute Known Values
At locked rotor, S = 1 and QM = LRQ
S at rated speed is SN, I = 1 and QM = 1
r M 2L
LRQR RI
= =
N N
syn ratedN
syn
R S
R
=
ω − ω=
ω
![Page 216: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/216.jpg)
Locked Rotor Case
Motor Current
Motor Torque
Tem
pera
ture
(U/U
L), R
otor
(R •
0.01
)
Time (s)
1.0
0.8
0.6
0.4
0.2
0
I2t Rotor Temperature
0 5 10 15 20 25 30
RM = RN
10
8
6
4
2
0
Cur
rent
(pu)
![Page 217: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/217.jpg)
Derive Slip Using Voltage and Current
When V1 and I1 are monitored, apparent positive-sequence
impedance looking into the motor is
= + = 1
1
VZ R jXI
![Page 218: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/218.jpg)
Motor Impedance
From the Steinmetz model
+ = + +
+ +
rr m
S Sr
r m
R jX • jXSZ R jX R jX jXS
![Page 219: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/219.jpg)
Motor Impedance
Expanding the equation
( )
( )
+ + + = + +
+ +
22r rm m r m r m
S S 22r
r m
R RX j X X X X XS S
Z R jXR X XS
![Page 220: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/220.jpg)
Motor Impedance
The real part of Z is
( )
2rm
S 22r
r m
R XSR R
R X XS
= + + +
![Page 221: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/221.jpg)
Motor Impedance
Divide numerator and denominator by (Xm)2
( )= +
+ +
r
S 22r mr
2 2m m
2r
2m
RSR R
X XR 1S X X
R 1But is negligibleS X
![Page 222: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/222.jpg)
Motor Impedance
2r m
m
rS
Let
X XAX
ThenRR R
A • S
+=
= +
![Page 223: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/223.jpg)
Derive Slip
Consider only the real part of motor impedance
rS
RR RA • S
= +
Next, substitute the linear equation for Rr+ in terms of slip, and solve for slip
( ) ( )N
S M N
RSA R R R R
=− − −
![Page 224: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/224.jpg)
Slip-Dependent Rotor Resistance
Positive-sequence rotor resistance
Negative-sequence rotor resistance
[ ]1 M N NR (s) (R R )S R= − +
[ ]2 M N NR (s) (R R )(2 S) R= − − +
![Page 225: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/225.jpg)
Motor Current and Rotor Temperature
Rotor Temperature
Motor Current
0 4 8 12 16 20
10
8
6
4
2
0
Cur
rent
(pu)
Tem
pera
ture
(pu
of li
mit)
1.0
0.8
0.6
0.4
0.2
0
Time (s)
Rr = (RM – RN)S + RN
![Page 226: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/226.jpg)
Constant Resistance Model Accuracy
Rotor Temperature
Motor Current
0 4 8 12 16 20
10
8
6
4
2
0
Cur
rent
(pu)
Tem
pera
ture
(pu)
1.0
0.8
0.6
0.4
0.2
0
I2t Relay
Time (s)
![Page 227: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/227.jpg)
Load-Loss / Load-Jam Protection
• Detects load loss on undercurrent or low power
• Trips for safety if load decouples
• Detects load jam using definite-time overcurrent (armed only when motor is running)
![Page 228: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/228.jpg)
Frequent Starts
• Repetitive intermittent operation can cause mechanical stressing of stator or rotor end windings
• Microprocessor-based relays provide for fixed time intervals between starts or limit the number of starts per hour
![Page 229: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/229.jpg)
Frequent Starts or Intermittent Operation
• Starts-per-hour protection limits the number of motor starts in any 60-minute period
• Minimum time between starts prevents immediate restart
• Settings developed using motor data sheet
![Page 230: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/230.jpg)
Frequent Starts or Intermittent Operation
• Induction motors, initially at ambient, usually allow two successive starts – coasting to reset between starts
• One start occurs with motor initially at operating temperature
![Page 231: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/231.jpg)
Antibackspin Protection
• Pump motors can spin backward for a short time after motor shutdown
• Restart during backspin period is dangerous (prevent high torque with premature starts)
• Simple lockout delay follows trip
![Page 232: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/232.jpg)
Synchronous Motor Protection Loss of Excitation
• Causes ♦ Operator error
♦ Excitation system failure
♦ Flashover across slip rings
♦ Incorrect tripping of rotor field breaker
• Consequences ♦ Motor operates as induction motor
♦ Motor draws reactive power from system
![Page 233: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/233.jpg)
Loss-of-Excitation Detection
Elements detect excessive VAR flow into the motor
• Impedance
• Power factor
• VAR
![Page 234: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/234.jpg)
Synchronous Motor Protection Loss of Synchronism
• Causes
♦ Excessive load
♦ Reduced supply voltage
♦ Low motor excitation
• Consequences
♦ High current pulses may exceed three-phase faults at motor terminals
♦ Motor operates at different speed
♦ Watts flow out and VAR flows into motor
![Page 235: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/235.jpg)
Loss-of-Synchronism Detection
• Element usually responds to variation on motor power factor angle or reactive power
• Impedance relays available for loss-of-excitation detection may also detect loss of synchronism
![Page 236: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/236.jpg)
Importance of Field Ground Detection
• Single point-to-ground fault in field winding circuit does not affect motor operation
• Second point-to-ground fault can cause severe damage to machine ♦ Excessive vibration
♦ Rotor steel and / or copper melting
![Page 237: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/237.jpg)
Rotor Ground Detection Methods
• Voltage divider
• DC injection
• AC injection
• Switched dc injection
![Page 238: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/238.jpg)
Switched DC Injection Method
BrushesExciter
Measured Voltage
Grounding Brush
Rotor and Field WindingField Breaker
R1
R2
–
+
Rs
![Page 239: Protection Basics - site.ieee.org · protection? • Name two protective devices • For what purpose is IEEE device 52 is used? • Why are seal-in and 52a contacts used in the dc](https://reader033.vdocument.in/reader033/viewer/2022041421/5e1efd9166cf496d44698fc9/html5/thumbnails/239.jpg)