PROTECTION OF TRANSFORMERSM-3311A TEST PLAN
![Page 2: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/2.jpg)
Chuck Mozina -- is a Consultant, Protection and Protection Systems for Beckwith Electric and resides in Palm Harbor (near Tampa), Florida. . He is a Life Fellow of the IEEE. His consulting practice involves projects relating to protective relay applications, protection system design and coordination. He specializes in generator and power plant protection.
Chuck is an active 20-year member of the IEEE Power System Relay Committee (PSRC) and is the past chairman of the Rotating Machinery Subcommittee. He is active in the IEEE IAS I&CPS, PCIC and PPIC committees, which address industrial system protection. He is a former U.S. representative to the CIGRE Study Committee 34 on System Protection and has chaired a CIGRE working group on generator protection. He also chaired the IEEE task force that produced the tutorial “The Protection of Synchronous Generators,” which won the PSRC’s 1997 Outstanding Working Group Award. Chuck is the 1993 recipient of the Power System Relay Committee’s Career Service Award and he recently received the 2002 IAS I&CPS Ralph Lee Prize Paper Award. His papers have been republished in the IAS Industrial Applications Magazine.
Chuck has a Bachelor of Science in Electrical Engineering from Purdue University and is a graduate of the eight month GE Power System Engineering Course. He has authored a number of papers and magazine articles on protective relaying. He has over 25 years of experience as a protection engineer at Centerior Energy, a major investor-owned utility in Cleveland, Ohio where he was the Manager of the System Protection Section. He is also a former instructor in the Graduate School of Electrical Engineering at Cleveland State University as well as a registered Professional Engineer in the state of Ohio
![Page 3: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/3.jpg)
Digital Transformer RelayM-3311A
![Page 4: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/4.jpg)
Three Winding Transformer Relay-- External Connections
•3 Three Phase Current, plus Two Ground Current Inputs!
•One Voltage Input
![Page 5: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/5.jpg)
TWO WINDING APPLICATION
![Page 6: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/6.jpg)
THREE WINDING APPLICATION
5 1W 1
A
5 0W 1
4 6W 3
5 0 B FW 3
5 0W 3
5 1W 3
5 9 G8 1O /U 2 7
3 -C T
3 -C T
M - 3 3 1 1
T h is f u n c t io n is a v a ila b le a s as ta n d a r d p r o te c t iv e f u n c t io n .
T h is f u n c t io n is a v a ila b le a s ao p t io n a l p r o te c t iv e f u n c t io n .
B
1 -C T
R
8 7 G DW 2
50NB F W 2
5 1 NW 2
8 7 H
W i n d i n g 1(W 1 )
W i n d i n g 2(W 2 ) W i n d i n g 3
(W 3 )5 0 GW 2
5 1 GW 2
C2 4
8 7 T
1
4 6W 2
5 0 B FW 2
5 0W 2
5 1W 2
1
5 0 GW 3
5 1 GW 3
8 7 G DW 3
50NB F W 3
5 1 NW 3
R
1
1
1
VT2
3 -C T
1 -C T
50NBFW 1
5 1 NW 1
5 0 B FW 1
4 9W 1
4 9W 2
4 9W 3
5 0 NW 2
5 0 NW 1
5 0 NW 3
T a r g e t s( O p t i o n a l )
I n t e g r a l H M I( O p t i o n a l )
M e t e r i n g
S e q u e n c e O fE v e n t s
W a v e f o r mC a p t u r e
I R I G - B
F r o n t R S - 2 3 2C o m m u n i c a t i o n
M u l t i p l e S e t t i n gG r o u p s
Pr o g r a m m a b l e I / O
S e l f D i a g n o s t i c s
D u a l P o we r S u p p ly( O p t io n a l)
R e a r M O D B U S o r D N P
C o m m u n ic a t io n
B r e a k e r M o n it o r in g
![Page 7: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/7.jpg)
FOUR WINDING APPLICATION
![Page 8: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/8.jpg)
FOUR WINDING APPLICATION – SUMMING CURRENT
![Page 9: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/9.jpg)
OVERALL TEST PLAN
1. Relay set-up
2. Simulate full load at unity P.F.
3. Test 87T for Wye-Wye Transformer
4. Test 87T For Delta-Wye Transformer
5. Oscillograph Demo
![Page 10: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/10.jpg)
OVERALL TEST PLAN
1. Relay set-up
2. Simulate full load at unity P.F.
![Page 11: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/11.jpg)
DIGITAL TRANSFORMERDIFFERENTIAL RELAY
Y-Y TRANSFORMER
![Page 12: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/12.jpg)
ANSI/IEEE PHASING STANDARD
H1, H2, H3 Primary Bushings
X1, X2, X3 Secondary Bushings
TransformerH1H2H3
X1X2X3
Wye-Wye H1 and X1 at zero degreesDelta-Delta H1 and X1 at zero degreesDelta-Wye H1 lead X1 by 30 degreesWye-Delta H1 lead X1 by 30 degrees
![Page 13: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/13.jpg)
TWO WINDING APPLICATION
![Page 14: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/14.jpg)
SOFTWARE DEMO
![Page 15: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/15.jpg)
![Page 16: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/16.jpg)
M-3311A CT Connections for Y-Y Transformer – 87T Test Connections
1800
600
- 600
![Page 17: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/17.jpg)
87T SET-UP – M-3311A
![Page 18: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/18.jpg)
87T SET-UP – M-3311A
![Page 19: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/19.jpg)
87T SET-UP – M-3311A
![Page 20: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/20.jpg)
87T SETTINGS
Pickup (pu) – 0.25 pu Slope 1 ------ 30% Slope 2 ------ 60% Breakpoint --- 2.0pu 2nd and 4th Harmonics ------- 15% 5th Harmonic ----------------- 30% Tap W1 ------------------------ 1.0A Tap W2 ------------------------ 1.0A
M-3311A —System Setup
![Page 21: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/21.jpg)
87T SETTINGS
![Page 22: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/22.jpg)
87T SETTINGS
![Page 23: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/23.jpg)
87T SETTINGS
![Page 24: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/24.jpg)
Typical Phase DifferentialCharacteristic – Percentage Slope
Min. Pickup
Slope 1
Slope 2
TRIPRESTRAIN
1.0 2.0
Break Point
UNITI1 I2
I3
I1 + I2 + I3 = 0= 0
![Page 25: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/25.jpg)
87T TESTING FOR Y-Y TRANSFORMER CONNECTION
CHECK FOR PROPER CONNECTIONS.
A) APPLY 5A THREE PHASE CURRENTS TO BOTH INPUT 1 and INPUT2. RELAY SHOULD NOT OPERATE. CHECK PHASE ANGLE METERING SCREEN FOR PROPER PHASING.
MINIMUM PICKUP TESTA) SET INPUT 1 CURRENTS = 0
B) HOLD DOWN TARGET RESET BUTTON. SLOWLY INCREASE CURRENTS IN INPUT 2 CURRENTS. THE RELAY WILL OPERATE WHEN CURRENT REACHES 0.25A. ( 1.0A TAP X 0.25 PU).
SLOPE 1 TEST
A) SET BOTH INPUT 1 AND INPUT 2 CURRENTS TO 1.0A.
B) CALCULATE THE VALUE OF INPUT 1 USING THE BELOW EQUATION WHERE S1 IS THE % SLOPE SETTING. FROM OUR SETTINGS: SLOPE 1 = 30%
INPUT 1 = INPUT 2 [ 200 + S1 ] = 1.0A [ 200 +30 ] = 1.35A 200 – S1 200 -30
C) HOLD DOWN TARGET RESET BUTTON AND SLOWLY INCREASE INPUT 2 CURRENTS. LED SHOULD COME ON AT 1.35A.
![Page 26: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/26.jpg)
87T TESTING FOR Y-Y TRANSFORMER CONNECTIONSLOPE 2 TEST
A) SET BOTH INPUT 1 and INPUT 2 CURRENTS TO 5.0A.
B) CALCULATE THE VALUE OF INPUT 1 USING THE BELOW EQUATION WHERE S1 AND S2 ARE THE SLOPE SETTING. FROM OUR SETTINGS: SLOPE 1 = 30% SLOPE 2 = 60% BP (BREAK POINT) =2.0
INPUT 1 = [ INPUT 2 (1+S2) + BP ( S1 – S2) ] _ 200 _100____
1 - S2200
= [ 5.0 ( 1 +60 ) + 2.0 ( 30-60) ]_______200________100____
1 - 60200
= 8.43A
C) HOLD DOWN TARGET RESET BUTTON AND SLOWLY INCREASE INPUT 2 CURRENTS. LED SHOULD COME ON AT 8.43A.
![Page 27: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/27.jpg)
87T TESTING FOR Y-Y TRANSFORMER CONNECTIONSECOND HARMONIC RESTRAINT TEST( ENERGIZING INRUSH RESTRAINT)
A) ENSURE THAT EVEN HARMONIC RESTRAINT IS ENABLED
B) APPLY 0 CURRENT TO INPUT 2
C) APPLY 110% OF PU TO INPUT 1 AT 60HZ. PU = 0.25A X 1.10 = 0.275A. RELAY SHOULD OPERATE.
D) APPLY ZERO CURRENT TO INPUT 1. CHANGE FREQUENCY TO 120 HZ.
E) HOLD DOWN TARGET RESET BUTTON AND SLOWLY INCREASE INPUT 1 CURRENTS TO 110% OF PICKUP ( 0.275A).
F) RELAY SHOULD NOT OPERATE (LED LIGHT OFF).
![Page 28: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/28.jpg)
87T TESTING FOR Y-Y TRANSFORMER CONNECTIONFOURTH HARMONIC RESTRAINT TEST( ENERGIZING INRUSH RESTRAINT)
A) ENSURE THAT 5TH HARMONIC RESTRAINT IS ENABLED
B) APPLY 0 CURRENT TO INPUT 2.
C) APPLY ZERO CURRENT TO INPUT 1. CHANGE FREQUENCY TO 240 HZ.
E) HOLD DOWN TARGET RESET BUTTON AND SLOWLY INCREASE INPUT 1 CURRENTS. TO 110% OF PICKUP (0.275A).
F) RELAY SHOULD NOT OPERATE (LED LIGHT OFF).
![Page 29: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/29.jpg)
87T TESTING FOR Y-Y TRANSFORMER CONNECTIONFIFTH HARMONIC RESTRAINT TEST ( OVEREXCITATION RESTRAINT)
A) ENSURE THAT 5TH HARMONIC RESTRAINT IS ENABLED
B) APPLY 0 CURRENT TO INPUT 2
C) APPLY ZERO CURRENT TO INPUT 1. CHANGE FREQUENCY TO 300 HZ.
D) HOLD DOWN TARGET RESET BUTTON AND SLOWLY INCREASE INPUT 1 CURRENTS.
E) RELAY SHOULD NOT OPERATE (LED LIGHT OFF) AT O.25A PU. CONTINUE TO INCREASE CURRENT. RELAY LED SHOULD BE EXTINGUISH FOR VALUE ABOVE PU (0.25A) TO 0.5A.
F) CONTINUE TO INCREASE CURRENT. THE LED SHOULD LIGHT WHEN THE 5TH
HARMONIC PICKUP SETTING OF 0.5A IS REACHED.
![Page 30: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/30.jpg)
DIGITAL TRANSFORMERDIFFERENTIAL RELAY
SETTING EXAMPLE(Delta- Wye Transformer)
![Page 31: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/31.jpg)
ANSI/IEEE PHASING STANDARD
H1, H2, H3 Primary Bushings
X1, X2, X3 Secondary Bushings
TransformerH1H2H3
X1X2X3
Wye-Wye H1 and X1 at zero degreesDelta-Delta H1 and X1 at zero degreesDelta-Wye H1 lead X1 by 30 degreesWye-Delta H1 lead X1 by 30 degrees
![Page 32: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/32.jpg)
Phasing Delta- Wye
H1 (A) leads X1 (a) by 30
Currents on “H” bushings are delta quantities
Can Describe as Delta AB (Ia =Ia-Ib)
HV LV
H1
H2
H3
X1
X3
X2
A
B
C
a
b
c
a
b
c A
B
C
Assume 1:1 transformer
![Page 33: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/33.jpg)
Phasing Wye- Delta
H1 (a) leads X1 (A) by 30
Currents on “X” bushings are delta quantities
Can Describe as Delta AC (Ia=IA-IC)
HV LV
H1
H2
H3
X1
X3
X2
a
b
c
A
B
C
IA-IC
IB-IA
IC-IB
Assume 1:1 transformer
a
b
c A
B
C
![Page 34: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/34.jpg)
Transformer Phasing – IEC Phasing StandardEuro-designations use 30 increments of LAG from the X1 bushing to the H1 bushings
0
6
39
8
7
10
11 12
5
4
![Page 35: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/35.jpg)
87T SET-UPM-3311A —System Setup
![Page 36: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/36.jpg)
87T SETTINGS
Pickup (pu) – 0.25 pu Slope 1 ------ 30% Slope 2 ------ 60% Breakpoint --- 2.0pu 2nd and 4th Harmonics ------- 15% 5th Harmonic ----------------- 30% Tap W1 ------------------------ 1.0A Tap W2 ------------------------ 1.0A
M-3311A —System Setup
![Page 37: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/37.jpg)
87T SETTINGS
![Page 38: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/38.jpg)
M-3311A CT Connections for DELTA-WYE Transformer – 87T
![Page 39: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/39.jpg)
![Page 40: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/40.jpg)
87T TESTING FOR DELTA -WYE TRANSFORMER CONNECTION
CHECK FOR PROPER CONNECTIONS.
A) APPLY THREE PHASE CURRENTS TO BOTH INPUT 1 = 5.0A and INPUT2 = 5.0A. RELAY SHOULD NOT OPERATE. CHECK PHASE ANGLE METERING SCREEN FOR PROPER PHASING.
MINIMUM PICKUP TESTA) SET INPUT 1 CURRENTS = 0
B) HOLD DOWN TARGET RESET BUTTON. SLOWLY INCREASE CURRENTS IN INPUT 2 CURRENTS. THE RELAY WILL OPERATE WHEN CURRENT REACHES 0.25A. ( 1.0A TAP X 0.25 PU).
SLOPE 1 TEST
A) SET INPUT 1= 1.00 AND INPUT 2 CURRENTS TO 1.0A.
B) CALCULATE THE VALUE OF INPUT 2 USING THE BELOW EQUATION WHERE S1 IS THE % SLOPE SETTING. FROM OUR SETTINGS: SLOPE 1 = 30%
INPUT 1 = 1.00 INPUT 2 = [ 200 + S1 ] = 1.0A [ 200 +30 ] = 1.35A 200 – S1 200 -30
C) HOLD DOWN TARGET RESET BUTTON AND SLOWLY INCREASE INPUT 2 CURRENTS. LED SHOULD COME ON AT 1.35A.
![Page 41: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/41.jpg)
87T TESTING FOR Delta-Wye TRANSFORMER CONNECTIONSLOPE 2 TEST
A) SET BOTH INPUT 1 = 5.00 A and INPUT 2 CURRENTS TO 5.0A.
B) CALCULATE THE VALUE OF INPUT 1 USING THE BELOW EQUATION WHERE S1 AND S2 ARE THE SLOPE SETTING. FROM OUR SETTINGS: SLOPE 1 = 30% SLOPE 2 = 60% BP (BREAK POINT) =2.0
INPUT 2 = [ INPUT 2 (1+S2) + BP ( S1 – S2) ] _ 200 _100____
1 - S2200
= [ 5.0 ( 1 +60 ) + 2.0 ( 30-60) ]_______200________100____
1 - 60200
= 8.43A
C) HOLD DOWN TARGET RESET BUTTON AND SLOWLY INCREASE INPUT 2 CURRENTS. LED SHOULD COME ON AT 8.43A.
![Page 42: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/42.jpg)
Oscillograph Demo
![Page 43: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/43.jpg)
Comtrade Format Oscillographs
![Page 44: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/44.jpg)
Waveform Capture (Phasor)
Area of current reversal
Phasor diagram withvalues displayed
Phasor display shown atat Marker #1 location
![Page 45: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/45.jpg)
Waveform Capture (Power and Impedance)
Marker #2
Marker #1
Impedance Trajectory Over Record
Power Trajectory Over Record
Power Value at Marker #1
Power Value at Marker #2
Impedance Values at Marker #1
Impedance Values at Marker #2
Waveform Capture (MW-MVAR, R-X)
![Page 46: PROTECTION OF TRANSFORMERS M-3311A TEST PLAN · PDF fileTypical Phase Differential Characteristic – Percentage Slope Min. Pickup Slope 1 Slope 2 TRIP RESTRAIN ... DIGITAL TRANSFORMER](https://reader031.vdocument.in/reader031/viewer/2022021421/5a9e16ff7f8b9a29228d7326/html5/thumbnails/46.jpg)
THE END
????QUESTION ????
3311A TRANSFORMER PROTECTIVE RELAYTEST PLAN