psb
DESCRIPTION
testing of PSB for sel312 relayTRANSCRIPT
-
Page 1 of 166
POWER SWING BLOCKING (PSB OR OOS) FEATURE:
Settings of Power Swing Blocking (OOS):
EOOS = Y
OOSB1 = N
OOSB2 = Y
OOSB3 = Y
OOSB4 = Y
OSBD = 1.50
EOOST = N
OSTD = 1.00
X1T5 = 42.00
X1B5 = -38.00
R1R5 = 23.00
R1L5 = -16.00
X1T6 = 63.00
X1B6 = -58.00
R1R6 = 35.00
R1L6 = -58.00
50ABC = 0.20
UBD = 0.50
OUT7 = OSB
For simulating OOS condition in SEL 321, following conditions should be fulfilled
i) Breaker should be close condition (3 pole open condition should not be there),
ii) Loss of potential condition should not be there, iii) Fault current selected should be greater than the 50ABC setting adopted in
the OOS settings,
iv) Impedance loci chosen for the simulation should lie in between the zone 5 & 6 or OOS zone more than the OSBD time chosen in the relay.
-
Page 2 of 166
OOS
Step 1 Click OMICRON Test Universe
1.51 Icon in desktop OMICRON start page window opens.
-
Page 3 of 166
Step 2 Click Distance in OMICRON start page.
OMICRON Distance {Test View: Distance1 window opens.
Step 3 OMICRON Distance window select Parameters > Test Object
Parameters For Protection Device menu window opens.
-
Page 4 of 166
Step 4 In Parameters For Protection Device menu window enter the parameters in Device Settings, System Settings.
This will configure the settings
essential for testing.
-
Page 5 of 166
-
Page 6 of 166
Procedure For Creating MHO Characteristics Zones:
Step 5 In Parameters For Protection Device > Zone Setting menu
Click New button New Zone will be added
Click Edit button Characteristic Editor window opens.
-
Page 7 of 166
In Characteristic Editor > Predefined Shapes menu click Circle button
It will add mho characteristics
Enter impedance reach value, offset
and line angle values in the Element list window then press OK button
The same procedure can be
followed for including any
number of Mho characteristics
for testing.
-
Page 8 of 166
-
Page 9 of 166
Procedure For Creating Power swing Characteristics:
Step 6 In Parameters For Protection Device > Zone Setting menu
Click New button New Zone will be added
Click Edit button Characteristic Editor window opens.
In Characteristic Editor > Predefined Shapes menu click rectangular button
It will add quadrilateral
characteristics
Enter impedance reach value, offset
and line angle values in the Element list window then press OK button
The same procedure can be
followed for including any
number of Mho characteristics
for testing.
In element list 1:
i) Choose Line cartesian ii) Enter R=0; X=-38; Angle =0
This will create the Power swing
blocking inner zone. For creating
PSB outer zone the same
procedure with following setting
Element 1
R=0; X=-58; Angle=0
Element 2
R=35; X=0; Angle=85
Element 3
R=0; X=63; Angle=0
Element 4
R=-58; X=0; Angle=85
In element list 2:
i) Choose Line cartesian ii) Enter R=28; X=0; Angle =85
In element list 3:
i) Choose Line cartesian ii) Enter R=0; X=42; Angle =0
In element list 4:
i) Choose Line cartesian ii) Enter R=-35; X=0;
Angle=85
-
Page 10 of 166
Step 7 In Parameters For Protection Device menu window enter the parameters in Test Settings,
This will configure the settings
essential for testing.
Step 8 In OMICRON Distance {Test View: Distance1 window select Parameters > Hardware Configuration
Hardware Configuration menu window opens.
-
Page 11 of 166
Step 9 In Hardware Configuration menu Click General > Test Set(s) > Details.
Output Configuration Details menu window opens.
Step 10 Select 3 Voltage and 3 current
sources & Click OK. Output Configuration Details menu window closes.
-
Page 12 of 166
Step 11 In Hardware Configuration menu Click Analog Outputs select the voltage and current sources.
-
-
Page 13 of 166
Step 12 In Hardware Configuration menu Click Binary / Analog Inputs and in Binary Outputs select none of the inputs / outputs.
-
-
Page 14 of 166
Step 13 In OMICRON Distance {Test View: Distance1 window select View > Test.
Test View Menu opens.
Step 14 In OMICRON Distance {Test View: Distance1 window Fault type menu select R-Y-B fault.
-
-
Page 15 of 166
Step 15 In OMICRON Distance {Test View: Distance1 window Shot menu enter the Test point impedances
at line angle to be tested and click
Add button for testing these test point.
Enter the test point in between
Zone 5 & 6 of PSB and the fault
time should be more than the
OSBD time delay, which is set
in the SEL 321 PSB settings.
This will ensure the PSB
operation.
Step 16 In OMICRON Distance {Test View: Distance1 window Settings menu enter the parameters for testing.
Maximum fault duration in
Setting should be greater than OSBD delay. And fault current
selected should be greater than
the 50ABC pickup level.
-
Page 16 of 166
Step 17 In OMICRON Distance {Test View: Distance1 window click and select Test >Single Test.
The impedance test point will be
applied to the relay.