testing of PSB for sel312 relay

TRANSCRIPT

  • Page 1 of 166

    POWER SWING BLOCKING (PSB OR OOS) FEATURE:

    Settings of Power Swing Blocking (OOS):

    EOOS = Y

    OOSB1 = N

    OOSB2 = Y

    OOSB3 = Y

    OOSB4 = Y

    OSBD = 1.50

    EOOST = N

    OSTD = 1.00

    X1T5 = 42.00

    X1B5 = -38.00

    R1R5 = 23.00

    R1L5 = -16.00

    X1T6 = 63.00

    X1B6 = -58.00

    R1R6 = 35.00

    R1L6 = -58.00

    50ABC = 0.20

    UBD = 0.50

    OUT7 = OSB

    For simulating OOS condition in SEL 321, following conditions should be fulfilled

    i) Breaker should be close condition (3 pole open condition should not be there),

    ii) Loss of potential condition should not be there, iii) Fault current selected should be greater than the 50ABC setting adopted in

    the OOS settings,

    iv) Impedance loci chosen for the simulation should lie in between the zone 5 & 6 or OOS zone more than the OSBD time chosen in the relay.

  • Page 2 of 166

    OOS

    Step 1 Click OMICRON Test Universe

    1.51 Icon in desktop OMICRON start page window opens.

  • Page 3 of 166

    Step 2 Click Distance in OMICRON start page.

    OMICRON Distance {Test View: Distance1 window opens.

    Step 3 OMICRON Distance window select Parameters > Test Object

    Parameters For Protection Device menu window opens.

  • Page 4 of 166

    Step 4 In Parameters For Protection Device menu window enter the parameters in Device Settings, System Settings.

    This will configure the settings

    essential for testing.

  • Page 5 of 166

  • Page 6 of 166

    Procedure For Creating MHO Characteristics Zones:

    Step 5 In Parameters For Protection Device > Zone Setting menu

    Click New button New Zone will be added

    Click Edit button Characteristic Editor window opens.

  • Page 7 of 166

    In Characteristic Editor > Predefined Shapes menu click Circle button

    It will add mho characteristics

    Enter impedance reach value, offset

    and line angle values in the Element list window then press OK button

    The same procedure can be

    followed for including any

    number of Mho characteristics

    for testing.

  • Page 8 of 166

  • Page 9 of 166

    Procedure For Creating Power swing Characteristics:

    Step 6 In Parameters For Protection Device > Zone Setting menu

    Click New button New Zone will be added

    Click Edit button Characteristic Editor window opens.

    In Characteristic Editor > Predefined Shapes menu click rectangular button

    It will add quadrilateral

    characteristics

    Enter impedance reach value, offset

    and line angle values in the Element list window then press OK button

    The same procedure can be

    followed for including any

    number of Mho characteristics

    for testing.

    In element list 1:

    i) Choose Line cartesian ii) Enter R=0; X=-38; Angle =0

    This will create the Power swing

    blocking inner zone. For creating

    PSB outer zone the same

    procedure with following setting

    Element 1

    R=0; X=-58; Angle=0

    Element 2

    R=35; X=0; Angle=85

    Element 3

    R=0; X=63; Angle=0

    Element 4

    R=-58; X=0; Angle=85

    In element list 2:

    i) Choose Line cartesian ii) Enter R=28; X=0; Angle =85

    In element list 3:

    i) Choose Line cartesian ii) Enter R=0; X=42; Angle =0

    In element list 4:

    i) Choose Line cartesian ii) Enter R=-35; X=0;

    Angle=85

  • Page 10 of 166

    Step 7 In Parameters For Protection Device menu window enter the parameters in Test Settings,

    This will configure the settings

    essential for testing.

    Step 8 In OMICRON Distance {Test View: Distance1 window select Parameters > Hardware Configuration

    Hardware Configuration menu window opens.

  • Page 11 of 166

    Step 9 In Hardware Configuration menu Click General > Test Set(s) > Details.

    Output Configuration Details menu window opens.

    Step 10 Select 3 Voltage and 3 current

    sources & Click OK. Output Configuration Details menu window closes.

  • Page 12 of 166

    Step 11 In Hardware Configuration menu Click Analog Outputs select the voltage and current sources.

    -

  • Page 13 of 166

    Step 12 In Hardware Configuration menu Click Binary / Analog Inputs and in Binary Outputs select none of the inputs / outputs.

    -

  • Page 14 of 166

    Step 13 In OMICRON Distance {Test View: Distance1 window select View > Test.

    Test View Menu opens.

    Step 14 In OMICRON Distance {Test View: Distance1 window Fault type menu select R-Y-B fault.

    -

  • Page 15 of 166

    Step 15 In OMICRON Distance {Test View: Distance1 window Shot menu enter the Test point impedances

    at line angle to be tested and click

    Add button for testing these test point.

    Enter the test point in between

    Zone 5 & 6 of PSB and the fault

    time should be more than the

    OSBD time delay, which is set

    in the SEL 321 PSB settings.

    This will ensure the PSB

    operation.

    Step 16 In OMICRON Distance {Test View: Distance1 window Settings menu enter the parameters for testing.

    Maximum fault duration in

    Setting should be greater than OSBD delay. And fault current

    selected should be greater than

    the 50ABC pickup level.

  • Page 16 of 166

    Step 17 In OMICRON Distance {Test View: Distance1 window click and select Test >Single Test.

    The impedance test point will be

    applied to the relay.